Packaged rooftop unit controller · BACnet points list
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0) BACnet points list
Updated 4 November 2026
SmartVu is a touchscreen unit control that speaks BACnet MS/TP on port J8 or BACnet IP on either Ethernet port, plus CCN. The 48/50LC*H list in this integration guide has 1,049 objects: 572 AVs, 450 BVs and 27 MVs covering temperatures, pressures, setpoints, network inputs, outputs, configuration and alert limits, unit and component states, and one BV per alarm or alert code. The guide gives object name, type, instance, access and a short description, but no units or state texts.
This page lists 1049 BACnet objects for the Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0) — 444 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
- Equipment
- Packaged rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 1049 (444 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- SmartVu version 2.X (PIC 6.0 hardware)
- Also known as
- 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
On the SmartVu Controller Config screens (user password 1111) set Primary BAS Network to BACnet and BACnet Enable to MS/TP or IP, then reboot. Occupancy comes from BACnet schedule objects or the Network Occupancy point (AV 363); write the occupied setpoints directly and read unit states, temperatures and the alarm relay.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 363 | GENUNIT_NETOCC | Network occupancy; Primary BAS Network must be BACnet | Write |
| AV 195 | COOLSTP_CLSP_OCC | Occupied cooling setpoint | Write |
| AV 313 | HEATSTP_HTSP_OCC | Occupied heating setpoint | Write |
| BV 1 | ALARMRST_RST_ALM | Alarm reset command | Write |
| MV 22 | STATES_IDFNUM | Indoor fan state | Read |
| AV 289 | GENUNIT_OCCUPIED | Confirms occupied/unoccupied | Read |
| AV 7 | AIRTEMP_SPT | Space temperature | Read |
| AV 4 | AIRTEMP_SAT | Supply air temperature | Read |
| BV 83 | DISCOUT_ALMOUT | Common alarm relay output | Read |
Enable & remote start
Primary BAS Network sets which network drives the occupancy schedule (BACnet, CCN, a CCN local schedule or none); CCN schedule zero makes the unit always occupied. The guide does not explain the values of Network Occupancy (GENUNIT_NETOCC, AV 363). Occupancy Source (MV 26) shows where occupancy currently comes from.
Heartbeat & communication loss
The list includes Network Input Timeout (SERVICE_NETINTO, AV 500), but the guide does not explain it or give a default.
Sensors & values from the BMS
Writable network inputs include Net SPT (AV 360), Net OAT (AV 362) and network thermostat calls Network Y1/Y2/W1/W2/G/HSTAT (BV 141-146). The guide does not explain how the unit selects them.
Network setup
- Communication settings are on the Controller Config screen, shown only after logging in with the user password 1111.
- BACnet MS/TP on port J8 of the touchscreen: set Serial Port Config to MS/TP, BACnet Enable to MS/TP, then network, MAC, identifier and baud. Max Masters 127 and Max Info Frames 20 or less are recommended; 32 nodes at 76,800 baud, 16 at 38,400.
- BACnet IP on Ethernet 0 (J15) or Ethernet 1 (J16); UDP 47808 by default; BACnet Mgmt Device can be None, Foreign Device or BBMD. Reboot after IP changes.
- The SmartVu is locally biased: don't put it on a network-biased segment; terminate with a TERM485 instead of router end-of-line switches. Fit 120 ohms at the first and last node.
Watch out for
- Many configuration values are AVs or BVs without documented codes; read the current value and check the touchscreen before writing.
- Percentages read as 0.00-1.00 or 0-100 depending on the Percentage Conversion setting.
- Modbus BAS and Rnet on J8 are not supported in this SmartVu version.
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | AIRPRESS_RAP | Return Air Pressure | Read | ||
| AV | 2 | AIRPRESS_SDP | Supply Pressure (SP) | Read | ||
| AV | 3 | AIRPRESS_BP | Building Pressure (BP) | Read | ||
| AVmin | 4 | AIRTEMP_SAT | Supply Air Temp (SAT) | Read | ||
| AV | 5 | AIRTEMP_SATO | Supply Air Temp Offset | Read | ||
| AV | 6 | AIRTEMP_RAT | Return Air Temp (RAT) | Read | ||
| AVmin | 7 | AIRTEMP_SPT | Space Temp (SPT) | Read | ||
| AV | 8 | AIRTEMP_SPTO | Space Temp Offset | Read | ||
| AV | 9 | AIRTEMP_OAT | Outside Air Temp (OAT) | Read | ||
| AV | 10 | AIRTEMP_MAT | Mixed Air Temp (MAT) | Read | ||
| AV | 11 | AIRTEMP_EAT | Exhaust Air Temp (EAT) | Read | ||
| AV | 12 | AIRTEMP_LST | Staged Gas Limit Temp | Read | ||
| AV | 13 | AIRTEMP_LAT | Staged Gas LAT | Read | ||
| AV | 14 | AIRTEMP_EFF_CP | Effective Control Point | Read | ||
| AV | 15 | AIRTEMP_DXLAT | Direct Expansion LAT | Read | ||
| AV | 16 | ALERTCFG_SPRHHL | SPRH High Limit | Write | ||
| AV | 17 | ALERTCFG_SPRHLL | SPRH Low Limit | Write | ||
| AV | 18 | ALERTCFG_SPTLLMTO | SPT Low Occu Limit | Write | ||
| AV | 19 | ALERTCFG_SPTHLMTO | SPT High Occu Limit | Write | ||
| AV | 20 | ALERTCFG_SPTLLMTU | SPT Low Unoc Limit | Write | ||
| AV | 21 | ALERTCFG_SPTHLMTU | SPT High Unoc Limit | Write | ||
| AV | 22 | ALERTCFG_SATLLMTO | SAT Low Occu Limit | Write | ||
| AV | 23 | ALERTCFG_SATHLMTO | SAT High Occu Limit | Write | ||
| AV | 24 | ALERTCFG_SATLLMTU | SAT Low Unoc Limit | Write | ||
| AV | 25 | ALERTCFG_SATHLMTU | SAT High Unoc Limit | Write | ||
| AV | 26 | ALERTCFG_RATLLMTO | RAT Low Occu Limit | Write | ||
| AV | 27 | ALERTCFG_RATHLMTO | RAT High Occu Limit | Write | ||
| AV | 28 | ALERTCFG_RATHLMTU | RAT High Unoc Limit | Write | ||
| AV | 29 | ALERTCFG_RATLLMTU | RAT Low Unoc Limit | Write | ||
| AV | 30 | ALERTCFG_RARH_LT | RARH Low Limit | Write | ||
| AV | 31 | ALERTCFG_RARH_HT | RARH High Limit | Write | ||
| AV | 32 | ALERTCFG_SP_LLMT | SP Low Limit | Write | ||
| AV | 33 | ALERTCFG_SP_HLMT | SP High Limit | Write | ||
| AV | 34 | ALERTCFG_BP_LLMT | BP Low Limit | Write | ||
| AV | 35 | ALERTCFG_BP_HLMT | BP High Limit | Write | ||
| AV | 36 | ALERTCFG_SAT_LTMP | SAT Low Limit | Write | ||
| AV | 37 | ALERTCFG_SAT_HTMP | SAT High Limit | Write | ||
| AV | 38 | ALERTCFG_OAT_LLMT | OAT Low Limit | Write | ||
| AV | 39 | ALERTCFG_OAT_HLMT | OAT High Limit | Write | ||
| AV | 40 | ALERTCFG_IAQ_HLMT | IAQ High Limit | Write | ||
| AV | 41 | ALERTCFG_MAINFLT | Pre-Filter Change Time | Write | ||
| AV | 42 | GENUNIT_PREFLTR_SRC | Pre-Filter Source | Write | ||
| AV | 43 | GENUNIT_PREFLTR_LIM | Pre-Filter Press Limit | Write | ||
| AV | 45 | ALERTCFG2_ERV_ALRT | ERV Frost Alert Limit | Write | ||
| AV | 46 | UNITCFG_PG_SP_DB | Prognostics SP Deadband | Write | ||
| AV | 47 | UNITCFG_PG_BP_DB | Prognostics BP Deadband | Write | ||
| AV | 48 | ALERTCFG_HIGH_SST | High SST Time | Write | ||
| AV | 49 | ALERTCFG_MINSUCA | Min Suc Chg Cir A | Write | ||
| AV | 50 | ALERTCFG_MINDISA | Min Disc Chg Cir A | Write | ||
| AV | 51 | ALERTCFG_MINSUCB | Min Suc Chg Cir B | Write | ||
| AV | 52 | ALERTCFG_MINDISB | Min Disc Chg Cir B | Write | ||
| AV | 53 | ALERTCFG_OFF_PRES | Off Press Ratio | Write | ||
| AV | 54 | ALERTCFG_CMPCMD_T | Compressor Cmd Time | Write | ||
| AV | 55 | ALERTCFG_OCFMSENS | Outdoor Air CFM | Write | ||
| AV | 56 | ALERTCFG_ECMINCFM | OAD Min CFM | Write | ||
| AV | 57 | OADCFG_FLTGAP | OAD Fault Detect Gap | Write | ||
| AV | 58 | OADCFG_FLTTIME | OAD Fault Detect Time | Write | ||
| AV | 59 | ALERTCFG_POSTFL | Final Filter Reminder | Write | ||
| AV | 60 | ALERTCFG_CP_C_TH | Comp Cycling Threshold | Write | ||
| AV | 61 | ALERTCFG_LSST4T | Low SST 4Min Threshold | Write | ||
| AV | 62 | ALERTCFG_LSST2T | Low SST 2Min Threshold | Write | ||
| AV | 63 | ALERTCFG_LSST1T | Low SST 1Min Threshold | Write | ||
| AV | 64 | ALERTCFG_LSST20sT | Low SST 20Sec Threshold | Write | ||
| AV | 65 | ALERTCFG_SSHALOW | Low SSH A Alert | Write | ||
| AV | 66 | ALERTCFG_SSHAPLLO | Low SSH A Part Load Alrt | Write | ||
| AV | 67 | ALERTCFG_SSHAFLLO | Low SSH A Full Load Alrt | Write | ||
| AV | 68 | ALERTCFG_SSHBLOW | Low SSH B Alert | Write | ||
| AV | 69 | ALERTCFG_SSHBPLLO | Low SSH B Part Load Alrt | Write | ||
| AV | 70 | ALERTCFG_SSHBFLLO | Low SSH B Full Load Alrt | Write | ||
| AV | 71 | ALERTCFG_LSSHTIME | Low SSH Alert Time | Write | ||
| AV | 72 | ALERTCFG_LPRL | Low Press Ratio Limit | Write | ||
| AV | 73 | LPRTIME | Low Pressure Ratio Time | Write | ||
| AV | 74 | ALERTCFG_COFS_ACT | COFS Action | Write | ||
| AV | 75 | ALERTCFG_COFS_TRP | COFS Trips | Write | ||
| AV | 76 | ALERTCFG_COFS_TME | COFS Time | Write | ||
| AV | 77 | ALERTCFG_OARADIFF | T24 OA RA diff | Write | ||
| AV | 78 | ALERTCFG_SATMOVE | T24 SAT Move Chk | Write | ||
| AV | 79 | ALERTCFG_SATCHNGE | T24 Sat Change | Write | ||
| AV | 80 | ALERTCFG_MOVEDTEC | T24 Move Detect | Write | ||
| AV | 81 | ALERTCFG_SASETTLE | T24 SAT Settle | Write | ||
| AV | 82 | ALERTCFG_T24ECMIN | T24 Econ Min Pos | Write | ||
| AV | 83 | ALERTCFG_T24ECMAX | T24 Econ Max Pos | Write | ||
| AV | 84 | ALERTCFG_HCDELAY | T24 Heat-Cool Delay | Write | ||
| AV | 85 | EFCFG_RAP_TH | Ret Air Press Threshold | Write | ||
| AV | 86 | ALERTCFG_MSDPT | Static Duct Press Limit | Write | ||
| AV | 87 | CMPSTKTM | Compressor Stuck On Time | Write | ||
| AV | 88 | CMPFLRTM | Compressor Failure Timer | Write | ||
| AV | 89 | HEATSINK_HSCTRLOF | Heat Sink Ctrl Offset | Write | ||
| AV | 90 | HEATSINK_HSHTMPDB | High Heat Sink Temp DB | Write | ||
| AV | 91 | HEATSINK_HSHTEMP | High Heat Sink Temp | Write | ||
| AV | 92 | ANALGOUT_DAMPCMD | OAD Command | Read | ||
| AV | 93 | ANALGOUT_DAMPCMD2 | RAD Cmd | Read | ||
| AV | 94 | ANALGOUT_HEATCMD | Actual heat command | Read | ||
| AV | 95 | ANALGOUT_HMV | HGRH Command | Read | ||
| AV | 96 | ANALGOUT_HMV2 | HGRH 2 Command | Read | ||
| AV | 97 | ANALGOUT_EFCMD | Exhaust Fan Cmd | Read | ||
| AV | 98 | ANALGOUT_ERV_OAF | ERV Outdoor Air Fan | Read | ||
| AV | 99 | ANALGOUT_CMPA1CMD | Comp A1 Command | Read | ||
| AV | 100 | ANALGOUT_CMPA2CMD | Comp A2 Command | Read | ||
| AV | 101 | ANALGOUT_CMPB1CMD | Comp B1 Command | Read | ||
| AV | 102 | ANALGOUT_CMPB2CMD | Comp B2 Command | Read | ||
| AV | 103 | ANALGOUT_IDFCMD | IDF1 Control Command | Read | ||
| AV | 104 | ANALGOUT_ODF1CMD | CF 1 Command | Read | ||
| AV | 105 | ANALGOUT_ODF2CMD | CF 2 Command | Read | ||
| AV | 106 | ANALGOUT_ODF3CMD | CF 3 Command | Read | ||
| AV | 107 | ANALGOUT_EXVA1CMD | EXV A1 Cmd | Read | ||
| AV | 108 | ANALGOUT_EXVA2CMD | EXV A2 Cmd | Read | ||
| AV | 109 | ANALGOUT_EXVB1CMD | EXV B1 Cmd | Read | ||
| AV | 110 | ANALGOUT_EXVB2CMD | EXV B2 Cmd | Read | ||
| AV | 111 | ANALOGIN_OACFM | Outdoor Air CFM | Read | ||
| AV | 112 | ANALOGIN_OACFMRST | Outdoor Air CFM Reset | Read | ||
| AV | 113 | ANALOGIN_OD3P_CMD | OAD 3rd Party Modulation | Read | ||
| AV | 114 | ANALOGIN_EF3P_CMD | EXF 3rd Party Modulation | Read | ||
