Water source heat pump controller · BACnet points list
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP) BACnet points list
Updated 7 November 2026
The TV-WSHP is a TruVu controller for Carrier 50 Series water source heat pumps. It speaks BACnet IP only on dual Ethernet ports; an MS/TP network needs a TruVu Compact Router (TV-CRB-E2). The table has 184 objects, including two sets of Unit Protection Module (UPM) data for stage 1 and stage 2 compressors, network inputs for space temperature, RH and CO2, and a BV per alarm.
This page lists 184 BACnet objects for the Carrier Water Source Heat Pump TruVu Controller (TV-WSHP) — 53 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- Water Source Heat Pump TruVu Controller (TV-WSHP)
- Equipment
- Water source heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 184 (53 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Connect the TV-WSHP to the BACnet IP network (or through a TV-CRB-E2 router for MS/TP), set Occupancy Source to BAS On/Off if the BMS should drive occupancy, then write MV 1001 and the occupied setpoints. Read System Mode, controlling temperature, fan and compressor status and the alarm BVs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1001 | keypad_ovrde | BAS occupancy: 1=Inactive, 2=Occupied, 3=Unoccupied | Write |
| AV 3001 | occ_cl_stpt | Occupied cooling setpoint | Write |
| AV 3002 | occ_ht_stpt | Occupied heating setpoint | Write |
| MV 2002 | run_status | System mode (cooling, heating, fan only, shutdown...) | Read |
| BV 2008 | occ_status | Current occupancy status | Read |
| AV 2035 | ctrl_temp | Controlling temperature | Read |
| BV 1003 | sfan_status | Supply fan status | Read |
| MV 1004 | shtdown_reason | Shutdown reason (sensor fail, condensate, UPM lockout) | Read |
| BV 7041 | hard_lck_out_alarm_mb | Unit hard lockout alarm | Read |
Enable & remote start
Occupancy Source (MV 1002) defaults to Always Occupied; set it to BAS On/Off (3) so the BMS can drive occupancy through BAS On/Off (MV 1001), or to BACnet Schedule (2) to follow a schedule.
Sensors & values from the BMS
System Space Temperature (AV 1902), System Space RH (AV 1904), System Space AQ (AV 1903), System Outdoor Air Temperature (AV 1901) and System Setpoint Adjustment (AV 1913) are writable network inputs; they default to -999 (no value).
Network setup
- BACnet IP only, on dual 10/100 Ethernet ports that can be daisy-chained.
- For an MS/TP system, add a TruVu Compact Router (TV-CRB-E2).
- Local access is through the Equipment Touch or Field Assistant over the local access port or Rnet.
Watch out for
- The Test AO/DO points (91000 range) are for service testing; leave them alone during normal operation.
- UPM DIP switch BVs (6106-6111, 6206-6211) only report switch positions; they cannot be changed over the network.
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 3001 | occ_cl_stpt | Cooling Occupied Setpoint | °F | Write | |
| AVmin | 3002 | occ_ht_stpt | Heating Occupied Setpoint | °F | Write | |
