Water-cooled centrifugal chiller controller · BACnet points list

Carrier AquaEdge 19XR (PIC6.1) BACnet points list

Updated 6 November 2026

Short answer

The 19XR PIC6.1 controller speaks BACnet MS/TP on RS-485 port J8 or BACnet IP on Ethernet port J15, plus Modbus RTU/TCP. Object names join the CCN table and point name (TEMP_LCW, GENUNIT_CHIL_S_S_wr). Commands use paired read (_rd) and write (_wr) objects; the list also carries temperatures, pressures, bearing and motor data, VFD values and one binary value per alarm or alert code (BV 10000 and up).

This page lists 463 BACnet objects for the Carrier AquaEdge 19XR (PIC6.1) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaEdge 19XR (PIC6.1)
Equipment
Water-cooled centrifugal chiller controller
Equipment type
Chillers
BACnet objects
463 (15 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
1600001
Also known as
19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller
Source document
AquaEdge 19XR Single-Stage and Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers - Controls Operation and Troubleshooting (Appendix D, Table C BACnet Object Table) · 19XR-CLT-9T · rev. 2024-11
Download CSV 463 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier AquaEdge 19XR (PIC6.1)

Integration in brief

Select BACnet MS/TP on port J8 or enable BACnet/IP in the BMS Protocol menu (Service password), set the identifier and network, and put the chiller in Network control mode. The chiller then starts when both BV 66 start/stop and BV 68 occupied are true; write control point and demand limit through the _wr objects and read status, water temperatures and alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 66GENUNIT_CHIL_S_S_wrNetwork start/stop commandWrite
BV 68GENUNIT_CHIL_OCC_wrNetwork occupied commandWrite
BV 67GENUNIT_EMSTOP_wrEmergency stop commandWrite
AV 147GENUNIT_CTRL_PNT_wrControl point commandWrite
AV 148GENUNIT_DEM_LIM_wrDemand limit commandWrite
MV 1GENUNIT_ctl_modeControl mode: Local, Network, Remote, Local SchedRead
AV 7GENUNIT_ch_stateChiller status codeRead
AV 9TEMP_LCWLeaving chilled water temperatureRead
AV 8TEMP_ECWEntering chilled water temperatureRead
AV 85ALARMRST_alarm_1Current alarm 1Read

Enable & remote start

In Network control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP for a shutdown. If the Stop Override point in GENUNIT is enabled the chiller cannot start.

Network setup

Watch out for

Carrier AquaEdge 19XR (PIC6.1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

