Air-cooled screw chiller controller · BACnet points list

Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet points list

Updated 12 November 2026

Short answer

This is the native BACnet object list from the 2019 edition of the 30XV Series B Carrier Controller manual: 559 AVs, 227 BVs and 51 Trend Logs named after their CCN table and point. Commands use separate _wr objects (start/stop, occupancy, control point, demand limit, emergency stop, pump commands) and each alarm has its own read-only BV. Many instance numbers differ from the later PIC6.1 list (Form 30XV-6T), so use the list that matches the controller software.

This page lists 837 BACnet objects for the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) — 71 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)
Equipment
Air-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
837 (71 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1600001
Also known as
30XV, AquaForce 30XV, 30XV-3T, 30XV Series B 2019, Carrier Controller, Greenspeed, 04-53300197-01
Source document
AquaForce 30XV140-500, Series B Variable Speed Air-Cooled Liquid Chillers with Greenspeed Intelligence and Carrier Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E, BACnet IP Points) · 30XV-3T · rev. 6-19
Download CSV 837 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)

Integration in brief

Enable BACnet (bacena), pick BACnet IP or MS/TP in the BACnet configuration menu and set the network and identifier, then put the machine under network control. Command through the _wr objects (start/stop, occupancy, control point, demand limit) and read run status, water temperatures, capacity and alarm state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 123GENUNIT_CHIL_S_S_wrNetwork start/stop commandWrite
BV 129GENUNIT_CHIL_OCC_wrNetwork occupied commandWrite
AV 557GENUNIT_CTRL_PNT_wrLeaving water control point from the BMSWrite
AV 558GENUNIT_DEM_LIM_wrDemand limit commandWrite
AV 20GENUNIT_CTRL_TYPControl type: Local, Network or RemoteRead
AV 21GENUNIT_STATUSRunning statusRead
AV 30TEMP_COOL_LWTLeaving chilled water temperatureRead
AV 29TEMP_COOL_EWTEntering chilled water temperatureRead
AV 24GENUNIT_CAP_TPercent total capacityRead
AV 109ALARMRST_ALMUnit alarm stateRead

Enable & remote start

Put the unit under network control (Network machine control method); start/stop and occupancy are then written to the _wr objects.

Network setup

Watch out for

Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

837 of 837 shown
Type
AnalogBinaryOther
Access
Show
Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet Points List
DescriptionStates
AV1GENCONF_prio_cirCir Priority SequenceRead0=Auto, 1=A Prio, 2=B Prio
AV2GENCONF_off_on_dUnit Off to On DelayRead
AV3GENCONF_lim_selDemand Limit Type SelectRead0=None, 1=Switch Control, 2=4-20mA Control
AV4GENCONF_nh_startNight Mode Start HourRead
AV5GENCONF_nh_endNight Mode End HourRead
AV6GENCONF_nh_limitNight Capacity LimitRead
AV7PUMPCONF_cpumpseqEvap Pumps SequenceRead0=No Pump, 1=One Pump Only, 2=Two Pumps Auto, 3=Pump#1 Manual, 4=Pump#2 Manual
AV8PUMPCONF_pump_delPump Auto Rotation DelayRead
AV9USERCONF_use_passUser PasswordWrite
AV10RESETCFG_cr_selCooling Reset SelectRead0=None, 1=OAT, 2=Delta T, 3=4-20mA control, 4=Space Temp
AV11RESETCFG_oat_crnoOAT No Reset ValueRead
AV12RESETCFG_oat_crfuOAT Full Reset ValueRead
AV13RESETCFG_dt_cr_noDelta T No Reset ValueRead
AV14RESETCFG_dt_cr_fuDelta T Full Reset ValueRead
AV15RESETCFG_v_cr_noCurrent No Reset ValueRead
AV16RESETCFG_v_cr_fuCurrent Full Reset ValueRead
AV17RESETCFG_spacr_noSpace T No Reset ValueRead
AV18RESETCFG_spacr_fuSpace T Full Reset ValueRead
AV19RESETCFG_cr_degCooling Reset Deg. ValueRead
AVmin20GENUNIT_CTRL_TYPLocal=0 Net.=1 Remote=2Read
AVmin21GENUNIT_STATUSRun StatusRead
AV22GENUNIT_min_leftMinutes Left for StartRead
AV23GENUNIT_SP_SEL_rdSetpoint Select, 0=Auto, 1=Spt1, 2=Spt2Read
AVmin24GENUNIT_CAP_TPercent Total CapacityRead
AV25GENUNIT_SPCurrent SetpointRead
AV26GENUNIT_CTRL_PNT_rdControl PointRead
AV27GENUNIT_DEM_LIM_rdActive Demand Limit ValRead
AV28GENUNIT_min_limDemand Limit MinimumRead
AVmin29TEMP_COOL_EWTEvap Entering FluidRead
AVmin30TEMP_COOL_LWTEvap Leaving FluidRead
AV31TEMP_OATOutdoor Air TemperatureRead
AV32TEMP_SCT_ASaturated Cond Tmp Cir ARead
AV33TEMP_SST_ASaturated Suction Temp ARead
AV34TEMP_SLT_ASaturated Liquid Temp ARead
AV35TEMP_SUCT_ACompressor Suction Tmp ARead
AV36TEMP_DGT_ADischarge Gas Temp Cir ARead
AV37TEMP_CP_TMP_AMotor Temperature Cir ARead
AV38TEMP_ECO_T_AEXV Eco. Tmp Cir ARead
AV39TEMP_LIQ_T_ALiquid Temperature ARead
AV40TEMP_SCT_BSaturated Cond Tmp Cir BRead
AV41TEMP_SST_BSaturated Suction Temp BRead
AV42TEMP_SLT_BSaturated Liquid Temp BRead