| AV | 3003 | unocc_cl_stpt | Cooling Unoccupied Setpoint | °F | Write | |
| AV | 3004 | unocc_ht_stpt | Heating Unoccupied Setpoint | °F | Write | |
| AV | 2702 | link_hwt | Aux Heat Boiler Water Temp | °F | Read | |
| AV | 3014 | aux_heat_stpt | Aux Heat Control Setpoint | °F | Read | |
| AV | 2021 | aux_heat_output | Auxiliary Heat Ctrl Output | % | Read | |
| AV | 2036 | src_wtr_diff_clg | Clg Src Water Diff Stpt | °F | Write | |
| AV | 5001 | comp_cap | Compressor Capacity | % | Read | |
| AV | 6122 | comp_run_stg1 | Comp Runtime Stage 1 (UPM) | hrs | Read | |
| AV | 6222 | comp_run_stg2 | Comp Runtime Stage 2 (UPM) | hrs | Read | |
| AV | 6118 | start_req_stg1 | Comp Start Requests Stage 1 (UPM) | Read | ||
| AV | 6218 | start_req_stg2 | Comp Start Requests Stage 2 (UPM) | Read | ||
| AV | 6120 | starts_stg1 | Comp Starts Stage 1 (UPM) | Read | ||
| AV | 6220 | starts_stg2 | Comp Starts Stage 2 (UPM) | Read | ||
| AVmin | 2035 | ctrl_temp | Controlling Temperature - Prime Variable | °F | Read | |
| AV | 9002 | oat_cl_lockout | Cooling OAT Lockout Temp | °F | Write | |
| AV | 6105 | flt_status_stg1 | Current Fault Status Stage 1 (UPM) | Read | ||
| AV | 6205 | flt_status_stg2 | Current Fault Status Stage 2 (UPM) | Read | ||
| AV | 2029 | hgrh_heat_output | Dehum Ctrl Output | % | Read | |
| AV | 3005 | eff_cl_stpt | Effective Cool Setpoint | °F | Read | |
| AV | 3006 | eff_ht_stpt | Effective Heat Setpoint | °F | Read | |
| AV | 3008 | src_wtr_diff_eff | Effective Src Water Diff Stpt | °F | Read | |
| AV | 1020 | cwe_temp | Entering SrcW Temp | °F | Read | |
| AV | 9024 | fan_delay_off | Fan Off Delay | sec | Write | |
| AV | 9025 | fan_delay_on | Fan On Delay | sec | Write | |
| AV | 2015 | filter_rntm | Filter Runtime | hrs | Read | |
| AV | 2019 | filter_service_hrs | Filter Service Alarm Timer | hrs | Write | |
| AV | 6123 | freeze1_stg1 | Freeze 1 Temp Stage 1 (UPM) | °F | Read | |
| AV | 6223 | freeze1_stg2 | Freeze 1 Temp Stage 2 (UPM) | °F | Read | |
| AV | 6124 | freeze2_stg1 | Freeze 2 Temp Stage 1 (UPM) | °F | Read | |
| AV | 6224 | freeze2_stg2 | Freeze 2 Temp Stage 2 (UPM) | °F | Read | |
| AV | 6104 | hd_lock_stg1 | Hard Lockout Status Stage 1 (UPM) | Read | ||
| AV | 6204 | hd_lock_stg2 | Hard Lockout Status Stage 2 (UPM) | Read | ||
| AV | 9003 | oat_ht_lockout | Heating OAT Lockout Temp | °F | Write | |
| AV | 2046 | src_wtr_diff_htg | Htg Src Water Diff Stpt | °F | Read | |
| AV | 2047 | src_wtr_diff_per | Htg Src Water Diff Stpt as % Clg Stpt | °F | Read | |
| AV | 1009 | iaq | Indoor Air Quality CO2 (ppm) | ppm | Read | |
| AV | 1017 | cwl_temp | Leaving SrcW Temp | °F | Read | |
| AV | 2024 | loop_request | Loop Pump Request | 0 (Off) / 1 (On) | Read | |
| AV | 83004 | sat_ht_max | Maximum Heating SAT | °F | Write | |
| AV | 83003 | sat_cl_min | Minimum Cooling SAT | °F | Write | |
| AV | 2022 | oad_output | OA Damper Ctrl Output | % | Read | |
| AV | 9028 | occ_ovr_delay | Occ Override Delay | min | Write | |
