- AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)
Air-cooled screw chiller controller · BACnet points list
Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet points list
Updated 12 November 2026
This is the native BACnet object list from the 2019 edition of the 30XV Series B Carrier Controller manual: 559 AVs, 227 BVs and 51 Trend Logs named after their CCN table and point. Commands use separate _wr objects (start/stop, occupancy, control point, demand limit, emergency stop, pump commands) and each alarm has its own read-only BV. Many instance numbers differ from the later PIC6.1 list (Form 30XV-6T), so use the list that matches the controller software.
This page lists 837 BACnet objects for the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) — 71 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)
- Equipment
- Air-cooled screw chiller controller
- Equipment type
- Chillers
- BACnet objects
- 837 (71 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1600001
- Also known as
- 30XV, AquaForce 30XV, 30XV-3T, 30XV Series B 2019, Carrier Controller, Greenspeed, 04-53300197-01
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)
Enable BACnet (bacena), pick BACnet IP or MS/TP in the BACnet configuration menu and set the network and identifier, then put the machine under network control. Command through the _wr objects (start/stop, occupancy, control point, demand limit) and read run status, water temperatures, capacity and alarm state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 123 | GENUNIT_CHIL_S_S_wr | Network start/stop command | Write |
| BV 129 | GENUNIT_CHIL_OCC_wr | Network occupied command | Write |
| AV 557 | GENUNIT_CTRL_PNT_wr | Leaving water control point from the BMS | Write |
| AV 558 | GENUNIT_DEM_LIM_wr | Demand limit command | Write |
| AV 20 | GENUNIT_CTRL_TYP | Control type: Local, Network or Remote | Read |
| AV 21 | GENUNIT_STATUS | Running status | Read |
| AV 30 | TEMP_COOL_LWT | Leaving chilled water temperature | Read |
| AV 29 | TEMP_COOL_EWT | Entering chilled water temperature | Read |
| AV 24 | GENUNIT_CAP_T | Percent total capacity | Read |
| AV 109 | ALARMRST_ALM | Unit alarm state | Read |
Enable & remote start
Put the unit under network control (Network machine control method); start/stop and occupancy are then written to the _wr objects.
Network setup
- BACnet is enabled with the bacena parameter in the BACnet configuration menu; the data link can be BACnet IP or MS/TP.
- Defaults shown: network 1601, identifier 1600001; BACnet management device 0 = none, 1 = foreign device, 2 = BBMD.
- RS485-4 (J8) is the BMS BACnet port; J15 is an Ethernet BMS / service port.
Watch out for
- Write the _wr object, not the read copy; the read copy only reports the current value.
- Cooling setpoints (AV 550-552) and switch limit setpoints (AV 554-556) are writable directly as well.
- Instance numbers differ from the later PIC6.1 (30XV-6T) list; check the controller software before mapping.
Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | GENCONF_prio_cir | Cir Priority Sequence | Read | 0=Auto, 1=A Prio, 2=B Prio | |
| AV | 2 | GENCONF_off_on_d | Unit Off to On Delay | Read | ||
| AV | 3 | GENCONF_lim_sel | Demand Limit Type Select | Read | 0=None, 1=Switch Control, 2=4-20mA Control | |
| AV | 4 | GENCONF_nh_start | Night Mode Start Hour | Read | ||
| AV | 5 | GENCONF_nh_end | Night Mode End Hour | Read | ||
| AV | 6 | GENCONF_nh_limit | Night Capacity Limit | Read | ||
| AV | 7 | PUMPCONF_cpumpseq | Evap Pumps Sequence | Read | 0=No Pump, 1=One Pump Only, 2=Two Pumps Auto, 3=Pump#1 Manual, 4=Pump#2 Manual | |
| AV | 8 | PUMPCONF_pump_del | Pump Auto Rotation Delay | Read | ||
| AV | 9 | USERCONF_use_pass | User Password | Write | ||
| AV | 10 | RESETCFG_cr_sel | Cooling Reset Select | Read | 0=None, 1=OAT, 2=Delta T, 3=4-20mA control, 4=Space Temp | |
| AV | 11 | RESETCFG_oat_crno | OAT No Reset Value | Read | ||
| AV | 12 | RESETCFG_oat_crfu | OAT Full Reset Value | Read | ||
| AV | 13 | RESETCFG_dt_cr_no | Delta T No Reset Value | Read | ||
| AV | 14 | RESETCFG_dt_cr_fu | Delta T Full Reset Value | Read | ||
| AV | 15 | RESETCFG_v_cr_no | Current No Reset Value | Read | ||
| AV | 16 | RESETCFG_v_cr_fu | Current Full Reset Value | Read | ||
| AV | 17 | RESETCFG_spacr_no | Space T No Reset Value | Read | ||
| AV | 18 | RESETCFG_spacr_fu | Space T Full Reset Value | Read | ||
| AV | 19 | RESETCFG_cr_deg | Cooling Reset Deg. Value | Read | ||
| AVmin | 20 | GENUNIT_CTRL_TYP | Local=0 Net.=1 Remote=2 | Read | ||
| AVmin | 21 | GENUNIT_STATUS | Run Status | Read | ||
| AV | 22 | GENUNIT_min_left | Minutes Left for Start | Read | ||
| AV | 23 | GENUNIT_SP_SEL_rd | Setpoint Select, 0=Auto, 1=Spt1, 2=Spt2 | Read | ||
| AVmin | 24 | GENUNIT_CAP_T | Percent Total Capacity | Read | ||
| AV | 25 | GENUNIT_SP | Current Setpoint | Read | ||
| AV | 26 | GENUNIT_CTRL_PNT_rd | Control Point | Read | ||
| AV | 27 | GENUNIT_DEM_LIM_rd | Active Demand Limit Val | Read | ||
| AV | 28 | GENUNIT_min_lim | Demand Limit Minimum | Read | ||
| AVmin | 29 | TEMP_COOL_EWT | Evap Entering Fluid | Read | ||
| AVmin | 30 | TEMP_COOL_LWT | Evap Leaving Fluid | Read | ||
| AV | 31 | TEMP_OAT | Outdoor Air Temperature | Read | ||
| AV | 32 | TEMP_SCT_A | Saturated Cond Tmp Cir A | Read | ||
| AV | 33 | TEMP_SST_A | Saturated Suction Temp A | Read | ||
| AV | 34 | TEMP_SLT_A | Saturated Liquid Temp A | Read | ||
| AV | 35 | TEMP_SUCT_A | Compressor Suction Tmp A | Read | ||
| AV | 36 | TEMP_DGT_A | Discharge Gas Temp Cir A | Read | ||
| AV | 37 | TEMP_CP_TMP_A | Motor Temperature Cir A | Read | ||
| AV | 38 | TEMP_ECO_T_A | EXV Eco. Tmp Cir A | Read | ||
| AV | 39 | TEMP_LIQ_T_A | Liquid Temperature A | Read | ||
| AV | 40 | TEMP_SCT_B | Saturated Cond Tmp Cir B | Read | ||
| AV | 41 | TEMP_SST_B | Saturated Suction Temp B | Read | ||
| AV | 42 | TEMP_SLT_B | Saturated Liquid Temp B | Read | ||
| AV | 43 | TEMP_SUCT_B | Compressor Suction Tmp B | Read | ||
| AV | 44 | TEMP_DGT_B | Discharge Gas Temp Cir B | Read | ||
| AV | 45 | TEMP_CP_TMP_B | Motor Temperature Cir B | Read | ||
| AV | 46 | TEMP_ECO_T_B | EXV Eco. Tmp Cir B | Read | ||
| AV | 47 | TEMP_LIQ_T_B | Liquid Temperature B | Read | ||
| AV | 48 | TEMP_SPACETMP | Space Temp (Opt.) | Read | ||
| AV | 49 | TEMP_CHWSTEMP | Chill Water Temp (Opt.) | Read | ||
| AV | 50 | PRESSURE_DP_A | Discharge Pressure A | Read | ||
| AV | 51 | PRESSURE_SP_A | Main Suction Pressure A | Read | ||
| AV | 52 | PRESSURE_OP_A | Oil Pressure A | Read | ||
| AV | 53 | PRESSURE_DOP_A | Delta Oil Pressure A | Read | ||
| AV | 54 | PRESSURE_ECO_P_A | Economizer Pressure A | Read | ||
| AV | 55 | PRESSURE_LIQ_P_A | Liquid Pressure A | Read | ||
| AV | 56 | PRESSURE_DP_B | Discharge Pressure B | Read | ||
| AV | 57 | PRESSURE_SP_B | Main Suction Pressure B | Read | ||
| AV | 58 | PRESSURE_OP_B | Oil Pressure B | Read | ||
| AV | 59 | PRESSURE_DOP_B | Delta Oil Pressure B | Read | ||
| AV | 60 | PRESSURE_ECO_P_B | Economizer Pressure B | Read | ||
| AV | 61 | PRESSURE_LIQ_P_B | Liquid Pressure B | Read | ||
| AV | 62 | INPUTS_SP_RESET | Remote Reset Setpoint | Read | ||
| AV | 63 | INPUTS_LIM_ANAL | Remote Dem. Limit | Read | ||
| AV | 64 | INPUTS_leak_v | Leakage Detector 1 | Read | ||
| AV | 65 | INPUTS_leak_2_v | Leakage Detector 2 | Read | ||
| AV | 66 | OUTPUTS_CAPT010A | Capacity Signal Cir A | Read | ||
| AV | 67 | OUTPUTS_VFAN_A | VariFan Speed A | Read | ||
| AV | 68 | OUTPUTS_CAPT010B | Capacity Signal Cir B | Read | ||
| AV | 69 | OUTPUTS_VFAN_B | VariFan Speed B | Read | ||
| AV | 70 | OUTPUTS_CAPT_010 | Chiller Capacity Signal | Read | ||
| AV | 71 | RUNTIME_HR_MACH | Machine Operating Hours | Read | ||
| AV | 72 | RUNTIME_st_mach | Machine Starts | Read | ||
| AV | 73 | RUNTIME_HR_CP_A | Compressor A Hours | Read | ||
| AV | 74 | RUNTIME_st_cp_a | Compressor A Starts | Read | ||
| AV | 75 | RUNTIME_HR_CP_B | Compressor B Hours | Read | ||
| AV | 76 | RUNTIME_st_cp_b | Compressor B Starts | Read | ||
| AV | 77 | RUNTIME_hr_cpum1 | Evap Pump #1 Hours | Read | ||
| AV | 78 | RUNTIME_hr_cpum2 | Evap Pump #2 Hours | Read | ||
| AV | 79 | RUNTIME_VIctA | VI Cycle Count A | Read | ||
| AV | 80 | RUNTIME_VIctB | VI Cycle Count B | Read | ||
| AV | 81 | RUNTIME_hrfana01 | Circuit A Fan #1 Hours | Read | ||
| AV | 82 | RUNTIME_hrfana02 | Circuit A Fan #2 Hours | Read | ||
| AV | 83 | RUNTIME_hrfana03 | Circuit A Fan #3 Hours | Read | ||
| AV | 84 | RUNTIME_hrfana04 | Circuit A Fan #4 Hours | Read | ||
| AV | 85 | RUNTIME_hrfana05 | Circuit A Fan #5 Hours | Read | ||
| AV | 86 | RUNTIME_hrfana06 | Circuit A Fan #6 Hours | Read | ||
| AV | 87 | RUNTIME_hrfana07 | Circuit A Fan #7 Hours | Read | ||
| AV | 88 | RUNTIME_hrfana08 | Circuit A Fan #8 Hours | Read | ||
| AV | 89 | RUNTIME_hrfana09 | Circuit A Fan #9 Hours | Read | ||
| AV | 90 | RUNTIME_hrfana10 | Circuit A Fan #10 Hours | Read | ||
| AV | 91 | RUNTIME_hrfana11 | Circuit A Fan #11 Hours | Read | ||
| AV | 92 | RUNTIME_hrfana12 | Circuit A Fan #12 Hours | Read | ||
| AV | 93 | RUNTIME_hrfana13 | Circuit A Fan #13 Hours | Read | ||
| AV | 94 | RUNTIME_hrfana14 | Circuit A Fan #14 Hours | Read | ||
| AV | 95 | RUNTIME_hrfanb01 | Circuit B Fan #1 Hours | Read | ||
| AV | 96 | RUNTIME_hrfanb02 | Circuit B Fan #2 Hours | Read | ||
| AV | 97 | RUNTIME_hrfanb03 | Circuit B Fan #3 Hours | Read | ||
| AV | 98 | RUNTIME_hrfanb04 | Circuit B Fan #4 Hours | Read | ||
| AV | 99 | RUNTIME_hrfanb05 | Circuit B Fan #5 Hours | Read | ||
| AV | 100 | RUNTIME_hrfanb06 | Circuit B Fan #6 Hours | Read | ||