463 of 463 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier AquaEdge 19XR (PIC6.1) BACnet Points List
DescriptionStates
MVmin1GENUNIT_ctl_modeControl ModeRead
BV1GENUNIT_statstopDeter Start Stop CommandRead
BV2GENUNIT_CHIL_S_S_rdNetwork:Cmd Start/StopRead
BV3GENUNIT_CHIL_OCC_rdNetwork:Cmd OccupiedRead
BV4GENUNIT_HC_SEL_rdCooling/Heating SelectRead
AV1GENUNIT_CTRL_PNT_rdControl PointRead
AV2GENUNIT_resetControl Point ResetRead
AV3GENUNIT_setpointActual SetpointRead
AV4GENUNIT_AMPS_PPercent CurrentRead
AV5GENUNIT_KW_PMotor Percent KilowattsRead
AV6GENUNIT_DEM_LIM_rdActual Demand LimitRead
BV5GENUNIT_EMSTOP_rdBMS Emergency StopRead
AVmin7GENUNIT_ch_stateChiller Status CodeRead
BV6GENUNIT_loc_occLocal Schedule OccupiedRead
BV7GENUNIT_ice_occIce Schedule OccupiedRead
BV8GENUNIT_FC_START_rdStart Free CoolingRead
BV9GENUNIT_BAC_OCCBACnet OccupiedRead
AVmin8TEMP_ECWEntering Chilled WaterRead
AVmin9TEMP_LCWLeaving Chilled WaterRead
AV10TEMP_ECDWEntering Condenser WaterRead
AV11TEMP_LCDWLeaving Condenser WaterRead
AV12TEMP_HR_EWTHeat Recl Entering TempRead
AV13TEMP_HR_LWTHeat Recl Leaving TempRead
AV14TEMP_EVAP_SATEvap Sat Refrig TempRead
AV15TEMP_EVAP_TEvap Refrig Liquid TempRead
AV16TEMP_evap_appEvaporator ApproachRead
AV17TEMP_cond_appCondenser ApproachRead
AV18TEMP_COND_SATCond Sat Refrig TempRead
AV19TEMP_DGTComp Discharge TempRead
AV20TEMP_DSHDischarge SuperheatRead
AV21TEMP_MTRB_OILThrust Bearing Oil TempRead
AV22TEMP_MTRBThrust Bearing TempRead
AV23TEMP_MTRB1Low Speed ME Brg TempRead
AV24TEMP_MTRB2Low Speed CE Brg TempRead
AV25TEMP_MTRB3High Speed ME Brg TempRead
AV26TEMP_MTRB4High Speed CE Brg TempRead
AV27TEMP_MTRW1Motor Winding 1 TempRead
AV28TEMP_MTRW2Motor Winding 2 TempRead
AV29TEMP_MTRW3Motor Winding 3 TempRead
AV30TEMP_OILT_SMPOil Sump TempRead
AV31TEMP_OILT_DISOil Supply TempRead
AV32TEMP_PGC_SUCTPurge Comp Suction TempRead
AV33TEMP_CBH1_T1st Stage Bearing TempRead
AV34TEMP_CBH2_T2nd Stage Bearing TempRead
AV36PRESSURE_EVAP_PEvaporator PressureRead
AV37PRESSURE_COND_PCondenser PressureRead
AV38PRESSURE_ECON_PEconomizer PressureRead
AV39PRESSURE_OIL_PDOil Pump Delta PRead
AV40PRESSURE_DIFF_PDiffuser PressureRead
AV41PRESSURE_HEAD_PHead Pressure ReferenceRead
AV42PRESSURE_REF_PDBearing Delta PRead
AV43PRESSURE_PUMP_PDRef Pump Delta PRead
BV10INPUTS_STAR_AUXCompressor Start ContactRead
MV2INPUTS_DMP_ACTECO DMP VLV StatusRead
MV3INPUTS_HGBP_ACTEC/HG VLV StatusRead
BV11INPUTS_HP_SWHigh Pressure SwitchRead
BV12INPUTS_REM_CONRemote Start/StopRead
BV13INPUTS_E_STOPEmergency Stop ContactRead
BV14INPUTS_ICE_CONIce Build ContactRead
BV15INPUTS_REM_LOCKChiller LockoutRead
BV16INPUTS_SAFETYSpare Safety InputRead
BV17INPUTS_STARTFLTStarter Fault FeedbackRead
BV18INPUTS_FS_LOCKFire Security InterlockRead
AV44INPUTS_GV1_ACTGuide Vane 1 Actual PosRead
AV45INPUTS_GV2_ACTGuide Vane 2 Actual PosRead
AV46INPUTS_VFD_ACTActual VFD Speed PerRead
AV47INPUTS_DIFF_ACTDiffuser Actual PosRead
AV48INPUTS_HGBPACTPEC/HG VLV Actual Pos PerRead
BV19INPUTS_TRIPRShunt Trip Relay StatusRead
BV21INPUTS_PGLE_LOPurge Level Switch LowRead
BV22INPUTS_PGLE_HIPurge Level Switch HighRead
BV23INPUTS_HF_LSLiquid Level SwitchRead
AV49OUTPUTS_DIFF_OUTDiffuser Output mARead
AV50OUTPUTS_HDPV_OUTHead Pres Output mARead
AV51OUTPUTS_CHST_OUTChiller Status (Analog)Read
AV52OUTPUTS_VFD_OUTVFD Speed Output mARead
AV53OUTPUTS_EXV_OUTOil Cooler EXV mARead
AV54OUTPUTS_llc_exvtLiquid Level EXV TargetRead
AV55OUTPUTS_op_vfd_tOil Pump VFD TargetRead
AV56OUTPUTS_GV1_OUTGuide Vane1 OutputRead
AV57OUTPUTS_GV2_OUTGuide Vane2 OutputRead
BV24OUTPUTS_ALMAlarm RelayRead
BV25OUTPUTS_ALEAlert RelayRead
BV26OUTPUTS_COMP_SRCompressor Start RelayRead
BV27OUTPUTS_GV1_DECGuide Vane 1 DecreaseRead
BV28OUTPUTS_GV1_INCGuide Vane 1 IncreaseRead
BV29OUTPUTS_OIL_HEATOil Heater RelayRead
BV30OUTPUTS_OIL_PUMPOil Pump RelayRead
BV31OUTPUTS_TFR_HIGHTower Fan Relay HighRead
BV32OUTPUTS_TFR_LOWTower Fan Relay LowRead
BV33OUTPUTS_ECON_IVECO Isolation VLVRead
BV34OUTPUTS_COND_CVCond Valve (Ref Lube)Read
BV35OUTPUTS_EVAP_CVEvap Valve (Ref Lube)Read
BV36OUTPUTS_EVAP_DCVEvaporator Drain ValveRead
BV37OUTPUTS_COND_DCVCondenser Drain ValveRead
BV38OUTPUTS_COND_PSVPurge Cond ValveRead
BV39OUTPUTS_COMP_PSVPurge Comp ValveRead
BV40OUTPUTS_DRASVONPurge Drainage ValveRead
BV41OUTPUTS_REG_PSVPurge Regeneration ValveRead
BV42OUTPUTS_DIS_PSVPurge Discharge ValveRead
BV43OUTPUTS_PGAPUMPPurge Vacuum PumpRead
BV44OUTPUTS_PG_COMPPurge CompressorRead
BV45OUTPUTS_PG_HEATPurge HeaterRead
BV46OUTPUTS_VS_SVVapor Source SVRead
BV47OUTPUTS_FC_VALVEFree Cooling ValveRead
BV48OUTPUTS_COND_FCVCond Charging (Ref Lube)Read
BV49HYDRLIC_CDWPCondenser Water PumpRead
BV50HYDRLIC_CDW_FLOWCondenser Water FlowRead