| AV | 3011 | occ_dehum_stpt | Occ Relative Humidity Setpoint | %rh | Write | |
| AV | 9054 | os_delay_mins | Occupied Standby Delay (T24) | min | Write | |
| AV | 9053 | os_stpt_offset | Occupied Standby Offset (T24) | °F | Write | |
| AV | 9026 | optm_start | Optimal Start | hrs | Write | |
| AV | 1003 | oa_temp | Outdoor Air Temperature | °F | Read | |
| AV | 9007 | start_delay | Power Fail Restart Delay | sec | Write | |
| AV | 9058 | os_delay_rem | Remaining Occupied Standby Delay (T24) | min | Read | |
| AV | 1010 | ra_temp | Return Air Temperature | °F | Read | |
| AV | 6116 | run_sf_lock_stg1 | Running Soft Lockouts Stage 1 (UPM) | Read | ||
| AV | 6216 | run_sf_lock_stg2 | Running Soft Lockouts Stage 2 (UPM) | Read | ||
| AV | 1006 | stpt_adj | Setpoint Adjustment | °F | Read | |
| AV | 9015 | stpt_adj_range | Setpoint Adjustment Range | °F | Write | |
| AV | 6106 | sf_lock_stg1 | Soft Lockouts Stage 1 (UPM) | Read | ||
| AV | 6206 | sf_lock_stg2 | Soft Lockouts Stage 2 (UPM) | Read | ||
| AV | 1011 | space_rh | Space Relative Humidity | %rh | Read | |
| AV | 2007 | space_temp | Space Temperature | °F | Read | |
| AV | 1033 | stdby_offset | Standby Offset | °F | Write | |
| AV | 1008 | sa_temp | Supply Air Temperature | °F | Read | |
| AV | 6103 | sys_config_stg1 | System Configuration Stage 1 (UPM) | Read | ||
| AV | 6203 | sys_config_stg2 | System Configuration Stage 2 (UPM) | Read | ||
| AV | 9006 | cool_demand_level | System Cooling Demand Level | Read | ||
| AV | 9036 | heat_demand_level | System Heating Demand Level | Read | ||
| AV | 1901 | system_oat | System Outdoor Air Temperature | °F | Write | |
| AV | 1913 | system_stpt_adj | System Setpoint Adjustment | °F | Write | |
| AV | 1903 | system_iaq | System Space AQ | ppm | Write | |
| AV | 1904 | system_rh | System Space RH | %rh | Write | |
| AV | 1902 | system_spt | System Space Temperature | °F | Write | |
| AV | 9023 | ovr_dur | T55 Override Duration | hrs | Write | |
| AV | 91008 | ao_two | Test AO-2 | % | Write | |
| AV | 91009 | ao_three | Test AO-3 | % | Write | |
| AV | 91010 | uo_one | Test UO-1 | % | Write | |
| AV | 3012 | unocc_dehum_stpt | Unocc Relative Humidity Setpoint | %rh | Write | |
| AV | 9016 | uno_spt_alrm_hi_lmt | Unoccupied High SPT Alarm Limit | °F | Write | |
| AV | 9017 | uno_spt_alrm_lo_lmt | Unoccupied Low SPT Alarm Limit | °F | Write | |
| AV | 6101 | firm_ver_stg1 | UPM Firmware Version Stage 1 (UPM) | Read | ||
| AV | 6201 | firm_ver_stg2 | UPM Firmware Version Stage 2 (UPM) | Read | ||
| AV | 4005 | econ_min | Vent Dmpr Pos / DCV Min Pos | % | Write | |
| AV | 3015 | h2o_econ_ctrl_stpt | Water Economizer Control Setpoint | °F | Read | |
| AV | 2023 | h2o_econ_output | Water Economizer Output | % | Read | |
| AV | 2701 | link_cwt | Water Loop Temp | °F | Read | |
| AV | 2042 | water_flow | Water Meter | GPM | Read | |
| BV | 2703 | hw_pump | Aux Heat HW Pump Status | Read | 0=Off, 1=On | |
| BV | 6105 | contact_status_stg1 | Compressor Contactor Status Stage 1 (UPM) | Read | ||
