Water-cooled centrifugal chiller controller · BACnet points list
Carrier AquaEdge 19XR (PIC6.1) BACnet points list
Updated 6 November 2026
The 19XR PIC6.1 controller speaks BACnet MS/TP on RS-485 port J8 or BACnet IP on Ethernet port J15, plus Modbus RTU/TCP. Object names join the CCN table and point name (TEMP_LCW, GENUNIT_CHIL_S_S_wr). Commands use paired read (_rd) and write (_wr) objects; the list also carries temperatures, pressures, bearing and motor data, VFD values and one binary value per alarm or alert code (BV 10000 and up).
This page lists 463 BACnet objects for the Carrier AquaEdge 19XR (PIC6.1) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaEdge 19XR (PIC6.1)
- Equipment
- Water-cooled centrifugal chiller controller
- Equipment type
- Chillers
- BACnet objects
- 463 (15 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 1600001
- Also known as
- 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier AquaEdge 19XR (PIC6.1)
Select BACnet MS/TP on port J8 or enable BACnet/IP in the BMS Protocol menu (Service password), set the identifier and network, and put the chiller in Network control mode. The chiller then starts when both BV 66 start/stop and BV 68 occupied are true; write control point and demand limit through the _wr objects and read status, water temperatures and alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 66 | GENUNIT_CHIL_S_S_wr | Network start/stop command | Write |
| BV 68 | GENUNIT_CHIL_OCC_wr | Network occupied command | Write |
| BV 67 | GENUNIT_EMSTOP_wr | Emergency stop command | Write |
| AV 147 | GENUNIT_CTRL_PNT_wr | Control point command | Write |
| AV 148 | GENUNIT_DEM_LIM_wr | Demand limit command | Write |
| MV 1 | GENUNIT_ctl_mode | Control mode: Local, Network, Remote, Local Sched | Read |
| AV 7 | GENUNIT_ch_state | Chiller status code | Read |
| AV 9 | TEMP_LCW | Leaving chilled water temperature | Read |
| AV 8 | TEMP_ECW | Entering chilled water temperature | Read |
| AV 85 | ALARMRST_alarm_1 | Current alarm 1 | Read |
Enable & remote start
In Network control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP for a shutdown. If the Stop Override point in GENUNIT is enabled the chiller cannot start.
Network setup
- BMS Protocol menu: port J8 carries BACnet MS/TP or Modbus RTU; BACnet/IP and Modbus TCP use Ethernet port J15 (default 169.254.0.1, mask 255.255.0.0).
- Defaults: BACnet identifier 1600001, BACnet network 1600, UDP port 47808, MS/TP MAC 1, MS/TP baud option 2 (38400), Max Master 3, Max Info Frames 5.
- BACnet MS/TP and BACnet IP cannot both be enabled.
- Changing a BACnet parameter reboots the board after 1 minute; an IP address change needs a manual reboot or power cycle.
Watch out for
- Write the _wr objects; the _rd objects only echo the current value.
- BV 304 GENUNIT_REM_RST resets alarms remotely.
- Alarm and alert flags exist only for the options fitted (VFD, AHF, hydraulic, free cooling and so on).
Carrier AquaEdge 19XR (PIC6.1) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 1 | GENUNIT_ctl_mode | Control Mode | Read | ||
| BV | 1 | GENUNIT_statstop | Deter Start Stop Command | Read | ||
| BV | 2 | GENUNIT_CHIL_S_S_rd | Network:Cmd Start/Stop | Read | ||
| BV | 3 | GENUNIT_CHIL_OCC_rd | Network:Cmd Occupied | Read | ||
| BV | 4 | GENUNIT_HC_SEL_rd | Cooling/Heating Select | Read | ||
| AV | 1 | GENUNIT_CTRL_PNT_rd | Control Point | Read | ||
| AV | 2 | GENUNIT_reset | Control Point Reset | Read | ||
| AV | 3 | GENUNIT_setpoint | Actual Setpoint | Read | ||
| AV | 4 | GENUNIT_AMPS_P | Percent Current | Read | ||
| AV | 5 | GENUNIT_KW_P | Motor Percent Kilowatts | Read | ||
| AV | 6 | GENUNIT_DEM_LIM_rd | Actual Demand Limit | Read | ||
| BV | 5 | GENUNIT_EMSTOP_rd | BMS Emergency Stop | Read | ||
| AVmin | 7 | GENUNIT_ch_state | Chiller Status Code | Read | ||
| BV | 6 | GENUNIT_loc_occ | Local Schedule Occupied | Read | ||
| BV | 7 | GENUNIT_ice_occ | Ice Schedule Occupied | Read | ||
| BV | 8 | GENUNIT_FC_START_rd | Start Free Cooling | Read | ||
| BV | 9 | GENUNIT_BAC_OCC | BACnet Occupied | Read | ||
| AVmin | 8 | TEMP_ECW | Entering Chilled Water | Read | ||
| AVmin | 9 | TEMP_LCW | Leaving Chilled Water | Read | ||
| AV | 10 | TEMP_ECDW | Entering Condenser Water | Read | ||
| AV | 11 | TEMP_LCDW | Leaving Condenser Water | Read | ||
| AV | 12 | TEMP_HR_EWT | Heat Recl Entering Temp | Read | ||
| AV | 13 | TEMP_HR_LWT | Heat Recl Leaving Temp | Read | ||
| AV | 14 | TEMP_EVAP_SAT | Evap Sat Refrig Temp | Read | ||
| AV | 15 | TEMP_EVAP_T | Evap Refrig Liquid Temp | Read | ||
| AV | 16 | TEMP_evap_app | Evaporator Approach | Read | ||
| AV | 17 | TEMP_cond_app | Condenser Approach | Read | ||
| AV | 18 | TEMP_COND_SAT | Cond Sat Refrig Temp | Read | ||
| AV | 19 | TEMP_DGT | Comp Discharge Temp | Read | ||
| AV | 20 | TEMP_DSH | Discharge Superheat | Read | ||
| AV | 21 | TEMP_MTRB_OIL | Thrust Bearing Oil Temp | Read | ||
| AV | 22 | TEMP_MTRB | Thrust Bearing Temp | Read | ||
| AV | 23 | TEMP_MTRB1 | Low Speed ME Brg Temp | Read | ||
| AV | 24 | TEMP_MTRB2 | Low Speed CE Brg Temp | Read | ||
| AV | 25 | TEMP_MTRB3 | High Speed ME Brg Temp | Read | ||
| AV | 26 | TEMP_MTRB4 | High Speed CE Brg Temp | Read | ||
| AV | 27 | TEMP_MTRW1 | Motor Winding 1 Temp | Read | ||
| AV | 28 | TEMP_MTRW2 | Motor Winding 2 Temp | Read | ||
| AV | 29 | TEMP_MTRW3 | Motor Winding 3 Temp | Read | ||
| AV | 30 | TEMP_OILT_SMP | Oil Sump Temp | Read | ||
| AV | 31 | TEMP_OILT_DIS | Oil Supply Temp | Read | ||
| AV | 32 | TEMP_PGC_SUCT | Purge Comp Suction Temp | Read | ||
| AV | 33 | TEMP_CBH1_T | 1st Stage Bearing Temp | Read | ||
| AV | 34 | TEMP_CBH2_T | 2nd Stage Bearing Temp | Read | ||
| AV | 36 | PRESSURE_EVAP_P | Evaporator Pressure | Read | ||
| AV | 37 | PRESSURE_COND_P | Condenser Pressure | Read | ||
| AV | 38 | PRESSURE_ECON_P | Economizer Pressure | Read | ||
| AV | 39 | PRESSURE_OIL_PD | Oil Pump Delta P | Read | ||
| AV | 40 | PRESSURE_DIFF_P | Diffuser Pressure | Read | ||
| AV | 41 | PRESSURE_HEAD_P | Head Pressure Reference | Read | ||
| AV | 42 | PRESSURE_REF_PD | Bearing Delta P | Read | ||
| AV | 43 | PRESSURE_PUMP_PD | Ref Pump Delta P | Read | ||
| BV | 10 | INPUTS_STAR_AUX | Compressor Start Contact | Read | ||
| MV | 2 | INPUTS_DMP_ACT | ECO DMP VLV Status | Read | ||
| MV | 3 | INPUTS_HGBP_ACT | EC/HG VLV Status | Read | ||
| BV | 11 | INPUTS_HP_SW | High Pressure Switch | Read | ||
| BV | 12 | INPUTS_REM_CON | Remote Start/Stop | Read | ||
| BV | 13 | INPUTS_E_STOP | Emergency Stop Contact | Read | ||
| BV | 14 | INPUTS_ICE_CON | Ice Build Contact | Read | ||
| BV | 15 | INPUTS_REM_LOCK | Chiller Lockout | Read | ||