AV58HYDRLIC_CDW_FVCond Water Flow ValueRead
AV59HYDRLIC_cdw_pdCondenser Water Delta PRead
BV51HYDRLIC_CHWPChilled Water PumpRead
BV52HYDRLIC_CHW_FLOWChilled Water FlowRead
AV60HYDRLIC_CHW_FVChilled Water Flow ValueRead
AV61HYDRLIC_chw_pdChilled Water Delta PRead
AV62HYDRLIC_ctrlw_dtControlled Water DTRead
AV63RUNTIME_C_STARTSCompressor Starts NumRead
AV64RUNTIME_COMP_HRSComp Total Running HrsRead
AV65RUNTIME_SRV_HRSAfter Service HrsRead
AV66POWER_I_AMPS_A_IActual Line CurrentRead
AV67POWER_I_AMPS_P_IPercent Line CurrentRead
AV68POWER_I_VOLT_AActual Line VoltageRead
AV69POWER_I_VOLT_PPercent Line VoltageRead
AV70POWER_I_KWLine KWRead
AV71POWER_I_POW_FACTLine Power FactorRead
AV72POWER_I_ln_imb_vLine Voltage Imbalance%Read
AV73POWER_O_VFD_LOADVFD Load CurrentRead
AV74POWER_O_amps_p_oPercent VFD Load CurrentRead
AV75POWER_O_MOT_FREQMotor Actual FrequencyRead
AV76POWER_O_bus_voltDC Bus VoltageRead
AV77POWER_O_vfd_actActual VFD Speed PerRead
AV78POWER_O_motor_pfMotor Power FactorRead
AV79POWER_O_motor_kwMotor KilowattsRead
AV80POWER_O_motorkwhMotor Kilowatt-HoursRead
AV81POWER_O_enc_tempVFD Enclosure TempRead
AV82POWER_O_inv_tempInverter TemperatureRead
AV83POWER_O_rec_tempRectifier TemperatureRead
BV53POWER_O_prech_fdPrecharge FeedbackRead
BV54POWER_O_lrtem_swLR Temp SwitchRead
AV84POWER_O_alm_codeVFD Alarm CodeRead
BV55POWER_O_spd_fdSPD FeedbackRead
BV56POWER_O_VFDC_HIHigh VFD CurrentRead
AVmin85ALARMRST_alarm_1Jbus Current Alarm 1Read
AV86ALARMRST_alarm_2Jbus Current Alarm 2Read
AV87ALARMRST_alarm_3Jbus Current Alarm 3Read
AV88ALARMRST_alarm_4Jbus Current Alarm 4Read
AV89ALARMRST_alarm_5Jbus Current Alarm 5Read
AV90CAPACTRL_ctrl_wtControlled Water TempRead
AV91CAPACTRL_gv1_tgtTarget GV1 PosRead
AV92CAPACTRL_gv2_tgtTarget GV2 PosRead
AV93CAPACTRL_vfd_tgtTarget VFD Speed PerRead
AV94CAPACTRL_hgbp_tpEC/HG VLV Target PerRead
AV95CAPACTRL_cm_stat1Comp1 Run State ValRead
AV96MAISURGE_act_regSurge RegionRead
AV97MAISURGE_dts_actActual Delta TsatRead
AV98MAISURGE_dts_calCalc Ref Delta TsatRead
AV99MAISURGE_scSurge CountsRead
AV100MAISURGE_spcSurge Protection CountsRead
AV101MAISURGE_surg_actSurge Prevention ActiveRead
AV102MAISURGE_surg_proSurge Protection ActiveRead
AV103MAISURGE_dts_maxcCal Surge Delta TsmaxRead
AV104MAISURGE_dts_mincCal Surge Delta TsminRead
AV105MAISURGE_dts_medcCal Surge Delta TsmedRead
AV106MAISURGE_gv1_sfulIGV1 Full Load PositionRead
AV107MAISURGE_gv1_sminIGV1 Minimum PositionRead
AV108MAISURGE_gv1_smedOpti-Sound IGV1 PositionRead
AV109MAISURGE_enlp_optEnvelope Line/HG Opt.Read
AV110QCK_TEST_Q_GV1ACTGuide Vane 1 Actual PosRead
AV111QCK_TEST_Q_DIFTGTDiffuser Target PosRead
AV112MAIN_SRD_diff_tgtDiffuser Target PosRead
BV57MAIN_SRD_diffaultDiffuser FaultRead
BV58MAIN_SRD_diff_almSRD Rotating Stall AlarmRead
AV113MAIN_SRD_lift_aActual LiftRead
AV114MAIN_SRD_lift_1VDO High Lift Load LineRead
AV115MAIN_SRD_lift_2VDO Low Lift Load LineRead
AV116MAIN_MS_lead_lagUnit is Lead or LagRead
AV117MAIN_MS_ms_ctrlPrimary Control TypeRead
AV118MAIN_MS_sl_ctrlSecondary Control TypeRead
BV59MAIN_MS_ll_commLead Lag CommunicationRead
AV119MAIN_MS_ll_faultPrimary Secondary FaultRead
AV120MAIN_MS_lagstatSecondary Run StatusRead
BV60MAIN_MS_lag_s_sSecondary Start/StopRead
AV121MAIN_MS_lagstartLag Start TimerRead
AV122MAIN_MS_lagstopLag Stop TimerRead
AV123MAIN_MS_prefltPrestart Fault TimerRead
AV124MAIN_MS_pulltimePulldown TimerRead
AV125MAIN_MS_ll_hr_dLead/Lag Hours DeltaRead
MV4FACTORY_chil_typChiller TypeRead
MV5FACTORY_vfd_optVFD/Starter OptionRead
AV126CFGSURGE_gv1_pminIGV1 Minimum PositionRead
AV127CFGSURGE_gv1_pfulIGV1 Full Load PositionRead
AV128CFGSURGE_sgl_offSurge Line OffsetRead
AV129CFGSURGE_sgl_loffSurge Line Lower DBRead
AV130CFGSURGE_sgl_hoffSurge Line Upper DBRead
AV131CFGSURGE_sgl_shfhSurge Line Shape FactorRead
AV132CFGSURGE_sgl_shflSound Line Shape FactorRead
AV133CFGSURGE_sgl_spdfSurge Line Speed FactorRead
AV134CFGSURGE_sgl_proSurge Profile OffsetRead
MV6CONF_OPT_hgbp_optEC/HG Valve OptionRead
MV7CONF_OPT_hgbp_selEC/HG Valve SelectionRead
BV61LABONLY_gv1_fcGV1 ForcedRead
BV62LABONLY_gv2_fcGV2 ForcedRead
AV135CONF_PRG_oil_qlyOil QualityRead
AV136CONF_PRG_oil_fltOil Filter FailureRead
AV137CONF_PRG_tran_devTransducer DeviationRead
AV138CONF_PRG_ref_chgRefrig Charge StatusRead
BV63CONNECT_bacenaBACnet/IP EnableRead
BV64CONNECT_bacunitBACnet Metric UnitRead
AV139CONNECT_networkBACnet NetworkRead
AV140CONNECT_bac_idBACnet IdentifierRead
AV141SETPOINT_ecw_spCooling ECW SetpointWrite
AV142SETPOINT_lcw_spCooling LCW SetpointWrite
AV143SETPOINT_ecdw_spHeating ECDW SetpointWrite
AV144SETPOINT_lcdw_spHeating LCDW SetpointWrite
AV145SETPOINT_ice_spIce Build SetpointWrite
