Easy BACnet
  1. Home
  2. BACnet points lists
  3. Carrier
  4. Connect Wi-Fi Thermostat (33CONNECTSTAT43)

Networked room thermostat · BACnet points list

Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43) BACnet points list

Updated 4 November 2026

Short answer

The 33CONNECTSTAT43 is a Wi-Fi thermostat that also speaks BACnet MS/TP on its A+/B- terminals (B-ASC profile). Its 113 objects cover space temperature and humidity, setpoints, stage output status, fault flags, mode and fan mode, and most installer settings. Installer settings are 'gated' writes that only work when BACnet Config Write is enabled at the thermostat, and BMS occupancy only works when BACnet BMS Occ is enabled.

This page lists 113 BACnet objects for the Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43) — 74 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Equipment
Networked room thermostat
Equipment type
Thermostats, sensors & meters
BACnet objects
113 (74 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
16 followed by the last 4 digits of the serial number (range 1-4194302)
Also known as
33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01
Source document
Carrier Connect Wi-Fi Thermostat 33CONNECTSTAT43 Installation Guide (Appendix: BACnet Points List) · 11-808-728-01 · rev. 2022-12-02
Download CSV 113 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)

Integration in brief

Wire the thermostat to the MS/TP trunk and set MAC address, baud and device ID in its advanced system settings. Turn on BACnet BMS Occ at the thermostat if the BMS should drive occupancy through BMS_OCC, and BACnet Config Write only if the BMS must change installer settings. Write the baseline occupied/unoccupied setpoints for permanent changes; writes to HEAT_SP/COOL_SP are temporary holds.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 400USER_MODEMode command: off, heat, cool, auto, emergency heatWrite
BV 405BMS_OCCBMS occupancy; needs BACnet BMS Occ enabled locallyWrite
AV 400OCC_HT_SPOccupied heating setpointWrite
AV 401OCC_CL_SPOccupied cooling setpointWrite
MV 404OCC_FANOccupied fan mode: auto or onWrite
MV 300CURRENT_MODEMode now running: off, heat or coolRead
AV 104SP_TEMP_CTRLSpace temperature used for controlRead
BV 205G_OUTFan output statusRead
BV 911OD_TEMP_FAILOutdoor sensor failureRead

Enable & remote start

BACNET BMS OCC (set at the thermostat screen) enables BACnet occupancy control through BMS_OCC (BV:405); setting it to YES forces the thermostat to non-programmable mode and turns off a remote sensor set to Occupancy. BACNET CONFIG WRITE (also local) allows writes to all GATED_WRITE points. USER_MODE (MSV:400) sets the system mode.

Heartbeat & communication loss

No communication-loss timeout is described. Network general purpose outputs return to inactive if not rewritten within the General Purpose Output Timeout (MSV:508: 2 min, 20 min, 1 h or unlimited).

Sensors & values from the BMS

Network Space Temperature (AV:103) and Network Space Humidity (AV:105) are writable, with enables Network Space Temp Enable (BV:407) and Network Space Hum Enable (BV:408). The guide gives no refresh time for them. Read SP_TEMP_CTRL (AV:104) and SP_HUM_CTRL (AV:106) for the values in use.