| BV | 16 | INPUTS_SAFETY | Spare Safety Input | Read | ||
| BV | 17 | INPUTS_STARTFLT | Starter Fault Feedback | Read | ||
| BV | 18 | INPUTS_FS_LOCK | Fire Security Interlock | Read | ||
| AV | 44 | INPUTS_GV1_ACT | Guide Vane 1 Actual Pos | Read | ||
| AV | 45 | INPUTS_GV2_ACT | Guide Vane 2 Actual Pos | Read | ||
| AV | 46 | INPUTS_VFD_ACT | Actual VFD Speed Per | Read | ||
| AV | 47 | INPUTS_DIFF_ACT | Diffuser Actual Pos | Read | ||
| AV | 48 | INPUTS_HGBPACTP | EC/HG VLV Actual Pos Per | Read | ||
| BV | 19 | INPUTS_TRIPR | Shunt Trip Relay Status | Read | ||
| BV | 21 | INPUTS_PGLE_LO | Purge Level Switch Low | Read | ||
| BV | 22 | INPUTS_PGLE_HI | Purge Level Switch High | Read | ||
| BV | 23 | INPUTS_HF_LS | Liquid Level Switch | Read | ||
| AV | 49 | OUTPUTS_DIFF_OUT | Diffuser Output mA | Read | ||
| AV | 50 | OUTPUTS_HDPV_OUT | Head Pres Output mA | Read | ||
| AV | 51 | OUTPUTS_CHST_OUT | Chiller Status (Analog) | Read | ||
| AV | 52 | OUTPUTS_VFD_OUT | VFD Speed Output mA | Read | ||
| AV | 53 | OUTPUTS_EXV_OUT | Oil Cooler EXV mA | Read | ||
| AV | 54 | OUTPUTS_llc_exvt | Liquid Level EXV Target | Read | ||
| AV | 55 | OUTPUTS_op_vfd_t | Oil Pump VFD Target | Read | ||
| AV | 56 | OUTPUTS_GV1_OUT | Guide Vane1 Output | Read | ||
| AV | 57 | OUTPUTS_GV2_OUT | Guide Vane2 Output | Read | ||
| BV | 24 | OUTPUTS_ALM | Alarm Relay | Read | ||
| BV | 25 | OUTPUTS_ALE | Alert Relay | Read | ||
| BV | 26 | OUTPUTS_COMP_SR | Compressor Start Relay | Read | ||
| BV | 27 | OUTPUTS_GV1_DEC | Guide Vane 1 Decrease | Read | ||
| BV | 28 | OUTPUTS_GV1_INC | Guide Vane 1 Increase | Read | ||
| BV | 29 | OUTPUTS_OIL_HEAT | Oil Heater Relay | Read | ||
| BV | 30 | OUTPUTS_OIL_PUMP | Oil Pump Relay | Read | ||
| BV | 31 | OUTPUTS_TFR_HIGH | Tower Fan Relay High | Read | ||
| BV | 32 | OUTPUTS_TFR_LOW | Tower Fan Relay Low | Read | ||
| BV | 33 | OUTPUTS_ECON_IV | ECO Isolation VLV | Read | ||
| BV | 34 | OUTPUTS_COND_CV | Cond Valve (Ref Lube) | Read | ||
| BV | 35 | OUTPUTS_EVAP_CV | Evap Valve (Ref Lube) | Read | ||
| BV | 36 | OUTPUTS_EVAP_DCV | Evaporator Drain Valve | Read | ||
| BV | 37 | OUTPUTS_COND_DCV | Condenser Drain Valve | Read | ||
| BV | 38 | OUTPUTS_COND_PSV | Purge Cond Valve | Read | ||
| BV | 39 | OUTPUTS_COMP_PSV | Purge Comp Valve | Read | ||
| BV | 40 | OUTPUTS_DRASVON | Purge Drainage Valve | Read | ||
| BV | 41 | OUTPUTS_REG_PSV | Purge Regeneration Valve | Read | ||
| BV | 42 | OUTPUTS_DIS_PSV | Purge Discharge Valve | Read | ||
| BV | 43 | OUTPUTS_PGAPUMP | Purge Vacuum Pump | Read | ||
| BV | 44 | OUTPUTS_PG_COMP | Purge Compressor | Read | ||
| BV | 45 | OUTPUTS_PG_HEAT | Purge Heater | Read | ||
| BV | 46 | OUTPUTS_VS_SV | Vapor Source SV | Read | ||
| BV | 47 | OUTPUTS_FC_VALVE | Free Cooling Valve | Read | ||
| BV | 48 | OUTPUTS_COND_FCV | Cond Charging (Ref Lube) | Read | ||
| BV | 49 | HYDRLIC_CDWP | Condenser Water Pump | Read | ||
| BV | 50 | HYDRLIC_CDW_FLOW | Condenser Water Flow | Read | ||
| AV | 58 | HYDRLIC_CDW_FV | Cond Water Flow Value | Read | ||
| AV | 59 | HYDRLIC_cdw_pd | Condenser Water Delta P | Read | ||
| BV | 51 | HYDRLIC_CHWP | Chilled Water Pump | Read | ||
| BV | 52 | HYDRLIC_CHW_FLOW | Chilled Water Flow | Read | ||
| AV | 60 | HYDRLIC_CHW_FV | Chilled Water Flow Value | Read | ||
| AV | 61 | HYDRLIC_chw_pd | Chilled Water Delta P | Read | ||
| AV | 62 | HYDRLIC_ctrlw_dt | Controlled Water DT | Read | ||
| AV | 63 | RUNTIME_C_STARTS | Compressor Starts Num | Read | ||
| AV | 64 | RUNTIME_COMP_HRS | Comp Total Running Hrs | Read | ||
| AV | 65 | RUNTIME_SRV_HRS | After Service Hrs | Read | ||
| AV | 66 | POWER_I_AMPS_A_I | Actual Line Current | Read | ||
| AV | 67 | POWER_I_AMPS_P_I | Percent Line Current | Read | ||
| AV | 68 | POWER_I_VOLT_A | Actual Line Voltage | Read | ||
| AV | 69 | POWER_I_VOLT_P | Percent Line Voltage | Read | ||
| AV | 70 | POWER_I_KW | Line KW | Read | ||
| AV | 71 | POWER_I_POW_FACT | Line Power Factor | Read | ||
| AV | 72 | POWER_I_ln_imb_v | Line Voltage Imbalance% | Read | ||
| AV | 73 | POWER_O_VFD_LOAD | VFD Load Current | Read | ||
| AV | 74 | POWER_O_amps_p_o | Percent VFD Load Current | Read | ||
| AV | 75 | POWER_O_MOT_FREQ | Motor Actual Frequency | Read | ||
| AV | 76 | POWER_O_bus_volt | DC Bus Voltage | Read | ||
| AV | 77 | POWER_O_vfd_act | Actual VFD Speed Per | Read | ||
| AV | 78 | POWER_O_motor_pf | Motor Power Factor | Read | ||
| AV | 79 | POWER_O_motor_kw | Motor Kilowatts | Read | ||
| AV | 80 | POWER_O_motorkwh | Motor Kilowatt-Hours | Read | ||
| AV | 81 | POWER_O_enc_temp | VFD Enclosure Temp | Read | ||
| AV | 82 | POWER_O_inv_temp | Inverter Temperature | Read | ||
| AV | 83 | POWER_O_rec_temp | Rectifier Temperature | Read | ||
| BV | 53 | POWER_O_prech_fd | Precharge Feedback | Read | ||
| BV | 54 | POWER_O_lrtem_sw | LR Temp Switch | Read | ||
| AV | 84 | POWER_O_alm_code | VFD Alarm Code | Read | ||
| BV | 55 | POWER_O_spd_fd | SPD Feedback | Read | ||
| BV | 56 | POWER_O_VFDC_HI | High VFD Current | Read | ||
| AVmin | 85 | ALARMRST_alarm_1 | Jbus Current Alarm 1 | Read | ||
| AV | 86 | ALARMRST_alarm_2 | Jbus Current Alarm 2 | Read | ||
| AV | 87 | ALARMRST_alarm_3 | Jbus Current Alarm 3 | Read | ||
| AV | 88 | ALARMRST_alarm_4 | Jbus Current Alarm 4 | Read | ||
| AV | 89 | ALARMRST_alarm_5 | Jbus Current Alarm 5 | Read | ||
| AV | 90 | CAPACTRL_ctrl_wt | Controlled Water Temp | Read | ||
| AV | 91 | CAPACTRL_gv1_tgt | Target GV1 Pos | Read | ||
| AV | 92 | CAPACTRL_gv2_tgt | Target GV2 Pos | Read | ||
| AV | 93 | CAPACTRL_vfd_tgt | Target VFD Speed Per | Read | ||
| AV | 94 | CAPACTRL_hgbp_tp | EC/HG VLV Target Per | Read | ||
| AV | 95 | CAPACTRL_cm_stat1 | Comp1 Run State Val | Read | ||
| AV | 96 | MAISURGE_act_reg | Surge Region | Read | ||
| AV | 97 | MAISURGE_dts_act | Actual Delta Tsat | Read | ||
| AV | 98 | MAISURGE_dts_cal | Calc Ref Delta Tsat | Read | ||
| AV | 99 | MAISURGE_sc | Surge Counts | Read | ||
| AV | 100 | MAISURGE_spc | Surge Protection Counts | Read | ||
| AV | 101 | MAISURGE_surg_act | Surge Prevention Active | Read | ||
| AV | 102 | MAISURGE_surg_pro | Surge Protection Active | Read | ||
| AV | 103 | MAISURGE_dts_maxc | Cal Surge Delta Tsmax | Read | ||
| AV | 104 | MAISURGE_dts_minc | Cal Surge Delta Tsmin | Read | ||
| AV | 105 | MAISURGE_dts_medc | Cal Surge Delta Tsmed | Read | ||
| AV | 106 | MAISURGE_gv1_sful | IGV1 Full Load Position | Read | ||
| AV | 107 | MAISURGE_gv1_smin | IGV1 Minimum Position | Read | ||
| AV | 108 | MAISURGE_gv1_smed | Opti-Sound IGV1 Position | Read | ||
| AV | 109 | MAISURGE_enlp_opt | Envelope Line/HG Opt. | Read | ||
