Heat pump plant sequencer (system manager) · BACnet points list

Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet points list

Updated 7 November 2026

Short answer

The SMS is a plant controller for up to four modular R-290 air-source heat pumps; it talks to the heat pumps over BACnet IP and offers BACnet IP and Modbus TCP to the BMS through the Ethernet switch in its cabinet. The object list has 315 objects grouped by function: general system commands and status, schedules, two heating/cooling zones, customer and DHW pump sets, the heat pump manager, and one block per heat pump.

This page lists 315 BACnet objects for the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps — 80 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Equipment
Heat pump plant sequencer (system manager)
Equipment type
Heat pumps
BACnet objects
315 (80 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe
Source document
SMS OPT275A BMS Protocols (BACnet object list SMS_OPT275A_BACNET_COM.xlsx) · EN_SMS_OPT275A_BMS_Protocols
Download CSV 315 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps

Integration in brief

Connect the BMS to the Ethernet switch in the SMS cabinet. Put the system in Auto operating type with the front button, then drive it with the On/Off input command (MV 502) and the heating/cooling selection (MV 521), adjust zone setpoints, and read system status, temperatures, heat pump status and the synthesis alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 502on_off_command_5On/off command: 1=Off, 2=On, 3=Based on scheduleWrite
MV 521manual_hc_sel_5Heating/cooling selection (3 = auto changeover on OAT)Write
MV 200z1_setpoint_input_2Zone 1 setpoint mode: Eco, Comfort or AutoWrite
AV 226z1_heat_comfort_setpoint_2Zone 1 comfort heating water setpointWrite
AV 216z1_cool_comfort_setpoint_2Zone 1 comfort cooling water setpointWrite
BV 505emergency_shutdown_5Emergency shutdown signal from the BMSWrite
AV 501manager_control_mode_5Front panel button: 1=Off, 2=On, 3=AutoRead
AV 1032lwt_evap_temp_1Common leaving water temperatureRead
MV 1052ch1_status_1Heat pump 1 status (running, failure, no comm...)Read
BV 548alarm_synthesis_5General (synthesis) alarmRead

Enable & remote start

The system follows the On/Off input command only in the Auto operating type selected with the SMS front button (AV 501 reports it). In Auto the command can be Off, On or Based on Schedule. The network emergency stop shuts the system down in any operating type.

Sensors & values from the BMS

Zone relative humidity for dew point calculation (AV 264) can be written by the BMS when floor sensors are used.

