- 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Rooftop unit controller · BACnet points list
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points) BACnet points list
Updated 7 November 2026
With software 4.X the applied rooftop SmartVu controller publishes a network points list of 129 analog values (configurations, setpoints, BACnet-specific points such as air source linkage and schedule objects, sensors and status) plus 231 binary values in a separate alarm list (one BV per alarm code, with alarm reset and alarm activate). BACnet MS/TP runs on serial port J7 or J8 and BACnet IP on the Ethernet port; only one of CCN or BACnet can be used at a time.
This page lists 360 BACnet objects for the Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points) — 56 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
- Equipment
- Rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 360 (56 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Software version 4.X
- Also known as
- 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Set the J7/J8 serial port (MS/TP) or the IP settings from the SmartVu touchscreen, reboot, then write the network occupancy point after every power cycle and keep network sensor inputs refreshed within the network input timeout. Map the operating mode, occupancy source and filter status, and poll the alarm BVs or Alarm Activate.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 363 | GENUNIT_NETOCC | Network occupancy command (rewrite after power cycle) | Write |
| AV 366 | OCCSBNET | Network occupied standby command | Write |
| AV 291 | MDESTS_OP_STATE | Operating mode (free, mech, staged, heating, dehum...) | Read |
| AV 731 | STATES_OCCSRNUM | Occupancy source in effect (local, BMS, remote...) | Read |
| AV 727 | STATES_IDFNUM | Indoor fan state | Read |
| AV 297 | FILTER_STATUS | Pre-filter status: 0=Clean, 1=Dirty | Read |
| BV 8094 | ALARMRST_ALM_ACT | Alarm active | Read |
| BV 1 | ALARMRST_RST_ALM | Alarm reset command | Write |
Enable & remote start
The network occupancy point must be written after every controller power cycle to set the unit occupied; otherwise it defaults to not used, which leaves the unit unoccupied. It does not time out and keeps its last value if communication is lost.
Heartbeat & communication loss
Network inputs must be written at least every 10 minutes (service configurable) and after a power cycle; if no write arrives, the unit falls back to its local sensor value if one exists.
Sensors & values from the BMS
Sensor values can come from network points (including airside linkage); the touchscreen hides a sensor when its local input is disabled unless set to show it.
Network setup
- J7 can be CCN or BACnet MS/TP (factory wired to the CCN comm board); J8 can be BACnet MS/TP or Rnet.
- Only one BAS protocol (CCN or BACnet) at a time; most configuration changes need a reboot.
- Excel versions of the network points are in the software download file on HVACPartners.
Watch out for
- Software versions before 2.4.0 use different point instances and names; confirm the controller software version first.
- The 4.X list differs from earlier SmartVu lists; do not reuse an older point map without checking instances.
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 8043 | ERVCFG_FLTSC | ERV OA Filter Source | Write | ||
| AV | 615 | FFLTSRC | Final Filter Change Source | Write | ||
| AV | 59 | ALERTCFG_POSTFL | Final Filter Reminder | Write | ||
| AV | 42 | GENUNIT_PREFLTR_SRC | Pre-Filter Change Source | Write | ||
| AV | 146 | ANALOGIN_DLC | Demand Limit Control | Read | ||
| AV | 601 | BACNET_ASL_Air_Src_Mode | ASL Air Source Mode | Write | ||
| AV | 602 | BACNET_ASL_Cooling_Req | ASL Cooling Required | Write | ||
| AV | 603 | BACNET_ASL_Heating_Req | ASL Heating Required | Write | ||
| AV | 604 | BACNET_ASL_Occ_Coolg_Req | ASL Occ Cooling Required | Write | ||
| AV | 605 | BACNET_ASL_Occ_Heatg_Req | ASL Occ Heating Required | Write | ||
| AV | 588 | BACNET_ASL_Occupcy_State | ASL Occupancy State | Write | ||
| AV | 606 | BACNET_ASL_Optimal_Start | ASL Optimal Start | Write | ||
| AV | 295 | BACNET_loc_occ | Local Sched Occ Request | Read | ||
| AV | 740 | BACNET_perc_bac | Percentage Conversion | Write | 0=0.00-1.00, 1=0-100% | |
| AV | 294 | BACNET_SCH_Objj | Sched Linked BACnet Object | Read | ||
| AV | 367 | ZS_OCCSB | Occupied Standby ZS | Write | ||
| AV | 8024 | BACNET_SPL_DEVST | System Touch Device Instance | Write | ||
| AV | 8025 | BACNET_SPL_POLLST | System Touch Polling Rate | Write | ||
| AV | 186 | COOLCFG_DEMAND | Cool/Heat Demand Source | Write | ||
| AV | 189 | COOLCFG_RSTRTIO | SAT Reset Ratio | Write | ||
| AV | 188 | COOLCFG_TPCTLRST | SAT Reset Source | Write | ||
| AV | 208 | DHUMCFG_DMD_SRC | Dehum Demand Source | Write | ||
| AV | 260 | ERVCFG_CHKTYPE | ERV Check Type | Write | ||
| AV | 635 | RELIEF3P | 3rd Party EXF/RTF Input Config | Write | ||
| AV | 8065 | SPR3PIDF | 3rd Party IDF/SPSR Input Config | Write | ||
| AV | 256 | EQUIPCFG_AUXRELAY | Aux Relay Config | Write | ||
| AV | 636 | SIO3AI10 | EAD 3rd Party Mod/BP Input Config | Write | ||
| AV | 303 | EQUIPCFG_FRZSWEN | Hydronic Heat Freeze Input Enable | Read | ||
| AV | 574 | EQUIPCFG_SIO3DI7 | IAQ or OAQ Input Config | Write | ||
| AV | 683 | EQUIPCFG_IAQSWEN | IAQ Switch Input Enable | Read | ||
| AV | 257 | EQUIPCFG_SIO1AI10 | IAQ/OAD Input Config | Write | ||
| AV | 8037 | EQUIPCFG_SIO3AI06 | Limiting/SATR Input Config | Write | ||
| AV | 678 | EQUIPCFG_OAQSWEN | OAQ Switch Input Enable | Read | ||
| AV | 255 | EQUIPCFG_RESWEN | Remote Switch Input Configuration | Write | ||
| AV | 235 | EFCFG_CONTROL | EXF Control Config | Write | ||
| AV | 278 | FRECLCFG_CHNGSEL | Free Cool Changeover Select | Write | ||