| BV | 6205 | contact_status_stg2 | Compressor Contactor Status Stage 2 (UPM) | Read | ||
| BV | 6104 | condensate_status | Primary Condensate Status (UPM) | Read | ||
| BV | 1011 | cl_enable | Cool Enable | Write | 0=Disable, 1=Enable | |
| BV | 2006 | dehum | Dehumidification | Read | 0=Inactive, 1=Active | |
| BV | 6106 | lck_sw_1stg_1 | DIP SW(1) Lockout Switch Stage 1 (UPM) | Read | 0=2, 1=4 | |
| BV | 6206 | lck_sw_1stg_2 | DIP SW(1) Lockout Switch Stage 2 (UPM) | Read | 0=2, 1=4 | |
| BV | 6107 | reset_sw_2stg_1 | DIP SW(2) Reset Switch Stage 1 (UPM) | Read | 0=Y, 1=R | |
| BV | 6207 | reset_sw_2stg_2 | DIP SW(2) Reset Switch Stage 2 (UPM) | Read | 0=Y, 1=R | |
| BV | 6108 | alm_sw_3stg_1 | DIP SW(3) Alarm Switch Stage 1 (UPM) | Read | 0=Pulse, 1=Continuous | |
| BV | 6208 | alm_sw_3stg_2 | DIP SW(3) Alarm Switch Stage 2 (UPM) | Read | 0=Pulse, 1=Continuous | |
| BV | 6109 | test_sw_4stg_1 | DIP SW(4) Test Switch Stage 1 (UPM) | Read | 0=No, 1=Yes | |
| BV | 6209 | test_sw_4stg_2 | DIP SW(4) Test Switch Stage 2 (UPM) | Read | 0=No, 1=Yes | |
| BV | 6110 | frz_sw_5stg_1 | DIP SW(5) Freeze 1 Switch Stage 1 (UPM) | Read | 0=25°F, 1=15°F | |
| BV | 6210 | frz_sw_5stg_2 | DIP SW(5) Freeze 1 Switch Stage 2 (UPM) | Read | 0=25°F, 1=15°F | |
| BV | 6111 | frz2_sw_6stg_1 | DIP SW(6) Freeze 2 Switch Stage 1 (UPM) | Read | 0=25°F, 1=15°F | |
| BV | 6211 | frz2_sw_6stg_2 | DIP SW(6) Freeze 2 Switch Stage 2 (UPM) | Read | 0=25°F, 1=15°F | |
| BV | 2011 | emerg_shtdwn_status | Emergency Shutdown Status | Read | 0=Off, 1=On | |
| BV | 9050 | ena_t24 | Enable CEC Title 24 (T24) | Write | 0=Disable, 1=Enable | |
| BV | 91000 | fac_test_enable | Factory Test | Write | 0=Disable, 1=Enable | |
| BV | 1005 | flow | Flow | Read | 0=Off, 1=On | |
| BV | 1002 | flow_sw_status | Flow Switch Input | Read | 0=No Flow, 1=Flow | |
| BV | 1012 | ht_enable | Heat Enable | Write | 0=Disable, 1=Enable | |
| BV | 6102 | hps_status_stg1 | HPS Status Stage 1 (UPM) | Read | 0=High Pressure Fault, 1=Normal | |
| BV | 6202 | hps_status_stg2 | HPS Status Stage 2 (UPM) | Read | 0=High Pressure Fault, 1=Normal | |
| BV | 9052 | os_inhib | Inhibit Occupied Standby from this zone? (T24) | Write | 0=No, 1=Yes | |
| BV | 2702 | loop_pump | Loop Pump Status | Read | 0=Off, 1=On | |
| BV | 6103 | lps_status_stg1 | LPS Status Stage 1 (UPM) | Read | 0=Low Pressure Fault, 1=Normal | |
| BV | 6203 | lps_status_stg2 | LPS Status Stage 2 (UPM) | Read | 0=Low Pressure Fault, 1=Normal | |
| BV | 1020 | occ_contact_status | Occupancy Contact | Read | 0=Inactive, 1=Active Occupied | |
| BVmin | 2008 | occ_status | Occupancy Status | Read | 0=Unoccupied, 1=Occupied | |
| BV | 9051 | occ_stndby | Occupied Standby (T24) | Write | 0=Disable, 1=Enable | |
| BV | 9057 | os_delay | Occupied Standby Delay (T24) | Read | 0=Inactive, 1=Active Occupied | |
| BV | 7517 | filter_rntm_clr | Reset Filter Alarm | Write | 0=Off, 1=On | |
| BV | 99005 | rev_vlv_type | Reversing Valve Type | Write | 0=O, 1=B | |
