- System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Heat pump plant sequencer (system manager) · BACnet points list
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet points list
Updated 7 November 2026
The SMS is a plant controller for up to four modular R-290 air-source heat pumps; it talks to the heat pumps over BACnet IP and offers BACnet IP and Modbus TCP to the BMS through the Ethernet switch in its cabinet. The object list has 315 objects grouped by function: general system commands and status, schedules, two heating/cooling zones, customer and DHW pump sets, the heat pump manager, and one block per heat pump.
This page lists 315 BACnet objects for the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps — 80 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
- Equipment
- Heat pump plant sequencer (system manager)
- Equipment type
- Heat pumps
- BACnet objects
- 315 (80 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Connect the BMS to the Ethernet switch in the SMS cabinet. Put the system in Auto operating type with the front button, then drive it with the On/Off input command (MV 502) and the heating/cooling selection (MV 521), adjust zone setpoints, and read system status, temperatures, heat pump status and the synthesis alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 502 | on_off_command_5 | On/off command: 1=Off, 2=On, 3=Based on schedule | Write |
| MV 521 | manual_hc_sel_5 | Heating/cooling selection (3 = auto changeover on OAT) | Write |
| MV 200 | z1_setpoint_input_2 | Zone 1 setpoint mode: Eco, Comfort or Auto | Write |
| AV 226 | z1_heat_comfort_setpoint_2 | Zone 1 comfort heating water setpoint | Write |
| AV 216 | z1_cool_comfort_setpoint_2 | Zone 1 comfort cooling water setpoint | Write |
| BV 505 | emergency_shutdown_5 | Emergency shutdown signal from the BMS | Write |
| AV 501 | manager_control_mode_5 | Front panel button: 1=Off, 2=On, 3=Auto | Read |
| AV 1032 | lwt_evap_temp_1 | Common leaving water temperature | Read |
| MV 1052 | ch1_status_1 | Heat pump 1 status (running, failure, no comm...) | Read |
| BV 548 | alarm_synthesis_5 | General (synthesis) alarm | Read |
Enable & remote start
The system follows the On/Off input command only in the Auto operating type selected with the SMS front button (AV 501 reports it). In Auto the command can be Off, On or Based on Schedule. The network emergency stop shuts the system down in any operating type.
Sensors & values from the BMS
Zone relative humidity for dew point calculation (AV 264) can be written by the BMS when floor sensors are used.
Network setup
- The SMS has five Ethernet ports for the heat pumps (BACnet IP) and the BMS (BACnet IP, Modbus TCP).
- Each heat pump must be set to Network control mode, or the SMS raises a 'not in network mode' alarm and drops it from the sequence.
Watch out for
- Maintenance-mode BVs (e.g. BV 126-129) stop a heat pump or pump when set; do not leave them active.
- Several points are labelled 'Zone n°1 or No Zone'; on a single-zone plant only the zone 1 points apply.
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 501 | manager_control_mode_5 | General: Front SMS panel button status | Read | 1=OFF, 2=ON, 3=AUTO | |
| AV | 526 | oat_5 | General: Average Outside Air Temperature | °C | Read | |
| AV | 542 | dhw_threshold_5 | General: Disabling DHW threshold: Disable DHW if DHW tank temperature is above this threshold (need DHW... | °C | Read | |
| MV | 522 | production_mode_5 | General: Current SMS production mode | Read | 1=Heat pumps production to buffer tank, 2=Heat pumps production to buffer tank and Heat pump n°1 production to DHW, 3=Heat pumps production to DHW, 4=Boiler production to buffer tank, 5=Boiler production to DHW, 6=Boiler production to DHW and heat pumps production to buffer tank | |
| MV | 551 | hmi_display_smart_grid_5 | General: Smart Grid status | Read | 1=Lock, 2=Normal, 3=Forced, 4=Boost | |
| BV | 516 | diverting_valve_command_5 | General: Command position for the diverting valve | Read | 0=to Buffer tank, 1=to DHW | |
| BV | 517 | dv_open_fail_5 | Alarm: Diverting valve opening alarm | Read | ||
| BV | 519 | dv_close_fail_5 | Alarm: Diverting valve closing alarm | Read | ||
| BV | 521 | dhw_cmd_5 | General: Domestic Hot Water mode running | Read | ||
| BV | 522 | dhw_heater_cmd_5 | General: DHW Heater command | Read | ||
| BV | 523 | legionella_cmd_5 | General: Legionella Prevention mode running | Read | ||
| BV | 524 | boiler_cmd_5 | General: Boiler command | Read | ||
| BV | 525 | bac_ehs_level_1_5 | General: Start command Electric Heat Stage (EHS) n°1 | Read | ||
| BV | 526 | bac_ehs_level_2_5 | General: Start command Electric Heat Stage (EHS) n°2 | Read | ||
| BV | 527 | bac_ehs_level_3_5 | General: Start command Electric Heat Stage (EHS) n°3 | Read | ||
| BV | 529 | hc_sel_5 | Current heating/cooling mode | Read | 0=Cooling, 1=Heating | |
| BV | 533 | m2033_5 | Alarm: Leaving Water Temperature sensor failure (common heat pumps outlet) | Read | ||
| BV | 534 | m2091_5 | Alert: Entering Water Temperature sensor failure (common heat pumps intlet) | Read | ||
| BV | 538 | standby_mode_5 | General: Stand-by mode for automatic changeover based on Outside Air Temperature (no heating, no cooling) | Read | ||
| BV | 547 | alert_synthesis_5 | General: Synthesis alert feedback | Read | ||
| BVmin | 548 | alarm_synthesis_5 | General: Synthesis alarm feedback | Read | ||
| BV | 728 | hoa_alarm_7 | Alert: At least one output switch is not set to "Auto" on the hardware C2 | Read | ||
| BV | 6020 | hoa_alarm_6 | Alert: At least one output switch is not set to "Auto" on the hardware C1 | Read | ||
| AV | 503 | dhw_sp_5 | General: Enabling DHW threshold | °C | Write | |
| AV | 504 | m3244_5 | General: Disabling DHW hysteresis: Disable DHW if DHW tank temperature is above DHW enabling threshold +... | Write | ||