| AV | 101 | RUNTIME_hrfanb07 | Circuit B Fan #7 Hours | Read | ||
| AV | 102 | RUNTIME_hrfanb08 | Circuit B Fan #8 Hours | Read | ||
| AV | 103 | RUNTIME_hrfanb09 | Circuit B Fan #9 Hours | Read | ||
| AV | 104 | RUNTIME_hrfanb10 | Circuit B Fan #10 Hours | Read | ||
| AV | 105 | RUNTIME_hrfanb11 | Circuit B Fan #11 Hours | Read | ||
| AV | 106 | RUNTIME_hrfanb12 | Circuit B Fan #12 Hours | Read | ||
| AV | 107 | RUNTIME_hrfanb13 | Circuit B Fan #13 Hours | Read | ||
| AV | 108 | RUNTIME_hrfanb14 | Circuit B Fan #14 Hours | Read | ||
| AVmin | 109 | ALARMRST_ALM | Alarm State | Read | ||
| AV | 110 | ALARMRST_alarm_1 | Jbus Current Alarm 1 | Read | ||
| AV | 111 | ALARMRST_alarm_2 | Jbus Current Alarm 2 | Read | ||
| AV | 112 | ALARMRST_alarm_3 | Jbus Current Alarm 3 | Read | ||
| AV | 113 | ALARMRST_alarm_4 | Jbus Current Alarm 4 | Read | ||
| AV | 114 | ALARMRST_alarm_5 | Jbus Current Alarm 5 | Read | ||
| AV | 115 | VLT_DRV_drv_pwra | Cir A Drive Power | Read | ||
| AV | 116 | VLT_DRV_drv_Ia | Cir A Drive Amps | Read | ||
| AV | 117 | VLT_DRV_drv_Va | Cir A Drive Voltage | Read | ||
| AV | 118 | VLT_DRV_drv_Sa | Cir A Drive Speed | Read | ||
| AV | 119 | VLT_DRV_drv_Fa | Cir A Drive Frequency | Read | ||
| AV | 120 | VLT_DRV_drv_Ta | Cir A Drive Torque | Read | ||
| AV | 121 | VLT_DRV_drv_DCVa | Cir A Drive DC Link Volt | Read | ||
| AV | 122 | VLT_DRV_drv_HSTa | Cir A Drive Heat Sink T | Read | ||
| AV | 123 | VLT_DRV_drv_CCTa | Cir A Drive Ctrl Card T | Read | ||
| AV | 124 | VLT_DRV_drv_HTRa | Cir A Drive Heater | Read | ||
| AV | 125 | VLT_DRV_drv_pwrb | Cir B Drive Power | Read | ||
| AV | 126 | VLT_DRV_drv_Ib | Cir B Drive Amps | Read | ||
| AV | 127 | VLT_DRV_drv_Vb | Cir B Drive Voltage | Read | ||
| AV | 128 | VLT_DRV_drv_Sb | Cir B Drive Speed | Read | ||
| AV | 129 | VLT_DRV_drv_Fb | Cir B Drive Frequency | Read | ||
| AV | 130 | VLT_DRV_drv_Tb | Cir B Drive Torque | Read | ||
| AV | 131 | VLT_DRV_drv_DCVb | Cir B Drive DC Link Volt | Read | ||
| AV | 132 | VLT_DRV_drv_HSTb | Cir B Drive Heat Sink T | Read | ||
| AV | 133 | VLT_DRV_drv_CCTb | Cir B Drive Ctrl Card T | Read | ||
| AV | 134 | VLT_DRV_drv_HTRb | Cir B Drive Heater | Read | ||
| AV | 135 | VLT_DRV_drv_pwr | Total Comp Drive Power | Read | ||
| AV | 136 | LAST_POR_date_on1 | Power On 1 :day-mon-year | Read | ||
| AV | 137 | LAST_POR_time_on1 | Power On 1 :hour-minute | Read | ||
| AV | 138 | LAST_POR_date_of1 | PowerDown 1:day-mon-year | Read | ||
| AV | 139 | LAST_POR_time_of1 | PowerDown 1:hour-minute | Read | ||
| AV | 140 | LAST_POR_date_on2 | Power On 2 :day-mon-year | Read | ||
| AV | 141 | LAST_POR_time_on2 | Power On 2 :hour-minute | Read | ||
| AV | 142 | LAST_POR_date_of2 | PowerDown 2:day-mon-year | Read | ||
| AV | 143 | LAST_POR_time_of2 | PowerDown 2:hour-minute | Read | ||
| AV | 144 | LAST_POR_date_on3 | Power On 3 :day-mon-year | Read | ||
| AV | 145 | LAST_POR_time_on3 | Power On 3 :hour-minute | Read | ||
| AV | 146 | LAST_POR_date_of3 | PowerDown 3:day-mon-year | Read | ||
| AV | 147 | LAST_POR_time_of3 | PowerDown 3:hour-minute | Read | ||
| AV | 148 | LAST_POR_date_on4 | Power On 4 :day-mon-year | Read | ||
| AV | 149 | LAST_POR_time_on4 | Power On 4 :hour-minute | Read | ||
| AV | 150 | LAST_POR_date_of4 | PowerDown 4:day-mon-year | Read | ||
| AV | 151 | LAST_POR_time_of4 | PowerDown 4:hour-minute | Read | ||
| AV | 152 | LAST_POR_date_on5 | Power On 5 :day-mon-year | Read | ||
| AV | 153 | LAST_POR_time_on5 | Power On 5 :hour-minute | Read | ||
| AV | 154 | LAST_POR_date_of5 | PowerDown 5:day-mon-year | Read | ||
| AV | 155 | LAST_POR_time_of5 | PowerDown 5:hour-minute | Read | ||
| AV | 156 | EXV_CTRL_ov_exv_a | EXV Override Circuit A | Read | ||
| AV | 157 | EXV_CTRL_EXV_A | EXV Position Circuit A | Read | ||
| AV | 158 | EXV_CTRL_DSH_A | Discharge Superheat A | Read | ||
| AV | 159 | EXV_CTRL_dsh_spa | Dis. Superheat Setpnt A | Read | ||
| AV | 160 | EXV_CTRL_SH_A | Suction Superheat A | Read | ||
| AV | 161 | EXV_CTRL_sh_sp_a | Suct. Superheat Setpnt A | Read | ||
| AV | 162 | EXV_CTRL_pinch_a | Evap ExchangeDT Cir A | Read | ||
| AV | 163 | EXV_CTRL_subcoola | Subcooling Circuit A | Read | ||
| AV | 164 | EXV_CTRL_subc_spa | Subcooling Setpoint A | Read | ||
| AV | 165 | EXV_CTRL_exv_sta | EXV State A | Read | ||
| AV | 166 | EXV_CTRL_exv_lsta | EXV Previous State A | Read | ||
| AV | 167 | EXV_CTRL_exvwposa | EXV Wished Position A | Read | ||
| AV | 168 | EXV_CTRL_ov_exv_b | EXV Override Circuit B | Read | ||
| AV | 169 | EXV_CTRL_EXV_B | EXV Position Circuit B | Read | ||
| AV | 170 | EXV_CTRL_DSH_B | Discharge Superheat B | Read | ||
| AV | 171 | EXV_CTRL_dsh_spb | Dis. Superheat Setpnt B | Read | ||
| AV | 172 | EXV_CTRL_SH_B | Suction Superheat B | Read | ||
| AV | 173 | EXV_CTRL_sh_sp_b | Suct. Superheat Setpnt B | Read | ||
| AV | 174 | EXV_CTRL_pinch_b | Evap ExchangeDT Cir B | Read | ||
| AV | 175 | EXV_CTRL_subcoolb | Subcooling Circuit B | Read | ||
| AV | 176 | EXV_CTRL_subc_spb | Subcooling Setpoint B | Read | ||
| AV | 177 | EXV_CTRL_exv_stb | EXV State B | Read | ||
| AV | 178 | EXV_CTRL_exv_lstb | EXV Previous State B | Read | ||
| AV | 179 | EXV_CTRL_exvwposb | EXV Wished Position B | Read | ||
| AV | 180 | M_MSTSLV_slv_stat | Slave Chiller State | Read | ||
| AV | 181 | M_MSTSLV_slv_capt | Slave Chiller Total Cap | Read | ||
| AV | 182 | M_MSTSLV_l_strt_d | Lag Start Delay | Read | ||
| AV | 183 | M_MSTSLV_ll_hr_d | Lead/lag Hours Delta | Read | ||
| AV | 184 | M_MSTSLV_ms_error | Master/Slave Error | Read | ||
| AV | 185 | M_MSTSLV_lagstat | Slave lagstat | Read | ||
| AV | 186 | M_MSTSLV_slav_hr | Slave Operating Hours | Read | ||
| AV | 187 | M_MSTSLV_slav_ewt | Slave Evap Ent. Fluid | Read | ||
| AV | 188 | M_MSTSLV_slav_lwt | Slave Evap Leav. Fluid | Read | ||
| AV | 189 | CAPACTRL_ctrl_wt | Controled Water Temp | Read | ||
| AV | 190 | CAPACTRL_cwt_rate | Ctrl Water Temp, Deg/Min | Read | ||
| AV | 191 | CAPACTRL_cap_lim | Current Capacity Limit | Read | ||
| AV | 192 | CAPACTRL_drvcmda | Wished Comp. Frequency A | Read | ||
| AV | 193 | CAPACTRL_capmoda | Capa Ctrl Stat Nb A | Read | ||
| AV | 194 | CAPACTRL_lcapmoda | Last Capa Ctrl Stat Nb A | Read | ||
| AV | 195 | CAPACTRL_overrida | Override Capacity Nb A | Read | ||
| AV | 196 | CAPACTRL_cap_pc_a | Estimated Capacity A | Read | ||
| AV | 197 | CAPACTRL_drvcmdb | Wished Comp. Frequency B | Read | ||
| AV | 198 | CAPACTRL_capmodb | Capacity Ctrl Stat Nb B | Read | ||
| AV | 199 | CAPACTRL_lcapmodb | Last Capa Ctrl Stat Nb B | Read | ||
| AV | 200 | CAPACTRL_overridb | Override Capacity Nb B | Read | ||
| AV | 201 | CAPACTRL_cap_pc_b | Estimated Capacity B | Read | ||
| AV | 202 | CAPACTRL_cMaxFrqA | Max Comp. Frequency A | Read | ||
| AV | 203 | CAPACTRL_cMaxFrqB | Max Comp. Frequency B | Read | ||
| AV | 204 | CAPACTRL_viCmdA | Comp. VI Cmd A | Read | ||
| AV | 205 | CAPACTRL_viCmdB | Comp. VI Cmd B | Read | ||
| AV | 206 | CAPACTRL_reset | Reset Amount | Read | ||
| AV | 207 | CAPACTRL_CirRunNb | Circuit Running Number | Read | ||
| AV | 208 | CAPACTRL_StatCirA | State of Circuit A | Read | ||
| AV | 209 | CAPACTRL_StatCirB | State of Circuit B | Read | ||
| AV | 210 | CAPACTRL_DualMast | Dual Circuit Master | Read | ||
| AV | 211 | CAPACTRL_xSpdHigh | Transfer Spd, add cir | Read | ||
| AV | 212 | CAPACTRL_xSpdLow | Transfer Spd, remove cir | Read | ||
| AV | 213 | LIMITS_dshacta | EXV_dsh_act A | Read | ||
| AV | 214 | LIMITS_dshstpa | EXV_dsh_stp A | Read | ||
| AV | 215 | LIMITS_elspacta | EXV_lsp_act A | Read | ||
| AV | 216 | LIMITS_elspstpa | EXV_lsp_stp A | Read | ||
| AV | 217 | LIMITS_chdpacta | ENV comp high dp act A | Read | ||
| AV | 218 | LIMITS_chdpstpa | ENV comp high dp stp A | Read | ||
| AV | 219 | LIMITS_fhdpacta | ENV fan high dp act A | Read | ||
| AV | 220 | LIMITS_fhdpstpa | ENV fan high dp stp A | Read | ||
| AV | 221 | LIMITS_ldpacta | ENV low dp act A | Read | ||
| AV | 222 | LIMITS_ldpstpa | ENV low dp stp A | Read | ||
| AV | 223 | LIMITS_hspacta | ENV high sp act A | Read | ||
| AV | 224 | LIMITS_hspstpa | ENV high sp stp A | Read | ||
| AV | 225 | LIMITS_lspacta | ENV low sp act A | Read | ||
| AV | 226 | LIMITS_lspstpa | ENV low sp stp A | Read | ||
| AV | 227 | LIMITS_lspdcpa | ENV low sp delta A | Read | ||
| AV | 228 | LIMITS_dgtacta | dgt act A | Read | ||
| AV | 229 | LIMITS_dgtstpa | dgt stp A | Read | ||
| AV | 230 | LIMITS_dshactb | EXV_dsh_act B | Read | ||
| AV | 231 | LIMITS_dshstpb | EXV_dsh_stp B | Read | ||
| AV | 232 | LIMITS_elspactb | EXV_lsp_act B | Read | ||
| AV | 233 | LIMITS_elspstpb | EXV_lsp_stp B | Read | ||
| AV | 234 | LIMITS_chdpactb | ENV comp high dp act B | Read | ||
| AV | 235 | LIMITS_chdpstpb | ENV comp high dp stp B | Read | ||
| AV | 236 | LIMITS_fhdpactb | ENV fan high dp act B | Read | ||
| AV | 237 | LIMITS_fhdpstpb | ENV fan high dp stp B | Read | ||
| AV | 238 | LIMITS_ldpactb | ENV low dp act B | Read | ||
| AV | 239 | LIMITS_ldpstpb | ENV low dp stp B | Read | ||
| AV | 240 | LIMITS_hspactb | ENV high sp act B | Read | ||
| AV | 241 | LIMITS_hspstpb | ENV high sp stp B | Read | ||
| AV | 242 | LIMITS_lspactb | ENV low sp act B | Read | ||
| AV | 243 | LIMITS_lspstpb | ENV low sp stp B | Read | ||
| AV | 244 | LIMITS_lspdcpb | ENV low sp delta B | Read | ||
| AV | 245 | LIMITS_dgtactb | dgt_act B | Read | ||
| AV | 246 | LIMITS_dgtstpb | dgt_stp B | Read | ||
| AV | 247 | ECO_CTRL_eco_a | EXV Eco Position Cir A | Read | ||
| AV | 248 | ECO_CTRL_eco_b | EXV Eco Position Cir B | Read | ||
