Air-cooled scroll chiller controller · BACnet points list
Carrier AquaSnap 30RC 065-252 (Carrier Controller) BACnet points list
Updated 6 November 2026
The 30RC 065-252's Carrier Controller serves BACnet IP on its Ethernet port and BACnet MS/TP on an RS-485 port, enabled from the BACnet Standard Conf. menu. The object table has about 740 objects: command points come as read (_rd) and write (_wr) pairs with the writable copies at 10000+ instances, plus temperatures, pressures, circuit, fan and pump drive data, and one BV per Carrier alarm code (e.g. BV 101199).
This page lists 738 BACnet objects for the Carrier AquaSnap 30RC 065-252 (Carrier Controller) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaSnap 30RC 065-252 (Carrier Controller)
- Equipment
- Air-cooled scroll chiller controller
- Equipment type
- Chillers
- BACnet objects
- 738 (23 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1600001
- Also known as
- 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Enable BACnet (bacena) under Main Menu > Configuration > Network > BACnet, set the device ID and network, then select the Network control method with the Start/Stop button. Command through the _wr objects (start/stop, occupancy, control point, demand limit) and read run status, water temperatures, capacity and alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10012 | GENUNIT_CHIL_S_S_wr | Network start/stop command | Write |
| BV 10058 | GENUNIT_CHIL_OCC_wr | Network occupied command | Write |
| AV 10006 | GENUNIT_CTRL_PNT_wr | Leaving water control point from the BMS | Write |
| AV 10008 | GENUNIT_DEM_LIM_wr | Demand limit command | Write |
| AV 21 | GENUNIT_CTRL_TYP | Control type: Local, Network or Remote | Read |
| AV 22 | GENUNIT_STATUS | Running status | Read |
| AV 2 | TEMP_LWT | Leaving water temperature | Read |
| AV 1 | TEMP_EWT | Entering water temperature | Read |
| AV 9 | GENUNIT_CAP_T | Percent total capacity | Read |
| AV 990 | ALARMRST_ALM | Unit alarm state | Read |
Enable & remote start
Select the Network machine control method with the Start/Stop button; the unit then follows CCN, BACnet (if enabled) or Modbus (if enabled) commands and ignores the remote control contacts. Start/stop and occupancy are written to the _wr objects.
Heartbeat & communication loss
The manual says that if communication with the network is lost, the machine starts and is controlled locally.
Network setup
- BACnet Enable (bacena) defaults to Disable; the appendix lists 1 = BACnet IP and 2 = BACnet MS/TP.
- Defaults shown: network 1600, UDP port 47808, manual device ID 1600001, auto device ID option off, alarm reporting on.
- IP port interface option 0 = J5/J15, 1 = J16.
Watch out for
- Write the _wr object, not the _rd one; the _rd copy only reports the current value.
- The BACnet menu has a BACnet Manage Occupancy option (mng_occ, default No) and the list has a writable BACnet_BMS_OCC (AV 66, 0 = unocc, 1 = occ, 2 = none); check how they interact with CHIL_OCC before relying on either.
Carrier AquaSnap 30RC 065-252 (Carrier Controller) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 985 | ALARMRST_alarm_1 | Current Alarm 1 index | Read | ||
| AV | 980 | ALARMRST_alarm_1c | Current Alarm 1 | Read | ||
| AV | 986 | ALARMRST_alarm_2 | Current Alarm 2 index | Read | ||
| AV | 981 | ALARMRST_alarm_2c | Current Alarm 2 | Read | ||
| AV | 987 | ALARMRST_alarm_3 | Current Alarm 3 index | Read | ||
| AV | 982 | ALARMRST_alarm_3c | Current Alarm 3 | Read | ||
| AV | 988 | ALARMRST_alarm_4 | Current Alarm 4 index | Read | ||
| AV | 983 | ALARMRST_alarm_4c | Current Alarm 4 | Read | ||
| AV | 989 | ALARMRST_alarm_5 | Current Alarm 5 index | Read | ||
| AV | 984 | ALARMRST_alarm_5c | Current Alarm 5 | Read | ||
| AVmin | 990 | ALARMRST_ALM | Alarm Status | Read | ||
| BV | 104502 | ALM_AUX1_1_COM_F | Loss of communication with Fan AUX1 Board Number 1 | Read | ||
| BV | 104501 | ALM_AUX2_FS_FAN_1_COM_F | Loss of communication with FS Fan AUX2 board Number 1 | Read | ||
| BV | 104503 | ALM_AUX2_FS_FAN_2_COM_F | Loss of communication with FS Fan AUX2 board Number 2 | Read | ||
| BV | 115011 | ALM_CHWSTEMP_F | Primary/Secondary Common Leaving Fluid Thermistor | Read | ||
| BV | 101199 | ALM_CPA1_F | Compressor A1 Failure | Read | ||
| BV | 110016 | ALM_CPA1_REVERSE_ROT_F | Compressor A1 Not Started or Pressure Increase not established | Read | ||
| BV | 101299 | ALM_CPA2_F | Compressor A2 Failure | Read | ||
| BV | 110017 | ALM_CPA2_REVERSE_ROT_F | Compressor A2 Not Started or Pressure Increase not established | Read | ||
| BV | 101399 | ALM_CPA3_F | Compressor A3 Failure | Read | ||
| BV | 110018 | ALM_CPA3_REVERSE_ROT_F | Compressor A3 Not Started or Pressure Increase not established | Read | ||
| BV | 101499 | ALM_CPA4_F | Compressor A4 Failure | Read | ||
| BV | 110019 | ALM_CPA4_REVERSE_ROT_F | Compressor A4 Not Started or Pressure Increase not established | Read | ||
| BV | 102199 | ALM_CPB1_F | Compressor B1 Failure | Read | ||
| BV | 110020 | ALM_CPB1_REVERSE_ROT_F | Compressor B1 Not Started or Pressure Increase not established | Read | ||
| BV | 102299 | ALM_CPB2_F | Compressor B2 Failure | Read | ||
| BV | 110021 | ALM_CPB2_REVERSE_ROT_F | Compressor B2 Not Started or Pressure Increase not established | Read | ||
| BV | 102399 | ALM_CPB3_F | Compressor B3 Failure | Read | ||
| BV | 110022 | ALM_CPB3_REVERSE_ROT_F | Compressor B3 Not Started or Pressure Increase not established | Read | ||
| BV | 102499 | ALM_CPB4_F | Compressor B4 Failure | Read | ||
| BV | 110023 | ALM_CPB4_REVERSE_ROT_F | Compressor B4 Not Started or Pressure Increase not established | Read | ||
| BV | 155001 | ALM_DATABASE_F | Database Module Failure | Read | ||
| BV | 115003 | ALM_DEFROST_T_A_F | Circuit A Defrost Thermistor | Read | ||
| BV | 115004 | ALM_DEFROST_T_B_F | Circuit B Defrost Thermistor | Read | ||
| BV | 112001 | ALM_DP_A_F | Circuit A Discharge Transducer | Read | ||
| BV | 112002 | ALM_DP_B_F | Circuit B Discharge Transducer | Read | ||
| BV | 110028 | ALM_ELEC_BOX_F | Electrical Box Fault | Read | ||
| BV | 115001 | ALM_EWT_F | Water Exchanger Entering Fluid Thermistor Failure | Read | ||
| BV | 110051 | ALM_EXCH_FLOW_F | Water Exchanger Flow Switch Failure | Read | ||
| BV | 110001 | ALM_EXCH_FREEZE_F | Water Exchanger Freeze Protection | Read | ||
| BV | 157020 | ALM_EXV_A_F | Main EXV Stepper Motor Failure - Cir A | Read | ||
| BV | 157021 | ALM_EXV_B_F | Main EXV Stepper Motor Failure - Cir B | Read | ||
| BV | 104701 | ALM_FAN_DRIVE_A_COM_F | Loss of communication with VFD Fan Drive 1 Circuit A | Read | ||
| BV | 104702 | ALM_FAN_DRIVE_A2_COM_F | Loss of communication with VFD Fan Drive 2 Circuit A | Read | ||
| BV | 104703 | ALM_FAN_DRIVE_B_COM_F | Loss of communication with VFD Fan Drive 1 Circuit B | Read | ||
| BV | 104704 | ALM_FAN_DRIVE_B2_COM_F | Loss of communication with VFD Fan Drive 2 Circuit B | Read | ||
| BV | 104601 | ALM_FC_AUX1_COM_F | FC_AUX1_COM_F | Read | ||
| AV | 110220 | ALM_FC_COIL_VALVE_F | FC Coils Valve Failure | Write | ||
| AV | 110222 | ALM_FC_EVAP_VALVE_F | FC Evaporator Valve Failure | Read | ||
| AV | 115058 | ALM_FC_EVAP_WT_F | FC Evaporator Water Thermistor Failure | Read | ||
| BV | 115047 | ALM_FC_LWT_F | FC_LWT_F | Read | ||
| BV | 115048 | ALM_FC_OAT_F | FC_OAT_F | Read | ||
| BV | 110101 | ALM_FC_PROCESS_F | Free Cooling Process Failure | Read | ||
| BV | 115046 | ALM_FC_WLOOP_F | FC_WLOOP_F | Read | ||
| BV | 113005 | ALM_FGAS_NEEDED | Fgas check needed, call your maintenance company | Read | ||
| BV | 110090 | ALM_FLOW_CONFIG_F | Water Exchanger Flow Switch: Setpoint Configuration Failure | Read | ||
| BV | 110050 | ALM_FLUIDE_FAIL | Refrigerant Leakage Detection | Read | ||
| BV | 110043 | ALM_HEAT_LOW_EWT_F | Low Entering Water Temperature in Heating | Read | ||
| BV | 110008 | ALM_HIGH_SH_A_F | Circuit A High Superheat | Read | ||
| BV | 110009 | ALM_HIGH_SH_B_F | Circuit B High Superheat | Read | ||
| BV | 110063 | ALM_HP_SWITCH_A_F | Circuit A High Pressure Switch Failure | Read | ||
| BV | 110064 | ALM_HP_SWITCH_B_F | Circuit B High Pressure Switch Failure | Read | ||
| BV | 10128 | ALM_HR_COND_FREEZE_F | Heat Reclaim Condenser Freeze Protection | Read | ||
| BV | 15008 | ALM_HR_EWT_F | Reclaim Condenser Entering Thermistor | Read | ||
| BV | 10052 | ALM_HR_FLOW_SW_F | Heat Reclaim flow switch failure | Read | ||
| BV | 10129 | ALM_HR_HIGH_LWT_F | Heat Reclaim high Water Temperature | Read | ||
| BV | 15009 | ALM_HR_LWT_F | Reclaim Condenser Leaving Thermistor | Read | ||
| BV | 108001 | ALM_ILL_BRAND | Illegal Brand identifier | Read | ||
| BV | 107001 | ALM_ILL_FACT_CONF_F | Illegal Factory Configuration Number #1 to nn | Read | ||
| BV | 108000 | ALM_INI_FACT_CONF_F | No Factory Configuration | Read | ||
| BV | 110014 | ALM_INTER_LOCK_F | Customer Interlock Failure | Read | ||
| BV | 156001 | ALM_LENSCAN_F | Lenscan Module Failure | Read | ||
| BV | 110030 | ALM_LOSS_COM_MS_F | Primary/Secondary Communication Failure | Read | ||
| BV | 110029 | ALM_LOSS_COM_SM_F | Loss of Communication With System Manager | Read | ||