| AV | 505 | legionella_sp_5 | General: Disabling Legionella Prevention threshold | °C | Write | |
| AV | 507 | m3273_5 | General: Disabling Legionella Prevention delay | min | Write | |
| AV | 510 | oat_hyst_boiler_5 | General: Hysteresis on Outside Air Temperature threshold to disable boiler usage | °C | Write | |
| AV | 511 | oat_boiler_5 | General: Outside Air Temperature threshold to enable boiler usage instead of heat pumps | °C | Write | |
| AV | 522 | heat_oat_threshold_5 | General: Threshold for automatic changeover based on Outside Air Temperature (from cooling mode to heating... | °C | Write | |
| AV | 523 | cool_oat_threshold_5 | General: Threshold for automatic changeover based on Outside Air Temperature (from heating mode to cooling... | °C | Write | |
| AV | 524 | heat_oat_delay_5 | General: Delay for automatic changeover based on Outside Air Temperature (from cooling mode to heating mode) | hr | Write | |
| AV | 525 | cool_oat_delay_5 | General: Delay for automatic changeover based on Outside Air Temperature (from heating mode to cooling mode) | hr | Write | |
| AV | 540 | dhw_setpoint_conf_5 | General: Domestic Hot Water setpoint configuration | °C | Write | |
| AV | 541 | legionella_setpoint_conf_5 | General: Legionella Prevention setpoint configuration | °C | Write | |
| MVmin | 502 | on_off_command_5 | General: On/Off SMS input command | Write | 1=OFF, 2=ON, 3=Based on Schedule | |
| MVmin | 521 | manual_hc_sel_5 | General: Heating/Cooling selection | Write | 1=Cooling mode, 2=Heating mode, 3=Automatic changeover based on Outside Air Temperature | |
| BV | 503 | general_ack_5 | General: SMS events acknowledgement | Write | ||
| BV | 504 | refrigerant_shutdown_5 | General: Refrigerant leak shutdown signal from BMS (will stop the SMS) | Write | ||
| BVmin | 505 | emergency_shutdown_5 | General: Emergency shutdown signal from BMS (will stop the SMS) | Write | ||
| BV | 558 | bms_start_dhw_5 | General: DHW enable command (schedule bypass) | Write | ||
| MV | 2401 | schedule_state_z1_24 | Schedule: Comfort No Zone or Zone n°1 schedule state | Read | 1=Eco, 2=Comfort, 3=Away | |
| MV | 2501 | schedule_state_z2_25 | Schedule: Comfort Zone n°2 schedule state | Read | 1=Eco, 2=Comfort, 3=Away | |
| BV | 21044 | schedule_state_21 | Schedule: Heat Pumps On/Off schedule state | Read | 0=Inactive, 1=Active | |
| BV | 2200 | mode_holiday_22 | Schedule: Holiday schedule state | Read | 0=Inactive, 1=Active | |
| BV | 26044 | schedule_state_night_26 | Schedule: Night mode schedule state | Read | 0=Inactive, 1=Active | |
| BV | 27044 | schedule_state_dhw_27 | Schedule: DHW schedule state | Read | 0=Inactive, 1=Active | |
| BV | 2816 | schedule_state_legion_27 | Schedule: Legionalla Prevention schedule state | Read | 0=Inactive, 1=Active | |
| AV | 268 | runtime_p1_2 | Zone n°1: Runtime pump | hr | Read | |
| AV | 269 | runtime_p2_2 | Zone n°2: Runtime pump | hr | Read | |
| AV | 270 | command_3wv_1_2 | Zone n°1: 3-way mixing valve command | % | Read | |
| AV | 271 | command_3wv_2_2 | Zone n°2: 3-way mixing valve command | % | Read | |
| AV | 272 | bac_dew_point_2 | Zone: Dew point temperature (floor sensor) | °C | Read | |
| AV | 274 | z1_setpoint_2 | Zone n°1 or No Zone: Effective setpoint | °C | Read | |
| AV | 276 | z2_setpoint_2 | Zone n°2: Effective setpoint | °C | Read | |
| BV | 222 | enable1_2 | Zone n°1: Command pump | Read | ||
| BV | 223 | status1_2 | Zone n°1: Running status pump | Read | ||
| BV | 226 | enable2_2 | Zone n°2: Command pump | Read | ||
| BV | 227 | status2_2 | Zone n°2: Running status pump | Read | ||
| BV | 233 | p1_fail_2 | Alarm: Fail to start pump Zone n°1 in the allowable time | Read | ||
| BV | 234 | p1_hand_2 | Alert: Pump Zone n°1 is running due to an external command | Read | ||
| BV | 235 | p2_fail_2 | Alarm: Fail to start pump Zone n°2 in the allowable time | Read | ||
| BV | 236 | p2_hand_2 | Alert: Pump Zone n°2 is running due to an external command | Read | ||
| BV | 237 | floor_sensor_fault_2 | Alarm: Floor temperature out of allowable range (will stop the pump) | Read | ||
| AVmin | 216 | z1_cool_comfort_setpoint_2 | Zone n°1 or No Zone: Static "Comfort" setpoint / Cooling mode | °C | Write | |
| AV | 217 | z1_cool_eco_setpoint_2 | Zone n°1 or No Zone: Static "Eco" setpoint / Cooling mode | °C | Write | |
| AV | 218 | z1_cool_away_setpoint_2 | Zone n°1 or No Zone: Static "Away" setpoint / Cooling mode | °C | Write | |
| AVmin | 226 | z1_heat_comfort_setpoint_2 | Zone n°1 or No Zone: Static "Comfort" setpoint / Heating mode | °C | Write | |
| AV | 227 | z1_heat_eco_setpoint_2 | Zone n°1 or No Zone: Static "Eco" setpoint / Heating mode | °C | Write | |
| AV | 228 | z1_heat_away_setpoint_2 | Zone n°1 or No Zone: Static "Away" setpoint / Heating mode | °C | Write | |
| AV | 235 | z2_cool_comfort_setpoint_2 | Zone n°2: Static "Comfort" setpoint / Cooling mode | °C | Write | |
| AV | 236 | z2_cool_eco_setpoint_2 | Zone n°2: Static "Eco" setpoint / Cooling mode | °C | Write | |
| AV | 237 | z2_cool_away_setpoint_2 | Zone n°2: Static "Away" setpoint / Cooling mode | °C | Write | |
| AV | 244 | z2_heat_comfort_setpoint_2 | Zone n°2: Static "Comfort" setpoint / Heating mode | °C | Write | |
| AV | 245 | z2_heat_eco_setpoint_2 | Zone n°2: Static "Eco" setpoint / Heating mode | °C | Write | |
| AV | 246 | z2_heat_away_setpoint_2 | Zone n°2: Static "Away" setpoint / Heating mode | °C | Write | |
| AV | 257 | v1_manual_value_2 | Zone n°1: 3-way mixing valve position command in manual forcing | % | Write | |
| AV | 263 | v2_manual_value_2 | Zone n°2: 3-way mixing valve position command in manual forcing | % | Write | |
| AV | 264 | bac_rh_2 | Zone: Relative humidity for dew point calculation (floor sensor) | % | Write | |