AV146SETPOINT_dem_baseBase Demand LimitWrite
BV65SETPOINT_EWT_OPTEWT Control OptionWrite
BVmin66GENUNIT_CHIL_S_S_wrChiller Start/StopWrite
AVmin147GENUNIT_CTRL_PNT_wrControl PointWrite
AVmin148GENUNIT_DEM_LIM_wrDemand LimitWrite
BVmin67GENUNIT_EMSTOP_wrBMS Emergency StopWrite
AV149GENUNIT_HC_SEL_wrHeatcool SelectWrite
BVmin68GENUNIT_CHIL_OCC_wrChiller occupied?Write
BV69GENUNIT_FC_START_wrStart Free CoolingWrite
MV8BACnet_COLOROperation Status ColorRead
AV150BACnet_PRIME_VValue of Prime variableRead
AV151RUNTIME_ST_CNT12Starts Num in 12 HoursRead
AV152POWER_I_ln_imb_iLine Current Imbalance%Read
MV9MODES_cm_stat1Comp1 Run State ValRead
AV153RUNTIME_PGP_NOTotal Pumpout NumbersRead
AV154RUNTIME_PGP_TMTotal Pumpout TimeRead
AV155RUNTIME_pgp_tm_wAvg Daily Purge in 7 DayRead
AV156POWER_I_KWHLine KWHRead
BV70OUTPUTS_RUN_STATChiller Status(Discrete)Read
AV200HYDRLIC_EVAP_EWPEntering Chilled Water PRead
AV201HYDRLIC_EVAP_LWPLeaving Chilled Water PRead
AV202RUNTIME_spst_timStop to Start TimerRead
AV203RUNTIME_stst_timStart to Start TimerRead
BV300INPUTS_POW_FDBMarine Pwr Req FeedbackRead
BV301OUTPUTS_POW_REQMarine Pwr Req OutputRead
AV204GENUNIT_cal_capaCalculated CapacityRead
BV302HYDRLIC_EVAP_FSEvap Water Flow SwitchRead
BV303HYDRLIC_COND_FSCond Water Flow SwitchRead
BV304GENUNIT_REM_RSTRemote Reset AlarmWrite
BV10100A_PRE_STARTS_LIMIT_EXCEEALT-100 Prestart Alert - Starts Limit ExceededRead
BV10101A_PRE_LOW_OIL_T_FALT-101 Prestart Alert - Low Oil TemperatureRead
BV10102A_PRE_HIGH_COND_PRESS_FALT-102 Prestart Alert - High Condenser PressureRead
BV10103A_PRE_EXCESSIVE_RECYCLE_ALT-103 Prestart Alert - Excessive Recycle StartsRead
BV10104A_PRE_WAIT_FOR_PERMISSIOALT-104 Prestart Alert - Waiting For Start PermissionRead
BV10120A_REMOTE_TEMP_OUT_OF_RANALT-120 Sensor Alert - Remote Temperature Out of RangeRead
BV10121A_SEN_AUTO_WATER_TEMP_REALT-121 Sensor Alert - Auto Water Temp ResetRead
BV10122A_SEN_AUTO_DEMAND_LIMIT_ALT-122 Sensor Alert - Auto Demand Limit InputRead
BV10123A_SEN_VFD_SPEED_OUT_OF_RALT-123 Sensor Alert - VFD Speed Out of RangeRead
BV10124A_SEN_HUMIDITY_SENSOR_FALT-124 Sensor Alert - Humidity SensorRead
BV10125A_SEN_REFRIG_LEAK_INPUT_ALT-125 Sensor Alert - Refrigerant Leak InputRead
BV10126A_SEN_DIFF_POS_FEEDBACK_ALT-126 Sensor Alert - Diffuser Pos FeedbackRead
BV10127A_SEN_VFD_CURRENT_INPUT_ALT-127 Sensor Alert - VFD Current InputRead
BV10128A_SEN_HI_COND_WATER_PRESALT-128 Sensor Alert - High Cond Water PressureRead
BV10129A_SEN_LCDW_FALT-129 Sensor Alert - Leaving Cond Water TempRead
BV10130A_SEN_ECDW_FALT-130 Sensor Alert - Entering Cond Water TempRead
BV10131A_SEN_ECDW_PRESS_FALT-131 Sensor Alert - Entering Cond Water PressRead
BV10132A_SEN_ECW_PRESS_FALT-132 Sensor Alert - Entering Chilled Water PressRead
BV10133A_SEN_LCDW_PRESS_FALT-133 Sensor Alert - Leaving Cond Water PressRead
BV10134A_SEN_LCW_PRESS_FALT-134 Sensor Alert - Leaving Chilled Water PressRead
BV10135A_SEN_GUIDE_VANE_1_POS_FALT-135 Sensor Alert - Guide Vane 1 PositionRead
BV10136A_CONF_TEMP_RESET_FALT-136 Configuration Error - Temp ResetRead
BV10137A_CONF_CTRL_WATER_DT_RESALT-137 Configuration Error - Controlled Water Delta T ResetRead
BV10138A_CONF_HEAD_PRESS_FALT-138 Configuration Error - Head PressureRead
BV10139A_SEN_GUIDE_VANE_2_POS_FALT-139 Sensor Alert - Guide Vane 2 PositionRead
BV10145A_PRO_PURGE_LL_SWITCH_MALT-145 Process Alert - Purge Liquid Level Switch MalfunctionRead
BV10146A_PRO_HIGH_FILTER_DP_FALT-146 Process Alert - High Ref Filter Delta PressureRead
BV10147A_PRO_DRAINAGE_SYS_FALT-147 Process Alert - Drainage System FailureRead
BV10148A_PRO_DAILY_PG_LIM_FALT-148 Process Alert - Purge Daily Pumpout Limit ExceedRead
BV10150A_PRO_LOW_DSH_FALT-150 Process Alert - Low Discharge SuperheatRead
BV10151A_PRO_HI_EVAP_APPROACH_FALT-151 Process Alert - High Evaporator ApproachRead
BV10152A_PRO_HI_COND_APPROACH_FALT-152 Process Alert - High Condenser ApproachRead
BV10153A_PRO_HI_NOISE_REGION_FALT-153 Process Alert - High Noise RegionRead
BV10154A_PRO_DAMPER_VALVE_FALT-154 Process Alert - Damper Valve AlertRead
BV10155A_PRO_ALT_LOW_OIL_PRES_FALT-155 Process Alert - Low Oil Pressure DifferenceRead
BV10156A_HGBP_VALVE_FALT-156 Process Alert - EC/HG Valve AlertRead
BV10157A_PRO_HI_COND_PRESS_CHILALT-157 Process Alert - High Condenser Pressure Chiller OffRead
BV10158A_PRO_PROGNOSTIC_FALT-158 Process Alert - Prognostic AlertRead
BV10159A_PRO_LEN_SCAN_WARNING_FALT-159 Process Alert - LEN Scan WarningRead
BV10160A_PRO_OIL_FILTER_REPLACEALT-160 Process Alert - Oil Filter ReplacementRead
BV10161A_PRO_TRANSDUCER_CALIBRAALT-161 Process Alert - Transducer CalibrationRead
BV10162A_PRO_LOW_REFRIGERANT_CHALT-162 Process Alert - Low Refrigerant ChargeRead