| AV | 249 | FAN_CTRL_fan_f_a | Fan Freq Cir A | Read | ||
| AV | 250 | FAN_CTRL_fan_sta | Fan State A | Read | ||
| AV | 251 | FAN_CTRL_fan_lsta | Fan Previous State A | Read | ||
| AV | 252 | FAN_CTRL_wfan_f_a | Fan Wished Freq A | Read | ||
| AV | 253 | FAN_CTRL_fan_moda | Fan Mode A | Read | ||
| AV | 254 | FAN_CTRL_fan_txta | Fan Mode Text A | Read | ||
| AV | 255 | FAN_CTRL_ftotpowa | Fan Tot Pwr Filtered A | Read | ||
| AV | 256 | FAN_CTRL_fcont_a | Fan Contactors On A | Read | ||
| AV | 257 | FAN_CTRL_fan_f_b | Fan Freq Cir B | Read | ||
| AV | 258 | FAN_CTRL_fan_stb | Fan State B | Read | ||
| AV | 259 | FAN_CTRL_fan_lstb | Fan Previous State B | Read | ||
| AV | 260 | FAN_CTRL_wfan_f_b | Fan Wished Freq B | Read | ||
| AV | 261 | FAN_CTRL_fan_modb | Fan Mode B | Read | ||
| AV | 262 | FAN_CTRL_fan_txtb | Fan Mode Text B | Read | ||
| AV | 263 | FAN_CTRL_ftotpowb | Fan Tot Pwr Filtered B | Read | ||
| AV | 264 | FAN_CTRL_fcont_b | Fan Contactors On B | Read | ||
| AV | 265 | FAN_DRV_fd_pwra1 | Fan Drive Power A1 | Read | ||
| AV | 266 | FAN_DRV_fd_Ia1 | Fan Drive Amps A1 | Read | ||
| AV | 267 | FAN_DRV_fd_Va1 | Fan Drive Voltage A1 | Read | ||
| AV | 268 | FAN_DRV_fd_Sa1 | Fan Drive Speed A1 | Read | ||
| AV | 269 | FAN_DRV_fd_Fa1 | Fan Drive Frequency A1 | Read | ||
| AV | 270 | FAN_DRV_fd_Ta1 | Fan Drive Torque A1 | Read | ||
| AV | 271 | FAN_DRV_fd_DCVa1 | Fan Drv DC Link Volt A1 | Read | ||
| AV | 272 | FAN_DRV_fd_HSTa1 | Fan Drive Heat Sink T A1 | Read | ||
| AV | 273 | FAN_DRV_fd_CCTa1 | Fan Drive Ctrl Card T A1 | Read | ||
| AV | 274 | FAN_DRV_fd_pwra2 | Fan Drive Power A2 | Read | ||
| AV | 275 | FAN_DRV_fd_Ia2 | Fan Drive Amps A2 | Read | ||
| AV | 276 | FAN_DRV_fd_Va2 | Fan Drive Voltage A2 | Read | ||
| AV | 277 | FAN_DRV_fd_Sa2 | Fan Drive Speed A2 | Read | ||
| AV | 278 | FAN_DRV_fd_Fa2 | Fan Drive Frequency A2 | Read | ||
| AV | 279 | FAN_DRV_fd_Ta2 | Fan Drive Torque A2 | Read | ||
| AV | 280 | FAN_DRV_fd_DCVa2 | Fan Drv DC Link Volt A2 | Read | ||
| AV | 281 | FAN_DRV_fd_HSTa2 | Fan Drive Heat Sink T A2 | Read | ||
| AV | 282 | FAN_DRV_fd_CCTa2 | Fan Drive Ctrl Card T A2 | Read | ||
| AV | 283 | FAN_DRV_fd_pwra3 | Fan Drive Power A3 | Read | ||
| AV | 284 | FAN_DRV_fd_Ia3 | Fan Drive Amps A3 | Read | ||
| AV | 285 | FAN_DRV_fd_Va3 | Fan Drive Voltage A3 | Read | ||
| AV | 286 | FAN_DRV_fd_Sa3 | Fan Drive Speed A3 | Read | ||
| AV | 287 | FAN_DRV_fd_Fa3 | Fan Drive Frequency A3 | Read | ||
| AV | 288 | FAN_DRV_fd_Ta3 | Fan Drive Torque A3 | Read | ||
| AV | 289 | FAN_DRV_fd_DCVa3 | Fan Drv DC Link Volt A3 | Read | ||
| AV | 290 | FAN_DRV_fd_HSTa3 | Fan Drive Heat Sink T A3 | Read | ||
| AV | 291 | FAN_DRV_fd_CCTa3 | Fan Drive Ctrl Card T A3 | Read | ||
| AV | 292 | FAN_DRV_fd_pwrb1 | Fan Drive Power B1 | Read | ||
| AV | 293 | FAN_DRV_fd_Ib1 | Fan Drive Amps B1 | Read | ||
| AV | 294 | FAN_DRV_fd_Vb1 | Fan Drive Voltage B1 | Read | ||
| AV | 295 | FAN_DRV_fd_Sb1 | Fan Drive Speed B1 | Read | ||
| AV | 296 | FAN_DRV_fd_Fb1 | Fan Drive Frequency B1 | Read | ||
| AV | 297 | FAN_DRV_fd_Tb1 | Fan Drive Torque B1 | Read | ||
| AV | 298 | FAN_DRV_fd_DCVb1 | Fan Drv DC Link Volt B1 | Read | ||
| AV | 299 | FAN_DRV_fd_HSTb1 | Fan Drive Heat Sink T B1 | Read | ||
| AV | 300 | FAN_DRV_fd_CCTb1 | Fan Drive Ctrl Card T B1 | Read | ||
| AV | 301 | FAN_DRV_fd_pwrb2 | Fan Drive Power B2 | Read | ||
| AV | 302 | FAN_DRV_fd_Ib2 | Fan Drive Amps B2 | Read | ||
| AV | 303 | FAN_DRV_fd_Vb2 | Fan Drive Voltage B2 | Read | ||
| AV | 304 | FAN_DRV_fd_Sb2 | Fan Drive Speed B2 | Read | ||
| AV | 305 | FAN_DRV_fd_Fb2 | Fan Drive Frequency B2 | Read | ||
| AV | 306 | FAN_DRV_fd_Tb2 | Fan Drive Torque B2 | Read | ||
| AV | 307 | FAN_DRV_fd_DCVb2 | Fan Drv DC Link Volt B2 | Read | ||
| AV | 308 | FAN_DRV_fd_HSTb2 | Fan Drive Heat Sink T B2 | Read | ||
| AV | 309 | FAN_DRV_fd_CCTb2 | Fan Drive Ctrl Card T B2 | Read | ||
| AV | 310 | FAN_DRV_fd_pwrb3 | Fan Drive Power B3 | Read | ||
| AV | 311 | FAN_DRV_fd_Ib3 | Fan Drive Amps B3 | Read | ||
| AV | 312 | FAN_DRV_fd_Vb3 | Fan Drive Voltage B3 | Read | ||
| AV | 313 | FAN_DRV_fd_Sb3 | Fan Drive Speed B3 | Read | ||
| AV | 314 | FAN_DRV_fd_Fb3 | Fan Drive Frequency B3 | Read | ||
| AV | 315 | FAN_DRV_fd_Tb3 | Fan Drive Torque B3 | Read | ||
| AV | 316 | FAN_DRV_fd_DCVb3 | Fan Drv DC Link Volt B3 | Read | ||
| AV | 317 | FAN_DRV_fd_HSTb3 | Fan Drive Heat Sink T B3 | Read | ||
| AV | 318 | FAN_DRV_fd_CCTb3 | Fan Drive Ctrl Card T B3 | Read | ||
| AV | 319 | FAN_DRV_fd_pwr | Total Fan Drive Power | Read | ||
| AV | 320 | FACTORY_unitsize | Unit Capacity | Read | ||
| AV | 321 | FACTORY_voltage | Power Supply Voltage | Read | ||
| AV | 322 | FACTORY_mfg_tier | Tier 0=STD, 1=MID, 2=HI | Read | ||
| AV | 323 | FACTORY_cpass_nb | Evap Pass Number | Read | ||
| AV | 324 | FACTORY_fac_pass | Factory Password | Read | ||
| AV | 325 | FACTORY_fMaxOvrA | Max Frequency Override A | Read | ||
| AV | 326 | FACTORY_fMaxOvrB | Max Frequency Override B | Read | ||
| AV | 327 | FACTORY_fan_fact | Fan Freq Factor(0.7-1.1) | Read | ||
| AV | 328 | FACTORY_fMinOvr | Min Frequency Override | Read | ||
| AV | 329 | FACTORY_lastspda | Low Amb. Start Spd A | Read | ||
| AV | 330 | FACTORY_lastspdb | Low Amb. Start Spd B | Read | ||
| AV | 331 | FACTORY2_exvmax_a | EXV A Maximum Steps Numb | Read | ||
| AV | 332 | FACTORY2_exvmax_b | EXV B Maximum Steps Numb | Read | ||
| AV | 333 | FACTORY2_eco_cnfa | Economizer A Steps Numb | Read | ||
| AV | 334 | FACTORY2_eco_cnfb | Economizer B Steps Numb | Read | ||
| AV | 335 | FACTORY2_vfd_cmp | Nb VFD Compressor | Read | ||
| AV | 336 | FACTORY2_vfd_fana | Nb Fan Drive Cir A | Read | ||
| AV | 337 | FACTORY2_vfd_fanb | Nb Fan Drive Cir B | Read | ||
| AV | 338 | SERVICE1_flui_typ | Evaporator Fluid Type | Read | 1=Water, 2=Med Brine, 3=Low Brine | |
| AV | 339 | SERVICE1_freezesp | Brine Freeze Setpoint | Read | ||
| AV | 340 | SERVICE1_mini_lwt | Brine Minimum Fluid Temp | Read | ||
| AV | 341 | SERVICE1_fastcapr | Fast Capacity Recovery | Read | ||
| AV | 342 | SERVICE1_ewt_cirA | EWT Probe on Cir A Side | Read | ||
| AV | 343 | SERVICE1_leak_thr | Leakage Charge Threshold | Read | ||
| AV | 344 | SERVICE1_leak_tmr | Leakage Charge Timer | Read | ||
| AV | 345 | SERVICE1_heatersp | Evap Heater Delta Spt | Read | ||
| AV | 346 | SERVICE1_freez_ov | Freeze Override Offset | Read | ||
| AV | 347 | SERVICE1_ViPwrChk | VI Self-Test Threshold | Write | ||
| AV | 348 | SERVICE1_odtrspd | Oil Delta Trigger Speed | Read | ||
| AV | 349 | SERVICE1_otrigtim | Oil Trigger Time | Read | ||
| AV | 350 | SERVICE1_odrecspd | Oil Delta Recover Speed | Read | ||
| AV | 351 | SERVICE1_orectim | Oil Recover Time | Read | ||
| AV | 352 | SERVICE1_wateesys | Water Temp Hysteresis | Read | ||
| AV | 353 | SERVICE1_vistrtdt | High VI Time at Start | Read | ||
| AV | 354 | SERVICE1_vistrten | Enable High VI at Start | Read | ||
| AV | 355 | SERVICE1_apr_en | Approach Ctrl at Start?? | Read | ||
| AV | 356 | UPDTHOUR_hr_mach | Machine Operating Hours | Read | ||
| AV | 357 | UPDTHOUR_st_mach | Machine Starts Number | Read | ||
| AV | 358 | UPDTHOUR_hr_cp_a | Compressor A Hours | Read | ||
| AV | 359 | UPDTHOUR_st_cp_a | Compressor A Starts | Read | ||
| AV | 360 | UPDTHOUR_hr_cp_b | Compressor B Hours | Read | ||
| AV | 361 | UPDTHOUR_st_cp_b | Compressor B Starts | Read | ||
| AV | 362 | UPDTHOUR_hr_cpum1 | Evap Pump #1 Hours | Read | ||
| AV | 363 | UPDTHOUR_hr_cpum2 | Evap Pump #2 Hours | Read | ||
| AV | 364 | UPDTHOUR_VIctA | VI Cycle Count A | Read | ||
| AV | 365 | UPDTHOUR_VIctB | VI Cycle Count B | Read | ||
| AV | 366 | UPDTHOUR_hrfana01 | Circuit A Fan #1 Hours | Read | ||
| AV | 367 | UPDTHOUR_hrfana02 | Circuit A Fan #2 Hours | Read | ||
| AV | 368 | UPDTHOUR_hrfana03 | Circuit A Fan #3 Hours | Read | ||
| AV | 369 | UPDTHOUR_hrfana04 | Circuit A Fan #4 Hours | Read | ||
| AV | 370 | UPDTHOUR_hrfana05 | Circuit A Fan #5 Hours | Read | ||
| AV | 371 | UPDTHOUR_hrfana06 | Circuit A Fan #6 Hours | Read | ||
| AV | 372 | UPDTHOUR_hrfana07 | Circuit A Fan #7 Hours | Read | ||
| AV | 373 | UPDTHOUR_hrfana08 | Circuit A Fan #8 Hours | Read | ||
| AV | 374 | UPDTHOUR_hrfana09 | Circuit A Fan #9 Hours | Read | ||
| AV | 375 | UPDTHOUR_hrfana10 | Circuit A Fan #10 Hours | Read | ||
| AV | 376 | UPDTHOUR_hrfana11 | Circuit A Fan #11 Hours | Read | ||
| AV | 377 | UPDTHOUR_hrfana12 | Circuit A Fan #12 Hours | Read | ||
| AV | 378 | UPDTHOUR_hrfana13 | Circuit A Fan #13 Hours | Read | ||
| AV | 379 | UPDTHOUR_hrfana14 | Circuit A Fan #14 Hours | Read | ||
| AV | 380 | UPDTHOUR_hrfanb01 | Circuit B Fan #1 Hours | Read | ||
| AV | 381 | UPDTHOUR_hrfanb02 | Circuit B Fan #2 Hours | Read | ||
| AV | 382 | UPDTHOUR_hrfanb03 | Circuit B Fan #3 Hours | Read | ||
| AV | 383 | UPDTHOUR_hrfanb04 | Circuit B Fan #4 Hours | Read | ||
| AV | 384 | UPDTHOUR_hrfanb05 | Circuit B Fan #5 Hours | Read | ||
| AV | 385 | UPDTHOUR_hrfanb06 | Circuit B Fan #6 Hours | Read | ||
| AV | 386 | UPDTHOUR_hrfanb07 | Circuit B Fan #7 Hours | Read | ||
| AV | 387 | UPDTHOUR_hrfanb08 | Circuit B Fan #8 Hours | Read | ||
| AV | 388 | UPDTHOUR_hrfanb09 | Circuit B Fan #9 Hours | Read | ||
| AV | 389 | UPDTHOUR_hrfanb10 | Circuit B Fan #10 Hours | Read | ||
| AV | 390 | UPDTHOUR_hrfanb11 | Circuit B Fan #11 Hours | Read | ||
| AV | 391 | UPDTHOUR_hrfanb12 | Circuit B Fan #12 Hours | Read | ||
| AV | 392 | UPDTHOUR_hrfanb13 | Circuit B Fan #13 Hours | Read | ||
| AV | 393 | UPDTHOUR_hrfanb14 | Circuit B Fan #14 Hours | Read | ||
| AV | 394 | MST_SLV_ms_sel | Master/Slave Select | Read | 0=Disable, 1=Master, 2=Slave | |