| AV | 110 | QCK_TEST_Q_GV1ACT | Guide Vane 1 Actual Pos | Read | ||
| AV | 111 | QCK_TEST_Q_DIFTGT | Diffuser Target Pos | Read | ||
| AV | 112 | MAIN_SRD_diff_tgt | Diffuser Target Pos | Read | ||
| BV | 57 | MAIN_SRD_diffault | Diffuser Fault | Read | ||
| BV | 58 | MAIN_SRD_diff_alm | SRD Rotating Stall Alarm | Read | ||
| AV | 113 | MAIN_SRD_lift_a | Actual Lift | Read | ||
| AV | 114 | MAIN_SRD_lift_1 | VDO High Lift Load Line | Read | ||
| AV | 115 | MAIN_SRD_lift_2 | VDO Low Lift Load Line | Read | ||
| AV | 116 | MAIN_MS_lead_lag | Unit is Lead or Lag | Read | ||
| AV | 117 | MAIN_MS_ms_ctrl | Primary Control Type | Read | ||
| AV | 118 | MAIN_MS_sl_ctrl | Secondary Control Type | Read | ||
| BV | 59 | MAIN_MS_ll_comm | Lead Lag Communication | Read | ||
| AV | 119 | MAIN_MS_ll_fault | Primary Secondary Fault | Read | ||
| AV | 120 | MAIN_MS_lagstat | Secondary Run Status | Read | ||
| BV | 60 | MAIN_MS_lag_s_s | Secondary Start/Stop | Read | ||
| AV | 121 | MAIN_MS_lagstart | Lag Start Timer | Read | ||
| AV | 122 | MAIN_MS_lagstop | Lag Stop Timer | Read | ||
| AV | 123 | MAIN_MS_preflt | Prestart Fault Timer | Read | ||
| AV | 124 | MAIN_MS_pulltime | Pulldown Timer | Read | ||
| AV | 125 | MAIN_MS_ll_hr_d | Lead/Lag Hours Delta | Read | ||
| MV | 4 | FACTORY_chil_typ | Chiller Type | Read | ||
| MV | 5 | FACTORY_vfd_opt | VFD/Starter Option | Read | ||
| AV | 126 | CFGSURGE_gv1_pmin | IGV1 Minimum Position | Read | ||
| AV | 127 | CFGSURGE_gv1_pful | IGV1 Full Load Position | Read | ||
| AV | 128 | CFGSURGE_sgl_off | Surge Line Offset | Read | ||
| AV | 129 | CFGSURGE_sgl_loff | Surge Line Lower DB | Read | ||
| AV | 130 | CFGSURGE_sgl_hoff | Surge Line Upper DB | Read | ||
| AV | 131 | CFGSURGE_sgl_shfh | Surge Line Shape Factor | Read | ||
| AV | 132 | CFGSURGE_sgl_shfl | Sound Line Shape Factor | Read | ||
| AV | 133 | CFGSURGE_sgl_spdf | Surge Line Speed Factor | Read | ||
| AV | 134 | CFGSURGE_sgl_pro | Surge Profile Offset | Read | ||
| MV | 6 | CONF_OPT_hgbp_opt | EC/HG Valve Option | Read | ||
| MV | 7 | CONF_OPT_hgbp_sel | EC/HG Valve Selection | Read | ||
| BV | 61 | LABONLY_gv1_fc | GV1 Forced | Read | ||
| BV | 62 | LABONLY_gv2_fc | GV2 Forced | Read | ||
| AV | 135 | CONF_PRG_oil_qly | Oil Quality | Read | ||
| AV | 136 | CONF_PRG_oil_flt | Oil Filter Failure | Read | ||
| AV | 137 | CONF_PRG_tran_dev | Transducer Deviation | Read | ||
| AV | 138 | CONF_PRG_ref_chg | Refrig Charge Status | Read | ||
| BV | 63 | CONNECT_bacena | BACnet/IP Enable | Read | ||
| BV | 64 | CONNECT_bacunit | BACnet Metric Unit | Read | ||
| AV | 139 | CONNECT_network | BACnet Network | Read | ||
| AV | 140 | CONNECT_bac_id | BACnet Identifier | Read | ||
| AV | 141 | SETPOINT_ecw_sp | Cooling ECW Setpoint | Write | ||
| AV | 142 | SETPOINT_lcw_sp | Cooling LCW Setpoint | Write | ||
| AV | 143 | SETPOINT_ecdw_sp | Heating ECDW Setpoint | Write | ||
| AV | 144 | SETPOINT_lcdw_sp | Heating LCDW Setpoint | Write | ||
| AV | 145 | SETPOINT_ice_sp | Ice Build Setpoint | Write | ||
| AV | 146 | SETPOINT_dem_base | Base Demand Limit | Write | ||
| BV | 65 | SETPOINT_EWT_OPT | EWT Control Option | Write | ||
| BVmin | 66 | GENUNIT_CHIL_S_S_wr | Chiller Start/Stop | Write | ||
| AVmin | 147 | GENUNIT_CTRL_PNT_wr | Control Point | Write | ||
| AVmin | 148 | GENUNIT_DEM_LIM_wr | Demand Limit | Write | ||
| BVmin | 67 | GENUNIT_EMSTOP_wr | BMS Emergency Stop | Write | ||
| AV | 149 | GENUNIT_HC_SEL_wr | Heatcool Select | Write | ||
| BVmin | 68 | GENUNIT_CHIL_OCC_wr | Chiller occupied? | Write | ||
| BV | 69 | GENUNIT_FC_START_wr | Start Free Cooling | Write | ||
| MV | 8 | BACnet_COLOR | Operation Status Color | Read | ||
| AV | 150 | BACnet_PRIME_V | Value of Prime variable | Read | ||
| AV | 151 | RUNTIME_ST_CNT12 | Starts Num in 12 Hours | Read | ||
| AV | 152 | POWER_I_ln_imb_i | Line Current Imbalance% | Read | ||
| MV | 9 | MODES_cm_stat1 | Comp1 Run State Val | Read | ||
| AV | 153 | RUNTIME_PGP_NO | Total Pumpout Numbers | Read | ||
| AV | 154 | RUNTIME_PGP_TM | Total Pumpout Time | Read | ||
| AV | 155 | RUNTIME_pgp_tm_w | Avg Daily Purge in 7 Day | Read | ||
| AV | 156 | POWER_I_KWH | Line KWH | Read | ||
| BV | 70 | OUTPUTS_RUN_STAT | Chiller Status(Discrete) | Read | ||
| AV | 200 | HYDRLIC_EVAP_EWP | Entering Chilled Water P | Read | ||
| AV | 201 | HYDRLIC_EVAP_LWP | Leaving Chilled Water P | Read | ||
| AV | 202 | RUNTIME_spst_tim | Stop to Start Timer | Read | ||
| AV | 203 | RUNTIME_stst_tim | Start to Start Timer | Read | ||
| BV | 300 | INPUTS_POW_FDB | Marine Pwr Req Feedback | Read | ||
| BV | 301 | OUTPUTS_POW_REQ | Marine Pwr Req Output | Read | ||
| AV | 204 | GENUNIT_cal_capa | Calculated Capacity | Read | ||
| BV | 302 | HYDRLIC_EVAP_FS | Evap Water Flow Switch | Read | ||
| BV | 303 | HYDRLIC_COND_FS | Cond Water Flow Switch | Read | ||
| BV | 304 | GENUNIT_REM_RST | Remote Reset Alarm | Write | ||
| BV | 10100 | A_PRE_STARTS_LIMIT_EXCEE | ALT-100 Prestart Alert - Starts Limit Exceeded | Read | ||
| BV | 10101 | A_PRE_LOW_OIL_T_F | ALT-101 Prestart Alert - Low Oil Temperature | Read | ||
| BV | 10102 | A_PRE_HIGH_COND_PRESS_F | ALT-102 Prestart Alert - High Condenser Pressure | Read | ||
| BV | 10103 | A_PRE_EXCESSIVE_RECYCLE_ | ALT-103 Prestart Alert - Excessive Recycle Starts | Read | ||
| BV | 10104 | A_PRE_WAIT_FOR_PERMISSIO | ALT-104 Prestart Alert - Waiting For Start Permission | Read | ||
| BV | 10120 | A_REMOTE_TEMP_OUT_OF_RAN | ALT-120 Sensor Alert - Remote Temperature Out of Range | Read | ||
| BV | 10121 | A_SEN_AUTO_WATER_TEMP_RE | ALT-121 Sensor Alert - Auto Water Temp Reset | Read | ||
| BV | 10122 | A_SEN_AUTO_DEMAND_LIMIT_ | ALT-122 Sensor Alert - Auto Demand Limit Input | Read | ||
| BV | 10123 | A_SEN_VFD_SPEED_OUT_OF_R | ALT-123 Sensor Alert - VFD Speed Out of Range | Read | ||
| BV | 10124 | A_SEN_HUMIDITY_SENSOR_F | ALT-124 Sensor Alert - Humidity Sensor | Read | ||
| BV | 10125 | A_SEN_REFRIG_LEAK_INPUT_ | ALT-125 Sensor Alert - Refrigerant Leak Input | Read | ||
| BV | 10126 | A_SEN_DIFF_POS_FEEDBACK_ | ALT-126 Sensor Alert - Diffuser Pos Feedback | Read | ||
| BV | 10127 | A_SEN_VFD_CURRENT_INPUT_ | ALT-127 Sensor Alert - VFD Current Input | Read | ||
| BV | 10128 | A_SEN_HI_COND_WATER_PRES | ALT-128 Sensor Alert - High Cond Water Pressure | Read | ||
| BV | 10129 | A_SEN_LCDW_F | ALT-129 Sensor Alert - Leaving Cond Water Temp | Read | ||
| BV | 10130 | A_SEN_ECDW_F | ALT-130 Sensor Alert - Entering Cond Water Temp | Read | ||
| BV | 10131 | A_SEN_ECDW_PRESS_F | ALT-131 Sensor Alert - Entering Cond Water Press | Read | ||
| BV | 10132 | A_SEN_ECW_PRESS_F | ALT-132 Sensor Alert - Entering Chilled Water Press | Read | ||
