- 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Self-contained unit controller · BACnet points list
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP) BACnet points list
Updated 7 November 2026
The SCU Open program runs on a UC Open XP controller and talks BACnet MS/TP or ARC156 on its EIA-485 port. The points list has 168 objects: setpoints and configuration as AVs, alarms and enables as BVs, and a few multistate values such as BAS On/Off and System Mode. It covers single-zone (space temperature) and VAV (supply air temperature and duct static) operation, plus water economizer, hot gas reheat and auxiliary hot water heat options.
This page lists 168 BACnet objects for the Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP) — 80 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
- Equipment
- Self-contained unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 168 (80 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Address the UC Open XP with its two rotary switches, set the MS/TP baud rate with the DIP switches, then command occupancy through BAS On/Off (MV 1001) and read System Mode, temperatures and alarms. Setpoints and enables are writable AVs and BVs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1001 | keypad_ovrde | BAS occupancy: 1=Inactive (schedule), 2=Occ, 3=Unocc | Write |
| AV 3001 | occ_cl_stpt | Occupied cooling setpoint | Write |
| AV 3002 | occ_ht_stpt | Occupied heating setpoint | Write |
| AV 3029 | sat_cl_stpt | Supply air setpoint (VAV units) | Write |
| MV 2002 | run_status | System mode (cooling, heating, economize, shutdown...) | Read |
| BV 2008 | occ_status | Current occupancy status | Read |
| AV 2035 | ctrl_temp | Controlling temperature | Read |
| AV 1008 | sa_temp | Supply air temperature | Read |
| BV 1003 | sfan_status | Supply fan status | Read |
| BV 7013 | comp_alarm | Compressor status alarm | Read |
Enable & remote start
BAS On/Off (MV 1001) sets occupancy from the network: state 1 (default, Inactive) follows the schedule, 2 forces occupied, 3 forces unoccupied. Forcing occupied or unoccupied disables Optimal Start. For BAS scheduling through BAS On/Off, the local Occupancy Schedules must be set to Disable.
Sensors & values from the BMS
The controller can take space temperature, setpoint adjustment, RH, CO2, outdoor air temperature, demand level and occupancy from the network (System Space Temperature AV 1902, System Setpoint Adjustment AV 1913, System Supply Air Temperature AV 1906 and the System network points). A BACnet network occupancy input can also be configured, but local occupancy schedules must be disabled to use it.
Network setup
- MAC address is set with the Tens and Ones rotary switches on the UC Open XP.
- DIP switches 1-2 set the MS/TP baud rate (9600 to 76.8 kbps); 3-4 select MS/TP or ARC156.
- The controller accepts three demand limit levels from the network, widening heating and cooling setpoints.
Watch out for
- Scheduling should come from one source only; an i-Vu download overwrites a local schedule set from an Equipment Touch or Field Assistant.
- Most VAV points (static pressure, SAT reset) only matter on VAV configurations; single-zone units control to space temperature.
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 2608 | link_sat | Air Source Supply Air Temp | °F | Read | |
| BV | 7030 | air_linkage_fail | Airside Linkage | Read | ||
| BV | 2601 | a_link_status | Airside Linkage | Read | ||
| AV | 2702 | link_hwt | Auxiliary Heat Boiler Water Temp | °F | Read | |
| AV | 3014 | aux_heat_stpt | Auxiliary Heat Control Setpoint | °F | Read | |
| AV | 2021 | aux_heat_output | Auxiliary Heat Output | % | Read | |