| AV | 395 | MST_SLV_ms_ctrl | Master Control Type | Read | 1=Local Control, 2=Remote Control, 3=CCN Control | |
| AV | 396 | MST_SLV_slv_addr | Slave Address | Read | ||
| AV | 397 | MST_SLV_lead_sel | Lead Lag Select | Read | 0=Always Lead, 1=Lag Once Failed Only, 2=Lead/Lag Runtime Sel | |
| AV | 398 | MST_SLV_ll_bal_d | Lead/Lag Balance Delta | Read | ||
| AV | 399 | MST_SLV_lstr_tim | Lead/Lag Start Timer | Read | ||
| AV | 400 | MST_SLV_lead_pul | Lead Pulldown Time | Read | ||
| AV | 401 | MST_SLV_start_dt | Start If Error Higher | Read | ||
| AV | 402 | MST_SLV_lag_mini | Lag Minimum Running Time | Read | ||
| AV | 403 | MST_SLV_lag_pump | Lag Unit Pump Control | Read | 0=Stop if Unit Stops, 1=Run if Unit Stops | |
| AV | 404 | CMP_PI_wt_kp_a | Water Temp PI, Kp, Cir A | Read | ||
| AV | 405 | CMP_PI_wt_ti_a | Water Temp PI, Ti Cir A | Read | ||
| AV | 406 | CMP_PI_wt_ni_a | Water Temp PI, NI Cir A | Read | ||
| AV | 407 | CMP_PI_dgt_kp_a | DGT PI Kp, Cir A | Read | ||
| AV | 408 | CMP_PI_dgt_ti_a | DGT PI, Ti Cir A | Read | ||
| AV | 409 | CMP_PI_dgt_ni_a | DGT PI, NI Cir A | Read | ||
| AV | 410 | CMP_PI_cpt_kp_a | Comp Temp PI, Kp Cir A | Read | ||
| AV | 411 | CMP_PI_cpt_ti_a | Comp Temp PI, Ti Cir A | Read | ||
| AV | 412 | CMP_PI_cpt_ni_a | Comp Temp PI, NI Cir A | Read | ||
| AV | 413 | CMP_PI_dp_kp_a | Disch Press PI, Kp Cir A | Read | ||
| AV | 414 | CMP_PI_dp_ti_a | Disch Press PI, Ti Cir A | Read | ||
| AV | 415 | CMP_PI_dp_ni_a | Disch Press PI, NI Cir A | Read | ||
| AV | 416 | CMP_PI_lsp_kp_a | Low SP PI, Kp Cir A | Read | ||
| AV | 417 | CMP_PI_lsp_ti_a | Low SP PI, Ti Cir A | Read | ||
| AV | 418 | CMP_PI_lsp_ni_a | Low SP PI, NI Cir A | Read | ||
| AV | 419 | CMP_PI_wt_kp_b | Water Temp PI, Kp, Cir B | Read | ||
| AV | 420 | CMP_PI_wt_ti_b | Water Temp PI, Ti Cir B | Read | ||
| AV | 421 | CMP_PI_wt_ni_b | Water Temp PI, NI Cir B | Read | ||
| AV | 422 | CMP_PI_dgt_kp_b | DGT PI Kp, Cir B | Read | ||
| AV | 423 | CMP_PI_dgt_ti_b | DGT PI, Ti Cir B | Read | ||
| AV | 424 | CMP_PI_dgt_ni_b | DGT PI, NI Cir B | Read | ||
| AV | 425 | CMP_PI_cpt_kp_b | Comp Temp PI, Kp Cir B | Read | ||
| AV | 426 | CMP_PI_cpt_ti_b | Comp Temp PI, Ti Cir B | Read | ||
| AV | 427 | CMP_PI_cpt_ni_b | Comp Temp PI, NI Cir B | Read | ||
| AV | 428 | CMP_PI_dp_kp_b | Disch Press PI, Kp Cir B | Read | ||
| AV | 429 | CMP_PI_dp_ti_b | Disch Press PI, Ti Cir B | Read | ||
| AV | 430 | CMP_PI_dp_ni_b | Disch Press PI, NI Cir B | Read | ||
| AV | 431 | CMP_PI_lsp_kp_b | Low SP PI, Kp Cir B | Read | ||
| AV | 432 | CMP_PI_lsp_ti_b | Low SP PI, Ti Cir B | Read | ||
| AV | 433 | CMP_PI_lsp_ni_b | Low SP PI, NI Cir B | Read | ||
| AV | 434 | EXV_CFG_fixeddsh | Fixed DSH Setpoint | Read | ||
| AV | 435 | EXV_CFG_scsp_max | Subcooling Setpoint Max | Read | ||
| AV | 436 | EXV_CFG_scsp_min | Subcooling Setpoint Min | Read | ||
| AV | 437 | EXV_CFG_sh_sp_a | Superheat Setpoint A | Read | ||
| AV | 438 | EXV_CFG_sh_sp_b | Superheat Setpoint B | Read | ||
| AV | 439 | EXV_CFG_apr_stp | Approach Setpoint | Read | ||
| AV | 440 | EXV_CFG_sbc_kp_a | Subcool PI, Kp Cir A | Read | ||
| AV | 441 | EXV_CFG_sbc_ti_a | Subcool PI, Ti Cir A | Read | ||
| AV | 442 | EXV_CFG_sbc_ni_a | Subcool PI, NI Cir A | Read | ||
| AV | 443 | EXV_CFG_dsh_kp_a | DSH PI, Kp Cir A | Read | ||
| AV | 444 | EXV_CFG_dsh_ti_a | DSH PI, Ti Cir A | Read | ||
| AV | 445 | EXV_CFG_dsh_ni_a | DSH PI, NI Cir A | Read | ||
| AV | 446 | EXV_CFG_hsp_kp_a | High SP PI, Kp Cir A | Read | ||
| AV | 447 | EXV_CFG_hsp_ti_a | High SP PI, Ti Cir A | Read | ||
| AV | 448 | EXV_CFG_hsp_ni_a | High SP PI, NI Cir A | Read | ||
| AV | 449 | EXV_CFG_lsp_kp_a | Low SP PI, Kp Cir A | Read | ||
| AV | 450 | EXV_CFG_lsp_ti_a | Low SP PI, Ti Cir A | Read | ||
| AV | 451 | EXV_CFG_lsp_ni_a | Low SP PI, NI Cir A | Read | ||
| AV | 452 | EXV_CFG_dop_kp_a | Dop PI, Kp Cir A | Read | ||
| AV | 453 | EXV_CFG_dop_ti_a | Dop PI, Ti Cir A | Read | ||
| AV | 454 | EXV_CFG_dop_ni_a | Dop PI, NI Cir A | Read | ||
| AV | 455 | EXV_CFG_ssh_kp_a | Suction SH PI, Kp Cir A | Read | ||
| AV | 456 | EXV_CFG_ssh_ti_a | Suction SH PI, Ti Cir A | Read | ||
| AV | 457 | EXV_CFG_ssh_ni_a | Suction SH PI, NI Cir A | Read | ||
| AV | 458 | EXV_CFG_sbc_kp_b | Subcool PI, Kp Cir B | Read | ||
| AV | 459 | EXV_CFG_sbc_ti_b | Subcool PI, Ti Cir B | Read | ||
| AV | 460 | EXV_CFG_sbc_ni_b | Subcool PI, NI Cir B | Read | ||
| AV | 461 | EXV_CFG_dsh_kp_b | DSH PI, Kp Cir B | Read | ||
| AV | 462 | EXV_CFG_dsh_ti_b | DSH PI, Ti Cir B | Read | ||
| AV | 463 | EXV_CFG_dsh_ni_b | DSH PI, NI Cir B | Read | ||
| AV | 464 | EXV_CFG_hsp_kp_b | High SP PI, Kp Cir B | Read | ||
| AV | 465 | EXV_CFG_hsp_ti_b | High SP PI, Ti Cir B | Read | ||
| AV | 466 | EXV_CFG_hsp_ni_b | High SP PI, NI Cir B | Read | ||
| AV | 467 | EXV_CFG_lsp_kp_b | Low SP PI, Kp Cir B | Read | ||
| AV | 468 | EXV_CFG_lsp_ti_b | Low SP PI, Ti Cir B | Read | ||
| AV | 469 | EXV_CFG_lsp_ni_b | Low SP PI, NI Cir B | Read | ||
| AV | 470 | EXV_CFG_dop_kp_b | Dop PI, Kp Cir B | Read | ||
| AV | 471 | EXV_CFG_dop_ti_b | Dop PI, Ti Cir B | Read | ||
| AV | 472 | EXV_CFG_dop_ni_b | Dop PI, NI Cir B | Read | ||
| AV | 473 | EXV_CFG_ssh_kp_b | Suction SH PI, Kp Cir B | Read | ||
| AV | 474 | EXV_CFG_ssh_ti_b | Suction SH PI, Ti Cir B | Read | ||
| AV | 475 | EXV_CFG_ssh_ni_b | Suction SH PI, NI Cir B | Read | ||
| AV | 476 | EXV_CFG_apr_kp_a | Appr. PI, Kp Cir A | Read | ||
| AV | 477 | EXV_CFG_apr_ti_a | Appr. PI, Ti Cir A | Read | ||
| AV | 478 | EXV_CFG_apr_ni_a | Appr. PI, NI Cir A | Read | ||
| AV | 479 | EXV_CFG_apr_kp_b | Appr. PI, Kp Cir B | Read | ||
| AV | 480 | EXV_CFG_apr_ti_b | Appr. PI, Ti Cir B | Read | ||
| AV | 481 | EXV_CFG_apr_ni_b | Appr. PI, NI Cir B | Read | ||
| AV | 482 | DELTA_wateesys | water_t_hysteresis | Read | ||
| AV | 483 | DELTA_chdp_hys | cmp high dp hysteresis | Read | ||
| AV | 484 | DELTA_chdtdact | cmp high dt act offset | Read | ||
| AV | 485 | DELTA_chdtdspt | cmp high dt stp offset | Read | ||
| AV | 486 | DELTA_fhdp_hys | fan high dp hysteresis | Read | ||
| AV | 487 | DELTA_fhdtdact | fan high dt act offset | Read | ||
| AV | 488 | DELTA_fhdtdstp | fan high dt stp offset | Read | ||
| AV | 489 | DELTA_ldp_hys | low dp hysteresis | Read | ||
| AV | 490 | DELTA_ldtdact | low dt act offset | Read | ||
| AV | 491 | DELTA_ldtdspt | low dt stp offset | Read | ||
| AV | 492 | DELTA_hsp_hyst | high sp hysteresis | Read | ||
| AV | 493 | DELTA_hstdact | high st act offset | Read | ||
| AV | 494 | DELTA_hstdspt | high st stp offset | Read | ||
| AV | 495 | DELTA_lsp_hyst | low sp hysteresis | Read | ||
| AV | 496 | DELTA_lstdact | low st act offset | Read | ||
| AV | 497 | DELTA_lstdspt | low st stp offset | Read | ||
| AV | 498 | DELTA_lstdcpa | deltat lstEXV vs lstCAPA | Read | ||
| AV | 499 | DELTA_mt_hyst | motor temp hysteresis | Read | ||
| AV | 500 | DELTA_mt_dact | motor temp act offset | Read | ||
| AV | 501 | DELTA_mt_dspt | motor temp stp offset | Read | ||
| AV | 502 | DELTA_dgt_hyst | dgt hysteresis | Read | ||
| AV | 503 | DELTA_dgt_act | dgt limit act offset | Read | ||
| AV | 504 | DELTA_dgt_spt | dgt limit spt offset | Read | ||
| AV | 505 | DELTA_dsh_hyst | dsh hysteresis | Read | ||
| AV | 506 | DELTA_dsh_act | dsh act offset | Read | ||
| AV | 507 | DELTA_dshdelay | exv_no_dsh_delay | Read | ||
| AV | 508 | DELTA_mopdelay | exv_no_mop_delay | Read | ||
| AV | 509 | DELTA_sbc_hys | subcool hysteresis | Read | ||
| AV | 510 | DELTA_sbc_act | subcool act offset | Read | ||
| AV | 511 | DELTA_sbc_spt | Subcooling Setpoint A | Read | ||
| AV | 512 | DELTA_cramprt | Compressor Ramp Rate | Read | ||
| AV | 513 | BACNET_network | Network | Read | ||
| AV | 514 | BACNET_ident | Identifier | Read | ||
| AV | 515 | BACNET_bbmd | BACnet Management Device | Read | ||
| AV | 516 | FAN_CFG_fldp_kpa | Fan Low DP PI, Kp, Cir A | Read | ||
| AV | 517 | FAN_CFG_fldp_tia | Fan Low DP PI, Ti Cir A | Read | ||
| AV | 518 | FAN_CFG_fldp_nia | Fan Low DP PI, NI Cir A | Read | ||
| AV | 519 | FAN_CFG_fldp_kpb | Fan Low DP PI, Kp, Cir B | Read | ||
| AV | 520 | FAN_CFG_fldp_tib | Fan Low DP PI, Ti Cir B | Read | ||
| AV | 521 | FAN_CFG_fldp_nib | Fan Low DP PI, NI Cir B | Read | ||
| AV | 522 | FAN_CFG_fan_hlim | Fan Max Frequency | Read | ||
| AV | 523 | FAN_CFG_fan_llim | Fan Min Frequency | Read | ||
| AV | 524 | FAN_CFG_sync_Kp | Sychronizing Output Kp | Read | ||
| AV | 525 | FAN_CFG_n_coilsA | Cir Cond Coil Number A | Read | ||
| AV | 526 | FAN_CFG_n_coilsB | Cir Cond Coil Number B | Read | ||
| AV | 527 | FAN_CFG_cp_factA | Compressor Factor A | Read | ||
| AV | 528 | FAN_CFG_cp_factB | Compressor Factor B | Read | ||
| AV | 529 | FAN_CFG_fldtfact | Fan Low Dis. Factor | Read | ||
| AV | 530 | FAN_CFG_xt_s_smp | Stablility Sample Nb | Read | ||
| AV | 531 | FAN_CFG_xt_in_tl | Opt. Deviation Tolerance | Read | ||
| AV | 532 | FAN_CFG_os_d_amp | Opt. Disturbance Ampl. | Read | ||
| AV | 533 | FAN_CFG_os_d_per | Opt. Disturbance Period | Read | ||
| AV | 534 | FAN_CFG_os_f_pow | Opt. Freeze Power Tol. | Read | ||
| AV | 535 | FAN_CFG_xtos_flt | Opt. Filter Time | Read | ||
| AV | 536 | FAN_CFG_sct_bias | SCT bias at start | Read | ||
| AV | 537 | FAN_CFG_sct_tim | Total SCT bias time | Read | ||
| AV | 538 | FAN_CFG_sct_decr | Decrement SCT bias time | Read | ||
| AV | 539 | ECO_PI_ecsh_kpa | EXV Eco. SH Kp, Cir A | Read | ||
| AV | 540 | ECO_PI_ecsh_tia | EXV Eco. SH Ti Cir A | Read | ||
| AV | 541 | ECO_PI_ecsh_nia | EXV Eco. SH NI Cir A | Read | ||
| AV | 542 | ECO_PI_ecsh_kpb | EXV Eco. SH Kp, Cir B | Read | ||