| BV | 10133 | A_SEN_LCDW_PRESS_F | ALT-133 Sensor Alert - Leaving Cond Water Press | Read | ||
| BV | 10134 | A_SEN_LCW_PRESS_F | ALT-134 Sensor Alert - Leaving Chilled Water Press | Read | ||
| BV | 10135 | A_SEN_GUIDE_VANE_1_POS_F | ALT-135 Sensor Alert - Guide Vane 1 Position | Read | ||
| BV | 10136 | A_CONF_TEMP_RESET_F | ALT-136 Configuration Error - Temp Reset | Read | ||
| BV | 10137 | A_CONF_CTRL_WATER_DT_RES | ALT-137 Configuration Error - Controlled Water Delta T Reset | Read | ||
| BV | 10138 | A_CONF_HEAD_PRESS_F | ALT-138 Configuration Error - Head Pressure | Read | ||
| BV | 10139 | A_SEN_GUIDE_VANE_2_POS_F | ALT-139 Sensor Alert - Guide Vane 2 Position | Read | ||
| BV | 10145 | A_PRO_PURGE_LL_SWITCH_M | ALT-145 Process Alert - Purge Liquid Level Switch Malfunction | Read | ||
| BV | 10146 | A_PRO_HIGH_FILTER_DP_F | ALT-146 Process Alert - High Ref Filter Delta Pressure | Read | ||
| BV | 10147 | A_PRO_DRAINAGE_SYS_F | ALT-147 Process Alert - Drainage System Failure | Read | ||
| BV | 10148 | A_PRO_DAILY_PG_LIM_F | ALT-148 Process Alert - Purge Daily Pumpout Limit Exceed | Read | ||
| BV | 10150 | A_PRO_LOW_DSH_F | ALT-150 Process Alert - Low Discharge Superheat | Read | ||
| BV | 10151 | A_PRO_HI_EVAP_APPROACH_F | ALT-151 Process Alert - High Evaporator Approach | Read | ||
| BV | 10152 | A_PRO_HI_COND_APPROACH_F | ALT-152 Process Alert - High Condenser Approach | Read | ||
| BV | 10153 | A_PRO_HI_NOISE_REGION_F | ALT-153 Process Alert - High Noise Region | Read | ||
| BV | 10154 | A_PRO_DAMPER_VALVE_F | ALT-154 Process Alert - Damper Valve Alert | Read | ||
| BV | 10155 | A_PRO_ALT_LOW_OIL_PRES_F | ALT-155 Process Alert - Low Oil Pressure Difference | Read | ||
| BV | 10156 | A_HGBP_VALVE_F | ALT-156 Process Alert - EC/HG Valve Alert | Read | ||
| BV | 10157 | A_PRO_HI_COND_PRESS_CHIL | ALT-157 Process Alert - High Condenser Pressure Chiller Off | Read | ||
| BV | 10158 | A_PRO_PROGNOSTIC_F | ALT-158 Process Alert - Prognostic Alert | Read | ||
| BV | 10159 | A_PRO_LEN_SCAN_WARNING_F | ALT-159 Process Alert - LEN Scan Warning | Read | ||
| BV | 10160 | A_PRO_OIL_FILTER_REPLACE | ALT-160 Process Alert - Oil Filter Replacement | Read | ||
| BV | 10161 | A_PRO_TRANSDUCER_CALIBRA | ALT-161 Process Alert - Transducer Calibration | Read | ||
| BV | 10162 | A_PRO_LOW_REFRIGERANT_CH | ALT-162 Process Alert - Low Refrigerant Charge | Read | ||
| BV | 10163 | A_PRO_HF_LOW_LEVEL | ALT-163 Process Alert - Low Liquid Level in High Float VLV | Read | ||
| BV | 10164 | A_PRO_ALT_DISPLACEMENT_F | ALT-164 Process Alert - Displacement Switch Failure | Read | ||
| BV | 10165 | A_PRO_HIGH_OIL_SUPPLY_TE | ALT-165 Process Alert - High Oil Supply Temperature | Read | ||
| BV | 10166 | A_PRO_COND_FLUSH_F | ALT-166 Process Alert - Condenser Flushing Suggested | Read | ||
| BV | 10167 | A_PRO_CUSTOMER_ALERT_F | ALT-167 Process Alert - Customer Alert | Read | ||
| BV | 10168 | A_PRO_COND_FREEZE_ALERT_ | ALT-168 Process Alert - Low Temp/Potential Cond Freeze-up | Read | ||
| BV | 10169 | A_PRO_ALT_HI_EVAP_PRESS_ | ALT-169 Process Alert - High Evaporator Pressure | Read | ||
| BV | 10170 | A_MS_SAME_ADDR_F | ALT-170 Primary Secondary - Same Address | Read | ||
| BV | 10171 | A_MS_CONFLICT_SW_VERSION | ALT-171 Primary Secondary - Conflict Application SW Version | Read | ||
| BV | 10172 | A_MS_CONFLICT_HEAT_COOL_ | ALT-172 Primary Secondary - Conflict Heating Cooling Mode | Read | ||
| BV | 10173 | A_MS_INCORRECT_SLAVE_CTR | ALT-173 Primary Secondary - Incorrect Secondary Control Type | Read | ||
| BV | 10174 | A_MS_SLAVE_TRIPOUT_F | ALT-174 Primary Secondary - Secondary Tripout | Read | ||
| BV | 10175 | A_MS_INCORRECT_MASTER_CT | ALT-175 Primary Secondary - Incorrect Primary Control Type | Read | ||
| BV | 10176 | A_MS_NO_COMMUNICATION_F | ALT-176 Primary Secondary - No Communication | Read | ||
| BV | 10179 | A_MS_MASTER_CCN_WRITE_RE | ALT-179 Primary Secondary - Primary CCN Write Rejection | Read | ||
| BV | 10180 | A_MS_DUPLICATED_F | ALT-180 Primary Secondary - Secondary Addr Not Secondary | Read | ||
| BV | 10181 | A_LOSS_COMM_WITH_GDCB_1_ | ALT-181 Loss Communication with AHF GDCB 1 | Read | ||
| BV | 10182 | A_LOSS_COMM_WITH_GDCB_2_ | ALT-182 Loss Communication with AHF GDCB 2 | Read | ||
| BV | 10183 | A_LOSS_COMM_WITH_GDCB_3_ | ALT-183 Loss Communication with AHF GDCB 3 | Read | ||
| BV | 10184 | A_LOSS_COMM_WITH_GDCB_4_ | ALT-184 Loss Communication with AHF GDCB 4 | Read | ||
| BV | 10185 | A_VFD_GDCB_1_FAULT_F | ALT-185 AHF GDCB 1 Start Failure | Read | ||
| BV | 10186 | A_VFD_GDCB_2_FAULT_F | ALT-186 AHF GDCB 2 Start Failure | Read | ||
| BV | 10187 | A_VFD_GDCB_3_FAULT_F | ALT-187 AHF GDCB 3 Start Failure | Read | ||
| BV | 10188 | A_VFD_GDCB_4_FAULT_F | ALT-188 AHF GDCB 4 Start Failure | Read | ||
| BV | 10189 | A_PRO_LOW_OIL_SUPPLY_TEM | ALT-189 Process Alert - Low Oil Supply Temperature | Read | ||
| BV | 10190 | A_AHF_FAULT_F | ALT-190 AHF FAULT | Read | ||
| BV | 10191 | A_LOSS_COMM_WITH_AHF_F | ALT-191 Loss Communication with AHF | Read | ||
| BV | 10200 | A_SEN_LCW_F | ALM-200 Sensor Fault - Leaving Chilled Water | Read | ||
| BV | 10201 | A_SEN_ECW_F | ALM-201 Sensor Fault - Entering Chilled Water | Read | ||
| BV | 10202 | A_SEN_LCDWT_FAULT_F | ALM-202 Sensor Fault - Leaving Cond Water Temp | Read | ||
| BV | 10203 | A_SEN_ECDWT_FAULT_F | ALM-203 Sensor Fault - Entering Cond Water Temp | Read | ||
| BV | 10204 | A_SEN_COMP_DISCHARGE_T_F | ALM-204 Sensor Fault - Comp Discharge Temp | Read | ||
| BV | 10205 | A_SEN_OIL_SUMP_TEMP_F | ALM-205 Sensor Fault - Oil Sump Temp | Read | ||
| BV | 10206 | A_SEN_OIL_DISCHARGE_T_F | ALM-206 Sensor Fault - Oil Supply Temp | Read | ||
| BV | 10207 | A_SEN_EVAP_REFRIG_LIQID_ | ALM-207 Sensor Fault - Evap Refrig Liquid Temp | Read | ||
| BV | 10208 | A_SEN_COMP_BEARING_T_1_F | ALM-208 Sensor Fault - Low Speed Motor End Bearing Temp | Read | ||
| BV | 10209 | A_SEN_COMP_BEARING_T_2_F | ALM-209 Sensor Fault - Low Speed Comp End Bearing Temp | Read | ||
| BV | 10210 | A_SEN_COMP_BEARING_T_3_F | ALM-210 Sensor Fault - High Speed Motor End Bearing Temp | Read | ||
| BV | 10211 | A_SEN_COMP_BEARING_T_4_F | ALM-211 Sensor Fault - High Speed Comp End Bearing Temp | Read | ||
| BV | 10212 | A_SEN_COMP_MOTOR_T_1 | ALM-212 Sensor Fault - Compressor Motor Winding 1 Temp | Read | ||
| BV | 10213 | A_SEN_COMP_MOTOR_T_2 | ALM-213 Sensor Fault - Compressor Motor Winding 2 Temp | Read | ||
| BV | 10214 | A_SEN_COMP_MOTOR_T_3 | ALM-214 Sensor Fault - Compressor Motor Winding 3 Temp | Read | ||
| BV | 10215 | A_SEN_COND_PRESS_F | ALM-215 Sensor Fault - Condenser Pressure | Read | ||