AV43TEMP_SUCT_BCompressor Suction Tmp BRead
AV44TEMP_DGT_BDischarge Gas Temp Cir BRead
AV45TEMP_CP_TMP_BMotor Temperature Cir BRead
AV46TEMP_ECO_T_BEXV Eco. Tmp Cir BRead
AV47TEMP_LIQ_T_BLiquid Temperature BRead
AV48TEMP_SPACETMPSpace Temp (Opt.)Read
AV49TEMP_CHWSTEMPChill Water Temp (Opt.)Read
AV50PRESSURE_DP_ADischarge Pressure ARead
AV51PRESSURE_SP_AMain Suction Pressure ARead
AV52PRESSURE_OP_AOil Pressure ARead
AV53PRESSURE_DOP_ADelta Oil Pressure ARead
AV54PRESSURE_ECO_P_AEconomizer Pressure ARead
AV55PRESSURE_LIQ_P_ALiquid Pressure ARead
AV56PRESSURE_DP_BDischarge Pressure BRead
AV57PRESSURE_SP_BMain Suction Pressure BRead
AV58PRESSURE_OP_BOil Pressure BRead
AV59PRESSURE_DOP_BDelta Oil Pressure BRead
AV60PRESSURE_ECO_P_BEconomizer Pressure BRead
AV61PRESSURE_LIQ_P_BLiquid Pressure BRead
AV62INPUTS_SP_RESETRemote Reset SetpointRead
AV63INPUTS_LIM_ANALRemote Dem. LimitRead
AV64INPUTS_leak_vLeakage Detector 1Read
AV65INPUTS_leak_2_vLeakage Detector 2Read
AV66OUTPUTS_CAPT010ACapacity Signal Cir ARead
AV67OUTPUTS_VFAN_AVariFan Speed ARead
AV68OUTPUTS_CAPT010BCapacity Signal Cir BRead
AV69OUTPUTS_VFAN_BVariFan Speed BRead
AV70OUTPUTS_CAPT_010Chiller Capacity SignalRead
AV71RUNTIME_HR_MACHMachine Operating HoursRead
AV72RUNTIME_st_machMachine StartsRead
AV73RUNTIME_HR_CP_ACompressor A HoursRead
AV74RUNTIME_st_cp_aCompressor A StartsRead
AV75RUNTIME_HR_CP_BCompressor B HoursRead
AV76RUNTIME_st_cp_bCompressor B StartsRead
AV77RUNTIME_hr_cpum1Evap Pump #1 HoursRead
AV78RUNTIME_hr_cpum2Evap Pump #2 HoursRead
AV79RUNTIME_VIctAVI Cycle Count ARead
AV80RUNTIME_VIctBVI Cycle Count BRead
AV81RUNTIME_hrfana01Circuit A Fan #1 HoursRead
AV82RUNTIME_hrfana02Circuit A Fan #2 HoursRead
AV83RUNTIME_hrfana03Circuit A Fan #3 HoursRead
AV84RUNTIME_hrfana04Circuit A Fan #4 HoursRead
AV85RUNTIME_hrfana05Circuit A Fan #5 HoursRead
AV86RUNTIME_hrfana06Circuit A Fan #6 HoursRead
AV87RUNTIME_hrfana07Circuit A Fan #7 HoursRead
AV88RUNTIME_hrfana08Circuit A Fan #8 HoursRead
AV89RUNTIME_hrfana09Circuit A Fan #9 HoursRead
AV90RUNTIME_hrfana10Circuit A Fan #10 HoursRead
AV91RUNTIME_hrfana11Circuit A Fan #11 HoursRead
AV92RUNTIME_hrfana12Circuit A Fan #12 HoursRead
AV93RUNTIME_hrfana13Circuit A Fan #13 HoursRead
AV94RUNTIME_hrfana14Circuit A Fan #14 HoursRead
AV95RUNTIME_hrfanb01Circuit B Fan #1 HoursRead
AV96RUNTIME_hrfanb02Circuit B Fan #2 HoursRead
AV97RUNTIME_hrfanb03Circuit B Fan #3 HoursRead
AV98RUNTIME_hrfanb04Circuit B Fan #4 HoursRead
AV99RUNTIME_hrfanb05Circuit B Fan #5 HoursRead
AV100RUNTIME_hrfanb06Circuit B Fan #6 HoursRead
AV101RUNTIME_hrfanb07Circuit B Fan #7 HoursRead
AV102RUNTIME_hrfanb08Circuit B Fan #8 HoursRead
AV103RUNTIME_hrfanb09Circuit B Fan #9 HoursRead
AV104RUNTIME_hrfanb10Circuit B Fan #10 HoursRead
AV105RUNTIME_hrfanb11Circuit B Fan #11 HoursRead
AV106RUNTIME_hrfanb12Circuit B Fan #12 HoursRead
AV107RUNTIME_hrfanb13Circuit B Fan #13 HoursRead
AV108RUNTIME_hrfanb14Circuit B Fan #14 HoursRead
AVmin109ALARMRST_ALMAlarm StateRead
AV110ALARMRST_alarm_1Jbus Current Alarm 1Read
AV111ALARMRST_alarm_2Jbus Current Alarm 2Read
AV112ALARMRST_alarm_3Jbus Current Alarm 3Read
AV113ALARMRST_alarm_4Jbus Current Alarm 4Read
AV114ALARMRST_alarm_5Jbus Current Alarm 5Read
AV115VLT_DRV_drv_pwraCir A Drive PowerRead
AV116VLT_DRV_drv_IaCir A Drive AmpsRead
AV117VLT_DRV_drv_VaCir A Drive VoltageRead
AV118VLT_DRV_drv_SaCir A Drive SpeedRead
AV119VLT_DRV_drv_FaCir A Drive FrequencyRead
AV120VLT_DRV_drv_TaCir A Drive TorqueRead
AV121VLT_DRV_drv_DCVaCir A Drive DC Link VoltRead
AV122VLT_DRV_drv_HSTaCir A Drive Heat Sink TRead
AV123VLT_DRV_drv_CCTaCir A Drive Ctrl Card TRead
AV124VLT_DRV_drv_HTRaCir A Drive HeaterRead
AV125VLT_DRV_drv_pwrbCir B Drive PowerRead
AV126VLT_DRV_drv_IbCir B Drive AmpsRead
AV127VLT_DRV_drv_VbCir B Drive VoltageRead
AV128VLT_DRV_drv_SbCir B Drive SpeedRead
AV129VLT_DRV_drv_FbCir B Drive FrequencyRead
AV130VLT_DRV_drv_TbCir B Drive TorqueRead
AV131VLT_DRV_drv_DCVbCir B Drive DC Link VoltRead
AV132VLT_DRV_drv_HSTbCir B Drive Heat Sink TRead
AV133VLT_DRV_drv_CCTbCir B Drive Ctrl Card TRead
AV134VLT_DRV_drv_HTRbCir B Drive HeaterRead
AV135VLT_DRV_drv_pwrTotal Comp Drive PowerRead
AV136LAST_POR_date_on1Power On 1 :day-mon-yearRead
AV137LAST_POR_time_on1Power On 1 :hour-minuteRead
AV138LAST_POR_date_of1PowerDown 1:day-mon-yearRead
AV139LAST_POR_time_of1PowerDown 1:hour-minuteRead
AV140LAST_POR_date_on2Power On 2 :day-mon-yearRead
AV141LAST_POR_time_on2Power On 2 :hour-minuteRead
AV142LAST_POR_date_of2PowerDown 2:day-mon-yearRead
AV143LAST_POR_time_of2PowerDown 2:hour-minuteRead
AV144LAST_POR_date_on3Power On 3 :day-mon-yearRead
AV145LAST_POR_time_on3Power On 3 :hour-minuteRead
AV146LAST_POR_date_of3PowerDown 3:day-mon-yearRead
AV147LAST_POR_time_of3PowerDown 3:hour-minuteRead