| AV | 266 | bac_high_temp_threshold_2 | Zone: High temperature threshold for floor temperature alarm (floor sensor) | °C | Write | |
| AV | 267 | bac_dew_point_hysteresis_2 | Zone: Hysteresis above dew point for low floor temperature alarm (floor sensor) | °C | Write | |
| MVmin | 200 | z1_setpoint_input_2 | Zone n°1 or No Zone: Setpoint mode | Write | 1=Eco, 2=Comfort, 3=Auto | |
| MV | 205 | z2_setpoint_input_2 | Zone n°2: Setpoint mode | Write | 1=Eco, 2=Comfort, 3=Auto | |
| MV | 247 | p1_manual_2 | Zone n°1: Pump Manual/Auto | Write | 1=Manual On, 2=Manual Off, 3=Automatic | |
| MV | 248 | p2_manual_2 | Zone n°2: Pump Manual/Auto | Write | 1=Manual On, 2=Manual Off, 3=Automatic | |
| BV | 200 | z1_ctrlpnt_method_2 | Zone n°1 or No Zone: Setpoint selection type | Write | 0=Climatic curve, 1=Static setpoint | |
| BV | 205 | z2_ctrlpnt_method_2 | Zone n°2: Setpoint selection type | Write | 0=Climatic curve, 1=Static setpoint | |
| BV | 211 | main1_2 | Zone n°1: Maintenance mode pump (stop the pump if active) | Write | ||
| BV | 212 | main2_2 | Zone n°2: Maintenance mode pump (stop the pump if active) | Write | ||
| BV | 217 | v1_manual_2 | Zone n°1: 3-way mixing valve Manual/Auto | Write | 0=Automatic, 1=Manual position | |
| BV | 219 | v2_manual_2 | Zone n°2: 3-way mixing valve Manual/Auto | Write | 0=Automatic, 1=Manual position | |
| AV | 332 | vfd_status1_3 | Customer pumps: VFD command | % | Read | |
| AV | 334 | runtime_p1_3 | Customer pumps: Runtime pump n°1 | hr | Read | |
| AV | 335 | runtime_p2_3 | Customer pumps: Runtime pump n°2 | hr | Read | |
| AV | 336 | diff_press_3 | Customer pumps: Differential pressure value | kPa | Read | |
| BV | 308 | enable1_3 | Customer pumps: Command pump n°1 | Read | ||
| BV | 309 | enable2_3 | Customer pumps: Command pump n°2 | Read | ||
| BV | 310 | status1_3 | Customer pumps: Running status pump n°1 | Read | ||
| BV | 311 | status2_3 | Customer pumps: Running status pump n°2 | Read | ||
| BV | 317 | press_hi_3 | Alert: Customer pump: Pressure difference too high from setpoint | Read | ||
| BV | 318 | press_lo_3 | Alert: Customer pump: Pressure difference too low from setpoint | Read | ||
| BV | 319 | p1_fail_3 | Alarm: Fail to start Customer pump n°1 in the allowable time | Read | ||
| BV | 320 | p1_hand_3 | Alert: Customer pump n°1 is running due to an external command | Read | ||
| BV | 321 | p2_fail_3 | Alarm: Fail to start Customer pump n°2 in the allowable time | Read | ||
| BV | 322 | p2_hand_3 | Alert: Customer pump n°2 is running due to an external command | Read | ||
| AV | 302 | vfd1_manual_3 | Customer pumps: VFD command in manual forcing | % | Write | |
| AV | 305 | pumps_rotation_type_selector_3 | Customer pumps: Rotation method selection | Write | 0=Lowest Runtime, 1=Fixed Order | |
| AV | 306 | man_order_p1_3 | Customer pumps: Order of pump 1 if rotation type is set to Fixed Order | Write | ||
| AV | 307 | man_order_p2_3 | Customer pumps: Order of pump 2 if rotation type is set to Fixed Order | Write | ||
| AV | 317 | dpstpt_3 | Customer pumps: Differential pressure setpoint | kPa | Write | |
| MV | 301 | p_manual_3 | Customer pumps: Manual/Auto | Write | 1=Pump n°1 Manual On, 2=Pump n°2 Manual On, 3=Manual Off, 4=Automatic | |
| BV | 300 | main1_3 | Customer pumps: Maintenance mode pump n°1 (stop the pump if active) | Write | ||
| BV | 301 | main2_3 | Customer pumps: Maintenance mode pump n°2 (stop the pump if active) | Write | ||
| AV | 433 | vfd_status1_4 | DHW pumps: VFD command | % | Read | |
| AV | 435 | runtime_p1_4 | DHW pumps: Runtime pump n°1 | hr | Read | |
| AV | 436 | runtime_p2_4 | DHW pumps: Runtime pump n°2 | hr | Read | |
| AV | 437 | diff_press_4 | DHW pumps: Differential pressure value | kPa | Read | |
| BV | 408 | enable1_4 | DHW pumps: Command pump n°1 | Read | ||
| BV | 409 | enable2_4 | DHW pumps: Command pump n°2 | Read | ||
| BV | 410 | status1_4 | DHW pumps: Running status pump n°1 | Read | ||
| BV | 411 | status2_4 | DHW pumps: Running status pump n°2 | Read | ||
| BV | 417 | press_hi_4 | Alert: DHW pump: Pressure difference too high from setpoint | Read | ||
| BV | 418 | press_lo_4 | Alert: DHW pump: Pressure difference too low from setpoint | Read | ||
| BV | 419 | p1_fail_4 | Alarm: Fail to start DHW pump n°1 in the allowable time | Read | ||
| BV | 420 | p1_hand_4 | Alert: DHW pump n°1 is running due to an external command | Read | ||
| BV | 421 | p2_fail_4 | Alarm: Fail to start DHW pump n°2 in the allowable time | Read | ||
| BV | 422 | p2_hand_4 | Alert: DHW pump n°2 is running due to an external command | Read | ||
| AV | 402 | vfd1_manual_4 | DHW pumps: VFD command in manual forcing | % | Write | |
| AV | 405 | pumps_rotation_type_selector_4 | DHW pumps: Rotation method selection | Write | 0=Lowest Runtime, 1=Fixed Order | |
| AV | 406 | man_order_p1_4 | DHW pumps: Order of pump 1 if rotation type is set to Fixed Order | Write | ||
| AV | 407 | man_order_p2_4 | DHW pumps: Order of pump 2 if rotation type is set to Fixed Order | Write | ||
| AV | 418 | dpstpt_4 | DHW pumps: Differential pressure setpoint | kPa | Write | |
| MV | 401 | p_manual_4 | DHW pumps: Manual/Auto | Write | 1=Pump n°1 Manual On, 2=Pump n°2 Manual On, 3=Manual Off, 4=Automatic | |
| BV | 400 | main1_4 | DHW pumps: Maintenance mode pump n°1 (stop the pump if active) | Write | ||
| BV | 401 | main2_4 | DHW pumps: Maintenance mode pump n°2 (stop the pump if active) | Write | ||
| AV | 1029 | nb_run_chillers_1 | Heat Pumps: Number of running heat pumps | Read | ||
| AV | 1030 | eff_chlr_chws_temp_stpt_value_1 | Heat Pumps: Effective cascade setpoint (heat pumps staging at Leaving Water Temperature sensor) | °C | Read | |
| AV | 1031 | nb_avail_chillers_1 | Heat Pumps: Number of available heat pumps | Read | ||
| AVmin | 1032 | lwt_evap_temp_1 | Heat Pumps: Leaving Water Temperature (common heat pumps outlet) / Regulation sensor for staging | °C | Read | |