Network setup

Watch out for

Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

315 of 315 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet Points List
DescriptionStates
AVmin501manager_control_mode_5General: Front SMS panel button statusRead1=OFF, 2=ON, 3=AUTO
AV526oat_5General: Average Outside Air Temperature°CRead
AV542dhw_threshold_5General: Disabling DHW threshold: Disable DHW if DHW tank temperature is above this threshold (need DHW...°CRead
MV522production_mode_5General: Current SMS production modeRead1=Heat pumps production to buffer tank, 2=Heat pumps production to buffer tank and Heat pump n°1 production to DHW, 3=Heat pumps production to DHW, 4=Boiler production to buffer tank, 5=Boiler production to DHW, 6=Boiler production to DHW and heat pumps production to buffer tank
MV551hmi_display_smart_grid_5General: Smart Grid statusRead1=Lock, 2=Normal, 3=Forced, 4=Boost
BV516diverting_valve_command_5General: Command position for the diverting valveRead0=to Buffer tank, 1=to DHW
BV517dv_open_fail_5Alarm: Diverting valve opening alarmRead
BV519dv_close_fail_5Alarm: Diverting valve closing alarmRead
BV521dhw_cmd_5General: Domestic Hot Water mode runningRead
BV522dhw_heater_cmd_5General: DHW Heater commandRead
BV523legionella_cmd_5General: Legionella Prevention mode runningRead
BV524boiler_cmd_5General: Boiler commandRead
BV525bac_ehs_level_1_5General: Start command Electric Heat Stage (EHS) n°1Read
BV526bac_ehs_level_2_5General: Start command Electric Heat Stage (EHS) n°2Read
BV527bac_ehs_level_3_5General: Start command Electric Heat Stage (EHS) n°3Read
BV529hc_sel_5Current heating/cooling modeRead0=Cooling, 1=Heating
BV533m2033_5Alarm: Leaving Water Temperature sensor failure (common heat pumps outlet)Read
BV534m2091_5Alert: Entering Water Temperature sensor failure (common heat pumps intlet)Read
BV538standby_mode_5General: Stand-by mode for automatic changeover based on Outside Air Temperature (no heating, no cooling)Read
BV547alert_synthesis_5General: Synthesis alert feedbackRead
BVmin548alarm_synthesis_5General: Synthesis alarm feedbackRead
BV728hoa_alarm_7Alert: At least one output switch is not set to "Auto" on the hardware C2Read
BV6020hoa_alarm_6Alert: At least one output switch is not set to "Auto" on the hardware C1Read
AV503dhw_sp_5General: Enabling DHW threshold°CWrite
AV504m3244_5General: Disabling DHW hysteresis: Disable DHW if DHW tank temperature is above DHW enabling threshold +...Write
AV505legionella_sp_5General: Disabling Legionella Prevention threshold°CWrite
AV507m3273_5General: Disabling Legionella Prevention delayminWrite
AV510oat_hyst_boiler_5General: Hysteresis on Outside Air Temperature threshold to disable boiler usage°CWrite
AV511oat_boiler_5General: Outside Air Temperature threshold to enable boiler usage instead of heat pumps°CWrite
AV522heat_oat_threshold_5General: Threshold for automatic changeover based on Outside Air Temperature (from cooling mode to heating...°CWrite
AV523cool_oat_threshold_5General: Threshold for automatic changeover based on Outside Air Temperature (from heating mode to cooling...°CWrite
AV524heat_oat_delay_5General: Delay for automatic changeover based on Outside Air Temperature (from cooling mode to heating mode)hrWrite
AV525cool_oat_delay_5General: Delay for automatic changeover based on Outside Air Temperature (from heating mode to cooling mode)hrWrite
AV540dhw_setpoint_conf_5General: Domestic Hot Water setpoint configuration°CWrite
AV541legionella_setpoint_conf_5General: Legionella Prevention setpoint configuration°CWrite
MVmin502on_off_command_5General: On/Off SMS input commandWrite1=OFF, 2=ON, 3=Based on Schedule
MVmin521manual_hc_sel_5General: Heating/Cooling selectionWrite1=Cooling mode, 2=Heating mode, 3=Automatic changeover based on Outside Air Temperature
BV503general_ack_5General: SMS events acknowledgementWrite
BV504refrigerant_shutdown_5General: Refrigerant leak shutdown signal from BMS (will stop the SMS)Write
BVmin505emergency_shutdown_5General: Emergency shutdown signal from BMS (will stop the SMS)Write
BV558bms_start_dhw_5General: DHW enable command (schedule bypass)Write
MV2401schedule_state_z1_24Schedule: Comfort No Zone or Zone n°1 schedule stateRead1=Eco, 2=Comfort, 3=Away
MV2501schedule_state_z2_25Schedule: Comfort Zone n°2 schedule stateRead1=Eco, 2=Comfort, 3=Away