| AV | 637 | HEATCFG_OCHTTYPE | Occupied Heating Type | Write | ||
| AV | 322 | IDFCFG_OPSELECT | IDF Control Type | Write | ||
| AV | 337 | IDFCFG_OCCUCFG | IDF Occupied Behavior | Write | ||
| AV | 749 | IDFCFG_OCCSBCFG | IDF Occupied Standby Behavior | Write | ||
| AV | 323 | IDFCFG_SAVTYPE | SAV Mode Selection | Write | ||
| AV | 339 | IDFCFG_SDPRS | SP Reset Source | Write | ||
| AV | 338 | IDFCFG_UNOCCFG | IDF Unoccupied Behavior | Write | ||
| AV | 221 | DMDLMCFG_AICLSEL | Limiting Analog Input Config | Write | ||
| AV | 305 | DMDLMCFG_DMDCPEN | Capacity Limit Enable | Read | ||
| AV | 222 | DMDLMCFG_CAPLMSRC | Capacity Limit Source | Write | ||
| AV | 304 | DMDLMCFG_DMDLMEN | Demand Limit Enable | Read | ||
| AV | 220 | DMDLMCFG_DMDLMSRC | Demand Limit Source | Write | ||
| AV | 706 | MDESTS_CIRCAMDN | Circuit A Mode | Read | 0=NORMAL, 1=TEST, 2=MAX | |
| AV | 707 | MDESTS_CIRCBMDN | Circuit B Mode | Read | 0=NORMAL, 1=TEST, 2=MAX | |
| AV | 708 | MDESTS_CMPA1MDN | Comp A1 Mode | Read | 0=NONE, 1=MANUAL, 2=FLD_TEMP, 3=DP_HIGH, 4=DP_LOW, 5=SP_HIGH, 6=SP_LOW, 7=DT_HIGH, 8=HTSTMPHI, 9=FLDTMPHI, 10=INVTMPHI, 11=RCTTMPHI, 12=OILVISLO, 13=MOTCURHI, 14=CMPSURGE, 15=MODE_MAX, 16=DP_HIGHF, 17=SP_LOWF, 18=SP_LOWSH | |
| AV | 709 | MDESTS_CMPA2MDN | Comp A2 Mode | Read | 0=NONE, 1=MANUAL, 2=FLD_TEMP, 3=DP_HIGH, 4=DP_LOW, 5=SP_HIGH, 6=SP_LOW, 7=DT_HIGH, 8=HTSTMPHI, 9=FLDTMPHI, 10=INVTMPHI, 11=RCTTMPHI, 12=OILVISLO, 13=MOTCURHI, 14=CMPSURGE, 15=MODE_MAX, 16=DP_HIGHF, 17=SP_LOWF, 18=SP_LOWSH | |
| AV | 710 | MDESTS_CMPB1MDN | Comp B1 Mode | Read | 0=NONE, 1=MANUAL, 2=FLD_TEMP, 3=DP_HIGH, 4=DP_LOW, 5=SP_HIGH, 6=SP_LOW, 7=DT_HIGH, 8=HTSTMPHI, 9=FLDTMPHI, 10=INVTMPHI, 11=RCTTMPHI, 12=OILVISLO, 13=MOTCURHI, 14=CMPSURGE, 15=MODE_MAX, 16=DP_HIGHF, 17=SP_LOWF, 18=SP_LOWSH | |
| AV | 711 | MDESTS_CMPB2MDN | Comp B2 Mode | Read | 0=NONE, 1=MANUAL, 2=FLD_TEMP, 3=DP_HIGH, 4=DP_LOW, 5=SP_HIGH, 6=SP_LOW, 7=DT_HIGH, 8=HTSTMPHI, 9=FLDTMPHI, 10=INVTMPHI, 11=RCTTMPHI, 12=OILVISLO, 13=MOTCURHI, 14=CMPSURGE, 15=MODE_MAX, 16=DP_HIGHF, 17=SP_LOWF, 18=SP_LOWSH | |
| AV | 803 | EADMDN | Exhaust Air Damper Mode | Write | 0=NONE, 1=MANUAL, 2=BP, 3=EXT_SIG, 4=OAD_MAP, 5=TRACK, 6=RTF_BP | |
| AV | 640 | MDESTS_EFMDN | Exhaust Fan Mode | Read | 0=NONE, 1=MANUAL, 2=SDP_NOM, 3=SDP_HIGH, 4=SDP_LOW, 5=CO2_NOM, 6=CO2_LOW, 7=CTRL_FLUID, 8=SST_LOW, 9=ST_LOW, 10=FLOW_NOM, 11=BP_NOM, 12=BP_HIGH, 13=BP_LOW, 14=TRACK, 15=ON, 16=OA_EACFM | |
| AV | 638 | MDESTS_EXVA1MN | EXV A1 Mode | Read | 0=NONE, 1=MANUAL, 2=APPROACH, 3=SUBCOOL, 4=LIQ_LVL, 5=SSH, 6=SSH_LOW, 7=DSH_LOW, 8=DST_LOW, 9=DST_HI, 10=SST_LOW, 11=SST_HI, 12=MODE_MAX, 13=DT_HI, 14=SSH_HI, 15=DOP_LOW, 16=SURGE_HI | |
| AV | 639 | MDESTS_EXVA2MN | EXV A2 Mode | Read | 0=NONE, 1=MANUAL, 2=APPROACH, 3=SUBCOOL, 4=LIQ_LVL, 5=SSH, 6=SSH_LOW, 7=DSH_LOW, 8=DST_LOW, 9=DST_HI, 10=SST_LOW, 11=SST_HI, 12=MODE_MAX, 13=DT_HI, 14=SSH_HI, 15=DOP_LOW, 16=SURGE_HI | |
| AV | 689 | MDESTS_EXVB1MN | EXV B1 Mode | Read | 0=NONE, 1=MANUAL, 2=APPROACH, 3=SUBCOOL, 4=LIQ_LVL, 5=SSH, 6=SSH_LOW, 7=DSH_LOW, 8=DST_LOW, 9=DST_HI, 10=SST_LOW, 11=SST_HI, 12=MODE_MAX, 13=DT_HI, 14=SSH_HI, 15=DOP_LOW, 16=SURGE_HI | |
| AV | 690 | MDESTS_EXVB2MN | EXV B2 Mode | Read | 0=NONE, 1=MANUAL, 2=APPROACH, 3=SUBCOOL, 4=LIQ_LVL, 5=SSH, 6=SSH_LOW, 7=DSH_LOW, 8=DST_LOW, 9=DST_HI, 10=SST_LOW, 11=SST_HI, 12=MODE_MAX, 13=DT_HI, 14=SSH_HI, 15=DOP_LOW, 16=SURGE_HI | |
| AV | 716 | MDESTS_HEATRMDN | Heater Mode | Read | 0=NONE, 1=FLD_TEMP, 2=MANUAL, 3=TRACK | |
| AV | 715 | MDESTS_IDFMDNUM | Indoor Fan Mode | Read | 0=NONE, 1=MANUAL, 2=SDP_NOM, 3=SDP_HIGH, 4=SDP_LOW, 5=CO2_NOM, 6=CO2_LOW, 7=CTLFLUID, 8=SST_LOW, 9=ST_LOW, 10=FLOW_NOM, 11=BP_NOM, 12=BP_HIGH, 13=BP_LOW, 14=TRACK, 15=ON, 16=OA_EACFM | |
| AV | 712 | MDESTS_ODF1MDN | ODF 1 Mode | Read | 0=NONE, 1=MANUAL, 2=DP_OPT, 3=DP_LOW, 4=DP_HIGH, 5=DT_HIGH | |
| AV | 713 | MDESTS_ODF2MDN | ODF 2 Mode | Read | 0=NONE, 1=MANUAL, 2=DP_OPT, 3=DP_LOW, 4=DP_HIGH, 5=DT_HIGH | |
| AV | 714 | MDESTS_ODF3MDN | ODF 3 Mode | Read | 0=NONE, 1=MANUAL, 2=DP_OPT, 3=DP_LOW, 4=DP_HIGH, 5=DT_HIGH | |
| AV | 717 | MDESTS_ECONMNUM | Outdoor Air Damper Mode | Read | 0=NONE, 1=MANUAL, 2=AMB_FLOW, 3=MNAIRQLY, 4=NOM_TRAC, 5=SAT, 6=IAQ_OVR, 7=AMBFLWSW | |
| AVmin | 363 | GENUNIT_NETOCC | Net Occupancy Command | Write | 0=UNOCC, 1=OCC, 2=NOT USED | |
| AVmin | 366 | OCCSBNET | Net Occupied Standby Command | Write | 0=NORMAL, 1=OCC STANDBY | |
| AV | 369 | OADCFG_IAQOCFG | IAQ Override Config | Write | ||
| AV | 382 | OADCFG_IAQRESET | IAQ Reset Source | Write | ||
| AV | 396 | OADCFG_OABPOREN | OAD BP Reset Override Enable | Write | ||
| AV | 8130 | UVNTCTRL | Unoccupied Vent Control Type | Write | ||
| AV | 368 | OADCFG_ECONCTRL | Occupied Vent Control Type | Write | ||
| AV | 8075 | EADCTRL | EAD Control Type | Write | ||
| AV | 766 | RFCFG_BPRESET | RTF BP Reset Enable | Write | ||
| AV | 644 | SFAN_RF_CONFIG | RTF Control Type | Write | ||
| AV | 647 | SFAN_RF_SRCRX | SA/RA CFM Reset Max | Write | ||
| AV | 646 | SFAN_RF_SRCRM | SA/RA CFM Reset Min | Write | ||
| AV | 454 | RUNTIME_CCHRA_SC | CCH A Start Count | Read | ||
| AV | 457 | RUNTIME_CCHRB_SC | CCH B Start Count | Read | ||
| AV | 418 | RUNTIME_COMPA1SC | Comp A1 Start Count | Read | ||
| AV | 421 | RUNTIME_COMPA2SC | Comp A2 Start Count | Read | ||
| AV | 424 | RUNTIME_COMPB1SC | Comp B1 Start Count | Read | ||
| AV | 426 | RUNTIME_COMPB2RT | Comp B2 Hours | Read | ||
| AV | 427 | RUNTIME_COMPB2SC | Comp B2 Start Count | Read | ||
| AV | 8060 | RUNTIME_ERVBP_SC | ERV Bypass Damper Start Count | Read | ||
| AV | 801 | MDESTS_ERVMDN | ERV Mode Number | Write | 0=NONE, 1=MANUAL, 2=AMB_FLOW, 3=MNAIRQLY, 4=NOM_TRAC, 5=SAT, 6=IAQ_OVR, 7=AMBFLWSW | |
| AV | 8056 | RUNTIME_ERV_SC | ERV Start Count | Read | ||