| BV | 110210 | ALM_LOW_DELTP_A_F | Low Delta Pressure Operation Failure - cir A | Read | ||
| BV | 110211 | ALM_LOW_DELTP_B_F | Low Delta Pressure Operation Failure - cir B | Read | ||
| BV | 110011 | ALM_LOW_SH_A_F | Circuit A Low Superheat | Read | ||
| BV | 110012 | ALM_LOW_SH_B_F | Circuit B Low Superheat | Read | ||
| BV | 110005 | ALM_LOW_SUCTION_A_F | Circuit A Low Saturated Suction Temperature | Read | ||
| BV | 110006 | ALM_LOW_SUCTION_B_F | Circuit B Low Saturated Suction Temperature | Read | ||
| BV | 115002 | ALM_LWT_F | Water Exchanger Leaving Fluid Thermistor Failure | Read | ||
| BV | 109001 | ALM_M_S_CONFIG_F | Primary Chiller Configuration Error Number #1 to nn | Read | ||
| BV | 110031 | ALM_NETWORK_EMSTOP_F | Unit is in Network emergency stop | Read | ||
| BV | 115010 | ALM_OAT_F | OAT Thermistor Failure | Read | ||
| BV | 104705 | ALM_PUMP_DRIVE_1_COM_F | Loss of communication with VFD Pump Drive Number 1 | Read | ||
| BV | 104706 | ALM_PUMP_DRIVE_2_COM_F | Loss of communication with VFD Pump Drive Number 2 | Read | ||
| BV | 110037 | ALM_REPEAT_HIGH_DGT_A_F | Circuit A - Repeated High Discharge Gas Overrides | Read | ||
| BV | 110038 | ALM_REPEAT_HIGH_DGT_B_F | Circuit B - Repeated High Discharge Gas Overrides | Read | ||
| BV | 110040 | ALM_REPEAT_LOW_SST_A_F | Circuit A - Repeated Low Suction Temp Overrides | Read | ||
| BV | 110041 | ALM_REPEAT_LOW_SST_B_F | Circuit B - Repeated Low Suction Temp Overrides | Read | ||
| BV | 110097 | ALM_SENSORS_SWAP_F | Water Exchanger Temperature Sensors Swapped | Read | ||
| BV | 113000 | ALM_SERV_MAINT_ALERT | Service Maintenance Alert Number # nn | Read | ||
| BV | 104901 | ALM_SIOB_A_COM_F | Loss of communication with Circuit A SIOB/CIOB board | Read | ||
| BV | 104902 | ALM_SIOB_B_COM_F | Loss of communication with Circuit B SIOB/CIOB board | Read | ||
| BV | 104906 | ALM_SIOB_EMM_COM_F | Loss of communication with Energy Management SIOB/CIOB board | Read | ||
| BV | 157001 | ALM_SIOB_LOWVOLT_CIRA_F | Circuit A SIOB/CIOB Low Voltage Failure | Read | ||
| BV | 157002 | ALM_SIOB_LOWVOLT_CIRB_F | Circuit B SIOB/CIOB Low Voltage Failure | Read | ||
| BV | 157006 | ALM_SIOB_LOWVOLT_EMM_F | EMM SIOB/CIOB Low Voltage Failure | Read | ||
| BV | 112004 | ALM_SP_A_F | Circuit A Suction Transducer | Read | ||
| BV | 112005 | ALM_SP_B_F | Circuit B Suction Transducer | Read | ||
| BV | 115021 | ALM_SPACE_TEMP_F | Space Temperature Thermistor | Read | ||
| BV | 115012 | ALM_SUCTION_T_A_F | Circuit A Suction Gas Thermistor | Read | ||
| BV | 115013 | ALM_SUCTION_T_B_F | Circuit B Suction Gas Thermistor | Read | ||
| BV | 135001 | ALM_VFAN_DRV_A1_ALERT | Circuit A VFD Fan Drive 1 Alert | Read | ||
| BV | 117001 | ALM_VFAN_DRV_A1_F | Circuit A VFD Fan Drive 1 Failure | Read | ||
| BV | 136001 | ALM_VFAN_DRV_A2_ALERT | Circuit A VFD Fan Drive 2 Alert | Read | ||
| BV | 118002 | ALM_VFAN_DRV_A2_F | Circuit A VFD Fan Drive 2 Failure | Read | ||
| BV | 137001 | ALM_VFAN_DRV_B1_ALERT | Circuit B VFD Fan Drive 1 Alert | Read | ||
| BV | 119001 | ALM_VFAN_DRV_B1_F | Circuit B VFD Fan Drive 1 Failure | Read | ||
| BV | 138001 | ALM_VFAN_DRV_B2_ALERT | Circuit B VFD Fan Drive 2 Alert | Read | ||
| BV | 120001 | ALM_VFAN_DRV_B2_F | Circuit B VFD Fan Drive 2 Failure | Read | ||
| BV | 139001 | ALM_VPUMP_DRV_1_ALERT | VFD Pump 1 Drive Alert | Read | ||
| BV | 121001 | ALM_VPUMP_DRV_1_F | VFD Pump 1 Drive Failure | Read | ||
| BV | 140001 | ALM_VPUMP_DRV_2_ALERT | VFD Pump 2 Drive Alert | Read | ||
| BV | 122001 | ALM_VPUMP_DRV_2_F | VFD Pump 2 Drive Failure | Read | ||
| BV | 106001 | ALM_WELDED_CONTACT_A_F | Circuit A Welded Contactor Failure | Read | ||
| BV | 106002 | ALM_WELDED_CONTACT_B_F | Circuit B Welded Contactor Failure | Read | ||
| BV | 111209 | ALM_WL_LO_PRESS_WARN | Water Loop: Low Pressure Warning | Read | ||
| BV | 111207 | ALM_WL_LOW_FLOW | Water Loop: Flow Too Low | Read | ||
| BV | 111208 | ALM_WL_PRESS_CROSS | Water Loop: Pressure Sensors Crossed | Read | ||
| BV | 111205 | ALM_WL_PRESS_ERR_IN_RUN | Water Loop: Pressure Error During Runtest | Read | ||
| BV | 111203 | ALM_WL_PRESS_TOO_LOW | Water Loop: Pressure Too Low | Read | ||
| BV | 111202 | ALM_WL_PRESS_ZERO_ERROR | Water Loop: Delta Pressure Error | Read | ||
| BV | 111204 | ALM_WL_PUMP_NOT_STARTED | Water Loop: Pump Not Started | Read | ||
| BV | 111206 | ALM_WL_PUMP_OVERLOAD | Water Loop: Pump Overload | Read | ||
| BV | 112024 | ALM_WP_IN_F | Water Exchanger Entering Fluid Transducer Failure | Read | ||
| BV | 112025 | ALM_WP_OUT_F | Water Exchanger Leaving Fluid Transducer Failure | Read | ||
| BV | 110032 | ALM_WPUMP1_F | Water Pump #1 Default | Read | ||
| BV | 110033 | ALM_WPUMP2_F | Water Pump #2 Default | Read | ||
| AV | 5039 | BACKUP_boil_th | Boiler OAT Threshold | Read | ||
| BV | 5042 | BACKUP_ehs_back | Last EHS for backup | Read | ||
| BV | 5043 | BACKUP_ehs_defr | Quick EHS for defrost | Read | ||
| AV | 5046 | BACKUP_ehs_kd | EHS Derivative Gain | Read | ||
| AV | 5045 | BACKUP_ehs_ki | EHS Integral Gain | Read | ||
| AV | 5044 | BACKUP_ehs_kp | EHS Proportional Gain | Read | ||
| AV | 5041 | BACKUP_ehs_pull | Electrical Pulldown Time | Read | ||
| AV | 5040 | BACKUP_ehs_th | Elec Stage OAT Threshold | Read | ||
| BV | 5439 | BACnet_auid_opt | Device Id Auto Option | Read | ||
| AV | 5438 | BACnet_bac_id_man | Device Id manual | Read | ||
| BV | 60 | BACnet_bacena | BACnet Enable | Read | ||
| BV | 61 | BACnet_bacunit | Metric Units? | Read | ||
| BV | 5440 | BACnet_balmena | Alarm reporting | Read | ||
| AV | 66 | BACnet_BMS_OCC | BMS occupancy request | Write | 0=Unoccupied, 1=Occupied, 2=None | |
| MV | 64 | BACnet_COLOR | ALC color value | Read | ||
| AV | 5442 | BACnet_conIFnam | IP port interface name | Read | ||
| AV | 63 | BACnet_ident | Device Id Actually Used | Read | ||
| BV | 5441 | BACnet_mng_occ | BACnet Manage Occupancy | Read | ||
| AV | 62 | BACnet_network | Network | Read | ||
| AV | 5437 | BACnet_port | UDP Port Number | Read | ||
| AV | 65 | BACnet_PRIME_V | ALC prime value | Read | ||
| BV | 5189 | CP_UNABL_un_cp_a1 | Compressor A1 Disable | Read | ||
| BV | 5190 | CP_UNABL_un_cp_a2 | Compressor A2 Disable | Read | ||
| BV | 5191 | CP_UNABL_un_cp_a3 | Compressor A3 Disable | Read | ||
| BV | 5192 | CP_UNABL_un_cp_a4 | Compressor A4 Disable | Read | ||
| BV | 5193 | CP_UNABL_un_cp_b1 | Compressor B1 Disable | Read | ||
| BV | 5194 | CP_UNABL_un_cp_b2 | Compressor B2 Disable | Read | ||
| BV | 5195 | CP_UNABL_un_cp_b3 | Compressor B3 Disable | Read | ||
| BV | 5196 | CP_UNABL_un_cp_b4 | Compressor B4 Disable | Read | ||
| AV | 5227 | DCFC_CFG_chil_del | Chiller Activation Delay | Read | ||
| AV | 5228 | DCFC_CFG_dband | Fan Start/Stop Dead Band | Read | ||
| AV | 5231 | DCFC_CFG_dg | Derivative Gain Vfan | Read | ||
| AV | 5238 | DCFC_CFG_dt_setp | Delta T Septoint | Read | ||
| AV | 5230 | DCFC_CFG_ig | Integral Gain Vfan | Read | ||
| AV | 5235 | DCFC_CFG_nb_fan | Number of Fix Speed Fans | Read | ||
| AV | 5234 | DCFC_CFG_nb_line | Number of Fan Lines | Read | ||
| AV | 5224 | DCFC_CFG_oat_s | OAT Selection | Read | ||
| AV | 5233 | DCFC_CFG_off_tmr | Fans Minimum Off Time | Read | ||
| AV | 5232 | DCFC_CFG_on_tmr | Fans Minimum On Time | Read | ||
| AV | 5229 | DCFC_CFG_pg | Proportional Gain Vfan | Read | ||
| AV | 5225 | DCFC_CFG_start_th | Start Valve Threshold | Read | ||
| AV | 5226 | DCFC_CFG_stop_th | Stop Valve Threshold | Read | ||
| AV | 5237 | DCFC_CFG_vf_delta | Vfan Stage Delta Speed | Read | ||
| BV | 5236 | DCFC_CFG_vfan | Variable Speed Fan Stage | Read | ||
| AV | 5751 | DCFC_CFG_vfan_max | Fan speed max | Read | ||
| AV | 5321 | DCFC_STA_dcfc_cap | FC Capacity | Read | ||
| AV | 5322 | DCFC_STA_f_stage | Fix Speed Fans Stage | Read | ||
| AV | 5327 | DCFC_STA_FC_FAN1H | DCFC Fan Stage 1 Hours | Read | ||
| AV | 5326 | DCFC_STA_FC_FAN1S | DCFC Fan Stage 1 Start | Read | ||
| AV | 5329 | DCFC_STA_FC_FAN2H | DCFC Fan Stage 2 Hours | Read | ||
| AV | 5328 | DCFC_STA_FC_FAN2S | DCFC Fan Stage 2 Start | Read | ||
| AV | 5331 | DCFC_STA_FC_FAN3H | DCFC Fan Stage 3 Hours | Read | ||
| AV | 5330 | DCFC_STA_FC_FAN3S | DCFC Fan Stage 3 Start | Read | ||
| AV | 5333 | DCFC_STA_FC_FAN4H | DCFC Fan Stage 4 Hours | Read | ||
| AV | 5332 | DCFC_STA_FC_FAN4S | DCFC Fan Stage 4 Start | Read | ||
| AV | 5335 | DCFC_STA_FC_FAN5H | DCFC Fan Stage 5 Hours | Read | ||
| AV | 5334 | DCFC_STA_FC_FAN5S | DCFC Fan Stage 5 Start | Read | ||
| AV | 5337 | DCFC_STA_FC_FAN6H | DCFC Fan Stage 6 Hours | Read | ||
| AV | 5336 | DCFC_STA_FC_FAN6S | DCFC Fan Stage 6 Start | Read | ||
| AV | 5339 | DCFC_STA_FC_FAN7H | DCFC Fan Stage 7 Hours | Read | ||
| AV | 5338 | DCFC_STA_FC_FAN7S | DCFC Fan Stage 7 Start | Read | ||
| AV | 5325 | DCFC_STA_FC_HOUR | DCFC Operating Hours | Read | ||
| AV | 5341 | DCFC_STA_FC_VFANH | DCFC Variable Fan Hours | Read | ||
| AV | 5340 | DCFC_STA_FC_VFANS | DCFC Variable Fan Start | Read | ||
| AV | 5318 | DCFC_STA_lwt | FC Leaving Water Temp | Read | ||
| BV | 5320 | DCFC_STA_m_dcfc | Free Cooling Mode Active | Read | ||
