Condensing unit (split system) controller · BACnet points list

Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option) BACnet points list

Updated 7 November 2026

Short answer

The 38RC controller has an Ethernet port (BACnet IP, Modbus TCP) and an RS-485 port (BACnet MS/TP, Modbus RTU); BACnet is turned on and the data link chosen in the HMI Configuration > BACnet Configuration menu. The network points list has 136 objects: unit start/stop, emergency stop, demand limit and cooling setpoints, circuit pressures and temperatures, compressor relays and feedback, run hours and starts, plus points for a second air handler (AHU2) on dual-circuit units.

This page lists 136 BACnet objects for the Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option) — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Equipment
Condensing unit (split system) controller
Equipment type
VRF & split air conditioners
BACnet objects
136 (27 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit
Source document
Gemini Select 38RCS025-050, 38RCD025-130 Commercial Air-Cooled Condensing Units - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix C, BACnet Option (IP and MS/TP), Network Points List) · 38RC-3T · rev. 2026-07
Download CSV 136 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)

Integration in brief

Enable BACnet in HMI Configuration > BACnet Configuration and pick IP or MS/TP as the data link, then set the unit's machine control method to Network. The BMS then starts and stops the unit (BV 4), writes demand limit and setpoints, and reads capacity, control mode and alarm state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 4A_UNIT_CHIL_S_SNetwork start/stop commandWrite
AV 2A_UNIT_DEM_LIMDemand limit command (%)Write
AV 5A_UNIT_CTRL_PNTControl pointWrite
BV 6A_UNIT_EMSTOPEmergency stop commandWrite
AV 8A_UNIT_STATControl mode / unit statusRead
AV 3A_UNIT_CAP_TPercent total capacityRead
AV 1008A_UNIT_SUPPLY_TSupply air temperatureWrite
MV 1A_UNIT_ALMAlarm stateRead

Enable & remote start

Set the machine control method to Network; the unit then follows CCN, BACnet (if enabled) or Modbus (if enabled) commands and ignores the remote contacts. In Local or Remote control it ignores network commands except Emergency Stop.

Sensors & values from the BMS

Return air (AV 1010), supply air (AV 1008), outdoor air (AV 1003) and space temperature (AV 2007) are listed as writable, so they can be supplied from the network when the unit is configured to use them.