| AV | 543 | ECO_PI_ecsh_tib | EXV Eco. SH Ti Cir B | Read | ||
| AV | 544 | ECO_PI_ecsh_nib | EXV Eco. SH NI Cir B | Read | ||
| AV | 545 | ECO_PI_eco_min | EXV Eco. Min Position | Read | ||
| AV | 546 | ECO_PI_eco_max | EXV Eco. Max Position | Read | ||
| AV | 547 | ECO_PI_capa_lim | Capacity Lim Disable Eco | Read | ||
| AV | 548 | ECO_PI_ecoshspa | Eco Superheat Setpoint A | Read | ||
| AV | 549 | ECO_PI_ecoshspb | Eco Superheat Setpoint B | Read | ||
| AV | 550 | SETPOINT_csp1 | Cooling Setpoint 1 | Write | ||
| AV | 551 | SETPOINT_csp2 | Cooling Setpoint 2 | Write | ||
| AV | 552 | SETPOINT_ice_sp | Cooling Ice Setpoint | Write | ||
| AV | 553 | SETPOINT_cramp_sp | Cooling Ramp Loading | Write | ||
| AV | 554 | SETPOINT_lim_sp1 | Switch Limit Setpoint 1 | Write | ||
| AV | 555 | SETPOINT_lim_sp2 | Switch Limit Setpoint 2 | Write | ||
| AV | 556 | SETPOINT_lim_sp3 | Switch Limit Setpoint 3 | Write | ||
| AVmin | 557 | GENUNIT_CTRL_PNT_wr | Control Point | Write | ||
| AVmin | 558 | GENUNIT_DEM_LIM_wr | Active Demand Limit Val | Write | ||
| AV | 559 | GENUNIT_SP_SEL_wr | Setpoint Select | Write | ||
| BV | 1 | GENCONF_ramp_sel | Ramp Loading Enable | Read | ||
| BV | 2 | GENCONF_ice_cnfg | Ice Mode Enable | Read | ||
| BV | 3 | GENCONF_shortcyc | Short Cycle Management | Read | ||
| BV | 4 | PUMPCONF_pump_per | Pump Sticking Protection | Read | ||
| BV | 5 | PUMPCONF_pump_loc | Flow Checked If Pump Off | Read | ||
| BV | 6 | GENUNIT_CHIL_S_S_rd | Net.: Cmd Start/Stop | Read | ||
| BV | 7 | GENUNIT_CHIL_OCC_rd | Net.: Cmd Occupied | Read | ||
| BV | 8 | GENUNIT_SP_OCC_rd | Setpoint Occupied? | Read | ||
| BV | 9 | GENUNIT_EMSTOP_rd | Emergency Stop | Read | ||
| BV | 10 | INPUTS_ONOFF_SW | Remote On/Off Switch | Read | ||
| BV | 11 | INPUTS_SETP_SW | Remote Setpoint Switch | Read | ||
| BV | 12 | INPUTS_LIM_SW1 | Limit Switch 1 | Read | ||
| BV | 13 | INPUTS_LIM_SW2 | Limit Switch 2 | Read | ||
| BV | 14 | INPUTS_OIL_L_A | Oil Level Input A | Read | ||
| BV | 15 | INPUTS_OIL_L_B | Oil Level Input B | Read | ||
| BV | 16 | INPUTS_REM_LOCK | Customer Interlock | Read | ||
| BV | 17 | INPUTS_ICE_SW | Ice Done Storage Switch | Read | ||
| BV | 18 | INPUTS_OCC_OVSW | Occupied Override Switch | Read | ||
| BV | 19 | INPUTS_HEATR_SW | Evap Heater Detector | Read | ||
| BV | 20 | OUTPUTS_LABEL_A | CIRCUIT A | Read | ||
| BV | 21 | OUTPUTS_CP_A | Compressor A | Read | ||
| BV | 22 | OUTPUTS_OIL_SL_A | Oil Solenoid Output A | Read | ||
| BV | 23 | OUTPUTS_VI_A | VI Solenoid Output A | Read | ||
| BV | 24 | OUTPUTS_ISO_OP_A | Ref Iso Relay Energize A | Read | ||
| BV | 25 | OUTPUTS_ISO_POSA | Ref Iso Valve State A | Read | ||
| BV | 26 | OUTPUTS_OIL_HT_A | Oil Heater Output A | Read | ||
| BV | 27 | OUTPUTS_LABEL_B | CIRCUIT B | Read | ||
| BV | 28 | OUTPUTS_CP_B | Compressor B | Read | ||
| BV | 29 | OUTPUTS_OIL_SL_B | Oil Solenoid Output B | Read | ||
| BV | 30 | OUTPUTS_VI_B | VI Solenoid Output B | Read | ||
| BV | 31 | OUTPUTS_ISO_OP_B | Ref Iso Relay Energize B | Read | ||
| BV | 32 | OUTPUTS_ISO_POSB | Ref Iso Valve State B | Read | ||
| BV | 33 | OUTPUTS_OIL_HT_B | Oil Heater Output B | Read | ||
| BV | 34 | OUTPUTS_ALARM | Alarm Relay Status | Read | ||
| BV | 35 | OUTPUTS_RUNNING | Running Relay Status | Read | ||
| BV | 36 | OUTPUTS_ALERT | Alert Relay State | Read | ||
| BV | 37 | OUTPUTS_SHUTDOWN | Shutdown Indicator State | Read | ||
| BV | 38 | OUTPUTS_C_HEATER | Evap Heater Output | Read | ||
| BV | 39 | OUTPUTS_FCA1 | Fan Contactor 1A | Read | ||
| BV | 40 | OUTPUTS_FCA2 | Fan Contactor 2A | Read | ||
| BV | 41 | OUTPUTS_FCA3 | Fan Contactor 3A | Read | ||
| BV | 42 | OUTPUTS_FCA4 | Fan Contactor 4A | Read | ||
| BV | 43 | OUTPUTS_FCA5 | Fan Contactor 5A | Read | ||
| BV | 44 | OUTPUTS_FCA6 | Fan Contactor 6A | Read | ||
| BV | 45 | OUTPUTS_FCA7 | Fan Contactor 7A | Read | ||
| BV | 46 | OUTPUTS_FCA8 | Fan Contactor 8A | Read | ||
| BV | 47 | OUTPUTS_FCB1 | Fan Contactor 1B | Read | ||
| BV | 48 | OUTPUTS_FCB2 | Fan Contactor 2B | Read | ||
| BV | 49 | OUTPUTS_FCB3 | Fan Contactor 3B | Read | ||
| BV | 50 | OUTPUTS_FCB4 | Fan Contactor 4B | Read | ||
| BV | 51 | OUTPUTS_FCB5 | Fan Contactor 5B | Read | ||
| BV | 52 | OUTPUTS_FCB6 | Fan Contactor 6B | Read | ||
| BV | 53 | OUTPUTS_FCB7 | Fan Contactor 7B | Read | ||
| BV | 54 | OUTPUTS_FCB8 | Fan Contactor 8B | Read | ||
| BV | 55 | OUTPUTS_VFD_EN_A | Comp. HW Enable A | Read | ||
| BV | 56 | OUTPUTS_VFD_EN_B | Comp. HW Enable B | Read | ||
| BV | 57 | OUTPUTS_BOX_HTR | Control Box Heater | Read | ||
| BV | 58 | PUMPSTAT_CPUMP_1_rd | Evap Pump #1 Command | Read | ||
| BV | 59 | PUMPSTAT_CPUMP_2_rd | Evap Pump #2 Command | Read | ||
| BV | 60 | PUMPSTAT_ROTCPUMP_rd | Rotate Evap Pumps ? | Read | ||
| BV | 61 | PUMPSTAT_FLOW_SW | Evap Flow Switch #1 | Read | ||
| BV | 62 | PUMPSTAT_FLOW_SWB | Evap Flow Switch #2 | Read | ||
| BV | 63 | MODES_m_delay | Start Up Delay In Effect | Read | ||
| BV | 64 | MODES_m_2stpt | Second Setpoint In Use | Read | ||
| BV | 65 | MODES_m_reset | Reset In Effect | Read | ||
| BV | 66 | MODES_m_demlim | Demand Limit Active | Read | ||
| BV | 67 | MODES_m_pmprot | Evaporator Pump Rotation | Read | ||
| BV | 68 | MODES_m_pmpper | Pump Periodic Start | Read | ||
| BV | 69 | MODES_m_night | Night Low Noise Active | Read | ||
| BV | 70 | MODES_m_slave | Master Slave Active | Read | ||
| BV | 71 | MODES_m_ice | Ice Mode In Effect, Active Alarms: | Read | ||
| BV | 72 | ALARMRST_RST_ALM | Alarm Reset | Read | ||
| BV | 73 | VLT_DRV_SET_DRVA | Drive A Attach | Read | ||
| BV | 74 | VLT_DRV_SET_DRVB | Drive B Attach | Read | ||
| BV | 75 | VLT_DRV_VLT_COMA | Comm with Drive A Ok | Read | ||
| BV | 76 | VLT_DRV_VLT_COMB | Comm with Drive B Ok | Read | ||
| BV | 77 | M_MSTSLV_ms_activ | Master/Slave Ctrl Active | Read | ||
| BV | 78 | M_MSTSLV_lead_sel | Lead Unit is the: | Read | ||
| BV | 79 | M_MSTSLV_ll_chang | Lead/lag Changeover? | Read | ||
| BV | 80 | M_MSTSLV_ll_pull | Lead Pulldown ? | Read | ||
| BV | 81 | M_MSTSLV_cap_max | Max Available Capacity ? | Read | ||
| BV | 82 | FAN_DRV2_SET_FDA1 | Fan Drive A1 Attach | Read | ||
| BV | 83 | FAN_DRV2_SET_FDA2 | Fan Drive A2 Attach | Read | ||
| BV | 84 | FAN_DRV2_SET_FDA3 | Fan Drive A3 Attach | Read | ||
| BV | 85 | FAN_DRV2_SET_FDB1 | Fan Drive B1 Attach | Read | ||
| BV | 86 | FAN_DRV2_SET_FDB2 | Fan Drive B2 Attach | Read | ||
| BV | 87 | FAN_DRV2_SET_FDB3 | Fan Drive B3 Attach | Read | ||
| BV | 88 | FAN_DRV2_FD_COMA1 | Comm Fan Drive A1 Ok | Read | ||
| BV | 89 | FAN_DRV2_FD_COMA2 | Comm Fan Drive A2 Ok | Read | ||
| BV | 90 | FAN_DRV2_FD_COMA3 | Comm Fan Drive A3 Ok | Read | ||
| BV | 91 | FAN_DRV2_FD_COMB1 | Comm Fan Drive B1 Ok | Read | ||
| BV | 92 | FAN_DRV2_FD_COMB2 | Comm Fan Drive B2 Ok | Read | ||
| BV | 93 | FAN_DRV2_FD_COMB3 | Comm Fan Drive B3 Ok | Read | ||
| BV | 94 | FAN_DRV2_stopfana | Stop Cir A Fan Drive | Read | ||
| BV | 95 | FAN_DRV2_stopfanb | Stop Cir B Fan Drive | Read | ||
| BV | 96 | FACTORY_freq_60H | 60Hz Sel (No=50, Yes=60) | Read | ||
| BV | 97 | FACTORY_probrine | Process Brine Evap | Read | ||
| BV | 98 | FACTORY_heat_sel | Evap Heater Installed | Read | ||
| BV | 99 | FACTORY_mst_slv | Master Slave Setup | Read | ||
| BV | 100 | FACTORY_emm_nrcp | Energy Management Module | Read | ||
| BV | 101 | FACTORY_loambopt | Low Ambient Option (STD) | Read | ||
| BV | 102 | FACTORY_leak_chk | Leakage Charge Detection | Read | ||
| BV | 103 | FACTORY_fMaxEnA | Enable Max Frequency A | Read | ||
| BV | 104 | FACTORY_fMaxEnB | Enable Max Frequency B | Read | ||
| BV | 105 | SERVICE1_ewt_opt | Entering Fluid Control | Read | ||
| BV | 106 | SERVICE1_ser_pass | Service Password | Read | ||
| BV | 107 | SERVICE1_RFI_conf | Compressor RFI Filter En | Read | ||
| BV | 108 | SERVICE1_metric | Metric Units? (Blackbox) | Read | ||
| BV | 109 | SERVICE1_fdrv_cfg | Send fan drive config? | Read | ||
| BV | 110 | SERVICE1_cdrv_cfg | Send comp. drive config? | Read | ||
| BV | 111 | SERVICE1_auto_sm | Auto Start When SM Lost | Read | ||
| BV | 112 | SERVICE1_ViChkEn | VI Self-Test Enable | Write | ||
| BV | 113 | SERVICE1_AntiFrz | Pump Rot. AntiFrz Protec | Read | ||
| BV | 114 | SERVICE1_http_en | HTTP Server | Read | ||
| BV | 115 | SERVICE1_ftp_en | FTP Server | Read | ||
| BV | 116 | MST_SLV_ll_serie | Chiller In Series | Read | ||
| BV | 117 | BACNET_bacena | BACnet Enable | Read | ||
| BV | 118 | BACNET_bacunit | Metric Units? (Blackbox) | Read | ||
| BV | 119 | FAN_CFG_fan_ctrl | Fan Ctrl Type (Vari,Fix), Optimization Parameters | Read | ||
| BV | 120 | FAN_CFG_xt_enabl | Optimization Enable | Read | ||
| BV | 121 | CP_ENABL_en_cp_a | Compressor A Disable | Read | ||
| BV | 122 | CP_ENABL_en_cp_b | Compressor B Disable | Read | ||
| BVmin | 123 | GENUNIT_CHIL_S_S_wr | Net.: Cmd Start/Stop | Write | ||
| BV | 124 | PUMPSTAT_CPUMP_1_wr | Evap Pump #1 Command | Write | ||
| BV | 125 | PUMPSTAT_CPUMP_2_wr | Evap Pump #2 Command | Write | ||
| BV | 126 | GENUNIT_EMSTOP_wr | Emergency Stop | Write | ||
| BV | 127 | PUMPSTAT_ROTCPUMP_wr | Rotate Evap Pumps ? | Write | ||
| BV | 128 | GENUNIT_SP_OCC_wr | Setpoint Occupied? | Write | ||
| BVmin | 129 | GENUNIT_CHIL_OCC_wr | Net.: Cmd Occupied | Write | ||
| BV | 130 | ALM_COOL_EWT_F | COOL_EWT_F | Read | ||
| BV | 131 | ALM_COOL_LWT_F | COOL_LWT_F | Read | ||
| BV | 132 | ALM_OAT_F | OAT_F | Read | ||
| BV | 133 | ALM_CHWSTEMP_F | CHWSTEMP_F | Read | ||
| BV | 134 | ALM_SUCTION_T_A_F | SUCTION_T_A_F | Read | ||
| BV | 135 | ALM_SUCTION_T_B_F | SUCTION_T_B_F | Read | ||