| AV | 1033 | ewt_evap_temp_1 | Heat Pumps: Entering Water Temperature (common heat pump inlet) | °C | Read | |
| AV | 1035 | time_before_acr_1 | Heat Pumps: Remaining time before staging up (start another heat pump) | min | Read | |
| AV | 1036 | time_before_rcr_1 | Heat Pumps: Remaining time before staging down (stop a heat pump) | min | Read | |
| AV | 1042 | next_chill_start_1 | Heat Pumps: Next heat pump to start when a stage up occurs | Read | ||
| AV | 1043 | next_chill_stop_1 | Heat Pumps: Next heat pump to stop when a stage down occurs | Read | ||
| AV | 1066 | average_plant_capacity_1 | Heat Pumps: Average plant capacity | % | Read | |
| MV | 1007 | ch1_manual_1 | Heat Pumps: Heat pump n°1 Manual/Auto | Read | 1=Manual On, 2=Manual Off, 3=Automatic | |
| MV | 1008 | ch2_manual_1 | Heat Pumps: Heat pump n°2 Manual/Auto | Read | 1=Manual On, 2=Manual Off, 3=Automatic | |
| MV | 1009 | ch3_manual_1 | Heat Pumps: Heat pump n°3 Manual/Auto | Read | 1=Manual On, 2=Manual Off, 3=Automatic | |
| MV | 1010 | ch4_manual_1 | Heat Pumps: Heat pump n°4 Manual/Auto | Read | 1=Manual On, 2=Manual Off, 3=Automatic | |
| MVmin | 1052 | ch1_status_1 | Heat Pumps: Heat pump n°1 status | Read | 1=Not configured, 2=In maintenance mode, 3=In manual mode, 4=BACnet OFF, 5=No communication, 6=Full failure, 7=Partial failure & OFF, 8=Partial failure & running, 9=Running, 10=Ready | |
| MV | 1053 | ch2_status_1 | Heat Pumps: Heat pump n°2 status | Read | 1=Not configured, 2=In maintenance mode, 3=In manual mode, 4=BACnet OFF, 5=No communication, 6=Full failure, 7=Partial failure & OFF, 8=Partial failure & running, 9=Running, 10=Ready | |
| MV | 1054 | ch3_status_1 | Heat Pumps: Heat pump n°3 status | Read | 1=Not configured, 2=In maintenance mode, 3=In manual mode, 4=BACnet OFF, 5=No communication, 6=Full failure, 7=Partial failure & OFF, 8=Partial failure & running, 9=Running, 10=Ready | |
| MV | 1055 | ch4_status_1 | Heat Pumps: Heat pump n°4 status | Read | 1=Not configured, 2=In maintenance mode, 3=In manual mode, 4=BACnet OFF, 5=No communication, 6=Full failure, 7=Partial failure & OFF, 8=Partial failure & running, 9=Running, 10=Ready | |
| BV | 137 | acr_1_1 | Heat Pumps: Staging up condition n°1 is valid (Temperature drift and evolution) | Read | ||
| BV | 139 | rcr_1_1 | Heat Pumps: Staging down condition n°1.1 is valid (Temperature in the allowable range) | Read | ||
| BV | 140 | acr_2_1 | Heat Pumps: Staging up condition n°2 is valid (Heat pumps capacity) | Read | ||
| BV | 141 | rcr_2_1 | Heat Pumps: Staging down condition n°1.2 is valid (Heat pumps average capacity below threshold) | Read | ||
| BV | 143 | acr_3_1 | Heat Pumps: Staging up condition n°3 is valid (Critical Temperature drift) | Read | ||
| BV | 144 | acr_active_1 | Heat Pumps: Staging up coming (waiting for end of delay) | Read | ||
| BV | 145 | rcr_active_1 | Heat Pumps: Staging down coming (waiting for end of delay) | Read | ||
| BV | 154 | communication_ch1_1 | Heat Pumps: Heat pump n°1 communication status | Read | 0=Inactive, 1=Active | |
| BV | 155 | communication_ch2_1 | Heat Pumps: Heat pump n°2 communication status | Read | 0=Inactive, 1=Active | |
| BV | 156 | communication_ch3_1 | Heat Pumps: Heat pump n°3 communication status | Read | 0=Inactive, 1=Active | |
| BV | 157 | communication_ch4_1 | Heat Pumps: Heat pump n°4 communication status | Read | 0=Inactive, 1=Active | |
| BV | 162 | ch1_is_running_1 | Heat Pumps: Heat pump n°1 running feedback | Read | ||
| BV | 163 | command_ch1_1 | Heat Pumps: Heat pump n°1 running command | Read | ||
| BV | 164 | ch2_is_running_1 | Heat Pumps: Heat pump n°2 running feedback | Read | ||
| BV | 165 | command_ch2_1 | Heat Pumps: Heat pump n°2 running command | Read | ||
| BV | 166 | ch3_is_running_1 | Heat Pumps: Heat pump n°3 running feedback | Read | ||
| BV | 167 | command_ch3_1 | Heat Pumps: Heat pump n°3 running command | Read | ||
| BV | 168 | ch4_is_running_1 | Heat Pumps: Heat pump n°4 running feedback | Read | ||
| BV | 169 | command_ch4_1 | Heat Pumps: Heat pump n°4 running command | Read | ||
| BV | 185 | acr_cap_exc_1 | Information: The capacity has reached the maximum available capacity | Read | ||
| BV | 187 | ch1_fail_1 | Alarm: Fail to start heat pump n°1 in the allowable time | Read | ||
| BV | 188 | ch1_hand_1 | Alert: Heat pump n°1 is running due to an external command | Read | ||
| BV | 189 | ch2_fail_1 | Alarm: Fail to start heat pump n°2 in the allowable time | Read | ||
| BV | 190 | ch2_hand_1 | Alert: Heat pump n°2 is running due to an external command | Read | ||
| BV | 191 | ch3_fail_1 | Alarm: Fail to start heat pump n°3 in the allowable time | Read | ||
| BV | 192 | ch3_hand_1 | Alert: Heat pump n°3 is running due to an external command | Read | ||
| BV | 193 | ch4_fail_1 | Alarm: Fail to start heat pump n°4 in the allowable time | Read | ||
| BV | 194 | ch4_hand_1 | Alert: Heat pump n°4 is running due to an external command | Read | ||
| BV | 1019 | vlv_1_close_alarm_1 | Alarm: Heat pump n°1 isolation valve closing alarm | Read | ||
| BV | 1020 | vlv_1_open_fail_1 | Alarm: Heat pump n°1 isolation valve opening alarm | Read | ||
| BV | 1035 | alarm_not_network_1_1 | Alarm: Heat pump n°1 is not in network mode | Read | ||
| BV | 1036 | alarm_not_network_2_1 | Alarm: Heat pump n°2 is not in network mode | Read | ||
| BV | 1037 | alarm_not_network_3_1 | Alarm: Heat pump n°3 is not in network mode | Read | ||
| BV | 1038 | alarm_not_network_4_1 | Alarm: Heat pump n°4 is not in network mode | Read | ||
| BV | 1043 | alarm_comm_1_1 | Alarm: Communication failure with heat pump n°1 | Read | ||
| BV | 1044 | alarm_comm_2_1 | Alarm: Communication failure with heat pump n°2 | Read | ||
| BV | 1045 | alarm_comm_3_1 | Alarm: Communication failure with heat pump n°3 | Read | ||