| BV | 2703 | hw_pump | Auxilary Heat HW Pump Status | Read | ||
| BV | 81004 | aux_heat_test | Auxilary Heat Test | Write | ||
| BV | 7024 | co2_fail | CO2 Sensor Failure | Read | ||
| BV | 7026 | comp1_fail | Compressor 1 Failure | Read | ||
| AV | 2100 | comp1_rntm | Compressor 1 Runtime | hr | Read | |
| BV | 7014 | comp1_rntm_alarm | Compressor 1 Runtime Alarm | Read | ||
| AV | 83106 | comp1_service_hrs | Compressor 1 Service Alarm Timer | hr | Write | |
| BV | 7152 | comp1_status | Compressor 1 Status | Read | ||
| BV | 7028 | comp2_fail | Compressor 2 Failure | Read | ||
| AV | 2101 | comp2_rntm | Compressor 2 Runtime | hr | Read | |
| BV | 7015 | comp2_rntm_alarm | Compressor 2 Runtime Alarm | Read | ||
| AV | 83107 | comp2_service_hrs | Compressor 2 Service Alarm Timer | hr | Write | |
| BV | 7153 | comp2_status | Compressor 2 Status | Read | ||
| BV | 7032 | comp3_fail | Compressor 3 Failure | Read | ||
| AV | 2102 | comp3_rntm | Compressor 3 Runtime | hr | Read | |
| BV | 7016 | comp3_rntm_alarm | Compressor 3 Runtime Alarm | Read | ||
| AV | 83108 | comp3_service_hrs | Compressor 3 Service Alarm Timer | hr | Write | |
| BV | 7156 | comp3_status | Compressor 3 Status | Read | ||
| BV | 7033 | comp4_fail | Compressor 4 Failure | Read | ||
| AV | 2103 | comp4_rntm | Compressor 4 Runtime | hr | Read | |
| BV | 7017 | comp4_rntm_alarm | Compressor 4 Runtime Alarm | Read | ||
| AV | 83109 | comp4_service_hrs | Compressor 4 Service Alarm Timer | hr | Write | |
| BV | 7159 | comp4_status | Compressor 4 Status | Read | ||
| AV | 5001 | comp_cap | Compressor Capacity | % | Read | |
| BVmin | 7013 | comp_alarm | Compressor Status Alarm | Read | ||
| BV | 81002 | comp_test | Compressor Test | Write | ||
| BV | 7027 | cwt_alarm | Cond. Water Temperature | Read | ||
| BV | 7025 | cwv_fail | Condenser Valve Failure | Read | ||
| BV | 7067 | ctrl_temp_fail | Control Temp Sensor Failure | Read | ||
| AVmin | 2035 | ctrl_temp | Controlling Temperature | °F | Read | |
| BV | 1011 | cl_enable | Cool Enable | Write | ||
| AV | 9002 | oat_cl_lockout | Cooling Lockout Temperature | °F | Write | |
| AV | 3031 | sa_static_stpt_value | Current Static Pressure Setpoint | in H2O | Read | |
| BV | 99009 | cw_dp_enable | CW Differential Pressure Switch | Write | ||
| BV | 7089 | dp_switch | CW Flow Switch | Read | ||
| BV | 7090 | cw_status | CW Valve Status | Read | ||
| AV | 2022 | oa_dpr_pos | Damper Output | % | Read | |
| BV | 2006 | dehum | Dehumidification | Read | ||
| BV | 81005 | econ_test | Economizer Test | Write | ||
| AV | 3005 | eff_cl_stpt | Effective Cool Setpoint | °F | Read | |
| AV | 3006 | eff_ht_stpt | Effective Heat Setpoint | °F | Read | |
| AV | 2033 | eff_sat_setpt_value | Effective Supply Air Temp Setpoint | °F | Read | |
| BV | 91000 | fac_test_enable | Factory Test | Write | ||
| AV | 9024 | fan_delay_off | Fan Off Delay | seconds | Write | |
| AV | 9025 | fan_delay_on | Fan On Delay | seconds | Write | |
| BV | 81001 | fan_test | Fan Test | Write | ||
| BV | 7019 | filter_alarm | Filter | Read | ||
| AV | 2015 | filter_rntm | Filter Runtime | hr | Read | |
| AV | 2019 | filter_service_hrs | Filter Service Alarm Timer | hr | Write | |
| BV | 1005 | filter_status | Filter Status Input | Read | ||
| BV | 7007 | fire_alarm | Fire / Smoke Shutdown | Read | ||
| BV | 99002 | rh_enable | Hardwired Humidity Sensor | Write | ||
| BV | 1012 | ht_enable | Heat Enable | Write | ||
| AV | 9003 | oat_ht_lockout | Heating Lockout Temperature | °F | Write | |
| AV | 2026 | hgrh_output | HGRH Output | % | Read | |
| BV | 81003 | dehum_test | HGRH Test | Write | ||
| BV | 7060 | sp_hi_alarm | Hi Static Pressure Shutdown | Read | ||