Network setup

Watch out for

Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

113 of 113 shown
Type
BinaryMulti-state
Access
Show
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43) BACnet Points List
DescriptionStates
AI100ID_SPACE_TEMPIndoor Space Temperature (writable only when out of service)°FRead
AI101ID_SPACE_HUMIndoor Space Humidity (writable only when out of service)%RHRead
AV100REM_SPACE_TEMPRemote Space Temperature°FRead
AV101OD_TEMPOutdoor Temperature°FRead
AV102SATSupply Air Temperature°FRead
AV103NET_SP_TEMPNetwork Space Temperature°FWrite
AVmin104SP_TEMP_CTRLSpace Temperature for Control°FRead
AV105NET_SP_HUMNetwork Space Humidity%RHWrite
AV106SP_HUM_CTRLSpace Humidity for Control%RHRead
AV300AIR_FLTR_HRS_LFTAir Filter Hours LefthRead
AV301OVRD_TIMEOverride Time RemainingsRead
AVmin400OCC_HT_SPOccupied Heat Setpoint°FWrite
AVmin401OCC_CL_SPOccupied Cool Setpoint°FWrite
AV402UNOCC_HT_SPUnoccupied Heat Setpoint°FWrite
AV403UNOCC_CL_SPUnoccupied Cool Setpoint°FWrite
AV406DEHUM_SPDehumidification Setpoint%RHWrite
AV407HUM_SPHumidification Setpoint%RHWrite
AV408SCRN_TMTScreen TimeoutminWrite
AV409HEAT_SPHeat Setpoint°FWrite
AV410COOL_SPCool Setpoint°FWrite
AV411ACTV_BCKLTActive Backlight%Write
AV412DRMNT_BCKLTDormant Backlight%Write
AV500ID_STAGESIndoor Equip Stages (gated write)%RHWrite
AV501OD_STAGESOutdoor Equip Stages (gated write)°FWrite
AV502MAX_HOLD_TIMEMax Temperature Hold Time (gated write)hWrite
AV503AUTO_XOVRAuto Changeover Delay (gated write)minWrite
AV504COOL_LOCKOUTCool Lockout Temperature (gated write)°FWrite
AV505LO_CL_LCKOUTLow Cool Lockout (HP only) (gated write)°FWrite
AV506LO_HT_LCKOUTLow Heat Lockout (HP only) (gated write)°FWrite
AV507DLY_BW_FUELDelay Between Fuel (HP only) (gated write)minWrite
AV508CYCLES_HRCycles Per Hour (gated write)cycles/hWrite
AV509MAX_HT_SPMax Heat Setpoint (gated write)°FWrite
AV510MIN_CL_SPMin Cool Setpoint (gated write)°FWrite
AV511AUX_HT_LCKOUTAux Heat Lockout (HP only) (gated write)°FWrite
AV512HP_LCKOUTHeat Pump Lockout (gated write)°FWrite
AV513STG_DELAYStage Delay (gated write)minWrite
AV514FRCD_STG_UPForced Stage Up Delay (gated write)minWrite
AV515DIFFERENTIALStage Change Temp Differential (gated write)Δ°FWrite
AV516LINE_FREQLine Frequency (gated write)HzWrite
AV517ID_TEMP_OFFIndoor Temperature Offset (gated write)Δ°FWrite
AV518ID_HUM_OFFIndoor Humidity Offset (gated write)%RHWrite
AV519SAT_OFFSETSAT Temp Offset (gated write)Δ°FWrite
AV520AIR_FLT_HRSAir Filter HourshRead
AV521MAX_SP_ERRMax Setpoint Error (gated write)Δ°FWrite
AV522ID_TMP_FLT_INHBTIndoor Temp Fault Inhibit (gated write)minWrite
BV200Y1_OUT1st Stage Cooling Out StatusRead0=OFF, 1=ON
BV201Y2_OUT2nd Stage Cooling Out StatusRead0=OFF, 1=ON
BV202Y3_OUT3rd Stage Cooling Out StatusRead0=OFF, 1=ON
BV203W1_OUT1st Stage Heating Out StatusRead0=OFF, 1=ON
BV204W2_OUT2nd Stage Heating Out StatusRead0=OFF, 1=ON
BVmin205G_OUTFan Out StatusRead0=OFF, 1=ON
BV206OB_OUTReversing Valve Out StatusRead0=OFF, 1=ON
BV208OCC_OUTOccupancy Out StatusRead0=OFF, 1=ON
BV209HUM_OUTHumidifier Out StatusRead0=OFF, 1=ON
BV210DEHUM_OUTDehumidifier Out StatusRead0=OFF, 1=ON
BV211NET_GP_Y3_OUTNetwork General Purpose Out Y3Write0=OFF, 1=ON
BV212NET_GP_W2_OUTNetwork General Purpose Out W2Write0=OFF, 1=ON
BV213NET_GP_OB_OUTNetwork General Purpose Out OBWrite0=OFF, 1=ON
BV400WIFI_TIME_SYNCWi-Fi Time SynchronizationWrite0=DISABLED, 1=ENABLED
BV401PROXIMITY_ENProximity Sensor EnableWrite0=DISABLED, 1=ENABLED
BV402AUTO_DSTAuto DST Time ShiftWrite0=DISABLED, 1=ENABLED
BV403WIFI_ENABLEWi-Fi EnableWrite0=DISABLED, 1=ENABLED
BV404SETPT_OVERRIDESetpoint OverrideWrite0=DISABLED, 1=ENABLED
BVmin405BMS_OCCBACnet BMS Occupancy (gated write)Write0=UNOCCUPIED, 1=OCCUPIED
BV406FLTR_TMR_RSTFilter Timer ResetWrite0=INACTIVE, 1=ACTIVE