| BV | 1001 | overflow_sw_status | Secondary Condensate Overflow | Read | 0=Off, 1=On | |
| BV | 1013 | stpt_adj_enable | Setpoint Adjustment | Write | 0=Disable, 1=Enable | |
| BV | 9001 | shutdown | Shutdown | Write | 0=Inactive, 1=Active | |
| BV | 2701 | cw_link_status | Source Water Linkage | Read | 0=Not Active, 1=Active | |
| BV | 1021 | src_vlv_otpt_bv | Source Water Valve | Read | 0=Close, 1=Open | |
| AV | 2048 | src_vlv_otpu_av | Src Water Valve Ctrl Output | % | Read | |
| BVmin | 1003 | sfan_status | Supply Fan Status | Read | 0=Off, 1=On | |
| BV | 91002 | do_two | Test DO-2 | Write | 0=Off, 1=On | |
| BV | 91003 | do_three | Test DO-3 | Write | 0=Off, 1=On | |
| BV | 91004 | do_four | Test DO-4 | Write | 0=Off, 1=On | |
| BV | 91005 | do_five | Test DO-5 | Write | 0=Off, 1=On | |
| BV | 91006 | do_six | Test DO-6 | Write | 0=Off, 1=On | |
| BV | 91007 | do_seven | Test DO-7 | Write | 0=Off, 1=On | |
| BV | 2027 | h2o_econ_output_bo | Water Economizer | Read | 0=Inactive, 1=Active | |
| BV | 6101 | y_call_stg1 | Y Call Stage 1 (UPM) | Read | 0=No Call, 1=Call | |
| BV | 6201 | y_call_stg2 | Y Call Stage 2 (UPM) | Read | 0=No Call, 1=Call | |
| MVmin | 1001 | keypad_ovrde | BAS On / Off | Write | 1=Inactive, 2=Occupied, 3=Unoccupied | |
| MV | 2013 | ctrl_temp_src | Ctrl Temp Source | Read | 1=Sensor Failure, 2=Space, 3=Return Air, 5=Locked Value | |
| MV | 6100 | cur_flt_stg1 | Current Fault Stage 1 (UPM) | Read | 1=No Fault, 2=HPC Fault, 3=LPC Fault, 4=Freeze 1 Fault, 5=Condensate Fault, 6=Brownout Fault, 7=Freeze 2 Fault, 8=Refrig Sensor Fault, 9=HPC1 Fault, 10=LPC1 Fault, 11=HPC2 Fault, 12=LPC2 Fault, 13=Freeze 1 Fault, 14=Condensate Fault, 15=Brownout Fault, 16=Freeze 2 Fault | |
| MV | 6200 | cur_flt_stg2 | Current Fault Stage 2 (UPM) | Read | Same as Current Fault Stage 1 (UPM) | |
| MV | 2004 | fan_run | Fan Speed | Read | 1=Off, 2=Low, 3=Medium, 4=High, 5=On | |
| MV | 6101 | hd_lk_stg1 | Hard Lockout Stage 1 (UPM) | Read | Same as Current Fault Stage 1 (UPM) | |
| MV | 6201 | hd_lk_stg2 | Hard Lockout Stage 2 (UPM) | Read | Same as Current Fault Stage 1 (UPM) | |
| MV | 1002 | occ_source | Occupancy Source | Write | 1=Always Occupied, 2=BACnet Schedule, 3=BAS OnOff, 4=Remote Occ Input | |
| MV | 9055 | occ_stndby_status | Occupied Standby Mode (T24) | Read | 1=Inactive, 2=Fan Off, 4=Heating, 5=Cooling, 6=Fan Running | |
| MV | 9056 | os_snsd_occ_source | Occupied Standby Source (T24) | Read | 1=Sensor Failure, 2=Local, 3=Network, 4=ZS Sensor, 5=Locked Value | |
| MV | 2009 | start_type | Optimal Start Type | Write | 1=None, 2=Temp Compensated, 3=Learning Adaptive | |
| MVmin | 1004 | shtdown_reason | Shutdown Reason | Read | 1=Normal Operation, 2=CTRL Temp Sensor Fail, 3=SAT Sensor Fail, 4=Condensate Overflow, 5=Hard Lockout UPM, 6=Emergency Shutdown | |
| MV | 2003 | spt_status | Space Temp Source | Read | 1=Not Available, 3=T55, 4=Network, 6=Locked Value, 7=ZS Sensor | |