BV10163A_PRO_HF_LOW_LEVELALT-163 Process Alert - Low Liquid Level in High Float VLVRead
BV10164A_PRO_ALT_DISPLACEMENT_FALT-164 Process Alert - Displacement Switch FailureRead
BV10165A_PRO_HIGH_OIL_SUPPLY_TEALT-165 Process Alert - High Oil Supply TemperatureRead
BV10166A_PRO_COND_FLUSH_FALT-166 Process Alert - Condenser Flushing SuggestedRead
BV10167A_PRO_CUSTOMER_ALERT_FALT-167 Process Alert - Customer AlertRead
BV10168A_PRO_COND_FREEZE_ALERT_ALT-168 Process Alert - Low Temp/Potential Cond Freeze-upRead
BV10169A_PRO_ALT_HI_EVAP_PRESS_ALT-169 Process Alert - High Evaporator PressureRead
BV10170A_MS_SAME_ADDR_FALT-170 Primary Secondary - Same AddressRead
BV10171A_MS_CONFLICT_SW_VERSIONALT-171 Primary Secondary - Conflict Application SW VersionRead
BV10172A_MS_CONFLICT_HEAT_COOL_ALT-172 Primary Secondary - Conflict Heating Cooling ModeRead
BV10173A_MS_INCORRECT_SLAVE_CTRALT-173 Primary Secondary - Incorrect Secondary Control TypeRead
BV10174A_MS_SLAVE_TRIPOUT_FALT-174 Primary Secondary - Secondary TripoutRead
BV10175A_MS_INCORRECT_MASTER_CTALT-175 Primary Secondary - Incorrect Primary Control TypeRead
BV10176A_MS_NO_COMMUNICATION_FALT-176 Primary Secondary - No CommunicationRead
BV10179A_MS_MASTER_CCN_WRITE_REALT-179 Primary Secondary - Primary CCN Write RejectionRead
BV10180A_MS_DUPLICATED_FALT-180 Primary Secondary - Secondary Addr Not SecondaryRead
BV10181A_LOSS_COMM_WITH_GDCB_1_ALT-181 Loss Communication with AHF GDCB 1Read
BV10182A_LOSS_COMM_WITH_GDCB_2_ALT-182 Loss Communication with AHF GDCB 2Read
BV10183A_LOSS_COMM_WITH_GDCB_3_ALT-183 Loss Communication with AHF GDCB 3Read
BV10184A_LOSS_COMM_WITH_GDCB_4_ALT-184 Loss Communication with AHF GDCB 4Read
BV10185A_VFD_GDCB_1_FAULT_FALT-185 AHF GDCB 1 Start FailureRead
BV10186A_VFD_GDCB_2_FAULT_FALT-186 AHF GDCB 2 Start FailureRead
BV10187A_VFD_GDCB_3_FAULT_FALT-187 AHF GDCB 3 Start FailureRead
BV10188A_VFD_GDCB_4_FAULT_FALT-188 AHF GDCB 4 Start FailureRead
BV10189A_PRO_LOW_OIL_SUPPLY_TEMALT-189 Process Alert - Low Oil Supply TemperatureRead
BV10190A_AHF_FAULT_FALT-190 AHF FAULTRead
BV10191A_LOSS_COMM_WITH_AHF_FALT-191 Loss Communication with AHFRead
BV10200A_SEN_LCW_FALM-200 Sensor Fault - Leaving Chilled WaterRead
BV10201A_SEN_ECW_FALM-201 Sensor Fault - Entering Chilled WaterRead
BV10202A_SEN_LCDWT_FAULT_FALM-202 Sensor Fault - Leaving Cond Water TempRead
BV10203A_SEN_ECDWT_FAULT_FALM-203 Sensor Fault - Entering Cond Water TempRead
BV10204A_SEN_COMP_DISCHARGE_T_FALM-204 Sensor Fault - Comp Discharge TempRead
BV10205A_SEN_OIL_SUMP_TEMP_FALM-205 Sensor Fault - Oil Sump TempRead
BV10206A_SEN_OIL_DISCHARGE_T_FALM-206 Sensor Fault - Oil Supply TempRead
BV10207A_SEN_EVAP_REFRIG_LIQID_ALM-207 Sensor Fault - Evap Refrig Liquid TempRead
BV10208A_SEN_COMP_BEARING_T_1_FALM-208 Sensor Fault - Low Speed Motor End Bearing TempRead
BV10209A_SEN_COMP_BEARING_T_2_FALM-209 Sensor Fault - Low Speed Comp End Bearing TempRead
BV10210A_SEN_COMP_BEARING_T_3_FALM-210 Sensor Fault - High Speed Motor End Bearing TempRead
BV10211A_SEN_COMP_BEARING_T_4_FALM-211 Sensor Fault - High Speed Comp End Bearing TempRead
BV10212A_SEN_COMP_MOTOR_T_1ALM-212 Sensor Fault - Compressor Motor Winding 1 TempRead
BV10213A_SEN_COMP_MOTOR_T_2ALM-213 Sensor Fault - Compressor Motor Winding 2 TempRead
BV10214A_SEN_COMP_MOTOR_T_3ALM-214 Sensor Fault - Compressor Motor Winding 3 TempRead
BV10215A_SEN_COND_PRESS_FALM-215 Sensor Fault - Condenser PressureRead
BV10216A_SEN_EVAP_PRESS_FALM-216 Sensor Fault - Evaporator PressureRead
BV10217A_SEN_ECON_PRESS_FALM-217 Sensor Fault - Economizer PressureRead
BV10218A_SEN_DIFF_PRESS_FALM-218 Sensor Fault - Diffuser PressureRead
BV10219A_SEN_OIL_SUMP_PRESS_FALM-219 Sensor Fault - Oil Sump PressureRead
BV10220A_SEN_OIL_DISCHARGE_PRESALM-220 Sensor Fault - Oil Supply PressureRead
BV10221A_SEN_COMP_THRUST_BEARINALM-221 Sensor Fault - Comp Thrust Bearing Oil TempRead
BV10223A_SEN_PURGE_COMP_INLET_TALM-223 Sensor Fault - Purge Compressor Suction TempRead
BV10225A_SEN_PUMP_INPUT_PRESS_FALM-225 Sensor Fault - Pump Inlet PressureRead
BV10226A_SEN_BEARING_INLET_PRESALM-226 Sensor Fault - Bearing Inlet PressureRead
BV10227A_SEN_BEARING_OUTLET_PREALM-227 Sensor Fault - Bearing Outlet PressureRead
BV10228A_SEN_CHWS_FALM-228 Sensor Fault - Common CHWS TempRead
BV10229A_SEN_CHWR_FALM-229 Sensor Fault - Common CHWR TempRead
BV10230A_PRE_HI_BEARING_T_FALM-230 Prestart Failure - High Bearing TemperatureRead
BV10231A_PRE_HI_MOTOR_T_FALM-231 Prestart Failure - High Motor TemperatureRead
BV10232A_PRE_HIGH_DISCHARGE_T_FALM-232 Prestart Failure - High Discharge TempRead
BV10233A_PRE_LOW_REFRI_TEMP_FALM-233 Prestart Failure - Low Refrigerant TempRead