BV21044schedule_state_21Schedule: Heat Pumps On/Off schedule stateRead0=Inactive, 1=Active
BV2200mode_holiday_22Schedule: Holiday schedule stateRead0=Inactive, 1=Active
BV26044schedule_state_night_26Schedule: Night mode schedule stateRead0=Inactive, 1=Active
BV27044schedule_state_dhw_27Schedule: DHW schedule stateRead0=Inactive, 1=Active
BV2816schedule_state_legion_27Schedule: Legionalla Prevention schedule stateRead0=Inactive, 1=Active
AV268runtime_p1_2Zone n°1: Runtime pumphrRead
AV269runtime_p2_2Zone n°2: Runtime pumphrRead
AV270command_3wv_1_2Zone n°1: 3-way mixing valve command%Read
AV271command_3wv_2_2Zone n°2: 3-way mixing valve command%Read
AV272bac_dew_point_2Zone: Dew point temperature (floor sensor)°CRead
AV274z1_setpoint_2Zone n°1 or No Zone: Effective setpoint°CRead
AV276z2_setpoint_2Zone n°2: Effective setpoint°CRead
BV222enable1_2Zone n°1: Command pumpRead
BV223status1_2Zone n°1: Running status pumpRead
BV226enable2_2Zone n°2: Command pumpRead
BV227status2_2Zone n°2: Running status pumpRead
BV233p1_fail_2Alarm: Fail to start pump Zone n°1 in the allowable timeRead
BV234p1_hand_2Alert: Pump Zone n°1 is running due to an external commandRead
BV235p2_fail_2Alarm: Fail to start pump Zone n°2 in the allowable timeRead
BV236p2_hand_2Alert: Pump Zone n°2 is running due to an external commandRead
BV237floor_sensor_fault_2Alarm: Floor temperature out of allowable range (will stop the pump)Read
AVmin216z1_cool_comfort_setpoint_2Zone n°1 or No Zone: Static "Comfort" setpoint / Cooling mode°CWrite
AV217z1_cool_eco_setpoint_2Zone n°1 or No Zone: Static "Eco" setpoint / Cooling mode°CWrite
AV218z1_cool_away_setpoint_2Zone n°1 or No Zone: Static "Away" setpoint / Cooling mode°CWrite
AVmin226z1_heat_comfort_setpoint_2Zone n°1 or No Zone: Static "Comfort" setpoint / Heating mode°CWrite
AV227z1_heat_eco_setpoint_2Zone n°1 or No Zone: Static "Eco" setpoint / Heating mode°CWrite
AV228z1_heat_away_setpoint_2Zone n°1 or No Zone: Static "Away" setpoint / Heating mode°CWrite
AV235z2_cool_comfort_setpoint_2Zone n°2: Static "Comfort" setpoint / Cooling mode°CWrite
AV236z2_cool_eco_setpoint_2Zone n°2: Static "Eco" setpoint / Cooling mode°CWrite
AV237z2_cool_away_setpoint_2Zone n°2: Static "Away" setpoint / Cooling mode°CWrite
AV244z2_heat_comfort_setpoint_2Zone n°2: Static "Comfort" setpoint / Heating mode°CWrite
AV245z2_heat_eco_setpoint_2Zone n°2: Static "Eco" setpoint / Heating mode°CWrite
AV246z2_heat_away_setpoint_2Zone n°2: Static "Away" setpoint / Heating mode°CWrite
AV257v1_manual_value_2Zone n°1: 3-way mixing valve position command in manual forcing%Write
AV263v2_manual_value_2Zone n°2: 3-way mixing valve position command in manual forcing%Write
AV264bac_rh_2Zone: Relative humidity for dew point calculation (floor sensor)%Write
AV266bac_high_temp_threshold_2Zone: High temperature threshold for floor temperature alarm (floor sensor)°CWrite
AV267bac_dew_point_hysteresis_2Zone: Hysteresis above dew point for low floor temperature alarm (floor sensor)°CWrite
MVmin200z1_setpoint_input_2Zone n°1 or No Zone: Setpoint modeWrite1=Eco, 2=Comfort, 3=Auto
MV205z2_setpoint_input_2Zone n°2: Setpoint modeWrite1=Eco, 2=Comfort, 3=Auto
MV247p1_manual_2Zone n°1: Pump Manual/AutoWrite1=Manual On, 2=Manual Off, 3=Automatic
MV248p2_manual_2Zone n°2: Pump Manual/AutoWrite1=Manual On, 2=Manual Off, 3=Automatic
BV200z1_ctrlpnt_method_2Zone n°1 or No Zone: Setpoint selection typeWrite0=Climatic curve, 1=Static setpoint
BV205z2_ctrlpnt_method_2Zone n°2: Setpoint selection typeWrite0=Climatic curve, 1=Static setpoint
BV211main1_2Zone n°1: Maintenance mode pump (stop the pump if active)Write
BV212main2_2Zone n°2: Maintenance mode pump (stop the pump if active)Write
BV217v1_manual_2Zone n°1: 3-way mixing valve Manual/AutoWrite0=Automatic, 1=Manual position
BV219v2_manual_2Zone n°2: 3-way mixing valve Manual/AutoWrite0=Automatic, 1=Manual position
AV332vfd_status1_3Customer pumps: VFD command%Read
AV334runtime_p1_3Customer pumps: Runtime pump n°1hrRead
AV335runtime_p2_3Customer pumps: Runtime pump n°2hrRead
AV336diff_press_3Customer pumps: Differential pressure valuekPaRead
BV308enable1_3Customer pumps: Command pump n°1Read
BV309enable2_3Customer pumps: Command pump n°2Read
BV310status1_3Customer pumps: Running status pump n°1Read
BV311status2_3Customer pumps: Running status pump n°2Read