| AV | 8136 | STATES_ERVSTEN | ERV State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 623 | RUNTIME_EAD_SC | Exhaust Air Damper Start Count | Read | ||
| AV | 442 | RUNTIME_EFAN_SC | Exhaust Fan Start Count | Read | ||
| AV | 445 | RUNTIME_SHEAT_SC | Heat Start Count | Read | ||
| AV | 448 | RUNTIME_HMVLV_SC | HGRH Valve Start Count | Read | ||
| AV | 465 | RUNTIME_HUMPUSC | Humdimizer Cycle Cnt | Read | ||
| AV | 439 | RUNTIME_IDF_SC | Indoor Fan Start Count | Read | ||
| AV | 451 | RUNTIME_DAMP_SC | OAD Start Count | Read | ||
| AV | 430 | RUNTIME_CND1_SC | ODF 1 Start Count | Read | ||
| AV | 433 | RUNTIME_CND2_SC | ODF 2 Start Count | Read | ||
| AV | 436 | RUNTIME_CND3_SC | ODF 3 Start Count | Read | ||
| AV | 459 | RUNTIME_OILACYSC | Cir A Count | Read | ||
| AV | 460 | RUNTIME_OILBCYSC | Cir B Count | Read | ||
| AV | 626 | GENUNIT_FFLT_RST | Reset Final Filter Hours | Read | ||
| AV | 620 | RUNTIME_RFAN_SC | Return Fan Start Count | Read | ||
| AV | 583 | UNITCFG_OCCUOVER | SPT Occupancy Override Type | Write | ||
| AV | 718 | STATES_CIRCASTN | Circuit A State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 719 | STATES_CIRCBSTN | Circuit B State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 720 | STATES_CMPA1STN | Compressor A1 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 721 | STATES_CMPA2STN | Compressor A2 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 722 | STATES_CMPB1STN | Compressor B1 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 723 | STATES_CMPB2STN | Compressor B2 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 670 | STATES_EFSTN | Exhaust Fan State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 668 | STATES_EXVA1STN | EXV A1 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 669 | STATES_EXVA2STN | EXV A2 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 692 | STATES_EXVB1STN | EXV B1 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 693 | STATES_EXVB2STN | EXV B2 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 729 | STATES_HEATRSTN | Heater State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 728 | STATES_RHTSTNUM | HZMR Bypss Valve State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AVmin | 727 | STATES_IDFNUM | Indoor Fan State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 730 | STATES_ECONNUM | Outdoor Air Damper State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 724 | STATES_ODF1STN | Outdoor Fan 1 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 725 | STATES_ODF2STN | Outdoor Fan 2 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 726 | STATES_ODF3STN | Outdoor Fan 3 State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 732 | STATES_RFNUM | Return Fan State | Read | 0=OFF, 1=NOT_RDY, 2=READY, 3=STARTING, 4=RUNNING, 5=STOPPING, 6=DISABLE, 7=TRIPOUT, 8=MAX | |
| AV | 290 | MDESTS_DMD_DET | Cool/Heat Demand | Read | 0=NONE, 1=LOW COOL, 2=MED COOL, 3=HIGH COOL, 4=VAV Cool, 5=LOW HEAT, 6=HIGH HEAT, 7=VENTILATION, 8=DOAS VENTILATION, 9=FORCED, 10=DOAS COOL, 11=DOAS HEAT, 12=COOL TEMPERED VENT, 13=HEAT TEMPERED VENT | |
| AV | 564 | LABONLY_DHUM_REQ | Dehum Request | Read | 0=NO, 1=YES | |
| AV | 628 | LINKAGE | Linkage Active? | Read | 0=NO, 1=YES | |
| AVmin | 731 | STATES_OCCSRNUM | Occupancy Source | Read | 0=Default Schedule, 1=Local Schedule, 2=BMS Schedule, 3=Remote Switch, 4=Timed Override, 5=Linkage, 6=Forced, 7=Motion Sensing | |
| AVmin | 291 | MDESTS_OP_STATE | Operating Mode | Read | 0=NONE, 1=FREE COOLING, 2=MECH COOLING, 3=INTEGRATED COOLING, 4=TEMPERED COOLING, 5=STAGED GAS HEATIING, 6=MOD GAS HEATING, 7=ELECTRIC HEATING, 8=HYDRONIC HEATING, 9=DEHUM HEATING, 10=DEHUM VENT, 11=DEHUM COOL, 12=VENT, 13=EMERGENCY PRESSURIZATION, 14=SMOKE EVAC, 15=SMOKE PURGE, 16=FIRE SHUTDOWN, 17=COOL TEMPERED VENT, 18=HEAT TEMPERED VENT, 19=OIL RECOVERY, 20=HZMR PURGE, 21=HZMR RECHARGE, 22=COOLING PREVENTED, 23=HEATING PREVENTED, 24=RECYCLE, 25=TEST, 26=EMERGENCY, 27=FREE COOL DEHUM | |
| AVmin | 297 | FILTER_STATUS | Pre-Filter Status | Read | 0=CLEAN, 1=DIRTY | |
| BVmin | 1 | ALARMRST_RST_ALM | Alarm Reset | Write | 0=NO, 1=YES | |
| BVmin | 8094 | ALARMRST_ALM_ACT | Alarm Activate | Read | 0=NORMAL, 1=ALARM | |
| BV | 275 | EVT_301 | COMM:301 - IOB1 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 276 | EVT_302 | COMM:302 - IOB2 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 277 | EVT_303 | COMM:303 - IOB3 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 278 | EVT_304 | COMM:304 - IOB4 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 650 | EVT_305 | COMM:305 - IOB5 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 651 | EVT_306 | COMM:306 - IOB6 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 274 | EVT_310 | COMM:310 - Compressor Drive Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 259 | EVT_320 | COMM:320 - Outdoor Fan 1 VFD Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 261 | EVT_321 | COMM:321 - Outdoor Fan 2 VFD Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 280 | EVT_330 | COMM:330 - Supply Fan VFD Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 320 | EVT_331 | COMM:331 - IDF 1 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 321 | EVT_332 | COMM:332 - IDF 2 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 322 | EVT_333 | COMM:333 - IDF 3 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 323 | EVT_334 | COMM:334 - IDF 4 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 324 | EVT_335 | COMM:335 - IDF 5 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 325 | EVT_336 | COMM:336 - IDF 6 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 335 | EVT_340 | COMM:340 - EXF ECM Fan 1 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 336 | EVT_341 | COMM:341 - EXF ECM Fan 2 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 473 | EVT_342 | COMM:342 - EXF ECM Fan 3 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 611 | EVT_343 | COMM:343 - EXF ECM Fan 4 Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 279 | EVT_344 | COMM:344 - OA CFM Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 638 | EVT_350 | COMM:350 - ERV Wheel Drive Communications Loss | Read | 0=NORMAL, 1=ALARM | |