| BV | 1046 | alarm_comm_4_1 | Alarm: Communication failure with heat pump n°4 | Read | ||
| BV | 1051 | vlv_1_open_status_1 | Heat Pumps: Heat pump n°1 isolation valve open status | Read | ||
| BV | 1052 | vlv_2_open_status_1 | Heat Pumps: Heat pump n°2 isolation valve open status | Read | ||
| BV | 1053 | vlv_3_open_status_1 | Heat Pumps: Heat pump n°3 isolation valve open status | Read | ||
| BV | 1054 | vlv_4_open_status_1 | Heat Pumps: Heat pump n°4 isolation valve open status | Read | ||
| BV | 1059 | vlv_1_close_status_1 | Heat Pumps: Heat pump n°1 isolation valve close status | Read | ||
| BV | 1060 | vlv_2_close_status_1 | Heat Pumps: Heat pump n°2 isolation valve close status | Read | ||
| BV | 1061 | vlv_3_close_status_1 | Heat Pumps: Heat pump n°3 isolation valve close status | Read | ||
| BV | 1062 | vlv_4_close_status_1 | Heat Pumps: Heat pump n°4 isolation valve close status | Read | ||
| BV | 1083 | ch1_running_dhw_1 | Heat Pumps: Heat pump n°1 is in dedicated production to DHW | Read | ||
| AV | 121 | rotation_type_selector_1 | Heat Pumps: Rotation method selection | Write | 0=Lowest Runtime, 1=Fixed Order | |
| AV | 131 | man_order_ch1_1 | Heat Pumps: Order of Heat pump n°1 if rotation type is set to Fixed Order | Write | ||
| AV | 132 | man_order_ch2_1 | Heat Pumps: Order of Heat pump n°2 if rotation type is set to Fixed Order | Write | ||
| AV | 133 | man_order_ch3_1 | Heat Pumps: Order of Heat pump n°3 if rotation type is set to Fixed Order | Write | ||
| AV | 134 | man_order_ch4_1 | Heat Pumps: Order of Heat pump n°4 if rotation type is set to Fixed Order | Write | ||
| AV | 178 | demand_limit_ch1_1 | Heat Pumps: Demand limit heat pump n°1 | % | Write | |
| AV | 179 | demand_limit_ch2_1 | Heat Pumps: Demand limit heat pump n°2 | % | Write | |
| AV | 180 | demand_limit_ch3_1 | Heat Pumps: Demand limit heat pump n°3 | % | Write | |
| AV | 181 | demand_limit_ch4_1 | Heat Pumps: Demand limit heat pump n°4 | % | Write | |
| AV | 186 | night_mode_demand_limit_ch1_1 | Heat Pumps: Night mode demand limit heat pump n°1 | % | Write | |
| AV | 187 | night_mode_demand_limit_ch3_1 | Heat Pumps: Night mode demand limit heat pump n°3 | % | Write | |
| AV | 190 | night_mode_demand_limit_ch2_1 | Heat Pumps: Night mode demand limit heat pump n°2 | % | Write | |
| AV | 191 | night_mode_demand_limit_ch4_1 | Heat Pumps: Night mode demand limit heat pump n°4 | % | Write | |
| MV | 100 | max_run_chillers_1 | Heat Pumps: Maximum number of heat pumps allowed to be started by the SMS | Write | ||
| MV | 102 | min_chlr_number_1 | Heat Pumps: Minimum number of heat pumps started by the SMS when running | Write | ||
| BV | 126 | main1_1 | Heat Pumps: Maintenance mode for heat pump n°1 (stop the unit if active) | Write | ||
| BV | 127 | main2_1 | Heat Pumps: Maintenance mode for heat pump n°2 (stop the unit if active) | Write | ||
| BV | 128 | main3_1 | Heat Pumps: Maintenance mode for heat pump n°3 (stop the unit if active) | Write | ||
| BV | 129 | main4_1 | Heat Pumps: Maintenance mode for heat pump n°4 (stop the unit if active) | Write | ||
| AV | 1101 | bac_heatcool_11 | Heat pump n°1: Heat/Cool status | Read | 0=Cooling, 1=Heating | |
| AV | 1104 | bac_cap_t_11 | Heat pump n°1: Percent total capacity | % | Read | |
| AV | 1105 | bac_capa_t_11 | Heat pump n°1: Circuit A total capacity | % | Read | |
| AV | 1106 | bac_capb_t_11 | Heat pump n°1: Circuit B total capacity | % | Read | |
| AV | 1111 | bac_dem_lim_11 | Heat pump n°1: Active demand limit (capacity limitation) | % | Read | |
| AV | 1113 | bac_ctrl_pnt_11 | Heat pump n°1: Control point | °C | Read | |
| AV | 1118 | bac_ewt_11 | Heat pump n°1: Entering water temperature | °C | Read | |
| AV | 1119 | bac_lwt_11 | Heat pump n°1: Leaving water temperature | °C | Read | |
| AV | 1120 | bac_oat_11 | Heat pump n°1: Outdoor air temperature | °C | Read | |
| AV | 1164 | bac_hr_mach_11 | Heat pump n°1: Machine operating hours | hr | Read | |
| AV | 1165 | bac_st_mach_11 | Heat pump n°1: Machine starts number | Read | ||
| AV | 11006 | bac_alarm_1c_11 | Heat pump n°1: Current alarm 1c | Read | ||
| AV | 11007 | bac_alarm_2c_11 | Heat pump n°1: Current alarm 2c | Read | ||
| AV | 11008 | bac_alarm_3c_11 | Heat pump n°1: Current alarm 3c | Read | ||
| AV | 11009 | bac_alarm_4c_11 | Heat pump n°1: Current alarm 4c | Read | ||
| AV | 11010 | bac_alarm_5c_11 | Heat pump n°1: Current alarm 5c | Read | ||
| MV | 1100 | bac_status_11 | Heat pump n°1: Run status | Read | 1=Off, 2=Running, 3=Stopping, 4=Delay, 5=Tripout, 6=Ready, 7=Override, 8=Defrost, 9=Run Test, 10=Test | |
| MV | 1102 | bac_alarm_state_11 | Heat pump n°1: Alarm status | Read | 1=Normal, 2=Partial, 3=Shutdown | |
| MV | 1103 | bac_ctrl_typ_11 | Heat pump n°1: Control type | Read | 1=Local, 2=Network, 3=Remote | |
| BV | 1103 | bac_chil_s_s_11 | Heat pump n°1: Command Start/Stop | Read | ||
| BV | 1131 | bac_cap_max_11 | Heat pump n°1: Max Capacity Reached | Read | ||
| BV | 1132 | service_maintenance_alert_11 | Heat pump n°1: Service Maintenance Alert | Read | ||
| BV | 1134 | bac_divvlv_o_11 | Heat pump n°1: Isolation valve open feedback | Read | ||
| BV | 1135 | bac_divvlv_c_11 | Heat pump n°1: Isolation valve close feedback | Read | ||
| AV | 1201 | bac_heatcool_12 | Heat pump n°2: Heat/Cool status | Read | 0=Cooling, 1=Heating | |
| AV | 1204 | bac_cap_t_12 | Heat pump n°2: Percent total capacity | % | Read | |
| AV | 1205 | bac_capa_t_12 | Heat pump n°2: Circuit A total capacity | % | Read | |
| AV | 1206 | bac_capb_t_12 | Heat pump n°2: Circuit B total capacity | % | Read | |
| AV | 1211 | bac_dem_lim_12 | Heat pump n°2: Active demand limit (capacity limitation) | % | Read | |
| AV | 1213 | bac_ctrl_pnt_12 | Heat pump n°2: Control point | °C | Read | |
| AV | 1218 | bac_ewt_12 | Heat pump n°2: Entering water temperature | °C | Read | |