| AV | 5317 | DCFC_STA_oat | OAT Free Cooling | Read | ||
| AV | 5324 | DCFC_STA_pid_out | PID Output | Read | ||
| AV | 5323 | DCFC_STA_vf_speed | Varifan Speed | Read | ||
| AV | 5319 | DCFC_STA_wloop | FC Water Loop Temp | Read | ||
| BV | 5408 | DEFROST_def_ac_a | Defrost Active? | Read | ||
| BV | 5423 | DEFROST_def_ac_b | Defrost Active? | Read | ||
| AV | 5419 | DEFROST_def_ca_a | Defrost Fan Start Cal A | Read | ||
| AV | 5434 | DEFROST_def_ca_b | Defrost Fan Start Cal B | Read | ||
| AV | 5420 | DEFROST_def_of_a | Defrost Fan Offset Cal A | Read | ||
| AV | 5435 | DEFROST_def_of_b | Defrost Fan Offset Cal B | Read | ||
| AV | 5406 | DEFROST_def_se_a | Next Sequence Allowed in | Read | ||
| AV | 5421 | DEFROST_def_se_b | Next Sequence Allowed in | Read | ||
| AV | 5411 | DEFROST_defr_dua | Defrost Duration | Read | ||
| AV | 5426 | DEFROST_defr_dub | Defrost Duration | Read | ||
| AV | 5410 | DEFROST_DEFRT_A | Defrost Temperature | Read | ||
| AV | 5425 | DEFROST_DEFRT_B | Defrost Temperature | Read | ||
| AV | 5415 | DEFROST_delt_a | Delta: OAT - Mean SST | Read | ||
| AV | 5430 | DEFROST_delt_b | Delta: OAT - Mean SST | Read | ||
| AV | 5416 | DEFROST_delt_r_a | Reference Delta | Read | ||
| AV | 5431 | DEFROST_delt_r_b | Reference Delta | Read | ||
| AV | 5417 | DEFROST_delt_v_a | Delta - Reference Delta | Read | ||
| AV | 5432 | DEFROST_delt_v_b | Delta - Reference Delta | Read | ||
| AV | 5418 | DEFROST_fr_int_a | Frost Integrator Gain | Read | ||
| AV | 5433 | DEFROST_fr_int_b | Frost Integrator Gain | Read | ||
| AV | 5436 | DEFROST_FrDfrTmr | water below ctrl_pnt | Read | ||
| AV | 5407 | DEFROST_frost_a | Exchanger Frost Factor | Read | ||
| AV | 5422 | DEFROST_frost_b | Exchanger Frost Factor | Read | ||
| AV | 5409 | DEFROST_over_d_a | Override State | Read | ||
| AV | 5424 | DEFROST_over_d_b | Override State | Read | ||
| AV | 5413 | DEFROST_sct_dm_a | Mean SCT Calculation | Read | ||
| AV | 5428 | DEFROST_sct_dm_b | Mean SCT Calculation | Read | ||
| AV | 5412 | DEFROST_sctlim_a | SCT limit Calculation | Read | ||
| AV | 5427 | DEFROST_sctlim_b | SCT limit Calculation | Read | ||
| AV | 5414 | DEFROST_sst_dm_a | Mean SST Calculation | Read | ||
| AV | 5429 | DEFROST_sst_dm_b | Mean SST Calculation | Read | ||
| AV | 1024 | DRV_CTL2_drv_F_5 | Pump Drive 1 Frequency | Read | ||
| AV | 2024 | DRV_CTL2_drv_F_6 | Pump Drive 2 Frequency | Read | ||
| AV | 1021 | DRV_CTL2_drv_I_5 | Pump Drive 1 Current | Read | ||
| AV | 2021 | DRV_CTL2_drv_I_6 | Pump Drive 2 Current | Read | ||
| AV | 1023 | DRV_CTL2_drv_T_5 | Pump Drive 1 Torque | Read | ||
| AV | 2023 | DRV_CTL2_drv_T_6 | Pump Drive 2 Torque | Read | ||
| AV | 1022 | DRV_CTL2_drv_V_5 | Pump Drive 1 Voltage | Read | ||
| AV | 2022 | DRV_CTL2_drv_V_6 | Pump Drive 2 Voltage | Read | ||
| AV | 1025 | DRV_CTL2_drvpwr_1 | Fan Drive A Power | Read | ||
| AV | 1026 | DRV_CTL2_drvpwr_2 | Fan Drive A2 Power | Read | ||
| AV | 2025 | DRV_CTL2_drvpwr_3 | Fan Drive B Power | Read | ||
| AV | 2026 | DRV_CTL2_drvpwr_4 | Fan Drive B2 Power | Read | ||
| AV | 1020 | DRV_CTL2_drvpwr_5 | Pump Drive 1 Power | Read | ||
| AV | 2020 | DRV_CTL2_drvpwr_6 | Pump Drive 2 Power | Read | ||
| AV | 5306 | ENERGY_cEnergIn | Electrical Energy Input | Read | ||
| AV | 5305 | ENERGY_cEnergOu | Cooling Energy Output | Read | ||
| AV | 5310 | ENERGY_cop | Coef. Of Perf. (COP) | Read | ||
| AV | 5303 | ENERGY_cPwrIn | Electical Power Input | Read | ||
| AV | 5302 | ENERGY_cPwrOut | Cooling Power Output | Read | ||
| AV | 5304 | ENERGY_eer | Energy Efficiency (EER) | Read | ||
| AV | 5313 | ENERGY_energCop | Integrated COP | Read | ||
| AV | 5307 | ENERGY_energEer | Integrated EER | Read | ||
| AV | 5312 | ENERGY_hEnergIn | Electrical Energy Input | Read | ||
| AV | 5311 | ENERGY_hEnergOu | Heating Energy Output | Read | ||
| AV | 5309 | ENERGY_hPwrIn | Electical Power Input | Read | ||
| AV | 5308 | ENERGY_hPwrOut | Heating Power Output | Read | ||
| BV | 5314 | ENERGY_reset_en | Reset of Energy Counter | Read | ||
| BV | 5242 | EOLRES_j10_eol | End Of Line Resistor J10 | Read | ||
| BV | 5239 | EOLRES_j6_eol | End Of Line Res. J6(LEN) | Read | ||
| BV | 5240 | EOLRES_j7_eol | End Of Line Res. J7(CCN) | Read | ||
| BV | 5241 | EOLRES_j8_eol | End Of Line Resistor J8 | Read | ||
| AV | 5067 | FACTORY_country | Country 0=EU, 1=US, 2=CH | Read | ||
| BV | 5071 | FACTORY_dcfc_sel | DC Free Cooling Select | Read | ||
| BV | 5056 | FACTORY_desuper | Desuperheater Select | Read | ||
| BV | 5062 | FACTORY_dual_pmp | Factory Dual Water Pump | Read | ||
| BV | 5058 | FACTORY_emm_opt | Energy Management Module | Read | ||
| BV | 5057 | FACTORY_exch_htr | Exchanger Heater Select | Read | ||
| AV | 5066 | FACTORY_fac_pass | Factory Password | Read | ||
| AV | 5055 | FACTORY_fan_spd | Fan Speed | Read | ||
| AV | 5054 | FACTORY_fan_typ | Fan Type | Read | ||
| AV | 78 | FACTORY_fc_opt | Free Cooling Option | Read | ||
| AV | 5069 | FACTORY_flui_typ | Exchanger Fluid Type | Read | ||
| BV | 5070 | FACTORY_leak_chk | Leakage Charge Detection | Read | ||
| BV | 5072 | FACTORY_opt_119C | Option 119C Selection | Read | ||
| AV | 5711 | FACTORY_opt_41C | Option 41C: HR Heater | Read | ||
| AV | 5061 | FACTORY_pump_typ | Pump Type | Read | ||
| AV | 5065 | FACTORY_QM_code | QM code | Read | ||
| AV | 5710 | FACTORY_rclm_opt | Option 50: Heat Reclaim | Read | ||
| BV | 5068 | FACTORY_refrig | Unit Refrigerant Type | Read | ||
| AV | 5051 | FACTORY_unit_typ | Unit Type (Heat Pump=2) | Read | ||
| AV | 5053 | FACTORY_unitsize | Unit Capacity | Read | ||
| AV | 5073 | FACTORY2_cap_a1 | Compressor A1 Capacity | Read | ||
| AV | 5074 | FACTORY2_cap_a2 | Compressor A2 Capacity | Read | ||
| AV | 5075 | FACTORY2_cap_a3 | Compressor A3 Capacity | Read | ||
| AV | 5076 | FACTORY2_cap_a4 | Compressor A4 Capacity | Read | ||
| AV | 5077 | FACTORY2_cap_b1 | Compressor B1 Capacity | Read | ||
| AV | 5078 | FACTORY2_cap_b2 | Compressor B2 Capacity | Read | ||
| AV | 5079 | FACTORY2_cap_b3 | Compressor B3 Capacity | Read | ||
| AV | 5080 | FACTORY2_cap_b4 | Compressor B4 Capacity | Read | ||
| AV | 5089 | FACTORY2_ClExchTp | Exchanger Type | Read | ||
| AV | 5091 | FACTORY2_ClPipgTp | Piping Type | Read | ||
| AV | 5087 | FACTORY2_ClPumpTp | Pump Type | Read | ||
| AV | 5083 | FACTORY2_exvmax_a | EXV A Maximum Steps Nb | Read | ||
| AV | 5085 | FACTORY2_exvmax_b | EXV B Maximum Steps Nb | Read | ||
| AV | 5084 | FACTORY2_exvRat_a | EXV A Rate (steps/sec) | Read | ||
| AV | 5086 | FACTORY2_exvRat_b | EXV B Rate (steps/sec) | Read | ||
| AV | 5081 | FACTORY2_nb_fan_a | Circuit A Total Fans NB | Read | ||
| AV | 5082 | FACTORY2_nb_fan_b | Circuit B Total Fans NB | Read | ||
| BV | 5011 | GENCONF_auto_sel | Auto Changeover Select | Read | ||
| BV | 5010 | GENCONF_both_sel | Both Command Sel (HSM) | Read | ||
| BV | 5093 | GENCONF_ewt_opt | Entering Fluid Control | Read | ||
| AV | 5005 | GENCONF_heat_th | Heating OAT Threshold | Read | ||
| BV | 5009 | GENCONF_ice_cnfg | Ice Mode Enable | Read | ||
| AV | 5003 | GENCONF_lim_sel | Demand Limit Type Select | Read | ||
| AV | 5007 | GENCONF_nh_end | Night Mode End Hour | Read | ||
| AV | 5008 | GENCONF_nh_limit | Night Capacity Limit | Read | ||
| AV | 5006 | GENCONF_nh_start | Night Mode Start Hour | Read | ||
| AV | 5004 | GENCONF_off_on_d | Unit Off to On Delay | Read | ||
| AV | 5000 | GENCONF_prio_cir | Cir Priority Sequence | Read | ||
| BV | 5002 | GENCONF_ramp_sel | Ramp Loading Select | Read | ||
| BV | 5001 | GENCONF_seq_typ | Staged Loading Sequence | Read | ||
| AVmin | 9 | GENUNIT_CAP_T | Unit Total Capacity | Read | ||
| AV | 1017 | GENUNIT_CAPA_T | Cir A Total Capacity | Read | ||
| AV | 2017 | GENUNIT_CAPB_T | Cir B Total Capacity | Read | ||
| BV | 58 | GENUNIT_CHIL_OCC_rd | Net.: Cmd Occupied | Read | ||
| BVmin | 10058 | GENUNIT_CHIL_OCC_wr | Net.: Cmd Occupied | Write | ||
| BV | 12 | GENUNIT_CHIL_S_S_rd | Net.: Cmd Start/Stop | Read | ||
| BVmin | 10012 | GENUNIT_CHIL_S_S_wr | Net.: Cmd Start/Stop | Write | ||
| AV | 6 | GENUNIT_CTRL_PNT_rd | Control Point | Read | ||
| AVmin | 10006 | GENUNIT_CTRL_PNT_wr | Control Point | Write | ||
| AVmin | 21 | GENUNIT_CTRL_TYP | Unit control type | Read | 0=Local, 1=Network, 2=Remote | |
| AV | 4 | GENUNIT_CTRL_WT | Control Water Temp | Read | ||
| AV | 8 | GENUNIT_DEM_LIM_rd | Active Demand Limit Val | Read | ||
| AVmin | 10008 | GENUNIT_DEM_LIM_wr | Active Demand Limit Val | Write | ||
| BV | 13 | GENUNIT_EMSTOP_rd | Emergency Stop | Read | ||
| BV | 10013 | GENUNIT_EMSTOP_wr | Emergency Stop | Write | ||
| AV | 23 | GENUNIT_HC_SEL_rd | Heat/Cool Select | Read | ||
| AV | 10023 | GENUNIT_HC_SEL_wr | Heat/Cool Select | Write | ||
| AV | 11 | GENUNIT_min_left | Minutes Left for Start | Read | ||
| AV | 7 | GENUNIT_SP | Current Setpoint | Read | ||
| BV | 59 | GENUNIT_SP_OCC_rd | Setpoint Occupied? | Read | ||
| BV | 10059 | GENUNIT_SP_OCC_wr | Setpoint Occupied? | Write | ||
| AV | 24 | GENUNIT_SP_SEL_rd | Setpoint Select | Read | ||
| AV | 10024 | GENUNIT_SP_SEL_wr | Setpoint Select | Write | ||
| AVmin | 22 | GENUNIT_STATUS | Run Status | Read | ||