| BV | 224 | EVT_500 | COOL:500 - Cir A High Pressure Switch Trip | Read | 0=NORMAL, 1=ALARM | |
| BV | 243 | EVT_501 | COOL:501 - Cir A Loss of Charge | Read | 0=NORMAL, 1=ALARM | |
| BV | 244 | EVT_502 | COOL:502 - Cir A Low Saturated Suction Temperature | Read | 0=NORMAL, 1=ALARM | |
| BV | 248 | EVT_503 | COOL:503 - Cir A High Saturated Suction Temperature | Read | 0=NORMAL, 1=ALARM | |
| BV | 251 | EVT_504 | COOL:504 - Cir A High Head Pressure | Read | 0=NORMAL, 1=ALARM | |
| BV | 375 | EVT_505 | COOL:505 - Cir A Circuit Stuck On | Read | 0=NORMAL, 1=ALARM | |
| BV | 376 | EVT_506 | COOL:506 - Cir A Circuit Unexpected Off | Read | 0=NORMAL, 1=ALARM | |
| BV | 302 | EVT_507 | COOL:507 - Cir A Low Pressure Ratio | Read | 0=NORMAL, 1=ALARM | |
| BV | 306 | EVT_508 | COOL:508 - Cir A Flooding Detected | Read | 0=NORMAL, 1=ALARM | |
| BV | 377 | EVT_509 | COOL:509 - Cir A Circuit Failure to Pressurize | Read | 0=NORMAL, 1=ALARM | |
| BV | 266 | EVT_510 | COOL:510 - Cir A Low Oil Level | Read | 0=NORMAL, 1=ALARM | |
| BV | 268 | EVT_511 | COOL:511 - Cir A Oil Recovery Failed | Read | 0=NORMAL, 1=ALARM | |
| BV | 269 | EVT_512 | COOL:512 - Cir A Oil Recovery Interrupted | Read | 0=NORMAL, 1=ALARM | |
| BV | 405 | EVT_513 | COOL:513 - Cir A Suction Pressure | Read | 0=NORMAL, 1=ALARM | |
| BV | 403 | EVT_514 | COOL:514 - Compressor Cycling | Read | 0=NORMAL, 1=ALARM | |
| BV | 439 | EVT_515 | COOL:515 - SDT High Temp | Read | 0=NORMAL, 1=ALARM | |
| BV | 226 | EVT_520 | COOL:520 - Cir B High Pressure Switch Trip | Read | 0=NORMAL, 1=ALARM | |
| BV | 636 | EVT_521 | COOL:521 - Cir B Loss of Charge | Read | 0=NORMAL, 1=ALARM | |
| BV | 246 | EVT_522 | COOL:522 - Cir B Low Saturated Suction Temperature | Read | 0=NORMAL, 1=ALARM | |
| BV | 249 | EVT_523 | COOL:523 - Cir B High Saturated Suction Temperature | Read | 0=NORMAL, 1=ALARM | |
| BV | 253 | EVT_524 | COOL:524 - Cir B High Head Pressure | Read | 0=NORMAL, 1=ALARM | |
| BV | 304 | EVT_527 | COOL:527 - Cir B Low Pressure Ratio | Read | 0=NORMAL, 1=ALARM | |
| BV | 308 | EVT_528 | COOL:528 - Cir B Flooding Detected | Read | 0=NORMAL, 1=ALARM | |
| BV | 378 | EVT_529 | COOL:529 - Cir B Circuit Failure to Pressurize | Read | 0=NORMAL, 1=ALARM | |
| BV | 267 | EVT_530 | COOL:530 - Cir B Low Oil Level | Read | 0=NORMAL, 1=ALARM | |
| BV | 270 | EVT_532 | COOL:532 - Cir B Oil Recovery Interrupted | Read | 0=NORMAL, 1=ALARM | |
| BV | 213 | EVT_550 | COOL:550 - Compressor A1 Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 214 | EVT_551 | COOL:551 - Compressor A1 Stuck on | Read | 0=NORMAL, 1=ALARM | |
| BV | 262 | EVT_552 | COOL:552 - A1 Reverse Rotation | Read | 0=NORMAL, 1=ALARM | |
| BV | 257 | EVT_555 | COOL:555 - Compressor Trip Lock | Read | 0=NORMAL, 1=ALARM | |
| BV | 273 | EVT_556 | COOL:556 - Compressor A1 Drive Warning | Read | 0=NORMAL, 1=ALARM | |
| BV | 255 | EVT_557 | COOL:557 - Digital Scroll High Discharge Temperature | Read | 0=NORMAL, 1=ALARM | |
| BV | 256 | EVT_558 | COOL:558 - Compressor A1 Drive Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 209 | EVT_559 | COOL:559 - VSC High VFD Heat Sink | Read | 0=NORMAL, 1=ALARM | |
| BV | 216 | EVT_560 | COOL:560 - Compressor A2 Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 217 | EVT_561 | COOL:561 - Compressor A2 Stuck on | Read | 0=NORMAL, 1=ALARM | |
| BV | 263 | EVT_562 | COOL:562 - A2 Reverse Rotation | Read | 0=NORMAL, 1=ALARM | |
| BV | 219 | EVT_570 | COOL:570 - Compressor B1 Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 220 | EVT_571 | COOL:571 - Compressor B1 Stuck on | Read | 0=NORMAL, 1=ALARM | |
| BV | 264 | EVT_572 | COOL:572 - B1 Reverse Rotation | Read | 0=NORMAL, 1=ALARM | |
| BV | 222 | EVT_580 | COOL:580 - Compressor B2 Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 223 | EVT_581 | COOL:581 - Compressor B2 Stuck on | Read | 0=NORMAL, 1=ALARM | |
| BV | 265 | EVT_582 | COOL:582 - B2 Reverse Rotation Alarm | Read | 0=NORMAL, 1=ALARM | |
| BV | 359 | EVT_590 | COOL:590 - SAT Below Minimum Threshold | Read | 0=NORMAL, 1=ALARM | |
| BV | 404 | EVT_591 | COOL:591 - OAT Compressor Lockout | Read | 0=NORMAL, 1=ALARM | |
| BV | 444 | EVT_592 | COOL:592 - Cool Capacity Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 326 | EVT_401 | FAN:401 - IDF ECM Fan 1 Error | Read | 0=NORMAL, 1=ALARM | |
| BV | 327 | EVT_402 | FAN:402 - IDF ECM Fan 2 Error | Read | 0=NORMAL, 1=ALARM | |
| BV | 328 | EVT_403 | FAN:403 - IDF ECM Fan 3 Error | Read | 0=NORMAL, 1=ALARM | |
| BV | 329 | EVT_404 | FAN:404 - IDF ECM Fan 4 Error | Read | 0=NORMAL, 1=ALARM | |
| BV | 330 | EVT_405 | FAN:405 - IDF ECM Fan 5 Error | Read | 0=NORMAL, 1=ALARM | |
| BV | 331 | EVT_406 | FAN:406 - IDF ECM Fan 6 Error | Read | 0=NORMAL, 1=ALARM | |
| BV | 258 | EVT_410 | FAN:410 - Outdoor Fan 1 VFD Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 260 | EVT_411 | FAN:411 - Outdoor Fan 2 VFD Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 282 | EVT_420 | FAN:420 - Exhaust Fan 1 VFD Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 283 | EVT_421 | FAN:421 - Exhaust Fan 2 VFD Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 472 | EVT_422 | FAN:422 - Exhaust Fan 3 VFD Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 610 | EVT_423 | FAN:423 - Exhaust Fan 4 VFD Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 442 | EVT_430 | FAN:430 - IDF VFD Bypass Active | Read | 0=NORMAL, 1=ALARM | |