| AV | 1219 | bac_lwt_12 | Heat pump n°2: Leaving water temperature | °C | Read | |
| AV | 1220 | bac_oat_12 | Heat pump n°2: Outdoor air temperature | °C | Read | |
| AV | 1264 | bac_hr_mach_12 | Heat pump n°2: Machine operating hours | hr | Read | |
| AV | 1265 | bac_st_mach_12 | Heat pump n°2: Machine starts number | Read | ||
| AV | 12006 | bac_alarm_1c_12 | Heat pump n°2: Current alarm 1c | Read | ||
| AV | 12007 | bac_alarm_2c_12 | Heat pump n°2: Current alarm 2c | Read | ||
| AV | 12008 | bac_alarm_3c_12 | Heat pump n°2: Current alarm 3c | Read | ||
| AV | 12009 | bac_alarm_4c_12 | Heat pump n°2: Current alarm 4c | Read | ||
| AV | 12010 | bac_alarm_5c_12 | Heat pump n°2: Current alarm 5c | Read | ||
| MV | 1200 | bac_status_12 | Heat pump n°2: Run status | Read | 1=Off, 2=Running, 3=Stopping, 4=Delay, 5=Tripout, 6=Ready, 7=Override, 8=Defrost, 9=Run Test, 10=Test | |
| MV | 1202 | bac_alarm_state_12 | Heat pump n°2: Alarm status | Read | 1=Normal, 2=Partial, 3=Shutdown | |
| MV | 1203 | bac_ctrl_typ_12 | Heat pump n°2: Control type | Read | 1=Local, 2=Network, 3=Remote | |
| BV | 1203 | bac_chil_s_s_12 | Heat pump n°2: Command Start/Stop | Read | ||
| BV | 1231 | bac_cap_max_12 | Heat pump n°2: Max Capacity Reached | Read | ||
| BV | 1232 | service_maintenance_alert_12 | Heat pump n°2: Service Maintenance Alert | Read | ||
| BV | 1234 | bac_divvlv_o_12 | Heat pump n°2: Isolation valve open feedback | Read | ||
| BV | 1235 | bac_divvlv_c_12 | Heat pump n°2: Isolation valve close feedback | Read | ||
| AV | 1301 | bac_heatcool_13 | Heat pump n°3: Heat/Cool status | Read | 0=Cooling, 1=Heating | |
| AV | 1304 | bac_cap_t_13 | Heat pump n°3: Percent total capacity | % | Read | |
| AV | 1305 | bac_capa_t_13 | Heat pump n°3: Circuit A total capacity | % | Read | |
| AV | 1306 | bac_capb_t_13 | Heat pump n°3: Circuit B total capacity | % | Read | |
| AV | 1311 | bac_dem_lim_13 | Heat pump n°3: Active demand limit (capacity limitation) | % | Read | |
| AV | 1313 | bac_ctrl_pnt_13 | Heat pump n°3: Control point | °C | Read | |
| AV | 1318 | bac_ewt_13 | Heat pump n°3: Entering water temperature | °C | Read | |
| AV | 1319 | bac_lwt_13 | Heat pump n°3: Leaving water temperature | °C | Read | |
| AV | 1320 | bac_oat_13 | Heat pump n°3: Outdoor air temperature | °C | Read | |
| AV | 1364 | bac_hr_mach_13 | Heat pump n°3: Machine operating hours | hr | Read | |
| AV | 1365 | bac_st_mach_13 | Heat pump n°3: Machine starts number | Read | ||
| AV | 13006 | bac_alarm_1c_13 | Heat pump n°3: Current alarm 1c | Read | ||
| AV | 13007 | bac_alarm_2c_13 | Heat pump n°3: Current alarm 2c | Read | ||
| AV | 13008 | bac_alarm_3c_13 | Heat pump n°3: Current alarm 3c | Read | ||
| AV | 13009 | bac_alarm_4c_13 | Heat pump n°3: Current alarm 4c | Read | ||
| AV | 13010 | bac_alarm_5c_13 | Heat pump n°3: Current alarm 5c | Read | ||
| MV | 1300 | bac_status_13 | Heat pump n°3: Run status | Read | 1=Off, 2=Running, 3=Stopping, 4=Delay, 5=Tripout, 6=Ready, 7=Override, 8=Defrost, 9=Run Test, 10=Test | |
| MV | 1302 | bac_alarm_state_13 | Heat pump n°3: Alarm status | Read | 1=Normal, 2=Partial, 3=Shutdown | |
| MV | 1303 | bac_ctrl_typ_13 | Heat pump n°3: Control type | Read | 1=Local, 2=Network, 3=Remote | |
| BV | 1303 | bac_chil_s_s_13 | Heat pump n°3: Command Start/Stop | Read | ||
| BV | 1331 | bac_cap_max_13 | Heat pump n°3: Max Capacity Reached | Read | ||
| BV | 1332 | service_maintenance_alert_13 | Heat pump n°3: Service Maintenance Alert | Read | ||
| BV | 1334 | bac_divvlv_o_13 | Heat pump n°3: Isolation valve open feedback | Read | ||
| BV | 1335 | bac_divvlv_c_13 | Heat pump n°3: Isolation valve close feedback | Read | ||
| AV | 1401 | bac_heatcool_14 | Heat pump n°4: Heat/Cool status | Read | 0=Cooling, 1=Heating | |
| AV | 1404 | bac_cap_t_14 | Heat pump n°4: Percent total capacity | % | Read | |
| AV | 1405 | bac_capa_t_14 | Heat pump n°4: Circuit A total capacity | % | Read | |
| AV | 1406 | bac_capb_t_14 | Heat pump n°4: Circuit B total capacity | % | Read | |
| AV | 1411 | bac_dem_lim_14 | Heat pump n°4: Active demand limit (capacity limitation) | % | Read | |
| AV | 1413 | bac_ctrl_pnt_14 | Heat pump n°4: Control point | °C | Read | |
| AV | 1418 | bac_ewt_14 | Heat pump n°4: Entering water temperature | °C | Read | |
| AV | 1419 | bac_lwt_14 | Heat pump n°4: Leaving water temperature | °C | Read | |
| AV | 1420 | bac_oat_14 | Heat pump n°4: Outdoor air temperature | °C | Read | |
| AV | 1464 | bac_hr_mach_14 | Heat pump n°4: Machine operating hours | hr | Read | |
| AV | 1465 | bac_st_mach_14 | Heat pump n°4: Machine starts number | Read | ||
| AV | 14006 | bac_alarm_1c_14 | Heat pump n°4: Current alarm 1c | Read | ||
| AV | 14007 | bac_alarm_2c_14 | Heat pump n°4: Current alarm 2c | Read | ||
| AV | 14008 | bac_alarm_3c_14 | Heat pump n°4: Current alarm 3c | Read | ||
| AV | 14009 | bac_alarm_4c_14 | Heat pump n°4: Current alarm 4c | Read | ||
| AV | 14010 | bac_alarm_5c_14 | Heat pump n°4: Current alarm 5c | Read | ||
| MV | 1400 | bac_status_14 | Heat pump n°4: Run status | Read | 1=Off, 2=Running, 3=Stopping, 4=Delay, 5=Tripout, 6=Ready, 7=Override, 8=Defrost, 9=Run Test, 10=Test | |
| MV | 1402 | bac_alarm_state_14 | Heat pump n°4: Alarm status | Read | 1=Normal, 2=Partial, 3=Shutdown | |
| MV | 1403 | bac_ctrl_typ_14 | Heat pump n°4: Control type | Read | 1=Local, 2=Network, 3=Remote | |
| BV | 1403 | bac_chil_s_s_14 | Heat pump n°4: Command Start/Stop | Read | ||
| BV | 1431 | bac_cap_max_14 | Heat pump n°4: Max Capacity Reached | Read | ||
| BV | 1432 | service_maintenance_alert_14 | Heat pump n°4: Service Maintenance Alert | Read | ||
| BV | 1434 | bac_divvlv_o_14 | Heat pump n°4: Isolation valve open feedback | Read | ||
| BV | 1435 | bac_divvlv_c_14 | Heat pump n°4: Isolation valve close feedback | Read |
No points match these filters.