BV317press_hi_3Alert: Customer pump: Pressure difference too high from setpointRead
BV318press_lo_3Alert: Customer pump: Pressure difference too low from setpointRead
BV319p1_fail_3Alarm: Fail to start Customer pump n°1 in the allowable timeRead
BV320p1_hand_3Alert: Customer pump n°1 is running due to an external commandRead
BV321p2_fail_3Alarm: Fail to start Customer pump n°2 in the allowable timeRead
BV322p2_hand_3Alert: Customer pump n°2 is running due to an external commandRead
AV302vfd1_manual_3Customer pumps: VFD command in manual forcing%Write
AV305pumps_rotation_type_selector_3Customer pumps: Rotation method selectionWrite0=Lowest Runtime, 1=Fixed Order
AV306man_order_p1_3Customer pumps: Order of pump 1 if rotation type is set to Fixed OrderWrite
AV307man_order_p2_3Customer pumps: Order of pump 2 if rotation type is set to Fixed OrderWrite
AV317dpstpt_3Customer pumps: Differential pressure setpointkPaWrite
MV301p_manual_3Customer pumps: Manual/AutoWrite1=Pump n°1 Manual On, 2=Pump n°2 Manual On, 3=Manual Off, 4=Automatic
BV300main1_3Customer pumps: Maintenance mode pump n°1 (stop the pump if active)Write
BV301main2_3Customer pumps: Maintenance mode pump n°2 (stop the pump if active)Write
AV433vfd_status1_4DHW pumps: VFD command%Read
AV435runtime_p1_4DHW pumps: Runtime pump n°1hrRead
AV436runtime_p2_4DHW pumps: Runtime pump n°2hrRead
AV437diff_press_4DHW pumps: Differential pressure valuekPaRead
BV408enable1_4DHW pumps: Command pump n°1Read
BV409enable2_4DHW pumps: Command pump n°2Read
BV410status1_4DHW pumps: Running status pump n°1Read
BV411status2_4DHW pumps: Running status pump n°2Read
BV417press_hi_4Alert: DHW pump: Pressure difference too high from setpointRead
BV418press_lo_4Alert: DHW pump: Pressure difference too low from setpointRead
BV419p1_fail_4Alarm: Fail to start DHW pump n°1 in the allowable timeRead
BV420p1_hand_4Alert: DHW pump n°1 is running due to an external commandRead
BV421p2_fail_4Alarm: Fail to start DHW pump n°2 in the allowable timeRead
BV422p2_hand_4Alert: DHW pump n°2 is running due to an external commandRead
AV402vfd1_manual_4DHW pumps: VFD command in manual forcing%Write
AV405pumps_rotation_type_selector_4DHW pumps: Rotation method selectionWrite0=Lowest Runtime, 1=Fixed Order
AV406man_order_p1_4DHW pumps: Order of pump 1 if rotation type is set to Fixed OrderWrite
AV407man_order_p2_4DHW pumps: Order of pump 2 if rotation type is set to Fixed OrderWrite
AV418dpstpt_4DHW pumps: Differential pressure setpointkPaWrite
MV401p_manual_4DHW pumps: Manual/AutoWrite1=Pump n°1 Manual On, 2=Pump n°2 Manual On, 3=Manual Off, 4=Automatic
BV400main1_4DHW pumps: Maintenance mode pump n°1 (stop the pump if active)Write
BV401main2_4DHW pumps: Maintenance mode pump n°2 (stop the pump if active)Write
AV1029nb_run_chillers_1Heat Pumps: Number of running heat pumpsRead
AV1030eff_chlr_chws_temp_stpt_value_1Heat Pumps: Effective cascade setpoint (heat pumps staging at Leaving Water Temperature sensor)°CRead
AV1031nb_avail_chillers_1Heat Pumps: Number of available heat pumpsRead
AVmin1032lwt_evap_temp_1Heat Pumps: Leaving Water Temperature (common heat pumps outlet) / Regulation sensor for staging°CRead
AV1033ewt_evap_temp_1Heat Pumps: Entering Water Temperature (common heat pump inlet)°CRead
AV1035time_before_acr_1Heat Pumps: Remaining time before staging up (start another heat pump)minRead
AV1036time_before_rcr_1Heat Pumps: Remaining time before staging down (stop a heat pump)minRead
AV1042next_chill_start_1Heat Pumps: Next heat pump to start when a stage up occursRead
AV1043next_chill_stop_1Heat Pumps: Next heat pump to stop when a stage down occursRead
AV1066average_plant_capacity_1Heat Pumps: Average plant capacity%Read
MV1007ch1_manual_1Heat Pumps: Heat pump n°1 Manual/AutoRead1=Manual On, 2=Manual Off, 3=Automatic
MV1008ch2_manual_1Heat Pumps: Heat pump n°2 Manual/AutoRead1=Manual On, 2=Manual Off, 3=Automatic
MV1009ch3_manual_1Heat Pumps: Heat pump n°3 Manual/AutoRead1=Manual On, 2=Manual Off, 3=Automatic
MV1010ch4_manual_1Heat Pumps: Heat pump n°4 Manual/AutoRead1=Manual On, 2=Manual Off, 3=Automatic
MVmin1052ch1_status_1Heat Pumps: Heat pump n°1 statusRead1=Not configured, 2=In maintenance mode, 3=In manual mode, 4=BACnet OFF, 5=No communication, 6=Full failure, 7=Partial failure & OFF, 8=Partial failure & running, 9=Running, 10=Ready