| BV | 136 | ALM_DGT_A_T_F | DGT_A_T_F | Read | ||
| BV | 137 | ALM_DGT_B_T_F | DGT_B_T_F | Read | ||
| BV | 138 | ALM_LIQUID_T_A_F | LIQUID_T_A_F | Read | ||
| BV | 139 | ALM_LIQUID_T_B_F | LIQUID_T_B_F | Read | ||
| BV | 140 | ALM_CP_TMP_A_F | CP_TMP_A_F | Read | ||
| BV | 141 | ALM_CP_TMP_B_F | CP_TMP_B_F | Read | ||
| BV | 142 | ALM_ECO_T_A_F | ECO_T_A_F | Read | ||
| BV | 143 | ALM_ECO_T_B_F | ECO_T_B_F | Read | ||
| BV | 144 | ALM_SPACE_TEMP_F | SPACE_TEMP_F | Read | ||
| BV | 145 | ALM_DP_A_F | DP_A_F | Read | ||
| BV | 146 | ALM_DP_B_F | DP_B_F | Read | ||
| BV | 147 | ALM_SP_A_F | SP_A_F | Read | ||
| BV | 148 | ALM_SP_B_F | SP_B_F | Read | ||
| BV | 149 | ALM_OIL_P_A_F | OIL_P_A_F | Read | ||
| BV | 150 | ALM_OIL_P_B_F | OIL_P_B_F | Read | ||
| BV | 151 | ALM_ECO_P_A_F | ECO_P_A_F | Read | ||
| BV | 152 | ALM_ECO_P_B_F | ECO_P_B_F | Read | ||
| BV | 153 | ALM_LIQUID_P_A_F | LIQUID_P_A_F | Read | ||
| BV | 154 | ALM_LIQUID_P_B_F | LIQUID_P_B_F | Read | ||
| BV | 155 | ALM_SIOB1_COM_F | SIOB1_COM_F | Read | ||
| BV | 156 | ALM_SIOB2_COM_F | SIOB2_COM_F | Read | ||
| BV | 157 | ALM_AUX1_1_COM_F | AUX1_1_COM_F | Read | ||
| BV | 158 | ALM_AUX1_2_COM_F | AUX1_2_COM_F | Read | ||
| BV | 159 | ALM_AUX1_3_COM_F | AUX1_3_COM_F | Read | ||
| BV | 160 | ALM_AUX1_4_COM_F | AUX1_4_COM_F | Read | ||
| BV | 161 | ALM_EMM_BRD_COM_F | EMM_BOARD_COM_F | Read | ||
| BV | 162 | ALM_VLT_DRIVE1_COM_F | VLT_DRIVE1_COM_F | Read | ||
| BV | 163 | ALM_VLT_DRIVE2_COM_F | VLT_DRIVE2_COM_F | Read | ||
| BV | 164 | ALM_FAN_DRIVEA1_COM_F | FAN_DRIVEA1_COM_F | Read | ||
| BV | 165 | ALM_FAN_DRIVEA2_COM_F | FAN_DRIVEA2_COM_F | Read | ||
| BV | 166 | ALM_FAN_DRIVEA3_COM_F | FAN_DRIVEA3_COM_F | Read | ||
| BV | 167 | ALM_FAN_DRIVEB1_COM_F | FAN_DRIVEB1_COM_F | Read | ||
| BV | 168 | ALM_FAN_DRIVEB2_COM_F | FAN_DRIVEB2_COM_F | Read | ||
| BV | 169 | ALM_FAN_DRIVEB3_COM_F | FAN_DRIVEB3_COM_F | Read | ||
| BV | 170 | ALM_COOLER_FREEZE_F | COOLER_FREEZE_F | Read | ||
| BV | 171 | ALM_LOW_SUCTION_A_F | LOW_SUCTION_A_F | Read | ||
| BV | 172 | ALM_LOW_SUCTION_B_F | LOW_SUCTION_B_F | Read | ||
| BV | 173 | ALM_LOCK_F | LOCK_F | Read | ||
| BV | 174 | ALM_LOSS_COM_MS_F | LOSS_COM_MS_F | Read | ||
| BV | 175 | ALM_LOW_OIL_A_P_F | LOW_OIL_A_P_F | Read | ||
| BV | 176 | ALM_LOW_OIL_B_P_F | LOW_OIL_B_P_F | Read | ||
| BV | 177 | ALM_OIL_FILT_A_P_F | OIL_FILT_A_P_F | Read | ||
| BV | 178 | ALM_OIL_FILT_B_P_F | OIL_FILT_B_P_F | Read | ||
| BV | 179 | ALM_OIL_DROP_A_P_F | OIL_DROP_A_P_F | Read | ||
| BV | 180 | ALM_OIL_DROP_B_P_F | OIL_DROP_B_P_F | Read | ||
| BV | 181 | ALM_LOW_OIL_LEVEL_A_F | LOW_OIL_LEVEL_A_F | Read | ||
| BV | 182 | ALM_LOW_OIL_LEVEL_B_F | LOW_OIL_LEVEL_B_F | Read | ||
| BV | 183 | ALM_M_S_CONFIG_F | M_S_CONFIG_F | Read | ||
| BV | 184 | ALM_INI_FACT_CONF_F | INI_FACT_CONF_F | Read | ||
| BV | 185 | ALM_ILL_FACT_CONF_F | ILL_FACT_CONF_F | Read | ||
| BV | 186 | ALM_CCN_EMSTOP_F | CCN_EMSTOP_F | Read | ||
| BV | 187 | ALM_COOL_PUMP1_F | COOL_PUMP1_F | Read | ||
| BV | 188 | ALM_COOL_PUMP2_F | COOL_PUMP2_F | Read | ||
| BV | 189 | ALM_SCT_OUT_OF_CP_M_A_F | SCT_OUT_OF_CP_MAP_A_F | Read | ||
| BV | 190 | ALM_SCT_OUT_OF_CP_M_B_F | SCT_OUT_OF_CP_MAP_B_F | Read | ||
| BV | 191 | ALM_REFRIG_ESCAPE_F | REFRIGERANT_ESCAPE_F | Read | ||
| BV | 192 | ALM_HIGH_DGT_A_F | HIGH_DGT_A_F | Read | ||
| BV | 193 | ALM_HIGH_DGT_B_F | HIGH_DGT_B_F | Read | ||
| BV | 194 | ALM_SUCT_VALV_CLOSD_A_F | SUCT_VALV_CLOSED_A_F | Read | ||
| BV | 195 | ALM_SUCT_VALV_CLOSD_B_F | SUCT_VALV_CLOSED_B_F | Read | ||
| BV | 196 | ALM_COOLER_FLOW_F | COOLER_FLOW_F | Read | ||
| BV | 197 | ALM_SENSORS_SWAP_F | SENSORS_SWAP_F | Read | ||
| BV | 198 | ALM_SST_OUT_OF_CP_M_A_F | SST_OUT_OF_CP_MAP_A_F | Read | ||
| BV | 199 | ALM_SST_OUT_OF_CP_M_B_F | SST_OUT_OF_CP_MAP_B_F | Read | ||
| BV | 200 | ALM_VLT_DRIVE_A_F | VLT_DRIVE_A_F | Read | ||
| BV | 201 | ALM_VLT_DRIVE_B_F | VLT_DRIVE_B_F | Read | ||
| BV | 202 | ALM_FAN_DRIVE_A1_F | FAN_DRIVE_A1_F | Read | ||
| BV | 203 | ALM_FAN_DRIVE_A2_F | FAN_DRIVE_A2_F | Read | ||
| BV | 204 | ALM_FAN_DRIVE_A3_F | FAN_DRIVE_A3_F | Read | ||
| BV | 205 | ALM_FAN_DRIVE_B1_F | FAN_DRIVE_B1_F | Read | ||
| BV | 206 | ALM_FAN_DRIVE_B2_F | FAN_DRIVE_B2_F | Read | ||
| BV | 207 | ALM_FAN_DRIVE_B3_F | FAN_DRIVE_B3_F | Read | ||
| BV | 208 | ALM_VLT_DRIVE_A_ALERT | VLT_DRIVE_A_ALERT | Read | ||
| BV | 209 | ALM_VLT_DRIVE_B_ALERT | VLT_DRIVE_B_ALERT | Read | ||
| BV | 210 | ALM_FAN_DRIVE_A1_ALERT | FAN_DRIVE_A1_ALERT | Read | ||
| BV | 211 | ALM_FAN_DRIVE_A2_ALERT | FAN_DRIVE_A2_ALERT | Read | ||
| BV | 212 | ALM_FAN_DRIVE_A3_ALERT | FAN_DRIVE_A3_ALERT | Read | ||
| BV | 213 | ALM_FAN_DRIVE_B1_ALERT | FAN_DRIVE_B1_ALERT | Read | ||
| BV | 214 | ALM_FAN_DRIVE_B2_ALERT | FAN_DRIVE_B2_ALERT | Read | ||
| BV | 215 | ALM_FAN_DRIVE_B3_ALERT | FAN_DRIVE_B3_ALERT | Read | ||
| BV | 216 | ALM_HIGH_CP_TMP_A_F | HIGH_CP_TMP_A_F | Read | ||
| BV | 217 | ALM_HIGH_CP_TMP_B_F | HIGH_CP_TMP_B_F | Read | ||
| BV | 218 | ALM_HP_SWITCH_A_F | HP_SWITCH_A_F | Read | ||
| BV | 219 | ALM_HP_SWITCH_B_F | HP_SWITCH_B_F | Read | ||
| BV | 220 | ALM_DATABASE_F | DATABASE_F | Read | ||
| BV | 221 | ALM_LENSCAN_F | LENSCAN_F | Read | ||
| BV | 222 | ALM_STEPPER_EXV_A_F | STEPPER_EXV_A_F | Read | ||
| BV | 223 | ALM_STEPPER_EXV_B_F | STEPPER_EXV_B_F | Read | ||
| BV | 224 | ALM_STEPPER_ECO_A_F | STEPPER_ECO_A_F | Read | ||
| BV | 225 | ALM_STEPPER_ECO_B_F | STEPPER_ECO_B_F | Read | ||
| BV | 226 | ALM_VI_DIAG_A_ALERT | VI_DIAG_A_ALERT | Read | ||
| BV | 227 | ALM_VI_DIAG_B_ALERT | VI_DIAG_B_ALERT | Read | ||
| TL | 1 | TL_STATUS | Run Status | Write | ||
| TL | 2 | TL_SP_SEL | Setpoint Select | Write | ||
| TL | 3 | TL_DEM_LIM | Active Demand Limit Val | Write | ||
| TL | 4 | TL_COOL_EWT | Evap Entering Fluid | Write | ||
| TL | 5 | TL_COOL_LWT | Evap Leaving Fluid | Write | ||
| TL | 6 | TL_OAT | Outdoor Air Temperature | Write | ||
| TL | 7 | TL_SCT_A | Saturated Cond Tmp Cir A | Write | ||
| TL | 8 | TL_SST_A | Saturated Suction Temp A | Write | ||
| TL | 9 | TL_DGT_A | Discharge Gas Temp Cir A | Write | ||
| TL | 10 | TL_CP_TMP_A | Motor Temperature Cir A | Write | ||
| TL | 11 | TL_ECO_T_A | EXV Eco. Tmp Cir A | Write | ||
| TL | 12 | TL_SCT_B | Saturated Cond Tmp Cir B | Write | ||
| TL | 13 | TL_SST_B | Saturated Suction Temp B | Write | ||
| TL | 14 | TL_DGT_B | Discharge Gas Temp Cir B | Write | ||
| TL | 15 | TL_CP_TMP_B | Motor Temperature Cir B | Write | ||
| TL | 16 | TL_ECO_T_B | EXV Eco. Tmp Cir B | Write | ||
| TL | 17 | TL_ECO_P_A | Economizer Pressure A | Write | ||
| TL | 18 | TL_ECO_P_B | Economizer Pressure B | Write | ||
| TL | 19 | TL_OIL_L_A | Oil Level Input A | Write | ||
| TL | 20 | TL_OIL_L_B | Oil Level Input B | Write | ||
| TL | 21 | TL_HR_MACH | Machine Operating Hours | Write | ||
| TL | 22 | TL_st_mach | Machine Starts | Write | ||
| TL | 23 | TL_HR_CP_A | Compressor A Hours | Write | ||
| TL | 24 | TL_st_cp_a | Compressor A Starts | Write | ||
| TL | 25 | TL_HR_CP_B | Compressor B Hours | Write | ||
| TL | 26 | TL_st_cp_b | Compressor B Starts | Write | ||
| TL | 27 | TL_drv_pwra | Cir A Drive Power | Write | ||
| TL | 28 | TL_drv_Ia | Cir A Drive Amps | Write | ||
| TL | 29 | TL_drv_Fa | Cir A Drive Frequency | Write | ||
| TL | 30 | TL_drv_pwrb | Cir B Drive Power | Write | ||
| TL | 31 | TL_drv_Ib | Cir B Drive Amps | Write | ||
| TL | 32 | TL_drv_Fb | Cir B Drive Frequency | Write | ||
| TL | 33 | TL_drv_pwr | Total Comp Drive Power | Write | ||
| TL | 34 | TL_ov_exv_a | EXV Override Circuit A | Write | ||
| TL | 35 | TL_EXV_A | EXV Position Circuit A | Write | ||
| TL | 36 | TL_ov_exv_b | EXV Override Circuit B | Write | ||
| TL | 37 | TL_EXV_B | EXV Position Circuit B | Write | ||
| TL | 38 | TL_ctrl_wt | Controled Water Temp | Write | ||
| TL | 39 | TL_overrida | Override Capacity Nb A | Write | ||
| TL | 40 | TL_cap_pc_a | Estimated Capacity A | Write | ||
| TL | 41 | TL_overridb | Override Capacity Nb B | Write | ||
| TL | 42 | TL_cap_pc_b | Estimated Capacity B | Write | ||
| TL | 43 | TL_eco_a | EXV Eco Position Cir A | Write | ||
| TL | 44 | TL_eco_b | EXV Eco Position Cir B | Write | ||
| TL | 45 | TL_fan_f_a | Fan Freq Cir A | Write | ||
| TL | 46 | TL_fan_f_b | Fan Freq Cir B | Write | ||
| TL | 47 | TL_fd_pwra1 | Fan Drive Power A1 | Write | ||
| TL | 48 | TL_fd_pwra2 | Fan Drive Power A2 | Write | ||
| TL | 49 | TL_fd_pwrb1 | Fan Drive Power B1 | Write | ||
| TL | 50 | TL_fd_pwrb2 | Fan Drive Power B2 | Write | ||
| TL | 51 | TL_fd_pwr | Total Fan Drive Power | Write |
No points match these filters.
Object ID lookup: Carrier AquaForce 30XV 140-500 Series B, Carrier Controller point IDs by name