AV148LAST_POR_date_on4Power On 4 :day-mon-yearRead
AV149LAST_POR_time_on4Power On 4 :hour-minuteRead
AV150LAST_POR_date_of4PowerDown 4:day-mon-yearRead
AV151LAST_POR_time_of4PowerDown 4:hour-minuteRead
AV152LAST_POR_date_on5Power On 5 :day-mon-yearRead
AV153LAST_POR_time_on5Power On 5 :hour-minuteRead
AV154LAST_POR_date_of5PowerDown 5:day-mon-yearRead
AV155LAST_POR_time_of5PowerDown 5:hour-minuteRead
AV156EXV_CTRL_ov_exv_aEXV Override Circuit ARead
AV157EXV_CTRL_EXV_AEXV Position Circuit ARead
AV158EXV_CTRL_DSH_ADischarge Superheat ARead
AV159EXV_CTRL_dsh_spaDis. Superheat Setpnt ARead
AV160EXV_CTRL_SH_ASuction Superheat ARead
AV161EXV_CTRL_sh_sp_aSuct. Superheat Setpnt ARead
AV162EXV_CTRL_pinch_aEvap ExchangeDT Cir ARead
AV163EXV_CTRL_subcoolaSubcooling Circuit ARead
AV164EXV_CTRL_subc_spaSubcooling Setpoint ARead
AV165EXV_CTRL_exv_staEXV State ARead
AV166EXV_CTRL_exv_lstaEXV Previous State ARead
AV167EXV_CTRL_exvwposaEXV Wished Position ARead
AV168EXV_CTRL_ov_exv_bEXV Override Circuit BRead
AV169EXV_CTRL_EXV_BEXV Position Circuit BRead
AV170EXV_CTRL_DSH_BDischarge Superheat BRead
AV171EXV_CTRL_dsh_spbDis. Superheat Setpnt BRead
AV172EXV_CTRL_SH_BSuction Superheat BRead
AV173EXV_CTRL_sh_sp_bSuct. Superheat Setpnt BRead
AV174EXV_CTRL_pinch_bEvap ExchangeDT Cir BRead
AV175EXV_CTRL_subcoolbSubcooling Circuit BRead
AV176EXV_CTRL_subc_spbSubcooling Setpoint BRead
AV177EXV_CTRL_exv_stbEXV State BRead
AV178EXV_CTRL_exv_lstbEXV Previous State BRead
AV179EXV_CTRL_exvwposbEXV Wished Position BRead
AV180M_MSTSLV_slv_statSlave Chiller StateRead
AV181M_MSTSLV_slv_captSlave Chiller Total CapRead
AV182M_MSTSLV_l_strt_dLag Start DelayRead
AV183M_MSTSLV_ll_hr_dLead/lag Hours DeltaRead
AV184M_MSTSLV_ms_errorMaster/Slave ErrorRead
AV185M_MSTSLV_lagstatSlave lagstatRead
AV186M_MSTSLV_slav_hrSlave Operating HoursRead
AV187M_MSTSLV_slav_ewtSlave Evap Ent. FluidRead
AV188M_MSTSLV_slav_lwtSlave Evap Leav. FluidRead
AV189CAPACTRL_ctrl_wtControled Water TempRead
AV190CAPACTRL_cwt_rateCtrl Water Temp, Deg/MinRead
AV191CAPACTRL_cap_limCurrent Capacity LimitRead
AV192CAPACTRL_drvcmdaWished Comp. Frequency ARead
AV193CAPACTRL_capmodaCapa Ctrl Stat Nb ARead
AV194CAPACTRL_lcapmodaLast Capa Ctrl Stat Nb ARead
AV195CAPACTRL_overridaOverride Capacity Nb ARead
AV196CAPACTRL_cap_pc_aEstimated Capacity ARead
AV197CAPACTRL_drvcmdbWished Comp. Frequency BRead
AV198CAPACTRL_capmodbCapacity Ctrl Stat Nb BRead
AV199CAPACTRL_lcapmodbLast Capa Ctrl Stat Nb BRead
AV200CAPACTRL_overridbOverride Capacity Nb BRead
AV201CAPACTRL_cap_pc_bEstimated Capacity BRead
AV202CAPACTRL_cMaxFrqAMax Comp. Frequency ARead
AV203CAPACTRL_cMaxFrqBMax Comp. Frequency BRead
AV204CAPACTRL_viCmdAComp. VI Cmd ARead
AV205CAPACTRL_viCmdBComp. VI Cmd BRead
AV206CAPACTRL_resetReset AmountRead
AV207CAPACTRL_CirRunNbCircuit Running NumberRead
AV208CAPACTRL_StatCirAState of Circuit ARead
AV209CAPACTRL_StatCirBState of Circuit BRead
AV210CAPACTRL_DualMastDual Circuit MasterRead
AV211CAPACTRL_xSpdHighTransfer Spd, add cirRead
AV212CAPACTRL_xSpdLowTransfer Spd, remove cirRead
AV213LIMITS_dshactaEXV_dsh_act ARead
AV214LIMITS_dshstpaEXV_dsh_stp ARead
AV215LIMITS_elspactaEXV_lsp_act ARead
AV216LIMITS_elspstpaEXV_lsp_stp ARead
AV217LIMITS_chdpactaENV comp high dp act ARead
AV218LIMITS_chdpstpaENV comp high dp stp ARead
AV219LIMITS_fhdpactaENV fan high dp act ARead
AV220LIMITS_fhdpstpaENV fan high dp stp ARead
AV221LIMITS_ldpactaENV low dp act ARead
AV222LIMITS_ldpstpaENV low dp stp ARead
AV223LIMITS_hspactaENV high sp act ARead
AV224LIMITS_hspstpaENV high sp stp ARead
AV225LIMITS_lspactaENV low sp act ARead
AV226LIMITS_lspstpaENV low sp stp ARead
AV227LIMITS_lspdcpaENV low sp delta ARead
AV228LIMITS_dgtactadgt act ARead
AV229LIMITS_dgtstpadgt stp ARead
AV230LIMITS_dshactbEXV_dsh_act BRead
AV231LIMITS_dshstpbEXV_dsh_stp BRead
AV232LIMITS_elspactbEXV_lsp_act BRead
AV233LIMITS_elspstpbEXV_lsp_stp BRead
AV234LIMITS_chdpactbENV comp high dp act BRead
AV235LIMITS_chdpstpbENV comp high dp stp BRead
AV236LIMITS_fhdpactbENV fan high dp act BRead
AV237LIMITS_fhdpstpbENV fan high dp stp BRead
AV238LIMITS_ldpactbENV low dp act BRead
AV239LIMITS_ldpstpbENV low dp stp BRead
AV240LIMITS_hspactbENV high sp act BRead
AV241LIMITS_hspstpbENV high sp stp BRead
AV242LIMITS_lspactbENV low sp act BRead
AV243LIMITS_lspstpbENV low sp stp BRead
AV244LIMITS_lspdcpbENV low sp delta BRead
AV245LIMITS_dgtactbdgt_act BRead
AV246LIMITS_dgtstpbdgt_stp BRead
AV247ECO_CTRL_eco_aEXV Eco Position Cir ARead
AV248ECO_CTRL_eco_bEXV Eco Position Cir BRead
AV249FAN_CTRL_fan_f_aFan Freq Cir ARead
AV250FAN_CTRL_fan_staFan State ARead
AV251FAN_CTRL_fan_lstaFan Previous State ARead
AV252FAN_CTRL_wfan_f_aFan Wished Freq ARead
AV253FAN_CTRL_fan_modaFan Mode ARead
AV254FAN_CTRL_fan_txtaFan Mode Text ARead