| BV | 7011 | spt_hi_alarm | High Space Temperature | Read | ||
| BV | 99004 | hgrh_enable | Hot Gas Reheat | Write | ||
| BV | 91010 | reheat_type | Hot Water Coil | Write | ||
| BV | 7005 | iaq_alarm | Indoor Air Quality | Read | ||
| AV | 1009 | iaq | Indoor Air Quality CO2 | ppm | Read | |
| AV | 1017 | cwl_temp | Leaving Cond. Water Temp | °F | Read | |
| AV | 2024 | loop_request | Loop Pump Request | Read | ||
| BV | 2702 | loop_pump | Loop Pump Status | Read | ||
| BV | 7012 | spt_lo_alarm | Low Space Temperature | Read | ||
| BV | 7062 | sp_low_alarm | Low Static Pressure Shutdown | Read | ||
| AV | 3026 | max_vfd_spd | Maximum VFD Output | % | Write | |
| AV | 83004 | sat_ht_max | Maximum Heating SAT | °F | Write | |
| AV | 3027 | min_vfd_spd | Minimum VFD Output | % | Write | |
| AV | 83003 | sat_cl_min | Minimum Cooling SAT | °F | Write | |
| BVmin | 2008 | occ_status | Occupancy Status | Read | ||
| BV | 2031 | occ_heat | Occupied Heating | Write | ||
| AV | 9028 | occ_ovr_delay | Occupied Override Delay | min | Write | |
| AV | 3011 | occ_dehum_stpt | Occupied Relative Humidity Setpoint | %rh | Write | |
| BV | 81007 | dpr_open | Open Vent Damper 100% | Write | ||
| AV | 9026 | optm_start | Optimal Start | hr | Write | |
| BV | 7029 | oat_fail | Outdoor Air Temp. Sensor Failure | Read | ||
| AV | 1003 | oa_temp | Outdoor Air Temperature | °F | Read | |
| BV | 7006 | ovrld_alarm | Overload Shutdown | Read | ||
| AV | 2016 | ovrde_time | Override Time Remaining | min | Read | |
| AV | 9007 | start_delay | Power Fail Restart Delay | seconds | Write | |
| BV | 81006 | dpr_preload | Preload OA Damper Position | Write | ||
| BV | 7514 | comp1_rntm_clr | Reset Comp 1 Runtime Alarm | Write | ||
| BV | 7515 | comp2_rntm_clr | Reset Comp 2 Runtime Alarm | Write | ||
| BV | 7516 | comp3_rntm_clr | Reset Comp 3 Runtime Alarm | Write | ||
| BV | 7517 | comp4_rntm_clr | Reset Comp 4 Runtime Alarm | Write | ||
| BV | 1908 | lsl_reset | Reset Low Static Shutdown | Write | ||
| AV | 9040 | sat_cl_stpt_reset_max | Reset Maximum Limit | delta °F | Write | |
| AV | 9041 | sat_cl_stpt_reset | Reset Ratio | Write | ||
| BV | 7518 | filter_rntm_clr | Reset Runtime Filter Alarm | Write | ||
| BV | 7021 | loc_rat_sensor_fail | Return Air Temp Sensor Failure | Read | ||
| AV | 1010 | ra_temp | Return Air Temperature | °F | Read | |
| BV | 7035 | rat_alarm | Return Air Temperature | Read | ||
| BV | 99005 | rev_vlv | Reversing Valve | Write | ||
| AVmin | 3001 | occ_cl_stpt | Occupied cooling setpoint | °F | Write | |
| AVmin | 3002 | occ_ht_stpt | Occupied heating setpoint | °F | Write | |
| AV | 3003 | unocc_cl_stpt | Unoccupied cooling setpoint | °F | Write | |
| AV | 3004 | unocc_ht_stpt | Unoccupied heating setpoint | °F | Write | |
| AV | 1006 | stpt_adj | Setpoint Adjustment | delta °F | Read | |
| BV | 1013 | stpt_adj_enable | Setpoint Adjustment | Write | ||
| AV | 9015 | stpt_adj_range | Setpoint Adjustment Range | delta °F | Write | |
| BV | 81000 | test_enable | Service Test | Write | ||
| BV | 9001 | shutdown | Shutdown | Write | ||
| BV | 1004 | smk_detect | Smoke Detector Input | Read | ||
| BV | 2701 | cw_link_status | Source Water Linkage | Read | ||
| BV | 7031 | cond_water_linkage_fail | Source Water Linkage | Read | ||
| AV | 69 | lo_sp_limit | SP Low Limit Trip Setpoint (Shutdown) | in H2O | Write | |
| AV | 1011 | space_rh | Space Relative Humidity | %rh | Read | |
| BV | 7018 | sprh_hi_alarm | Space Relative Humidity | Read | ||
| AV | 2007 | space_temp | Space Temperature | °F | Read | |
| AV | 2028 | static_press | Static Pressure | in H2O | Read | |
| BV | 7061 | sp_fail | Static Pressure Sensor Failure | Read | ||