| BV | 390 | EVT_431 | FAN:431 - Supply Fan Limit Switch Trip | Read | 0=NORMAL, 1=ALARM | |
| BV | 344 | EVT_601 | HEAT:601 - Heating Temperature Limit Switch Trip | Read | 0=NORMAL, 1=ALARM | |
| BV | 345 | EVT_602 | HEAT:602 - SAT Above Maximum Threshold | Read | 0=NORMAL, 1=ALARM | |
| BV | 360 | EVT_604 | HEAT:604 - Hydronic Freeze Stat Trip | Read | 0=NORMAL, 1=ALARM | |
| BV | 406 | EVT_605 | HEAT:605 - OAT Heater Lockout | Read | 0=NORMAL, 1=ALARM | |
| BV | 443 | EVT_606 | HEAT:606 - Heat Capacity Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 645 | EVT_607 | HEAT:607 - HeatCo Limit Switch Active | Read | 0=NORMAL, 1=ALARM | |
| BV | 225 | EVT_901 | OBS:901 - Cir A High Pressure Switch Trip | Read | 0=NORMAL, 1=ALARM | |
| BV | 245 | EVT_902 | OBS:902 - Cir A Low Saturated Suction Temperature | Read | 0=NORMAL, 1=ALARM | |
| BV | 250 | EVT_903 | OBS:903 - Cir A High Head Pressure | Read | 0=NORMAL, 1=ALARM | |
| BV | 227 | EVT_904 | OBS:904 - Cir B High Pressure Switch Trip | Read | 0=NORMAL, 1=ALARM | |
| BV | 247 | EVT_905 | OBS:905 - Cir B Low Saturated Suction Temperature | Read | 0=NORMAL, 1=ALARM | |
| BV | 252 | EVT_906 | OBS:906 - Cir B High Head Pressure | Read | 0=NORMAL, 1=ALARM | |
| BV | 212 | EVT_907 | OBS:907 - Compressor A1 Failure Warning | Read | 0=NORMAL, 1=ALARM | |
| BV | 215 | EVT_908 | OBS:908 - Compressor A2 Failure Warning | Read | 0=NORMAL, 1=ALARM | |
| BV | 218 | EVT_909 | OBS:909 - Compressor B1 Failure Warning | Read | 0=NORMAL, 1=ALARM | |
| BV | 221 | EVT_910 | OBS:910 - Compressor B2 Failure Warning | Read | 0=NORMAL, 1=ALARM | |
| BV | 301 | EVT_911 | OBS:911 - Cir A Low Pressure Ratio | Read | 0=NORMAL, 1=ALARM | |
| BV | 303 | EVT_912 | OBS:912 - Cir B Low Pressure Ratio | Read | 0=NORMAL, 1=ALARM | |
| BV | 305 | EVT_913 | OBS:913 - Cir A Flooding Detected | Read | 0=NORMAL, 1=ALARM | |
| BV | 307 | EVT_914 | OBS:914 - Cir B Flooding Detected | Read | 0=NORMAL, 1=ALARM | |
| BV | 379 | EVT_915 | OBS:915 - Cir A Circuit Failure to Pressurize | Read | 0=NORMAL, 1=ALARM | |
| BV | 380 | EVT_916 | OBS:916 - Cir B Circuit Failure to Pressurize | Read | 0=NORMAL, 1=ALARM | |
| BV | 440 | EVT_917 | OBS:917 - Cir A Low Compressor Ratio | Read | 0=NORMAL, 1=ALARM | |
| BV | 441 | EVT_918 | OBS:918 - Cir B Low Compressor Ratio | Read | 0=NORMAL, 1=ALARM | |
| BV | 635 | EVT_919 | OBS:919 - SAT Below Minimum Threshold | Read | 0=NORMAL, 1=ALARM | |
| BV | 211 | EVT_920 | OBS:920 - SPRH Sensor Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 415 | EVT_921 | OBS:921 - High Circuit Charge Alert (Auto-Test) | Read | 0=NORMAL, 1=ALARM | |
| BV | 346 | EVT_922 | OBS:922 - SAT Above Maximum Threshold | Read | 0=NORMAL, 1=ALARM | |
| BV | 229 | EVT_923 | OBS:923 - Outside Air Temperature Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 232 | EVT_924 | OBS:924 - Leaving Evap Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 234 | EVT_925 | OBS:925 - Return Air Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 237 | EVT_926 | OBS:926 - Cir A Discharge Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 240 | EVT_927 | OBS:927 - Cir A Suction Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 309 | EVT_928 | OBS:928 - Static Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 351 | EVT_929 | OBS:929 - Building Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 353 | EVT_930 | OBS:930 - Building Pressure Transducer System Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 384 | EVT_931 | OBS:931 - 3rd Party OA Damper Input Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 386 | EVT_932 | OBS:932 - 3rd Party SF Speed Input Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 388 | EVT_933 | OBS:933 - 3rd Party EF Speed Input Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 393 | EVT_934 | OBS:934 - Supply Air Relative Humidity Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 354 | EVT_935 | OBS:935 - Indoor Air Quality Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 339 | EVT_936 | OBS:936 - Digital Scroll Discharge Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 230 | EVT_201 | SNSR:201 - Outside Air Temperature Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 235 | EVT_202 | SNSR:202 - Return Air Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 231 | EVT_203 | SNSR:203 - Supply Air Temperature Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 338 | EVT_204 | SNSR:204 - Space Temperature Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 382 | EVT_205 | SNSR:205 - Mixed Air Temperature Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 383 | EVT_206 | SNSR:206 - Exhaust Air Temperature Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 392 | EVT_207 | SNSR:207 - Cooling Coil Temperature Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 233 | EVT_208 | SNSR:208 - Leaving Evap Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 8091 | EVT_209 | SNSR:209 - Wheel Leaving Air Temperature Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 347 | EVT_210 | SNSR:210 - Outside Air Relative Humidity Snsr Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 349 | EVT_211 | SNSR:211 - Return Air Relative Humidity Snsr Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 348 | EVT_212 | SNSR:212 - Space Relative Humidity Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 350 | EVT_213 | SNSR:213 - Space Temperature Offset Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 394 | EVT_214 | SNSR:214 - Mixed Air Relative Humidity Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 238 | EVT_230 | SNSR:230 - Cir A Discharge Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 241 | EVT_231 | SNSR:231 - Cir B Suction Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 446 | EVT_232 | SNSR:232 - Cir B Discharge Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 447 | EVT_233 | SNSR:233 - Cir B Suction Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 310 | EVT_234 | SNSR:234 - Static Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 312 | EVT_235 | SNSR:235 - 4-20 mA Static Pressure Reset | Read | 0=NORMAL, 1=ALARM | |