| AV | 115 | ANALOGIN_SF3P_CMD | IDF 3rd Party Modulation | Read | ||
| AV | 116 | ANALOGIN_IAQOPRST | IAQ OAD Pos Reset | Read | ||
| AV | 117 | ANALOGIN_IAQ | Indoor Air Quality | Read | ||
| AV | 118 | ANALOGIN_OAQ | Outdoor Air Quality | Read | ||
| AV | 119 | ANALOGIN_OARH | Outdoor Air RH (OARH) | Read | ||
| AV | 120 | AIRTEMP_OADP | Outside Air Dew Point | Read | ||
| AV | 121 | ANALOGIN_RARH | Return Air RH (RARH) | Read | ||
| AV | 122 | ANALOGIN_SARH | Supply Air RH (SARH) | Read | ||
| AV | 123 | AIRTEMP_SADP | Supply Air Dew Point | Read | ||
| AV | 124 | ANALOGIN_SPRH | Space RH (SPRH) | Read | ||
| AV | 125 | ANALOGIN_MARH | Mixed Air RH (MARH) | Read | ||
| AV | 126 | ANALOGIN_ZDP | Zone Damper Position | Read | ||
| AV | 127 | ANALOGIN_DAMPPOS | OAD Feedback | Read | ||
| AV | 128 | ANALOGIN_DAMPPOS2 | RAD Feedback | Read | ||
| AV | 129 | ANALOGIN_HMD | HGRH Valve Feedback | Read | ||
| AV | 130 | ANALOGIN_HMD2 | HGRH Valve 2 Feedback | Read | ||
| AV | 131 | ANALOGIN_CMPA1SPD | Comp A1 Speed | Read | ||
| AV | 132 | ANALOGIN_CMPA2SPD | Comp A2 Speed | Read | ||
| AV | 133 | ANALOGIN_CMPB1SPD | Comp B1 Speed | Read | ||
| AV | 134 | ANALOGIN_CMPB2SPD | Comp B2 Speed | Read | ||
| AV | 135 | ANALOGIN_ODF1SPD | CF 1 Speed | Read | ||
| AV | 136 | ANALOGIN_ODF2SPD | CF 2 Speed | Read | ||
| AV | 137 | ANALOGIN_ODF3SPD | CF 3 Speed | Read | ||
| AV | 138 | ANALOGIN_IDFSPD | IDF Speed | Read | ||
| AV | 139 | ANALOGIN_IDFRPM | IDF Speed RPM | Read | ||
| AV | 140 | ANALOGIN_EFSPD | Exhaust Fan Speed | Read | ||
| AV | 141 | ANALOGIN_EXV_A1 | EXV A1 | Read | ||
| AV | 142 | ANALOGIN_EXV_A2 | EXV A2 | Read | ||
| AV | 143 | ANALOGIN_EXV_B1 | EXV B1 | Read | ||
| AV | 144 | ANALOGIN_EXV_B2 | EXV B2 | Read | ||
| AV | 145 | ANALOGIN_SPSR | Static Pressure Stpt Rst | Read | ||
| AV | 146 | ANALOGIN_DLC | Demand Limit Control | Read | ||
| AV | 147 | ANALOGIN_PFPD | Pre Filt Press Drop | Read | ||
| AV | 148 | ANALOGIN_FFPD | Final Filt Press Drop | Read | ||
| AV | 149 | ANALOGIN_OA_ENTH | Outdoor Air Enthalpy | Read | ||
| AV | 150 | ANALOGIN_RA_ENTH | Return Air Enthalpy | Read | ||
| AV | 151 | EMPTY_NOPOINT | Menu is empty | Read | ||
| AV | 152 | COMMADDR_AUX1 | AUX | Read | ||
| AV | 153 | COMMADDR_NGC1 | NGC IOB 1 | Read | ||
| AV | 154 | COMMADDR_PD4_EXV1 | PD4 EXV | Read | ||
| AV | 155 | COMMADDR_SIOB1 | SIOB 1 | Read | ||
| AV | 156 | COMMADDR_SIOB2 | SIOB 2 | Read | ||
| AV | 157 | COMMADDR_SIOB3 | SIOB 3 | Read | ||
| AV | 158 | COMMADDR_SYSTEMVU | ZIOB | Read | ||
| AV | 159 | COMMADDR_COMP_A1 | Compressor A1 | Read | ||
| AV | 160 | COMMADDR_IDF_1 | Supply Fan 1 | Read | ||
| AV | 161 | COMMADDR_IDF_2 | Supply Fan 2 | Read | ||
| AV | 162 | COMMADDR_IDF_3 | Supply Fan 3 | Read | ||
| AV | 163 | COMMADDR_IDF_4 | Supply Fan 4 | Read | ||
| AV | 164 | COMMADDR_IDF_5 | Supply Fan 5 | Read | ||
| AV | 165 | COMMADDR_IDF_6 | Supply Fan 6 | Read | ||
| AV | 166 | COMMADDR_ODF_1 | ODF 1 | Read | ||
| AV | 167 | COMMADDR_ODF_2 | ODF 2 | Read | ||
| AV | 168 | COMMADDR_ODF_3 | ODF 3 | Read | ||
| AV | 169 | COMMADDR_RF_1 | Return Fan 1 | Read | ||
| AV | 170 | COMMADDR_RF_2 | Return Fan 2 | Read | ||
| AV | 171 | COMMADDR_PWREXH_1 | Power Exhaust 1 | Read | ||
| AV | 172 | COMMADDR_PWREXH_2 | Power Exhaust 2 | Read | ||
| AV | 173 | LEN_status | LEN SCAN Status | Read | ||
| AV | 174 | LEN_nb_message_10s | Nbr of messges in 10 s | Read | ||
| AV | 175 | LEN_nb_nb_arh_busy_10s | Nbr of ARH busy in 10 s | Read | ||
| AV | 176 | LEN_total_nb_arh_busy | Number of ARH busy | Read | ||
| AV | 177 | LEN_total_nb_message | Number of Message | Read | ||
| AV | 178 | LEN_total_nb_nack | Number of NACK | Read | ||
| AV | 179 | LEN_total_nb_no_resp | Number of no response | Read | ||
| AV | 180 | MODSCAN_status | Modbus SCAN Status | Read | ||
| AV | 181 | MODSCAN_nb_message_10s | Nbr of messges in 10 s | Read | ||
| AV | 182 | MODSCAN_total_nb_message | Nbr of Messages | Read | ||
| AV | 183 | MODSCAN_total_nb_nack | Number of NACK | Read | ||
| AV | 184 | MODSCAN_total_nb_no_resp | Number of no response | Read | ||
| AV | 185 | MODSCAN_total_nb_rtry_fl | Number of retry fails | Read | ||
| AV | 186 | COOLCFG_DEMAND | Cool/Heat Demand Source | Write | ||
| AV | 187 | COOLCFG_SPLYDB | Vent Deadband | Write | ||
| AV | 188 | COOLCFG_TPCTLRST | SAT Reset Source | Write | ||
| AV | 189 | COOLCFG_RSTRTIO | SAT Reset Ratio | Write | ||
| AV | 190 | COOLCFG_RSTLMIT | SAT Reset Limit | Write | ||
| AV | 191 | COOLCFG_CLTREND | Cool Trend Level | Write | ||
| AV | 192 | COOLCFG_CLTNDTM | Cool Trend Time | Write | ||
| AV | 193 | COOLCFG_GAP_CLHT | Cool Heat Gap Config | Write | ||
| AV | 194 | SERVICE_TCSTCOOL | TC Start Cool Factor | Write | ||
| AVmin | 195 | COOLSTP_CLSP_OCC | Occupied Cooling | Write | ||
| AV | 196 | COOLSTP_CLSP_UNO | Unoccupied Cooling | Write | ||
| AV | 197 | COOLSTP_SALOCLSP | Lo Cool SAT | Write | ||
| AV | 198 | COOLSTP_SAHICLSP | Hi Cool SAT | Write | ||
| AV | 199 | COOLSTP_HODALCL | 100% OA Low Cool SAT | Write | ||
| AV | 200 | COOLSTP_HODAHCL | 100% OA High Cool SAT | Write | ||
| AV | 201 | COOLCFG_DOLOCLON | Lo Cool On DB | Write | ||
| AV | 202 | COOLCFG_DOLOCLOF | Lo Cool Off DB | Write | ||
| AV | 203 | COOLCFG_DOHICLON | Hi Cool On DB | Write | ||
| AV | 204 | COOLSTP_VAVCLSP | VAV Cooling SAT | Write | ||
| AV | 205 | COOLCFG_DOVAVCON | VAV Cool On DB | Write | ||
| AV | 206 | COOLCFG_DOVAVCOF | VAV Cool Off DB | Write | ||
| AV | 207 | COOLSTP_SPLYAVSP | Vent SAT | Write | ||
| AV | 208 | DHUMCFG_DMD_SRC | Dehum Demand Source | Write | ||
| AV | 209 | DHUMCFG_DHMATLCK | High MT Dehum Lockout | Write | ||
| AV | 210 | DHUMCFG_RHTOPTME | HGRH Coil Open Time | Write | ||
| AV | 211 | DHUMCFG_RHTCLTME | HGRH Coil Closed Time | Write | ||
| AV | 212 | DHUMCFG_CCBYPTME | Con Coil Bypass Time | Write | ||
| AV | 213 | DHUMCFG_CCPRGPOS | Cond Coil Purge Pos | Write | ||
| AV | 214 | DHUMCFG_CCPRGTME | Cond Coil Purge Time | Write | ||
| AV | 215 | DHUMSTP_DHUMRHSP | Dehum RH | Write | ||
| AV | 216 | DHUMCFG_RLOS_ON | Dehum RH On DB | Write | ||
| AV | 217 | DHUMCFG_RLOS_OFF | Dehum RH Off DB | Write | ||
| AV | 218 | DHUMSTP_CCTSTP | Dehum CCT | Write | ||
| AV | 219 | DISCOUT_POWEXH1 | Power Exhaust Enable | Read | ||
| AV | 220 | DMDLMCFG_DMDLMSRC | Demand Limit Source | Write | ||
| AV | 221 | DMDLMCFG_AICLSEL | Analog Limit Mode | Write | ||
| AV | 222 | DMDLMCFG_CAPLMSRC | Capacity Limit Source | Write | ||
| AV | 223 | COOLSTP_CLCAPSTP | Max Cool Capacity | Write | ||
| AV | 224 | COOLSTP_CAPLIMS1 | Cool Capacity Limit S1 | Write | ||
| AV | 225 | COOLSTP_CAPLIMS2 | Cool Capacity Limit S2 | Write | ||
| AV | 226 | COOLSTP_DMDLIMS1 | Cool Demand Limit S1 | Write | ||
| AV | 227 | COOLSTP_DMDLIMS2 | Cool Demand Limit S2 | Write | ||
| AV | 228 | HEATSTP_HTCAPSTP | Max Heat Capacity | Write | ||
| AV | 229 | HEATSTP_CAPLIMS1 | Heat Capacity Limit S1 | Write | ||
| AV | 230 | HEATSTP_CAPLIMS2 | Heat Capacity Limit S2 | Write | ||
| AV | 231 | HEATSTP_DMDLIMS1 | Heat Demand Limit S1 | Write | ||
| AV | 232 | HEATSTP_DMDLIMS2 | Heat Demand Limit S2 | Write | ||
| AV | 233 | COOLSTP_DMDRSTCL | Dmd Reset Cool Adjust | Write | ||
| AV | 234 | HEATSTP_DMDRSTHT | Dmd Reset Heat Adjust | Write | ||
| AV | 235 | EFCFG_CONTROL | EXF Control Config | Write | ||
| AV | 236 | EFCFG_MINSPD | EXF Min Speed | Write | ||
| AV | 237 | EFCFG_MAXSPD | EXF Max Speed | Write | ||
| AV | 238 | EFCFG_SPEED1 | EXF Speed OAD Pos 1 | Write | ||
| AV | 239 | EFCFG_SPEED2 | EXF Speed OAD Pos 2 | Write | ||
| AV | 240 | EFCFG_DAMPPOS1 | EXF OAD Pos 1 | Write | ||
| AV | 241 | EFCFG_DAMPPOS2 | EXF OAD Pos 2 | Write | ||
| AV | 242 | EFCFG_PEOAD1 | EXF OAD Position 1 | Write | ||
| AV | 243 | EFCFG_PEOAD2 | EXF OAD Position 2 | Write | ||
| AV | 244 | EFCFG_PEOAD3 | EXF OAD Position 3 | Write | ||
| AV | 245 | EFCFG_PEOAD4 | EXF OAD Position 4 | Write | ||
| AV | 246 | EFCFG_PEOAD5 | EXF OAD Position 5 | Write | ||
| AV | 247 | EFCFG_PEOAD6 | EXF OAD Position 6 | Write | ||
| AV | 248 | EFCFG_EXFPURGE | EXF Smoke Purge Speed | Write | ||
| AV | 249 | EFCFG_EXFEVAC | EXF Evacuation Speed | Write | ||
| AV | 250 | EFSTP_EFBPSPT | Building Pressure | Write | ||
| AV | 251 | EMAILCFG_Send | Send Email option | Write | ||
| AV | 252 | EMAILCFG_portNbr | Port Number | Write | ||
| AV | 253 | EMAILCFG_srvTim | Server Timeout | Write | ||
| AV | 254 | EMAILCFG_attach_blackbox | Attach Blackbox Log | Write | ||
| AV | 255 | EQUIPCFG_RESWEN | Remote Input | Write | ||
| AV | 256 | EQUIPCFG_AUXRELAY | Aux Relay | Write | ||
| AV | 257 | EQUIPCFG_SIO1AI10 | IAQ/OAD Input Config | Write | ||
| AV | 258 | OCCSTNDT | Occupied Standby Time | Write | ||
| AV | 259 | UNITCFG_OCC_OT | Occupancy Override Time | Write | ||
| AV | 260 | ERVCFG_CHKTYPE | ERV Check Type | Write | ||
| AV | 261 | ERVCFG_TMPTOL | ERV Temp Tolerance | Write | ||
| AV | 262 | ERVCFG_ENTTOL | ERV Enthalpy Tolerance | Write | ||
| AV | 263 | ERVCFG_MAXBYPOP | ERV Fan Max Bypass Open | Write | ||
| AV | 264 | ERVCFG_MAXBYPCL | ERV Fan Max Bypass Close | Write | ||
| AV | 265 | ERVCFG_ERVMINPS | ERV Fan Damper Min Pos | Write | ||
| AV | 266 | ERVCFG_WHMINPOS | ERV Wheel-Minimum Pos | Write | ||
| AV | 267 | ERVCFG_ERVEFMIN | ERV Wheel Exh Min Speed | Write | ||
| AV | 268 | ERVCFG_OFFTMPDB | ERV Off Temp DB | Write | ||
| AV | 269 | ERVCFG_OFFENTDB | ERV Off Enthalpy DB | Write | ||
| AV | 270 | EXVSTP_SupHtA1 | A1 Superheat Setpoint | Write | ||
| AV | 271 | EXVSTP_SupHtA2 | A2 Superheat Setpoint | Write | ||
| AV | 272 | EXVSTP_SupHtB1 | B1 Superheat Setpoint | Write | ||
| AV | 273 | EXVSTP_SupHtB2 | B2 Superheat Setpoint | Write | ||
| AV | 274 | EXVSTP_EXVSTA1 | A1 Start Pos | Write | ||
| AV | 275 | EXVSTP_EXVSTA2 | A2 Start Pos | Write | ||
| AV | 276 | EXVSTP_EXVSTB1 | B1 Start Pos | Write | ||
| AV | 277 | EXVSTP_EXVSTB2 | B2 Start Pos | Write | ||
| AV | 278 | FRECLCFG_CHNGSEL | Changeover Select | Write | ||
| AV | 279 | FRECLCFG_DIFFENTH | Diff Enthalpy Threshold | Write | ||
| AV | 280 | FRECLCFG_DRYBLBTH | OAT Dry Bulb Threshold | Write | ||
| AV | 281 | FRECLCFG_DEWLIMTH | OADP Threshold | Write | ||
| AV | 282 | FRECLCFG_DIFFDBTH | Diff Dry Bulb Threshold | Write | ||
| AV | 283 | FRECLCFG_IAQOADRS | IAQ Switch OAD Pos Reset | Write | ||
| AV | 284 | HCSTATUS_HEATREQ | Heat Request from UI | Read | ||
| AV | 285 | HCSTATUS_SATCTLPT | Supply Air Temp Cntrl Pt | Read | ||
| AV | 286 | HCSTATUS_CAPACT | Cooling Capacity | Read | ||
| AV | 287 | IDFSTP_ZPSETPT | Zone Pressure | Read | ||
| AV | 288 | IDFCFG_SDPRLMIT | SP Reset Limit | Read | ||
| AVmin | 289 | GENUNIT_OCCUPIED | Occupied | Read | ||
| AV | 290 | MDESTS_DMD_DET | Demand Determination | Read | ||
| AV | 291 | MDESTS_OP_STATE | Operational State | Read | ||