BV407NET_SP_TEMP_ENNetwork Space Temp EnableWrite0=DISABLED, 1=ENABLED
BV408NET_SP_HUM_ENNetwork Space Hum EnableWrite0=DISABLED, 1=ENABLED
BV500OCC_IN_POLOccupancy Input Polarity (gated write)Write0=OCCUPIED, 1=UNOCCUPIED
BV501ALLOW_AUTOAuto Mode Allowed (gated write)Write0=NO, 1=YES
BV502ALLOW_PROGProg Mode Allowed (gated write)Write0=NO, 1=YES
BV503CELSIUS_DISPCelsius Display (gated write)Write0=F°, 1=C°
BV504FAN_WITH_WFan On with W (gated write)Write0=NO, 1=YES
BV505RVS_VLV_DIRRvs Vlv Energized Ht (gated write)Write0=ENERGIZED FOR COOL, 1=ENERGIZED FOR HEAT
BV506HUM_INSTHumidifier Installed (gated write)Write0=NO, 1=YES
BV507BMS_OCC_ENBMS Occupancy Enable (gated write)Write0=DISABLED, 1=ENABLED
BV511CFG_WR_ENBACnet Config Write Enable (gated write)Write0=DISABLED, 1=ENABLED
BV900ID_TEMP_SENS_HIID TEMP SENSOR HIGHRead0=DISABLED, 1=ENABLED
BV901ID_TEMP_SENS_LOID TEMP SENSOR LOWRead0=INACTIVE, 1=ACTIVE
BV902REM_TEMP_HIREMOTE SENSOR HIGHRead0=INACTIVE, 1=ACTIVE
BV903REM_TEMP_LOREMOTE SENSOR LOWRead0=INACTIVE, 1=ACTIVE
BV904HUM_TEMP_HIHUM TEMP SENSOR HIGHRead0=INACTIVE, 1=ACTIVE
BV905HUM_TEMP_LOHUM TEMP SENSOR LOWRead0=INACTIVE, 1=ACTIVE
BV906ID_TEMP_RNG_HIID TEMP RANGE HIGHRead0=INACTIVE, 1=ACTIVE
BV907ID_TEMP_RNG_LOID TEMP RANGE LOWRead0=INACTIVE, 1=ACTIVE
BV908HUM_SENS_FAILHUM SENSOR FAILURERead0=INACTIVE, 1=ACTIVE
BV909HUM_TOO_HIHUMIDITY RANGE HIGHRead0=INACTIVE, 1=ACTIVE
BV910HUM_TOO_LOHUMIDITY RANGE LOWRead0=INACTIVE, 1=ACTIVE
BVmin911OD_TEMP_FAILOUTDOOR SENSOR FAILURERead0=INACTIVE, 1=ACTIVE
BV912SRVR_CONN_FAILNOT CONNECTED TO SERVERRead0=INACTIVE, 1=ACTIVE
BV913RTR_CONN_FAILNOT CONNECTED TO ROUTERRead0=INACTIVE, 1=ACTIVE
BV914WIFI_CONF_FAILWIFI HARDWARE FAULTRead0=INACTIVE, 1=ACTIVE
BV915ECON_FAULTECONOMIZER FAULTRead0=INACTIVE, 1=ACTIVE
BV916LOCKOUT_FAILLOCKOUT-5 BAD PIN ENTRIESRead0=INACTIVE, 1=ACTIVE
MVmin300CURRENT_MODECurrent Mode StatusRead1=OFF, 2=HEAT, 3=COOL
MVmin400USER_MODEUser ModeWrite1=OFF, 2=HEAT, 3=COOL, 4=AUTO, 5=E-HEAT
MV401PROX_SENSIR Proximity SensitivityWrite1=HIGH, 2=MEDIUM, 3=LOW
MV402SOUNDSound EffectWrite1=OFF, 2=CLICK, 3=BEEP
MV403SCHED_DAY_PARTSNumber of Parts in Schedule DayWrite1=2 PARTS, 2=4 PARTS
MVmin404OCC_FANOccupied Fan ModeWrite1=AUTO, 2=ON
MV405UNOCC_FANUnoccupied Fan ModeWrite1=AUTO, 2=ON
MV406FAN MODECurrent Fan ModeWrite1=AUTO, 2=ON, 3=OVERRIDE AUTO, 4=OVERRIDE ON
MV500ID_EQUIP_TYPEIndoor Equipment TypeRead1=NO INDOOR, 2=FURNACE, 3=AIR HANDLER
MV501OD_EQUIP_TYPEOutdoor Equipment Type (gated write)Write1=NO OUTDOOR, 2=A/C, 3=HEAT PUMP
MV502REMOTE_SENSORRemote Sensor Type (gated write)Write1=NONE, 2=OUTDOOR, 3=SPACE, 4=AVERAGE, 5=OCCUPANCY, 6=FAULT_INPUT, 7=SAT
MV503DEHUM_TYPEDehumidification Type (gated write)Write1=NO, 2=YES, 3=OVRCRL(2F), 4=HUMIDIMIZER
MV504OCC_OUTPUTOccupancy Output Terminal (gated write)Write1=OFF, 2=Y3, 3=O/B, 4=W2
MV505HUM_OUTPUTHumidification Output Terminal (gated write)Write1=OFF, 2=Y3, 3=O/B, 4=W2
MV506DEHUM_OUTPUTDehumidification Output Terminal (gated write)Write1=OFF, 2=Y3, 3=O/B, 4=W2
MV507SMART_RECVRYSmart Recovery (gated write)Write1=NO, 2=30 MIN, 3=60 MIN, 4=90 MIN
MV508GP_OUT_TIMEOUTGeneral Purpose Output Timeout (gated write)Write1=2 MIN, 2=20 MIN, 3=1 HR, 4=UNLIMITED
MV509NET_GP_Y3_MODENetwork GP Y3 Mode (gated write)Write1=DISABLED, 2=ENERGIZED_ACTIVE, 3=ENERGIZED_INACTIVE
MV510NET_GP_W2_MODENetwork GP W2 Mode (gated write)Write1=DISABLED, 2=ENERGIZED_ACTIVE, 3=ENERGIZED_INACTIVE
MV511NET_GP_OB_MODENetwork GP OB Mode (gated write)Write1=DISABLED, 2=ENERGIZED_ACTIVE, 3=ENERGIZED_INACTIVE
Object ID lookup: Carrier Connect Wi-Fi Thermostat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Connect Wi-Fi Thermostat (33CONNECTSTAT43) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)