| BV | 352 | EVT_236 | SNSR:236 - Building Pressure Transducer Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 284 | EVT_240 | SNSR:240 - EXV A1 Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 285 | EVT_241 | SNSR:241 - EXV A2 Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 286 | EVT_242 | SNSR:242 - EXV B1 Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 287 | EVT_243 | SNSR:243 - EXV B2 Thermistor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 228 | EVT_250 | SNSR:250 - Supply Air Reset Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 355 | EVT_251 | SNSR:251 - Indoor Air Quality Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 356 | EVT_252 | SNSR:252 - Outdoor Air Quality Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 357 | EVT_253 | SNSR:253 - OA CFM Sensor Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 385 | EVT_260 | SNSR:260 - 3rd Party OA Damper Input Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 387 | EVT_261 | SNSR:261 - 3rd Party SF Speed Input Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 389 | EVT_262 | SNSR:262 - 3rd Party EF Speed Input Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 311 | EVT_263 | SNSR:263 - 4-20 mA Demand Limit Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 449 | EVT_101 | SYS:101 - SIOB1 Low Voltage | Read | 0=NORMAL, 1=ALARM | |
| BV | 450 | EVT_102 | SYS:102 - SIOB2 Low Voltage | Read | 0=NORMAL, 1=ALARM | |
| BV | 451 | EVT_103 | SYS:103 - SIOB3 Low Voltage | Read | 0=NORMAL, 1=ALARM | |
| BV | 452 | EVT_104 | SYS:104 - NGC IOB Low Voltage | Read | 0=NORMAL, 1=ALARM | |
| BV | 210 | EVT_107 | SYS:107 - SPRH Sensor Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 271 | EVT_108 | SYS:108 - Local Emergency Stop Command | Read | 0=NORMAL, 1=ALARM | |
| BV | 272 | EVT_109 | SYS:109 - Emergency Stop Input | Read | 0=NORMAL, 1=ALARM | |
| BV | 281 | EVT_110 | SYS:110 - FFPD Out of Range | Read | 0=NORMAL, 1=ALARM | |
| BV | 288 | EVT_111 | SYS:111 - Space Temperature Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 289 | EVT_112 | SYS:112 - Space Temperature Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 290 | EVT_113 | SYS:113 - Supply Air Temperature Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 291 | EVT_114 | SYS:114 - Supply Air Temperature Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 292 | EVT_115 | SYS:115 - Return Air Temperature Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 293 | EVT_116 | SYS:116 - Return Air Temperature Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 294 | EVT_117 | SYS:117 - Return Air Relative Humidity Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 295 | EVT_118 | SYS:118 - Return Air Relative Humidity Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 296 | EVT_119 | SYS:119 - Building Pressure Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 297 | EVT_120 | SYS:120 - Building Pressure Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 298 | EVT_121 | SYS:121 - IAQ Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 299 | EVT_122 | SYS:122 - OAT Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 300 | EVT_123 | SYS:123 - OAT Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 313 | EVT_124 | SYS:124 - Supply Duct Static Pressure Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 314 | EVT_125 | SYS:125 - Supply Duct Static Pressure Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 333 | EVT_126 | SYS:126 - EXV A1 Motor Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 334 | EVT_127 | SYS:127 - EXV B1 Motor Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 646 | EVT_128 | SYS:128 - EXV A2 Motor Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 647 | EVT_129 | SYS:129 - EXV B2 Motor Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 648 | EVT_130 | SYS:130 - HMV Motor Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 340 | EVT_131 | SYS:131-Thermostat Y2 Input ON without Y1 ON | Read | 0=NORMAL, 1=ALARM | |
| BV | 341 | EVT_132 | SYS:132 - Thermostat W2 Input ON without W1 ON | Read | 0=NORMAL, 1=ALARM | |
| BV | 342 | EVT_133 | SYS:133 - Thermostat Y and W Inputs ON | Read | 0=NORMAL, 1=ALARM | |
| BV | 343 | EVT_134 | SYS:134 - Thermostat G Input OFF on a Call for Cooling | Read | 0=NORMAL, 1=ALARM | |
| BV | 361 | EVT_135 | SYS:135 - Fire Shutdown | Read | 0=NORMAL, 1=ALARM | |
| BV | 362 | EVT_136 | SYS:136 - Smoke Evacuation | Read | 0=NORMAL, 1=ALARM | |
| BV | 363 | EVT_137 | SYS:137 - Pressurization | Read | 0=NORMAL, 1=ALARM | |
| BV | 364 | EVT_138 | SYS:138 - Smoke Purge | Read | 0=NORMAL, 1=ALARM | |
| BV | 367 | EVT_139 | SYS:139 - Dirty Pre-Filter | Read | 0=NORMAL, 1=ALARM | |
| BV | 614 | EVT_140 | SYS:140 - Dirty Final Filter | Read | 0=NORMAL, 1=ALARM | |
| BV | 368 | EVT_141 | SYS:141 - Static Pressure (SP) Not Holding Setpoint | Read | 0=NORMAL, 1=ALARM | |
| BV | 369 | EVT_142 | SYS:142 - Building Pressure (BP) Not Holding Setpoint | Read | 0=NORMAL, 1=ALARM | |
| BV | 395 | EVT_143 | SYS:143 - Static Duct Pressure Above Maximum Threshold | Read | 0=NORMAL, 1=ALARM | |
| BV | 407 | EVT_144 | SYS:144 - MAT Compressor Lockout | Read | 0=NORMAL, 1=ALARM | |
| BV | 408 | EVT_145 | SYS:145 - Condensate Overflow Switch Circuit Lockout | Read | 0=NORMAL, 1=ALARM | |