| AV | 3030 | sa_static_stpt | Static Pressure Setpoint | in H2O | Write | |
| AVmin | 3029 | sat_cl_stpt | Supply Air Setpoint | °F | Write | |
| BV | 9004 | sa_reset_en | Supply Air Temp Reset | Write | ||
| BV | 7020 | sat_sensor_fail | Supply Air Temp. Sensor Failure | Read | ||
| AVmin | 1008 | sa_temp | Supply Air Temperature | °F | Read | |
| BV | 7004 | sat_alarm | Supply Air Temperature | Read | ||
| BV | 7008 | sfan_fail_alarm | Supply Fan Failure | Read | ||
| BVmin | 1003 | sfan_status | Supply Fan Status | Read | ||
| AV | 2027 | vfd_output | Supply Fan VFD Output | % | Read | |
| AV | 9006 | cool_demand_level | System Cooling Demand Level | Read | ||
| AV | 9036 | heat_demand_level | System Heating Demand Level | Read | ||
| AV | 1901 | system_oat | System Outdoor Air Temperature | °F | Write | |
| AV | 1920 | system_rat | System Return Air Temperature | °F | Write | |
| AV | 1913 | system_stpt_adj | System Setpoint Adjustment | °F | Write | |
| AV | 1903 | system_iaq | System Space IAQ | ppm | Write | |
| AV | 1904 | system_rh | System Space RH | % | Write | |
| AV | 1902 | system_spt | System Space Temperature | °F | Write | |
| AV | 1906 | system_sat | System Supply Air Temperature | °F | Write | |
| AV | 92001 | ao_one | Test AO-1 | % | Write | |
| AV | 92002 | ao_two | Test AO-2 | % | Write | |
| AV | 92003 | ao_three | Test AO-3 | % | Write | |
| BV | 91001 | do_one | Test DO-1 | Write | ||
| BV | 91002 | do_two | Test DO-2 | Write | ||
| BV | 91003 | do_three | Test DO-3 | Write | ||
| BV | 91004 | do_four | Test DO-4 | Write | ||
| BV | 91005 | do_five | Test DO-5 | Write | ||
| BV | 91006 | do_six | Test DO-6 | Write | ||
| AV | 92004 | ao_one_three | Test Expander 1 AO-3 | % | Write | |
| BV | 91007 | do_one_one | Test Expander 1 DO-1 | Write | ||
| BV | 91008 | do_one_two | Test Expander 1 DO-2 | Write | ||
| BV | 7022 | upm1_alm | Unit Protection Module 1 Alarm | Read | ||
| BV | 7023 | upm2_alm | Unit Protection Module 2 Alarm | Read | ||
| BV | 99001 | unit_type | Unit Type | Write | ||
| AV | 3012 | unocc_dehum_stpt | Unoccupied Relative Humidity Setpoint | %rh | Write | |
| AV | 4005 | econ_min | Vent Damper Pos / DCV Min Pos | % | Write | |
| AV | 3015 | h2o_econ_ctrl_stpt | Water Economizer Control Setpoint | °F | Read | |
| AV | 2023 | h2o_econ_output | Water Economizer Output | % | Read | |
| AV | 2701 | link_cwt | Water Loop Temp | °F | Read | |
| BV | 7055 | zs_config_fail | ZS Sensor Configuration | Read | ||
| BV | 7051 | zst_sensor_fail | ZS Temperature Sensor Failure | Read | ||
| MV | 2005 | link_ahu_mode | Air Source Mode | Read | 1=OFF, 2=WARMUP, 3=HEAT, 4=COOLING, 5=FREECOOL, 6=PRESSURE, 7=EVAC, 8=VENT | |
| MVmin | 1001 | keypad_ovrde | BAS On / Off | Write | 1=Inactive, 2=Occupied, 3=Unoccupied | |
| MV | 2013 | ctrl_temp_src | Control Temp Source | Read | 1=Sensor Failure, 2=Space, 3=Return Air, 4=Linkage Zone, 5=Locked Value | |
| MV | 91001 | h2o_econ_type | Entering Air Water Economizer | Write | 1=None, 2=2-Pos | |
| MV | 2009 | start_type | Optimal Start Type | Write | 1=None, 2=Temp Compensated, 3=Learning Adaptive | |
| MV | 9033 | sp_reset_dmd_lvl | SP Reset Demand Level | Write | 1=Not Active, 2=Cool Dmd Lvl 1, 3=Cool Dmd Lvl 2, 4=Cool Dmd Lvl 3 | |
| MV | 2004 | fan_run | Supply Fan Speed | Read | 1=Off, 2=Low, 3=Medium, 4=High, 5=On | |
| MVmin | 2002 | run_status | System Mode | Read | 1=OFF, 2=Fan Only, 3=Economize, 4=Cooling, 5=Heating, 6=Cont Fan, 7=Test, 8=Start Delay, 9=Dehumidify, 10=Fire Shutdown, 11=Shutdown, 12=IAQ Override | |
| MV | 91002 | dpr_type | Ventilation Damper Type | Write | 1=None, 2=2-Pos, 3=DCV |
No points match these filters.