BV10234A_PRE_LOW_LINE_VOLT_FALM-234 Prestart Failure - Low Line VoltageRead
BV10235A_PRE_HIGH_LINE_VOLT_FALM-235 Prestart Failure - High Line VoltageRead
BV10236A_GV1_CALIB_NOT_COMPLETEALM-236 Guide Vane 1 Calibration Not CompletedRead
BV10237A_PRE_NO_PERMISSION_TO_SALM-237 Prestart Failure - No Power SupplyRead
BV10238A_GV2_CALIB_NOT_COMPLETEALM-238 Guide Vane 2 Calibration Not CompletedRead
BV10239A_HGBP_CALIB_NOT_COMPLETALM-239 Envelope Control Valve Calibration Not CompletedRead
BV10240A_DMP_CALIB_NOT_COMPLETEALM-240 Damper Valve Calibration Not CompletedRead
BV10250A_PRO_LOW_OIL_PRESS_DIFFALM-250 Protective Limit - Oil Pressure Difference FailureRead
BV10251A_PRO_LOW_CHILLED_WATER_ALM-251 Protective Limit - Low Chilled Water FlowRead
BV10252A_PRO_LOW_COND_WATER_FLOALM-252 Protective Limit - Low Condenser Water FlowRead
BV10253A_PRO_HI_DSH_TEMP_FALM-253 Protective Limit - High Discharge TempRead
BV10255A_PRO_HI_MOTOR_T_FALM-255 Protective Limit - High Motor TemperatureRead
BV10256A_PRO_HI_BEARING_T_FALM-256 Protective Limit - High Bearing TemperatureRead
BV10257A_PRO_HI_COND_PRESS_FALM-257 Protective Limit - High Condenser PressureRead
BV10258A_PRO_SPARE_SAFETY_DEV_FALM-258 Protective Limit - Spare Safety DeviceRead
BV10259A_PRO_EXCESSIVE_COMP_SURALM-259 Protective Limit - Excessive Compressor SurgeRead
BV10260A_PRO_COMP_RELAY_START_FALM-260 Protective Limit - Comp Start Relay Start FailureRead
BV10261A_PRO_EVAP_FREEZE_FALM-261 Protective Limit - Low Temp / Potential Evap Freeze-upRead
BV10262A_PRO_COND_FREEZE_FALM-262 Protective Limit - Low Temp / Potential Cond Freeze-upRead
BV10263A_PRO_INVALID_DIFF_CONF_ALM-263 Protective Limit - Invalid Diffuser ConfigRead
BV10264A_PRO_DIFF_POS_FALM-264 Protective Limit - Diffuser Position FaultRead
BV10265A_PRO_REFRIG_LEAK_FALM-265 Protective Limit - Refrigerant LeakRead
BV10266A_PRO_IOB_LOW_VOLT_FALM-266 Protective Limit - IOB Low VoltageRead
BV10267A_PRO_GV1_FALM-267 Protective Limit - Guide Vane 1 FaultRead
BV10268A_PRO_DAMPER_VALVE_FAULTALM-268 Protective Limit - Damper Valve FaultRead
BV10269A_PRO_HGBP_VALVE_FALM-269 Protective Limit - Envelope Control Valve FaultRead
BV10270A_PRO_HI_COND_WATER_FLOWALM-270 Protective Limit - High Cond Water FlowRead
BV10271A_PRO_EMERGENCY_STOP_FALM-271 Protective Limit - Emergency StopRead
BV10272A_PRO_ISM_CONF_CONFLIG_FALM-272 Protective Limit - ISM Config ConflictRead
BV10273A_PRO_SWIFT_LIMIT_EXCEEDALM-273 Protective Limit - Swift Restarts Limit ExceededRead
BV10274A_PRO_CHILLER_LOCKOUT_FALM-274 Protective Limit - Chiller LockoutRead
BV10275A_PRO_FIRE_ALM_FALM-275 Protective Limit - Fire AlarmRead
BV10276A_PRO_STOP_OVERRIDE_FALM-276 Protective Limit - Stop OverrideRead
BV10277A_PRO_UI_FREEZE_FALM-277 Protective Limit - UI Freeze RebootRead
BV10278A_PRO_VFD_CONF_CONFLICT_ALM-278 Protective Limit - VFD Config ConflictRead
BV10279A_PRO_VFD_CONF_ERROR_FALM-279 Protective Limit - VFD Config FailureRead
BV10280A_PRO_HIGH_VFD_SPEED_FALM-280 Protective Limit - High VFD SpeedRead
BV10282A_PRO_BEARING_DISPLACEMEALM-282 Protective Limit - Displacement Switch OpenRead
BV10283A_PRO_HIGH_PRESSURE_SWITALM-283 Protective Limit - High Pressure SwitchRead
BV10284A_PRO_POWER_FDB_LOSSALM-284 Protective Limit - Power Feedback LossRead
BV10285A_PRO_LOW_BEARING_DELTA_ALM-285 Protective Limit - Low Bearing Delta Pres DifferenceRead
BV10286A_PRO_ECO_PRESSURE_LOWALM-286 Protective Limit - Economizer Pressure LowRead
BV10287A_PRO_OIL_PRESS_TRANS_FALM-287 Protective Limit - Oil Pressure Transducer AbnormalRead
BV10288A_PRO_VFD_EMERGENCY_STOPALM-288 Protective Limit - VFD Emergency StopRead
BV10292A_PRO_GV2_FALM-292 Protective Limit - Guide Vane 2 FaultRead
BV10296A_PRO_HI_EVAP_PRESS_CUTOALM-296 Protective Limit - High Evaporator PressureRead
BV10300A_LOSS_COMM_WITH_ISM_FALM-300 Loss Communication With ISMRead
BV10301A_LOSS_COMM_WITH_IOB1_FALM-301 Loss Communication With IOB1Read
BV10302A_LOSS_COMM_WITH_IOB2_FALM-302 Loss Communication With IOB2Read
BV10303A_LOSS_COMM_WITH_IOB3_FALM-303 Loss Communication With IOB3Read
BV10304A_LOSS_COMM_WITH_IOB4_FALM-304 Loss Communication With IOB4Read
BV10305A_LOSS_COMM_WITH_IOB5_FALM-305 Loss Communication With IOB5Read
BV10306A_LOSS_COMM_WITH_SIOB_FALM-306 Loss Communication With SIOBRead
BV10307A_LEN_SCAN_ERROR_FALM-307 LEN Scan ErrorRead
BV10308A_LOSS_COMM_WITH_32VS_VFALM-308 Loss Communication With 32VS VFDRead
BV10309A_LOSS_COMM_WITH_GATEWAYALM-309 Loss Communication With VFD Gateway (LEN)Read
BV10310A_LOSS_COMM_WITH_MODBUS_ALM-310 Loss Communication With VFD/Starter (Modbus)Read
BV10311A_LOSS_COMM_WITH_DANFOSSALM-311 Loss Communication With Danfoss VFDRead