| BV | 10216 | A_SEN_EVAP_PRESS_F | ALM-216 Sensor Fault - Evaporator Pressure | Read | ||
| BV | 10217 | A_SEN_ECON_PRESS_F | ALM-217 Sensor Fault - Economizer Pressure | Read | ||
| BV | 10218 | A_SEN_DIFF_PRESS_F | ALM-218 Sensor Fault - Diffuser Pressure | Read | ||
| BV | 10219 | A_SEN_OIL_SUMP_PRESS_F | ALM-219 Sensor Fault - Oil Sump Pressure | Read | ||
| BV | 10220 | A_SEN_OIL_DISCHARGE_PRES | ALM-220 Sensor Fault - Oil Supply Pressure | Read | ||
| BV | 10221 | A_SEN_COMP_THRUST_BEARIN | ALM-221 Sensor Fault - Comp Thrust Bearing Oil Temp | Read | ||
| BV | 10223 | A_SEN_PURGE_COMP_INLET_T | ALM-223 Sensor Fault - Purge Compressor Suction Temp | Read | ||
| BV | 10225 | A_SEN_PUMP_INPUT_PRESS_F | ALM-225 Sensor Fault - Pump Inlet Pressure | Read | ||
| BV | 10226 | A_SEN_BEARING_INLET_PRES | ALM-226 Sensor Fault - Bearing Inlet Pressure | Read | ||
| BV | 10227 | A_SEN_BEARING_OUTLET_PRE | ALM-227 Sensor Fault - Bearing Outlet Pressure | Read | ||
| BV | 10228 | A_SEN_CHWS_F | ALM-228 Sensor Fault - Common CHWS Temp | Read | ||
| BV | 10229 | A_SEN_CHWR_F | ALM-229 Sensor Fault - Common CHWR Temp | Read | ||
| BV | 10230 | A_PRE_HI_BEARING_T_F | ALM-230 Prestart Failure - High Bearing Temperature | Read | ||
| BV | 10231 | A_PRE_HI_MOTOR_T_F | ALM-231 Prestart Failure - High Motor Temperature | Read | ||
| BV | 10232 | A_PRE_HIGH_DISCHARGE_T_F | ALM-232 Prestart Failure - High Discharge Temp | Read | ||
| BV | 10233 | A_PRE_LOW_REFRI_TEMP_F | ALM-233 Prestart Failure - Low Refrigerant Temp | Read | ||
| BV | 10234 | A_PRE_LOW_LINE_VOLT_F | ALM-234 Prestart Failure - Low Line Voltage | Read | ||
| BV | 10235 | A_PRE_HIGH_LINE_VOLT_F | ALM-235 Prestart Failure - High Line Voltage | Read | ||
| BV | 10236 | A_GV1_CALIB_NOT_COMPLETE | ALM-236 Guide Vane 1 Calibration Not Completed | Read | ||
| BV | 10237 | A_PRE_NO_PERMISSION_TO_S | ALM-237 Prestart Failure - No Power Supply | Read | ||
| BV | 10238 | A_GV2_CALIB_NOT_COMPLETE | ALM-238 Guide Vane 2 Calibration Not Completed | Read | ||
| BV | 10239 | A_HGBP_CALIB_NOT_COMPLET | ALM-239 Envelope Control Valve Calibration Not Completed | Read | ||
| BV | 10240 | A_DMP_CALIB_NOT_COMPLETE | ALM-240 Damper Valve Calibration Not Completed | Read | ||
| BV | 10250 | A_PRO_LOW_OIL_PRESS_DIFF | ALM-250 Protective Limit - Oil Pressure Difference Failure | Read | ||
| BV | 10251 | A_PRO_LOW_CHILLED_WATER_ | ALM-251 Protective Limit - Low Chilled Water Flow | Read | ||
| BV | 10252 | A_PRO_LOW_COND_WATER_FLO | ALM-252 Protective Limit - Low Condenser Water Flow | Read | ||
| BV | 10253 | A_PRO_HI_DSH_TEMP_F | ALM-253 Protective Limit - High Discharge Temp | Read | ||
| BV | 10255 | A_PRO_HI_MOTOR_T_F | ALM-255 Protective Limit - High Motor Temperature | Read | ||
| BV | 10256 | A_PRO_HI_BEARING_T_F | ALM-256 Protective Limit - High Bearing Temperature | Read | ||
| BV | 10257 | A_PRO_HI_COND_PRESS_F | ALM-257 Protective Limit - High Condenser Pressure | Read | ||
| BV | 10258 | A_PRO_SPARE_SAFETY_DEV_F | ALM-258 Protective Limit - Spare Safety Device | Read | ||
| BV | 10259 | A_PRO_EXCESSIVE_COMP_SUR | ALM-259 Protective Limit - Excessive Compressor Surge | Read | ||
| BV | 10260 | A_PRO_COMP_RELAY_START_F | ALM-260 Protective Limit - Comp Start Relay Start Failure | Read | ||
| BV | 10261 | A_PRO_EVAP_FREEZE_F | ALM-261 Protective Limit - Low Temp / Potential Evap Freeze-up | Read | ||
| BV | 10262 | A_PRO_COND_FREEZE_F | ALM-262 Protective Limit - Low Temp / Potential Cond Freeze-up | Read | ||
| BV | 10263 | A_PRO_INVALID_DIFF_CONF_ | ALM-263 Protective Limit - Invalid Diffuser Config | Read | ||
| BV | 10264 | A_PRO_DIFF_POS_F | ALM-264 Protective Limit - Diffuser Position Fault | Read | ||
| BV | 10265 | A_PRO_REFRIG_LEAK_F | ALM-265 Protective Limit - Refrigerant Leak | Read | ||
| BV | 10266 | A_PRO_IOB_LOW_VOLT_F | ALM-266 Protective Limit - IOB Low Voltage | Read | ||
| BV | 10267 | A_PRO_GV1_F | ALM-267 Protective Limit - Guide Vane 1 Fault | Read | ||
| BV | 10268 | A_PRO_DAMPER_VALVE_FAULT | ALM-268 Protective Limit - Damper Valve Fault | Read | ||
| BV | 10269 | A_PRO_HGBP_VALVE_F | ALM-269 Protective Limit - Envelope Control Valve Fault | Read | ||
| BV | 10270 | A_PRO_HI_COND_WATER_FLOW | ALM-270 Protective Limit - High Cond Water Flow | Read | ||
| BV | 10271 | A_PRO_EMERGENCY_STOP_F | ALM-271 Protective Limit - Emergency Stop | Read | ||
| BV | 10272 | A_PRO_ISM_CONF_CONFLIG_F | ALM-272 Protective Limit - ISM Config Conflict | Read | ||
| BV | 10273 | A_PRO_SWIFT_LIMIT_EXCEED | ALM-273 Protective Limit - Swift Restarts Limit Exceeded | Read | ||
| BV | 10274 | A_PRO_CHILLER_LOCKOUT_F | ALM-274 Protective Limit - Chiller Lockout | Read | ||
| BV | 10275 | A_PRO_FIRE_ALM_F | ALM-275 Protective Limit - Fire Alarm | Read | ||
| BV | 10276 | A_PRO_STOP_OVERRIDE_F | ALM-276 Protective Limit - Stop Override | Read | ||
| BV | 10277 | A_PRO_UI_FREEZE_F | ALM-277 Protective Limit - UI Freeze Reboot | Read | ||
| BV | 10278 | A_PRO_VFD_CONF_CONFLICT_ | ALM-278 Protective Limit - VFD Config Conflict | Read | ||
| BV | 10279 | A_PRO_VFD_CONF_ERROR_F | ALM-279 Protective Limit - VFD Config Failure | Read | ||
| BV | 10280 | A_PRO_HIGH_VFD_SPEED_F | ALM-280 Protective Limit - High VFD Speed | Read | ||
| BV | 10282 | A_PRO_BEARING_DISPLACEME | ALM-282 Protective Limit - Displacement Switch Open | Read | ||
| BV | 10283 | A_PRO_HIGH_PRESSURE_SWIT | ALM-283 Protective Limit - High Pressure Switch | Read | ||
| BV | 10284 | A_PRO_POWER_FDB_LOSS | ALM-284 Protective Limit - Power Feedback Loss | Read | ||
| BV | 10285 | A_PRO_LOW_BEARING_DELTA_ | ALM-285 Protective Limit - Low Bearing Delta Pres Difference | Read | ||
| BV | 10286 | A_PRO_ECO_PRESSURE_LOW | ALM-286 Protective Limit - Economizer Pressure Low | Read | ||
| BV | 10287 | A_PRO_OIL_PRESS_TRANS_F | ALM-287 Protective Limit - Oil Pressure Transducer Abnormal | Read | ||
| BV | 10288 | A_PRO_VFD_EMERGENCY_STOP | ALM-288 Protective Limit - VFD Emergency Stop | Read | ||
| BV | 10292 | A_PRO_GV2_F | ALM-292 Protective Limit - Guide Vane 2 Fault | Read | ||
| BV | 10296 | A_PRO_HI_EVAP_PRESS_CUTO | ALM-296 Protective Limit - High Evaporator Pressure | Read | ||
| BV | 10300 | A_LOSS_COMM_WITH_ISM_F | ALM-300 Loss Communication With ISM | Read | ||
| BV | 10301 | A_LOSS_COMM_WITH_IOB1_F | ALM-301 Loss Communication With IOB1 | Read | ||
| BV | 10302 | A_LOSS_COMM_WITH_IOB2_F | ALM-302 Loss Communication With IOB2 | Read | ||
| BV | 10303 | A_LOSS_COMM_WITH_IOB3_F | ALM-303 Loss Communication With IOB3 | Read | ||
| BV | 10304 | A_LOSS_COMM_WITH_IOB4_F | ALM-304 Loss Communication With IOB4 | Read | ||