AV255FAN_CTRL_ftotpowaFan Tot Pwr Filtered ARead
AV256FAN_CTRL_fcont_aFan Contactors On ARead
AV257FAN_CTRL_fan_f_bFan Freq Cir BRead
AV258FAN_CTRL_fan_stbFan State BRead
AV259FAN_CTRL_fan_lstbFan Previous State BRead
AV260FAN_CTRL_wfan_f_bFan Wished Freq BRead
AV261FAN_CTRL_fan_modbFan Mode BRead
AV262FAN_CTRL_fan_txtbFan Mode Text BRead
AV263FAN_CTRL_ftotpowbFan Tot Pwr Filtered BRead
AV264FAN_CTRL_fcont_bFan Contactors On BRead
AV265FAN_DRV_fd_pwra1Fan Drive Power A1Read
AV266FAN_DRV_fd_Ia1Fan Drive Amps A1Read
AV267FAN_DRV_fd_Va1Fan Drive Voltage A1Read
AV268FAN_DRV_fd_Sa1Fan Drive Speed A1Read
AV269FAN_DRV_fd_Fa1Fan Drive Frequency A1Read
AV270FAN_DRV_fd_Ta1Fan Drive Torque A1Read
AV271FAN_DRV_fd_DCVa1Fan Drv DC Link Volt A1Read
AV272FAN_DRV_fd_HSTa1Fan Drive Heat Sink T A1Read
AV273FAN_DRV_fd_CCTa1Fan Drive Ctrl Card T A1Read
AV274FAN_DRV_fd_pwra2Fan Drive Power A2Read
AV275FAN_DRV_fd_Ia2Fan Drive Amps A2Read
AV276FAN_DRV_fd_Va2Fan Drive Voltage A2Read
AV277FAN_DRV_fd_Sa2Fan Drive Speed A2Read
AV278FAN_DRV_fd_Fa2Fan Drive Frequency A2Read
AV279FAN_DRV_fd_Ta2Fan Drive Torque A2Read
AV280FAN_DRV_fd_DCVa2Fan Drv DC Link Volt A2Read
AV281FAN_DRV_fd_HSTa2Fan Drive Heat Sink T A2Read
AV282FAN_DRV_fd_CCTa2Fan Drive Ctrl Card T A2Read
AV283FAN_DRV_fd_pwra3Fan Drive Power A3Read
AV284FAN_DRV_fd_Ia3Fan Drive Amps A3Read
AV285FAN_DRV_fd_Va3Fan Drive Voltage A3Read
AV286FAN_DRV_fd_Sa3Fan Drive Speed A3Read
AV287FAN_DRV_fd_Fa3Fan Drive Frequency A3Read
AV288FAN_DRV_fd_Ta3Fan Drive Torque A3Read
AV289FAN_DRV_fd_DCVa3Fan Drv DC Link Volt A3Read
AV290FAN_DRV_fd_HSTa3Fan Drive Heat Sink T A3Read
AV291FAN_DRV_fd_CCTa3Fan Drive Ctrl Card T A3Read
AV292FAN_DRV_fd_pwrb1Fan Drive Power B1Read
AV293FAN_DRV_fd_Ib1Fan Drive Amps B1Read
AV294FAN_DRV_fd_Vb1Fan Drive Voltage B1Read
AV295FAN_DRV_fd_Sb1Fan Drive Speed B1Read
AV296FAN_DRV_fd_Fb1Fan Drive Frequency B1Read
AV297FAN_DRV_fd_Tb1Fan Drive Torque B1Read
AV298FAN_DRV_fd_DCVb1Fan Drv DC Link Volt B1Read
AV299FAN_DRV_fd_HSTb1Fan Drive Heat Sink T B1Read
AV300FAN_DRV_fd_CCTb1Fan Drive Ctrl Card T B1Read
AV301FAN_DRV_fd_pwrb2Fan Drive Power B2Read
AV302FAN_DRV_fd_Ib2Fan Drive Amps B2Read
AV303FAN_DRV_fd_Vb2Fan Drive Voltage B2Read
AV304FAN_DRV_fd_Sb2Fan Drive Speed B2Read
AV305FAN_DRV_fd_Fb2Fan Drive Frequency B2Read
AV306FAN_DRV_fd_Tb2Fan Drive Torque B2Read
AV307FAN_DRV_fd_DCVb2Fan Drv DC Link Volt B2Read
AV308FAN_DRV_fd_HSTb2Fan Drive Heat Sink T B2Read
AV309FAN_DRV_fd_CCTb2Fan Drive Ctrl Card T B2Read
AV310FAN_DRV_fd_pwrb3Fan Drive Power B3Read
AV311FAN_DRV_fd_Ib3Fan Drive Amps B3Read
AV312FAN_DRV_fd_Vb3Fan Drive Voltage B3Read
AV313FAN_DRV_fd_Sb3Fan Drive Speed B3Read
AV314FAN_DRV_fd_Fb3Fan Drive Frequency B3Read
AV315FAN_DRV_fd_Tb3Fan Drive Torque B3Read
AV316FAN_DRV_fd_DCVb3Fan Drv DC Link Volt B3Read
AV317FAN_DRV_fd_HSTb3Fan Drive Heat Sink T B3Read
AV318FAN_DRV_fd_CCTb3Fan Drive Ctrl Card T B3Read
AV319FAN_DRV_fd_pwrTotal Fan Drive PowerRead
AV320FACTORY_unitsizeUnit CapacityRead
AV321FACTORY_voltagePower Supply VoltageRead
AV322FACTORY_mfg_tierTier 0=STD, 1=MID, 2=HIRead
AV323FACTORY_cpass_nbEvap Pass NumberRead
AV324FACTORY_fac_passFactory PasswordRead
AV325FACTORY_fMaxOvrAMax Frequency Override ARead
AV326FACTORY_fMaxOvrBMax Frequency Override BRead
AV327FACTORY_fan_factFan Freq Factor(0.7-1.1)Read
AV328FACTORY_fMinOvrMin Frequency OverrideRead
AV329FACTORY_lastspdaLow Amb. Start Spd ARead
AV330FACTORY_lastspdbLow Amb. Start Spd BRead
AV331FACTORY2_exvmax_aEXV A Maximum Steps NumbRead
AV332FACTORY2_exvmax_bEXV B Maximum Steps NumbRead
AV333FACTORY2_eco_cnfaEconomizer A Steps NumbRead
AV334FACTORY2_eco_cnfbEconomizer B Steps NumbRead
AV335FACTORY2_vfd_cmpNb VFD CompressorRead
AV336FACTORY2_vfd_fanaNb Fan Drive Cir ARead
AV337FACTORY2_vfd_fanbNb Fan Drive Cir BRead
AV338SERVICE1_flui_typEvaporator Fluid TypeRead1=Water, 2=Med Brine, 3=Low Brine
AV339SERVICE1_freezespBrine Freeze SetpointRead
AV340SERVICE1_mini_lwtBrine Minimum Fluid TempRead
AV341SERVICE1_fastcaprFast Capacity RecoveryRead
AV342SERVICE1_ewt_cirAEWT Probe on Cir A SideRead
AV343SERVICE1_leak_thrLeakage Charge ThresholdRead
AV344SERVICE1_leak_tmrLeakage Charge TimerRead
AV345SERVICE1_heaterspEvap Heater Delta SptRead
AV346SERVICE1_freez_ovFreeze Override OffsetRead
AV347SERVICE1_ViPwrChkVI Self-Test ThresholdWrite
AV348SERVICE1_odtrspdOil Delta Trigger SpeedRead
AV349SERVICE1_otrigtimOil Trigger TimeRead
AV350SERVICE1_odrecspdOil Delta Recover SpeedRead
AV351SERVICE1_orectimOil Recover TimeRead
AV352SERVICE1_wateesysWater Temp HysteresisRead
AV353SERVICE1_vistrtdtHigh VI Time at StartRead
AV354SERVICE1_vistrtenEnable High VI at StartRead
AV355SERVICE1_apr_enApproach Ctrl at Start??Read
AV356UPDTHOUR_hr_machMachine Operating HoursRead