Object ID lookup: Carrier SMS Option 275A point IDs by name
AV501manager_control_mode_5AV526oat_5AV542dhw_threshold_5MV522production_mode_5MV551hmi_display_smart_grid_5BV516diverting_valve_command_5BV517dv_open_fail_5BV519dv_close_fail_5BV521dhw_cmd_5BV522dhw_heater_cmd_5BV523legionella_cmd_5BV524boiler_cmd_5BV525bac_ehs_level_1_5BV526bac_ehs_level_2_5BV527bac_ehs_level_3_5BV529hc_sel_5BV533m2033_5BV534m2091_5BV538standby_mode_5BV547alert_synthesis_5BV548alarm_synthesis_5BV728hoa_alarm_7BV6020hoa_alarm_6AV503dhw_sp_5AV504m3244_5AV505legionella_sp_5AV507m3273_5AV510oat_hyst_boiler_5AV511oat_boiler_5AV522heat_oat_threshold_5AV523cool_oat_threshold_5AV524heat_oat_delay_5AV525cool_oat_delay_5AV540dhw_setpoint_conf_5AV541legionella_setpoint_conf_5MV502on_off_command_5MV521manual_hc_sel_5BV503general_ack_5BV504refrigerant_shutdown_5BV505emergency_shutdown_5BV558bms_start_dhw_5MV2401schedule_state_z1_24MV2501schedule_state_z2_25BV21044schedule_state_21BV2200mode_holiday_22BV26044schedule_state_night_26BV27044schedule_state_dhw_27BV2816schedule_state_legion_27AV268runtime_p1_2AV269runtime_p2_2AV270command_3wv_1_2AV271command_3wv_2_2AV272bac_dew_point_2AV274z1_setpoint_2AV276z2_setpoint_2BV222enable1_2BV223status1_2BV226enable2_2BV227status2_2BV233p1_fail_2BV234p1_hand_2BV235p2_fail_2BV236p2_hand_2BV237floor_sensor_fault_2AV216z1_cool_comfort_setpoint_2AV217z1_cool_eco_setpoint_2AV218z1_cool_away_setpoint_2AV226z1_heat_comfort_setpoint_2AV227z1_heat_eco_setpoint_2AV228z1_heat_away_setpoint_2AV235z2_cool_comfort_setpoint_2AV236z2_cool_eco_setpoint_2AV237z2_cool_away_setpoint_2AV244z2_heat_comfort_setpoint_2AV245z2_heat_eco_setpoint_2AV246z2_heat_away_setpoint_2AV257v1_manual_value_2AV263v2_manual_value_2AV264bac_rh_2AV266bac_high_temp_threshold_2AV267bac_dew_point_hysteresis_2MV200z1_setpoint_input_2MV205z2_setpoint_input_2MV247p1_manual_2MV248p2_manual_2BV200z1_ctrlpnt_method_2BV205z2_ctrlpnt_method_2BV211main1_2BV212main2_2BV217v1_manual_2BV219v2_manual_2AV332vfd_status1_3AV334runtime_p1_3AV335runtime_p2_3AV336diff_press_3BV308enable1_3BV309enable2_3BV310status1_3BV311status2_3BV317press_hi_3BV318press_lo_3BV319p1_fail_3BV320p1_hand_3BV321p2_fail_3BV322p2_hand_3AV302vfd1_manual_3AV305pumps_rotation_type_selector_3AV306man_order_p1_3AV307man_order_p2_3AV317dpstpt_3MV301p_manual_3BV300main1_3BV301main2_3AV433vfd_status1_4AV435runtime_p1_4AV436runtime_p2_4AV437diff_press_4BV408enable1_4BV409enable2_4BV410status1_4BV411status2_4BV417press_hi_4BV418press_lo_4BV419p1_fail_4BV420p1_hand_4BV421p2_fail_4BV422p2_hand_4AV402vfd1_manual_4AV405pumps_rotation_type_selector_4AV406man_order_p1_4AV407man_order_p2_4AV418dpstpt_4MV401p_manual_4BV400main1_4BV401main2_4AV1029nb_run_chillers_1AV1030eff_chlr_chws_temp_stpt_value_1AV1031nb_avail_chillers_1AV1032lwt_evap_temp_1AV1033ewt_evap_temp_1AV1035time_before_acr_1AV1036time_before_rcr_1AV1042next_chill_start_1AV1043next_chill_stop_1AV1066average_plant_capacity_1MV1007ch1_manual_1MV1008ch2_manual_1MV1009ch3_manual_1MV1010ch4_manual_1MV1052ch1_status_1MV1053ch2_status_1MV1054ch3_status_1MV1055ch4_status_1BV137acr_1_1BV139rcr_1_1BV140acr_2_1BV141rcr_2_1BV143acr_3_1BV144acr_active_1BV145rcr_active_1BV154communication_ch1_1BV155communication_ch2_1BV156communication_ch3_1BV157communication_ch4_1BV162ch1_is_running_1BV163command_ch1_1BV164ch2_is_running_1BV165command_ch2_1BV166ch3_is_running_1BV167command_ch3_1BV168ch4_is_running_1BV169command_ch4_1BV185acr_cap_exc_1BV187ch1_fail_1BV188ch1_hand_1BV189ch2_fail_1BV190ch2_hand_1BV191ch3_fail_1BV192ch3_hand_1BV193ch4_fail_1BV194ch4_hand_1BV1019vlv_1_close_alarm_1BV1020vlv_1_open_fail_1BV1035alarm_not_network_1_1BV1036alarm_not_network_2_1BV1037alarm_not_network_3_1BV1038alarm_not_network_4_1BV1043alarm_comm_1_1BV1044alarm_comm_2_1BV1045alarm_comm_3_1BV1046alarm_comm_4_1BV1051vlv_1_open_status_1BV1052vlv_2_open_status_1BV1053vlv_3_open_status_1BV1054vlv_4_open_status_1BV1059vlv_1_close_status_1BV1060vlv_2_close_status_1BV1061vlv_3_close_status_1BV1062vlv_4_close_status_1BV1083ch1_running_dhw_1AV121rotation_type_selector_1AV131man_order_ch1_1AV132man_order_ch2_1AV133man_order_ch3_1AV134man_order_ch4_1AV178demand_limit_ch1_1AV179demand_limit_ch2_1AV180demand_limit_ch3_1AV181demand_limit_ch4_1AV186night_mode_demand_limit_ch1_1AV187night_mode_demand_limit_ch3_1AV190night_mode_demand_limit_ch2_1AV191night_mode_demand_limit_ch4_1MV100max_run_chillers_1MV102min_chlr_number_1BV126main1_1BV127main2_1BV128main3_1BV129main4_1AV1101bac_heatcool_11AV1104bac_cap_t_11AV1105bac_capa_t_11AV1106bac_capb_t_11AV1111bac_dem_lim_11AV1113bac_ctrl_pnt_11AV1118bac_ewt_11AV1119bac_lwt_11AV1120bac_oat_11AV1164bac_hr_mach_11AV1165bac_st_mach_11AV11006bac_alarm_1c_11AV11007bac_alarm_2c_