BV10350A_SEN_1ST_BEARING_TALM-350 Sensor Fault - 19DV 1st Stage Bearing TempRead
BV10351A_SEN_2ND_BEARING_TALM-351 Sensor Fault - 19DV 2nd Stage Bearing TempRead
BV10352A_SEN_PUMP_OUTPUT_PRESS_ALM-352 Sensor Fault - 19DV Pump Outlet PressureRead
BV10353A_SEN_HR_EWTALM-353 Sensor Fault - Heat Reclaim Entering TempRead
BV10354A_SEN_HR_LWTALM-354 Sensor Fault - Heat Reclaim Leaving TempRead
BV10400A_ISM_LINE_VOLT_DROPOUT_ALM-400 ISM Fault - Line Voltage DropoutRead
BV10401A_ISM_LINE_PHASE_LOSS_FALM-401 ISM Fault - Line Phase LossRead
BV10402A_ISM_HI_LINE_VOLT_FALM-402 ISM Fault - High Line VoltageRead
BV10403A_ISM_LOW_LINE_VOLT_FALM-403 ISM Fault - Low Line VoltageRead
BV10404A_ISM_LINE_CURRENT_IMB_FALM-404 ISM Fault - Line Current ImbalanceRead
BV10405A_ISM_LINE_VOLT_IMB_FALM-405 ISM Fault - Line Voltage ImbalanceRead
BV10406A_ISM_OVER_LOAD_TRIP_FALM-406 ISM Fault - Overload TripRead
BV10407A_ISM_MOTOR_LOCKED_ROTORALM-407 ISM Fault - Motor Locked Rotor TripRead
BV10408A_ISM_STARTER_LOCK_ROTORALM-408 ISM Fault - Starter Lock Rotor TripRead
BV10409A_ISM_GROUND_FAULT_FALM-409 ISM Fault - Ground FaultRead
BV10410A_ISM_PHASE_REVER_TRIP_FALM-410 ISM Fault - Phase Reversal TripRead
BV10411A_ISM_FREQ_TRIP_FALM-411 ISM Fault - Line Frequency TripRead
BV10412A_ISM_STARTER_MODULE_RESALM-412 ISM Fault - Starter Module ResetRead
BV10413A_ISM_1M_CONTACT_FALM-413 ISM Fault - Start Contact FaultRead
BV10414A_ISM_2M_CONTACT_FALM-414 ISM Fault - Transition Contact FaultRead
BV10415A_ISM_HI_COND_PRESS_FALM-415 ISM Fault - Oil Pump or HPS FailureRead
BV10416A_ISM_STARTER_FALM-416 ISM Fault - Starter FaultRead
BV10417A_ISM_MOTOR_AMPS_NOT_SENALM-417 ISM Fault - Motor Amps Not SensedRead
BV10418A_ISM_EXCESS_ACCEL_TIME_ALM-418 ISM Fault - Excessive Acceleration TimeRead
BV10419A_ISM_EXCESS_MOTOR_AMPS_ALM-419 ISM Fault - Excessive Motor AmpsRead
BV10420A_ISM_1M2M_CONTACT_FALM-420 ISM Fault - Start Transition Contact FaultRead
BV10421A_ISM_MOTOR_AMPS_WHEN_STALM-421 ISM Fault - Motor Amps When StoppedRead
BV10422A_ISM_STARTER_MODULE_FAIALM-422 ISM Fault - Starter Module FailureRead
BV10423A_ISM_CALIB_FACTOR_ERRORALM-423 ISM Fault - Calibration Factor ErrorRead
BV10424A_ISM_INVALID_CONFIG_ERRALM-424 ISM Fault - Invalid Configuration ErrorRead
BV10425A_VFD_SINGLE_CYCLE_DROPOALM-425 VFD Fault - Single Cycle DropoutRead
BV10426A_VFD_LINE_CURRENT_IMBALALM-426 VFD Fault - Line Current ImbalanceRead
BV10427A_VFD_HIGH_LINE_VOLTAGE_ALM-427 VFD Fault - High Line VoltageRead
BV10428A_VFD_LOW_LINE_VOLTAGE_FALM-428 VFD Fault - Low Line VoltageRead
BV10429A_VFD_LOW_DC_BUS_VOLTAGEALM-429 VFD Fault - Low DC Bus VoltageRead
BV10430A_VFD_HIGH_DC_BUS_VOLTAGALM-430 VFD Fault - High DC Bus VoltageRead
BV10431A_VFD_POWER_ON_RESET_FALM-431 VFD Fault - VFD Power On ResetRead
BV10432A_VFD_GROUND_FAULT_FALM-432 VFD Fault - Ground FaultRead
BV10433A_VFD_LINE_PHASE_REVERSAALM-433 VFD Fault - Line Phase ReversalRead
BV10434A_VFD_MOTOR_OVERLOAD_TRIALM-434 VFD Fault - Motor Overload TripRead
BV10435A_VFD_RECTIFIER_POWER_FAALM-435 VFD Fault - Rectifier Power FaultRead
BV10436A_VFD_INVERTER_POWER_FAUALM-436 VFD Fault - Inverter Power FaultRead
BV10437A_VFD_RECTIFIER_OVERCURRALM-437 VFD Fault - Rectifier OvercurrentRead
BV10438A_VFD_INVERTER_OVERCURREALM-438 VFD Fault - Inverter OvercurrentRead
BV10439A_VFD_CONDENSER_HIGH_PREALM-439 VFD Fault - Condenser High PressureRead
BV10440A_VFD_MOTOR_AMPS_NOT_SENALM-440 VFD Fault - Motor Amps Not SensedRead
BV10441A_VFD_MOTOR_ACCELERATIONALM-441 VFD Fault - Motor Acceleration FaultRead
BV10442A_VFD_STOP_FAULT_FALM-442 VFD Fault - Stop FaultRead
BV10443A_VFD_RECTIFIER_OVERTEMPALM-443 VFD Fault - Rectifier OvertempRead
BV10444A_VFD_INVERTER_OVERTEMP_ALM-444 VFD Fault - Inverter OvertempRead
BV10445A_VFD_MOTOR_CURRENT_IMBAALM-445 VFD Fault - Motor Current ImbalanceRead
BV10446A_VFD_LINE_VOLTAGE_IMBALALM-446 VFD Fault - Line Voltage ImbalanceRead
BV10447A_VFD_FREQUENCY_FAULT_FALM-447 VFD Fault - Frequency FaultRead
BV10448A_VFD_COMM_FAIL_FALM-448 VFD/Starter Fault - Communication FaultRead
BV10449A_VFD_FAULT_FALM-449 VFD Fault - VFD FaultRead
BV10450A_VFD_START_INHIBIT_FALM-450 VFD Fault - VFD Start InhibitRead
BV10451A_VFD_CHECKSUM_ERROR_FALM-451 VFD Fault - VFD Checksum ErrorRead
BV10452A_VFD_INDUCTOR_OVERTEMP_ALM-452 VFD Fault - Inductor Overtemp SwitchRead
BV10453A_VFD_INCOMPATIBILITY_FAALM-453 VFD Fault - Incompatibility FaultRead
BV10454A_VFD_MAIN_FAILURE_FALM-454 VFD Fault - Main Power FailureRead
BV10000A_ALARM_NULLALM Message EndRead
Object ID lookup: Carrier AquaEdge 19XR PIC6.1 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaEdge 19XR (PIC6.1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaEdge 19XR (PIC6.1)