AV357UPDTHOUR_st_machMachine Starts NumberRead
AV358UPDTHOUR_hr_cp_aCompressor A HoursRead
AV359UPDTHOUR_st_cp_aCompressor A StartsRead
AV360UPDTHOUR_hr_cp_bCompressor B HoursRead
AV361UPDTHOUR_st_cp_bCompressor B StartsRead
AV362UPDTHOUR_hr_cpum1Evap Pump #1 HoursRead
AV363UPDTHOUR_hr_cpum2Evap Pump #2 HoursRead
AV364UPDTHOUR_VIctAVI Cycle Count ARead
AV365UPDTHOUR_VIctBVI Cycle Count BRead
AV366UPDTHOUR_hrfana01Circuit A Fan #1 HoursRead
AV367UPDTHOUR_hrfana02Circuit A Fan #2 HoursRead
AV368UPDTHOUR_hrfana03Circuit A Fan #3 HoursRead
AV369UPDTHOUR_hrfana04Circuit A Fan #4 HoursRead
AV370UPDTHOUR_hrfana05Circuit A Fan #5 HoursRead
AV371UPDTHOUR_hrfana06Circuit A Fan #6 HoursRead
AV372UPDTHOUR_hrfana07Circuit A Fan #7 HoursRead
AV373UPDTHOUR_hrfana08Circuit A Fan #8 HoursRead
AV374UPDTHOUR_hrfana09Circuit A Fan #9 HoursRead
AV375UPDTHOUR_hrfana10Circuit A Fan #10 HoursRead
AV376UPDTHOUR_hrfana11Circuit A Fan #11 HoursRead
AV377UPDTHOUR_hrfana12Circuit A Fan #12 HoursRead
AV378UPDTHOUR_hrfana13Circuit A Fan #13 HoursRead
AV379UPDTHOUR_hrfana14Circuit A Fan #14 HoursRead
AV380UPDTHOUR_hrfanb01Circuit B Fan #1 HoursRead
AV381UPDTHOUR_hrfanb02Circuit B Fan #2 HoursRead
AV382UPDTHOUR_hrfanb03Circuit B Fan #3 HoursRead
AV383UPDTHOUR_hrfanb04Circuit B Fan #4 HoursRead
AV384UPDTHOUR_hrfanb05Circuit B Fan #5 HoursRead
AV385UPDTHOUR_hrfanb06Circuit B Fan #6 HoursRead
AV386UPDTHOUR_hrfanb07Circuit B Fan #7 HoursRead
AV387UPDTHOUR_hrfanb08Circuit B Fan #8 HoursRead
AV388UPDTHOUR_hrfanb09Circuit B Fan #9 HoursRead
AV389UPDTHOUR_hrfanb10Circuit B Fan #10 HoursRead
AV390UPDTHOUR_hrfanb11Circuit B Fan #11 HoursRead
AV391UPDTHOUR_hrfanb12Circuit B Fan #12 HoursRead
AV392UPDTHOUR_hrfanb13Circuit B Fan #13 HoursRead
AV393UPDTHOUR_hrfanb14Circuit B Fan #14 HoursRead
AV394MST_SLV_ms_selMaster/Slave SelectRead0=Disable, 1=Master, 2=Slave
AV395MST_SLV_ms_ctrlMaster Control TypeRead1=Local Control, 2=Remote Control, 3=CCN Control
AV396MST_SLV_slv_addrSlave AddressRead
AV397MST_SLV_lead_selLead Lag SelectRead0=Always Lead, 1=Lag Once Failed Only, 2=Lead/Lag Runtime Sel
AV398MST_SLV_ll_bal_dLead/Lag Balance DeltaRead
AV399MST_SLV_lstr_timLead/Lag Start TimerRead
AV400MST_SLV_lead_pulLead Pulldown TimeRead
AV401MST_SLV_start_dtStart If Error HigherRead
AV402MST_SLV_lag_miniLag Minimum Running TimeRead
AV403MST_SLV_lag_pumpLag Unit Pump ControlRead0=Stop if Unit Stops, 1=Run if Unit Stops
AV404CMP_PI_wt_kp_aWater Temp PI, Kp, Cir ARead
AV405CMP_PI_wt_ti_aWater Temp PI, Ti Cir ARead
AV406CMP_PI_wt_ni_aWater Temp PI, NI Cir ARead
AV407CMP_PI_dgt_kp_aDGT PI Kp, Cir ARead
AV408CMP_PI_dgt_ti_aDGT PI, Ti Cir ARead
AV409CMP_PI_dgt_ni_aDGT PI, NI Cir ARead
AV410CMP_PI_cpt_kp_aComp Temp PI, Kp Cir ARead
AV411CMP_PI_cpt_ti_aComp Temp PI, Ti Cir ARead
AV412CMP_PI_cpt_ni_aComp Temp PI, NI Cir ARead
AV413CMP_PI_dp_kp_aDisch Press PI, Kp Cir ARead
AV414CMP_PI_dp_ti_aDisch Press PI, Ti Cir ARead
AV415CMP_PI_dp_ni_aDisch Press PI, NI Cir ARead
AV416CMP_PI_lsp_kp_aLow SP PI, Kp Cir ARead
AV417CMP_PI_lsp_ti_aLow SP PI, Ti Cir ARead
AV418CMP_PI_lsp_ni_aLow SP PI, NI Cir ARead
AV419CMP_PI_wt_kp_bWater Temp PI, Kp, Cir BRead
AV420CMP_PI_wt_ti_bWater Temp PI, Ti Cir BRead
AV421CMP_PI_wt_ni_bWater Temp PI, NI Cir BRead
AV422CMP_PI_dgt_kp_bDGT PI Kp, Cir BRead
AV423CMP_PI_dgt_ti_bDGT PI, Ti Cir BRead
AV424CMP_PI_dgt_ni_bDGT PI, NI Cir BRead
AV425CMP_PI_cpt_kp_bComp Temp PI, Kp Cir BRead
AV426CMP_PI_cpt_ti_bComp Temp PI, Ti Cir BRead
AV427CMP_PI_cpt_ni_bComp Temp PI, NI Cir BRead
AV428CMP_PI_dp_kp_bDisch Press PI, Kp Cir BRead
AV429CMP_PI_dp_ti_bDisch Press PI, Ti Cir BRead
AV430CMP_PI_dp_ni_bDisch Press PI, NI Cir BRead
AV431CMP_PI_lsp_kp_bLow SP PI, Kp Cir BRead
AV432CMP_PI_lsp_ti_bLow SP PI, Ti Cir BRead
AV433CMP_PI_lsp_ni_bLow SP PI, NI Cir BRead
AV434EXV_CFG_fixeddshFixed DSH SetpointRead
AV435EXV_CFG_scsp_maxSubcooling Setpoint MaxRead
AV436EXV_CFG_scsp_minSubcooling Setpoint MinRead
AV437EXV_CFG_sh_sp_aSuperheat Setpoint ARead
AV438EXV_CFG_sh_sp_bSuperheat Setpoint BRead
AV439EXV_CFG_apr_stpApproach SetpointRead
AV440EXV_CFG_sbc_kp_aSubcool PI, Kp Cir ARead
AV441EXV_CFG_sbc_ti_aSubcool PI, Ti Cir ARead
AV442EXV_CFG_sbc_ni_aSubcool PI, NI Cir ARead
AV443EXV_CFG_dsh_kp_aDSH PI, Kp Cir ARead
AV444EXV_CFG_dsh_ti_aDSH PI, Ti Cir ARead
AV445EXV_CFG_dsh_ni_aDSH PI, NI Cir ARead
AV446EXV_CFG_hsp_kp_aHigh SP PI, Kp Cir ARead
AV447EXV_CFG_hsp_ti_aHigh SP PI, Ti Cir ARead
AV448EXV_CFG_hsp_ni_aHigh SP PI, NI Cir ARead
AV449EXV_CFG_lsp_kp_aLow SP PI, Kp Cir ARead
AV450EXV_CFG_lsp_ti_aLow SP PI, Ti Cir ARead
AV451EXV_CFG_lsp_ni_aLow SP PI, NI Cir ARead
AV452EXV_CFG_dop_kp_aDop PI, Kp Cir ARead
AV453EXV_CFG_dop_ti_aDop PI, Ti Cir ARead
AV454EXV_CFG_dop_ni_aDop PI, NI Cir ARead
AV455EXV_CFG_ssh_kp_aSuction SH PI, Kp Cir ARead