AV1GENCONF_prio_cirAV2GENCONF_off_on_dAV3GENCONF_lim_selAV4GENCONF_nh_startAV5GENCONF_nh_endAV6GENCONF_nh_limitAV7PUMPCONF_cpumpseqAV8PUMPCONF_pump_delAV9USERCONF_use_passAV10RESETCFG_cr_selAV11RESETCFG_oat_crnoAV12RESETCFG_oat_crfuAV13RESETCFG_dt_cr_noAV14RESETCFG_dt_cr_fuAV15RESETCFG_v_cr_noAV16RESETCFG_v_cr_fuAV17RESETCFG_spacr_noAV18RESETCFG_spacr_fuAV19RESETCFG_cr_degAV20GENUNIT_CTRL_TYPAV21GENUNIT_STATUSAV22GENUNIT_min_leftAV23GENUNIT_SP_SEL_rdAV24GENUNIT_CAP_TAV25GENUNIT_SPAV26GENUNIT_CTRL_PNT_rdAV27GENUNIT_DEM_LIM_rdAV28GENUNIT_min_limAV29TEMP_COOL_EWTAV30TEMP_COOL_LWTAV31TEMP_OATAV32TEMP_SCT_AAV33TEMP_SST_AAV34TEMP_SLT_AAV35TEMP_SUCT_AAV36TEMP_DGT_AAV37TEMP_CP_TMP_AAV38TEMP_ECO_T_AAV39TEMP_LIQ_T_AAV40TEMP_SCT_BAV41TEMP_SST_BAV42TEMP_SLT_BAV43TEMP_SUCT_BAV44TEMP_DGT_BAV45TEMP_CP_TMP_BAV46TEMP_ECO_T_BAV47TEMP_LIQ_T_BAV48TEMP_SPACETMPAV49TEMP_CHWSTEMPAV50PRESSURE_DP_AAV51PRESSURE_SP_AAV52PRESSURE_OP_AAV53PRESSURE_DOP_AAV54PRESSURE_ECO_P_AAV55PRESSURE_LIQ_P_AAV56PRESSURE_DP_BAV57PRESSURE_SP_BAV58PRESSURE_OP_BAV59PRESSURE_DOP_BAV60PRESSURE_ECO_P_BAV61PRESSURE_LIQ_P_BAV62INPUTS_SP_RESETAV63INPUTS_LIM_ANALAV64INPUTS_leak_vAV65INPUTS_leak_2_vAV66OUTPUTS_CAPT010AAV67OUTPUTS_VFAN_AAV68OUTPUTS_CAPT010BAV69OUTPUTS_VFAN_BAV70OUTPUTS_CAPT_010AV71RUNTIME_HR_MACHAV72RUNTIME_st_machAV73RUNTIME_HR_CP_AAV74RUNTIME_st_cp_aAV75RUNTIME_HR_CP_BAV76RUNTIME_st_cp_bAV77RUNTIME_hr_cpum1AV78RUNTIME_hr_cpum2AV79RUNTIME_VIctAAV80RUNTIME_VIctBAV81RUNTIME_hrfana01AV82RUNTIME_hrfana02AV83RUNTIME_hrfana03AV84RUNTIME_hrfana04AV85RUNTIME_hrfana05AV86RUNTIME_hrfana06AV87RUNTIME_hrfana07AV88RUNTIME_hrfana08AV89RUNTIME_hrfana09AV90RUNTIME_hrfana10AV91RUNTIME_hrfana11AV92RUNTIME_hrfana12AV93RUNTIME_hrfana13AV94RUNTIME_hrfana14AV95RUNTIME_hrfanb01AV96RUNTIME_hrfanb02AV97RUNTIME_hrfanb03AV98RUNTIME_hrfanb04AV99RUNTIME_hrfanb05AV100RUNTIME_hrfanb06AV101RUNTIME_hrfanb07AV102RUNTIME_hrfanb08AV103RUNTIME_hrfanb09AV104RUNTIME_hrfanb10AV105RUNTIME_hrfanb11AV106RUNTIME_hrfanb12AV107RUNTIME_hrfanb13AV108RUNTIME_hrfanb14AV109ALARMRST_ALMAV110ALARMRST_alarm_1AV111ALARMRST_alarm_2AV112ALARMRST_alarm_3AV113ALARMRST_alarm_4AV114ALARMRST_alarm_5AV115VLT_DRV_drv_pwraAV116VLT_DRV_drv_IaAV117VLT_DRV_drv_VaAV118VLT_DRV_drv_SaAV119VLT_DRV_drv_FaAV120VLT_DRV_drv_TaAV121VLT_DRV_drv_DCVaAV122VLT_DRV_drv_HSTaAV123VLT_DRV_drv_CCTaAV124VLT_DRV_drv_HTRaAV125VLT_DRV_drv_pwrbAV126VLT_DRV_drv_IbAV127VLT_DRV_drv_VbAV128VLT_DRV_drv_SbAV129VLT_DRV_drv_FbAV130VLT_DRV_drv_TbAV131VLT_DRV_drv_DCVbAV132VLT_DRV_drv_HSTbAV133VLT_DRV_drv_CCTbAV134VLT_DRV_drv_HTRbAV135VLT_DRV_drv_pwrAV136LAST_POR_date_on1AV137LAST_POR_time_on1AV138LAST_POR_date_of1AV139LAST_POR_time_of1AV140LAST_POR_date_on2AV141LAST_POR_time_on2AV142LAST_POR_date_of2AV143LAST_POR_time_of2AV144LAST_POR_date_on3AV145LAST_POR_time_on3AV146LAST_POR_date_of3AV147LAST_POR_time_of3AV148LAST_POR_date_on4AV149LAST_POR_time_on4AV150LAST_POR_date_of4AV151LAST_POR_time_of4AV152LAST_POR_date_on5AV153LAST_POR_time_on5AV154LAST_POR_date_of5AV155LAST_POR_time_of5AV156EXV_CTRL_ov_exv_aAV157EXV_CTRL_EXV_AAV158EXV_CTRL_DSH_AAV159EXV_CTRL_dsh_spaAV160EXV_CTRL_SH_AAV161EXV_CTRL_sh_sp_aAV162EXV_CTRL_pinch_aAV163EXV_CTRL_subcoolaAV164EXV_CTRL_subc_spaAV165EXV_CTRL_exv_staAV166EXV_CTRL_exv_lstaAV167EXV_CTRL_exvwposaAV168EXV_CTRL_ov_exv_bAV169EXV_CTRL_EXV_BAV170EXV_CTRL_DSH_BAV171EXV_CTRL_dsh_spbAV172EXV_CTRL_SH_BAV173EXV_CTRL_sh_sp_bAV174EXV_CTRL_pinch_bAV175EXV_CTRL_subcoolbAV176EXV_CTRL_subc_spbAV177EXV_CTRL_exv_stbAV178EXV_CTRL_exv_lstbAV179EXV_CTRL_exvwposbAV180M_MSTSLV_slv_statAV181M_MSTSLV_slv_captAV182M_MSTSLV_l_strt_dAV183M_MSTSLV_ll_hr_dAV184M_MSTSLV_ms_errorAV185M_MSTSLV_lagstatAV186M_MSTSLV_slav_hrAV187M_MSTSLV_slav_ewtAV188M_MSTSLV_slav_lwtAV189CAPACTRL_ctrl_wtAV190CAPACTRL_cwt_rateAV191CAPACTRL_cap_limAV192CAPACTRL_drvcmdaAV193CAPACTRL_capmodaAV194CAPACTRL_lcapmodaAV195CAPACTRL_overridaAV196CAPACTRL_cap_pc_aAV197CAPACTRL_drvcmdbAV198CAPACTRL_capmodbAV199CAPACTRL_lcapmodbAV200CAPACTRL_overridbAV201CAPACTRL_cap_pc_bAV202CAPACTRL_cMaxFrqAAV203CAPACTRL_cMaxFrqBAV204CAPACTRL_viCmdAAV205CAPACTRL_viCmdBAV206CAPACTRL_resetAV207CAPACTRL_CirRunNbAV208CAPACTRL_StatCirAAV209CAPACTRL_StatCirBAV210CAPACTRL_DualMastAV211CAPACTRL_xSpdHighAV212CAPACTRL_xSpdLowAV213LIMITS_dshactaAV214LIMITS_dshstpaAV215LIMITS_elspactaAV216LIMITS_elspstpaAV217LIMITS_chdpactaAV218LIMITS_chdpstpaAV219LIMITS_fhdpactaAV220LIMITS_fhdpstpaAV221LIMITS_ldpactaAV222LIMITS_ldpstpaAV223LIMITS_hspactaAV224LIMITS_hspstpaAV225LIMITS_lspactaAV226LIMITS_lspstpaAV227LIMITS_lspdcpaAV228LIMITS_dgtactaAV229LIMITS_dgtstpaAV230LIMITS_dshactbAV231LIMITS_dshstpbAV232LIMITS_elspactbAV233LIMITS_elspstpbAV234LIMITS_chdpactbAV235LIMITS_chdpstpbAV236LIMITS_fhdpactbAV237LIMITS_fhdpstpbAV238LIMITS_ldpactbAV239LIMITS_ldpstpbAV240LIMITS_hspactbAV241LIMITS_hspstpbAV242LIMITS_lspactbAV243LIMITS_lspstpbAV244LIMITS_lspdcpbAV245LIMITS_dgtactbAV246LIMITS_dgtstpbAV247ECO_CTRL_eco_aAV248ECO_CTRL_eco_bAV249FAN_CTRL_fan_f_aAV250FAN_CTRL_fan_staAV251FAN_CTRL_fan_lstaAV252FAN_CTRL_wfan_f_aAV253FAN_CTRL_fan_modaAV254FAN_CTRL_fan_txtaAV255FAN_CTRL_ftotpowaAV256FAN_CTRL_fcont_aAV257FAN_CTRL_fan_f_bAV258FAN_CTRL_fan_stbAV259FAN_CTRL_fan_lstbAV260FAN_CTRL_wfan_f_bAV261FAN_CTRL_fan_modbAV262FAN_CTRL_fan_txtbAV263FAN_CTRL_ftotpowbAV264FAN_CTRL_fcont_bAV265FAN_DRV_fd_pwra1AV266FAN_DRV_fd_Ia1AV267FAN_DRV_fd_Va1AV268FAN_DRV_fd_Sa1AV269FAN_DRV_fd_Fa1AV270FAN_DRV_fd_Ta1AV271FAN_DRV_fd_DCVa1AV272FAN_DRV_fd_HSTa1AV273FAN_DRV_fd_CCTa1AV274FAN_DRV_fd_pwra2AV275FAN_DRV_fd_Ia2AV276FAN_DRV_fd_Va2AV277FAN_DRV_fd_Sa2AV278FAN_DRV_fd_Fa2AV279FAN_DRV_fd_Ta2AV280FAN_DRV_fd_DCVa2AV281FAN_DRV_fd_HSTa2AV282FAN_DRV_fd_CCTa2AV283FAN_DRV_fd_pwra3AV284FAN_DRV_fd_Ia3AV285FAN_DRV_fd_Va3AV286FAN_DRV_fd_Sa3AV287FAN_DRV_fd_Fa3AV288FAN_DRV_fd_Ta3AV289FAN_DRV_fd_DCVa3AV290FAN_DRV_fd_HSTa3AV291FAN_DRV_fd_CCTa3AV292FAN_DRV_fd_pwrb1AV293FAN_DRV_fd_Ib1AV294FAN_DRV_fd_Vb1AV295FAN_DRV_fd_Sb1AV296FAN_DRV_fd_Fb1AV297FAN_DRV_fd_Tb1AV298FAN_DRV_fd_DCVb1AV299FAN_DRV_fd_HSTb1AV300FAN_DRV_fd_CCTb1AV301FAN_DRV_fd_pwrb2AV302FAN_DRV_fd_Ib2AV303FAN_DRV_fd_Vb2AV304FAN_DRV_fd_Sb2AV305FAN_DRV_fd_Fb2AV306FAN_DRV_fd_Tb2AV307FAN_DRV_fd_DCVb2AV308FAN_DRV_fd_HSTb2AV309FAN_DRV_fd_CCTb2AV310FAN_DRV_fd_pwrb3AV311FAN_DRV_fd_Ib3AV312FAN_DRV_fd_Vb3AV313FAN_DRV_fd_Sb3AV314FAN_DRV_fd_Fb3AV315FAN_DRV_fd_Tb3AV316FAN_DRV_fd_DCVb3AV317FAN_DRV_fd_HSTb3AV318FAN_DRV_fd_CCTb3AV319FAN_DRV_fd_pwrAV320FACTORY_unitsizeAV321FACTORY_voltageAV322FACTORY_mfg_tierAV323FACTORY_cpass_nbAV324FACTORY_fac_passAV325FACTORY_fMaxOvrAAV326FACTORY_fMaxOvrBAV327FACTORY_fan_factAV328FACTORY_fMinOvrAV329FACTORY_lastspdaAV330FACTORY_lastspdbAV331FACTORY2_exvmax_aAV332FACTORY2_exvmax_bAV333FACTORY2_eco_cnfaAV334FACTORY2_eco_cnfbAV335FACTORY2_vfd_cmpAV336FACTORY2_vfd_fanaAV337FACTORY2_vfd_fanbAV338SERVICE1_flui_typAV339SERVICE1_freezespAV340SERVICE1_mini_lwtAV341SERVICE1_fastcaprAV342SERVICE1_ewt_cirAAV343SERVICE1_leak_thrAV344SERVICE1_leak_tmrAV345SERVICE1_heaterspAV346SERVICE1_freez_ovAV347SERVICE1_ViPwrChkAV348SERVICE1_odtrspdAV349SERVICE1_otrigtimAV350SERVICE1_odrecspdAV351SERVICE1_orectimAV352SERVICE1_wateesysAV353SERVICE1_vistrtdtAV354SERVICE1_vistrtenAV355SERVICE1_apr_enAV356UPDTHOUR_hr_machAV357UPDTHOUR_st_machAV358UPDTHOUR_hr_cp_aAV359UPDTHOUR_st_cp_aAV360UPDTHOUR_hr_cp_bAV361UPDTHOUR_st_cp_bAV362UPDTHOUR_hr_cpum1AV363UPDTHOUR_hr_cpum2AV364UPDTHOUR_VIctAAV365UPDTHOUR_VIctBAV366UPDTHOUR_hrfana01AV367UPDTHOUR_hrfana02AV368UPDTHOUR_hrfana03AV369UPDTHOUR_hrfana04AV370UPDTHOUR_hrfana05AV371UPDTHOUR_hrfana06AV372UPDTHOUR_hrfana07AV373UPDTHOUR_hrfana08AV374UPDTHOUR_hrfana09AV375UPDTHOUR_hrfana10AV376UPDTHOUR_hrfana11AV377UPDTHOUR_hrfana12AV378UPDTHOUR_hrfana13AV379UPDTHOUR_hrfana14AV380UPDTHOUR_hrfanb01AV381UPDTHOUR_hrfanb02AV382UPDTHOUR_hrfanb03AV383UPDTHOUR_hrfanb04AV384UPDTHOUR_hrfanb05AV385UPDTHOUR_hrfanb06AV386UPDTHOUR_hrfanb07AV387UPDTHOUR_hrfanb08AV388UPDTHOUR_hrfanb09AV389UPDTHOUR_hrfanb10AV390UPDTHOUR_hrfanb11AV391UPDTHOUR_hrfanb12AV392UPDTHOUR_hrfanb13AV393UPDTHOUR_hrfanb14AV394MST_SLV_ms_selAV395MST_SLV_ms_ctrlAV396MST_SLV_slv_addrAV397MST_SLV_lead_selAV398MST_SLV_ll_bal_dAV399MST_SLV_lstr_timAV400MST_SLV_lead_pulAV401MST_SLV_start_dtAV402MST_SLV_lag_miniAV403MST_SLV_lag_pumpAV404CMP_PI_wt_kp_aAV405CMP_PI_wt_ti_aAV406CMP_PI_wt_ni_aAV407CMP_PI_dgt_kp_aAV408CMP_PI_dgt_ti_aAV409CMP_PI_dgt_ni_aAV410CMP_PI_cpt_kp_aAV411CMP_PI_cpt_ti_aAV412CMP_PI_cpt_ni_aAV413CMP_PI_dp_kp_aAV414CMP_PI_dp_ti_aAV415CMP_PI_dp_ni_aAV416CMP_PI_lsp_kp_aAV417CMP_PI_lsp_ti_aAV418CMP_PI_lsp_ni_aAV419CMP_PI_wt_kp_bAV420CMP_PI_wt_ti_bAV421CMP_PI_wt_ni_bAV422CMP_PI_dgt_kp_bAV423CMP_PI_dgt_ti_bAV424CMP_PI_dgt_ni_bAV425CMP_PI_cpt_kp_bAV426CMP_PI_cpt_ti_bAV427CMP_PI_cpt_ni_bAV428CMP_PI_dp_kp_bAV429CMP_PI_dp_ti_bAV430CMP_PI_dp_ni_bAV431CMP_PI_lsp_kp_bAV432CMP_PI_lsp_ti_bAV433CMP_PI_lsp_ni_bAV434EXV_CFG_fixeddshAV435EXV_CFG_scsp_maxAV436EXV_CFG_scsp_minAV437EXV_CFG_sh_sp_aAV438EXV_CFG_sh_sp_bAV439EXV_CFG_apr_stpAV440EXV_CFG_sbc_kp_aAV441EXV_CFG_sbc_ti_aAV442EXV_CFG_sbc_ni_aAV443EXV_CFG_dsh_kp_aAV444EXV_CFG_dsh_ti_aAV445EXV_CFG_dsh_ni_aAV446EXV_CFG_hsp_kp_aAV447EXV_CFG_hsp_ti_aAV448EXV_CFG_hsp_ni_aAV449EXV_CFG_lsp_kp_aAV450EXV_CFG_lsp_ti_aAV451EXV_CFG_lsp_ni_aAV452EXV_CFG_dop_kp_aAV453EXV_CFG_dop_ti_aAV454EXV_CFG_dop_ni_aAV455EXV_CFG_ssh_kp_aAV456EXV_CFG_ssh_ti_aAV457EXV_CFG_ssh_ni_aAV458EXV_CFG_sbc_kp_bAV459EXV_CFG_sbc_ti_bAV460EXV_CFG_sbc_ni_bAV461EXV_CFG_dsh_kp_bAV462EXV_CFG_dsh_ti_bAV463EXV_CFG_dsh_ni_bAV464EXV_CFG_hsp_kp_bAV465EXV_CFG_hsp_ti_bAV466EXV_CFG_hsp_ni_bAV467EXV_CFG_lsp_kp_bAV468EXV_CFG_lsp_ti_bAV469EXV_CFG_lsp_ni_bAV470EXV_CFG_dop_kp_bAV471EXV_CFG_dop_ti_bAV472EXV_CFG_dop_ni_bAV473EXV_CFG_ssh_kp_bAV474EXV_CFG_ssh_ti_bAV475EXV_CFG_ssh_ni_bAV476EXV_CFG_apr_kp_aAV477EXV_CFG_apr_ti_aAV478EXV_CFG_apr_ni_aAV479EXV_CFG_apr_kp_bAV480EXV_CFG_apr_ti_bAV481EXV_CFG_apr_ni_bAV482DELTA_wateesysAV483DELTA_chdp_hysAV484DELTA_chdtdactAV485DELTA_chdtdsptAV486DELTA_fhdp_hysAV487DELTA_fhdtdactAV488DELTA_fhdtdstpAV489DELTA_ldp_hysAV490DELTA_ldtdactAV491DELTA_ldtdsptAV492DELTA_hsp_hystAV493DELTA_hstdactAV494DELTA_hstdsptAV495DELTA_lsp_hystAV496DELTA_lstdactAV497DELTA_lstdsptAV498DELTA_lstdcpaAV499DELTA_mt_hystAV500DELTA_mt_dactAV501DELTA_mt_dsptAV502DELTA_dgt_hystAV503DELTA_dgt_actAV504DELTA_dgt_sptAV505DELTA_dsh_hystAV506DELTA_dsh_actAV507DELTA_dshdelayAV508DELTA_mopdelayAV509DELTA_sbc_hysAV510DELTA_sbc_actAV511DELTA_sbc_sptAV512DELTA_cramprtAV513BACNET_networkAV514BACNET_identAV515BACNET_bbmdAV516FAN_CFG_fldp_kpaAV517FAN_CFG_fldp_tiaAV518FAN_CFG_fldp_niaAV519FAN_CFG_fldp_kpbAV520FAN_CFG_fldp_tibAV521FAN