| MVmin | 2002 | run_status | System Mode | Read | 1=Off, 2=Fan Only, 3=Economize, 4=Cooling, 5=Heating, 6=Continuous Fan, 7=Test, 8=Start Delay, 9=Dehumidify, 10=Emerg. Shutdown, 11=Manual Shutdown, 12=IAQ Override, 13=I/O Config Error | |
| MV | 91002 | dpr_type | Ventilation Damper Control | Write | 1=2-Pos, 2=DCV | |
| BV | 7034 | airdeltat_alm | Airside Delta T Alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7024 | co2_fail | CO2 Sensor Failure | Read | 0=Normal, 1=Alarm | |
| BV | 7013 | comp1_alarm | Compressor 1 Status | Read | 0=Normal, 1=Alarm | |
| BV | 7014 | comp2_alarm | Compressor 2 Status | Read | 0=Normal, 1=Alarm | |
| BV | 7088 | cool_cwt_alarm | Cooling Source Water Temperature | Read | 0=Normal, 1=Alarm | |
| BV | 7067 | ctrl_temp_fail | Ctrl Temp Sensor Failure | Read | 0=Normal, 1=Alarm | |
| BV | 7007 | emergency_alarm | Emergency Shutdown | Read | 0=Normal, 1=Alarm | |
| BV | 7017 | filter_alarm | Filter | Read | 0=Normal, 1=Alarm | |
| BV | 7027 | heat_cwt_alarm | Heating Source Water Temperature | Read | 0=Normal, 1=Alarm | |
| BV | 7011 | spt_hi_alarm | High Space Temperature | Read | 0=Normal, 1=Alarm | |
| BV | 7005 | iaq_alarm | Indoor Air Quality | Read | 0=Normal, 1=Alarm | |
| BV | 7025 | inpt_cfg_alarm | Input Configuration | Read | 0=Normal, 1=Alarm | |
| BV | 7012 | spt_lo_alarm | Low Space Temperature | Read | 0=Normal, 1=Alarm | |
| BV | 7026 | low_flow_alarm | Low Water Flow | Read | 0=Normal, 1=Alarm | |
| BV | 7030 | sa_oad_alarm | OA Damper Alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7029 | oat_fail | Outdoor Air Temp Sensor | Read | 0=Normal, 1=Alarm | |
| BV | 7070 | otpt_cfg_alarm | Output Configuration | Read | 0=Normal, 1=Alarm | |
| BV | 7040 | pri_overflow_alarm_mb | Primary Condensate Overflow (UPM) | Read | 0=Normal, 1=Alarm | |
| BV | 7035 | rat_alarm | Return Air Temperature Alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7071 | ra_temp_fail | Return Temp Sensor Failure | Read | 0=Normal, 1=Alarm | |
| BV | 7028 | overflow_alarm | Secondary Condensate Overflow | Read | 0=Normal, 1=Alarm | |
| BV | 7031 | cond_water_linkage_fail | Source Water Linkage | Read | 0=Normal, 1=Alarm | |
| BV | 7018 | sprh_hi_alarm | Space Relative Humidity | Read | 0=Normal, 1=Alarm | |
| BV | 7032 | sv_src_water_alarm | Src Water Valve Alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7033 | srcwdeltat_alm | SrcW Delta T Alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7004 | sat_alarm | Supply Air Temperature Alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7008 | sfan_fail_alarm | Supply Fan Failure | Read | 0=Normal, 1=Alarm | |
| BV | 7069 | sa_temp_fail | Supply Temp Sensor Failure | Read | 0=Normal, 1=Alarm | |
| BVmin | 7041 | hard_lck_out_alarm_mb | Unit Hard Lockout | Read | 0=Normal, 1=Alarm | |
| BV | 7036 | sv_wse_alarm | Water Economizer Alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7055 | zs_config_fail | ZS Sensor Configuration | Read | 0=Normal, 1=Alarm | |
| BV | 7051 | zst_sensor_fail | ZS Temp Sensor | Read | 0=Normal, 1=Alarm |
No points match these filters.