MV1053ch2_status_1Heat Pumps: Heat pump n°2 statusRead1=Not configured, 2=In maintenance mode, 3=In manual mode, 4=BACnet OFF, 5=No communication, 6=Full failure, 7=Partial failure & OFF, 8=Partial failure & running, 9=Running, 10=Ready
MV1054ch3_status_1Heat Pumps: Heat pump n°3 statusRead1=Not configured, 2=In maintenance mode, 3=In manual mode, 4=BACnet OFF, 5=No communication, 6=Full failure, 7=Partial failure & OFF, 8=Partial failure & running, 9=Running, 10=Ready
MV1055ch4_status_1Heat Pumps: Heat pump n°4 statusRead1=Not configured, 2=In maintenance mode, 3=In manual mode, 4=BACnet OFF, 5=No communication, 6=Full failure, 7=Partial failure & OFF, 8=Partial failure & running, 9=Running, 10=Ready
BV137acr_1_1Heat Pumps: Staging up condition n°1 is valid (Temperature drift and evolution)Read
BV139rcr_1_1Heat Pumps: Staging down condition n°1.1 is valid (Temperature in the allowable range)Read
BV140acr_2_1Heat Pumps: Staging up condition n°2 is valid (Heat pumps capacity)Read
BV141rcr_2_1Heat Pumps: Staging down condition n°1.2 is valid (Heat pumps average capacity below threshold)Read
BV143acr_3_1Heat Pumps: Staging up condition n°3 is valid (Critical Temperature drift)Read
BV144acr_active_1Heat Pumps: Staging up coming (waiting for end of delay)Read
BV145rcr_active_1Heat Pumps: Staging down coming (waiting for end of delay)Read
BV154communication_ch1_1Heat Pumps: Heat pump n°1 communication statusRead0=Inactive, 1=Active
BV155communication_ch2_1Heat Pumps: Heat pump n°2 communication statusRead0=Inactive, 1=Active
BV156communication_ch3_1Heat Pumps: Heat pump n°3 communication statusRead0=Inactive, 1=Active
BV157communication_ch4_1Heat Pumps: Heat pump n°4 communication statusRead0=Inactive, 1=Active
BV162ch1_is_running_1Heat Pumps: Heat pump n°1 running feedbackRead
BV163command_ch1_1Heat Pumps: Heat pump n°1 running commandRead
BV164ch2_is_running_1Heat Pumps: Heat pump n°2 running feedbackRead
BV165command_ch2_1Heat Pumps: Heat pump n°2 running commandRead
BV166ch3_is_running_1Heat Pumps: Heat pump n°3 running feedbackRead
BV167command_ch3_1Heat Pumps: Heat pump n°3 running commandRead
BV168ch4_is_running_1Heat Pumps: Heat pump n°4 running feedbackRead
BV169command_ch4_1Heat Pumps: Heat pump n°4 running commandRead
BV185acr_cap_exc_1Information: The capacity has reached the maximum available capacityRead
BV187ch1_fail_1Alarm: Fail to start heat pump n°1 in the allowable timeRead
BV188ch1_hand_1Alert: Heat pump n°1 is running due to an external commandRead
BV189ch2_fail_1Alarm: Fail to start heat pump n°2 in the allowable timeRead
BV190ch2_hand_1Alert: Heat pump n°2 is running due to an external commandRead
BV191ch3_fail_1Alarm: Fail to start heat pump n°3 in the allowable timeRead
BV192ch3_hand_1Alert: Heat pump n°3 is running due to an external commandRead
BV193ch4_fail_1Alarm: Fail to start heat pump n°4 in the allowable timeRead
BV194ch4_hand_1Alert: Heat pump n°4 is running due to an external commandRead
BV1019vlv_1_close_alarm_1Alarm: Heat pump n°1 isolation valve closing alarmRead
BV1020vlv_1_open_fail_1Alarm: Heat pump n°1 isolation valve opening alarmRead
BV1035alarm_not_network_1_1Alarm: Heat pump n°1 is not in network modeRead
BV1036alarm_not_network_2_1Alarm: Heat pump n°2 is not in network modeRead
BV1037alarm_not_network_3_1Alarm: Heat pump n°3 is not in network modeRead
BV1038alarm_not_network_4_1Alarm: Heat pump n°4 is not in network modeRead
BV1043alarm_comm_1_1Alarm: Communication failure with heat pump n°1Read
BV1044alarm_comm_2_1Alarm: Communication failure with heat pump n°2Read
BV1045alarm_comm_3_1Alarm: Communication failure with heat pump n°3Read
BV1046alarm_comm_4_1Alarm: Communication failure with heat pump n°4Read
BV1051vlv_1_open_status_1Heat Pumps: Heat pump n°1 isolation valve open statusRead
BV1052vlv_2_open_status_1Heat Pumps: Heat pump n°2 isolation valve open statusRead
BV1053vlv_3_open_status_1Heat Pumps: Heat pump n°3 isolation valve open statusRead
BV1054vlv_4_open_status_1Heat Pumps: Heat pump n°4 isolation valve open statusRead
BV1059vlv_1_close_status_1Heat Pumps: Heat pump n°1 isolation valve close statusRead
BV1060vlv_2_close_status_1Heat Pumps: Heat pump n°2 isolation valve close statusRead
BV1061vlv_3_close_status_1Heat Pumps: Heat pump n°3 isolation valve close statusRead