11AV11008bac_alarm_3c_11AV11009bac_alarm_4c_11AV11010bac_alarm_5c_11MV1100bac_status_11MV1102bac_alarm_state_11MV1103bac_ctrl_typ_11BV1103bac_chil_s_s_11BV1131bac_cap_max_11BV1132service_maintenance_alert_11BV1134bac_divvlv_o_11BV1135bac_divvlv_c_11AV1201bac_heatcool_12AV1204bac_cap_t_12AV1205bac_capa_t_12AV1206bac_capb_t_12AV1211bac_dem_lim_12AV1213bac_ctrl_pnt_12AV1218bac_ewt_12AV1219bac_lwt_12AV1220bac_oat_12AV1264bac_hr_mach_12AV1265bac_st_mach_12AV12006bac_alarm_1c_12AV12007bac_alarm_2c_12AV12008bac_alarm_3c_12AV12009bac_alarm_4c_12AV12010bac_alarm_5c_12MV1200bac_status_12MV1202bac_alarm_state_12MV1203bac_ctrl_typ_12BV1203bac_chil_s_s_12BV1231bac_cap_max_12BV1232service_maintenance_alert_12BV1234bac_divvlv_o_12BV1235bac_divvlv_c_12AV1301bac_heatcool_13AV1304bac_cap_t_13AV1305bac_capa_t_13AV1306bac_capb_t_13AV1311bac_dem_lim_13AV1313bac_ctrl_pnt_13AV1318bac_ewt_13AV1319bac_lwt_13AV1320bac_oat_13AV1364bac_hr_mach_13AV1365bac_st_mach_13AV13006bac_alarm_1c_13AV13007bac_alarm_2c_13AV13008bac_alarm_3c_13AV13009bac_alarm_4c_13AV13010bac_alarm_5c_13MV1300bac_status_13MV1302bac_alarm_state_13MV1303bac_ctrl_typ_13BV1303bac_chil_s_s_13BV1331bac_cap_max_13BV1332service_maintenance_alert_13BV1334bac_divvlv_o_13BV1335bac_divvlv_c_13AV1401bac_heatcool_14AV1404bac_cap_t_14AV1405bac_capa_t_14AV1406bac_capb_t_14AV1411bac_dem_lim_14AV1413bac_ctrl_pnt_14AV1418bac_ewt_14AV1419bac_lwt_14AV1420bac_oat_14AV1464bac_hr_mach_14AV1465bac_st_mach_14AV14006bac_alarm_1c_14AV14007bac_alarm_2c_14AV14008bac_alarm_3c_14AV14009bac_alarm_4c_14AV14010bac_alarm_5c_14MV1400bac_status_14MV1402bac_alarm_state_14MV1403bac_ctrl_typ_14BV1403bac_chil_s_s_14BV1431bac_cap_max_14BV1432service_maintenance_alert_14BV1434bac_divvlv_o_14BV1435bac_divvlv_c_14
Integration notes
- Source is the BACnet object spreadsheet (SMS_OPT275A_BACNET_COM) inside Carrier's "BMS Protocols" zip for option 275A; the zip's Modbus files are not used.
- State texts are taken from the description cells (e.g. 1 = OFF / 2 = ON / 3 = Based on Schedule); long descriptions are shortened.
- The heat pump n°1 to n°4 blocks are all printed in the sheet; blocks for heat pumps that are not installed stay unused.
- Zone 2, DHW, boiler and pump-set points only apply when those parts of the plant are configured.
- Integration notes also draw on the SMS IOM control manual (Carrier Europe document 10991, 12-2025).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
How many BACnet points does the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps have?
This list has 315 BACnet objects: 144 analog values, 137 binary values, 34 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet points are writable?
80 of the 315 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps BACnet documentation?
The source is SMS OPT275A BMS Protocols (BACnet object list SMS_OPT275A_BACNET_COM.xlsx) (EN_SMS_OPT275A_BMS_Protocols), published free by Carrier at https://brandportal.carrier.com/asset/081c4b3d-90a3-48e5-a641-f9ee46d25993/EN_SMS_OPT275A_BMS_Protocols.zip.
What are the minimum BACnet points to integrate the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps?
Start with MV 502 on_off_command_5 (On/off command: 1=Off, 2=On, 3=Based on schedule); MV 521 manual_hc_sel_5 (Heating/cooling selection (3 = auto changeover on OAT)); MV 200 z1_setpoint_input_2 (Zone 1 setpoint mode: Eco, Comfort or Auto); AV 226 z1_heat_comfort_setpoint_2 (Zone 1 comfort heating water setpoint); AV 216 z1_cool_comfort_setpoint_2 (Zone 1 comfort cooling water setpoint); BV 505 emergency_shutdown_5 (Emergency shutdown signal from the BMS); AV 501 manager_control_mode_5 (Front panel button: 1=Off, 2=On, 3=Auto); AV 1032 lwt_evap_temp_1 (Common leaving water temperature); MV 1052 ch1_status_1 (Heat pump 1 status (running, failure, no comm...)); BV 548 alarm_synthesis_5 (General (synthesis) alarm).
How do I enable BMS control of the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps?
The system follows the On/Off input command only in the Auto operating type selected with the SMS front button (AV 501 reports it). In Auto the command can be Off, On or Based on Schedule. The network emergency stop shuts the system down in any operating type.
Can the BMS supply sensor values to the Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps?
Zone relative humidity for dew point calculation (AV 264) can be written by the BMS when floor sensors are used.
How do I check these points on the real System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: SMS OPT275A BMS Protocols (BACnet object list SMS_OPT275A_BACNET_COM.xlsx) · EN_SMS_OPT275A_BMS_Protocols. Object names, instances and units are reproduced as published; descriptions are our own.