AV456EXV_CFG_ssh_ti_aSuction SH PI, Ti Cir ARead
AV457EXV_CFG_ssh_ni_aSuction SH PI, NI Cir ARead
AV458EXV_CFG_sbc_kp_bSubcool PI, Kp Cir BRead
AV459EXV_CFG_sbc_ti_bSubcool PI, Ti Cir BRead
AV460EXV_CFG_sbc_ni_bSubcool PI, NI Cir BRead
AV461EXV_CFG_dsh_kp_bDSH PI, Kp Cir BRead
AV462EXV_CFG_dsh_ti_bDSH PI, Ti Cir BRead
AV463EXV_CFG_dsh_ni_bDSH PI, NI Cir BRead
AV464EXV_CFG_hsp_kp_bHigh SP PI, Kp Cir BRead
AV465EXV_CFG_hsp_ti_bHigh SP PI, Ti Cir BRead
AV466EXV_CFG_hsp_ni_bHigh SP PI, NI Cir BRead
AV467EXV_CFG_lsp_kp_bLow SP PI, Kp Cir BRead
AV468EXV_CFG_lsp_ti_bLow SP PI, Ti Cir BRead
AV469EXV_CFG_lsp_ni_bLow SP PI, NI Cir BRead
AV470EXV_CFG_dop_kp_bDop PI, Kp Cir BRead
AV471EXV_CFG_dop_ti_bDop PI, Ti Cir BRead
AV472EXV_CFG_dop_ni_bDop PI, NI Cir BRead
AV473EXV_CFG_ssh_kp_bSuction SH PI, Kp Cir BRead
AV474EXV_CFG_ssh_ti_bSuction SH PI, Ti Cir BRead
AV475EXV_CFG_ssh_ni_bSuction SH PI, NI Cir BRead
AV476EXV_CFG_apr_kp_aAppr. PI, Kp Cir ARead
AV477EXV_CFG_apr_ti_aAppr. PI, Ti Cir ARead
AV478EXV_CFG_apr_ni_aAppr. PI, NI Cir ARead
AV479EXV_CFG_apr_kp_bAppr. PI, Kp Cir BRead
AV480EXV_CFG_apr_ti_bAppr. PI, Ti Cir BRead
AV481EXV_CFG_apr_ni_bAppr. PI, NI Cir BRead
AV482DELTA_wateesyswater_t_hysteresisRead
AV483DELTA_chdp_hyscmp high dp hysteresisRead
AV484DELTA_chdtdactcmp high dt act offsetRead
AV485DELTA_chdtdsptcmp high dt stp offsetRead
AV486DELTA_fhdp_hysfan high dp hysteresisRead
AV487DELTA_fhdtdactfan high dt act offsetRead
AV488DELTA_fhdtdstpfan high dt stp offsetRead
AV489DELTA_ldp_hyslow dp hysteresisRead
AV490DELTA_ldtdactlow dt act offsetRead
AV491DELTA_ldtdsptlow dt stp offsetRead
AV492DELTA_hsp_hysthigh sp hysteresisRead
AV493DELTA_hstdacthigh st act offsetRead
AV494DELTA_hstdspthigh st stp offsetRead
AV495DELTA_lsp_hystlow sp hysteresisRead
AV496DELTA_lstdactlow st act offsetRead
AV497DELTA_lstdsptlow st stp offsetRead
AV498DELTA_lstdcpadeltat lstEXV vs lstCAPARead
AV499DELTA_mt_hystmotor temp hysteresisRead
AV500DELTA_mt_dactmotor temp act offsetRead
AV501DELTA_mt_dsptmotor temp stp offsetRead
AV502DELTA_dgt_hystdgt hysteresisRead
AV503DELTA_dgt_actdgt limit act offsetRead
AV504DELTA_dgt_sptdgt limit spt offsetRead
AV505DELTA_dsh_hystdsh hysteresisRead
AV506DELTA_dsh_actdsh act offsetRead
AV507DELTA_dshdelayexv_no_dsh_delayRead
AV508DELTA_mopdelayexv_no_mop_delayRead
AV509DELTA_sbc_hyssubcool hysteresisRead
AV510DELTA_sbc_actsubcool act offsetRead
AV511DELTA_sbc_sptSubcooling Setpoint ARead
AV512DELTA_cramprtCompressor Ramp RateRead
AV513BACNET_networkNetworkRead
AV514BACNET_identIdentifierRead
AV515BACNET_bbmdBACnet Management DeviceRead
AV516FAN_CFG_fldp_kpaFan Low DP PI, Kp, Cir ARead
AV517FAN_CFG_fldp_tiaFan Low DP PI, Ti Cir ARead
AV518FAN_CFG_fldp_niaFan Low DP PI, NI Cir ARead
AV519FAN_CFG_fldp_kpbFan Low DP PI, Kp, Cir BRead
AV520FAN_CFG_fldp_tibFan Low DP PI, Ti Cir BRead
AV521FAN_CFG_fldp_nibFan Low DP PI, NI Cir BRead
AV522FAN_CFG_fan_hlimFan Max FrequencyRead
AV523FAN_CFG_fan_llimFan Min FrequencyRead
AV524FAN_CFG_sync_KpSychronizing Output KpRead
AV525FAN_CFG_n_coilsACir Cond Coil Number ARead
AV526FAN_CFG_n_coilsBCir Cond Coil Number BRead
AV527FAN_CFG_cp_factACompressor Factor ARead
AV528FAN_CFG_cp_factBCompressor Factor BRead
AV529FAN_CFG_fldtfactFan Low Dis. FactorRead
AV530FAN_CFG_xt_s_smpStablility Sample NbRead
AV531FAN_CFG_xt_in_tlOpt. Deviation ToleranceRead
AV532FAN_CFG_os_d_ampOpt. Disturbance Ampl.Read
AV533FAN_CFG_os_d_perOpt. Disturbance PeriodRead
AV534FAN_CFG_os_f_powOpt. Freeze Power Tol.Read
AV535FAN_CFG_xtos_fltOpt. Filter TimeRead
AV536FAN_CFG_sct_biasSCT bias at startRead
AV537FAN_CFG_sct_timTotal SCT bias timeRead
AV538FAN_CFG_sct_decrDecrement SCT bias timeRead
AV539ECO_PI_ecsh_kpaEXV Eco. SH Kp, Cir ARead
AV540ECO_PI_ecsh_tiaEXV Eco. SH Ti Cir ARead
AV541ECO_PI_ecsh_niaEXV Eco. SH NI Cir ARead
AV542ECO_PI_ecsh_kpbEXV Eco. SH Kp, Cir BRead
AV543ECO_PI_ecsh_tibEXV Eco. SH Ti Cir BRead
AV544ECO_PI_ecsh_nibEXV Eco. SH NI Cir BRead
AV545ECO_PI_eco_minEXV Eco. Min PositionRead
AV546ECO_PI_eco_maxEXV Eco. Max PositionRead
AV547ECO_PI_capa_limCapacity Lim Disable EcoRead
AV548ECO_PI_ecoshspaEco Superheat Setpoint ARead
AV549ECO_PI_ecoshspbEco Superheat Setpoint BRead
AV550SETPOINT_csp1Cooling Setpoint 1Write
AV551SETPOINT_csp2Cooling Setpoint 2Write
AV552SETPOINT_ice_spCooling Ice SetpointWrite
AV553SETPOINT_cramp_spCooling Ramp LoadingWrite
AV554SETPOINT_lim_sp1Switch Limit Setpoint 1Write
AV555SETPOINT_lim_sp2Switch Limit Setpoint 2Write
AV556SETPOINT_lim_sp3Switch Limit Setpoint 3Write
AVmin557GENUNIT_CTRL_PNT_wrControl PointWrite
AVmin558GENUNIT_DEM_LIM_wrActive Demand Limit ValWrite
AV559GENUNIT_SP_SEL_wrSetpoint SelectWrite
BV1GENCONF_ramp_selRamp Loading EnableRead
BV2GENCONF_ice_cnfgIce Mode EnableRead