| AV | 5705 | HR_CFG_flowTmr | HR delay flow switch | Read | ||
| BV | 5694 | HR_CFG_hr_eco | HR eco mode? | Read | ||
| BV | 5693 | HR_CFG_hr_flui | HR condenser fluid | Read | ||
| BV | 5696 | HR_CFG_HRewtctl | HR Control on EWT? | Read | ||
| AV | 5699 | HR_CFG_kd_HR3wv | PID gain deri 3w valve | Read | ||
| AV | 5702 | HR_CFG_kd_HRFan | PID gain deri fan | Read | ||
| AV | 5698 | HR_CFG_ki_HR3wv | PID gain int 3w valve | Read | ||
| AV | 5701 | HR_CFG_ki_HRFan | PID gain int fan | Read | ||
| AV | 5697 | HR_CFG_kp_HR3wv | PID gain prop 3w valve | Read | ||
| AV | 5700 | HR_CFG_kp_HRFan | PID gain prop fan | Read | ||
| AV | 5704 | HR_CFG_maxHR3wv | 3WayValve/VarPmp max pos | Read | ||
| AV | 5706 | HR_CFG_minFloEn | Min flow 3wv enable | Read | ||
| AV | 5707 | HR_CFG_minFlow | Min flow 3wv position | Read | ||
| AV | 5703 | HR_CFG_minHRpmp | HR VarPump min pos | Read | ||
| BV | 5695 | HR_CFG_rev_3WV | HR reverse 3WV cmd? | Read | ||
| AV | 966 | HR_PARTIAL_DOWNTIME | Cumul Time Partial Alm | Read | ||
| AV | 967 | HR_TOTAL_DOWNTIME | Cumul Time Tripout Alm | Read | ||
| AV | 83 | HYD_FC_fc_cv_rq | FC Coil Valve Request | Read | ||
| BV | 79 | HYD_FC_FC_DSBLE_rd | Free Cooling Disable? | Read | ||
| AV | 82 | HYD_FC_fc_ev_rq | FC Evap Valve Request | Read | ||
| AV | 81 | HYD_FC_fcCapT | Total FC Capacity | Read | ||
| AV | 80 | HYD_FC_wLoopPstV | Water Loop Position | Read | ||
| BV | 43 | INPUTS_ELEC_BOX | Electrical Box Failure | Read | ||
| BV | 52 | INPUTS_FLOW_SW | Flow Switch Status | Read | ||
| BV | 45 | INPUTS_HC_SW | Remote HeatCool Switch | Read | ||
| AV | 5243 | INPUTS_HP_SW_A | High Pressure Switch A | Read | ||
| AV | 5244 | INPUTS_HP_SW_B | High Pressure Switch B | Read | ||
| AV | 5246 | INPUTS_LIM_4_20 | Capacity Limit Control | Read | ||
| BV | 18 | INPUTS_LIM_SW1 | Limit Switch 1 | Read | ||
| BV | 19 | INPUTS_LIM_SW2 | Limit Switch 2 | Read | ||
| BV | 16 | INPUTS_ONOFF_SW | Remote On/Off Switch | Read | ||
| BV | 14 | INPUTS_REM_LOCK | Remote Interlock Status | Read | ||
| BV | 48 | INPUTS_SETP_SW | Remote Setpoint Switch | Read | ||
| AV | 5245 | INPUTS_SP_RESET | Setpoint Reset Signal | Read | ||
| AV | 5374 | LAST_POR_date_of1 | PowerDown 1:day-mon-year | Read | ||
| AV | 5378 | LAST_POR_date_of2 | PowerDown 2:day-mon-year | Read | ||
| AV | 5382 | LAST_POR_date_of3 | PowerDown 3:day-mon-year | Read | ||
| AV | 5386 | LAST_POR_date_of4 | PowerDown 4:day-mon-year | Read | ||
| AV | 5390 | LAST_POR_date_of5 | PowerDown 5:day-mon-year | Read | ||
| AV | 5372 | LAST_POR_date_on1 | Power On 1:day-mon-year | Read | ||
| AV | 5376 | LAST_POR_date_on2 | Power On 2:day-mon-year | Read | ||
| AV | 5380 | LAST_POR_date_on3 | Power On 3:day-mon-year | Read | ||
| AV | 5384 | LAST_POR_date_on4 | Power On 4:day-mon-year | Read | ||
| AV | 5388 | LAST_POR_date_on5 | Power On 5:day-mon-year | Read | ||
| AV | 5375 | LAST_POR_time_of1 | PowerDown 1:hour-minute | Read | ||
| AV | 5379 | LAST_POR_time_of2 | PowerDown 2:hour-minute | Read | ||
| AV | 5383 | LAST_POR_time_of3 | PowerDown 3:hour-minute | Read | ||
| AV | 5387 | LAST_POR_time_of4 | PowerDown 4:hour-minute | Read | ||
| AV | 5391 | LAST_POR_time_of5 | PowerDown 5:hour-minute | Read | ||
| AV | 5373 | LAST_POR_time_on1 | Power On 1:hour-minute | Read | ||
| AV | 5377 | LAST_POR_time_on2 | Power On 2:hour-minute | Read | ||
| AV | 5381 | LAST_POR_time_on3 | Power On 3:hour-minute | Read | ||
| AV | 5385 | LAST_POR_time_on4 | Power On 4:hour-minute | Read | ||
| AV | 5389 | LAST_POR_time_on5 | Power On 5:hour-minute | Read | ||
| AV | 5351 | LOADFACT_cap_lim | Actual Capacity Limit | Read | ||
| AV | 5350 | LOADFACT_cap_t | Actual Capacity | Read | ||
| AV | 5354 | LOADFACT_cur_stag | Active Stage Number | Read | ||
| AV | 5366 | LOADFACT_eh_stage | Requested Electric Stage | Read | ||
| AV | 5368 | LOADFACT_ehs_stat | EHS status | Read | ||
| BV | 5367 | LOADFACT_ehspulld | Electrical Pulldown? | Read | ||
| AV | 5363 | LOADFACT_exv_v_a | EXV value A | Read | ||
| AV | 5364 | LOADFACT_exv_v_b | EXV value B | Read | ||
| AV | 5370 | LOADFACT_flowSw_s | Flow Switch Cfg status | Read | ||
| AV | 5371 | LOADFACT_hydKit_s | Hydronic Kit Status | Read | ||
| AV | 5358 | LOADFACT_minSct_a | Minimum SCT Threshold A | Read | ||
| AV | 5361 | LOADFACT_ov_exv_a | EXV Override Circuit A | Read | ||
| AV | 5362 | LOADFACT_ov_exv_b | EXV Override Circuit B | Read | ||
| AV | 5356 | LOADFACT_ov_hd_a | H P Ctrl Override Cir A | Read | ||
| AV | 5355 | LOADFACT_over_cap | Active Capacity Override | Read | ||
| AV | 5365 | LOADFACT_over_ehs | EHS Ctrl Override | Read | ||
| AV | 1013 | LOADFACT_pinch_a | Cooler Exchange DT Cir A | Read | ||
| AV | 2013 | LOADFACT_pinch_b | Cooler Exchange DT Cir B | Read | ||
| AV | 5369 | LOADFACT_req_pwr | Required Cooling Power | Read | ||
| AV | 5357 | LOADFACT_sct_ct_a | SCT Control Point Cir A | Read | ||
| AV | 5359 | LOADFACT_sh_sp_a | SH Setpoint Circuit A | Read | ||
| AV | 5360 | LOADFACT_sh_sp_b | SH Setpoint Circuit B | Read | ||
| AV | 5353 | LOADFACT_smz | Load/Unload Factor | Read | ||
| AV | 5349 | LOADFACT_tp_error | Controlled Temp Error | Read | ||
| AV | 5352 | LOADFACT_zm | Current Z Multiplier Val | Read | ||
| BV | 5401 | M_MSTSLV_cap_max | Max Available Capacity? | Read | ||
| AV | 5396 | M_MSTSLV_l_strt_d | Lag Start Delay | Read | ||
| AV | 5402 | M_MSTSLV_lagstat | Secondary lagstat | Read | ||
| BV | 5393 | M_MSTSLV_lead_sel | Lead Unit is the: | Read | ||
| BV | 5398 | M_MSTSLV_ll_chang | Lead/lag Changeover? | Read | ||
| AV | 5397 | M_MSTSLV_ll_hr_d | Lead/lag Hours Delta | Read | ||
| BV | 5399 | M_MSTSLV_ll_pull | Lead Pulldown? | Read | ||
| BV | 5392 | M_MSTSLV_ms_activ | Primary/Secondary Ctrl Active | Read | ||
| AV | 5400 | M_MSTSLV_ms_error | Primary/Secondary Error | Read | ||
| AV | 5404 | M_MSTSLV_slav_ewt | Secondary Entering Fluid | Read | ||
| AV | 5403 | M_MSTSLV_slav_hr | Secondary Operating Hours | Read | ||
| AV | 5405 | M_MSTSLV_slav_lwt | Secondary Leaving Fluid | Read | ||
| AV | 5395 | M_MSTSLV_slv_capt | Secondary Chiller Total Cap | Read | ||
| AV | 5394 | M_MSTSLV_slv_stat | Secondary Chiller State | Read | ||
| BV | 5210 | MAINTCFG_charge_c | Refrigerant Charge Ctrl | Read | ||
| AV | 5216 | MAINTCFG_fgas_frq | Fgas Check Freq (months) | Read | ||
| AV | 5214 | MAINTCFG_hr_freq | Frequency in hours | Read | ||
| AV | 5212 | MAINTCFG_mntn_typ | Maintenance Alert Type | Read | ||
| AV | 5213 | MAINTCFG_mth_freq | Frequency in months | Read | ||
| AV | 5215 | MAINTCFG_run_days | Running Days | Read | ||
| BV | 5209 | MAINTCFG_s_alert | Servicing Alert | Read | ||
| BV | 5211 | MAINTCFG_wloop_c | Water Loop Control | Read | ||
| BV | 5277 | MODES_m_2stpt | Second Setpoint In Use | Read | ||
| BV | 5295 | MODES_m_autoch | Auto Changeover Active | Read | ||
| BV | 5298 | MODES_m_boiler | Boiler Active | Read | ||
| BV | 5296 | MODES_m_defr_a | Defrost Active Circuit A | Read | ||
| BV | 5297 | MODES_m_defr_b | Defrost Active Circuit B | Read | ||
| BV | 5276 | MODES_m_delay | Start Up Delay In Effect | Read | ||
| BV | 5279 | MODES_m_demlim | Demand limit active | Read | ||
| BV | 5290 | MODES_m_dltp_a | Low Delta Press Cir A | Read | ||
| BV | 5291 | MODES_m_dltp_b | Low Delta Press Cir B | Read | ||
| BV | 5299 | MODES_m_ehs | Electric Heater Active | Read | ||
| BV | 5300 | MODES_m_ewtlck | Heating Low EWT Lockout | Read | ||
| BV | 5286 | MODES_m_hidgta | High DGT Circuit A | Read | ||
| BV | 5287 | MODES_m_hidgtb | High DGT Circuit B | Read | ||
| BV | 5288 | MODES_m_hiprsa | High Press Override CirA | Read | ||
| BV | 5289 | MODES_m_hiprsb | High Press Override CirB | Read | ||
| BV | 5293 | MODES_m_hsm | System Manager Active | Read | ||
| BV | 5301 | MODES_m_ice | Ice Mode In Effect | Read | ||
| BV | 5284 | MODES_m_lowsca | Low Suction Circuit A | Read | ||
| BV | 5285 | MODES_m_lowscb | Low Suction Circuit B | Read | ||
| BV | 5292 | MODES_m_night | Night Low Noise Active | Read | ||
| BV | 5283 | MODES_m_pmpper | Pump Periodic Start | Read | ||
| BV | 5282 | MODES_m_pmprot | Water Pump Rotation | Read | ||
| BV | 5278 | MODES_m_reset | Reset In Effect | Read | ||
| BV | 5280 | MODES_m_rpload | Ramp Loading Active | Read | ||
| BV | 5294 | MODES_m_secondary | Primary Secondary Active | Read | ||
| BV | 5281 | MODES_m_whtr | Water Exchanger Heater | Read | ||
| BV | 5217 | MSC_SERV_eco_pmp | Eco Pump Enable | Read | ||
| AV | 5218 | MSC_SERV_ecop_off | Pump Off Time | Read | ||
| AV | 5219 | MSC_SERV_ecop_on | Pump On Time | Read | ||
| BV | 5220 | MSC_STAT_m_ecopmp | Eco Pump Mode Active | Read | ||
| BV | 5188 | MST_SLV_islegacy | Legacy compatibility? | Read | ||
| BV | 5187 | MST_SLV_isLwtToo | Is Lwt is too low or too high? | Read | ||
| AV | 5182 | MST_SLV_lag_mini | Lag Minimum Running Time | Read | ||
| BV | 5183 | MST_SLV_lag_pump | Lag Unit Pump Control | Read | ||
| AV | 5180 | MST_SLV_lead_pul | Lead Pulldown Time | Read | ||
| AV | 5177 | MST_SLV_lead_sel | Lead Lag Select | Read | ||
| AV | 5178 | MST_SLV_ll_bal_d | Lead/Lag Balance Delta | Read | ||