Object ID lookup: Carrier 50BV SCU Open point IDs by name
AV2608link_satBV7030air_linkage_failBV2601a_link_statusAV2702link_hwtAV3014aux_heat_stptAV2021aux_heat_outputBV2703hw_pumpBV81004aux_heat_testBV7024co2_failBV7026comp1_failAV2100comp1_rntmBV7014comp1_rntm_alarmAV83106comp1_service_hrsBV7152comp1_statusBV7028comp2_failAV2101comp2_rntmBV7015comp2_rntm_alarmAV83107comp2_service_hrsBV7153comp2_statusBV7032comp3_failAV2102comp3_rntmBV7016comp3_rntm_alarmAV83108comp3_service_hrsBV7156comp3_statusBV7033comp4_failAV2103comp4_rntmBV7017comp4_rntm_alarmAV83109comp4_service_hrsBV7159comp4_statusAV5001comp_capBV7013comp_alarmBV81002comp_testBV7027cwt_alarmBV7025cwv_failBV7067ctrl_temp_failAV2035ctrl_tempBV1011cl_enableAV9002oat_cl_lockoutAV3031sa_static_stpt_valueBV99009cw_dp_enableBV7089dp_switchBV7090cw_statusAV2022oa_dpr_posBV2006dehumBV81005econ_testAV3005eff_cl_stptAV3006eff_ht_stptAV2033eff_sat_setpt_valueBV91000fac_test_enableAV9024fan_delay_offAV9025fan_delay_onBV81001fan_testBV7019filter_alarmAV2015filter_rntmAV2019filter_service_hrsBV1005filter_statusBV7007fire_alarmBV99002rh_enableBV1012ht_enableAV9003oat_ht_lockoutAV2026hgrh_outputBV81003dehum_testBV7060sp_hi_alarmBV7011spt_hi_alarmBV99004hgrh_enableBV91010reheat_typeBV7005iaq_alarmAV1009iaqAV1017cwl_tempAV2024loop_requestBV2702loop_pumpBV7012spt_lo_alarmBV7062sp_low_alarmAV3026max_vfd_spdAV83004sat_ht_maxAV3027min_vfd_spdAV83003sat_cl_minBV2008occ_statusBV2031occ_heatAV9028occ_ovr_delayAV3011occ_dehum_stptBV81007dpr_openAV9026optm_startBV7029oat_failAV1003oa_tempBV7006ovrld_alarmAV2016ovrde_timeAV9007start_delayBV81006dpr_preloadBV7514comp1_rntm_clrBV7515comp2_rntm_clrBV7516comp3_rntm_clrBV7517comp4_rntm_clrBV1908lsl_resetAV9040sat_cl_stpt_reset_maxAV9041sat_cl_stpt_resetBV7518filter_rntm_clrBV7021loc_rat_sensor_failAV1010ra_tempBV7035rat_alarmBV99005rev_vlvAV3001occ_cl_stptAV3002occ_ht_stptAV3003unocc_cl_stptAV3004unocc_ht_stptAV1006stpt_adjBV1013stpt_adj_enableAV9015stpt_adj_rangeBV81000test_enableBV9001shutdownBV1004smk_detectBV2701cw_link_statusBV7031cond_water_linkage_failAV69lo_sp_limitAV1011space_rhBV7018sprh_hi_alarmAV2007space_tempAV2028static_pressBV7061sp_failAV3030sa_static_stptAV3029sat_cl_stptBV9004sa_reset_enBV7020sat_sensor_failAV1008sa_tempBV7004sat_alarmBV7008sfan_fail_alarmBV1003sfan_statusAV2027vfd_outputAV9006cool_demand_levelAV9036heat_demand_levelAV1901system_oatAV1920system_ratAV1913system_stpt_adjAV1903system_iaqAV1904system_rhAV1902system_sptAV1906system_satAV92001ao_oneAV92002ao_twoAV92003ao_threeBV91001do_oneBV91002do_twoBV91003do_threeBV91004do_fourBV91005do_fiveBV91006do_sixAV92004ao_one_threeBV91007do_one_oneBV91008do_one_twoBV7022upm1_almBV7023upm2_almBV99001unit_typeAV3012unocc_dehum_stptAV4005econ_minAV3015h2o_econ_ctrl_stptAV2023h2o_econ_outputAV2701link_cwtBV7055zs_config_failBV7051zst_sensor_failMV2005link_ahu_modeMV1001keypad_ovrdeMV2013ctrl_temp_srcMV91001h2o_econ_typeMV2009start_typeMV9033sp_reset_dmd_lvlMV2004fan_runMV2002run_statusMV91002dpr_type
Integration notes