BV1062vlv_4_close_status_1Heat Pumps: Heat pump n°4 isolation valve close statusRead
BV1083ch1_running_dhw_1Heat Pumps: Heat pump n°1 is in dedicated production to DHWRead
AV121rotation_type_selector_1Heat Pumps: Rotation method selectionWrite0=Lowest Runtime, 1=Fixed Order
AV131man_order_ch1_1Heat Pumps: Order of Heat pump n°1 if rotation type is set to Fixed OrderWrite
AV132man_order_ch2_1Heat Pumps: Order of Heat pump n°2 if rotation type is set to Fixed OrderWrite
AV133man_order_ch3_1Heat Pumps: Order of Heat pump n°3 if rotation type is set to Fixed OrderWrite
AV134man_order_ch4_1Heat Pumps: Order of Heat pump n°4 if rotation type is set to Fixed OrderWrite
AV178demand_limit_ch1_1Heat Pumps: Demand limit heat pump n°1%Write
AV179demand_limit_ch2_1Heat Pumps: Demand limit heat pump n°2%Write
AV180demand_limit_ch3_1Heat Pumps: Demand limit heat pump n°3%Write
AV181demand_limit_ch4_1Heat Pumps: Demand limit heat pump n°4%Write
AV186night_mode_demand_limit_ch1_1Heat Pumps: Night mode demand limit heat pump n°1%Write
AV187night_mode_demand_limit_ch3_1Heat Pumps: Night mode demand limit heat pump n°3%Write
AV190night_mode_demand_limit_ch2_1Heat Pumps: Night mode demand limit heat pump n°2%Write
AV191night_mode_demand_limit_ch4_1Heat Pumps: Night mode demand limit heat pump n°4%Write
MV100max_run_chillers_1Heat Pumps: Maximum number of heat pumps allowed to be started by the SMSWrite
MV102min_chlr_number_1Heat Pumps: Minimum number of heat pumps started by the SMS when runningWrite
BV126main1_1Heat Pumps: Maintenance mode for heat pump n°1 (stop the unit if active)Write
BV127main2_1Heat Pumps: Maintenance mode for heat pump n°2 (stop the unit if active)Write
BV128main3_1Heat Pumps: Maintenance mode for heat pump n°3 (stop the unit if active)Write
BV129main4_1Heat Pumps: Maintenance mode for heat pump n°4 (stop the unit if active)Write
AV1101bac_heatcool_11Heat pump n°1: Heat/Cool statusRead0=Cooling, 1=Heating
AV1104bac_cap_t_11Heat pump n°1: Percent total capacity%Read
AV1105bac_capa_t_11Heat pump n°1: Circuit A total capacity%Read
AV1106bac_capb_t_11Heat pump n°1: Circuit B total capacity%Read
AV1111bac_dem_lim_11Heat pump n°1: Active demand limit (capacity limitation)%Read
AV1113bac_ctrl_pnt_11Heat pump n°1: Control point°CRead
AV1118bac_ewt_11Heat pump n°1: Entering water temperature°CRead
AV1119bac_lwt_11Heat pump n°1: Leaving water temperature°CRead
AV1120bac_oat_11Heat pump n°1: Outdoor air temperature°CRead
AV1164bac_hr_mach_11Heat pump n°1: Machine operating hourshrRead
AV1165bac_st_mach_11Heat pump n°1: Machine starts numberRead
AV11006bac_alarm_1c_11Heat pump n°1: Current alarm 1cRead
AV11007bac_alarm_2c_11Heat pump n°1: Current alarm 2cRead
AV11008bac_alarm_3c_11Heat pump n°1: Current alarm 3cRead
AV11009bac_alarm_4c_11Heat pump n°1: Current alarm 4cRead
AV11010bac_alarm_5c_11Heat pump n°1: Current alarm 5cRead
MV1100bac_status_11Heat pump n°1: Run statusRead1=Off, 2=Running, 3=Stopping, 4=Delay, 5=Tripout, 6=Ready, 7=Override, 8=Defrost, 9=Run Test, 10=Test
MV1102bac_alarm_state_11Heat pump n°1: Alarm statusRead1=Normal, 2=Partial, 3=Shutdown
MV1103bac_ctrl_typ_11Heat pump n°1: Control typeRead1=Local, 2=Network, 3=Remote
BV1103bac_chil_s_s_11Heat pump n°1: Command Start/StopRead
BV1131bac_cap_max_11Heat pump n°1: Max Capacity ReachedRead
BV1132service_maintenance_alert_11Heat pump n°1: Service Maintenance AlertRead
BV1134bac_divvlv_o_11Heat pump n°1: Isolation valve open feedbackRead
BV1135bac_divvlv_c_11Heat pump n°1: Isolation valve close feedbackRead
AV1201bac_heatcool_12Heat pump n°2: Heat/Cool statusRead0=Cooling, 1=Heating
AV1204bac_cap_t_12Heat pump n°2: Percent total capacity%Read
AV1205bac_capa_t_12Heat pump n°2: Circuit A total capacity%Read
AV1206bac_capb_t_12Heat pump n°2: Circuit B total capacity%Read
AV1211bac_dem_lim_12Heat pump n°2: Active demand limit (capacity limitation)%Read
AV1213bac_ctrl_pnt_12Heat pump n°2: Control point°CRead
AV1218bac_ewt_12Heat pump n°2: Entering water temperature°CRead
AV1219bac_lwt_12Heat pump n°2: Leaving water temperature°CRead
AV1220bac_oat_12Heat pump n°2: Outdoor air temperature°CRead
AV1264bac_hr_mach_12Heat pump n°2: Machine operating hourshrRead
AV1265bac_st_mach_12Heat pump n°2: Machine starts numberRead
AV12006bac_alarm_1c_12Heat pump n°2: Current alarm 1cRead