| AV | 292 | GENUNIT_HEATCOOL | Heat/Cool status | Read | ||
| AV | 293 | RFGTEMP_CCT | Cooling Coil Temp | Read | ||
| AV | 294 | BACNET_SCH_Objj | Sched Linked BACnet Obj | Read | ||
| AV | 295 | BACNET_loc_occ | Local Sched Occ Request | Read | ||
| AV | 296 | COOLSTP_HODACLSP | 100% OA Cool SAT | Read | ||
| AV | 297 | FILTER_STATUS | Filter Status | Read | ||
| AV | 298 | SERVICE1_M_FILTER | Pre-Filter Hours | Read | ||
| AV | 299 | RFGTEMP_SGT1 | Suction Gas Temp 1 | Read | ||
| AV | 300 | RFGTEMP_DGTA | Discharge Gas Temp A | Read | ||
| AV | 301 | HMZR_CONDPURG | Humidizer Purge | Read | ||
| AV | 302 | DHUMSTP_DHUMSADP | Dehum SADP | Read | ||
| AV | 303 | EQUIPCFG_FRZSWEN | Freeze Switch | Read | ||
| AV | 304 | DMDLMCFG_DMDLMEN | Demand Limit Enable | Read | ||
| AV | 305 | DMDLMCFG_DMDCPEN | Capacity Limit Enable | Read | ||
| AV | 306 | HEATCFG_HEATTTDB | Heat Tempered Cooling DB | Write | ||
| AV | 307 | HEATCFG_HTTREND | Heat Trend Level | Write | ||
| AV | 308 | HEATCFG_HTTNDTM | Heat Trend Time | Write | ||
| AV | 309 | HEATCFG_HT2DTG | Heat 2Stage Dn Timeguard | Write | ||
| AV | 310 | HEATCFG_HT2UTG | Heat 2Stage Up Timeguard | Write | ||
| AV | 311 | SERVICE_TCSTHEAT | TC Start Heat Factor | Write | ||
| AV | 312 | HEATCFG_HEAT_FOD | Heat Fan Off Delay Timer | Write | ||
| AVmin | 313 | HEATSTP_HTSP_OCC | Occupied Heating | Write | ||
| AV | 314 | HEATSTP_HTSP_UNO | Unoccupied Heating | Write | ||
| AV | 315 | HEATSTP_SALOHTSP | Lo Heat SAT | Write | ||
| AV | 316 | HEATSTP_SAHIHTSP | Hi Heat SAT | Write | ||
| AV | 317 | HEATSTP_HODALHT | 100% OA Low Heat SAT | Write | ||
| AV | 318 | HEATSTP_HODAHHT | 100% OA High Heat SAT | Write | ||
| AV | 319 | HEATCFG_DOLOHTON | Lo Heat On DB | Write | ||
| AV | 320 | HEATCFG_DOLOHTOF | Lo Heat Off DB | Write | ||
| AV | 321 | HEATCFG_DOHIHTON | Hi Heat On DB | Write | ||
| AV | 322 | IDFCFG_OPSELECT | IDF Control | Write | ||
| AV | 323 | IDFCFG_SAVTYPE | SAV Mode Selection | Write | ||
| AV | 324 | IDFCFG_IDFMNSPD | Indoor Fan Min Speed | Write | ||
| AV | 325 | IDFCFG_IDFMXSPD | Indoor Fan Max Speed | Write | ||
| AV | 326 | IDFCFG_IDFCSPD1 | Lo Cool IDF Speed | Write | ||
| AV | 327 | IDFCFG_IDFMCSPD | Med Cool IDF Speed | Write | ||
| AV | 328 | IDFCFG_IDFCSPD2 | Hi Cool IDF Speed | Write | ||
| AV | 329 | IDFCFG_SAVLCCTH | SAV Low Cool Cap Thresh | Write | ||
| AV | 330 | IDFCFG_SAVMCCTH | SAV Med Cool Cap Thresh | Write | ||
| AV | 331 | IDFCFG_SAVHCCTH | SAV High Cool Cap Thresh | Write | ||
| AV | 332 | IDFCFG_IDFHSPD1 | Lo Heat IDF Speed | Write | ||
| AV | 333 | IDFCFG_IDFHSPD2 | Hi Heat IDF Speed | Write | ||
| AV | 334 | IDFCFG_IDFPURGE | IDF PURGE Speed | Write | ||
| AV | 335 | IDFCFG_IDFPRESS | IDF Pressurization Speed | Write | ||
| AV | 336 | IDFCFG_IDFEVAC | IDF Evacuation Speed | Write | ||
| AV | 337 | IDFCFG_OCCUCFG | Occupied Fan | Write | ||
| AV | 338 | IDFCFG_UNOCCFG | Unoccupied Fan | Write | ||
| AV | 339 | IDFCFG_SDPRS | SP Reset Source | Write | ||
| AV | 340 | IDFCFG_SDPRRTIO | SP Reset Ratio | Write | ||
| AV | 341 | IDFCFG_SDPRTIME | SDP Reset Time | Write | ||
| AV | 342 | IDFCFG_SDPRZDP | SDP Reset ZDP Threshold | Write | ||
| AV | 343 | IDFSTP_CO2LVL | CO2 Level | Write | ||
| AV | 344 | IDFSTP_DUCTSET | Supply Pressure | Write | ||
| AV | 345 | IDFSTP_AIRFLOW | Air Flow Setpoint | Write | ||
| AV | 346 | CMPASTS_BOOSTSTA | Cir A VSC Boost State | Read | ||
| AV | 347 | ANALOGIN_SPRHNET | Net SPRH | Write | ||
| AV | 348 | ANALOGIN_RARHNET | Net RARH | Write | ||
| AV | 349 | ANALOGIN_OACFMNET | Net Outdoor Air CFM | Write | ||
| AV | 350 | ANALOGIN_OCFMRNET | Net OA CFM Reset | Write | ||
| AV | 351 | ANALOGIN_IAQORNET | Net IAQ OAD Pos Reset | Write | ||
| AV | 352 | AIRPRESS_BPNET | Net Building Pressure | Write | ||
| AV | 353 | ANALOGIN_EF3P_NET | Net 3rd Party EXF | Write | ||
| AV | 354 | ANALOGIN_OD3P_NET | Net 3rd Party OAD | Write | ||
| AV | 355 | ANALOGIN_SF3P_NET | Net 3rd Party IDF | Write | ||
| AV | 356 | ANALOGIN_OAQNET | Net Outdoor Air Quality | Write | ||
| AV | 357 | ANALOGIN_IAQNET | Net Indoor Air Quality | Write | ||
| AV | 358 | ANALOGIN_IAQRNET | Net IAQ Reset | Write | ||
| AV | 359 | AIRPRESS_SDP_NET | Network Supply Pressure | Write | ||
| AV | 360 | AIRTEMP_SPTNET | Net SPT | Write | ||
| AV | 361 | AIRTEMP_SPTONET | Net Space Temp Offset | Write | ||
| AV | 362 | AIRTEMP_OATNET | Net OAT | Write | ||
| AVmin | 363 | GENUNIT_NETOCC | Network Occupancy | Write | ||
| AV | 364 | ANALOGIN_SPSR_NET | Net SP Reset | Write | ||
| AV | 365 | ANALOGIN_ZDPNET | Net Zone Damper Position | Write | ||
| AV | 366 | OCCSBNET | Occupied Standby Net | Write | ||
| AV | 367 | ZS_OCCSB | Occupied Standby ZS | Write | ||
| AV | 368 | OADCFG_ECONCTRL | Ventilation Control | Write | ||
| AV | 369 | OADCFG_IAQOCFG | IAQ Override Conf | Write | ||
| AV | 370 | OADCFG_MINPOS | OAD Min Position | Write | ||
| AV | 371 | OADCFG_MAXPOS | OAD Max Position | Write | ||
| AV | 372 | OADCFG_MINOADCP | Min OAD Control Point | Write | ||
| AV | 373 | OADCFG_OADEVAC | OAD Smoke Evac Speed | Write | ||
| AV | 374 | IDFCFG_VENTSPD1 | IDF Vent Speed 1 | Write | ||
| AV | 375 | IDFCFG_VENTSPD2 | IDF Vent Speed 2 | Write | ||
| AV | 376 | IDFCFG_VENTSPD3 | IDF Vent Speed 3 | Write | ||
| AV | 377 | IDFCFG_VENTSPD4 | IDF Vent Speed 4 | Write | ||
| AV | 378 | OADCFG_OADPOS1 | OA Damper Vent Pos 1 | Write | ||
| AV | 379 | OADCFG_OADPOS2 | OA Damper Vent Pos 2 | Write | ||
| AV | 380 | OADCFG_OADPOS3 | OA Damper Vent Pos 3 | Write | ||
| AV | 381 | OADCFG_OADPOS4 | OA Damper Vent Pos 4 | Write | ||
| AV | 382 | OADCFG_IAQRESET | IAQ Reset Source | Write | ||
| AV | 383 | OADCFG_IAQOTH | IAQ Override Threshold | Write | ||
| AV | 384 | OADCFG_IAQODB | IAQ Override Deadband | Write | ||
| AV | 385 | OADCFG_IAQOPOS | IAQ Override Position | Write | ||
| AV | 386 | OADCFG_IAQPDUR | IAQ Purge Duration | Write | ||
| AV | 387 | OADCFG_IAQPLOCK | IAQ Purge Lockout | Write | ||
| AV | 388 | OADCFG_IAQPRGLL | IAQ Purge OAT Lo Lockout | Write | ||
| AV | 389 | OADCFG_IAQPRGHL | IAQ Purge OAT Hi Lockout | Write | ||
| AV | 390 | OADCFG_IAQPLOTP | IAQ Purge Lo Temp Pos | Write | ||
| AV | 391 | OADCFG_IAQPHITP | IAQ Purge Hi Temp Pos | Write | ||
| AV | 392 | OADCFG_IAQCFMRS | IAQ OA CFM Reset | Write | ||
| AV | 393 | OADCFG_PRGSHORT | Purge Short Duration | Write | ||
| AV | 394 | OADCFG_PRGLONG | Purge Long Duration | Write | ||
| AV | 395 | FRECLCFG_ODAIRQTH | OAQ Lockout | Write | ||
| AV | 396 | OADCFG_OABPOREN | Bld Pressure Override En | Write | ||
| AV | 397 | OADCFG_OABPORTH | Bld Pressure Threshold | Write | ||
| AV | 398 | OADCFG_OABPORDB | Bld Pressure Deadband | Write | ||
| AV | 399 | OADCFG_CFMSP | OACFM Setpoint | Write | ||
| AV | 400 | RFGPRESS_SPA | Cir A Suction Pressure | Read | ||
| AV | 401 | RFGPRESS_SPB | Cir B Suction Pressure | Read | ||
| AV | 402 | RFGPRESS_DPA | Cir A Discharge Pressure | Read | ||
| AV | 403 | RFGPRESS_DPB | Cir B Discharge Pressure | Read | ||
| AV | 404 | RFGTEMP_SSTA | Saturated Suction A | Read | ||
| AV | 405 | RFGTEMP_SSTB | Saturated Suction B | Read | ||
| AV | 406 | RFGTEMP_SDTA | Saturated Discharge CirA | Read | ||
| AV | 407 | RFGTEMP_SDTB | Saturated Discharge CirB | Read | ||
| AV | 408 | RFGTEMP_SSHA1 | A1 Superheat Temp | Read | ||
| AV | 409 | RFGTEMP_SSHA2 | A2 Superheat Temp | Read | ||
| AV | 410 | RFGTEMP_SSHB1 | B1 Superheat Temp | Read | ||
| AV | 411 | RFGTEMP_SSHB2 | B2 Superheat Temp | Read | ||
| AV | 412 | RFGTEMP_SGTA1 | Suction Gas Temp Cir A1 | Read | ||
| AV | 413 | RFGTEMP_SGTA2 | Suction Gas Temp Cir A2 | Read | ||
| AV | 414 | RFGTEMP_SGTB1 | Suction Gas Temp Cir B1 | Read | ||
| AV | 415 | RFGTEMP_SGTB2 | Suction Gas Temp Cir B2 | Read | ||
| AV | 416 | RFGTEMP_OILTSMPA | Oil Sump Temp | Read | ||
| AV | 417 | RUNTIME_COMPA1RT | Comp A1 Minutes | Read | ||
| AV | 418 | RUNTIME_COMPA1SC | Comp A1 Start Count | Read | ||
| AV | 419 | RUNTIME_COMPA1RC | Comp A1 Reset Count | Read | ||
| AV | 420 | RUNTIME_COMPA2RT | Comp A2 Minutes | Read | ||
| AV | 421 | RUNTIME_COMPA2SC | Comp A2 Start Count | Read | ||
| AV | 422 | RUNTIME_COMPA2RC | Comp A2 Reset Count | Read | ||
| AV | 423 | RUNTIME_COMPB1RT | Comp B1 Minutes | Read | ||
| AV | 424 | RUNTIME_COMPB1SC | Comp B1 Start Count | Read | ||
| AV | 425 | RUNTIME_COMPB1RC | Comp B1 Reset Count | Read | ||
| AV | 426 | RUNTIME_COMPB2RT | Comp B2 Minutes | Read | ||
| AV | 427 | RUNTIME_COMPB2SC | Comp B2 Start Count | Read | ||
| AV | 428 | RUNTIME_COMPB2RC | Comp B2 Reset Count | Read | ||
| AV | 429 | RUNTIME_CND1_RT | CF 1 Minutes | Read | ||
| AV | 430 | RUNTIME_CND1_SC | CF 1 Start Count | Read | ||
| AV | 431 | RUNTIME_CND1_RC | CF 1 Reset Count | Read | ||
| AV | 432 | RUNTIME_CND2_RT | CF 2 Minutes | Read | ||
| AV | 433 | RUNTIME_CND2_SC | CF 2 Start Count | Read | ||
| AV | 434 | RUNTIME_CND2_RC | CF 2 Reset Count | Read | ||
| AV | 435 | RUNTIME_CND3_RT | CF 3 Minutes | Read | ||
| AV | 436 | RUNTIME_CND3_SC | CF 3 Start Count | Read | ||
| AV | 437 | RUNTIME_CND3_RC | CF 3 Reset Count | Read | ||
| AV | 438 | RUNTIME_IDF_RT | Indoor Fan Minutes | Read | ||
| AV | 439 | RUNTIME_IDF_SC | Indoor Fan Start Count | Read | ||
| AV | 440 | RUNTIME_IDF_RC | Indoor Fan Reset Count | Read | ||
| AV | 441 | RUNTIME_EFAN_RT | Exhaust Fan Minutes | Read | ||
| AV | 442 | RUNTIME_EFAN_SC | Exhaust Fan Start Count | Read | ||
| AV | 443 | RUNTIME_EFAN_RC | Exhaust Fan Reset Count | Read | ||
| AV | 444 | RUNTIME_SHEAT_RT | Heat Minutes | Read | ||
| AV | 445 | RUNTIME_SHEAT_SC | Heat Start Count | Read | ||
| AV | 446 | RUNTIME_SHEAT_RC | Heat Reset Count | Read | ||
| AV | 447 | RUNTIME_HMVLV_RT | HGRH Valve Minutes | Read | ||
| AV | 448 | RUNTIME_HMVLV_SC | HGRH Valve Start Count | Read | ||
| AV | 449 | RUNTIME_HMVLV_RC | HGRH Valve Reset Count | Read | ||
| AV | 450 | RUNTIME_DAMP_RT | OAD Minutes | Read | ||
| AV | 451 | RUNTIME_DAMP_SC | OAD Start Count | Read | ||
| AV | 452 | RUNTIME_DAMP_RC | OAD Reset Count | Read | ||
| AV | 453 | RUNTIME_CCHRA_RT | CCH A Minutes | Read | ||
| AV | 454 | RUNTIME_CCHRA_SC | CCH A Start Count | Read | ||
| AV | 455 | RUNTIME_CCHRA_RC | CCH A Reset Count | Read | ||
| AV | 456 | RUNTIME_CCHRB_RT | CCH B Minutes | Read | ||
| AV | 457 | RUNTIME_CCHRB_SC | CCH B Start Count | Read | ||
| AV | 458 | RUNTIME_CCHRB_RC | CCH B Reset Count | Read | ||
| AV | 459 | RUNTIME_OILACYSC | Oil Cir A Count | Read | ||
| AV | 460 | RUNTIME_OILBCYSC | Oil Cir B Count | Read | ||
| AV | 461 | CMPASTS_OILRECAC | Oil Recovery Actv Cir A | Read | ||
| AV | 462 | CMPASTS_ORTMLFTA | Cir A Oil Rec Time Left | Read | ||
| AV | 463 | CMPBSTS_OILRECAC | Oil Recovery Actv Cir B | Read | ||
| AV | 464 | CMPBSTS_ORTMLFTB | Cir B Oil Rec Time Left | Read | ||