| BV | 5184 | MST_SLV_ll_serie | Chiller In Series | Read | ||
| AV | 5179 | MST_SLV_lstr_tim | Lead/Lag Start Timer | Read | ||
| AV | 5175 | MST_SLV_ms_ctrl | Primary Control Type | Read | ||
| AV | 5174 | MST_SLV_ms_sel | Primary/Secondary Select | Read | ||
| BV | 5185 | MST_SLV_mstEnbl | primary enable | Read | ||
| AV | 5176 | MST_SLV_slv_addr | Secondary Address | Read | ||
| BV | 5186 | MST_SLV_slvEnbl | secondary enable | Read | ||
| AV | 5181 | MST_SLV_start_dt | Start If Error Higher | Read | ||
| AV | 5222 | OPT_SEL_boil_en | Boiler Enable | Read | ||
| AV | 5223 | OPT_SEL_dcfc_en | DC Free Cooling Enable | Read | ||
| AV | 5221 | OPT_SEL_ehs_en | Electrical Heat Stages | Read | ||
| BV | 5342 | OPT_STA_demo_sta | Demo Mode Status | Read | ||
| BV | 5343 | OPT_STA_opt149 | OPT149: BACnet | Read | ||
| BV | 5348 | OPT_STA_opt149B | OPT149B: Modbus | Read | ||
| BV | 5347 | OPT_STA_opt295 | OPT295: Fast Cap Reco | Read | ||
| BV | 5344 | OPT_STA_opt5 | OPT5: Medium Brine | Read | ||
| BV | 5345 | OPT_STA_opt6 | OPT6: Low Brine | Read | ||
| BV | 5346 | OPT_STA_opt8 | OPT8: Light Brine | Read | ||
| BV | 5253 | OUTPUTS_ALARM | Alarm Relay Status | Read | ||
| BV | 5254 | OUTPUTS_ALERT | Alert Relay State | Read | ||
| BV | 5259 | OUTPUTS_BOILER | Boiler Output | Read | ||
| AV | 5258 | OUTPUTS_CAPT_010 | Chiller Capacity Running | Read | ||
| BV | 5251 | OUTPUTS_CO_HTR_A | Coil Heater A | Read | ||
| BV | 5252 | OUTPUTS_CO_HTR_B | Coil Heater B | Read | ||
| BV | 1032 | OUTPUTS_CP_A1 | Compressor A1 | Read | ||
| BV | 1033 | OUTPUTS_CP_A2 | Compressor A2 | Read | ||
| BV | 1034 | OUTPUTS_CP_A3 | Compressor A3 | Read | ||
| BV | 1035 | OUTPUTS_CP_A4 | Compressor A4 | Read | ||
| BV | 2032 | OUTPUTS_CP_B1 | Compressor B1 | Read | ||
| BV | 2033 | OUTPUTS_CP_B2 | Compressor B2 | Read | ||
| BV | 2034 | OUTPUTS_CP_B3 | Compressor B3 | Read | ||
| BV | 2035 | OUTPUTS_CP_B4 | Compressor B4 | Read | ||
| BV | 5260 | OUTPUTS_EHS1 | Electrical Heat Stage 1 | Read | ||
| BV | 5261 | OUTPUTS_EHS2 | Electrical Heat Stage 2 | Read | ||
| BV | 5262 | OUTPUTS_EHS3 | Electrical Heat Stage 3 | Read | ||
| BV | 5263 | OUTPUTS_EHS4 | Electrical Heat Stage 4 | Read | ||
| BV | 5256 | OUTPUTS_EXCH_HTR | Exchanger Heater | Read | ||
| AV | 1014 | OUTPUTS_EXV_A | EXV position Circuit A | Read | ||
| AV | 2014 | OUTPUTS_EXV_B | EXV position Circuit B | Read | ||
| AV | 5247 | OUTPUTS_FAN_ST_A | Fan Staging Number Cir A | Read | ||
| AV | 5248 | OUTPUTS_FAN_ST_B | Fan Staging Number Cir B | Read | ||
| BV | 57 | OUTPUTS_HD_HTR_A | Compressor Head Heater A | Read | ||
| AV | 75 | OUTPUTS_HD_HTR_B | Compressor Head Heater B | Read | ||
| BV | 15 | OUTPUTS_RUNNING | Running Relay Status | Read | ||
| BV | 5249 | OUTPUTS_RV_A | 4-way Refrig. Valve A | Read | ||
| BV | 5250 | OUTPUTS_RV_B | 4-way Refrig. Valve B | Read | ||
| BV | 5257 | OUTPUTS_SETFLOW | Flow Switch Setpoint cfg | Read | ||
| BV | 5255 | OUTPUTS_SHUTDOWN | Shutdown Indicator State | Read | ||
| AV | 1015 | OUTPUTS_VFAN_A | Variable fan A command | Read | ||
| AV | 2015 | OUTPUTS_VFAN_B | Variable fan B command | Read | ||
| AV | 1000 | PRESSURE_DP_A | Discharge Pressure A | Read | ||
| AV | 2000 | PRESSURE_DP_B | Discharge Pressure B | Read | ||
| AV | 37 | PRESSURE_PUMP_EWP | Inlet unit water pres. | Read | ||
| AV | 38 | PRESSURE_PUMP_LWP | Outlet unit water pres. | Read | ||
| AV | 1001 | PRESSURE_SP_A | Main Suction Pressure A | Read | ||
| AV | 2001 | PRESSURE_SP_B | Main Suction Pressure B | Read | ||
| BV | 10079 | PROTOCOL_FC_DSBLE_wr | Free Cooling Disable? | Write | ||
| AV | 5106 | PUMPCONF_dp_stp | Flow Delta P Setpoint | Read | ||
| AV | 5105 | PUMPCONF_dt_stp | Flow Delta T Setpoint | Read | ||
| AV | 5104 | PUMPCONF_flow_ctl | Flow Control Method | Read | ||
| AV | 5117 | PUMPCONF_MinWpThr | Min Water Press Thres | Read | ||
| AV | 5013 | PUMPCONF_pump_del | Pump Auto Rotation Delay | Read | ||
| BV | 5016 | PUMPCONF_pump_loc | Flow Checked If Pump Off | Read | ||
| AV | 5110 | PUMPCONF_pump_max | Pump Maximum Speed | Read | ||
| AV | 5108 | PUMPCONF_pump_min | Pump Minimum Speed | Read | ||
| BV | 5014 | PUMPCONF_pump_per | Pump Sticking Protection | Read | ||
| AV | 5109 | PUMPCONF_pump_sav | Pump Min Speed Cap=0% | Read | ||
| BV | 5015 | PUMPCONF_pump_sby | Stop Pump During Standby | Read | ||
| AV | 73 | PUMPCONF_pump_seq | Pumps Sequence | Read | ||
| AV | 5107 | PUMPCONF_wtr_zval | Pressure Zero Value | Read | ||
| AV | 5273 | PUMPSTAT_delta_p | Current Water Delta P | Read | ||
| AV | 5271 | PUMPSTAT_delta_t | Current Water Delta T | Read | ||
| AV | 5272 | PUMPSTAT_dp_stp | Water Delta P Setpoint | Read | ||
| AV | 5270 | PUMPSTAT_dt_stp | Water Delta T Setpoint | Read | ||
| AV | 71 | PUMPSTAT_flowa | Water Flow | Read | ||
| AV | 72 | PUMPSTAT_flowa | Pump Control Method | Read | ||
| BV | 50 | PUMPSTAT_PUMP_1_rd | Water Pump #1 Command | Read | ||
| BV | 10050 | PUMPSTAT_PUMP_1_wr | Water Pump #1 Command | Write | ||
| BV | 51 | PUMPSTAT_PUMP_2_rd | Water Pump #2 Command | Read | ||
| BV | 10051 | PUMPSTAT_PUMP_2_wr | Water Pump #2 Command | Write | ||
| BV | 5264 | PUMPSTAT_ROTWPUMP | Rotate Water Pumps Now? | Read | ||
| AV | 70 | PUMPSTAT_VPMP_CMDb | Variable speed pump cmd | Read | ||
| BV | 5266 | PUMPSTAT_WP_CAL | Water Pres. Calibration? | Read | ||
| AV | 5268 | PUMPSTAT_wp_filt | Delta Pressure Filter | Read | ||
| AV | 5265 | PUMPSTAT_wp_in | Inlet Water Pres.(cor) | Read | ||
| AV | 5269 | PUMPSTAT_wp_min | Minimum Water Pressure | Read | ||
| AV | 5267 | PUMPSTAT_wp_off | Water Pressure Offset | Read | ||
| AV | 5264 | PUMPSTAT_wp_out | Outlet Water Pres.(cor) | Read | ||
| BV | 5681 | RECLAIM_actiMode | HR active mode (3WV/Fan) | Read | ||
| AV | 5678 | RECLAIM_cmd_3WV | 3WayValve / VarPump cmd | Read | ||
| BV | 5670 | RECLAIM_HR_FLOW | Heat Reclaim Flow switch | Read | ||
| AV | 5672 | RECLAIM_HR_LWT | HR Leaving Fluid temp | Read | ||
| BV | 5682 | RECLAIM_HR_pump | Reclaim pump command | Read | ||
| BV | 5668 | RECLAIM_HR_stat | Reclaim Status | Read | ||
| AV | 5669 | RECLAIM_HRCtrPnt | Reclaim control point | Read | ||
| AV | 5671 | RECLAIM_HRCtrWat | Reclaim controlled water | Read | ||
| BV | 5674 | RECLAIM_HRheater | Reclaim BPHE Heater | Read | ||
| AV | 5680 | RECLAIM_mode_3WV | 3WayValve / VarPump mode | Read | ||
| AV | 5679 | RECLAIM_out_3WV | 3WayValve / VarPump outp | Read | ||
| BV | 5667 | RECLAIM_RECL_SEL_rd | Reclaim Selection | Read | ||
| BV | 15667 | RECLAIM_RECL_SEL_wr | Reclaim Select | Write | ||
| AV | 5029 | RESETCFG_cr_deg | Cooling Reset Deg. Value | Read | ||
| AV | 5019 | RESETCFG_cr_sel | Cooling Reset Select | Read | ||
| AV | 5024 | RESETCFG_dt_cr_fu | Delta T Full Reset Value | Read | ||
| AV | 5023 | RESETCFG_dt_cr_no | Delta T No Reset Value | Read | ||
| AV | 5033 | RESETCFG_dt_hr_fu | Delta T Full Reset Value | Read | ||
| AV | 5032 | RESETCFG_dt_hr_no | Delta T No Reset Value | Read | ||
| AV | 5038 | RESETCFG_hr_deg | Heating Reset Deg. Value | Read | ||
| AV | 5020 | RESETCFG_hr_sel | Heating Reset Select | Read | ||
| AV | 5026 | RESETCFG_I_cr_fu | Current Full Reset Value | Read | ||
| AV | 5025 | RESETCFG_I_cr_no | Current No Reset Value | Read | ||
| AV | 5035 | RESETCFG_I_hr_fu | Current Full Reset Value | Read | ||
| AV | 5034 | RESETCFG_I_hr_no | Current No Reset Value | Read | ||
| AV | 5022 | RESETCFG_oat_crfu | OAT Full Reset Value | Read | ||
| AV | 5021 | RESETCFG_oat_crno | OAT No Reset Value | Read | ||
| AV | 5031 | RESETCFG_oat_hrfu | OAT Full Reset Value | Read | ||
| AV | 5030 | RESETCFG_oat_hrno | OAT No Reset Value | Read | ||
| AV | 5028 | RESETCFG_spacr_fu | Space T Full Reset Value | Read | ||
| AV | 5027 | RESETCFG_spacr_no | Space T No Reset Value | Read | ||
| AV | 5037 | RESETCFG_spahr_fu | Space T Full Reset Value | Read | ||
| AV | 5036 | RESETCFG_spahr_no | Space T No Reset Value | Read | ||
| AV | 1960 | RUNTIME_hr_cp_a1 | Compressor A1 Hours | Read | ||
| AV | 1961 | RUNTIME_hr_cp_a2 | Compressor A2 Hours | Read | ||
| AV | 1962 | RUNTIME_hr_cp_a3 | Compressor A3 Hours | Read | ||
| AV | 1963 | RUNTIME_hr_cp_a4 | Compressor A4 Hours | Read | ||
| AV | 2960 | RUNTIME_hr_cp_b1 | Compressor B1 Hours | Read | ||
| AV | 2961 | RUNTIME_hr_cp_b2 | Compressor B2 Hours | Read | ||
| AV | 2962 | RUNTIME_hr_cp_b3 | Compressor B3 Hours | Read | ||
| AV | 2963 | RUNTIME_hr_cp_b4 | Compressor B4 Hours | Read | ||
| AV | 1969 | RUNTIME_hr_fana1 | Fan A1 Hours | Read | ||
| AV | 1970 | RUNTIME_hr_fana2 | Fan A2 Hours | Read | ||
| AV | 1971 | RUNTIME_hr_fana3 | Fan A3 Hours | Read | ||
| AV | 1972 | RUNTIME_hr_fana4 | Fan A4 Hours | Read | ||
| AV | 1973 | RUNTIME_hr_fana5 | Fan A5 Hours | Read | ||
| AV | 1974 | RUNTIME_hr_fana6 | Fan A6 Hours | Read | ||
| AV | 1975 | RUNTIME_hr_fana7 | Fan A7 Hours | Read | ||
| AV | 1976 | RUNTIME_hr_fana8 | Fan A8 Hours | Read | ||
| AV | 2969 | RUNTIME_hr_fanb1 | Fan B1 Hours | Read | ||
| AV | 2970 | RUNTIME_hr_fanb2 | Fan B2 Hours | Read | ||
| AV | 2971 | RUNTIME_hr_fanb3 | Fan B3 Hours | Read | ||
| AV | 2972 | RUNTIME_hr_fanb4 | Fan B4 Hours | Read | ||