AV12007bac_alarm_2c_12Heat pump n°2: Current alarm 2cRead
AV12008bac_alarm_3c_12Heat pump n°2: Current alarm 3cRead
AV12009bac_alarm_4c_12Heat pump n°2: Current alarm 4cRead
AV12010bac_alarm_5c_12Heat pump n°2: Current alarm 5cRead
MV1200bac_status_12Heat pump n°2: Run statusRead1=Off, 2=Running, 3=Stopping, 4=Delay, 5=Tripout, 6=Ready, 7=Override, 8=Defrost, 9=Run Test, 10=Test
MV1202bac_alarm_state_12Heat pump n°2: Alarm statusRead1=Normal, 2=Partial, 3=Shutdown
MV1203bac_ctrl_typ_12Heat pump n°2: Control typeRead1=Local, 2=Network, 3=Remote
BV1203bac_chil_s_s_12Heat pump n°2: Command Start/StopRead
BV1231bac_cap_max_12Heat pump n°2: Max Capacity ReachedRead
BV1232service_maintenance_alert_12Heat pump n°2: Service Maintenance AlertRead
BV1234bac_divvlv_o_12Heat pump n°2: Isolation valve open feedbackRead
BV1235bac_divvlv_c_12Heat pump n°2: Isolation valve close feedbackRead
AV1301bac_heatcool_13Heat pump n°3: Heat/Cool statusRead0=Cooling, 1=Heating
AV1304bac_cap_t_13Heat pump n°3: Percent total capacity%Read
AV1305bac_capa_t_13Heat pump n°3: Circuit A total capacity%Read
AV1306bac_capb_t_13Heat pump n°3: Circuit B total capacity%Read
AV1311bac_dem_lim_13Heat pump n°3: Active demand limit (capacity limitation)%Read
AV1313bac_ctrl_pnt_13Heat pump n°3: Control point°CRead
AV1318bac_ewt_13Heat pump n°3: Entering water temperature°CRead
AV1319bac_lwt_13Heat pump n°3: Leaving water temperature°CRead
AV1320bac_oat_13Heat pump n°3: Outdoor air temperature°CRead
AV1364bac_hr_mach_13Heat pump n°3: Machine operating hourshrRead
AV1365bac_st_mach_13Heat pump n°3: Machine starts numberRead
AV13006bac_alarm_1c_13Heat pump n°3: Current alarm 1cRead
AV13007bac_alarm_2c_13Heat pump n°3: Current alarm 2cRead
AV13008bac_alarm_3c_13Heat pump n°3: Current alarm 3cRead
AV13009bac_alarm_4c_13Heat pump n°3: Current alarm 4cRead
AV13010bac_alarm_5c_13Heat pump n°3: Current alarm 5cRead
MV1300bac_status_13Heat pump n°3: Run statusRead1=Off, 2=Running, 3=Stopping, 4=Delay, 5=Tripout, 6=Ready, 7=Override, 8=Defrost, 9=Run Test, 10=Test
MV1302bac_alarm_state_13Heat pump n°3: Alarm statusRead1=Normal, 2=Partial, 3=Shutdown
MV1303bac_ctrl_typ_13Heat pump n°3: Control typeRead1=Local, 2=Network, 3=Remote
BV1303bac_chil_s_s_13Heat pump n°3: Command Start/StopRead
BV1331bac_cap_max_13Heat pump n°3: Max Capacity ReachedRead
BV1332service_maintenance_alert_13Heat pump n°3: Service Maintenance AlertRead
BV1334bac_divvlv_o_13Heat pump n°3: Isolation valve open feedbackRead
BV1335bac_divvlv_c_13Heat pump n°3: Isolation valve close feedbackRead
AV1401bac_heatcool_14Heat pump n°4: Heat/Cool statusRead0=Cooling, 1=Heating
AV1404bac_cap_t_14Heat pump n°4: Percent total capacity%Read
AV1405bac_capa_t_14Heat pump n°4: Circuit A total capacity%Read
AV1406bac_capb_t_14Heat pump n°4: Circuit B total capacity%Read
AV1411bac_dem_lim_14Heat pump n°4: Active demand limit (capacity limitation)%Read
AV1413bac_ctrl_pnt_14Heat pump n°4: Control point°CRead
AV1418bac_ewt_14Heat pump n°4: Entering water temperature°CRead
AV1419bac_lwt_14Heat pump n°4: Leaving water temperature°CRead
AV1420bac_oat_14Heat pump n°4: Outdoor air temperature°CRead
AV1464bac_hr_mach_14Heat pump n°4: Machine operating hourshrRead
AV1465bac_st_mach_14Heat pump n°4: Machine starts numberRead
AV14006bac_alarm_1c_14Heat pump n°4: Current alarm 1cRead
AV14007bac_alarm_2c_14Heat pump n°4: Current alarm 2cRead
AV14008bac_alarm_3c_14Heat pump n°4: Current alarm 3cRead
AV14009bac_alarm_4c_14Heat pump n°4: Current alarm 4cRead
AV14010bac_alarm_5c_14Heat pump n°4: Current alarm 5cRead
MV1400bac_status_14Heat pump n°4: Run statusRead1=Off, 2=Running, 3=Stopping, 4=Delay, 5=Tripout, 6=Ready, 7=Override, 8=Defrost, 9=Run Test, 10=Test
MV1402bac_alarm_state_14Heat pump n°4: Alarm statusRead1=Normal, 2=Partial, 3=Shutdown
MV1403bac_ctrl_typ_14Heat pump n°4: Control typeRead1=Local, 2=Network, 3=Remote
BV1403bac_chil_s_s_14Heat pump n°4: Command Start/StopRead
BV1431bac_cap_max_14Heat pump n°4: Max Capacity ReachedRead
BV1432service_maintenance_alert_14Heat pump n°4: Service Maintenance AlertRead
BV1434bac_divvlv_o_14Heat pump n°4: Isolation valve open feedbackRead
BV1435bac_divvlv_c_14Heat pump n°4: Isolation valve close feedbackRead
Object ID lookup: Carrier SMS Option 275A point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps

How many BACnet points does the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps have?

This list has 315 BACnet objects: 144 analog values, 137 binary values, 34 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet points are writable?

80 of the 315 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet documentation?

The source is SMS OPT275A BMS Protocols (BACnet object list SMS_OPT275A_BACNET_COM.xlsx) (EN_SMS_OPT275A_BMS_Protocols), published free by Carrier at https://brandportal.carrier.com/asset/081c4b3d-90a3-48e5-a641-f9ee46d25993/EN_SMS_OPT275A_BMS_Protocols.zip.

What are the minimum BACnet points to integrate the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps?

Start with MV 502 on_off_command_5 (On/off command: 1=Off, 2=On, 3=Based on schedule); MV 521 manual_hc_sel_5 (Heating/cooling selection (3 = auto changeover on OAT)); MV 200 z1_setpoint_input_2 (Zone 1 setpoint mode: Eco, Comfort or Auto); AV 226 z1_heat_comfort_setpoint_2 (Zone 1 comfort heating water setpoint); AV 216 z1_cool_comfort_setpoint_2 (Zone 1 comfort cooling water setpoint); BV 505 emergency_shutdown_5 (Emergency shutdown signal from the BMS); AV 501 manager_control_mode_5 (Front panel button: 1=Off, 2=On, 3=Auto); AV 1032 lwt_evap_temp_1 (Common leaving water temperature); MV 1052 ch1_status_1 (Heat pump 1 status (running, failure, no comm...)); BV 548 alarm_synthesis_5 (General (synthesis) alarm).

How do I enable BMS control of the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps?

The system follows the On/Off input command only in the Auto operating type selected with the SMS front button (AV 501 reports it). In Auto the command can be Off, On or Based on Schedule. The network emergency stop shuts the system down in any operating type.

Can the BMS supply sensor values to the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps?

Zone relative humidity for dew point calculation (AV 264) can be written by the BMS when floor sensors are used.

How do I check these points on the real System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.