| AV | 465 | RUNTIME_HUMPUSC | Humdimizer Cycle Cnt | Read | ||
| AV | 466 | GENUINIT_FILT_RT | Filter Minutes | Read | ||
| AV | 467 | SERVICE_MAXOACFM | OACFM Sensor Max Range | Write | ||
| AV | 468 | SERVICE1_HTTOCL | Heat to Cool Guard | Write | ||
| AV | 469 | SERVICE1_CLTOHT | Cool to Heat Guard | Write | ||
| AV | 470 | SERVICE1_ZDORCAP | ZDOR Heat Cap Thresh | Write | ||
| AV | 471 | COOLCFG_CCHTHA | CCH A OAT Lockout | Write | ||
| AV | 472 | COOLCFG_CCHTHB | CCH B OAT Lockout | Write | ||
| AV | 473 | FRECLCFG_FCOOL_TG | Free Cool Timeguard | Write | ||
| AV | 474 | COOLSTP_CMPMAXA1 | Cmp Nominal Spd Max A1 | Write | ||
| AV | 475 | COOLSTP_CMPMINA1 | Cmp Nominal Spd Min A1 | Write | ||
| AV | 476 | COOLSTP_CMPMAXA2 | Cmp Nominal Spd Max A2 | Write | ||
| AV | 477 | COOLSTP_CMPMINA2 | Cmp Nominal Spd Min A2 | Write | ||
| AV | 478 | COOLSTP_CMPMAXB1 | Cmp Nominal Spd Max B1 | Write | ||
| AV | 479 | COOLSTP_CMPMINB1 | Cmp Nominal Spd Min B1 | Write | ||
| AV | 480 | COOLSTP_CMPMAXB2 | Cmp Nominal Spd Max B2 | Write | ||
| AV | 481 | COOLSTP_CMPMINB2 | Cmp Nominal Spd Min B2 | Write | ||
| AV | 482 | COOLCFG_SATLO_DB | SAT Lo Deadband | Write | ||
| AV | 483 | COOLCFG_SATHI_DB | SAT High Deadband | Write | ||
| AV | 484 | DHUMCFG_DHUMMODE | Dehum Control Mode | Write | ||
| AV | 485 | COOLCFG_SCT_HLIM | SCT High Limit | Write | ||
| AV | 486 | COOLCFG_SCT_LLIM | SCT Low Limit | Write | ||
| AV | 487 | DHUMCFG_RHMINPOS | HGRH Valve Min Pos | Write | ||
| AV | 488 | DHUMCFG_RHMAXPOS | HGRH Valve Max Pos | Write | ||
| AV | 489 | DHUMCFG_RHSTART | HGRH Start Pos | Write | ||
| AV | 490 | DHUMCFG_RHTIME | HGRH Startup Time | Write | ||
| AV | 491 | SERVICE1_CMPMATL | Comp MAT Lockout | Write | ||
| AV | 492 | SERVICE1_CMPOATL | Comp OAT Lock | Write | ||
| AV | 493 | CNDSTP_SDTTEMP1 | SDT Setpoint 1 | Write | ||
| AV | 494 | CNDSTP_SDTTEMP2 | SDT Setpoint 2 | Write | ||
| AV | 495 | CNDSTP_SDTTEMP3 | SDT Setpoint 3 | Write | ||
| AV | 496 | COOLCFG_CFSPDMN1 | CF Speed MIN | Write | ||
| AV | 497 | COOLCFG_CFSPDMX1 | CF Speed MAX | Write | ||
| AV | 498 | COOLCFG_CFSTSPD1 | CF User Start Speed | Write | ||
| AV | 499 | SERVICE1_SVTESTMT | Test Mode Timeout | Write | ||
| AV | 500 | SERVICE_NETINTO | Network Input Timeout | Write | ||
| AV | 501 | SERVICE_LLAGCFG | Lead Lag Config | Write | ||
| AV | 502 | SERVICE_RCYCLIM | Recycle Limit | Write | ||
| AV | 503 | SERVICE_RCYCDB | Recycle DB | Write | ||
| AV | 504 | DHUMCFG_OILLOWTH | Oil Recov Low Thld | Write | ||
| AV | 505 | DHUMCFG_OILHITH | Oil Recov High Thld | Write | ||
| AV | 506 | DHUMCFG_OILTIME | Dehum Oil Recov Time | Write | ||
| AV | 507 | FACTORY_OILRHLDT | Oil Recovery Hold Time | Write | ||
| AV | 508 | FACTORY_OILRECSP | Oil Recovery Speed | Write | ||
| AV | 509 | FACTORY_OILTIME1 | Oil Recovery Time 1 | Write | ||
| AV | 510 | FACTORY_OILTIME2 | Oil Recovery Time 2 | Write | ||
| AV | 511 | FACTORY_LOWOILA | Low Oil Threshold A | Write | ||
| AV | 512 | FACTORY_LOWOILB | Low Oil Threshold B | Write | ||
| AV | 513 | FACTORY_LOWOILTM | Oil Threshold Timer | Write | ||
| AV | 514 | FACTORY_OILRSTLM | Oil Threshold Reset Lim | Write | ||
| AV | 515 | FACTORY_LOWOILRT | Low Oil Reset Threshold | Write | ||
| AV | 516 | STATES_MINTILOC | Time Until Next Occupied | Read | ||
| AV | 517 | LABONLY_CAPAPCT | System Capacity Req % | Read | ||
| AV | 518 | LABONLY_CAPACT | System Capacity Act % | Read | ||
| AV | 519 | CMPA1STS_LOADREQ | Load Request Comp A1 | Read | ||
| AV | 520 | CMPA2STS_LOADREQ | Load Request Comp A2 | Read | ||
| AV | 521 | CMPB1STS_LOADREQ | Load Request Comp B1 | Read | ||
| AV | 522 | CMPB2STS_LOADREQ | Load Request Comp B2 | Read | ||
| AV | 523 | OUTPUTS_EXVA1OBJ | EXV A1 Objective | Read | ||
| AV | 524 | OUTPUTS_EXVA2OBJ | EXV A2 Objective | Read | ||
| AV | 525 | OUTPUTS_EXVB1OBJ | EXV B1 Objective | Read | ||
| AV | 526 | OUTPUTS_EXVB2OBJ | EXV B2 Objective | Read | ||
| AV | 527 | COOLSTP_ACTV_SP | SAT Setpt | Read | ||
| AV | 528 | CMPASTS_SSTENVMN | SST Env Min CirA | Read | ||
| AV | 529 | CMPASTS_SSTENVMX | SST Env Max CirA | Read | ||
| AV | 530 | CMPASTS_SDTENVMN | SDT Env Min CirA | Read | ||
| AV | 531 | CMPASTS_SDTENVMX | SDT Env Max CirA | Read | ||
| AV | 532 | CMPBSTS_SSTENVMN | SST Env Min Cir B | Read | ||
| AV | 533 | CMPBSTS_SSTENVMX | SST Env Max Cir B | Read | ||
| AV | 534 | CMPBSTS_SDTENVMN | SDT Env Min Cir B | Read | ||
| AV | 535 | CMPBSTS_SDTENVMX | SDT Env Max Cir B | Read | ||
| AV | 536 | CMPASTS_SSTABSMN | SST Abs Min CirA | Read | ||
| AV | 537 | CMPASTS_SSTABSMX | SST Abs Max CirA | Read | ||
| AV | 538 | CMPASTS_SDTABSMN | SDT Abs Min Cir A | Read | ||
| AV | 539 | CMPASTS_SDTABSMX | SDT Abs Max Cir A | Read | ||
| AV | 540 | CMPBSTS_SSTABSMN | SST Abs Min Cir B | Read | ||
| AV | 541 | CMPBSTS_SSTABSMX | SST Abs Max Cir B | Read | ||
| AV | 542 | CMPBSTS_SDTABSMN | SDT Abs Min Cir B | Read | ||
| AV | 543 | CMPBSTS_SDTABSMX | SDT Abs Max Cir B | Read | ||
| AV | 544 | LAB_SSHCMDA1 | EXVA1 SSHCMD | Read | ||
| AV | 545 | LAB_SSHSTPA1 | EXVA1 SSHSTPT | Read | ||
| AV | 546 | LAB_SSHCMDA2 | EXVA2 SSHCMD | Read | ||
| AV | 547 | LAB_SSHSTPA2 | EXVA2 SSHSTPT | Read | ||
| AV | 548 | LAB_SSHCMDB1 | EXVB1 SSHCMD | Read | ||
| AV | 549 | LAB_SSHSTPB1 | EXVB1 SSHSTPT | Read | ||
| AV | 550 | LAB_SSHCMDB2 | EXVB2 SSHCMD | Read | ||
| AV | 551 | LAB_SSHSTPB2 | EXVB2 SSHSTPT | Read | ||
| AV | 552 | LAB_DSTKPA1 | EXVA1 DST KP | Read | ||
| AV | 553 | LAB_DSTTIA1 | EXVA1 DST TI | Read | ||
| AV | 554 | LAB_SSHKPA1 | EXVA1 SSH KP | Read | ||
| AV | 555 | LAB_SSHTIA1 | EXVA1 SSH TI | Read | ||
| AV | 556 | LAB_DSTKPA2 | EXVA2 DST KP | Read | ||
| AV | 557 | LAB_DSTTIA2 | EXVA2 DST TI | Read | ||
| AV | 558 | LAB_SSHKPA2 | EXVA2 SSH KP | Read | ||
| AV | 559 | LAB_SSHTIA2 | EXVA2 SSH TI | Read | ||
| AV | 560 | LAB_DSTKPB1 | EXVB1 DST KP | Read | ||
| AV | 561 | LAB_DSTTIB1 | EXVB1 DST TI | Read | ||
| AV | 562 | LAB_SSHKPB2 | EXVB2 SSH KP | Read | ||
| AV | 563 | LAB_SSHTIB2 | EXVB2 SSH TI | Read | ||
| AV | 564 | LABONLY_DHUM_REQ | Dehum Request | Read | ||
| AV | 565 | LAB_SDTTARG | SDT Target | Read | ||
| AV | 566 | LAB_SATCTLPT | SAT Control Point | Read | ||
| AV | 567 | GENUNIT_SMAXCCAP | Sys Max Cool Cap | Read | ||
| AV | 568 | GENUNIT_SMAXHCAP | Sys Max Heat Cap | Read | ||
| AV | 569 | LAB_OACFMCP | OA CFM Control Point | Read | ||
| AV | 571 | HOME_SCREEN_ID | Current home screen ID | Read | ||
| AV | 573 | BACNET_ALC_PRIME | Value of Prime variable | Read | ||
| AV | 574 | EQUIPCFG_SIO3DI7 | Select IAQ or OAQ Switch | Write | ||
| AV | 575 | LPALMHYS | Low Power Hysteresis(mS) | Write | ||
| BVmin | 1 | ALARMRST_RST_ALM | Alarm Reset | Write | ||
| BV | 2 | UNITCFG_PG_SP_EN | Prognostics SP Enable | Write | ||
| BV | 3 | UNITCFG_PG_BP_EN | Prognostics BP Enable | Write | ||
| BV | 4 | ALERTCFG_LOCK_OUT | Lockout Notification | Write | ||
| BV | 5 | ALERTCFG_T24ENAB | T24 Diagnostic | Write | ||
| BV | 6 | IDFFDBK_STATUS | IDF Feedback Status | Read | ||
| BV | 7 | COOLCFG_TMPDVNT | Cool Tempered Venting | Write | ||
| BV | 8 | SVCOUT_CMTRNDAC | Cool Comfort Trending | Write | ||
| BV | 9 | DHUMCFG_UNOCENAB | Unoccupied Dehum | Write | ||
| BV | 10 | DHUMCFG_SUPPHEAT | Supplemental Heat | Write | ||
| BV | 11 | DHUMCFG_DHUMVENT | Vent/None Dehum | Write | ||
| BV | 12 | DHUMCFG_DHUMVAV | VAV Cool Dehum | Write | ||
| BV | 13 | DHUMCFG_DHUMHICL | High Cool Dehum | Write | ||
| BV | 14 | DHUMCFG_DHUMLOCL | Low Cool Dehum | Write | ||
| BV | 15 | DHUMCFG_DHUMHIHT | High Heat Dehum | Write | ||
| BV | 16 | DHUMCFG_DHUMLOHT | Low Heat Dehum | Write | ||
| BV | 17 | OADCFG_OADHUMEN | OA Dehum Enable | Write | ||
| BV | 18 | DHUMCFG_OFDHUMEN | Occupied Free Dehum | Write | ||
| BV | 19 | DHUMCFG_UFDHUMEN | Unoccupied Free Dehum | Write | ||
| BV | 20 | DISCIN_TSTAT_G | Indoor Fan Input (G) | Read | ||
| BV | 21 | DISCIN_TSTAT_Y1 | Lo Cool Input (Y1) | Read | ||
| BV | 22 | DISCIN_TSTAT_Y2 | Hi Cool Input (Y2) | Read | ||
| BV | 23 | DISCIN_TSTAT_W1 | Lo Heat Input (W1) | Read | ||
| BV | 24 | DISCIN_TSTAT_W2 | Hi Heat Input (W2) | Read | ||
| BV | 25 | DISCIN_FIRESW | Fire Shutdown Switch | Read | ||
| BV | 26 | DISCIN_SMOKESW | Smoke Detector | Read | ||
| BV | 27 | DISCIN_SMKPRGSW | Smoke Purge Switch | Read | ||
| BV | 28 | DISCIN_PMR_STAT | Phase Monitor | Read | ||
| BV | 29 | DISCIN_SHTDWNSW | Shutdown Switch | Read | ||
| BV | 30 | DISCIN_FILTSTAT | Filter Switch | Read | ||
| BV | 31 | DISCIN_IDF_LSM | Indoor Fan Limit Switch | Read | ||
| BV | 32 | DISCIN_HT_ALARM | Heat Alarm | Read | ||
| BV | 33 | DISCIN_CNDOSW | COFS | Read | ||
| BV | 34 | DISCIN_DEHUMSW | Dehumidify Switch | Read | ||
| BV | 35 | DISCIN_CMPFBKA1 | Comp A1 Feedback | Read | ||
| BV | 36 | DISCIN_CMPFBKA2 | Comp A2 Feedback | Read | ||
| BV | 37 | DISCIN_CMPFBKB1 | Comp B1 Feedback | Read | ||
| BV | 38 | DISCIN_CMPFBKB2 | Comp B2 Feedback | Read | ||
| BV | 39 | DISCIN_HPSA | Cir A HPS Switch | Read | ||
| BV | 40 | DISCIN_HPSB | Cir B HPS Switch | Read | ||
| BV | 41 | DISCIN_RESW | Remote Switch | Read | ||
| BV | 42 | DISCIN_ERV_FRST | ERV Frost Indicator | Read | ||
| BV | 43 | DISCIN_WHEEL_ST | ERV Motion Sensor | Read | ||
| BV | 44 | DISCIN_ERVFSS | ERV OD Filt Stat Switch | Read | ||
| BV | 45 | DISCIN_DLS1 | DemandLimSwitch1 | Read | ||
| BV | 46 | DISCIN_DLS2 | DemandLimSwitch2 | Read | ||
| BV | 47 | DISCIN_IGCFANSW | IGC IDF Switch | Read | ||
| BV | 48 | DISCIN_PFPSS | Pre Filter Switch | Read | ||
| BV | 49 | DISCIN_PRESSSW | Fire Press Switch | Read | ||
| BV | 50 | DISCIN_EVACSW | Smoke Evac Switch | Read | ||
| BV | 51 | DISCIN_FRZSW | Hydronic Freeze Switch | Read | ||
| BV | 52 | DISCIN_PPSS | Pressure Safety | Read | ||
| BV | 53 | DISCIN_IAQSW | IAQ Switch | Read | ||
| BV | 54 | DISCIN_OAQSW | OAQ Switch | Read | ||
| BV | 55 | DISCIN_ODENTHSW | Outdoor Enthalpy | Read | ||
| BV | 56 | DISCIN_ENEGPRES | OAD Neg Pressure | Read | ||
| BV | 57 | DISCIN_VSOLSWA | VS Oil Level Switch A | Read | ||
| BV | 58 | DISCIN_INRFGLK | Indoor RFG Sensor ALM | Read | ||
| BV | 59 | DISCIN_OUTRFGLK | Outdoor RFG Sensor ALM | Read | ||
| BV | 60 | DISCOUT_CPA1 | Compressor A1 | Read | ||
| BV | 61 | DISCOUT_CMPRELA1 | Comp A1 Modulation RLY | Read | ||
| BV | 62 | DISCOUT_CPA2 | Compressor A2 | Read | ||
| BV | 63 | DISCOUT_CMPRELA2 | Comp A2 Modulation RLY | Read | ||
| BV | 64 | DISCOUT_CPB1 | Compressor B1 | Read | ||
| BV | 65 | DISCOUT_CPB2 | Compressor B2 | Read | ||
| BV | 66 | DISCOUT_IDFBYREL | IDF VFD Bypass Relay | Read | ||
| BV | 67 | DISCOUT_ODF1 | CF 1 Relay | Read | ||
| BV | 68 | DISCOUT_ODF2 | CF 2 Relay | Read | ||
| BV | 69 | DISCOUT_ODF3 | CF 3 Relay | Read | ||
| BV | 70 | DISCOUT_CCHRA | CCH A | Read | ||
| BV | 71 | DISCOUT_CCHRB | CCH B | Read | ||