Object ID lookup: Carrier TV-WSHP point IDs by name
AV3001occ_cl_stptAV3002occ_ht_stptAV3003unocc_cl_stptAV3004unocc_ht_stptAV2702link_hwtAV3014aux_heat_stptAV2021aux_heat_outputAV2036src_wtr_diff_clgAV5001comp_capAV6122comp_run_stg1AV6222comp_run_stg2AV6118start_req_stg1AV6218start_req_stg2AV6120starts_stg1AV6220starts_stg2AV2035ctrl_tempAV9002oat_cl_lockoutAV6105flt_status_stg1AV6205flt_status_stg2AV2029hgrh_heat_outputAV3005eff_cl_stptAV3006eff_ht_stptAV3008src_wtr_diff_effAV1020cwe_tempAV9024fan_delay_offAV9025fan_delay_onAV2015filter_rntmAV2019filter_service_hrsAV6123freeze1_stg1AV6223freeze1_stg2AV6124freeze2_stg1AV6224freeze2_stg2AV6104hd_lock_stg1AV6204hd_lock_stg2AV9003oat_ht_lockoutAV2046src_wtr_diff_htgAV2047src_wtr_diff_perAV1009iaqAV1017cwl_tempAV2024loop_requestAV83004sat_ht_maxAV83003sat_cl_minAV2022oad_outputAV9028occ_ovr_delayAV3011occ_dehum_stptAV9054os_delay_minsAV9053os_stpt_offsetAV9026optm_startAV1003oa_tempAV9007start_delayAV9058os_delay_remAV1010ra_tempAV6116run_sf_lock_stg1AV6216run_sf_lock_stg2AV1006stpt_adjAV9015stpt_adj_rangeAV6106sf_lock_stg1AV6206sf_lock_stg2AV1011space_rhAV2007space_tempAV1033stdby_offsetAV1008sa_tempAV6103sys_config_stg1AV6203sys_config_stg2AV9006cool_demand_levelAV9036heat_demand_levelAV1901system_oatAV1913system_stpt_adjAV1903system_iaqAV1904system_rhAV1902system_sptAV9023ovr_durAV91008ao_twoAV91009ao_threeAV91010uo_oneAV3012unocc_dehum_stptAV9016uno_spt_alrm_hi_lmtAV9017uno_spt_alrm_lo_lmtAV6101firm_ver_stg1AV6201firm_ver_stg2AV4005econ_minAV3015h2o_econ_ctrl_stptAV2023h2o_econ_outputAV2701link_cwtAV2042water_flowBV2703hw_pumpBV6105contact_status_stg1BV6205contact_status_stg2BV6104condensate_statusBV1011cl_enableBV2006dehumBV6106lck_sw_1stg_1BV6206lck_sw_1stg_2BV6107reset_sw_2stg_1BV6207reset_sw_2stg_2BV6108alm_sw_3stg_1BV6208alm_sw_3stg_2BV6109test_sw_4stg_1BV6209test_sw_4stg_2BV6110frz_sw_5stg_1BV6210frz_sw_5stg_2BV6111frz2_sw_6stg_1BV6211frz2_sw_6stg_2BV2011emerg_shtdwn_statusBV9050ena_t24BV91000fac_test_enableBV1005flowBV1002flow_sw_statusBV1012ht_enableBV6102hps_status_stg1BV6202hps_status_stg2BV9052os_inhibBV2702loop_pumpBV6103lps_status_stg1BV6203lps_status_stg2BV1020occ_contact_statusBV2008occ_statusBV9051occ_stndbyBV9057os_delayBV7517filter_rntm_clrBV99005rev_vlv_typeBV1001overflow_sw_statusBV1013stpt_adj_enableBV9001shutdownBV2701cw_link_statusBV1021src_vlv_otpt_bvAV2048src_vlv_otpu_avBV1003sfan_statusBV91002do_twoBV91003do_threeBV91004do_fourBV91005do_fiveBV91006do_sixBV91007do_sevenBV2027h2o_econ_output_boBV6101y_call_stg1BV6201y_call_stg2MV1001keypad_ovrdeMV2013ctrl_temp_srcMV6100cur_flt_stg1MV6200cur_flt_stg2MV2004fan_runMV6101hd_lk_stg1MV6201hd_lk_stg2MV1002occ_sourceMV9055occ_stndby_statusMV9056os_snsd_occ_sourceMV2009start_typeMV1004shtdown_reasonMV2003spt_statusMV2002run_statusMV91002dpr_typeBV7034airdeltat_almBV7024co2_failBV7013comp1_alarmBV7014comp2_alarmBV7088cool_cwt_alarmBV7067ctrl_temp_failBV7007emergency_alarmBV7017filter_alarmBV7027heat_cwt_alarmBV7011spt_hi_alarmBV7005iaq_alarmBV7025inpt_cfg_alarmBV7012spt_lo_alarmBV7026low_flow_alarmBV7030sa_oad_alarmBV7029oat_failBV7070otpt_cfg_alarmBV7040pri_overflow_alarm_mbBV7035rat_alarmBV7071ra_temp_failBV7028overflow_alarmBV7031cond_water_linkage_failBV7018sprh_hi_alarmBV7032sv_src_water_alarmBV7033srcwdeltat_almBV7004sat_alarmBV7008sfan_fail_alarmBV7069sa_temp_failBV7041hard_lck_out_alarm_mbBV7036sv_wse_alarmBV7055zs_config_failBV7051zst_sensor_fail