| AV | 2973 | RUNTIME_hr_fanb5 | Fan B5 Hours | Read | ||
| AV | 2974 | RUNTIME_hr_fanb6 | Fan B6 Hours | Read | ||
| AV | 2975 | RUNTIME_hr_fanb7 | Fan B7 Hours | Read | ||
| AV | 2976 | RUNTIME_hr_fanb8 | Fan B8 Hours | Read | ||
| AV | 960 | RUNTIME_hr_mach | Machine Operating Hours | Read | ||
| AV | 962 | RUNTIME_hr_pump1 | Water Pump #1 Hours | Read | ||
| AV | 963 | RUNTIME_hr_pump2 | Water Pump #2 Hours | Read | ||
| AV | 5274 | RUNTIME_nb_defra | Circuit A Defrost Number | Read | ||
| AV | 5275 | RUNTIME_nb_defrb | Circuit B Defrost Number | Read | ||
| AV | 1964 | RUNTIME_st_cp_a1 | Compressor A1 Starts | Read | ||
| AV | 1965 | RUNTIME_st_cp_a2 | Compressor A2 Starts | Read | ||
| AV | 1966 | RUNTIME_st_cp_a3 | Compressor A3 Starts | Read | ||
| AV | 1967 | RUNTIME_st_cp_a4 | Compressor A4 Starts | Read | ||
| AV | 2964 | RUNTIME_st_cp_b1 | Compressor B1 Starts | Read | ||
| AV | 2965 | RUNTIME_st_cp_b2 | Compressor B2 Starts | Read | ||
| AV | 2966 | RUNTIME_st_cp_b3 | Compressor B3 Starts | Read | ||
| AV | 2967 | RUNTIME_st_cp_b4 | Compressor B4 Starts | Read | ||
| AV | 961 | RUNTIME_st_mach | Machine Starts Number | Read | ||
| BV | 5098 | SERVICE1_auto_sm | Auto Start when SM lost | Read | ||
| BV | 5111 | SERVICE1_b_metric | Blackbox In Metric? | Read | ||
| AV | 5102 | SERVICE1_flow_sp | Flow Setpoint | Read | ||
| AV | 5113 | SERVICE1_FrDfrPer | Free Defr Allowed Period | Read | ||
| AV | 5096 | SERVICE1_freezesp | Brine Freeze Setpoint | Read | ||
| AV | 5100 | SERVICE1_hc_zm | Maximum Z Multiplier | Read | ||
| AV | 5095 | SERVICE1_heatersp | Exch. Heater Delta Spt | Read | ||
| AV | 5094 | SERVICE1_hp_th | High Pressure Threshold | Read | ||
| AV | 5115 | SERVICE1_Leak_thr | Leakage Charge Threshold | Read | ||
| AV | 5116 | SERVICE1_Leak_tmr | Leakage Charge Timer | Read | ||
| AV | 5097 | SERVICE1_mini_lwt | Minimum LWT Setpoint | Read | ||
| AV | 5114 | SERVICE1_OatFrDfr | Oat Min for Free Defrost | Read | ||
| BV | 5103 | SERVICE1_pump_cyc | Pump Cycl. Freeze Prot. | Read | ||
| AV | 5101 | SERVICE1_ser_pass | Service Password | Read | ||
| AV | 5112 | SERVICE1_unit_alt | Unit Altitude (in meter) | Read | ||
| AV | 5099 | SERVICE1_zm_stp | Auto Z Multiplier Stp | Read | ||
| AV | 5199 | SERVICE2_fan_kd | Varifan PID Deriv Gain | Read | ||
| AV | 5198 | SERVICE2_fan_ki | Varifan PID Integ Gain | Read | ||
| AV | 5197 | SERVICE2_fan_kp | Varifan PID Prop Gain | Read | ||
| AV | 5200 | SERVICE2_fan_max | Maximum Fan Speed | Read | ||
| AV | 5204 | SERVICE2_mop_sp | EXV MOP Setpoint | Read | ||
| AV | 5205 | SERVICE2_sh_sp_a | EXV A Superheat Setpoint | Read | ||
| AV | 5206 | SERVICE2_sh_sp_b | EXV B Superheat Setpoint | Read | ||
| AV | 5203 | SERVICE2_vfheatkd | Varifan Heat. Deriv Gain | Read | ||
| AV | 5202 | SERVICE2_vfheatki | Varifan Heat. Integ Gain | Read | ||
| AV | 5201 | SERVICE2_vfheatkp | Varifan Heat. Prop Gain | Read | ||
| AV | 900 | SETPOINT_csp1 | Cooling Setpoint 1 | Write | ||
| AV | 901 | SETPOINT_csp2 | Cooling Setpoint 2 | Write | ||
| AV | 5709 | SETPOINT_hr_stp | Heat Reclaim Setpoint | Write | ||
| AV | 903 | SETPOINT_hsp1 | Heating Setpoint 1 | Write | ||
| AV | 904 | SETPOINT_hsp2 | Heating Setpoint 2 | Write | ||
| AV | 902 | SETPOINT_ice_sp | Cooling Ice Setpoint | Write | ||
| AV | 905 | SETPOINT_lim_sp1 | Switch Limit Setpoint 1 | Write | ||
| AV | 906 | SETPOINT_lim_sp2 | Switch Limit Setpoint 2 | Write | ||
| AV | 907 | SETPOINT_lim_sp3 | Switch Limit Setpoint 3 | Write | ||
| AV | 5 | TEMP_CHWSTEMP | Cold Water System Temp | Read | ||
| AV | 1009 | TEMP_DGT_A | Discharge Gas Temp A | Read | ||
| AV | 2009 | TEMP_DGT_B | Discharge Gas Temp B | Read | ||
| AVmin | 1 | TEMP_EWT | Entering Fluid Temp | Read | ||
| AV | 84 | TEMP_FC_EV_WT | FC Evap Water Temp | Read | ||
| AVmin | 2 | TEMP_LWT | Leaving Fluid Temp | Read | ||
| AV | 3 | TEMP_OAT | Outdoor Air Temp | Read | ||
| AV | 1005 | TEMP_SCT_A | Saturated Cond Tmp cir A | Read | ||
| AV | 2005 | TEMP_SCT_B | Saturated Cond Tmp cir B | Read | ||
| AV | 1011 | TEMP_SH_A | Suction Superheat Tmp A | Read | ||
| AV | 2011 | TEMP_SH_B | Suction Superheat Tmp B | Read | ||
| AV | 1006 | TEMP_SST_A | Saturated Suction Temp A | Read | ||
| AV | 2006 | TEMP_SST_B | Saturated Suction Temp B | Read | ||
| AV | 1007 | TEMP_SUCT_A | Compressor Suction Tmp A | Read | ||
| AV | 2007 | TEMP_SUCT_B | Compressor Suction Tmp B | Read | ||
| AV | 77 | UNIT_HEATCOOL | Run Status | Read | ||
| AV | 5161 | UPDTHOUR_FC_FAN1H | FC Fan Stage 1 Hours | Read | ||
| AV | 5160 | UPDTHOUR_FC_FAN1S | FC Fan Stage 1 Start | Read | ||
| AV | 5163 | UPDTHOUR_FC_FAN2H | FC Fan Stage 2 Hours | Read | ||
| AV | 5162 | UPDTHOUR_FC_FAN2S | FC Fan Stage 2 Start | Read | ||
| AV | 5165 | UPDTHOUR_FC_FAN3H | FC Fan Stage 3 Hours | Read | ||
| AV | 5164 | UPDTHOUR_FC_FAN3S | FC Fan Stage 3 Start | Read | ||
| AV | 5167 | UPDTHOUR_FC_FAN4H | FC Fan Stage 4 Hours | Read | ||
| AV | 5166 | UPDTHOUR_FC_FAN4S | FC Fan Stage 4 Start | Read | ||
| AV | 5169 | UPDTHOUR_FC_FAN5H | FC Fan Stage 5 Hours | Read | ||
| AV | 5168 | UPDTHOUR_FC_FAN5S | FC Fan Stage 5 Start | Read | ||
| AV | 5171 | UPDTHOUR_FC_FAN6H | FC Fan Stage 6 Hours | Read | ||
| AV | 5170 | UPDTHOUR_FC_FAN6S | FC Fan Stage 6 Start | Read | ||
| AV | 5173 | UPDTHOUR_FC_FAN7H | FC Fan Stage 7 Hours | Read | ||
| AV | 5172 | UPDTHOUR_FC_FAN7S | FC Fan Stage 7 Start | Read | ||
| AV | 5159 | UPDTHOUR_FC_HOUR | FC Operating Hours | Read | ||
| AV | 5120 | UPDTHOUR_hr_cp_a1 | Compressor A1 Hours | Read | ||
| AV | 5121 | UPDTHOUR_hr_cp_a2 | Compressor A2 Hours | Read | ||
| AV | 5122 | UPDTHOUR_hr_cp_a3 | Compressor A3 Hours | Read | ||
| AV | 5123 | UPDTHOUR_hr_cp_a4 | Compressor A4 Hours | Read | ||
| AV | 5124 | UPDTHOUR_hr_cp_b1 | Compressor B1 Hours | Read | ||
| AV | 5125 | UPDTHOUR_hr_cp_b2 | Compressor B2 Hours | Read | ||
| AV | 5126 | UPDTHOUR_hr_cp_b3 | Compressor B3 Hours | Read | ||
| AV | 5127 | UPDTHOUR_hr_cp_b4 | Compressor B4 Hours | Read | ||
| AV | 5136 | UPDTHOUR_hr_fana1 | Fan A1 Hours | Read | ||
| AV | 5137 | UPDTHOUR_hr_fana2 | Fan A2 Hours | Read | ||
| AV | 5138 | UPDTHOUR_hr_fana3 | Fan A3 Hours | Read | ||
| AV | 5139 | UPDTHOUR_hr_fana4 | Fan A4 Hours | Read | ||
| AV | 5140 | UPDTHOUR_hr_fana5 | Fan A5 Hours | Read | ||
| AV | 5141 | UPDTHOUR_hr_fana6 | Fan A6 Hours | Read | ||
| AV | 5142 | UPDTHOUR_hr_fana7 | Fan A7 Hours | Read | ||
| AV | 5143 | UPDTHOUR_hr_fana8 | Fan A8 Hours | Read | ||
| AV | 5144 | UPDTHOUR_hr_fanb1 | Fan B1 Hours | Read | ||
| AV | 5145 | UPDTHOUR_hr_fanb2 | Fan B2 Hours | Read | ||
| AV | 5146 | UPDTHOUR_hr_fanb3 | Fan B3 Hours | Read | ||
| AV | 5147 | UPDTHOUR_hr_fanb4 | Fan B4 Hours | Read | ||
| AV | 5148 | UPDTHOUR_hr_fanb5 | Fan B5 Hours | Read | ||
| AV | 5149 | UPDTHOUR_hr_fanb6 | Fan B6 Hours | Read | ||
| AV | 5150 | UPDTHOUR_hr_fanb7 | Fan B7 Hours | Read | ||
| AV | 5151 | UPDTHOUR_hr_fanb8 | Fan B8 Hours | Read | ||
| AV | 5118 | UPDTHOUR_hr_mach | Machine Operating Hours | Read | ||
| AV | 5152 | UPDTHOUR_hr_pump1 | Water Pump #1 Hours | Read | ||
| AV | 5153 | UPDTHOUR_hr_pump2 | Water Pump #2 Hours | Read | ||
| AV | 5157 | UPDTHOUR_nb_defra | Circuit A Defrost Number | Read | ||
| AV | 5158 | UPDTHOUR_nb_defrb | Circuit B Defrost Number | Read | ||
| AV | 5128 | UPDTHOUR_st_cp_a1 | Compressor A1 Starts | Read | ||
| AV | 5129 | UPDTHOUR_st_cp_a2 | Compressor A2 Starts | Read | ||
| AV | 5130 | UPDTHOUR_st_cp_a3 | Compressor A3 Starts | Read | ||
| AV | 5131 | UPDTHOUR_st_cp_a4 | Compressor A4 Starts | Read | ||
| AV | 5132 | UPDTHOUR_st_cp_b1 | Compressor B1 Starts | Read | ||
| AV | 5133 | UPDTHOUR_st_cp_b2 | Compressor B2 Starts | Read | ||
| AV | 5134 | UPDTHOUR_st_cp_b3 | Compressor B3 Starts | Read | ||
| AV | 5135 | UPDTHOUR_st_cp_b4 | Compressor B4 Starts | Read | ||
| AV | 5119 | UPDTHOUR_st_mach | Machine Starts Number | Read | ||
| AV | 5018 | USERCONF_language | Language Selection | Read | ||
| AV | 5017 | USERCONF_use_pass | User Password | Read |
No points match these filters.
Object ID lookup: Carrier AquaSnap 30RC 065-252 point IDs by name