| BV | 72 | DISCOUT_HMS | Reheat 3-way valve | Read | ||
| BV | 73 | DISCOUT_RH3PRLY | 3rd Party Reheat Relay | Read | ||
| BV | 74 | DISCOUT_ERVWHEEL | ERV Wheel | Read | ||
| BV | 75 | DISCOUT_STGHEAT1 | Heat Enable 1 | Read | ||
| BV | 76 | DISCOUT_STGHEAT2 | Heat Enable 2 | Read | ||
| BV | 77 | DISCOUT_STGHEAT3 | Heat Enable 3 | Read | ||
| BV | 78 | DISCOUT_STGHEAT4 | Heat Enable 4 | Read | ||
| BV | 79 | DISCOUT_STGHEAT5 | Heat Enable 5 | Read | ||
| BV | 80 | DISCOUT_STGHEAT6 | Heat Enable 6 | Read | ||
| BV | 81 | DISCOUT_BYP_DAMP | ERV Bypass Damper | Read | ||
| BV | 82 | DISCOUT_ZDOR | Zone Damper Override RLY | Read | ||
| BVmin | 83 | DISCOUT_ALMOUT | Alarm | Read | ||
| BV | 84 | DISCOUT_HIR | Heat Interlock Relay | Read | ||
| BV | 85 | DISCOUT_HMFR | Humidifier | Read | ||
| BV | 86 | DISCOUT_HRR | Heat Reclaim | Read | ||
| BV | 87 | DISCOUT_PEA | Power Exh A | Read | ||
| BV | 88 | DISCOUT_PEB | Power Exh B | Read | ||
| BV | 89 | DISCOUT_PEC | Power Exh C | Read | ||
| BV | 90 | DISCOUT_AUTOADDR | Fan Auto Address | Read | ||
| BV | 91 | DMDLMCFG_DLSWSEN | Demand Switch Enable | Write | ||
| BV | 92 | OCCSB_EN | Occupied Standby Enable | Write | ||
| BV | 93 | EQUIPCFG_DMDLIM | Demand/Capacity Anlg In | Write | ||
| BV | 94 | EQUIPCFG_SMOKEEN | Smoke Detector | Write | ||
| BV | 95 | EQUIPCFG_TSTATEN | Thermostat | Write | ||
| BV | 96 | EQUIPCFG_HUMSWEN | Humidistat | Write | ||
| BV | 97 | EQUIPCFG_FILTSWEN | Pre-Filter Switch | Write | ||
| BV | 98 | EQUIPCFG_PMREN | Phase Monitor | Write | ||
| BV | 99 | EQUIPCFG_SHTDWNEN | Emergency Shutdown En | Write | ||
| BV | 100 | EQUIPCFG_ZDOREN | ZDOR | Write | ||
| BV | 101 | EQUIPCFG_ALARMEN | Alarm Output | Write | ||
| BV | 102 | EQUIPCFG_EATEN | EAT Sensor | Write | ||
| BV | 103 | EQUIPCFG_OACFMEN | OACFM Sensor | Write | ||
| BV | 104 | EQUIPCFG_IDFVFDBY | IDF VFD Bypass | Write | ||
| BV | 105 | EQUIPCFG_SF3PEN | IDF 3rd Party Mod | Write | ||
| BV | 106 | EQUIPCFG_SPSREN | SPSR Sensor | Write | ||
| BV | 107 | EQUIPCFG_EF3PEN | EXF 3rd Party Mod | Write | ||
| BV | 108 | EQUIPCFG_RH3PEN | 3rd Party Reheat Enable | Write | ||
| BV | 109 | EQUIPCFG_OAD3PEN | OAD 3rd Party Mod | Write | ||
| BV | 110 | EQUIPCFG_ERVEN | ERV | Write | ||
| BV | 111 | EQUIPCFG_ERVOAFEN | ERV OAF | Write | ||
| BV | 112 | EQUIPCFG_ERVBYPEN | ERV Bypass Damper | Write | ||
| BV | 113 | EQUIPCFG_FIRESWEN | Fire Switch | Write | ||
| BV | 114 | EQUIPCFG_EVACEN | Evacuation Switch | Write | ||
| BV | 115 | EQUIPCFG_PRESSEN | Pressurization Switch | Write | ||
| BV | 116 | EQUIPCFG_EFEN | Exhaust Fan | Write | ||
| BV | 117 | EQUIPCFG_ECONEN | Economizer (OAD) | Write | ||
| BV | 118 | EQUIPCFG_HT1EN | Heat Stage 1 Relay | Write | ||
| BV | 119 | EQUIPCFG_HT2EN | Heat Stage 2 Relay | Write | ||
| BV | 120 | EQUIPCFG_HT3EN | Heat Stage 3 Relay | Write | ||
| BV | 121 | EQUIPCFG_HT4EN | Heat Stage 4 Relay | Write | ||
| BV | 122 | EQUIPCFG_DMDRSTEN | Demand Reset Switch | Write | ||
| BV | 123 | EQUIPCFG_CONDEN | COFS | Write | ||
| BV | 124 | EQUIPCFG_ENTHSWEN | Enthalpy Switch | Write | ||
| BV | 125 | EQUIPCFG_IAQOREN | IAQ-OD Pos Reset Enable | Write | ||
| BV | 126 | EQUIPCFG_OAQSWEN | OAQ Switch | Write | ||
| BV | 127 | EQUIPCFG_IAQSWEN | IAQ Switch | Write | ||
| BV | 128 | EXVSTP_SETPTENB | User Setpoint Enable | Write | ||
| BV | 129 | EXVSTP_EXVSTENB | Manual Start Pos Enable | Write | ||
| BV | 130 | FRECLCFG_FREECLEN | Occ Free Cool | Write | ||
| BV | 131 | FRECLCFG_UFC | Unocc Free Cooling | Write | ||
| BV | 132 | FRECLCFG_DRYBLB | Dry Bulb Chngeover (OAT) | Write | ||
| BV | 133 | FRECLCFG_DEWLIM | OADP Limit Check | Write | ||
| BV | 134 | HEATCFG_HTMPDVNT | Heat Tempered Venting | Write | ||
| BV | 135 | HEATCFG_HTTEMPCL | Heat Tempered Cooling | Write | ||
| BV | 136 | SVCOUT_CMTRNDAH | Add Heat Comfort Trend | Write | ||
| BV | 137 | HEATCFG_HEAT_EBL | Morning Warmup Only | Write | ||
| BV | 138 | MDESTS_ERVCHECK | ERV Check Status | Read | ||
| BV | 139 | MDESTS_DHUMPURG | Reheat Oil Purge | Read | ||
| BV | 140 | LINK_ACT | Linkage Active | Read | ||
| BV | 141 | NETIN_Y1_NET | Network Y1 | Write | ||
| BV | 142 | NETIN_Y2_NET | Network Y2 | Write | ||
| BV | 143 | NETIN_W1_NET | Network W1 | Write | ||
| BV | 144 | NETIN_W2_NET | Network W2 | Write | ||
| BV | 145 | NETIN_G_NET | Network G | Write | ||
| BV | 146 | NETIN_HSTATNET | Network HSTAT | Write | ||
| BV | 147 | FRECLCFG_ODAIRQ | OAQ Check | Write | ||
| BV | 148 | OADCFG_IAQSBVEN | IAQ Vent Standby Demand | Write | ||
| BV | 149 | OADCFG_IAQPOP | IAQ Pre-Occ Purge | Write | ||
| BV | 150 | RESET_RT_CMPA1 | Reset Comp A1 Min/Starts | Write | ||
| BV | 151 | RESET_RT_CMPA2 | Reset Comp A2 Min/Starts | Write | ||
| BV | 152 | RESET_RT_CMPB1 | Reset Comp B1 Min/Starts | Write | ||
| BV | 153 | RESET_RT_CMPB2 | Reset Comp B2 Min/Starts | Write | ||
| BV | 154 | RESET_RT_CND1 | Reset CF 1 Min/Starts | Write | ||
| BV | 155 | RESET_RT_CND2 | Reset CF 2 Min/Starts | Write | ||
| BV | 156 | RESET_RT_CND3 | Reset CF 3 Min/Starts | Write | ||
| BV | 157 | RESET_RT_CNDA | Reset CF A Min/Starts | Write | ||
| BV | 158 | RESET_RT_CNDB | Reset CF B Min/Starts | Write | ||
| BV | 159 | RESET_RT_IDF | Reset IDF Min/Starts | Write | ||
| BV | 160 | RESET_RT_EFAN | Reset EXF Min/Starts | Write | ||
| BV | 161 | RESET_RT_CCHA | Reset CCH A Min/Starts | Write | ||
| BV | 162 | RESET_RT_CCHB | Reset CCH B Min/Starts | Write | ||
| BV | 163 | RESET_RT_CCH | Reset CCH Min/Starts | Write | ||
| BV | 164 | RESET_RT_DAMP | Reset OAD Min/Starts | Write | ||
| BV | 165 | RESET_RT_STGHEAT | Reset Heat Min/Starts | Write | ||
| BV | 166 | RESET_RT_HMZRVLV | Reset HGRH Min/Starts | Write | ||
| BV | 167 | GENUNIT_FLTR_RST | Reset Filter Hours | Write | ||
| BV | 168 | RESET_RT_OILCYCLA | Reset Oil Cnt Cir A | Write | ||
| BV | 169 | RESET_RT_OILCYCLB | Reset OilCnt Cir B | Write | ||
| BV | 170 | RESET_RT_HUMPURC | Reset Humidimer Cnt | Write | ||
| BV | 171 | CNDSTP_SDTStpEn | SDT Setpoint Enable | Write | ||
| BV | 172 | CNDSTP_SPDStpEN | CF User Start Spd Enab | Write | ||
| BV | 173 | SERVICE_DISABLEM | Service Lock Out | Write | ||
| BV | 174 | COOLCFG_LCRCO | Low Cap Req Comp On | Write | ||
| BV | 175 | COOLCFG_VSCFS_OR | VSC Fixed Speed Override | Write | ||
| BV | 176 | STATES_OKTOFRCL | Free Cooling Available | Read | ||
| BV | 177 | MDESTS_MODETCST | Temp Compensated Start | Read | ||
| BV | 178 | STATES_PURGEACT | Pre-Occ Purge State | Read | ||
| BV | 179 | OCCSB | Occupied Standby | Read | ||
| BV | 180 | STATES_OKTOFDHM | Free Dehum Status | Read | ||
| BV | 181 | SWTCHCFG_HTALMINV | Heat Alarm/Limit Switch | Write | ||
| BV | 182 | SWTCHCFG_CNDSWINV | Condensate Ovrflw Switch | Write | ||
| BV | 183 | SWTCHCFG_SMKSWINV | Smoke Detector | Write | ||
| BV | 184 | SWTCHCFG_IDFSWINV | Indoor Fan Limit Switch | Write | ||
| BV | 185 | SWTCHCFG_HPSAINV | High Pressure Switch | Write | ||
| BV | 186 | SWTCHCFG_TSTGINV | Thermostat G | Write | ||
| BV | 187 | SWTCHCFG_TSTY1INV | Thermostat Y1 | Write | ||
| BV | 188 | SWTCHCFG_TSTY2INV | Thermostat Y2 | Write | ||
| BV | 189 | SWTCHCFG_DHMSWINV | Humidistat Switch | Write | ||
| BV | 190 | SWTCHCFG_TSTW1INV | Thermostat W1 | Write | ||
| BV | 191 | SWTCHCFG_TSTW2INV | Thermostat W2 | Write | ||
| BV | 192 | SWTCHCFG_FLTSWINV | Filter Status Switch | Write | ||
| BV | 193 | SWTCHCFG_RESWINV | Remote Input | Write | ||
| BV | 194 | SWTCHCFG_PMRSWINV | Phase Monitor | Write | ||
| BV | 195 | SWTCHCFG_FRESWINV | Fire Shutdown | Write | ||
| BV | 196 | SWTCHCFG_FRSTINV | ERV Frost Indication | Write | ||
| BV | 197 | SWTCHCFG_WHLSTINV | ERV Wheel Motion Sensor | Write | ||
| BV | 198 | SWTCHCFG_HTENINV | Heat Enable | Write | ||
| BV | 199 | SWTCHCFG_DORINV | Damper Override Relay | Write | ||
| BV | 200 | SWTCHCFG_CMPA1INV | Compressor A1 | Write | ||
| BV | 201 | SWTCHCFG_CMPA2INV | Compressor A2 | Write | ||
| BV | 202 | SWTCHCFG_CCHRAINV | Crankcase Heater A | Write | ||
| BV | 203 | SWTCHCFG_PEENINV | EXF Enable | Write | ||
| BV | 204 | SWTCHCFG_EVBYPINV | ERV Bypass Damper | Write | ||
| BV | 205 | SWTCHCFG_ERVINV | ERV Wheel | Write | ||
| BV | 206 | SWTCHCFG_ALARMINV | Alarm Relay | Write | ||
| BV | 207 | UNITCFG_AUTRST | Auto Restart | Write | ||
| BV | 208 | LABONLY_SYSON | System On | Read | ||
| BV | 209 | ALM_61413 | T413 | Read | ||
| BV | 210 | ALM_61085 | T085 | Read | ||
| BV | 211 | ALM_61086 | T086 | Read | ||
| BV | 212 | ALM_62051 | P051 | Read | ||
| BV | 213 | ALM_61051 | T051 | Read | ||
| BV | 214 | ALM_60051 | A051 | Read | ||
| BV | 215 | ALM_62052 | P052 | Read | ||
| BV | 216 | ALM_61052 | T052 | Read | ||
| BV | 217 | ALM_60052 | A052 | Read | ||
| BV | 218 | ALM_62054 | P054 | Read | ||
| BV | 219 | ALM_61054 | T054 | Read | ||
| BV | 220 | ALM_60054 | A054 | Read | ||
| BV | 221 | ALM_62055 | P055 | Read | ||
| BV | 222 | ALM_61055 | T055 | Read | ||
| BV | 223 | ALM_60055 | A055 | Read | ||
| BV | 224 | ALM_60057 | A057 | Read | ||
| BV | 225 | ALM_61057 | T057 | Read | ||
| BV | 226 | ALM_60058 | A058 | Read | ||
| BV | 227 | ALM_61058 | T058 | Read | ||
| BV | 228 | ALM_61072 | T072 | Read | ||
| BV | 229 | ALM_61073 | T073 | Read | ||
| BV | 230 | ALM_60073 | A073 | Read | ||
| BV | 231 | ALM_60700 | A700 | Read | ||
| BV | 232 | ALM_61706 | T706 | Read | ||
| BV | 233 | ALM_60706 | A706 | Read | ||
| BV | 234 | ALM_61075 | T075 | Read | ||
| BV | 235 | ALM_60075 | A075 | Read | ||
| BV | 236 | ALM_60710 | A710 | Read | ||
| BV | 237 | ALM_61090 | T090 | Read | ||
| BV | 238 | ALM_60090 | A090 | Read | ||
| BV | 240 | ALM_61092 | T092 | Read | ||
| BV | 241 | ALM_60092 | A092 | Read | ||
| BV | 243 | ALM_60110 | A110 | Read | ||
| BV | 244 | ALM_60120 | A120 | Read | ||
| BV | 245 | ALM_61120 | T120 | Read | ||
| BV | 246 | ALM_60121 | A121 | Read | ||
| BV | 247 | ALM_61121 | T121 | Read | ||
| BV | 248 | ALM_61122 | T122 | Read | ||
| BV | 249 | ALM_61123 | T123 | Read | ||
| BV | 250 | ALM_60126 | A126 | Read | ||
| BV | 251 | ALM_61126 | T126 | Read | ||
| BV | 252 | ALM_60127 | A127 | Read | ||
| BV | 253 | ALM_61127 | T127 | Read | ||
| BV | 254 | ALM_61128 | T128 | Read | ||
| BV | 255 | ALM_60128 | A128 | Read | ||
| BV | 256 | ALM_61069 | A069 | Read | ||
| BV | 257 | ALM_60071 | A071 | Read | ||
| BV | 258 | ALM_61425 | T425 | Read | ||
| BV | 259 | ALM_61181 | T181 | Read | ||
| BV | 260 | ALM_61426 | T426 | Read | ||
| BV | 261 | ALM_61182 | T182 | Read | ||
| BV | 262 | ALM_60140 | A140 | Read | ||
| BV | 263 | ALM_60141 | A141 | Read | ||
| BV | 264 | ALM_60142 | A142 | Read | ||
| BV | 265 | ALM_60143 | A143 | Read | ||
| BV | 266 | ALM_61102 | T102 | Read | ||
| BV | 267 | ALM_61103 | T103 | Read | ||
| BV | 268 | ALM_60104 | A104 | Read | ||
| BV | 269 | ALM_60106 | A106 | Read | ||