| BV | 409 | EVT_146 | SYS:146 - Condensate Overflow Switch Unit Lockout | Read | 0=NORMAL, 1=ALARM | |
| BV | 410 | EVT_147 | SYS:147 - Condensate Overflow Switch Circuit | Read | 0=NORMAL, 1=ALARM | |
| BV | 411 | EVT_148 | SYS:148 - Condensate Overflow Switch Unit | Read | 0=NORMAL, 1=ALARM | |
| BV | 412 | EVT_149 | SYS:149 - 3-Phase Power Failure | Read | 0=NORMAL, 1=ALARM | |
| BV | 413 | EVT_150 | SYS:150 - Shutdown Switch Input | Read | 0=NORMAL, 1=ALARM | |
| BV | 437 | EVT_151 | SYS:151 - Refrigerant Dissipation | Read | 0=NORMAL, 1=ALARM | |
| BV | 629 | EVT_152 | SYS:152 - Return Air Pressure Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 632 | EVT_153 | SYS:153 - RAP Below Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 633 | EVT_154 | SYS:154 - RAP Above Limit | Read | 0=NORMAL, 1=ALARM | |
| BV | 634 | EVT_155 | SYS:155 - RAP Out of Range | Read | 0=NORMAL, 1=ALARM | |
| BV | 414 | EVT_156 | SYS:156 - Limp Mode Active | Read | 0=NORMAL, 1=ALARM | |
| BV | 8074 | EVT_157 | SYS:157 - Smoke Detector Shutdown | Read | 0=NORMAL, 1=ALARM | |
| BV | 381 | EVT_701 | VENT:701 - Outside Air Damper Out of Range | Read | 0=NORMAL, 1=ALARM | |
| BV | 453 | EVT_702 | VENT:702 - Combined Dampers Not Open Enough | Read | 0=NORMAL, 1=ALARM | |
| BV | 332 | EVT_703 | VENT:703 - Econ 2 (Return) Damper Stuck or Jammed | Read | 0=NORMAL, 1=ALARM | |
| BV | 358 | EVT_704 | VENT:704 - Excess Outdoor Air | Read | 0=NORMAL, 1=ALARM | |
| BV | 370 | EVT_705 | VENT:705 - Not Economizing When it Should | Read | 0=NORMAL, 1=ALARM | |
| BV | 371 | EVT_706 | VENT:706 - Economizing When it Should Not | Read | 0=NORMAL, 1=ALARM | |
| BV | 372 | EVT_707 | VENT:707 - Damper Not Modulating | Read | 0=NORMAL, 1=ALARM | |
| BV | 373 | EVT_708 | VENT:708 - Economizer Mechanically Disconnected | Read | 0=NORMAL, 1=ALARM | |
| BV | 254 | EVT_720 | VENT:720 - ERV Pressure Switch | Read | 0=NORMAL, 1=ALARM | |
| BV | 637 | EVT_721 | VENT:721 - ERV Wheel Drive Fault | Read | 0=NORMAL, 1=ALARM | |
| BV | 374 | EVT_722 | VENT:722 - ERV Unexpected Defrost | Read | 0=NORMAL, 1=ALARM | |
| BV | 401 | EVT_723 | VENT:723 - ERV Wheel Stuck | Read | 0=NORMAL, 1=ALARM | |
| BV | 402 | EVT_724 | VENT:724 - ERV Wheel Free Spinning | Read | 0=NORMAL, 1=ALARM | |
| BV | 236 | EVT_725 | VENT:725 - Failed Defrost | Read | 0=NORMAL, 1=ALARM | |
| BV | 659 | EVT_726 | VENT:726 - Dirty ERV Filter | Read | 0=NORMAL, 1=ALARM | |
| BV | 8075 | EVT_727 | VENT:727 - ERV Bypas Damper Stuck | Read | 0=NORMAL, 1=ALARM | |
| BV | 8101 | EVT_728 | VENT:728 - ERV Frost Indication | Read | 0=NORMAL, 1=ALARM |
No points match these filters.
Object ID lookup: Carrier 48/50K, 48/50V SmartVu 4.X point IDs by name
AV8043ERVCFG_FLTSCAV615FFLTSRCAV59ALERTCFG_POSTFLAV42GENUNIT_PREFLTR_SRCAV146ANALOGIN_DLCAV601BACNET_ASL_Air_Src_ModeAV602BACNET_ASL_Cooling_ReqAV603BACNET_ASL_Heating_ReqAV604BACNET_ASL_Occ_Coolg_ReqAV605BACNET_ASL_Occ_Heatg_ReqAV588BACNET_ASL_Occupcy_StateAV606BACNET_ASL_Optimal_StartAV295BACNET_loc_occAV740BACNET_perc_bacAV294BACNET_SCH_ObjjAV367ZS_OCCSBAV8024BACNET_SPL_DEVSTAV8025BACNET_SPL_POLLSTAV186COOLCFG_DEMANDAV189COOLCFG_RSTRTIOAV188COOLCFG_TPCTLRSTAV208DHUMCFG_DMD_SRCAV260ERVCFG_CHKTYPEAV635RELIEF3PAV8065SPR3PIDFAV256EQUIPCFG_AUXRELAYAV636SIO3AI10AV303EQUIPCFG_FRZSWENAV574EQUIPCFG_SIO3DI7AV683EQUIPCFG_IAQSWENAV257EQUIPCFG_SIO1AI10AV8037EQUIPCFG_SIO3AI06AV678EQUIPCFG_OAQSWENAV255EQUIPCFG_RESWENAV235EFCFG_CONTROLAV278FRECLCFG_CHNGSELAV637HEATCFG_OCHTTYPEAV322IDFCFG_OPSELECTAV337IDFCFG_OCCUCFGAV749IDFCFG_OCCSBCFGAV323IDFCFG_SAVTYPEAV339IDFCFG_SDPRSAV338IDFCFG_UNOCCFGAV221DMDLMCFG_AICLSELAV305DMDLMCFG_DMDCPENAV222DMDLMCFG_CAPLMSRCAV304DMDLMCFG_DMDLMENAV220DMDLMCFG_DMDLMSRCAV706MDESTS_CIRCAMDNAV707MDESTS_CIRCBMDNAV708MDESTS_CMPA1MDNAV709MDESTS_CMPA2MDNAV710MDESTS_CMPB1MDNAV711MDESTS_CMPB2MDNAV803EADMDNAV640MDESTS_EFMDNAV638MDESTS_EXVA1MNAV639MDESTS_EXVA2MNAV689MDESTS_EXVB1MNAV690MDESTS_EXVB2MNAV716MDESTS_HEATRMDNAV715MDESTS_IDFMDNUMAV712MDESTS_ODF1MDNAV713MDESTS_ODF2MDNAV714MDESTS_ODF3MDNAV717MDESTS_ECONMNUMAV363GENUNIT_NETOCCAV366OCCSBNETAV369OADCFG_IAQOCFGAV382OADCFG_IAQRESETAV396OADCFG_OABPORENAV8130UVNTCTRLAV368OADCFG_ECONCTRLAV8075EADCTRLAV766RFCFG_BPRESETAV644SFAN_RF_CONFIGAV647SFAN_RF_SRCRXAV646SFAN_RF_SRCRMAV454RUNTIME_CCHRA_SCAV457RUNTIME_CCHRB_SCAV418RUNTIME_COMPA1SCAV421RUNTIME_COMPA2SCAV424RUNTIME_COMPB1SCAV426RUNTIME_COMPB2RTAV427RUNTIME_COMPB2SCAV8060RUNTIME_ERVBP_SCAV801MDESTS_ERVMDNAV8056RUNTIME_ERV_SCAV8136STATES_ERVSTENAV623RUNTIME_EAD_SCAV442RUNTIME_EFAN_SCAV445RUNTIME_SHEAT_SCAV448RUNTIME_HMVLV_SCAV465RUNTIME_HUMPUSCAV439RUNTIME_IDF_SCAV451RUNTIME_DAMP_SCAV430RUNTIME_CND1_SCAV433RUNTIME_CND2_SCAV436RUNTIME_CND3_SCAV459RUNTIME_OILACYSCAV460RUNTIME_OILBCYSCAV626GENUNIT_FFLT_RSTAV620RUNTIME_RFAN_SCAV583UNITCFG_OCCUOVERAV718STATES_CIRCASTNAV719STATES_CIRCBSTNAV720STATES_CMPA1STNAV721STATES_CMPA2STNAV722STATES_CMPB1STNAV723STATES_CMPB2STNAV670STATES_EFSTNAV668STATES_EXVA1STNAV669STATES_EXVA2STNAV692STATES_EXVB1STNAV693STATES_EXVB2STNAV729STATES_HEATRSTNAV728STATES_RHTSTNUMAV727STATES_IDFNUMAV730STATES_ECONNUMAV724STATES_ODF1STNAV725STATES_ODF2STNAV726STATES_ODF3STNAV732STATES_RFNUMAV290MDESTS_DMD_DETAV564LABONLY_DHUM_REQAV628LINKAGEAV731STATES_OCCSRNUMAV291MDESTS_OP_STATEAV297FILTER_STATUSBV1ALARMRST_RST_ALMBV8094ALARMRST_ALM_ACTBV275EVT_301BV276EVT_302BV277EVT_303BV278EVT_304BV650EVT_305BV651EVT_306BV274EVT_310BV259EVT_320BV261EVT_321BV280EVT_330BV320EVT_331BV321EVT_332BV322EVT_333BV323EVT_334BV324EVT_335BV325EVT_336BV335EVT_340BV336EVT_341BV473EVT_342BV611EVT_343BV279EVT_344BV638EVT_350BV224EVT_500BV243EVT_501BV244EVT_502BV248EVT_503BV251EVT_504BV375EVT_505BV376EVT_506BV302EVT_507BV306EVT_508BV377EVT_509BV266EVT_510BV268EVT_511BV269EVT_512BV405EVT_513BV403EVT_514BV439EVT_515BV226EVT_520BV636EVT_521BV246EVT_522BV249EVT_523BV253