Network setup

Watch out for

Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

136 of 136 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option) BACnet Points List
DescriptionStates
MVmin1A_UNIT_ALMAlarm StateRead
AVmin3A_UNIT_CAP_TPercent Total CapacityRead
BVmin4A_UNIT_CHIL_S_SCCN ChillerWrite
AV6A_UNIT_COOL_MA4-20 mA Setpoint SignalRead
AVmin5A_UNIT_CTRL_PNTControl PointWrite
AV2923A_UNIT_CTRL_PNT2Control Point AHU2Write
AVmin2A_UNIT_DEM_LIMActive Demand LimitWrite
BVmin6A_UNIT_EMSTOPEmergency StopWrite
AV32A_UNIT_MIN_LEFTMinutes Left for StartRead
BV5A_UNIT_MODEOverride Modes in EffectRead
BV2008A_UNIT_OCCOccupiedRead
AV1010A_UNIT_RETURN_TReturn Air TemperatureWrite
AV4A_UNIT_SPActive SetpointRead
AV2922A_UNIT_SP2Active Setpoint 2Read
AV52A_UNIT_SPTMODESpace Temp Control ModeRead
AV2921A_UNIT_SPTMODE2Space Temp Control Mode AH2Write
AVmin8A_UNIT_STATControl ModeRead
AVmin1008A_UNIT_SUPPLY_TSupply Air TemperatureWrite
AV2928AIRTEMP_DGT_ACirA Discharge Gas TempWrite
AV2929AIRTEMP_DGT_BCirc B Discharge TempWrite
AV12CIRCA_AN_CAPA_APercent Available Cap.Read
AV11CIRCA_AN_CAPA_TPercent Total CapacityRead
AV7CIRCA_AN_DIGCMPDTDischarge Gas TempRead
AV13CIRCA_AN_DP_ACirc A Disc PressureRead
AV40CIRCA_AN_SCTASaturated Condensing TmpRead
AV44CIRCA_AN_SH_ASuction Superheat TempRead
AV14CIRCA_AN_SP_ACirc A Suction PressureRead
AV17CIRCA_AN_SSTASaturated Suction TempRead
AV22CIRCB_AN_CAPB_APercent Available Cap.Read
AV21CIRCB_AN_CAPB_TPercent Total CapacityRead
AV23CIRCB_AN_DP_BCirc B Disc PressureRead
AV39CIRCB_AN_SCTBSaturated Condensing TmpRead
AV45CIRCB_AN_SH_BSuction Superheat TempRead
AV24CIRCB_AN_SP_BCirc B Suction PressureRead
AV26CIRCB_AN_SSTBSaturated Suction TempRead
BV38CURRMODS_MODE_10Minimum OFF time activeRead
BV40CURRMODS_MODE_14Temperature ResetRead
BV41CURRMODS_MODE_15Demand LimitedRead
BV43CURRMODS_MODE_17Low Temperature CoolingRead
BV44CURRMODS_MODE_18High Temperature CoolingRead
BV47CURRMODS_MODE_21High SCT Circuit ARead
BV48CURRMODS_MODE_22High SCT Circuit BRead
BV49CURRMODS_MODE_23Minimum Comp On TimeRead
BV51CURRMODS_MODE_25Low Sound ModeRead
BV33CURRMODS_MODE_5Ramp Load LimitedRead
BV34CURRMODS_MODE_6Timed Override in effectRead
BV37CURRMODS_MODE_9Slow Change OverrideRead
BV2918CURRMODS_MODE_B_17Low Temp Cooling AHU2Read
BV2919CURRMODS_MODE_B_18High Temp Cooling AHU2Read
BV2920CURRMODS_MODE_B_23Min Comp On Time AHU2Read
BV2916CURRMODS_MODE_B_5Ramp Load Ltd AHU2Read
BV2917CURRMODS_MODE_B_9Slow Chng Override AHU2Read
BV67CURRMODS_MODE_TGTime Guard ActiveRead
AV68CY_A1Compressor A1 StartsRead
AV69CY_A2Compressor A2 StartsRead
AV70CY_A3Compressor A3 StartsRead
AV72CY_B1Compressor B1 StartsRead
AV73CY_B2Compressor B2 StartsRead
AV74CY_B3Compressor B3 StartsRead
AV67CY_CIRACircuit A StartsRead
AV71CY_CIRBCircuit B StartsRead
AV58CY_MACHMachine StartsRead
AV34DIGITAL_LOADComp A1 Load PercentRead
BV60FAN_CONTACTOR1Fan Contactor 1Read
BV61FAN_CONTACTOR2Fan Contactor 2Read
BV62FAN_CONTACTOR3Fan Contactor 3Read
BV63FAN_CONTACTOR4Fan Contactor 4Read
BV64FAN_CONTACTOR5Fan Contactor 5Read
AV35FanStageAFanStageARead
AV15FanStageBFanStageBRead
BV2400GENUNIT_BAC_OCCBACnet OccupiedRead
BV2401GENUNIT_OCCUPIEDOccupiedRead
BV79HGBP_ValveHGBP Valve SelectRead
AV60HR_A1Compressor A1 Run HoursRead
AV61HR_A2Compressor A2 Run HoursRead
AV62HR_A3Compressor A3 Run HoursRead
AV64HR_B1Compressor B1 Run HoursRead
AV65HR_B2Compressor B2 Run HoursRead
AV66HR_B3Compressor B3 Run HoursRead
AV59HR_CIRACircuit A Run HoursRead
AV63HR_CIRBCircuit B Run HoursRead
AV57HR_MACHMachine Operating HoursRead
BV16K_A1_FBKCompressor A1 FeedbackRead
BV13K_A1_RLYCompressor A1 RelayRead
BV17K_A2_FBKCompressor A2 FeedbackRead
BV14K_A2_RLYCompressor A2 RelayRead
BV18K_A3_FBKCompressor A3 FeedbackRead
BV15K_A3_RLYCompressor A3 RelayRead
BV22K_B1_FBKCompressor B1 FeedbackRead
BV19K_B1_RLYCompressor B1 RelayRead
BV23K_B2_FBKCompressor B2 FeedbackRead
BV20K_B2_RLYCompressor B2 RelayRead
BV24K_B3_FBKCompressor B3 FeedbackRead
BV21K_B3_RLYCompressor B3 RelayRead
AV43LEAD_TYPLead/Lag Circuit SelectWrite
BV8LLSV_ALiquid Line Solenoid ARead
BV2402LLSV_A2Liquid Line Solenoid A2Read
BV9LLSV_BLiquid Line Solenoid BRead
BV2403LLSV_B2Liquid Line Solenoid B2Read
AV37OPTIONS_DL_STATCCN Loadshed SignalRead
BV25OPTIONS_DMD_SW1Demand Limit Switch 1Read
BV26OPTIONS_DMD_SW2Demand Limit Switch 2Read
AV36OPTIONS_LMT_MA4-20 mA Demand SignalRead
AV1003OPTIONS_OATOutside Air TemperatureWrite
AV33OPTIONS_RST_MA4-20 ma Reset SignalRead
AV2007OPTIONS_SPTSpaceTemperatureWrite
MV5OPTIONS2_CTRL_MODEControl MethodRead
MV3OPTIONS2_CTRLTYPEMachine Control TypeRead
AV42OPTIONS2_DELAYMinutes Off TimeWrite
AV77OPTIONS2_SEQ_TYPELoading Sequence SelectWrite
AV2925RAT2Return Air Temp AHU2Read
MV7RESETCON_CRST_TYPCooling Reset TypeRead
MV8RESETCON_DMD_CTRLDemand Limit SelectRead
AV2924SAT2Supply Air Temp AHU2Read
AV53SETPOINT_CSP1Cooling setpoint 1Write
AV54SETPOINT_CSP2Cooling setpoint 2Write
AV2926SETPOINT_CSP3Cooling setpoint 3Write
AV2927SETPOINT_CSP4Cooling setpoint 4Write
AV25SETPOINT_DMDHCONHI Cool On SetpointWrite
AV30SETPOINT_DMDLCOFFLo Cool Off SetpointWrite
AV31SETPOINT_DMDLCONLo Cool On SetpointWrite
AV76SETPOINT_SPSP_POSpace T SP Plus OffsetWrite
AV51SETPOINT_SPT_SPSpace T Cool SetpointWrite
AV55SETPOINT_SPTOSpace Temp OffsetWrite
BV10SETPOINT_SPTOSENSSpace Temp Offset EnableWrite
BV11SPTSENSSpace Temp SensorRead
AV9STAGERequested StageRead
BV2TSTAT_IN_IDFA_FSIndoor Fan Status CIRARead
BV3TSTAT_IN_IDFB_FSIndoor Fan Status CIRBRead
BV27TSTAT_IN_Y1Y1 Thermostat InputRead
BV28TSTAT_IN_Y2Y2 Thermostat InputRead
BV29TSTAT_IN_Y3Y3 Thermostat InputRead
BV30TSTAT_IN_Y4Y4 Thermostat InputRead
AV56UNIT_COOLING_RAMPCooling Ramp LoadingWrite
AV19VHPA_ACTVar Head Press % Cir ARead
AV83VHPB_ACTVar Head Press % Cir BRead
Object ID lookup: Carrier 38RC Gemini Select point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)