- Object IDs are printed as AV:3001 style references; access is from the Point Access column (R/W listed as writable).
- The four occupied/unoccupied heating and cooling setpoints (AV 3001-3004) are printed only as "Setpoint" in the name column; their descriptions here come from the BACnet point names.
- Water economizer, hot gas reheat, auxiliary heat, humidity and CO2 points only apply when those options are installed and enabled.
- ARC156 is a Carrier-specific 156 kbps network; third-party systems connect over BACnet MS/TP.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
How many BACnet points does the Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP) have?
This list has 168 BACnet objects: 74 analog values, 85 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP) BACnet points are writable?
80 of the 168 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP) BACnet documentation?
The source is 50BVT, 50BVV, 50BVQ 024-034, 50VQP 210-360 (Cooling Only), and 50BVW with SCU Open Controller - Controls, Start-Up, Operation and Troubleshooting (Appendix B, BACnet Points List) (50BV-SCU-3T), revision 2025-07, published free by Carrier at https://brandportal.carrier.com/asset/da433b3f-04c2-4303-b317-269c7e85b240/50BV-SCU-3T.pdf.
What are the minimum BACnet points to integrate the Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)?
Start with MV 1001 keypad_ovrde (BAS occupancy: 1=Inactive (schedule), 2=Occ, 3=Unocc); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); AV 3029 sat_cl_stpt (Supply air setpoint (VAV units)); MV 2002 run_status (System mode (cooling, heating, economize, shutdown...)); BV 2008 occ_status (Current occupancy status); AV 2035 ctrl_temp (Controlling temperature); AV 1008 sa_temp (Supply air temperature); BV 1003 sfan_status (Supply fan status); BV 7013 comp_alarm (Compressor status alarm).
How do I enable BMS control of the Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)?
BAS On/Off (MV 1001) sets occupancy from the network: state 1 (default, Inactive) follows the schedule, 2 forces occupied, 3 forces unoccupied. Forcing occupied or unoccupied disables Optimal Start. For BAS scheduling through BAS On/Off, the local Occupancy Schedules must be set to Disable.
Can the BMS supply sensor values to the Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)?
The controller can take space temperature, setpoint adjustment, RH, CO2, outdoor air temperature, demand level and occupancy from the network (System Space Temperature AV 1902, System Setpoint Adjustment AV 1913, System Supply Air Temperature AV 1906 and the System network points). A BACnet network occupancy input can also be configured, but local occupancy schedules must be disabled to use it.
How do I check these points on the real 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: 50BVT, 50BVV, 50BVQ 024-034, 50VQP 210-360 (Cooling Only), and 50BVW with SCU Open Controller - Controls, Start-Up, Operation and Troubleshooting (Appendix B, BACnet Points List) · 50BV-SCU-3T · rev. 2025-07. Object names, instances and units are reproduced as published; descriptions are our own.