| BV | 270 | ALM_60107 | A107 | Read | ||
| BV | 271 | ALM_60150 | A150 | Read | ||
| BV | 272 | ALM_60151 | A151 | Read | ||
| BV | 273 | ALM_61163 | T163 - Compressor Drive Warning | Read | ||
| BV | 274 | ALM_61164 | A164 | Read | ||
| BV | 275 | ALM_60166 | A166 | Read | ||
| BV | 276 | ALM_60167 | A167 | Read | ||
| BV | 277 | ALM_60168 | A168 | Read | ||
| BV | 278 | ALM_60169 | A169 | Read | ||
| BV | 279 | ALM_60179 | A179 | Read | ||
| BV | 280 | ALM_60175 | A175 | Read | ||
| BV | 281 | ALM_61410 | T410 | Read | ||
| BV | 282 | ALM_61411 | T411 | Read | ||
| BV | 283 | ALM_61412 | T412 | Read | ||
| BV | 284 | ALM_61094 | T094 | Read | ||
| BV | 285 | ALM_61095 | T095 | Read | ||
| BV | 286 | ALM_61096 | T096 | Read | ||
| BV | 287 | ALM_61097 | T097 | Read | ||
| BV | 288 | ALM_61300 | T300 | Read | ||
| BV | 289 | ALM_61301 | T301 | Read | ||
| BV | 290 | ALM_61302 | T302 | Read | ||
| BV | 291 | ALM_61303 | T303 | Read | ||
| BV | 292 | ALM_61304 | T304 | Read | ||
| BV | 293 | ALM_61305 | T305 | Read | ||
| BV | 294 | ALM_61308 | T308 | Read | ||
| BV | 295 | ALM_61309 | T309 | Read | ||
| BV | 296 | ALM_61312 | T312 | Read | ||
| BV | 297 | ALM_61313 | T313 | Read | ||
| BV | 298 | ALM_61314 | T314 | Read | ||
| BV | 299 | ALM_61316 | T316 | Read | ||
| BV | 300 | ALM_61317 | T317 | Read | ||
| BV | 301 | ALM_61329 | T329 - Cir A Press Ratio Alert | Read | ||
| BV | 302 | ALM_60329 | A329 - Cir A Press Ratio Alarm | Read | ||
| BV | 303 | ALM_61330 | T330 - Cir B Press Ratio Alert | Read | ||
| BV | 304 | ALM_60330 | A330 - Cir B Press Ratio Alarm | Read | ||
| BV | 305 | ALM_61331 | T331 | Read | ||
| BV | 306 | ALM_60331 | A331 | Read | ||
| BV | 307 | ALM_61333 | T333 | Read | ||
| BV | 308 | ALM_60333 | A333 | Read | ||
| BV | 309 | ALM_61211 | T211 | Read | ||
| BV | 310 | ALM_60211 | A211 | Read | ||
| BV | 311 | ALM_61177 | T177 | Read | ||
| BV | 312 | ALM_61178 | T178 | Read | ||
| BV | 313 | ALM_61310 | T310 | Read | ||
| BV | 314 | ALM_61311 | T311 | Read | ||
| BV | 315 | ALM_60152 | A152 | Read | ||
| BV | 316 | ALM_61190 | T190 | Read | ||
| BV | 317 | ALM_60191 | A191 | Read | ||
| BV | 318 | ALM_60195 | A195 | Read | ||
| BV | 319 | ALM_60196 | A196 | Read | ||
| BV | 320 | ALM_60184 | A184 | Read | ||
| BV | 321 | ALM_60185 | A185 | Read | ||
| BV | 322 | ALM_60186 | A186 | Read | ||
| BV | 323 | ALM_60189 | A189 | Read | ||
| BV | 324 | ALM_60190 | A190 | Read | ||
| BV | 325 | ALM_60192 | A192 | Read | ||
| BV | 326 | ALM_60193 | A193 | Read | ||
| BV | 327 | ALM_60194 | A194 | Read | ||
| BV | 328 | ALM_60197 | A197 | Read | ||
| BV | 329 | ALM_60198 | A198 | Read | ||
| BV | 330 | ALM_60199 | A199 | Read | ||
| BV | 331 | ALM_60201 | A201 | Read | ||
| BV | 332 | ALM_60627 | T627 | Read | ||
| BV | 333 | ALM_60202 | A202 | Read | ||
| BV | 334 | ALM_60203 | A203 | Read | ||
| BV | 335 | ALM_60187 | A187 | Read | ||
| BV | 336 | ALM_60188 | A188 | Read | ||
| BV | 337 | ALM_61068 | T068 | Read | ||
| BV | 338 | ALM_61074 | T074 | Read | ||
| BV | 339 | ALM_61707 | T707 | Read | ||
| BV | 340 | ALM_61421 | T421 | Read | ||
| BV | 341 | ALM_61422 | T422 | Read | ||
| BV | 342 | ALM_61423 | T423 | Read | ||
| BV | 343 | ALM_61424 | T424 | Read | ||
| BV | 344 | ALM_61434 | T434 | Read | ||
| BV | 345 | ALM_60435 | A435 | Read | ||
| BV | 346 | ALM_61435 | T435 | Read | ||
| BV | 347 | ALM_61076 | T076 | Read | ||
| BV | 348 | ALM_61077 | T077 | Read | ||
| BV | 349 | ALM_61078 | T078 | Read | ||
| BV | 350 | ALM_61082 | T082 | Read | ||
| BV | 351 | ALM_61210 | T210 | Read | ||
| BV | 352 | ALM_62210 | A2101 | Read | ||
| BV | 353 | ALM_60210 | A210 | Read | ||
| BV | 354 | ALM_61220 | T220 | Read | ||
| BV | 355 | ALM_60220 | A220 | Read | ||
| BV | 356 | ALM_61221 | T221 | Read | ||
| BV | 357 | ALM_61245 | T245 | Read | ||
| BV | 358 | ALM_61335 | T335 | Read | ||
| BV | 359 | ALM_60436 | A436 | Read | ||
| BV | 360 | ALM_60400 | A400 | Read | ||
| BV | 361 | ALM_60404 | A404 | Read | ||
| BV | 362 | ALM_60405 | T405 | Read | ||
| BV | 363 | ALM_60406 | T406 | Read | ||
| BV | 364 | ALM_60407 | T407 | Read | ||
| BV | 365 | ALM_61415 | T415 | Read | ||
| BV | 366 | ALM_61416 | T416 | Read | ||
| BV | 367 | ALM_61408 | T408 | Read | ||
| BV | 368 | ALM_61318 | T318 | Read | ||
| BV | 369 | ALM_61319 | T319 | Read | ||
| BV | 370 | ALM_61615 | T615 | Read | ||
| BV | 371 | ALM_61616 | T616 | Read | ||
| BV | 372 | ALM_61617 | T617 | Read | ||
| BV | 373 | ALM_61414 | T414 | Read | ||
| BV | 374 | ALM_61352 | T352 | Read | ||
| BV | 375 | ALM_61045 | T045 | Read | ||
| BV | 376 | ALM_60046 | A046 | Read | ||
| BV | 377 | ALM_60047 | A047 | Read | ||
| BV | 378 | ALM_60048 | A048 | Read | ||
| BV | 379 | ALM_61047 | T047 | Read | ||
| BV | 380 | ALM_61048 | T048 | Read | ||
| BV | 381 | ALM_60228 | A228 | Read | ||
| BV | 382 | ALM_61079 | T079 | Read | ||
| BV | 383 | ALM_61080 | T080 | Read | ||
| BV | 384 | ALM_61222 | T222 | Read | ||
| BV | 385 | ALM_60222 | A222 | Read | ||
| BV | 386 | ALM_61223 | T223 | Read | ||
| BV | 387 | ALM_60223 | A223 | Read | ||
| BV | 388 | ALM_61224 | T224 | Read | ||
| BV | 389 | ALM_60224 | A224 | Read | ||
| BV | 390 | ALM_60420 | A420 | Read | ||
| BV | 391 | ALM_60200 | A200 | Read | ||
| BV | 392 | ALM_61084 | T084 | Read | ||
| BV | 393 | ALM_60083 | T083 | Read | ||
| BV | 394 | ALM_60081 | T081 | Read | ||
| BV | 395 | ALM_62437 | A437 | Read | ||
| BV | 396 | ALM_61153 | T153 | Read | ||
| BV | 397 | ALM_60154 | A154 | Read | ||
| BV | 398 | ALM_61155 | T155 | Read | ||
| BV | 399 | ALM_60156 | A156 | Read | ||
| BV | 400 | ALM_60157 | A157 | Read | ||
| BV | 401 | ALM_61350 | T350 | Read | ||
| BV | 402 | ALM_61351 | T351 | Read | ||
| BV | 403 | ALM_61320 | T320 | Read | ||
| BV | 404 | ALM_61321 | T321 | Read | ||
| BV | 405 | ALM_61062 | T062 | Read | ||
| BV | 406 | ALM_61322 | T322 | Read | ||
| BV | 407 | ALM_61323 | T323 | Read | ||
| BV | 408 | ALM_62445 | A2445 | Read | ||
| BV | 409 | ALM_63445 | A3445 | Read | ||
| BV | 410 | ALM_61445 | A1445 | Read | ||
| BV | 411 | ALM_60445 | A445 | Read | ||
| BV | 412 | ALM_60433 | A433 | Read | ||
| BV | 413 | ALM_60438 | A438 | Read | ||
| BV | 414 | ALM_61112 | T112 | Read | ||
| BV | 415 | ALM_61114 | T114 | Read | ||
| BV | 416 | ALM_65000 | Y000 | Read | ||
| BV | 417 | ALM_65001 | Y001 | Read | ||
| BV | 418 | ALM_65002 | Y002 | Read | ||
| BV | 419 | ALM_65003 | Y003 | Read | ||
| BV | 420 | ALM_65004 | Y004 | Read | ||
| BV | 421 | ALM_65005 | Y005 | Read | ||
| BV | 422 | ALM_65006 | Y006 | Read | ||
| BV | 423 | ALM_65007 | Y007 | Read | ||
| BV | 424 | ALM_65008 | Y008 | Read | ||
| BV | 425 | ALM_65009 | Y009 | Read | ||
| BV | 426 | ALM_65010 | Y010 | Read | ||
| BV | 427 | ALM_65011 | Y011 | Read | ||
| BV | 428 | ALM_65012 | Y012 | Read | ||
| BV | 429 | ALM_65013 | Y013 | Read | ||
| BV | 430 | ALM_65014 | Y014 | Read | ||
| BV | 431 | ALM_65015 | Y015 | Read | ||
| BV | 432 | ALM_65016 | Y016 | Read | ||
| BV | 433 | ALM_65017 | Y017 | Read | ||
| BV | 434 | ALM_65018 | Y018 | Read | ||
| BV | 435 | ALM_65019 | Y019 | Read | ||
| BV | 437 | ALM_60629 | T629 | Read | ||
| BV | 438 | ALM_61000 | 0 | Read | ||
| BV | 439 | ALM_61147 | T147 | Read | ||
| BV | 440 | ALM_60129 | Low Compressor Ratio Ckt A | Read | ||
| BV | 441 | ALM_60130 | Low Compressor Ratio Ckt B | Read | ||
| BV | 442 | ALM_61109 | IDF VFD Bypass Active | Read | ||
| BV | 443 | ALM_61087 | Heat Capacity Limit Alert | Read | ||
| BV | 444 | ALM_61088 | Cool Capacity Limit Alert | Read | ||
| BV | 445 | DISCOUT_VSCA1_SS | VSC A1 Safe Stop | Read | ||
| BV | 446 | ALM_60091 | A091 | Read | ||
| BV | 447 | ALM_60093 | A093 | Read | ||
| BV | 448 | LPALMEN | Low Power Alarm Enable | Write | ||
| BV | 449 | ALM_60266 | A266 | Read | ||
| BV | 450 | ALM_60267 | A267 | Read | ||
| BV | 451 | ALM_60268 | A268 | Read | ||
| BV | 452 | ALM_60269 | A269 | Read | ||
| BV | 453 | ALM_61628 | OAD/RAD % Open Alarm | Read | ||
| MV | 1 | MDESTS_CIRCAMDN | Circuit A Mode | Read | ||
| MV | 2 | MDESTS_CIRCBMDN | Circuit B Mode | Read | ||
| MV | 3 | MDESTS_CMPA1MDN | Comp A1 Mode | Read | ||
| MV | 4 | MDESTS_CMPA2MDN | Comp A2 Mode | Read | ||
| MV | 5 | MDESTS_CMPB1MDN | Comp B1 Mode | Read | ||
| MV | 6 | MDESTS_CMPB2MDN | Comp B2 Mode | Read | ||
| MV | 7 | MDESTS_ODF1MDN | CF 1 Mode | Read | ||
| MV | 8 | MDESTS_ODF2MDN | CF 2 Mode | Read | ||
| MV | 9 | MDESTS_ODF3MDN | CF 3 Mode | Read | ||
| MV | 10 | MDESTS_IDFMDNUM | Indoor Fan Mode | Read | ||
| MV | 11 | MDESTS_HEATRMDN | Heater Mode | Read | ||
| MV | 12 | MDESTS_ECONMNUM | OAD Mode | Read | ||
| MV | 13 | STATES_CIRCASTN | Circuit A State | Read | ||
| MV | 14 | STATES_CIRCBSTN | Circuit B State | Read | ||
| MV | 15 | STATES_CMPA1STN | Comp A1 State | Read | ||
| MV | 16 | STATES_CMPA2STN | Comp A2 State | Read | ||
| MV | 17 | STATES_CMPB1STN | Comp B1 State | Read | ||
| MV | 18 | STATES_CMPB2STN | Comp B2 State | Read | ||
| MV | 19 | STATES_ODF1STN | ODF A State | Read | ||
| MV | 20 | STATES_ODF2STN | CF 2 State | Read | ||
| MV | 21 | STATES_ODF3STN | CF 3 State | Read | ||
| MVmin | 22 | STATES_IDFNUM | Indoor Fan State | Read | ||
| MV | 23 | STATES_RHTSTNUM | HGRH State | Read | ||
| MV | 24 | STATES_HEATRSTN | Heater State | Read | ||
| MV | 25 | STATES_ECONNUM | OAD State | Read | ||
| MV | 26 | STATES_OCCSRNUM | Occupancy Source | Read | ||
| MV | 27 | BACNET_ALC_COLOR | Operation Status Color | Read |
No points match these filters.
Object ID lookup: Carrier 48/50LC*H Light Commercial Rooftop point IDs by name