Integration notes
- This is the TruVu generation; the older WSHP Open v3 controller has its own list.
- State texts are re-keyed from the Units column of the table (e.g. 0=Off, 1=On). MV 6100 lists states 1-16; MV 6200, 6101 and 6201 are printed as the same states as MV 6100.
- Stage 2 UPM points only apply to two-stage or two-compressor units.
- Space Temp Source (MV 2003) is printed with states 1, 3, 4, 6 and 7 only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Water Source Heat Pump TruVu Controller (TV-WSHP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
How many BACnet points does the Carrier Water Source Heat Pump TruVu Controller (TV-WSHP) have?
This list has 184 BACnet objects: 86 analog values, 83 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier Water Source Heat Pump TruVu Controller (TV-WSHP) BACnet points are writable?
53 of the 184 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier Water Source Heat Pump TruVu Controller (TV-WSHP) BACnet documentation?
The source is Water-Source Heat Pumps with TruVu Controller - Controls, Start-Up, Operation, and Troubleshooting (Appendix A, BACnet Points List) (TVWSHP-02T), revision 2026-06, published free by Carrier at https://brandportal.carrier.com/asset/a0bcfa77-38d3-428c-8e03-d6dd6a30d295/TVWSHP-02T.pdf.
What are the minimum BACnet points to integrate the Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)?
Start with MV 1001 keypad_ovrde (BAS occupancy: 1=Inactive, 2=Occupied, 3=Unoccupied); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); MV 2002 run_status (System mode (cooling, heating, fan only, shutdown...)); BV 2008 occ_status (Current occupancy status); AV 2035 ctrl_temp (Controlling temperature); BV 1003 sfan_status (Supply fan status); MV 1004 shtdown_reason (Shutdown reason (sensor fail, condensate, UPM lockout)); BV 7041 hard_lck_out_alarm_mb (Unit hard lockout alarm).
How do I enable BMS control of the Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)?
Occupancy Source (MV 1002) defaults to Always Occupied; set it to BAS On/Off (3) so the BMS can drive occupancy through BAS On/Off (MV 1001), or to BACnet Schedule (2) to follow a schedule.
Can the BMS supply sensor values to the Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)?
System Space Temperature (AV 1902), System Space RH (AV 1904), System Space AQ (AV 1903), System Outdoor Air Temperature (AV 1901) and System Setpoint Adjustment (AV 1913) are writable network inputs; they default to -999 (no value).
How do I check these points on the real Water Source Heat Pump TruVu Controller (TV-WSHP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: Water-Source Heat Pumps with TruVu Controller - Controls, Start-Up, Operation, and Troubleshooting (Appendix A, BACnet Points List) · TVWSHP-02T · rev. 2026-06. Object names, instances and units are reproduced as published; descriptions are our own.