How many BACnet points does the Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43) have?

This list has 113 BACnet objects: 2 analog inputs, 43 analog values, 48 binary values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43) BACnet points are writable?

74 of the 113 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43) BACnet documentation?

The source is Carrier Connect Wi-Fi Thermostat 33CONNECTSTAT43 Installation Guide (Appendix: BACnet Points List) (11-808-728-01), revision 2022-12-02, published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/0C/11-808-728-01.pdf.

What are the minimum BACnet points to integrate the Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)?

Start with MV 400 USER_MODE (Mode command: off, heat, cool, auto, emergency heat); BV 405 BMS_OCC (BMS occupancy; needs BACnet BMS Occ enabled locally); AV 400 OCC_HT_SP (Occupied heating setpoint); AV 401 OCC_CL_SP (Occupied cooling setpoint); MV 404 OCC_FAN (Occupied fan mode: auto or on); MV 300 CURRENT_MODE (Mode now running: off, heat or cool); AV 104 SP_TEMP_CTRL (Space temperature used for control); BV 205 G_OUT (Fan output status); BV 911 OD_TEMP_FAIL (Outdoor sensor failure).

How do I enable BMS control of the Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)?

BACNET BMS OCC (set at the thermostat screen) enables BACnet occupancy control through BMS_OCC (BV:405); setting it to YES forces the thermostat to non-programmable mode and turns off a remote sensor set to Occupancy. BACNET CONFIG WRITE (also local) allows writes to all GATED_WRITE points. USER_MODE (MSV:400) sets the system mode.

Does the Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43) need a BACnet heartbeat or have a communication timeout?

No communication-loss timeout is described. Network general purpose outputs return to inactive if not rewritten within the General Purpose Output Timeout (MSV:508: 2 min, 20 min, 1 h or unlimited).

Can the BMS supply sensor values to the Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)?

Network Space Temperature (AV:103) and Network Space Humidity (AV:105) are writable, with enables Network Space Temp Enable (BV:407) and Network Space Hum Enable (BV:408). The guide gives no refresh time for them. Read SP_TEMP_CTRL (AV:104) and SP_HUM_CTRL (AV:106) for the values in use.

How do I check these points on the real Connect Wi-Fi Thermostat (33CONNECTSTAT43)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: Carrier Connect Wi-Fi Thermostat 33CONNECTSTAT43 Installation Guide (Appendix: BACnet Points List) · 11-808-728-01 · rev. 2022-12-02. Object names, instances and units are reproduced as published; descriptions are our own.