BV3GENCONF_shortcycShort Cycle ManagementRead
BV4PUMPCONF_pump_perPump Sticking ProtectionRead
BV5PUMPCONF_pump_locFlow Checked If Pump OffRead
BV6GENUNIT_CHIL_S_S_rdNet.: Cmd Start/StopRead
BV7GENUNIT_CHIL_OCC_rdNet.: Cmd OccupiedRead
BV8GENUNIT_SP_OCC_rdSetpoint Occupied?Read
BV9GENUNIT_EMSTOP_rdEmergency StopRead
BV10INPUTS_ONOFF_SWRemote On/Off SwitchRead
BV11INPUTS_SETP_SWRemote Setpoint SwitchRead
BV12INPUTS_LIM_SW1Limit Switch 1Read
BV13INPUTS_LIM_SW2Limit Switch 2Read
BV14INPUTS_OIL_L_AOil Level Input ARead
BV15INPUTS_OIL_L_BOil Level Input BRead
BV16INPUTS_REM_LOCKCustomer InterlockRead
BV17INPUTS_ICE_SWIce Done Storage SwitchRead
BV18INPUTS_OCC_OVSWOccupied Override SwitchRead
BV19INPUTS_HEATR_SWEvap Heater DetectorRead
BV20OUTPUTS_LABEL_ACIRCUIT ARead
BV21OUTPUTS_CP_ACompressor ARead
BV22OUTPUTS_OIL_SL_AOil Solenoid Output ARead
BV23OUTPUTS_VI_AVI Solenoid Output ARead
BV24OUTPUTS_ISO_OP_ARef Iso Relay Energize ARead
BV25OUTPUTS_ISO_POSARef Iso Valve State ARead
BV26OUTPUTS_OIL_HT_AOil Heater Output ARead
BV27OUTPUTS_LABEL_BCIRCUIT BRead
BV28OUTPUTS_CP_BCompressor BRead
BV29OUTPUTS_OIL_SL_BOil Solenoid Output BRead
BV30OUTPUTS_VI_BVI Solenoid Output BRead
BV31OUTPUTS_ISO_OP_BRef Iso Relay Energize BRead
BV32OUTPUTS_ISO_POSBRef Iso Valve State BRead
BV33OUTPUTS_OIL_HT_BOil Heater Output BRead
BV34OUTPUTS_ALARMAlarm Relay StatusRead
BV35OUTPUTS_RUNNINGRunning Relay StatusRead
BV36OUTPUTS_ALERTAlert Relay StateRead
BV37OUTPUTS_SHUTDOWNShutdown Indicator StateRead
BV38OUTPUTS_C_HEATEREvap Heater OutputRead
BV39OUTPUTS_FCA1Fan Contactor 1ARead
BV40OUTPUTS_FCA2Fan Contactor 2ARead
BV41OUTPUTS_FCA3Fan Contactor 3ARead
BV42OUTPUTS_FCA4Fan Contactor 4ARead
BV43OUTPUTS_FCA5Fan Contactor 5ARead
BV44OUTPUTS_FCA6Fan Contactor 6ARead
BV45OUTPUTS_FCA7Fan Contactor 7ARead
BV46OUTPUTS_FCA8Fan Contactor 8ARead
BV47OUTPUTS_FCB1Fan Contactor 1BRead
BV48OUTPUTS_FCB2Fan Contactor 2BRead
BV49OUTPUTS_FCB3Fan Contactor 3BRead
BV50OUTPUTS_FCB4Fan Contactor 4BRead
BV51OUTPUTS_FCB5Fan Contactor 5BRead
BV52OUTPUTS_FCB6Fan Contactor 6BRead
BV53OUTPUTS_FCB7Fan Contactor 7BRead
BV54OUTPUTS_FCB8Fan Contactor 8BRead
BV55OUTPUTS_VFD_EN_AComp. HW Enable ARead
BV56OUTPUTS_VFD_EN_BComp. HW Enable BRead
BV57OUTPUTS_BOX_HTRControl Box HeaterRead
BV58PUMPSTAT_CPUMP_1_rdEvap Pump #1 CommandRead
BV59PUMPSTAT_CPUMP_2_rdEvap Pump #2 CommandRead
BV60PUMPSTAT_ROTCPUMP_rdRotate Evap Pumps ?Read
BV61PUMPSTAT_FLOW_SWEvap Flow Switch #1Read
BV62PUMPSTAT_FLOW_SWBEvap Flow Switch #2Read
BV63MODES_m_delayStart Up Delay In EffectRead
BV64MODES_m_2stptSecond Setpoint In UseRead
BV65MODES_m_resetReset In EffectRead
BV66MODES_m_demlimDemand Limit ActiveRead
BV67MODES_m_pmprotEvaporator Pump RotationRead
BV68MODES_m_pmpperPump Periodic StartRead
BV69MODES_m_nightNight Low Noise ActiveRead
BV70MODES_m_slaveMaster Slave ActiveRead
BV71MODES_m_iceIce Mode In Effect, Active Alarms:Read
BV72ALARMRST_RST_ALMAlarm ResetRead
BV73VLT_DRV_SET_DRVADrive A AttachRead
BV74VLT_DRV_SET_DRVBDrive B AttachRead
BV75VLT_DRV_VLT_COMAComm with Drive A OkRead
BV76VLT_DRV_VLT_COMBComm with Drive B OkRead
BV77M_MSTSLV_ms_activMaster/Slave Ctrl ActiveRead
BV78M_MSTSLV_lead_selLead Unit is the:Read
BV79M_MSTSLV_ll_changLead/lag Changeover?Read
BV80M_MSTSLV_ll_pullLead Pulldown ?Read
BV81M_MSTSLV_cap_maxMax Available Capacity ?Read
BV82FAN_DRV2_SET_FDA1Fan Drive A1 AttachRead
BV83FAN_DRV2_SET_FDA2Fan Drive A2 AttachRead
BV84FAN_DRV2_SET_FDA3Fan Drive A3 AttachRead
BV85FAN_DRV2_SET_FDB1Fan Drive B1 AttachRead
BV86FAN_DRV2_SET_FDB2Fan Drive B2 AttachRead
BV87FAN_DRV2_SET_FDB3Fan Drive B3 AttachRead
BV88FAN_DRV2_FD_COMA1Comm Fan Drive A1 OkRead
BV89FAN_DRV2_FD_COMA2Comm Fan Drive A2 OkRead
BV90FAN_DRV2_FD_COMA3Comm Fan Drive A3 OkRead
BV91FAN_DRV2_FD_COMB1Comm Fan Drive B1 OkRead
BV92FAN_DRV2_FD_COMB2Comm Fan Drive B2 OkRead
BV93FAN_DRV2_FD_COMB3Comm Fan Drive B3 OkRead
BV94FAN_DRV2_stopfanaStop Cir A Fan DriveRead
BV95FAN_DRV2_stopfanbStop Cir B Fan DriveRead
BV96FACTORY_freq_60H60Hz Sel (No=50, Yes=60)Read
BV97FACTORY_probrineProcess Brine EvapRead
BV98FACTORY_heat_selEvap Heater InstalledRead
BV99FACTORY_mst_slvMaster Slave SetupRead
BV100FACTORY_emm_nrcpEnergy Management ModuleRead
BV101FACTORY_loamboptLow Ambient Option (STD)Read
BV102FACTORY_leak_chkLeakage Charge DetectionRead
BV103FACTORY_fMaxEnAEnable Max Frequency ARead
BV104FACTORY_fMaxEnBEnable Max Frequency BRead
BV105SERVICE1_ewt_optEntering Fluid ControlRead
BV106SERVICE1_ser_passService PasswordRead
BV107SERVICE1_RFI_confCompressor RFI Filter EnRead
BV108SERVICE1_metricMetric Units? (Blackbox)Read
BV109SERVICE1_fdrv_cfgSend fan drive config?Read
BV110SERVICE1_cdrv_cfgSend comp. drive config?Read
BV111SERVICE1_auto_smAuto Start When SM LostRead