AV1AIRPRESS_RAPAV2AIRPRESS_SDPAV3AIRPRESS_BPAV4AIRTEMP_SATAV5AIRTEMP_SATOAV6AIRTEMP_RATAV7AIRTEMP_SPTAV8AIRTEMP_SPTOAV9AIRTEMP_OATAV10AIRTEMP_MATAV11AIRTEMP_EATAV12AIRTEMP_LSTAV13AIRTEMP_LATAV14AIRTEMP_EFF_CPAV15AIRTEMP_DXLATAV16ALERTCFG_SPRHHLAV17ALERTCFG_SPRHLLAV18ALERTCFG_SPTLLMTOAV19ALERTCFG_SPTHLMTOAV20ALERTCFG_SPTLLMTUAV21ALERTCFG_SPTHLMTUAV22ALERTCFG_SATLLMTOAV23ALERTCFG_SATHLMTOAV24ALERTCFG_SATLLMTUAV25ALERTCFG_SATHLMTUAV26ALERTCFG_RATLLMTOAV27ALERTCFG_RATHLMTOAV28ALERTCFG_RATHLMTUAV29ALERTCFG_RATLLMTUAV30ALERTCFG_RARH_LTAV31ALERTCFG_RARH_HTAV32ALERTCFG_SP_LLMTAV33ALERTCFG_SP_HLMTAV34ALERTCFG_BP_LLMTAV35ALERTCFG_BP_HLMTAV36ALERTCFG_SAT_LTMPAV37ALERTCFG_SAT_HTMPAV38ALERTCFG_OAT_LLMTAV39ALERTCFG_OAT_HLMTAV40ALERTCFG_IAQ_HLMTAV41ALERTCFG_MAINFLTAV42GENUNIT_PREFLTR_SRCAV43GENUNIT_PREFLTR_LIMAV45ALERTCFG2_ERV_ALRTAV46UNITCFG_PG_SP_DBAV47UNITCFG_PG_BP_DBAV48ALERTCFG_HIGH_SSTAV49ALERTCFG_MINSUCAAV50ALERTCFG_MINDISAAV51ALERTCFG_MINSUCBAV52ALERTCFG_MINDISBAV53ALERTCFG_OFF_PRESAV54ALERTCFG_CMPCMD_TAV55ALERTCFG_OCFMSENSAV56ALERTCFG_ECMINCFMAV57OADCFG_FLTGAPAV58OADCFG_FLTTIMEAV59ALERTCFG_POSTFLAV60ALERTCFG_CP_C_THAV61ALERTCFG_LSST4TAV62ALERTCFG_LSST2TAV63ALERTCFG_LSST1TAV64ALERTCFG_LSST20sTAV65ALERTCFG_SSHALOWAV66ALERTCFG_SSHAPLLOAV67ALERTCFG_SSHAFLLOAV68ALERTCFG_SSHBLOWAV69ALERTCFG_SSHBPLLOAV70ALERTCFG_SSHBFLLOAV71ALERTCFG_LSSHTIMEAV72ALERTCFG_LPRLAV73LPRTIMEAV74ALERTCFG_COFS_ACTAV75ALERTCFG_COFS_TRPAV76ALERTCFG_COFS_TMEAV77ALERTCFG_OARADIFFAV78ALERTCFG_SATMOVEAV79ALERTCFG_SATCHNGEAV80ALERTCFG_MOVEDTECAV81ALERTCFG_SASETTLEAV82ALERTCFG_T24ECMINAV83ALERTCFG_T24ECMAXAV84ALERTCFG_HCDELAYAV85EFCFG_RAP_THAV86ALERTCFG_MSDPTAV87CMPSTKTMAV88CMPFLRTMAV89HEATSINK_HSCTRLOFAV90HEATSINK_HSHTMPDBAV91HEATSINK_HSHTEMPAV92ANALGOUT_DAMPCMDAV93ANALGOUT_DAMPCMD2AV94ANALGOUT_HEATCMDAV95ANALGOUT_HMVAV96ANALGOUT_HMV2AV97ANALGOUT_EFCMDAV98ANALGOUT_ERV_OAFAV99ANALGOUT_CMPA1CMDAV100ANALGOUT_CMPA2CMDAV101ANALGOUT_CMPB1CMDAV102ANALGOUT_CMPB2CMDAV103ANALGOUT_IDFCMDAV104ANALGOUT_ODF1CMDAV105ANALGOUT_ODF2CMDAV106ANALGOUT_ODF3CMDAV107ANALGOUT_EXVA1CMDAV108ANALGOUT_EXVA2CMDAV109ANALGOUT_EXVB1CMDAV110ANALGOUT_EXVB2CMDAV111ANALOGIN_OACFMAV112ANALOGIN_OACFMRSTAV113ANALOGIN_OD3P_CMDAV114ANALOGIN_EF3P_CMDAV115ANALOGIN_SF3P_CMDAV116ANALOGIN_IAQOPRSTAV117ANALOGIN_IAQAV118ANALOGIN_OAQAV119ANALOGIN_OARHAV120AIRTEMP_OADPAV121ANALOGIN_RARHAV122ANALOGIN_SARHAV123AIRTEMP_SADPAV124ANALOGIN_SPRHAV125ANALOGIN_MARHAV126ANALOGIN_ZDPAV127ANALOGIN_DAMPPOSAV128ANALOGIN_DAMPPOS2AV129ANALOGIN_HMDAV130ANALOGIN_HMD2AV131ANALOGIN_CMPA1SPDAV132ANALOGIN_CMPA2SPDAV133ANALOGIN_CMPB1SPDAV134ANALOGIN_CMPB2SPDAV135ANALOGIN_ODF1SPDAV136ANALOGIN_ODF2SPDAV137ANALOGIN_ODF3SPDAV138ANALOGIN_IDFSPDAV139ANALOGIN_IDFRPMAV140ANALOGIN_EFSPDAV141ANALOGIN_EXV_A1AV142ANALOGIN_EXV_A2AV143ANALOGIN_EXV_B1AV144ANALOGIN_EXV_B2AV145ANALOGIN_SPSRAV146ANALOGIN_DLCAV147ANALOGIN_PFPDAV148ANALOGIN_FFPDAV149ANALOGIN_OA_ENTHAV150ANALOGIN_RA_ENTHAV151EMPTY_NOPOINTAV152COMMADDR_AUX1AV153COMMADDR_NGC1AV154COMMADDR_PD4_EXV1AV155COMMADDR_SIOB1AV156COMMADDR_SIOB2AV157COMMADDR_SIOB3AV158COMMADDR_SYSTEMVUAV159COMMADDR_COMP_A1AV160COMMADDR_IDF_1AV161COMMADDR_IDF_2AV162COMMADDR_IDF_3AV163COMMADDR_IDF_4AV164COMMADDR_IDF_5AV165COMMADDR_IDF_6AV166COMMADDR_ODF_1AV167COMMADDR_ODF_2AV168COMMADDR_ODF_3AV169COMMADDR_RF_1AV170COMMADDR_RF_2AV171COMMADDR_PWREXH_1AV172COMMADDR_PWREXH_2AV173LEN_statusAV174LEN_nb_message_10sAV175LEN_nb_nb_arh_busy_10sAV176LEN_total_nb_arh_busyAV177LEN_total_nb_messageAV178LEN_total_nb_nackAV179LEN_total_nb_no_respAV180MODSCAN_statusAV181MODSCAN_nb_message_10sAV182MODSCAN_total_nb_messageAV183MODSCAN_total_nb_nackAV184MODSCAN_total_nb_no_respAV185MODSCAN_total_nb_rtry_flAV186COOLCFG_DEMANDAV187COOLCFG_SPLYDBAV188COOLCFG_TPCTLRSTAV189COOLCFG_RSTRTIOAV190COOLCFG_RSTLMITAV191COOLCFG_CLTRENDAV192COOLCFG_CLTNDTMAV193COOLCFG_GAP_CLHTAV194SERVICE_TCSTCOOLAV195COOLSTP_CLSP_OCCAV196COOLSTP_CLSP_UNOAV197COOLSTP_SALOCLSPAV198COOLSTP_SAHICLSPAV199COOLSTP_HODALCLAV200COOLSTP_HODAHCLAV201COOLCFG_DOLOCLONAV202COOLCFG_DOLOCLOFAV203COOLCFG_DOHICLONAV204COOLSTP_VAVCLSPAV205COOLCFG_DOVAVCONAV206COOLCFG_DOVAVCOFAV207COOLSTP_SPLYAVSPAV208DHUMCFG_DMD_SRCAV209DHUMCFG_DHMATLCKAV210DHUMCFG_RHTOPTMEAV211DHUMCFG_RHTCLTMEAV212DHUMCFG_CCBYPTMEAV213DHUMCFG_CCPRGPOSAV214DHUMCFG_CCPRGTMEAV215DHUMSTP_DHUMRHSPAV216DHUMCFG_RLOS_ONAV217DHUMCFG_RLOS_OFFAV218DHUMSTP_CCTSTPAV219DISCOUT_POWEXH1AV220DMDLMCFG_DMDLMSRCAV221DMDLMCFG_AICLSELAV222DMDLMCFG_CAPLMSRCAV223COOLSTP_CLCAPSTPAV224COOLSTP_CAPLIMS1AV225COOLSTP_CAPLIMS2AV226COOLSTP_DMDLIMS1AV227COOLSTP_DMDLIMS2AV228HEATSTP_HTCAPSTPAV229HEATSTP_CAPLIMS1AV230HEATSTP_CAPLIMS2AV231HEATSTP_DMDLIMS1AV232HEATSTP_DMDLIMS2AV233COOLSTP_DMDRSTCLAV234HEATSTP_DMDRSTHTAV235EFCFG_CONTROLAV236EFCFG_MINSPDAV237EFCFG_MAXSPDAV238EFCFG_SPEED1AV239EFCFG_SPEED2AV240EFCFG_DAMPPOS1AV241EFCFG_DAMPPOS2AV242EFCFG_PEOAD1AV243EFCFG_PEOAD2AV244EFCFG_PEOAD3AV245EFCFG_PEOAD4AV246EFCFG_PEOAD5AV247EFCFG_PEOAD6AV248EFCFG_EXFPURGEAV249EFCFG_EXFEVACAV250EFSTP_EFBPSPTAV251EMAILCFG_SendAV252EMAILCFG_portNbrAV253EMAILCFG_srvTimAV254EMAILCFG_attach_blackboxAV255EQUIPCFG_RESWENAV256EQUIPCFG_AUXRELAYAV257EQUIPCFG_SIO1AI10AV258OCCSTNDTAV259UNITCFG_OCC_OTAV260ERVCFG_CHKTYPEAV261ERVCFG_TMPTOLAV262ERVCFG_ENTTOLAV263ERVCFG_MAXBYPOPAV264ERVCFG_MAXBYPCLAV265ERVCFG_ERVMINPSAV266ERVCFG_WHMINPOSAV267ERVCFG_ERVEFMINAV268ERVCFG_OFFTMPDBAV269ERVCFG_OFFENTDBAV270EXVSTP_SupHtA1AV271EXVSTP_SupHtA2AV272EXVSTP_SupHtB1AV273EXVSTP_SupHtB2AV274EXVSTP_EXVSTA1AV275EXVSTP_EXVSTA2AV276EXVSTP_EXVSTB1AV277EXVSTP_EXVSTB2AV278FRECLCFG_CHNGSELAV279FRECLCFG_DIFFENTHAV280FRECLCFG_DRYBLBTHAV281FRECLCFG_DEWLIMTHAV282FRECLCFG_DIFFDBTHAV283FRECLCFG_IAQOADRSAV284HCSTATUS_HEATREQAV285HCSTATUS_SATCTLPTAV286HCSTATUS_CAPACTAV287IDFSTP_ZPSETPTAV288IDFCFG_SDPRLMITAV289GENUNIT_OCCUPIEDAV290MDESTS_DMD_DETAV291MDESTS_OP_STATEAV292GENUNIT_HEATCOOLAV293RFGTEMP_CCTAV294BACNET_SCH_ObjjAV295BACNET_loc_occAV296COOLSTP_HODACLSPAV297FILTER_STATUSAV298SERVICE1_M_FILTERAV299RFGTEMP_SGT1AV300RFGTEMP_DGTAAV301HMZR_CONDPURGAV302DHUMSTP_DHUMSADPAV303EQUIPCFG_FRZSWENAV304DMDLMCFG_DMDLMENAV305DMDLMCFG_DMDCPENAV306HEATCFG_HEATTTDBAV307HEATCFG_HTTRENDAV308HEATCFG_HTTNDTMAV309HEATCFG_HT2DTGAV310HEATCFG_HT2UTGAV311SERVICE_TCSTHEATAV312HEATCFG_HEAT_FODAV313HEATSTP_HTSP_OCCAV314HEATSTP_HTSP_UNOAV315HEATSTP_SALOHTSPAV316HEATSTP_SAHIHTSPAV317HEATSTP_HODALHTAV318HEATSTP_HODAHHTAV319HEATCFG_DOLOHTONAV320HEATCFG_DOLOHTOFAV321HEATCFG_DOHIHTONAV322IDFCFG_OPSELECTAV323IDFCFG_SAVTYPEAV324IDFCFG_IDFMNSPDAV325IDFCFG_IDFMXSPDAV326IDFCFG_IDFCSPD1AV327IDFCFG_IDFMCSPDAV328IDFCFG_IDFCSPD2AV329IDFCFG_SAVLCCTHAV330IDFCFG_SAVMCCTHAV331IDFCFG_SAVHCCTHAV332IDFCFG_IDFHSPD1AV333IDFCFG_IDFHSPD2AV334IDFCFG_IDFPURGEAV335IDFCFG_IDFPRESSAV336IDFCFG_IDFEVACAV337IDFCFG_OCCUCFGAV338IDFCFG_UNOCCFGAV339IDFCFG_SDPRSAV340IDFCFG_SDPRRTIOAV341IDFCFG_SDPRTIMEAV342IDFCFG_SDPRZDPAV343IDFSTP_CO2LVLAV344IDFSTP_DUCTSETAV345IDFSTP_AIRFLOWAV346CMPASTS_BOOSTSTAAV347ANALOGIN_SPRHNETAV348ANALOGIN_RARHNETAV349ANALOGIN_OACFMNETAV350ANALOGIN_OCFMRNETAV351ANALOGIN_IAQORNETAV352AIRPRESS_BPNETAV353ANALOGIN_EF3P_NETAV354ANALOGIN_OD3P_NETAV355ANALOGIN_SF3P_NETAV356ANALOGIN_OAQNETAV357ANALOGIN_IAQNETAV358ANALOGIN_IAQRNETAV359AIRPRESS_SDP_NETAV360AIRTEMP_SPTNETAV361AIRTEMP_SPTONETAV362AIRTEMP_OATNETAV363GENUNIT_NETOCCAV364ANALOGIN_SPSR_NETAV365ANALOGIN_ZDPNETAV366OCCSBNETAV367ZS_OCCSBAV368OADCFG_ECONCTRLAV369OADCFG_IAQOCFGAV370OADCFG_MINPOSAV371OADCFG_MAXPOSAV372OADCFG_MINOADCPAV373OADCFG_OADEVACAV374IDFCFG_VENTSPD1AV375IDFCFG_VENTSPD2AV376IDFCFG_VENTSPD3AV377IDFCFG_VENTSPD4AV378OADCFG_OADPOS1AV379OADCFG_OADPOS2AV380OADCFG_OADPOS3AV381OADCFG_OADPOS4AV382OADCFG_IAQRESETAV383OADCFG_IAQOTHAV384OADCFG_IAQODBAV385OADCFG_IAQOPOSAV386OADCFG_IAQPDURAV387OADCFG_IAQPLOCKAV388OADCFG_IAQPRGLLAV389OADCFG_IAQPRGHLAV390OADCFG_IAQPLOTPAV391OADCFG_IAQPHITPAV392OADCFG_IAQCFMRSAV393OADCFG_PRGSHORTAV394OADCFG_PRGLONGAV395FRECLCFG_ODAIRQTHAV396OADCFG_OABPORENAV397OADCFG_OABPORTHAV398OADCFG_OABPORDBAV399OADCFG_CFMSPAV400RFGPRESS_SPAAV401RFGPRESS_SPBAV402RFGPRESS_DPAAV403RFGPRESS_DPBAV404RFGTEMP_SSTAAV405RFGTEMP_SSTBAV406RFGTEMP_SDTAAV407RFGTEMP_SDTBAV408RFGTEMP_SSHA1AV409RFGTEMP_SSHA2AV410RFGTEMP_SSHB1AV411RFGTEMP_SSHB2AV412RFGTEMP_SGTA1AV413RFGTEMP_SGTA2AV414RFGTEMP_SGTB1AV415RFGTEMP_SGTB2AV416RFGTEMP_OILTSMPAAV417RUNTIME_COMPA1RTAV418RUNTIME_COMPA1SCAV419RUNTIME_COMPA1RCAV420RUNTIME_COMPA2RTAV421RUNTIME_COMPA2SCAV422RUNTIME_COMPA2RCAV423RUNTIME_COMPB1RTAV424RUNTIME_COMPB1SCAV425RUNTIME_COMPB1RCAV426RUNTIME_COMPB2RTAV427RUNTIME_COMPB2SCAV428RUNTIME_COMPB2RCAV429RUNTIME_CND1_RTAV430RUNTIME_CND1_SCAV431RUNTIME_CND1_RCAV432RUNTIME_CND2_RTAV433RUNTIME_CND2_SCAV434RUNTIME_CND2_RCAV435RUNTIME_CND3_RTAV436RUNTIME_CND3_SCAV437RUNTIME_CND3_RCAV438RUNTIME_IDF_RTAV439RUNTIME_IDF_SCAV440RUNTIME_IDF_RCAV441RUNTIME_EFAN_RTAV442RUNTIME_EFAN_SCAV443RUNTIME_EFAN_RCAV444RUNTIME_SHEAT_RTAV445RUNTIME_SHEAT_SCAV446RUNTIME_SHEAT_RCAV447RUNTIME_HMVLV_RTAV448RUNTIME_HMVLV_SCAV449RUNTIME_HMVLV_RCAV450RUNTIME_DAMP_RTAV451RUNTIME_DAMP_SCAV452RUNTIME_DAMP_RCAV453RUNTIME_CCHRA_RTAV454RUNTIME_CCHRA_SCAV455RUNTIME_CCHRA_RCAV456RUNTIME_CCHRB_RTAV457RUNTIME_CCHRB_SCAV458RUNTIME_CCHRB_RCAV459RUNTIME_OILACYSCAV460RUNTIME_OILBCYSCAV461CMPASTS_OILRECACAV462CMPASTS_ORTMLFTAAV463CMPBSTS_OILRECACAV464CMPBSTS_ORTMLFTBAV465RUNTIME_HUMPUSCAV466GENUINIT_FILT_RTAV467SERVICE_MAXOACFMAV468SERVICE1_HTTOCLAV469SERVICE1_CLTOHTAV470SERVICE1_ZDORCAPAV471COOLCFG_CCHTHAAV472COOLCFG_CCHTHBAV473FRECLCFG_FCOOL_TGAV474COOLSTP_CMPMAXA1AV475COOLSTP_CMPMINA1AV476COOLSTP_CMPMAXA2AV477COOLSTP_CMPMINA2AV478COOLSTP_CMPMAXB1AV479COOLSTP_CMPMINB1AV480COOLSTP_CMPMAXB2AV481COOLSTP_CMPMINB2AV482COOLCFG_SATLO_DBAV483COOLCFG_SATHI_DBAV484DHUMCFG_DHUMMODEAV485COOLCFG_SCT_HLIMAV486COOLCFG_SCT_LLIMAV487DHUMCFG_RHMINPOSAV488DHUMCFG_RHMAXPOSAV489DHUMCFG_RHSTARTAV490DHUMCFG_RHTIMEAV491SERVICE1_CMPMATLAV492SERVICE1_CMPOATLAV493CNDSTP_SDTTEMP1AV494CNDSTP_SDTTEMP2AV495CNDSTP_SDTTEMP3AV496COOLCFG_CFSPDMN1AV497COOLCFG_CFSPDMX1AV498COOLCFG_CFSTSPD1AV499SERVICE1_SVTESTMTAV500SERVICE_NETINTOAV501SERVICE_LLAGCFGAV502SERVICE_RCYCLIMAV503SERVICE_RCYCDBAV504DHUMCFG_OILLOWTHAV505DHUMCFG_OILHITHAV506DHUMCFG_OILTIMEAV507FACTORY_OILRHLDTAV508FACTORY_OILRECSPAV509FACTORY_OILTIME1AV510FACTORY_OILTIME2AV511FACTORY_LOWOILAAV512FACTORY_LOWOILBAV513FACTORY_LOWOILTMAV514FACTORY_OILRSTLMAV515FACTORY_LOWOILRTAV516STATES_MINTILOCAV517LABONLY_CAPAPCTAV518LABONLY_CAPACTAV519CMPA1STS_LOADREQAV520CMPA2STS_LOADREQAV521CMPB1STS_LOADREQAV522CMPB2STS_LOADREQAV523OUTPUTS_EXVA1OBJAV524OUTPUTS_EXVA2OBJAV525OUTPUTS_EXVB1OBJAV526OUTPUTS_EXVB2OBJAV527COOLSTP_ACTV_SPAV528CMPASTS_SSTENVMNAV529CMPASTS_SSTENVMXAV530CMPASTS_SDTENVMNAV531CMPASTS_SDTENVMXAV532CMPBSTS_SSTENVMNAV533CMPBSTS_SSTENVMXAV534CMPBSTS_SDTENVMNAV535CMPBSTS_SDTENVMXAV536CMPASTS_SSTABSMNAV537CMPASTS_SSTABSMXAV538CMPASTS_SDTABSMNAV539CMPASTS_SDTABSMXAV540CMPBSTS_SSTABSMNAV541CMPBSTS_SSTABSMXAV542CMPBSTS_SDTABSMNAV543CMPBSTS_SDTABSMXAV544LAB_SSHCMDA1AV545LAB_SSHSTPA1AV546LAB_SSHCMDA2AV547LAB_SSHSTPA2AV548LAB_SSHCMDB1AV549LAB_SSHSTPB1AV550LAB_SSHCMDB2AV551LAB_SSHSTPB2AV552LAB_DSTKPA1AV553LAB_DSTTIA1AV554LAB_SSHKPA1AV555LAB_SSHTIA1AV556LAB_DSTKPA2AV557LAB_DSTTIA2AV558LAB_SSHKPA2AV559LAB_SSHTIA2AV560LAB_DSTKPB1AV561LAB_DSTTIB1AV562LAB_SSHKPB2AV563LAB_SSHTIB2AV564LABONLY_DHUM_REQAV565LAB_SDTTARGAV566LAB_SATCTLPTAV567GENUNIT_SMAXCCAPAV568GENUNIT_SMAXHCAPAV569LAB_OACFMCPAV571HOME_SCREEN_IDAV573BACNET_ALC_PRIMEAV574EQUIPCFG_SIO3DI7AV575LPALMHYSBV1ALARMRST_RST_ALMBV2UNITCFG_PG_SP_ENBV3UNITCFG_PG_BP_ENBV4ALERTCFG_LOCK_OUTBV5ALERTCFG_T24ENABBV6IDFFDBK_STATUSBV7COOLCFG_TMPDVNTBV8SVCOUT_CMTRNDACBV9DHUMCFG_UNOCENABBV10DHUMCFG_SUPPHEATBV11DHUMCFG_DHUMVENTBV12DHUMCFG_DHUMVAVBV13DHUMCFG_DHUMHICLBV14DHUMCFG_DHUMLOCLBV15DHUMCFG_DHUMHIHTBV16DHUMCFG_DHUMLOHTBV17OADCFG_OADHUMENBV18DHUMCFG_OFDHUMENBV19DHUMCFG_UFDHUMENBV20DISCIN_TSTAT_GBV21DISCIN_TSTAT_Y1BV22DISCIN_TSTAT_Y2BV23DISCIN_TSTAT_W1BV24DISCIN_TSTAT_W2BV25DISCIN_FIRESWBV26DISCIN_SMOKESWBV27DISCIN_SMKPRGSWBV28DISCIN_PMR_STATBV29DISCIN_SHTDWNSWBV30DISCIN_FILTSTATBV31DISCIN_IDF_LSMBV32DISCIN_HT_ALARMBV33DISCIN_CNDOSWBV34DISCIN_DEHUMSWBV35DISCIN_CMPFBKA1BV