AV985ALARMRST_alarm_1AV980ALARMRST_alarm_1cAV986ALARMRST_alarm_2AV981ALARMRST_alarm_2cAV987ALARMRST_alarm_3AV982ALARMRST_alarm_3cAV988ALARMRST_alarm_4AV983ALARMRST_alarm_4cAV989ALARMRST_alarm_5AV984ALARMRST_alarm_5cAV990ALARMRST_ALMBV104502ALM_AUX1_1_COM_FBV104501ALM_AUX2_FS_FAN_1_COM_FBV104503ALM_AUX2_FS_FAN_2_COM_FBV115011ALM_CHWSTEMP_FBV101199ALM_CPA1_FBV110016ALM_CPA1_REVERSE_ROT_FBV101299ALM_CPA2_FBV110017ALM_CPA2_REVERSE_ROT_FBV101399ALM_CPA3_FBV110018ALM_CPA3_REVERSE_ROT_FBV101499ALM_CPA4_FBV110019ALM_CPA4_REVERSE_ROT_FBV102199ALM_CPB1_FBV110020ALM_CPB1_REVERSE_ROT_FBV102299ALM_CPB2_FBV110021ALM_CPB2_REVERSE_ROT_FBV102399ALM_CPB3_FBV110022ALM_CPB3_REVERSE_ROT_FBV102499ALM_CPB4_FBV110023ALM_CPB4_REVERSE_ROT_FBV155001ALM_DATABASE_FBV115003ALM_DEFROST_T_A_FBV115004ALM_DEFROST_T_B_FBV112001ALM_DP_A_FBV112002ALM_DP_B_FBV110028ALM_ELEC_BOX_FBV115001ALM_EWT_FBV110051ALM_EXCH_FLOW_FBV110001ALM_EXCH_FREEZE_FBV157020ALM_EXV_A_FBV157021ALM_EXV_B_FBV104701ALM_FAN_DRIVE_A_COM_FBV104702ALM_FAN_DRIVE_A2_COM_FBV104703ALM_FAN_DRIVE_B_COM_FBV104704ALM_FAN_DRIVE_B2_COM_FBV104601ALM_FC_AUX1_COM_FAV110220ALM_FC_COIL_VALVE_FAV110222ALM_FC_EVAP_VALVE_FAV115058ALM_FC_EVAP_WT_FBV115047ALM_FC_LWT_FBV115048ALM_FC_OAT_FBV110101ALM_FC_PROCESS_FBV115046ALM_FC_WLOOP_FBV113005ALM_FGAS_NEEDEDBV110090ALM_FLOW_CONFIG_FBV110050ALM_FLUIDE_FAILBV110043ALM_HEAT_LOW_EWT_FBV110008ALM_HIGH_SH_A_FBV110009ALM_HIGH_SH_B_FBV110063ALM_HP_SWITCH_A_FBV110064ALM_HP_SWITCH_B_FBV10128ALM_HR_COND_FREEZE_FBV15008ALM_HR_EWT_FBV10052ALM_HR_FLOW_SW_FBV10129ALM_HR_HIGH_LWT_FBV15009ALM_HR_LWT_FBV108001ALM_ILL_BRANDBV107001ALM_ILL_FACT_CONF_FBV108000ALM_INI_FACT_CONF_FBV110014ALM_INTER_LOCK_FBV156001ALM_LENSCAN_FBV110030ALM_LOSS_COM_MS_FBV110029ALM_LOSS_COM_SM_FBV110210ALM_LOW_DELTP_A_FBV110211ALM_LOW_DELTP_B_FBV110011ALM_LOW_SH_A_FBV110012ALM_LOW_SH_B_FBV110005ALM_LOW_SUCTION_A_FBV110006ALM_LOW_SUCTION_B_FBV115002ALM_LWT_FBV109001ALM_M_S_CONFIG_FBV110031ALM_NETWORK_EMSTOP_FBV115010ALM_OAT_FBV104705ALM_PUMP_DRIVE_1_COM_FBV104706ALM_PUMP_DRIVE_2_COM_FBV110037ALM_REPEAT_HIGH_DGT_A_FBV110038ALM_REPEAT_HIGH_DGT_B_FBV110040ALM_REPEAT_LOW_SST_A_FBV110041ALM_REPEAT_LOW_SST_B_FBV110097ALM_SENSORS_SWAP_FBV113000ALM_SERV_MAINT_ALERTBV104901ALM_SIOB_A_COM_FBV104902ALM_SIOB_B_COM_FBV104906ALM_SIOB_EMM_COM_FBV157001ALM_SIOB_LOWVOLT_CIRA_FBV157002ALM_SIOB_LOWVOLT_CIRB_FBV157006ALM_SIOB_LOWVOLT_EMM_FBV112004ALM_SP_A_FBV112005ALM_SP_B_FBV115021ALM_SPACE_TEMP_FBV115012ALM_SUCTION_T_A_FBV115013ALM_SUCTION_T_B_FBV135001ALM_VFAN_DRV_A1_ALERTBV117001ALM_VFAN_DRV_A1_FBV136001ALM_VFAN_DRV_A2_ALERTBV118002ALM_VFAN_DRV_A2_FBV137001ALM_VFAN_DRV_B1_ALERTBV119001ALM_VFAN_DRV_B1_FBV138001ALM_VFAN_DRV_B2_ALERTBV120001ALM_VFAN_DRV_B2_FBV139001ALM_VPUMP_DRV_1_ALERTBV121001ALM_VPUMP_DRV_1_FBV140001ALM_VPUMP_DRV_2_ALERTBV122001ALM_VPUMP_DRV_2_FBV106001ALM_WELDED_CONTACT_A_FBV106002ALM_WELDED_CONTACT_B_FBV111209ALM_WL_LO_PRESS_WARNBV111207ALM_WL_LOW_FLOWBV111208ALM_WL_PRESS_CROSSBV111205ALM_WL_PRESS_ERR_IN_RUNBV111203ALM_WL_PRESS_TOO_LOWBV111202ALM_WL_PRESS_ZERO_ERRORBV111204ALM_WL_PUMP_NOT_STARTEDBV111206ALM_WL_PUMP_OVERLOADBV112024ALM_WP_IN_FBV112025ALM_WP_OUT_FBV110032ALM_WPUMP1_FBV110033ALM_WPUMP2_FAV5039BACKUP_boil_thBV5042BACKUP_ehs_backBV5043BACKUP_ehs_defrAV5046BACKUP_ehs_kdAV5045BACKUP_ehs_kiAV5044BACKUP_ehs_kpAV5041BACKUP_ehs_pullAV5040BACKUP_ehs_thBV5439BACnet_auid_optAV5438BACnet_bac_id_manBV60BACnet_bacenaBV61BACnet_bacunitBV5440BACnet_balmenaAV66BACnet_BMS_OCCMV64BACnet_COLORAV5442BACnet_conIFnamAV63BACnet_identBV5441BACnet_mng_occAV62BACnet_networkAV5437BACnet_portAV65BACnet_PRIME_VBV5189CP_UNABL_un_cp_a1BV5190CP_UNABL_un_cp_a2BV5191CP_UNABL_un_cp_a3BV5192CP_UNABL_un_cp_a4BV5193CP_UNABL_un_cp_b1BV5194CP_UNABL_un_cp_b2BV5195CP_UNABL_un_cp_b3BV5196CP_UNABL_un_cp_b4AV5227DCFC_CFG_chil_delAV5228DCFC_CFG_dbandAV5231DCFC_CFG_dgAV5238DCFC_CFG_dt_setpAV5230DCFC_CFG_igAV5235DCFC_CFG_nb_fanAV5234DCFC_CFG_nb_lineAV5224DCFC_CFG_oat_sAV5233DCFC_CFG_off_tmrAV5232DCFC_CFG_on_tmrAV5229DCFC_CFG_pgAV5225DCFC_CFG_start_thAV5226DCFC_CFG_stop_thAV5237DCFC_CFG_vf_deltaBV5236DCFC_CFG_vfanAV5751DCFC_CFG_vfan_maxAV5321DCFC_STA_dcfc_capAV5322DCFC_STA_f_stageAV5327DCFC_STA_FC_FAN1HAV5326DCFC_STA_FC_FAN1SAV5329DCFC_STA_FC_FAN2HAV5328DCFC_STA_FC_FAN2SAV5331DCFC_STA_FC_FAN3HAV5330DCFC_STA_FC_FAN3SAV5333DCFC_STA_FC_FAN4HAV5332DCFC_STA_FC_FAN4SAV5335DCFC_STA_FC_FAN5HAV5334DCFC_STA_FC_FAN5SAV5337DCFC_STA_FC_FAN6HAV5336DCFC_STA_FC_FAN6SAV5339DCFC_STA_FC_FAN7HAV5338DCFC_STA_FC_FAN7SAV5325DCFC_STA_FC_HOURAV5341DCFC_STA_FC_VFANHAV5340DCFC_STA_FC_VFANSAV5318DCFC_STA_lwtBV5320DCFC_STA_m_dcfcAV5317DCFC_STA_oatAV5324DCFC_STA_pid_outAV5323DCFC_STA_vf_speedAV5319DCFC_STA_wloopBV5408DEFROST_def_ac_aBV5423DEFROST_def_ac_bAV5419DEFROST_def_ca_aAV5434DEFROST_def_ca_bAV5420DEFROST_def_of_aAV5435DEFROST_def_of_bAV5406DEFROST_def_se_aAV5421DEFROST_def_se_bAV5411DEFROST_defr_duaAV5426DEFROST_defr_dubAV5410DEFROST_DEFRT_AAV5425DEFROST_DEFRT_BAV5415DEFROST_delt_aAV5430DEFROST_delt_bAV5416DEFROST_delt_r_aAV5431DEFROST_delt_r_bAV5417DEFROST_delt_v_aAV5432DEFROST_delt_v_bAV5418DEFROST_fr_int_aAV5433DEFROST_fr_int_bAV5436DEFROST_FrDfrTmrAV5407DEFROST_frost_aAV5422DEFROST_frost_bAV5409DEFROST_over_d_aAV5424DEFROST_over_d_bAV5413DEFROST_sct_dm_aAV5428DEFROST_sct_dm_bAV5412DEFROST_sctlim_aAV5427DEFROST_sctlim_bAV5414DEFROST_sst_dm_aAV5429DEFROST_sst_dm_bAV1024DRV_CTL2_drv_F_5AV2024DRV_CTL2_drv_F_6AV1021DRV_CTL2_drv_I_5AV2021DRV_CTL2_drv_I_6AV1023DRV_CTL2_drv_T_5AV2023DRV_CTL2_drv_T_6AV1022DRV_CTL2_drv_V_5AV2022DRV_CTL2_drv_V_6AV1025DRV_CTL2_drvpwr_1AV1026DRV_CTL2_drvpwr_2AV2025DRV_CTL2_drvpwr_3AV2026DRV_CTL2_drvpwr_4AV1020DRV_CTL2_drvpwr_5AV2020DRV_CTL2_drvpwr_6AV5306ENERGY_cEnergInAV5305ENERGY_cEnergOuAV5310ENERGY_copAV5303ENERGY_cPwrInAV5302ENERGY_cPwrOutAV5304ENERGY_eerAV5313ENERGY_energCopAV5307ENERGY_energEerAV5312ENERGY_hEnergInAV5311ENERGY_hEnergOuAV5309ENERGY_hPwrInAV5308ENERGY_hPwrOutBV5314ENERGY_reset_enBV5242EOLRES_j10_eolBV5239EOLRES_j6_eolBV5240EOLRES_j7_eolBV5241EOLRES_j8_eolAV5067FACTORY_countryBV5071FACTORY_dcfc_selBV5056FACTORY_desuperBV5062FACTORY_dual_pmpBV5058FACTORY_emm_optBV5057FACTORY_exch_htrAV5066FACTORY_fac_passAV5055FACTORY_fan_spdAV5054FACTORY_fan_typAV78FACTORY_fc_optAV5069FACTORY_flui_typBV5070FACTORY_leak_chkBV5072FACTORY_opt_119CAV5711FACTORY_opt_41CAV5061FACTORY_pump_typAV5065FACTORY_QM_codeAV5710FACTORY_rclm_optBV5068FACTORY_refrigAV5051FACTORY_unit_typAV5053FACTORY_unitsizeAV5073FACTORY2_cap_a1AV5074FACTORY2_cap_a2AV5075FACTORY2_cap_a3AV5076FACTORY2_cap_a4AV5077FACTORY2_cap_b1AV5078FACTORY2_cap_b2AV5079FACTORY2_cap_b3AV5080FACTORY2_cap_b4AV5089FACTORY2_ClExchTpAV5091FACTORY2_ClPipgTpAV5087FACTORY2_ClPumpTpAV5083FACTORY2_exvmax_aAV5085FACTORY2_exvmax_bAV5084FACTORY2_exvRat_aAV5086FACTORY2_exvRat_bAV5081FACTORY2_nb_fan_aAV5082FACTORY2_nb_fan_bBV5011GENCONF_auto_selBV5010GENCONF_both_selBV5093GENCONF_ewt_optAV5005GENCONF_heat_thBV5009GENCONF_ice_cnfgAV5003GENCONF_lim_selAV5007GENCONF_nh_endAV5008GENCONF_nh_limitAV5006GENCONF_nh_startAV5004GENCONF_off_on_dAV5000GENCONF_prio_cirBV5002GENCONF_ramp_selBV5001GENCONF_seq_typAV9GENUNIT_CAP_TAV1017GENUNIT_CAPA_TAV2017GENUNIT_CAPB_TBV58GENUNIT_CHIL_OCC_rdBV10058GENUNIT_CHIL_OCC_wrBV12GENUNIT_CHIL_S_S_rdBV10012GENUNIT_CHIL_S_S_wrAV6GENUNIT_CTRL_PNT_rdAV10006GENUNIT_CTRL_PNT_wrAV21GENUNIT_CTRL_TYPAV4GENUNIT_CTRL_WTAV8GENUNIT_DEM_LIM_rdAV10008GENUNIT_DEM_LIM_wrBV13GENUNIT_EMSTOP_rdBV10013GENUNIT_EMSTOP_wrAV23GENUNIT_HC_SEL_rdAV10023GENUNIT_HC_SEL_wrAV11GENUNIT_min_leftAV7GENUNIT_SPBV59GENUNIT_SP_OCC_rdBV10059GENUNIT_SP_OCC_wrAV24GENUNIT_SP_SEL_rdAV10024GENUNIT_SP_SEL_wrAV22GENUNIT_STATUSAV5705HR_CFG_flowTmrBV5694HR_CFG_hr_ecoBV5693HR_CFG_hr_fluiBV5696HR_CFG_HRewtctlAV5699HR_CFG_kd_HR3wvAV5702HR_CFG_kd_HRFanAV5698HR_CFG_ki_HR3wvAV5701HR_CFG_ki_HRFanAV5697HR_CFG_kp_HR3wvAV5700HR_CFG_kp_HRFanAV5704HR_CFG_maxHR3wvAV5706HR_CFG_minFloEnAV5707HR_CFG_minFlowAV5703HR_CFG_minHRpmpBV5695HR_CFG_rev_3WVAV966HR_PARTIAL_DOWNTIMEAV967HR_TOTAL_DOWNTIMEAV83HYD_FC_fc_cv_rqBV79HYD_FC_FC_DSBLE_rdAV82HYD_FC_fc_ev_rqAV81HYD_FC_fcCapTAV80HYD_FC_wLoopPstVBV43INPUTS_ELEC_BOXBV52INPUTS_FLOW_SWBV45INPUTS_HC_SWAV5243INPUTS_HP_SW_AAV5244INPUTS_HP_SW_BAV5246INPUTS_LIM_4_20BV18INPUTS_LIM_SW1BV19INPUTS_LIM_SW2BV16INPUTS_ONOFF_SWBV14INPUTS_REM_LOCKBV48INPUTS_SETP_SWAV5245INPUTS_SP_RESETAV5374LAST_POR_date_of1AV5378LAST_POR_date_of2AV5382LAST_POR_date_of3AV5386LAST_POR_date_of4AV5390LAST_POR_date_of5AV5372LAST_POR_date_on1AV5376LAST_POR_date_on2AV5380LAST_POR_date_on3AV5384LAST_POR_date_on4AV5388LAST_POR_date_on5AV5375LAST_POR_time_of1AV5379LAST_POR_time_of2AV5383LAST_POR_time_of3AV5387LAST_POR_time_of4AV5391LAST_POR_time_of5AV5373LAST_POR_time_on1AV5377LAST_POR_time_on2AV5381LAST_POR_time_on3AV5385LAST_POR_time_on4AV5389LAST_POR_time_on5AV5351LOADFACT_cap_limAV5350LOADFACT_cap_tAV5354LOADFACT_cur_stagAV5366LOADFACT_eh_stageAV5368LOADFACT_ehs_statBV5367LOADFACT_ehspulldAV5363LOADFACT_exv_v_aAV5364LOADFACT_exv_v_bAV5370LOADFACT_flowSw_sAV5371LOADFACT_hydKit_sAV5358LOADFACT_minSct_aAV5361LOADFACT_ov_exv_aAV5362LOADFACT_ov_exv_bAV5356LOADFACT_ov_hd_aAV5355LOADFACT_over_capAV5365LOADFACT_over_ehsAV1013LOADFACT_pinch_aAV2013LOADFACT_pinch_bAV5369LOADFACT_req_pwrAV5357LOADFACT_sct_ct_aAV5359LOADFACT_sh_sp_aAV5360LOADFACT_sh_sp_bAV5353LOADFACT_smzAV5349LOADFACT_tp_errorAV5352LOADFACT_zmBV5401M_MSTSLV_cap_maxAV5396M_MSTSLV_l_strt_dAV5402M_MSTSLV_lagstatBV5393M_MSTSLV_lead_selBV5398M_MSTSLV_ll_changAV5397M_MSTSLV_ll_hr_dBV5399M_MSTSLV_ll_pullBV5392M_MSTSLV_ms_activAV5400M_MSTSLV_ms_errorAV5404M_MSTSLV_slav_ewtAV5403M_MSTSLV_slav_hrAV5405M_MSTSLV_slav_lwtAV5395M_MSTSLV_slv_captAV5394M_MSTSLV_slv_statBV5210MAINTCFG_charge_cAV5216MAINTCFG_fgas_frqAV5214MAINTCFG_hr_freqAV5212MAINTCFG_mntn_typAV5213MAINTCFG_mth_freqAV5215MAINTCFG_run_daysBV5209MAINTCFG_s_alertBV5211MAINTCFG_wloop_cBV5277MODES_m_2stptBV5295MODES_m_autochBV5298MODES_m_boilerBV5296MODES_m_defr_aBV5297MODES_m_defr_bBV5276MODES_m_delayBV5279MODES_m_demlimBV5290MODES_m_dltp_aBV5291MODES_m_dltp_bBV5299MODES_m_ehsBV5300MODES_m_ewtlckBV5286MODES_m_hidgtaBV5287MODES_m_hidgtbBV5288MODES_m_hiprsaBV5289MODES_m_hiprsbBV5293MODES_m_hsmBV5301