| BV | 10305 | A_LOSS_COMM_WITH_IOB5_F | ALM-305 Loss Communication With IOB5 | Read | ||
| BV | 10306 | A_LOSS_COMM_WITH_SIOB_F | ALM-306 Loss Communication With SIOB | Read | ||
| BV | 10307 | A_LEN_SCAN_ERROR_F | ALM-307 LEN Scan Error | Read | ||
| BV | 10308 | A_LOSS_COMM_WITH_32VS_VF | ALM-308 Loss Communication With 32VS VFD | Read | ||
| BV | 10309 | A_LOSS_COMM_WITH_GATEWAY | ALM-309 Loss Communication With VFD Gateway (LEN) | Read | ||
| BV | 10310 | A_LOSS_COMM_WITH_MODBUS_ | ALM-310 Loss Communication With VFD/Starter (Modbus) | Read | ||
| BV | 10311 | A_LOSS_COMM_WITH_DANFOSS | ALM-311 Loss Communication With Danfoss VFD | Read | ||
| BV | 10350 | A_SEN_1ST_BEARING_T | ALM-350 Sensor Fault - 19DV 1st Stage Bearing Temp | Read | ||
| BV | 10351 | A_SEN_2ND_BEARING_T | ALM-351 Sensor Fault - 19DV 2nd Stage Bearing Temp | Read | ||
| BV | 10352 | A_SEN_PUMP_OUTPUT_PRESS_ | ALM-352 Sensor Fault - 19DV Pump Outlet Pressure | Read | ||
| BV | 10353 | A_SEN_HR_EWT | ALM-353 Sensor Fault - Heat Reclaim Entering Temp | Read | ||
| BV | 10354 | A_SEN_HR_LWT | ALM-354 Sensor Fault - Heat Reclaim Leaving Temp | Read | ||
| BV | 10400 | A_ISM_LINE_VOLT_DROPOUT_ | ALM-400 ISM Fault - Line Voltage Dropout | Read | ||
| BV | 10401 | A_ISM_LINE_PHASE_LOSS_F | ALM-401 ISM Fault - Line Phase Loss | Read | ||
| BV | 10402 | A_ISM_HI_LINE_VOLT_F | ALM-402 ISM Fault - High Line Voltage | Read | ||
| BV | 10403 | A_ISM_LOW_LINE_VOLT_F | ALM-403 ISM Fault - Low Line Voltage | Read | ||
| BV | 10404 | A_ISM_LINE_CURRENT_IMB_F | ALM-404 ISM Fault - Line Current Imbalance | Read | ||
| BV | 10405 | A_ISM_LINE_VOLT_IMB_F | ALM-405 ISM Fault - Line Voltage Imbalance | Read | ||
| BV | 10406 | A_ISM_OVER_LOAD_TRIP_F | ALM-406 ISM Fault - Overload Trip | Read | ||
| BV | 10407 | A_ISM_MOTOR_LOCKED_ROTOR | ALM-407 ISM Fault - Motor Locked Rotor Trip | Read | ||
| BV | 10408 | A_ISM_STARTER_LOCK_ROTOR | ALM-408 ISM Fault - Starter Lock Rotor Trip | Read | ||
| BV | 10409 | A_ISM_GROUND_FAULT_F | ALM-409 ISM Fault - Ground Fault | Read | ||
| BV | 10410 | A_ISM_PHASE_REVER_TRIP_F | ALM-410 ISM Fault - Phase Reversal Trip | Read | ||
| BV | 10411 | A_ISM_FREQ_TRIP_F | ALM-411 ISM Fault - Line Frequency Trip | Read | ||
| BV | 10412 | A_ISM_STARTER_MODULE_RES | ALM-412 ISM Fault - Starter Module Reset | Read | ||
| BV | 10413 | A_ISM_1M_CONTACT_F | ALM-413 ISM Fault - Start Contact Fault | Read | ||
| BV | 10414 | A_ISM_2M_CONTACT_F | ALM-414 ISM Fault - Transition Contact Fault | Read | ||
| BV | 10415 | A_ISM_HI_COND_PRESS_F | ALM-415 ISM Fault - Oil Pump or HPS Failure | Read | ||
| BV | 10416 | A_ISM_STARTER_F | ALM-416 ISM Fault - Starter Fault | Read | ||
| BV | 10417 | A_ISM_MOTOR_AMPS_NOT_SEN | ALM-417 ISM Fault - Motor Amps Not Sensed | Read | ||
| BV | 10418 | A_ISM_EXCESS_ACCEL_TIME_ | ALM-418 ISM Fault - Excessive Acceleration Time | Read | ||
| BV | 10419 | A_ISM_EXCESS_MOTOR_AMPS_ | ALM-419 ISM Fault - Excessive Motor Amps | Read | ||
| BV | 10420 | A_ISM_1M2M_CONTACT_F | ALM-420 ISM Fault - Start Transition Contact Fault | Read | ||
| BV | 10421 | A_ISM_MOTOR_AMPS_WHEN_ST | ALM-421 ISM Fault - Motor Amps When Stopped | Read | ||
| BV | 10422 | A_ISM_STARTER_MODULE_FAI | ALM-422 ISM Fault - Starter Module Failure | Read | ||
| BV | 10423 | A_ISM_CALIB_FACTOR_ERROR | ALM-423 ISM Fault - Calibration Factor Error | Read | ||
| BV | 10424 | A_ISM_INVALID_CONFIG_ERR | ALM-424 ISM Fault - Invalid Configuration Error | Read | ||
| BV | 10425 | A_VFD_SINGLE_CYCLE_DROPO | ALM-425 VFD Fault - Single Cycle Dropout | Read | ||
| BV | 10426 | A_VFD_LINE_CURRENT_IMBAL | ALM-426 VFD Fault - Line Current Imbalance | Read | ||
| BV | 10427 | A_VFD_HIGH_LINE_VOLTAGE_ | ALM-427 VFD Fault - High Line Voltage | Read | ||
| BV | 10428 | A_VFD_LOW_LINE_VOLTAGE_F | ALM-428 VFD Fault - Low Line Voltage | Read | ||
| BV | 10429 | A_VFD_LOW_DC_BUS_VOLTAGE | ALM-429 VFD Fault - Low DC Bus Voltage | Read | ||
| BV | 10430 | A_VFD_HIGH_DC_BUS_VOLTAG | ALM-430 VFD Fault - High DC Bus Voltage | Read | ||
| BV | 10431 | A_VFD_POWER_ON_RESET_F | ALM-431 VFD Fault - VFD Power On Reset | Read | ||
| BV | 10432 | A_VFD_GROUND_FAULT_F | ALM-432 VFD Fault - Ground Fault | Read | ||
| BV | 10433 | A_VFD_LINE_PHASE_REVERSA | ALM-433 VFD Fault - Line Phase Reversal | Read | ||
| BV | 10434 | A_VFD_MOTOR_OVERLOAD_TRI | ALM-434 VFD Fault - Motor Overload Trip | Read | ||
| BV | 10435 | A_VFD_RECTIFIER_POWER_FA | ALM-435 VFD Fault - Rectifier Power Fault | Read | ||
| BV | 10436 | A_VFD_INVERTER_POWER_FAU | ALM-436 VFD Fault - Inverter Power Fault | Read | ||
| BV | 10437 | A_VFD_RECTIFIER_OVERCURR | ALM-437 VFD Fault - Rectifier Overcurrent | Read | ||
| BV | 10438 | A_VFD_INVERTER_OVERCURRE | ALM-438 VFD Fault - Inverter Overcurrent | Read | ||
| BV | 10439 | A_VFD_CONDENSER_HIGH_PRE | ALM-439 VFD Fault - Condenser High Pressure | Read | ||
| BV | 10440 | A_VFD_MOTOR_AMPS_NOT_SEN | ALM-440 VFD Fault - Motor Amps Not Sensed | Read | ||
| BV | 10441 | A_VFD_MOTOR_ACCELERATION | ALM-441 VFD Fault - Motor Acceleration Fault | Read | ||
| BV | 10442 | A_VFD_STOP_FAULT_F | ALM-442 VFD Fault - Stop Fault | Read | ||
| BV | 10443 | A_VFD_RECTIFIER_OVERTEMP | ALM-443 VFD Fault - Rectifier Overtemp | Read | ||
| BV | 10444 | A_VFD_INVERTER_OVERTEMP_ | ALM-444 VFD Fault - Inverter Overtemp | Read | ||
| BV | 10445 | A_VFD_MOTOR_CURRENT_IMBA | ALM-445 VFD Fault - Motor Current Imbalance | Read | ||
| BV | 10446 | A_VFD_LINE_VOLTAGE_IMBAL | ALM-446 VFD Fault - Line Voltage Imbalance | Read | ||
| BV | 10447 | A_VFD_FREQUENCY_FAULT_F | ALM-447 VFD Fault - Frequency Fault | Read | ||
| BV | 10448 | A_VFD_COMM_FAIL_F | ALM-448 VFD/Starter Fault - Communication Fault | Read | ||
| BV | 10449 | A_VFD_FAULT_F | ALM-449 VFD Fault - VFD Fault | Read | ||
| BV | 10450 | A_VFD_START_INHIBIT_F | ALM-450 VFD Fault - VFD Start Inhibit | Read | ||
| BV | 10451 | A_VFD_CHECKSUM_ERROR_F | ALM-451 VFD Fault - VFD Checksum Error | Read | ||
| BV | 10452 | A_VFD_INDUCTOR_OVERTEMP_ | ALM-452 VFD Fault - Inductor Overtemp Switch | Read | ||
| BV | 10453 | A_VFD_INCOMPATIBILITY_FA | ALM-453 VFD Fault - Incompatibility Fault | Read | ||
| BV | 10454 | A_VFD_MAIN_FAILURE_F | ALM-454 VFD Fault - Main Power Failure | Read | ||
| BV | 10000 | A_ALARM_NULL | ALM Message End | Read |
No points match these filters.
Object ID lookup: Carrier AquaEdge 19XR PIC6.1 point IDs by name