36DISCIN_CMPFBKA2BV37DISCIN_CMPFBKB1BV38DISCIN_CMPFBKB2BV39DISCIN_HPSABV40DISCIN_HPSBBV41DISCIN_RESWBV42DISCIN_ERV_FRSTBV43DISCIN_WHEEL_STBV44DISCIN_ERVFSSBV45DISCIN_DLS1BV46DISCIN_DLS2BV47DISCIN_IGCFANSWBV48DISCIN_PFPSSBV49DISCIN_PRESSSWBV50DISCIN_EVACSWBV51DISCIN_FRZSWBV52DISCIN_PPSSBV53DISCIN_IAQSWBV54DISCIN_OAQSWBV55DISCIN_ODENTHSWBV56DISCIN_ENEGPRESBV57DISCIN_VSOLSWABV58DISCIN_INRFGLKBV59DISCIN_OUTRFGLKBV60DISCOUT_CPA1BV61DISCOUT_CMPRELA1BV62DISCOUT_CPA2BV63DISCOUT_CMPRELA2BV64DISCOUT_CPB1BV65DISCOUT_CPB2BV66DISCOUT_IDFBYRELBV67DISCOUT_ODF1BV68DISCOUT_ODF2BV69DISCOUT_ODF3BV70DISCOUT_CCHRABV71DISCOUT_CCHRBBV72DISCOUT_HMSBV73DISCOUT_RH3PRLYBV74DISCOUT_ERVWHEELBV75DISCOUT_STGHEAT1BV76DISCOUT_STGHEAT2BV77DISCOUT_STGHEAT3BV78DISCOUT_STGHEAT4BV79DISCOUT_STGHEAT5BV80DISCOUT_STGHEAT6BV81DISCOUT_BYP_DAMPBV82DISCOUT_ZDORBV83DISCOUT_ALMOUTBV84DISCOUT_HIRBV85DISCOUT_HMFRBV86DISCOUT_HRRBV87DISCOUT_PEABV88DISCOUT_PEBBV89DISCOUT_PECBV90DISCOUT_AUTOADDRBV91DMDLMCFG_DLSWSENBV92OCCSB_ENBV93EQUIPCFG_DMDLIMBV94EQUIPCFG_SMOKEENBV95EQUIPCFG_TSTATENBV96EQUIPCFG_HUMSWENBV97EQUIPCFG_FILTSWENBV98EQUIPCFG_PMRENBV99EQUIPCFG_SHTDWNENBV100EQUIPCFG_ZDORENBV101EQUIPCFG_ALARMENBV102EQUIPCFG_EATENBV103EQUIPCFG_OACFMENBV104EQUIPCFG_IDFVFDBYBV105EQUIPCFG_SF3PENBV106EQUIPCFG_SPSRENBV107EQUIPCFG_EF3PENBV108EQUIPCFG_RH3PENBV109EQUIPCFG_OAD3PENBV110EQUIPCFG_ERVENBV111EQUIPCFG_ERVOAFENBV112EQUIPCFG_ERVBYPENBV113EQUIPCFG_FIRESWENBV114EQUIPCFG_EVACENBV115EQUIPCFG_PRESSENBV116EQUIPCFG_EFENBV117EQUIPCFG_ECONENBV118EQUIPCFG_HT1ENBV119EQUIPCFG_HT2ENBV120EQUIPCFG_HT3ENBV121EQUIPCFG_HT4ENBV122EQUIPCFG_DMDRSTENBV123EQUIPCFG_CONDENBV124EQUIPCFG_ENTHSWENBV125EQUIPCFG_IAQORENBV126EQUIPCFG_OAQSWENBV127EQUIPCFG_IAQSWENBV128EXVSTP_SETPTENBBV129EXVSTP_EXVSTENBBV130FRECLCFG_FREECLENBV131FRECLCFG_UFCBV132FRECLCFG_DRYBLBBV133FRECLCFG_DEWLIMBV134HEATCFG_HTMPDVNTBV135HEATCFG_HTTEMPCLBV136SVCOUT_CMTRNDAHBV137HEATCFG_HEAT_EBLBV138MDESTS_ERVCHECKBV139MDESTS_DHUMPURGBV140LINK_ACTBV141NETIN_Y1_NETBV142NETIN_Y2_NETBV143NETIN_W1_NETBV144NETIN_W2_NETBV145NETIN_G_NETBV146NETIN_HSTATNETBV147FRECLCFG_ODAIRQBV148OADCFG_IAQSBVENBV149OADCFG_IAQPOPBV150RESET_RT_CMPA1BV151RESET_RT_CMPA2BV152RESET_RT_CMPB1BV153RESET_RT_CMPB2BV154RESET_RT_CND1BV155RESET_RT_CND2BV156RESET_RT_CND3BV157RESET_RT_CNDABV158RESET_RT_CNDBBV159RESET_RT_IDFBV160RESET_RT_EFANBV161RESET_RT_CCHABV162RESET_RT_CCHBBV163RESET_RT_CCHBV164RESET_RT_DAMPBV165RESET_RT_STGHEATBV166RESET_RT_HMZRVLVBV167GENUNIT_FLTR_RSTBV168RESET_RT_OILCYCLABV169RESET_RT_OILCYCLBBV170RESET_RT_HUMPURCBV171CNDSTP_SDTStpEnBV172CNDSTP_SPDStpENBV173SERVICE_DISABLEMBV174COOLCFG_LCRCOBV175COOLCFG_VSCFS_ORBV176STATES_OKTOFRCLBV177MDESTS_MODETCSTBV178STATES_PURGEACTBV179OCCSBBV180STATES_OKTOFDHMBV181SWTCHCFG_HTALMINVBV182SWTCHCFG_CNDSWINVBV183SWTCHCFG_SMKSWINVBV184SWTCHCFG_IDFSWINVBV185SWTCHCFG_HPSAINVBV186SWTCHCFG_TSTGINVBV187SWTCHCFG_TSTY1INVBV188SWTCHCFG_TSTY2INVBV189SWTCHCFG_DHMSWINVBV190SWTCHCFG_TSTW1INVBV191SWTCHCFG_TSTW2INVBV192SWTCHCFG_FLTSWINVBV193SWTCHCFG_RESWINVBV194SWTCHCFG_PMRSWINVBV195SWTCHCFG_FRESWINVBV196SWTCHCFG_FRSTINVBV197SWTCHCFG_WHLSTINVBV198SWTCHCFG_HTENINVBV199SWTCHCFG_DORINVBV200SWTCHCFG_CMPA1INVBV201SWTCHCFG_CMPA2INVBV202SWTCHCFG_CCHRAINVBV203SWTCHCFG_PEENINVBV204SWTCHCFG_EVBYPINVBV205SWTCHCFG_ERVINVBV206SWTCHCFG_ALARMINVBV207UNITCFG_AUTRSTBV208LABONLY_SYSONBV209ALM_61413BV210ALM_61085BV211ALM_61086BV212ALM_62051BV213ALM_61051BV214ALM_60051BV215ALM_62052BV216ALM_61052BV217ALM_60052BV218ALM_62054BV219ALM_61054BV220ALM_60054BV221ALM_62055BV222ALM_61055BV223ALM_60055BV224ALM_60057BV225ALM_61057BV226ALM_60058BV227ALM_61058BV228ALM_61072BV229ALM_61073BV230ALM_60073BV231ALM_60700BV232ALM_61706BV233ALM_60706BV234ALM_61075BV235ALM_60075BV236ALM_60710BV237ALM_61090BV238ALM_60090BV240ALM_61092BV241ALM_60092BV243ALM_60110BV244ALM_60120BV245ALM_61120BV246ALM_60121BV247ALM_61121BV248ALM_61122BV249ALM_61123BV250ALM_60126BV251ALM_61126BV252ALM_60127BV253ALM_61127BV254ALM_61128BV255ALM_60128BV256ALM_61069BV257ALM_60071BV258ALM_61425BV259ALM_61181BV260ALM_61426BV261ALM_61182BV262ALM_60140BV263ALM_60141BV264ALM_60142BV265ALM_60143BV266ALM_61102BV267ALM_61103BV268ALM_60104BV269ALM_60106BV270ALM_60107BV271ALM_60150BV272ALM_60151BV273ALM_61163BV274ALM_61164BV275ALM_60166BV276ALM_60167BV277ALM_60168BV278ALM_60169BV279ALM_60179BV280ALM_60175BV281ALM_61410BV282ALM_61411BV283ALM_61412BV284ALM_61094BV285ALM_61095BV286ALM_61096BV287ALM_61097BV288ALM_61300BV289ALM_61301BV290ALM_61302BV291ALM_61303BV292ALM_61304BV293ALM_61305BV294ALM_61308BV295ALM_61309BV296ALM_61312BV297ALM_61313BV298ALM_61314BV299ALM_61316BV300ALM_61317BV301ALM_61329BV302ALM_60329BV303ALM_61330BV304ALM_60330BV305ALM_61331BV306ALM_60331BV307ALM_61333BV308ALM_60333BV309ALM_61211BV310ALM_60211BV311ALM_61177BV312ALM_61178BV313ALM_61310BV314ALM_61311BV315ALM_60152BV316ALM_61190BV317ALM_60191BV318ALM_60195BV319ALM_60196BV320ALM_60184BV321ALM_60185BV322ALM_60186BV323ALM_60189BV324ALM_60190BV325ALM_60192BV326ALM_60193BV327ALM_60194BV328ALM_60197BV329ALM_60198BV330ALM_60199BV331ALM_60201BV332ALM_60627BV333ALM_60202BV334ALM_60203BV335ALM_60187BV336ALM_60188BV337ALM_61068BV338ALM_61074BV339ALM_61707BV340ALM_61421BV341ALM_61422BV342ALM_61423BV343ALM_61424BV344ALM_61434BV345ALM_60435BV346ALM_61435BV347ALM_61076BV348ALM_61077BV349ALM_61078BV350ALM_61082BV351ALM_61210BV352ALM_62210BV353ALM_60210BV354ALM_61220BV355ALM_60220BV356ALM_61221BV357ALM_61245BV358ALM_61335BV359ALM_60436BV360ALM_60400BV361ALM_60404BV362ALM_60405BV363ALM_60406BV364ALM_60407BV365ALM_61415BV366ALM_61416BV367ALM_61408BV368ALM_61318BV369ALM_61319BV370ALM_61615BV371ALM_61616BV372ALM_61617BV373ALM_61414BV374ALM_61352BV375ALM_61045BV376ALM_60046BV377ALM_60047BV378ALM_60048BV379ALM_61047BV380ALM_61048BV381ALM_60228BV382ALM_61079BV383ALM_61080BV384ALM_61222BV385ALM_60222BV386ALM_61223BV387ALM_60223BV388ALM_61224BV389ALM_60224BV390ALM_60420BV391ALM_60200BV392ALM_61084BV393ALM_60083BV394ALM_60081BV395ALM_62437BV396ALM_61153BV397ALM_60154BV398ALM_61155BV399ALM_60156BV400ALM_60157BV401ALM_61350BV402ALM_61351BV403ALM_61320BV404ALM_61321BV405ALM_61062BV406ALM_61322BV407ALM_61323BV408ALM_62445BV409ALM_63445BV410ALM_61445BV411ALM_60445BV412ALM_60433BV413ALM_60438BV414ALM_61112BV415ALM_61114BV416ALM_65000BV417ALM_65001BV418ALM_65002BV419ALM_65003BV420ALM_65004BV421ALM_65005BV422ALM_65006BV423ALM_65007BV424ALM_65008BV425ALM_65009BV426ALM_65010BV427ALM_65011BV428ALM_65012BV429ALM_65013BV430ALM_65014BV431ALM_65015BV432ALM_65016BV433ALM_65017BV434ALM_65018BV435ALM_65019BV437ALM_60629BV438ALM_61000BV439ALM_61147BV440ALM_60129BV441ALM_60130BV442ALM_61109BV443ALM_61087BV444ALM_61088BV445DISCOUT_VSCA1_SSBV446ALM_60091BV447ALM_60093BV448LPALMENBV449ALM_60266BV450ALM_60267BV451ALM_60268BV452ALM_60269BV453ALM_61628MV1MDESTS_CIRCAMDNMV2MDESTS_CIRCBMDNMV3MDESTS_CMPA1MDNMV4MDESTS_CMPA2MDNMV5MDESTS_CMPB1MDNMV6MDESTS_CMPB2MDNMV7MDESTS_ODF1MDNMV8MDESTS_ODF2MDNMV9MDESTS_ODF3MDNMV10MDESTS_IDFMDNUMMV11MDESTS_HEATRMDNMV12MDESTS_ECONMNUMMV13STATES_CIRCASTNMV14STATES_CIRCBSTNMV15STATES_CMPA1STNMV16STATES_CMPA2STNMV17STATES_CMPB1STNMV18STATES_CMPB2STNMV19STATES_ODF1STNMV20STATES_ODF2STNMV21STATES_ODF3STNMV22STATES_IDFNUMMV23STATES_RHTSTNUMMV24STATES_HEATRSTNMV25STATES_ECONNUMMV26STATES_OCCSRNUMMV27BACNET_ALC_COLOR
Integration notes
- Point availability varies by model, unit type, size and configuration; not every object exists on every unit.
- The guide prints no units or multistate texts for the BACnet objects. Metric Units and Percentage Conversion settings change how values read (percentages as 0-100 or 0.00-1.00).
- The guide's Appendix B prints the same 1,049-object BACnet table for 48/50V units on PIC 6.0 (only AV 571 is spelled in lower case there). Our separate 48/50K and 48/50V SmartVu PIC 6.1 entry (48-50-ART-SVU-1T) uses the same object names and instances for the 715 objects it lists.
- ALM_6xxxx BVs (instances 214-450) are one flag per alarm or alert code; the description is the code only (e.g. T322, A267).
- An Option column (Type 4, 5 or 6) is printed for every object but not explained in the guide; it is not captured here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
How many BACnet points does the Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0) have?
This list has 1049 BACnet objects: 572 analog values, 450 binary values, 27 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0) BACnet points are writable?
444 of the 1049 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0) BACnet documentation?
The source is SmartVu Controls Version 2.X for Light Commercial and Applied Rooftop Gas Heat/Electric Cooling and Electric Heat/Electric Cooling Units with PIC 6.0 Hardware - Integration Guide (Appendix A: BACnet Points for 48/50LC*H) (48-50-LRT-SMVU-2T), revision 4-25, published free by Carrier at https://brandportal.carrier.com/asset/372917a4-9cbe-4b10-b124-328f4316d083/48-50-LRT-SMVU-2T.pdf.
What are the minimum BACnet points to integrate the Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)?
Start with AV 363 GENUNIT_NETOCC (Network occupancy; Primary BAS Network must be BACnet); AV 195 COOLSTP_CLSP_OCC (Occupied cooling setpoint); AV 313 HEATSTP_HTSP_OCC (Occupied heating setpoint); BV 1 ALARMRST_RST_ALM (Alarm reset command); MV 22 STATES_IDFNUM (Indoor fan state); AV 289 GENUNIT_OCCUPIED (Confirms occupied/unoccupied); AV 7 AIRTEMP_SPT (Space temperature); AV 4 AIRTEMP_SAT (Supply air temperature); BV 83 DISCOUT_ALMOUT (Common alarm relay output).
How do I enable BMS control of the Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)?
Primary BAS Network sets which network drives the occupancy schedule (BACnet, CCN, a CCN local schedule or none); CCN schedule zero makes the unit always occupied. The guide does not explain the values of Network Occupancy (GENUNIT_NETOCC, AV 363). Occupancy Source (MV 26) shows where occupancy currently comes from.
Does the Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0) need a BACnet heartbeat or have a communication timeout?
The list includes Network Input Timeout (SERVICE_NETINTO, AV 500), but the guide does not explain it or give a default.
Can the BMS supply sensor values to the Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)?
Writable network inputs include Net SPT (AV 360), Net OAT (AV 362) and network thermostat calls Network Y1/Y2/W1/W2/G/HSTAT (BV 141-146). The guide does not explain how the unit selects them.
How do I check these points on the real 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: SmartVu Controls Version 2.X for Light Commercial and Applied Rooftop Gas Heat/Electric Cooling and Electric Heat/Electric Cooling Units with PIC 6.0 Hardware - Integration Guide (Appendix A: BACnet Points for 48/50LC*H) · 48-50-LRT-SMVU-2T · rev. 4-25. Object names, instances and units are reproduced as published; descriptions are our own.