How many BACnet points does the Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option) have?

This list has 136 BACnet objects: 75 analog values, 56 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option) BACnet points are writable?

27 of the 136 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option) BACnet documentation?

The source is Gemini Select 38RCS025-050, 38RCD025-130 Commercial Air-Cooled Condensing Units - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix C, BACnet Option (IP and MS/TP), Network Points List) (38RC-3T), revision 2026-07, published free by Carrier at https://brandportal.carrier.com/asset/160e5c92-20ff-43ec-8e76-bbca78e4376c/38RC-3T.pdf.

What are the minimum BACnet points to integrate the Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)?

Start with BV 4 A_UNIT_CHIL_S_S (Network start/stop command); AV 2 A_UNIT_DEM_LIM (Demand limit command (%)); AV 5 A_UNIT_CTRL_PNT (Control point); BV 6 A_UNIT_EMSTOP (Emergency stop command); AV 8 A_UNIT_STAT (Control mode / unit status); AV 3 A_UNIT_CAP_T (Percent total capacity); AV 1008 A_UNIT_SUPPLY_T (Supply air temperature); MV 1 A_UNIT_ALM (Alarm state).

How do I enable BMS control of the Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)?

Set the machine control method to Network; the unit then follows CCN, BACnet (if enabled) or Modbus (if enabled) commands and ignores the remote contacts. In Local or Remote control it ignores network commands except Emergency Stop.

Can the BMS supply sensor values to the Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)?

Return air (AV 1010), supply air (AV 1008), outdoor air (AV 1003) and space temperature (AV 2007) are listed as writable, so they can be supplied from the network when the unit is configured to use them.

How do I check these points on the real Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: Gemini Select 38RCS025-050, 38RCD025-130 Commercial Air-Cooled Condensing Units - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix C, BACnet Option (IP and MS/TP), Network Points List) · 38RC-3T · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.