MV1GENUNIT_ctl_modeBV1GENUNIT_statstopBV2GENUNIT_CHIL_S_S_rdBV3GENUNIT_CHIL_OCC_rdBV4GENUNIT_HC_SEL_rdAV1GENUNIT_CTRL_PNT_rdAV2GENUNIT_resetAV3GENUNIT_setpointAV4GENUNIT_AMPS_PAV5GENUNIT_KW_PAV6GENUNIT_DEM_LIM_rdBV5GENUNIT_EMSTOP_rdAV7GENUNIT_ch_stateBV6GENUNIT_loc_occBV7GENUNIT_ice_occBV8GENUNIT_FC_START_rdBV9GENUNIT_BAC_OCCAV8TEMP_ECWAV9TEMP_LCWAV10TEMP_ECDWAV11TEMP_LCDWAV12TEMP_HR_EWTAV13TEMP_HR_LWTAV14TEMP_EVAP_SATAV15TEMP_EVAP_TAV16TEMP_evap_appAV17TEMP_cond_appAV18TEMP_COND_SATAV19TEMP_DGTAV20TEMP_DSHAV21TEMP_MTRB_OILAV22TEMP_MTRBAV23TEMP_MTRB1AV24TEMP_MTRB2AV25TEMP_MTRB3AV26TEMP_MTRB4AV27TEMP_MTRW1AV28TEMP_MTRW2AV29TEMP_MTRW3AV30TEMP_OILT_SMPAV31TEMP_OILT_DISAV32TEMP_PGC_SUCTAV33TEMP_CBH1_TAV34TEMP_CBH2_TAV36PRESSURE_EVAP_PAV37PRESSURE_COND_PAV38PRESSURE_ECON_PAV39PRESSURE_OIL_PDAV40PRESSURE_DIFF_PAV41PRESSURE_HEAD_PAV42PRESSURE_REF_PDAV43PRESSURE_PUMP_PDBV10INPUTS_STAR_AUXMV2INPUTS_DMP_ACTMV3INPUTS_HGBP_ACTBV11INPUTS_HP_SWBV12INPUTS_REM_CONBV13INPUTS_E_STOPBV14INPUTS_ICE_CONBV15INPUTS_REM_LOCKBV16INPUTS_SAFETYBV17INPUTS_STARTFLTBV18INPUTS_FS_LOCKAV44INPUTS_GV1_ACTAV45INPUTS_GV2_ACTAV46INPUTS_VFD_ACTAV47INPUTS_DIFF_ACTAV48INPUTS_HGBPACTPBV19INPUTS_TRIPRBV21INPUTS_PGLE_LOBV22INPUTS_PGLE_HIBV23INPUTS_HF_LSAV49OUTPUTS_DIFF_OUTAV50OUTPUTS_HDPV_OUTAV51OUTPUTS_CHST_OUTAV52OUTPUTS_VFD_OUTAV53OUTPUTS_EXV_OUTAV54OUTPUTS_llc_exvtAV55OUTPUTS_op_vfd_tAV56OUTPUTS_GV1_OUTAV57OUTPUTS_GV2_OUTBV24OUTPUTS_ALMBV25OUTPUTS_ALEBV26OUTPUTS_COMP_SRBV27OUTPUTS_GV1_DECBV28OUTPUTS_GV1_INCBV29OUTPUTS_OIL_HEATBV30OUTPUTS_OIL_PUMPBV31OUTPUTS_TFR_HIGHBV32OUTPUTS_TFR_LOWBV33OUTPUTS_ECON_IVBV34OUTPUTS_COND_CVBV35OUTPUTS_EVAP_CVBV36OUTPUTS_EVAP_DCVBV37OUTPUTS_COND_DCVBV38OUTPUTS_COND_PSVBV39OUTPUTS_COMP_PSVBV40OUTPUTS_DRASVONBV41OUTPUTS_REG_PSVBV42OUTPUTS_DIS_PSVBV43OUTPUTS_PGAPUMPBV44OUTPUTS_PG_COMPBV45OUTPUTS_PG_HEATBV46OUTPUTS_VS_SVBV47OUTPUTS_FC_VALVEBV48OUTPUTS_COND_FCVBV49HYDRLIC_CDWPBV50HYDRLIC_CDW_FLOWAV58HYDRLIC_CDW_FVAV59HYDRLIC_cdw_pdBV51HYDRLIC_CHWPBV52HYDRLIC_CHW_FLOWAV60HYDRLIC_CHW_FVAV61HYDRLIC_chw_pdAV62HYDRLIC_ctrlw_dtAV63RUNTIME_C_STARTSAV64RUNTIME_COMP_HRSAV65RUNTIME_SRV_HRSAV66POWER_I_AMPS_A_IAV67POWER_I_AMPS_P_IAV68POWER_I_VOLT_AAV69POWER_I_VOLT_PAV70POWER_I_KWAV71POWER_I_POW_FACTAV72POWER_I_ln_imb_vAV73POWER_O_VFD_LOADAV74POWER_O_amps_p_oAV75POWER_O_MOT_FREQAV76POWER_O_bus_voltAV77POWER_O_vfd_actAV78POWER_O_motor_pfAV79POWER_O_motor_kwAV80POWER_O_motorkwhAV81POWER_O_enc_tempAV82POWER_O_inv_tempAV83POWER_O_rec_tempBV53POWER_O_prech_fdBV54POWER_O_lrtem_swAV84POWER_O_alm_codeBV55POWER_O_spd_fdBV56POWER_O_VFDC_HIAV85ALARMRST_alarm_1AV86ALARMRST_alarm_2AV87ALARMRST_alarm_3AV88ALARMRST_alarm_4AV89ALARMRST_alarm_5AV90CAPACTRL_ctrl_wtAV91CAPACTRL_gv1_tgtAV92CAPACTRL_gv2_tgtAV93CAPACTRL_vfd_tgtAV94CAPACTRL_hgbp_tpAV95CAPACTRL_cm_stat1AV96MAISURGE_act_regAV97MAISURGE_dts_actAV98MAISURGE_dts_calAV99MAISURGE_scAV100MAISURGE_spcAV101MAISURGE_surg_actAV102MAISURGE_surg_proAV103MAISURGE_dts_maxcAV104MAISURGE_dts_mincAV105MAISURGE_dts_medcAV106MAISURGE_gv1_sfulAV107MAISURGE_gv1_sminAV108MAISURGE_gv1_smedAV109MAISURGE_enlp_optAV110QCK_TEST_Q_GV1ACTAV111QCK_TEST_Q_DIFTGTAV112MAIN_SRD_diff_tgtBV57MAIN_SRD_diffaultBV58MAIN_SRD_diff_almAV113MAIN_SRD_lift_aAV114MAIN_SRD_lift_1AV115MAIN_SRD_lift_2AV116MAIN_MS_lead_lagAV117MAIN_MS_ms_ctrlAV118MAIN_MS_sl_ctrlBV59MAIN_MS_ll_commAV119MAIN_MS_ll_faultAV120MAIN_MS_lagstatBV60MAIN_MS_lag_s_sAV121MAIN_MS_lagstartAV122MAIN_MS_lagstopAV123MAIN_MS_prefltAV124MAIN_MS_pulltimeAV125MAIN_MS_ll_hr_dMV4FACTORY_chil_typMV5FACTORY_vfd_optAV126CFGSURGE_gv1_pminAV127CFGSURGE_gv1_pfulAV128CFGSURGE_sgl_offAV129CFGSURGE_sgl_loffAV130CFGSURGE_sgl_hoffAV131CFGSURGE_sgl_shfhAV132CFGSURGE_sgl_shflAV133CFGSURGE_sgl_spdfAV134CFGSURGE_sgl_proMV6CONF_OPT_hgbp_optMV7CONF_OPT_hgbp_selBV61LABONLY_gv1_fcBV62LABONLY_gv2_fcAV135CONF_PRG_oil_qlyAV136CONF_PRG_oil_fltAV137CONF_PRG_tran_devAV138CONF_PRG_ref_chgBV63CONNECT_bacenaBV64CONNECT_bacunitAV139CONNECT_networkAV140CONNECT_bac_idAV141SETPOINT_ecw_spAV142SETPOINT_lcw_spAV143SETPOINT_ecdw_spAV144SETPOINT_lcdw_spAV145SETPOINT_ice_spAV146SETPOINT_dem_baseBV65SETPOINT_EWT_OPTBV66GENUNIT_CHIL_S_S_wrAV147GENUNIT_CTRL_PNT_wrAV148GENUNIT_DEM_LIM_wrBV67GENUNIT_EMSTOP_wrAV149GENUNIT_HC_SEL_wrBV68GENUNIT_CHIL_OCC_wrBV69GENUNIT_FC_START_wrMV8BACnet_COLORAV150BACnet_PRIME_VAV151RUNTIME_ST_CNT12AV152POWER_I_ln_imb_iMV9MODES_cm_stat1AV153RUNTIME_PGP_NOAV154RUNTIME_PGP_TMAV155RUNTIME_pgp_tm_wAV156POWER_I_KWHBV70OUTPUTS_RUN_STATAV200HYDRLIC_EVAP_EWPAV201HYDRLIC_EVAP_LWPAV202RUNTIME_spst_timAV203RUNTIME_stst_timBV300INPUTS_POW_FDBBV301OUTPUTS_POW_REQAV204GENUNIT_cal_capaBV302HYDRLIC_EVAP_FSBV303HYDRLIC_COND_FSBV304GENUNIT_REM_RSTBV10100A_PRE_STARTS_LIMIT_EXCEEBV10101A_PRE_LOW_OIL_T_FBV10102A_PRE_HIGH_COND_PRESS_FBV10103A_PRE_EXCESSIVE_RECYCLE_BV10104A_PRE_WAIT_FOR_PERMISSIOBV10120A_REMOTE_TEMP_OUT_OF_RANBV10121A_SEN_AUTO_WATER_TEMP_REBV10122A_SEN_AUTO_DEMAND_LIMIT_BV10123A_SEN_VFD_SPEED_OUT_OF_RBV10124A_SEN_HUMIDITY_SENSOR_FBV10125A_SEN_REFRIG_LEAK_INPUT_BV10126A_SEN_DIFF_POS_FEEDBACK_BV10127A_SEN_VFD_CURRENT_INPUT_BV10128A_SEN_HI_COND_WATER_PRESBV10129A_SEN_LCDW_FBV10130A_SEN_ECDW_FBV10131A_SEN_ECDW_PRESS_FBV10132A_SEN_ECW_PRESS_FBV10133A_SEN_LCDW_PRESS_FBV10134A_SEN_LCW_PRESS_FBV10135A_SEN_GUIDE_VANE_1_POS_FBV10136A_CONF_TEMP_RESET_FBV10137A_CONF_CTRL_WATER_DT_RESBV10138A_CONF_HEAD_PRESS_FBV10139A_SEN_GUIDE_VANE_2_POS_FBV10145A_PRO_PURGE_LL_SWITCH_MBV10146A_PRO_HIGH_FILTER_DP_FBV10147A_PRO_DRAINAGE_SYS_FBV10148A_PRO_DAILY_PG_LIM_FBV10150A_PRO_LOW_DSH_FBV10151A_PRO_HI_EVAP_APPROACH_FBV10152A_PRO_HI_COND_APPROACH_FBV10153A_PRO_HI_NOISE_REGION_FBV10154A_PRO_DAMPER_VALVE_FBV10155A_PRO_ALT_LOW_OIL_PRES_FBV10156A_HGBP_VALVE_FBV10157A_PRO_HI_COND_PRESS_CHILBV10158A_PRO_PROGNOSTIC_FBV10159A_PRO_LEN_SCAN_WARNING_FBV10160A_PRO_OIL_FILTER_REPLACEBV10161A_PRO_TRANSDUCER_CALIBRABV10162A_PRO_LOW_REFRIGERANT_CHBV10163A_PRO_HF_LOW_LEVELBV10164A_PRO_ALT_DISPLACEMENT_FBV10165A_PRO_HIGH_OIL_SUPPLY_TEBV10166A_PRO_COND_FLUSH_FBV10167A_PRO_CUSTOMER_ALERT_FBV10168A_PRO_COND_FREEZE_ALERT_BV10169A_PRO_ALT_HI_EVAP_PRESS_BV10170A_MS_SAME_ADDR_FBV10171A_MS_CONFLICT_SW_VERSIONBV10172A_MS_CONFLICT_HEAT_COOL_BV10173A_MS_INCORRECT_SLAVE_CTRBV10174A_MS_SLAVE_TRIPOUT_FBV10175A_MS_INCORRECT_MASTER_CTBV10176A_MS_NO_COMMUNICATION_FBV10179A_MS_MASTER_CCN_WRITE_REBV10180A_MS_DUPLICATED_FBV10181A_LOSS_COMM_WITH_GDCB_1_BV10182A_LOSS_COMM_WITH_GDCB_2_BV10183A_LOSS_COMM_WITH_GDCB_3_BV10184A_LOSS_COMM_WITH_GDCB_4_BV10185A_VFD_GDCB_1_FAULT_FBV10186A_VFD_GDCB_2_FAULT_FBV10187A_VFD_GDCB_3_FAULT_FBV10188A_VFD_GDCB_4_FAULT_FBV10189A_PRO_LOW_OIL_SUPPLY_TEMBV10190A_AHF_FAULT_FBV10191A_LOSS_COMM_WITH_AHF_FBV10200A_SEN_LCW_FBV10201A_SEN_ECW_FBV10202A_SEN_LCDWT_FAULT_FBV10203A_SEN_ECDWT_FAULT_FBV10204A_SEN_COMP_DISCHARGE_T_FBV10205A_SEN_OIL_SUMP_TEMP_FBV10206A_SEN_OIL_DISCHARGE_T_FBV10207A_SEN_EVAP_REFRIG_LIQID_BV10208A_SEN_COMP_BEARING_T_1_FBV10209A_SEN_COMP_BEARING_T_2_FBV10210A_SEN_COMP