_CFG_fldp_nibAV522FAN_CFG_fan_hlimAV523FAN_CFG_fan_llimAV524FAN_CFG_sync_KpAV525FAN_CFG_n_coilsAAV526FAN_CFG_n_coilsBAV527FAN_CFG_cp_factAAV528FAN_CFG_cp_factBAV529FAN_CFG_fldtfactAV530FAN_CFG_xt_s_smpAV531FAN_CFG_xt_in_tlAV532FAN_CFG_os_d_ampAV533FAN_CFG_os_d_perAV534FAN_CFG_os_f_powAV535FAN_CFG_xtos_fltAV536FAN_CFG_sct_biasAV537FAN_CFG_sct_timAV538FAN_CFG_sct_decrAV539ECO_PI_ecsh_kpaAV540ECO_PI_ecsh_tiaAV541ECO_PI_ecsh_niaAV542ECO_PI_ecsh_kpbAV543ECO_PI_ecsh_tibAV544ECO_PI_ecsh_nibAV545ECO_PI_eco_minAV546ECO_PI_eco_maxAV547ECO_PI_capa_limAV548ECO_PI_ecoshspaAV549ECO_PI_ecoshspbAV550SETPOINT_csp1AV551SETPOINT_csp2AV552SETPOINT_ice_spAV553SETPOINT_cramp_spAV554SETPOINT_lim_sp1AV555SETPOINT_lim_sp2AV556SETPOINT_lim_sp3AV557GENUNIT_CTRL_PNT_wrAV558GENUNIT_DEM_LIM_wrAV559GENUNIT_SP_SEL_wrBV1GENCONF_ramp_selBV2GENCONF_ice_cnfgBV3GENCONF_shortcycBV4PUMPCONF_pump_perBV5PUMPCONF_pump_locBV6GENUNIT_CHIL_S_S_rdBV7GENUNIT_CHIL_OCC_rdBV8GENUNIT_SP_OCC_rdBV9GENUNIT_EMSTOP_rdBV10INPUTS_ONOFF_SWBV11INPUTS_SETP_SWBV12INPUTS_LIM_SW1BV13INPUTS_LIM_SW2BV14INPUTS_OIL_L_ABV15INPUTS_OIL_L_BBV16INPUTS_REM_LOCKBV17INPUTS_ICE_SWBV18INPUTS_OCC_OVSWBV19INPUTS_HEATR_SWBV20OUTPUTS_LABEL_ABV21OUTPUTS_CP_ABV22OUTPUTS_OIL_SL_ABV23OUTPUTS_VI_ABV24OUTPUTS_ISO_OP_ABV25OUTPUTS_ISO_POSABV26OUTPUTS_OIL_HT_ABV27OUTPUTS_LABEL_BBV28OUTPUTS_CP_BBV29OUTPUTS_OIL_SL_BBV30OUTPUTS_VI_BBV31OUTPUTS_ISO_OP_BBV32OUTPUTS_ISO_POSBBV33OUTPUTS_OIL_HT_BBV34OUTPUTS_ALARMBV35OUTPUTS_RUNNINGBV36OUTPUTS_ALERTBV37OUTPUTS_SHUTDOWNBV38OUTPUTS_C_HEATERBV39OUTPUTS_FCA1BV40OUTPUTS_FCA2BV41OUTPUTS_FCA3BV42OUTPUTS_FCA4BV43OUTPUTS_FCA5BV44OUTPUTS_FCA6BV45OUTPUTS_FCA7BV46OUTPUTS_FCA8BV47OUTPUTS_FCB1BV48OUTPUTS_FCB2BV49OUTPUTS_FCB3BV50OUTPUTS_FCB4BV51OUTPUTS_FCB5BV52OUTPUTS_FCB6BV53OUTPUTS_FCB7BV54OUTPUTS_FCB8BV55OUTPUTS_VFD_EN_ABV56OUTPUTS_VFD_EN_BBV57OUTPUTS_BOX_HTRBV58PUMPSTAT_CPUMP_1_rdBV59PUMPSTAT_CPUMP_2_rdBV60PUMPSTAT_ROTCPUMP_rdBV61PUMPSTAT_FLOW_SWBV62PUMPSTAT_FLOW_SWBBV63MODES_m_delayBV64MODES_m_2stptBV65MODES_m_resetBV66MODES_m_demlimBV67MODES_m_pmprotBV68MODES_m_pmpperBV69MODES_m_nightBV70MODES_m_slaveBV71MODES_m_iceBV72ALARMRST_RST_ALMBV73VLT_DRV_SET_DRVABV74VLT_DRV_SET_DRVBBV75VLT_DRV_VLT_COMABV76VLT_DRV_VLT_COMBBV77M_MSTSLV_ms_activBV78M_MSTSLV_lead_selBV79M_MSTSLV_ll_changBV80M_MSTSLV_ll_pullBV81M_MSTSLV_cap_maxBV82FAN_DRV2_SET_FDA1BV83FAN_DRV2_SET_FDA2BV84FAN_DRV2_SET_FDA3BV85FAN_DRV2_SET_FDB1BV86FAN_DRV2_SET_FDB2BV87FAN_DRV2_SET_FDB3BV88FAN_DRV2_FD_COMA1BV89FAN_DRV2_FD_COMA2BV90FAN_DRV2_FD_COMA3BV91FAN_DRV2_FD_COMB1BV92FAN_DRV2_FD_COMB2BV93FAN_DRV2_FD_COMB3BV94FAN_DRV2_stopfanaBV95FAN_DRV2_stopfanbBV96FACTORY_freq_60HBV97FACTORY_probrineBV98FACTORY_heat_selBV99FACTORY_mst_slvBV100FACTORY_emm_nrcpBV101FACTORY_loamboptBV102FACTORY_leak_chkBV103FACTORY_fMaxEnABV104FACTORY_fMaxEnBBV105SERVICE1_ewt_optBV106SERVICE1_ser_passBV107SERVICE1_RFI_confBV108SERVICE1_metricBV109SERVICE1_fdrv_cfgBV110SERVICE1_cdrv_cfgBV111SERVICE1_auto_smBV112SERVICE1_ViChkEnBV113SERVICE1_AntiFrzBV114SERVICE1_http_enBV115SERVICE1_ftp_enBV116MST_SLV_ll_serieBV117BACNET_bacenaBV118BACNET_bacunitBV119FAN_CFG_fan_ctrlBV120FAN_CFG_xt_enablBV121CP_ENABL_en_cp_aBV122CP_ENABL_en_cp_bBV123GENUNIT_CHIL_S_S_wrBV124PUMPSTAT_CPUMP_1_wrBV125PUMPSTAT_CPUMP_2_wrBV126GENUNIT_EMSTOP_wrBV127PUMPSTAT_ROTCPUMP_wrBV128GENUNIT_SP_OCC_wrBV129GENUNIT_CHIL_OCC_wrBV130ALM_COOL_EWT_FBV131ALM_COOL_LWT_FBV132ALM_OAT_FBV133ALM_CHWSTEMP_FBV134ALM_SUCTION_T_A_FBV135ALM_SUCTION_T_B_FBV136ALM_DGT_A_T_FBV137ALM_DGT_B_T_FBV138ALM_LIQUID_T_A_FBV139ALM_LIQUID_T_B_FBV140ALM_CP_TMP_A_FBV141ALM_CP_TMP_B_FBV142ALM_ECO_T_A_FBV143ALM_ECO_T_B_FBV144ALM_SPACE_TEMP_FBV145ALM_DP_A_FBV146ALM_DP_B_FBV147ALM_SP_A_FBV148ALM_SP_B_FBV149ALM_OIL_P_A_FBV150ALM_OIL_P_B_FBV151ALM_ECO_P_A_FBV152ALM_ECO_P_B_FBV153ALM_LIQUID_P_A_FBV154ALM_LIQUID_P_B_FBV155ALM_SIOB1_COM_FBV156ALM_SIOB2_COM_FBV157ALM_AUX1_1_COM_FBV158ALM_AUX1_2_COM_FBV159ALM_AUX1_3_COM_FBV160ALM_AUX1_4_COM_FBV161ALM_EMM_BRD_COM_FBV162ALM_VLT_DRIVE1_COM_FBV163ALM_VLT_DRIVE2_COM_FBV164ALM_FAN_DRIVEA1_COM_FBV165ALM_FAN_DRIVEA2_COM_FBV166ALM_FAN_DRIVEA3_COM_FBV167ALM_FAN_DRIVEB1_COM_FBV168ALM_FAN_DRIVEB2_COM_FBV169ALM_FAN_DRIVEB3_COM_FBV170ALM_COOLER_FREEZE_FBV171ALM_LOW_SUCTION_A_FBV172ALM_LOW_SUCTION_B_FBV173ALM_LOCK_FBV174ALM_LOSS_COM_MS_FBV175ALM_LOW_OIL_A_P_FBV176ALM_LOW_OIL_B_P_FBV177ALM_OIL_FILT_A_P_FBV178ALM_OIL_FILT_B_P_FBV179ALM_OIL_DROP_A_P_FBV180ALM_OIL_DROP_B_P_FBV181ALM_LOW_OIL_LEVEL_A_FBV182ALM_LOW_OIL_LEVEL_B_FBV183ALM_M_S_CONFIG_FBV184ALM_INI_FACT_CONF_FBV185ALM_ILL_FACT_CONF_FBV186ALM_CCN_EMSTOP_FBV187ALM_COOL_PUMP1_FBV188ALM_COOL_PUMP2_FBV189ALM_SCT_OUT_OF_CP_M_A_FBV190ALM_SCT_OUT_OF_CP_M_B_FBV191ALM_REFRIG_ESCAPE_FBV192ALM_HIGH_DGT_A_FBV193ALM_HIGH_DGT_B_FBV194ALM_SUCT_VALV_CLOSD_A_FBV195ALM_SUCT_VALV_CLOSD_B_FBV196ALM_COOLER_FLOW_FBV197ALM_SENSORS_SWAP_FBV198ALM_SST_OUT_OF_CP_M_A_FBV199ALM_SST_OUT_OF_CP_M_B_FBV200ALM_VLT_DRIVE_A_FBV201ALM_VLT_DRIVE_B_FBV202ALM_FAN_DRIVE_A1_FBV203ALM_FAN_DRIVE_A2_FBV204ALM_FAN_DRIVE_A3_FBV205ALM_FAN_DRIVE_B1_FBV206ALM_FAN_DRIVE_B2_FBV207ALM_FAN_DRIVE_B3_FBV208ALM_VLT_DRIVE_A_ALERTBV209ALM_VLT_DRIVE_B_ALERTBV210ALM_FAN_DRIVE_A1_ALERTBV211ALM_FAN_DRIVE_A2_ALERTBV212ALM_FAN_DRIVE_A3_ALERTBV213ALM_FAN_DRIVE_B1_ALERTBV214ALM_FAN_DRIVE_B2_ALERTBV215ALM_FAN_DRIVE_B3_ALERTBV216ALM_HIGH_CP_TMP_A_FBV217ALM_HIGH_CP_TMP_B_FBV218ALM_HP_SWITCH_A_FBV219ALM_HP_SWITCH_B_FBV220ALM_DATABASE_FBV221ALM_LENSCAN_FBV222ALM_STEPPER_EXV_A_FBV223ALM_STEPPER_EXV_B_FBV224ALM_STEPPER_ECO_A_FBV225ALM_STEPPER_ECO_B_FBV226ALM_VI_DIAG_A_ALERTBV227ALM_VI_DIAG_B_ALERTTL1TL_STATUSTL2TL_SP_SELTL3TL_DEM_LIMTL4TL_COOL_EWTTL5TL_COOL_LWTTL6TL_OATTL7TL_SCT_ATL8TL_SST_ATL9TL_DGT_ATL10TL_CP_TMP_ATL11TL_ECO_T_ATL12TL_SCT_BTL13TL_SST_BTL14TL_DGT_BTL15TL_CP_TMP_BTL16TL_ECO_T_BTL17TL_ECO_P_ATL18TL_ECO_P_BTL19TL_OIL_L_ATL20TL_OIL_L_BTL21TL_HR_MACHTL22TL_st_machTL23TL_HR_CP_ATL24TL_st_cp_aTL25TL_HR_CP_BTL26TL_st_cp_bTL27TL_drv_pwraTL28TL_drv_IaTL29TL_drv_FaTL30TL_drv_pwrbTL31TL_drv_IbTL32TL_drv_FbTL33TL_drv_pwrTL34TL_ov_exv_aTL35TL_EXV_ATL36TL_ov_exv_bTL37TL_EXV_BTL38TL_ctrl_wtTL39TL_overridaTL40TL_cap_pc_aTL41TL_overridbTL42TL_cap_pc_bTL43TL_eco_aTL44TL_eco_bTL45TL_fan_f_aTL46TL_fan_f_bTL47TL_fd_pwra1TL48TL_fd_pwra2TL49TL_fd_pwrb1TL50TL_fd_pwrb2TL51TL_fd_pwr
Integration notes
- From Appendix E "BACnet IP Points" (manual pages 310-327). The table has no units column; temperatures and pressures follow the Metric Units setting (bacunit).
- Command points have a read object and a separate _wr object; the writable ones are BV 123-129, AV 557-559, the setpoints AV 550-556, BV 112, AV 347 and AV 9 (User Password).
- Most object names (754 of 786) also appear in the later 30XV-6T (PIC6.1) list, but only 359 keep the same type and instance; e.g. GENUNIT_CTRL_PNT_wr is AV 557 here and AV 552 there.
- The Trend Log table prints TL_fd_pwr and TL_fd_pwra1 to TL_fd_pwrb2 twice; each is listed once. SERVICE1_leak_thr (AV 343) has no access value printed and is listed as read-only.
- Alarm BV descriptions in the table are just the alarm code. The option column (IR, COV, CMD) and the BACnet/Modbus translator list (Appendix D) are not reproduced.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)
How many BACnet points does the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) have?
This list has 837 BACnet objects: 559 analog values, 227 binary values, 51 trend logs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet points are writable?
71 of the 837 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet documentation?
The source is AquaForce 30XV140-500, Series B Variable Speed Air-Cooled Liquid Chillers with Greenspeed Intelligence and Carrier Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E, BACnet IP Points) (30XV-3T), revision 6-19, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/06/30XV-3T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)?
Start with BV 123 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 129 GENUNIT_CHIL_OCC_wr (Network occupied command); AV 557 GENUNIT_CTRL_PNT_wr (Leaving water control point from the BMS); AV 558 GENUNIT_DEM_LIM_wr (Demand limit command); AV 20 GENUNIT_CTRL_TYP (Control type: Local, Network or Remote); AV 21 GENUNIT_STATUS (Running status); AV 30 TEMP_COOL_LWT (Leaving chilled water temperature); AV 29 TEMP_COOL_EWT (Entering chilled water temperature); AV 24 GENUNIT_CAP_T (Percent total capacity); AV 109 ALARMRST_ALM (Unit alarm state).
How do I enable BMS control of the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)?
Put the unit under network control (Network machine control method); start/stop and occupancy are then written to the _wr objects.
How do I check these points on the real AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points
Carrier AquaForce 30XV140-500 chillers with the Touch Pilot controller and the optional BACnet/Modbus Translator on BACnet MS/TP.
Also known as: 30XV, AquaForce 30XV, 30XV-2T, 30XV BACnet translator, BACnet/Modbus Translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points
Carrier AquaForce 30XV140-500 variable speed air-cooled screw chillers with the Touch Pilot display (original / Series A documentation, 2017).
Also known as: 30XV, AquaForce 30XV, 30XV-2T, 30XV Touch Pilot, 30XV Series A, Greenspeed 30XV - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaForce 30XV140-500, Series B Variable Speed Air-Cooled Liquid Chillers with Greenspeed Intelligence and Carrier Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E, BACnet IP Points) · 30XV-3T · rev. 6-19. Object names, instances and units are reproduced as published; descriptions are our own.