MODES_m_iceBV5284MODES_m_lowscaBV5285MODES_m_lowscbBV5292MODES_m_nightBV5283MODES_m_pmpperBV5282MODES_m_pmprotBV5278MODES_m_resetBV5280MODES_m_rploadBV5294MODES_m_secondaryBV5281MODES_m_whtrBV5217MSC_SERV_eco_pmpAV5218MSC_SERV_ecop_offAV5219MSC_SERV_ecop_onBV5220MSC_STAT_m_ecopmpBV5188MST_SLV_islegacyBV5187MST_SLV_isLwtTooAV5182MST_SLV_lag_miniBV5183MST_SLV_lag_pumpAV5180MST_SLV_lead_pulAV5177MST_SLV_lead_selAV5178MST_SLV_ll_bal_dBV5184MST_SLV_ll_serieAV5179MST_SLV_lstr_timAV5175MST_SLV_ms_ctrlAV5174MST_SLV_ms_selBV5185MST_SLV_mstEnblAV5176MST_SLV_slv_addrBV5186MST_SLV_slvEnblAV5181MST_SLV_start_dtAV5222OPT_SEL_boil_enAV5223OPT_SEL_dcfc_enAV5221OPT_SEL_ehs_enBV5342OPT_STA_demo_staBV5343OPT_STA_opt149BV5348OPT_STA_opt149BBV5347OPT_STA_opt295BV5344OPT_STA_opt5BV5345OPT_STA_opt6BV5346OPT_STA_opt8BV5253OUTPUTS_ALARMBV5254OUTPUTS_ALERTBV5259OUTPUTS_BOILERAV5258OUTPUTS_CAPT_010BV5251OUTPUTS_CO_HTR_ABV5252OUTPUTS_CO_HTR_BBV1032OUTPUTS_CP_A1BV1033OUTPUTS_CP_A2BV1034OUTPUTS_CP_A3BV1035OUTPUTS_CP_A4BV2032OUTPUTS_CP_B1BV2033OUTPUTS_CP_B2BV2034OUTPUTS_CP_B3BV2035OUTPUTS_CP_B4BV5260OUTPUTS_EHS1BV5261OUTPUTS_EHS2BV5262OUTPUTS_EHS3BV5263OUTPUTS_EHS4BV5256OUTPUTS_EXCH_HTRAV1014OUTPUTS_EXV_AAV2014OUTPUTS_EXV_BAV5247OUTPUTS_FAN_ST_AAV5248OUTPUTS_FAN_ST_BBV57OUTPUTS_HD_HTR_AAV75OUTPUTS_HD_HTR_BBV15OUTPUTS_RUNNINGBV5249OUTPUTS_RV_ABV5250OUTPUTS_RV_BBV5257OUTPUTS_SETFLOWBV5255OUTPUTS_SHUTDOWNAV1015OUTPUTS_VFAN_AAV2015OUTPUTS_VFAN_BAV1000PRESSURE_DP_AAV2000PRESSURE_DP_BAV37PRESSURE_PUMP_EWPAV38PRESSURE_PUMP_LWPAV1001PRESSURE_SP_AAV2001PRESSURE_SP_BBV10079PROTOCOL_FC_DSBLE_wrAV5106PUMPCONF_dp_stpAV5105PUMPCONF_dt_stpAV5104PUMPCONF_flow_ctlAV5117PUMPCONF_MinWpThrAV5013PUMPCONF_pump_delBV5016PUMPCONF_pump_locAV5110PUMPCONF_pump_maxAV5108PUMPCONF_pump_minBV5014PUMPCONF_pump_perAV5109PUMPCONF_pump_savBV5015PUMPCONF_pump_sbyAV73PUMPCONF_pump_seqAV5107PUMPCONF_wtr_zvalAV5273PUMPSTAT_delta_pAV5271PUMPSTAT_delta_tAV5272PUMPSTAT_dp_stpAV5270PUMPSTAT_dt_stpAV71PUMPSTAT_flowaAV72PUMPSTAT_flowaBV50PUMPSTAT_PUMP_1_rdBV10050PUMPSTAT_PUMP_1_wrBV51PUMPSTAT_PUMP_2_rdBV10051PUMPSTAT_PUMP_2_wrBV5264PUMPSTAT_ROTWPUMPAV70PUMPSTAT_VPMP_CMDbBV5266PUMPSTAT_WP_CALAV5268PUMPSTAT_wp_filtAV5265PUMPSTAT_wp_inAV5269PUMPSTAT_wp_minAV5267PUMPSTAT_wp_offAV5264PUMPSTAT_wp_outBV5681RECLAIM_actiModeAV5678RECLAIM_cmd_3WVBV5670RECLAIM_HR_FLOWAV5672RECLAIM_HR_LWTBV5682RECLAIM_HR_pumpBV5668RECLAIM_HR_statAV5669RECLAIM_HRCtrPntAV5671RECLAIM_HRCtrWatBV5674RECLAIM_HRheaterAV5680RECLAIM_mode_3WVAV5679RECLAIM_out_3WVBV5667RECLAIM_RECL_SEL_rdBV15667RECLAIM_RECL_SEL_wrAV5029RESETCFG_cr_degAV5019RESETCFG_cr_selAV5024RESETCFG_dt_cr_fuAV5023RESETCFG_dt_cr_noAV5033RESETCFG_dt_hr_fuAV5032RESETCFG_dt_hr_noAV5038RESETCFG_hr_degAV5020RESETCFG_hr_selAV5026RESETCFG_I_cr_fuAV5025RESETCFG_I_cr_noAV5035RESETCFG_I_hr_fuAV5034RESETCFG_I_hr_noAV5022RESETCFG_oat_crfuAV5021RESETCFG_oat_crnoAV5031RESETCFG_oat_hrfuAV5030RESETCFG_oat_hrnoAV5028RESETCFG_spacr_fuAV5027RESETCFG_spacr_noAV5037RESETCFG_spahr_fuAV5036RESETCFG_spahr_noAV1960RUNTIME_hr_cp_a1AV1961RUNTIME_hr_cp_a2AV1962RUNTIME_hr_cp_a3AV1963RUNTIME_hr_cp_a4AV2960RUNTIME_hr_cp_b1AV2961RUNTIME_hr_cp_b2AV2962RUNTIME_hr_cp_b3AV2963RUNTIME_hr_cp_b4AV1969RUNTIME_hr_fana1AV1970RUNTIME_hr_fana2AV1971RUNTIME_hr_fana3AV1972RUNTIME_hr_fana4AV1973RUNTIME_hr_fana5AV1974RUNTIME_hr_fana6AV1975RUNTIME_hr_fana7AV1976RUNTIME_hr_fana8AV2969RUNTIME_hr_fanb1AV2970RUNTIME_hr_fanb2AV2971RUNTIME_hr_fanb3AV2972RUNTIME_hr_fanb4AV2973RUNTIME_hr_fanb5AV2974RUNTIME_hr_fanb6AV2975RUNTIME_hr_fanb7AV2976RUNTIME_hr_fanb8AV960RUNTIME_hr_machAV962RUNTIME_hr_pump1AV963RUNTIME_hr_pump2AV5274RUNTIME_nb_defraAV5275RUNTIME_nb_defrbAV1964RUNTIME_st_cp_a1AV1965RUNTIME_st_cp_a2AV1966RUNTIME_st_cp_a3AV1967RUNTIME_st_cp_a4AV2964RUNTIME_st_cp_b1AV2965RUNTIME_st_cp_b2AV2966RUNTIME_st_cp_b3AV2967RUNTIME_st_cp_b4AV961RUNTIME_st_machBV5098SERVICE1_auto_smBV5111SERVICE1_b_metricAV5102SERVICE1_flow_spAV5113SERVICE1_FrDfrPerAV5096SERVICE1_freezespAV5100SERVICE1_hc_zmAV5095SERVICE1_heaterspAV5094SERVICE1_hp_thAV5115SERVICE1_Leak_thrAV5116SERVICE1_Leak_tmrAV5097SERVICE1_mini_lwtAV5114SERVICE1_OatFrDfrBV5103SERVICE1_pump_cycAV5101SERVICE1_ser_passAV5112SERVICE1_unit_altAV5099SERVICE1_zm_stpAV5199SERVICE2_fan_kdAV5198SERVICE2_fan_kiAV5197SERVICE2_fan_kpAV5200SERVICE2_fan_maxAV5204SERVICE2_mop_spAV5205SERVICE2_sh_sp_aAV5206SERVICE2_sh_sp_bAV5203SERVICE2_vfheatkdAV5202SERVICE2_vfheatkiAV5201SERVICE2_vfheatkpAV900SETPOINT_csp1AV901SETPOINT_csp2AV5709SETPOINT_hr_stpAV903SETPOINT_hsp1AV904SETPOINT_hsp2AV902SETPOINT_ice_spAV905SETPOINT_lim_sp1AV906SETPOINT_lim_sp2AV907SETPOINT_lim_sp3AV5TEMP_CHWSTEMPAV1009TEMP_DGT_AAV2009TEMP_DGT_BAV1TEMP_EWTAV84TEMP_FC_EV_WTAV2TEMP_LWTAV3TEMP_OATAV1005TEMP_SCT_AAV2005TEMP_SCT_BAV1011TEMP_SH_AAV2011TEMP_SH_BAV1006TEMP_SST_AAV2006TEMP_SST_BAV1007TEMP_SUCT_AAV2007TEMP_SUCT_BAV77UNIT_HEATCOOLAV5161UPDTHOUR_FC_FAN1HAV5160UPDTHOUR_FC_FAN1SAV5163UPDTHOUR_FC_FAN2HAV5162UPDTHOUR_FC_FAN2SAV5165UPDTHOUR_FC_FAN3HAV5164UPDTHOUR_FC_FAN3SAV5167UPDTHOUR_FC_FAN4HAV5166UPDTHOUR_FC_FAN4SAV5169UPDTHOUR_FC_FAN5HAV5168UPDTHOUR_FC_FAN5SAV5171UPDTHOUR_FC_FAN6HAV5170UPDTHOUR_FC_FAN6SAV5173UPDTHOUR_FC_FAN7HAV5172UPDTHOUR_FC_FAN7SAV5159UPDTHOUR_FC_HOURAV5120UPDTHOUR_hr_cp_a1AV5121UPDTHOUR_hr_cp_a2AV5122UPDTHOUR_hr_cp_a3AV5123UPDTHOUR_hr_cp_a4AV5124UPDTHOUR_hr_cp_b1AV5125UPDTHOUR_hr_cp_b2AV5126UPDTHOUR_hr_cp_b3AV5127UPDTHOUR_hr_cp_b4AV5136UPDTHOUR_hr_fana1AV5137UPDTHOUR_hr_fana2AV5138UPDTHOUR_hr_fana3AV5139UPDTHOUR_hr_fana4AV5140UPDTHOUR_hr_fana5AV5141UPDTHOUR_hr_fana6AV5142UPDTHOUR_hr_fana7AV5143UPDTHOUR_hr_fana8AV5144UPDTHOUR_hr_fanb1AV5145UPDTHOUR_hr_fanb2AV5146UPDTHOUR_hr_fanb3AV5147UPDTHOUR_hr_fanb4AV5148UPDTHOUR_hr_fanb5AV5149UPDTHOUR_hr_fanb6AV5150UPDTHOUR_hr_fanb7AV5151UPDTHOUR_hr_fanb8AV5118UPDTHOUR_hr_machAV5152UPDTHOUR_hr_pump1AV5153UPDTHOUR_hr_pump2AV5157UPDTHOUR_nb_defraAV5158UPDTHOUR_nb_defrbAV5128UPDTHOUR_st_cp_a1AV5129UPDTHOUR_st_cp_a2AV5130UPDTHOUR_st_cp_a3AV5131UPDTHOUR_st_cp_a4AV5132UPDTHOUR_st_cp_b1AV5133UPDTHOUR_st_cp_b2AV5134UPDTHOUR_st_cp_b3AV5135UPDTHOUR_st_cp_b4AV5119UPDTHOUR_st_machAV5018USERCONF_languageAV5017USERCONF_use_pass
Integration notes
- This is the larger 30RC 065-252 range; the 30RC 010-060 has its own, much shorter list (30RC-101T).
- Points are from the "BACnet 2" object table. The "BACnet 1" table before it is a trend log list (object name, log interval, trend log instance) with no object types, so it is not reproduced.
- Access is from the PV ACCESS column: RW and WO as writable, RO as read-only. BV 5320 DCFC_STA_m_dcfc is printed NA and is listed as read-only.
- No units column; temperatures follow the BACnet Metric Unit setting (bacunit, default Yes).
- Free cooling, heat reclaim, heat pump, electric heat and pump drive points only apply to units with those options.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaSnap 30RC 065-252 (Carrier Controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaSnap 30RC 065-252 (Carrier Controller)
How many BACnet points does the Carrier AquaSnap 30RC 065-252 (Carrier Controller) have?
This list has 738 BACnet objects: 469 analog values, 268 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaSnap 30RC 065-252 (Carrier Controller) BACnet points are writable?
23 of the 738 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaSnap 30RC 065-252 (Carrier Controller) BACnet documentation?
The source is AquaSnap 30RC 065-252 Air-Cooled Chillers with Carrier Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix D, BACnet IP and MS/TP Points) (30RC-3T), revision 2026-07, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/09/30RC-3T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaSnap 30RC 065-252 (Carrier Controller)?
Start with BV 10012 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 10058 GENUNIT_CHIL_OCC_wr (Network occupied command); AV 10006 GENUNIT_CTRL_PNT_wr (Leaving water control point from the BMS); AV 10008 GENUNIT_DEM_LIM_wr (Demand limit command); AV 21 GENUNIT_CTRL_TYP (Control type: Local, Network or Remote); AV 22 GENUNIT_STATUS (Running status); AV 2 TEMP_LWT (Leaving water temperature); AV 1 TEMP_EWT (Entering water temperature); AV 9 GENUNIT_CAP_T (Percent total capacity); AV 990 ALARMRST_ALM (Unit alarm state).
How do I enable BMS control of the Carrier AquaSnap 30RC 065-252 (Carrier Controller)?
Select the Network machine control method with the Start/Stop button; the unit then follows CCN, BACnet (if enabled) or Modbus (if enabled) commands and ignores the remote control contacts. Start/stop and occupancy are written to the _wr objects.
Does the Carrier AquaSnap 30RC 065-252 (Carrier Controller) need a BACnet heartbeat or have a communication timeout?
The manual says that if communication with the network is lost, the machine starts and is controlled locally.
How do I check these points on the real AquaSnap 30RC 065-252 (Carrier Controller)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaSnap 30RC 065-252 Air-Cooled Chillers with Carrier Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix D, BACnet IP and MS/TP Points) · 30RC-3T · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.