EVT_524BV304EVT_527BV308EVT_528BV378EVT_529BV267EVT_530BV270EVT_532BV213EVT_550BV214EVT_551BV262EVT_552BV257EVT_555BV273EVT_556BV255EVT_557BV256EVT_558BV209EVT_559BV216EVT_560BV217EVT_561BV263EVT_562BV219EVT_570BV220EVT_571BV264EVT_572BV222EVT_580BV223EVT_581BV265EVT_582BV359EVT_590BV404EVT_591BV444EVT_592BV326EVT_401BV327EVT_402BV328EVT_403BV329EVT_404BV330EVT_405BV331EVT_406BV258EVT_410BV260EVT_411BV282EVT_420BV283EVT_421BV472EVT_422BV610EVT_423BV442EVT_430BV390EVT_431BV344EVT_601BV345EVT_602BV360EVT_604BV406EVT_605BV443EVT_606BV645EVT_607BV225EVT_901BV245EVT_902BV250EVT_903BV227EVT_904BV247EVT_905BV252EVT_906BV212EVT_907BV215EVT_908BV218EVT_909BV221EVT_910BV301EVT_911BV303EVT_912BV305EVT_913BV307EVT_914BV379EVT_915BV380EVT_916BV440EVT_917BV441EVT_918BV635EVT_919BV211EVT_920BV415EVT_921BV346EVT_922BV229EVT_923BV232EVT_924BV234EVT_925BV237EVT_926BV240EVT_927BV309EVT_928BV351EVT_929BV353EVT_930BV384EVT_931BV386EVT_932BV388EVT_933BV393EVT_934BV354EVT_935BV339EVT_936BV230EVT_201BV235EVT_202BV231EVT_203BV338EVT_204BV382EVT_205BV383EVT_206BV392EVT_207BV233EVT_208BV8091EVT_209BV347EVT_210BV349EVT_211BV348EVT_212BV350EVT_213BV394EVT_214BV238EVT_230BV241EVT_231BV446EVT_232BV447EVT_233BV310EVT_234BV312EVT_235BV352EVT_236BV284EVT_240BV285EVT_241BV286EVT_242BV287EVT_243BV228EVT_250BV355EVT_251BV356EVT_252BV357EVT_253BV385EVT_260BV387EVT_261BV389EVT_262BV311EVT_263BV449EVT_101BV450EVT_102BV451EVT_103BV452EVT_104BV210EVT_107BV271EVT_108BV272EVT_109BV281EVT_110BV288EVT_111BV289EVT_112BV290EVT_113BV291EVT_114BV292EVT_115BV293EVT_116BV294EVT_117BV295EVT_118BV296EVT_119BV297EVT_120BV298EVT_121BV299EVT_122BV300EVT_123BV313EVT_124BV314EVT_125BV333EVT_126BV334EVT_127BV646EVT_128BV647EVT_129BV648EVT_130BV340EVT_131BV341EVT_132BV342EVT_133BV343EVT_134BV361EVT_135BV362EVT_136BV363EVT_137BV364EVT_138BV367EVT_139BV614EVT_140BV368EVT_141BV369EVT_142BV395EVT_143BV407EVT_144BV408EVT_145BV409EVT_146BV410EVT_147BV411EVT_148BV412EVT_149BV413EVT_150BV437EVT_151BV629EVT_152BV632EVT_153BV633EVT_154BV634EVT_155BV414EVT_156BV8074EVT_157BV381EVT_701BV453EVT_702BV332EVT_703BV358EVT_704BV370EVT_705BV371EVT_706BV372EVT_707BV373EVT_708BV254EVT_720BV637EVT_721BV374EVT_722BV401EVT_723BV402EVT_724BV236EVT_725BV659EVT_726BV8075EVT_727BV8101EVT_728
Integration notes
- This list is for software 4.X and uses different instances from our earlier 48/50K and 48/50V SmartVu list (48-50-ART-SVU-1T); only about 37 of the 129 analog values share an instance with it.
- The table pages are printed rotated; analog values come from Appendix A (BACnet and CCN Network Points) and binary values from Appendix B (Alarms List). Points with no separate BACnet object name use the printed name.
- Access is from the WRITE? column (Yes = writable). Enumerations are kept in the states field as printed (e.g. 0=CLEAN, 1=DIRTY). All Appendix B points are BVs; unless noted 0 = NORMAL and 1 = ALARM.
- Not all points exist on every unit; availability depends on model, size and options. Software before 2.4.0 uses different instances and names.
- Analog value enumerations are kept in the states field as printed (e.g. 0=OFF ... 8=MAX for the component state points).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
How many BACnet points does the Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points) have?
This list has 360 BACnet objects: 129 analog values, 231 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points) BACnet points are writable?
56 of the 360 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points) BACnet documentation?
The source is Applied Rooftop Units with PIC 6.1 Hardware and SmartVu Controls Version 4.X - Integration Guide (Appendix A, BACnet and CCN Network Points; Appendix B, Alarms List) (48-50-ART-SMVU-3T), revision 2026-09, published free by Carrier at https://brandportal.carrier.com/asset/2e92f64c-8801-4bec-9223-b684911196bf/48-50-ART-SMVU-3T.pdf.
What are the minimum BACnet points to integrate the Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)?
Start with AV 363 GENUNIT_NETOCC (Network occupancy command (rewrite after power cycle)); AV 366 OCCSBNET (Network occupied standby command); AV 291 MDESTS_OP_STATE (Operating mode (free, mech, staged, heating, dehum...)); AV 731 STATES_OCCSRNUM (Occupancy source in effect (local, BMS, remote...)); AV 727 STATES_IDFNUM (Indoor fan state); AV 297 FILTER_STATUS (Pre-filter status: 0=Clean, 1=Dirty); BV 8094 ALARMRST_ALM_ACT (Alarm active); BV 1 ALARMRST_RST_ALM (Alarm reset command).
How do I enable BMS control of the Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)?
The network occupancy point must be written after every controller power cycle to set the unit occupied; otherwise it defaults to not used, which leaves the unit unoccupied. It does not time out and keeps its last value if communication is lost.
Does the Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points) need a BACnet heartbeat or have a communication timeout?
Network inputs must be written at least every 10 minutes (service configurable) and after a power cycle; if no write arrives, the unit falls back to its local sensor value if one exists.
Can the BMS supply sensor values to the Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)?
Sensor values can come from network points (including airside linkage); the touchscreen hides a sensor when its local input is disabled unless set to show it.
How do I check these points on the real 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: Applied Rooftop Units with PIC 6.1 Hardware and SmartVu Controls Version 4.X - Integration Guide (Appendix A, BACnet and CCN Network Points; Appendix B, Alarms List) · 48-50-ART-SMVU-3T · rev. 2026-09. Object names, instances and units are reproduced as published; descriptions are our own.