How many BACnet points does the Carrier AquaEdge 19XR (PIC6.1) have?

This list has 463 BACnet objects: 160 analog values, 294 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaEdge 19XR (PIC6.1) BACnet points are writable?

15 of the 463 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaEdge 19XR (PIC6.1) BACnet documentation?

The source is AquaEdge 19XR Single-Stage and Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers - Controls Operation and Troubleshooting (Appendix D, Table C BACnet Object Table) (19XR-CLT-9T), revision 2024-11, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0C/19XR-CLT-9T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaEdge 19XR (PIC6.1)?

Start with BV 66 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 68 GENUNIT_CHIL_OCC_wr (Network occupied command); BV 67 GENUNIT_EMSTOP_wr (Emergency stop command); AV 147 GENUNIT_CTRL_PNT_wr (Control point command); AV 148 GENUNIT_DEM_LIM_wr (Demand limit command); MV 1 GENUNIT_ctl_mode (Control mode: Local, Network, Remote, Local Sched); AV 7 GENUNIT_ch_state (Chiller status code); AV 9 TEMP_LCW (Leaving chilled water temperature); AV 8 TEMP_ECW (Entering chilled water temperature); AV 85 ALARMRST_alarm_1 (Current alarm 1).

How do I enable BMS control of the Carrier AquaEdge 19XR (PIC6.1)?

In Network control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP for a shutdown. If the Stop Override point in GENUNIT is enabled the chiller cannot start.

How do I check these points on the real AquaEdge 19XR (PIC6.1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaEdge 19XR Single-Stage and Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers - Controls Operation and Troubleshooting (Appendix D, Table C BACnet Object Table) · 19XR-CLT-9T · rev. 2024-11. Object names, instances and units are reproduced as published; descriptions are our own.