_BEARING_T_3_FBV10211A_SEN_COMP_BEARING_T_4_FBV10212A_SEN_COMP_MOTOR_T_1BV10213A_SEN_COMP_MOTOR_T_2BV10214A_SEN_COMP_MOTOR_T_3BV10215A_SEN_COND_PRESS_FBV10216A_SEN_EVAP_PRESS_FBV10217A_SEN_ECON_PRESS_FBV10218A_SEN_DIFF_PRESS_FBV10219A_SEN_OIL_SUMP_PRESS_FBV10220A_SEN_OIL_DISCHARGE_PRESBV10221A_SEN_COMP_THRUST_BEARINBV10223A_SEN_PURGE_COMP_INLET_TBV10225A_SEN_PUMP_INPUT_PRESS_FBV10226A_SEN_BEARING_INLET_PRESBV10227A_SEN_BEARING_OUTLET_PREBV10228A_SEN_CHWS_FBV10229A_SEN_CHWR_FBV10230A_PRE_HI_BEARING_T_FBV10231A_PRE_HI_MOTOR_T_FBV10232A_PRE_HIGH_DISCHARGE_T_FBV10233A_PRE_LOW_REFRI_TEMP_FBV10234A_PRE_LOW_LINE_VOLT_FBV10235A_PRE_HIGH_LINE_VOLT_FBV10236A_GV1_CALIB_NOT_COMPLETEBV10237A_PRE_NO_PERMISSION_TO_SBV10238A_GV2_CALIB_NOT_COMPLETEBV10239A_HGBP_CALIB_NOT_COMPLETBV10240A_DMP_CALIB_NOT_COMPLETEBV10250A_PRO_LOW_OIL_PRESS_DIFFBV10251A_PRO_LOW_CHILLED_WATER_BV10252A_PRO_LOW_COND_WATER_FLOBV10253A_PRO_HI_DSH_TEMP_FBV10255A_PRO_HI_MOTOR_T_FBV10256A_PRO_HI_BEARING_T_FBV10257A_PRO_HI_COND_PRESS_FBV10258A_PRO_SPARE_SAFETY_DEV_FBV10259A_PRO_EXCESSIVE_COMP_SURBV10260A_PRO_COMP_RELAY_START_FBV10261A_PRO_EVAP_FREEZE_FBV10262A_PRO_COND_FREEZE_FBV10263A_PRO_INVALID_DIFF_CONF_BV10264A_PRO_DIFF_POS_FBV10265A_PRO_REFRIG_LEAK_FBV10266A_PRO_IOB_LOW_VOLT_FBV10267A_PRO_GV1_FBV10268A_PRO_DAMPER_VALVE_FAULTBV10269A_PRO_HGBP_VALVE_FBV10270A_PRO_HI_COND_WATER_FLOWBV10271A_PRO_EMERGENCY_STOP_FBV10272A_PRO_ISM_CONF_CONFLIG_FBV10273A_PRO_SWIFT_LIMIT_EXCEEDBV10274A_PRO_CHILLER_LOCKOUT_FBV10275A_PRO_FIRE_ALM_FBV10276A_PRO_STOP_OVERRIDE_FBV10277A_PRO_UI_FREEZE_FBV10278A_PRO_VFD_CONF_CONFLICT_BV10279A_PRO_VFD_CONF_ERROR_FBV10280A_PRO_HIGH_VFD_SPEED_FBV10282A_PRO_BEARING_DISPLACEMEBV10283A_PRO_HIGH_PRESSURE_SWITBV10284A_PRO_POWER_FDB_LOSSBV10285A_PRO_LOW_BEARING_DELTA_BV10286A_PRO_ECO_PRESSURE_LOWBV10287A_PRO_OIL_PRESS_TRANS_FBV10288A_PRO_VFD_EMERGENCY_STOPBV10292A_PRO_GV2_FBV10296A_PRO_HI_EVAP_PRESS_CUTOBV10300A_LOSS_COMM_WITH_ISM_FBV10301A_LOSS_COMM_WITH_IOB1_FBV10302A_LOSS_COMM_WITH_IOB2_FBV10303A_LOSS_COMM_WITH_IOB3_FBV10304A_LOSS_COMM_WITH_IOB4_FBV10305A_LOSS_COMM_WITH_IOB5_FBV10306A_LOSS_COMM_WITH_SIOB_FBV10307A_LEN_SCAN_ERROR_FBV10308A_LOSS_COMM_WITH_32VS_VFBV10309A_LOSS_COMM_WITH_GATEWAYBV10310A_LOSS_COMM_WITH_MODBUS_BV10311A_LOSS_COMM_WITH_DANFOSSBV10350A_SEN_1ST_BEARING_TBV10351A_SEN_2ND_BEARING_TBV10352A_SEN_PUMP_OUTPUT_PRESS_BV10353A_SEN_HR_EWTBV10354A_SEN_HR_LWTBV10400A_ISM_LINE_VOLT_DROPOUT_BV10401A_ISM_LINE_PHASE_LOSS_FBV10402A_ISM_HI_LINE_VOLT_FBV10403A_ISM_LOW_LINE_VOLT_FBV10404A_ISM_LINE_CURRENT_IMB_FBV10405A_ISM_LINE_VOLT_IMB_FBV10406A_ISM_OVER_LOAD_TRIP_FBV10407A_ISM_MOTOR_LOCKED_ROTORBV10408A_ISM_STARTER_LOCK_ROTORBV10409A_ISM_GROUND_FAULT_FBV10410A_ISM_PHASE_REVER_TRIP_FBV10411A_ISM_FREQ_TRIP_FBV10412A_ISM_STARTER_MODULE_RESBV10413A_ISM_1M_CONTACT_FBV10414A_ISM_2M_CONTACT_FBV10415A_ISM_HI_COND_PRESS_FBV10416A_ISM_STARTER_FBV10417A_ISM_MOTOR_AMPS_NOT_SENBV10418A_ISM_EXCESS_ACCEL_TIME_BV10419A_ISM_EXCESS_MOTOR_AMPS_BV10420A_ISM_1M2M_CONTACT_FBV10421A_ISM_MOTOR_AMPS_WHEN_STBV10422A_ISM_STARTER_MODULE_FAIBV10423A_ISM_CALIB_FACTOR_ERRORBV10424A_ISM_INVALID_CONFIG_ERRBV10425A_VFD_SINGLE_CYCLE_DROPOBV10426A_VFD_LINE_CURRENT_IMBALBV10427A_VFD_HIGH_LINE_VOLTAGE_BV10428A_VFD_LOW_LINE_VOLTAGE_FBV10429A_VFD_LOW_DC_BUS_VOLTAGEBV10430A_VFD_HIGH_DC_BUS_VOLTAGBV10431A_VFD_POWER_ON_RESET_FBV10432A_VFD_GROUND_FAULT_FBV10433A_VFD_LINE_PHASE_REVERSABV10434A_VFD_MOTOR_OVERLOAD_TRIBV10435A_VFD_RECTIFIER_POWER_FABV10436A_VFD_INVERTER_POWER_FAUBV10437A_VFD_RECTIFIER_OVERCURRBV10438A_VFD_INVERTER_OVERCURREBV10439A_VFD_CONDENSER_HIGH_PREBV10440A_VFD_MOTOR_AMPS_NOT_SENBV10441A_VFD_MOTOR_ACCELERATIONBV10442A_VFD_STOP_FAULT_FBV10443A_VFD_RECTIFIER_OVERTEMPBV10444A_VFD_INVERTER_OVERTEMP_BV10445A_VFD_MOTOR_CURRENT_IMBABV10446A_VFD_LINE_VOLTAGE_IMBALBV10447A_VFD_FREQUENCY_FAULT_FBV10448A_VFD_COMM_FAIL_FBV10449A_VFD_FAULT_FBV10450A_VFD_START_INHIBIT_FBV10451A_VFD_CHECKSUM_ERROR_FBV10452A_VFD_INDUCTOR_OVERTEMP_BV10453A_VFD_INCOMPATIBILITY_FABV10454A_VFD_MAIN_FAILURE_FBV10000A_ALARM_NULL
Integration notes
- Access is taken from the PV ACCESS column: RW objects are listed as writable, RO as read-only.
- This is the PIC6.1 controller; the older PIC5 19XR has its own list (19XR-CLT-3T).
- The guide says the controller holds up to 500 objects; the table prints 463 (160 AV, 294 BV, 9 MV).
- BV 10000-10454 are one flag per alert (ALT-) or alarm (ALM-) code; BV 10000 marks the end of the alarm message list.
- No units column; values follow the BACnet Metric Unit setting (bacunit).
- Some alarm object names are cut at 24 characters in the guide (for example A_PRO_ALT_HI_EVAP_PRESS_); they are kept as printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaEdge 19XR (PIC6.1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaEdge 19XR (PIC6.1)
How many BACnet points does the Carrier AquaEdge 19XR (PIC6.1) have?
This list has 463 BACnet objects: 160 analog values, 294 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaEdge 19XR (PIC6.1) BACnet points are writable?
15 of the 463 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaEdge 19XR (PIC6.1) BACnet documentation?
The source is AquaEdge 19XR Single-Stage and Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers - Controls Operation and Troubleshooting (Appendix D, Table C BACnet Object Table) (19XR-CLT-9T), revision 2024-11, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0C/19XR-CLT-9T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaEdge 19XR (PIC6.1)?
Start with BV 66 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 68 GENUNIT_CHIL_OCC_wr (Network occupied command); BV 67 GENUNIT_EMSTOP_wr (Emergency stop command); AV 147 GENUNIT_CTRL_PNT_wr (Control point command); AV 148 GENUNIT_DEM_LIM_wr (Demand limit command); MV 1 GENUNIT_ctl_mode (Control mode: Local, Network, Remote, Local Sched); AV 7 GENUNIT_ch_state (Chiller status code); AV 9 TEMP_LCW (Leaving chilled water temperature); AV 8 TEMP_ECW (Entering chilled water temperature); AV 85 ALARMRST_alarm_1 (Current alarm 1).
How do I enable BMS control of the Carrier AquaEdge 19XR (PIC6.1)?
In Network control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP for a shutdown. If the Stop Override point in GENUNIT is enabled the chiller cannot start.
How do I check these points on the real AquaEdge 19XR (PIC6.1)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaEdge 19XR Single-Stage and Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers - Controls Operation and Troubleshooting (Appendix D, Table C BACnet Object Table) · 19XR-CLT-9T · rev. 2024-11. Object names, instances and units are reproduced as published; descriptions are our own.