BV112SERVICE1_ViChkEnVI Self-Test EnableWrite
BV113SERVICE1_AntiFrzPump Rot. AntiFrz ProtecRead
BV114SERVICE1_http_enHTTP ServerRead
BV115SERVICE1_ftp_enFTP ServerRead
BV116MST_SLV_ll_serieChiller In SeriesRead
BV117BACNET_bacenaBACnet EnableRead
BV118BACNET_bacunitMetric Units? (Blackbox)Read
BV119FAN_CFG_fan_ctrlFan Ctrl Type (Vari,Fix), Optimization ParametersRead
BV120FAN_CFG_xt_enablOptimization EnableRead
BV121CP_ENABL_en_cp_aCompressor A DisableRead
BV122CP_ENABL_en_cp_bCompressor B DisableRead
BVmin123GENUNIT_CHIL_S_S_wrNet.: Cmd Start/StopWrite
BV124PUMPSTAT_CPUMP_1_wrEvap Pump #1 CommandWrite
BV125PUMPSTAT_CPUMP_2_wrEvap Pump #2 CommandWrite
BV126GENUNIT_EMSTOP_wrEmergency StopWrite
BV127PUMPSTAT_ROTCPUMP_wrRotate Evap Pumps ?Write
BV128GENUNIT_SP_OCC_wrSetpoint Occupied?Write
BVmin129GENUNIT_CHIL_OCC_wrNet.: Cmd OccupiedWrite
BV130ALM_COOL_EWT_FCOOL_EWT_FRead
BV131ALM_COOL_LWT_FCOOL_LWT_FRead
BV132ALM_OAT_FOAT_FRead
BV133ALM_CHWSTEMP_FCHWSTEMP_FRead
BV134ALM_SUCTION_T_A_FSUCTION_T_A_FRead
BV135ALM_SUCTION_T_B_FSUCTION_T_B_FRead
BV136ALM_DGT_A_T_FDGT_A_T_FRead
BV137ALM_DGT_B_T_FDGT_B_T_FRead
BV138ALM_LIQUID_T_A_FLIQUID_T_A_FRead
BV139ALM_LIQUID_T_B_FLIQUID_T_B_FRead
BV140ALM_CP_TMP_A_FCP_TMP_A_FRead
BV141ALM_CP_TMP_B_FCP_TMP_B_FRead
BV142ALM_ECO_T_A_FECO_T_A_FRead
BV143ALM_ECO_T_B_FECO_T_B_FRead
BV144ALM_SPACE_TEMP_FSPACE_TEMP_FRead
BV145ALM_DP_A_FDP_A_FRead
BV146ALM_DP_B_FDP_B_FRead
BV147ALM_SP_A_FSP_A_FRead
BV148ALM_SP_B_FSP_B_FRead
BV149ALM_OIL_P_A_FOIL_P_A_FRead
BV150ALM_OIL_P_B_FOIL_P_B_FRead
BV151ALM_ECO_P_A_FECO_P_A_FRead
BV152ALM_ECO_P_B_FECO_P_B_FRead
BV153ALM_LIQUID_P_A_FLIQUID_P_A_FRead
BV154ALM_LIQUID_P_B_FLIQUID_P_B_FRead
BV155ALM_SIOB1_COM_FSIOB1_COM_FRead
BV156ALM_SIOB2_COM_FSIOB2_COM_FRead
BV157ALM_AUX1_1_COM_FAUX1_1_COM_FRead
BV158ALM_AUX1_2_COM_FAUX1_2_COM_FRead
BV159ALM_AUX1_3_COM_FAUX1_3_COM_FRead
BV160ALM_AUX1_4_COM_FAUX1_4_COM_FRead
BV161ALM_EMM_BRD_COM_FEMM_BOARD_COM_FRead
BV162ALM_VLT_DRIVE1_COM_FVLT_DRIVE1_COM_FRead
BV163ALM_VLT_DRIVE2_COM_FVLT_DRIVE2_COM_FRead
BV164ALM_FAN_DRIVEA1_COM_FFAN_DRIVEA1_COM_FRead
BV165ALM_FAN_DRIVEA2_COM_FFAN_DRIVEA2_COM_FRead
BV166ALM_FAN_DRIVEA3_COM_FFAN_DRIVEA3_COM_FRead
BV167ALM_FAN_DRIVEB1_COM_FFAN_DRIVEB1_COM_FRead
BV168ALM_FAN_DRIVEB2_COM_FFAN_DRIVEB2_COM_FRead
BV169ALM_FAN_DRIVEB3_COM_FFAN_DRIVEB3_COM_FRead
BV170ALM_COOLER_FREEZE_FCOOLER_FREEZE_FRead
BV171ALM_LOW_SUCTION_A_FLOW_SUCTION_A_FRead
BV172ALM_LOW_SUCTION_B_FLOW_SUCTION_B_FRead
BV173ALM_LOCK_FLOCK_FRead
BV174ALM_LOSS_COM_MS_FLOSS_COM_MS_FRead
BV175ALM_LOW_OIL_A_P_FLOW_OIL_A_P_FRead
BV176ALM_LOW_OIL_B_P_FLOW_OIL_B_P_FRead
BV177ALM_OIL_FILT_A_P_FOIL_FILT_A_P_FRead
BV178ALM_OIL_FILT_B_P_FOIL_FILT_B_P_FRead
BV179ALM_OIL_DROP_A_P_FOIL_DROP_A_P_FRead
BV180ALM_OIL_DROP_B_P_FOIL_DROP_B_P_FRead
BV181ALM_LOW_OIL_LEVEL_A_FLOW_OIL_LEVEL_A_FRead
BV182ALM_LOW_OIL_LEVEL_B_FLOW_OIL_LEVEL_B_FRead
BV183ALM_M_S_CONFIG_FM_S_CONFIG_FRead
BV184ALM_INI_FACT_CONF_FINI_FACT_CONF_FRead
BV185ALM_ILL_FACT_CONF_FILL_FACT_CONF_FRead
BV186ALM_CCN_EMSTOP_FCCN_EMSTOP_FRead
BV187ALM_COOL_PUMP1_FCOOL_PUMP1_FRead
BV188ALM_COOL_PUMP2_FCOOL_PUMP2_FRead
BV189ALM_SCT_OUT_OF_CP_M_A_FSCT_OUT_OF_CP_MAP_A_FRead
BV190ALM_SCT_OUT_OF_CP_M_B_FSCT_OUT_OF_CP_MAP_B_FRead
BV191ALM_REFRIG_ESCAPE_FREFRIGERANT_ESCAPE_FRead
BV192ALM_HIGH_DGT_A_FHIGH_DGT_A_FRead
BV193ALM_HIGH_DGT_B_FHIGH_DGT_B_FRead
BV194ALM_SUCT_VALV_CLOSD_A_FSUCT_VALV_CLOSED_A_FRead
BV195ALM_SUCT_VALV_CLOSD_B_FSUCT_VALV_CLOSED_B_FRead
BV196ALM_COOLER_FLOW_FCOOLER_FLOW_FRead
BV197ALM_SENSORS_SWAP_FSENSORS_SWAP_FRead
BV198ALM_SST_OUT_OF_CP_M_A_FSST_OUT_OF_CP_MAP_A_FRead
BV199ALM_SST_OUT_OF_CP_M_B_FSST_OUT_OF_CP_MAP_B_FRead
BV200ALM_VLT_DRIVE_A_FVLT_DRIVE_A_FRead
BV201ALM_VLT_DRIVE_B_FVLT_DRIVE_B_FRead
BV202ALM_FAN_DRIVE_A1_FFAN_DRIVE_A1_FRead
BV203ALM_FAN_DRIVE_A2_FFAN_DRIVE_A2_FRead
BV204ALM_FAN_DRIVE_A3_FFAN_DRIVE_A3_FRead
BV205ALM_FAN_DRIVE_B1_FFAN_DRIVE_B1_FRead
BV206ALM_FAN_DRIVE_B2_FFAN_DRIVE_B2_FRead
BV207ALM_FAN_DRIVE_B3_FFAN_DRIVE_B3_FRead
BV208ALM_VLT_DRIVE_A_ALERTVLT_DRIVE_A_ALERTRead
BV209ALM_VLT_DRIVE_B_ALERTVLT_DRIVE_B_ALERTRead
BV210ALM_FAN_DRIVE_A1_ALERTFAN_DRIVE_A1_ALERTRead
BV211ALM_FAN_DRIVE_A2_ALERTFAN_DRIVE_A2_ALERTRead
BV212ALM_FAN_DRIVE_A3_ALERTFAN_DRIVE_A3_ALERTRead
BV213ALM_FAN_DRIVE_B1_ALERTFAN_DRIVE_B1_ALERTRead
BV214ALM_FAN_DRIVE_B2_ALERTFAN_DRIVE_B2_ALERTRead
BV215ALM_FAN_DRIVE_B3_ALERTFAN_DRIVE_B3_ALERTRead
BV216ALM_HIGH_CP_TMP_A_FHIGH_CP_TMP_A_FRead
BV217ALM_HIGH_CP_TMP_B_FHIGH_CP_TMP_B_FRead
BV218ALM_HP_SWITCH_A_FHP_SWITCH_A_FRead
BV219ALM_HP_SWITCH_B_FHP_SWITCH_B_FRead
BV220ALM_DATABASE_FDATABASE_FRead
BV221ALM_LENSCAN_FLENSCAN_FRead
BV222ALM_STEPPER_EXV_A_FSTEPPER_EXV_A_FRead
BV223ALM_STEPPER_EXV_B_FSTEPPER_EXV_B_FRead
BV224ALM_STEPPER_ECO_A_FSTEPPER_ECO_A_FRead
BV225ALM_STEPPER_ECO_B_FSTEPPER_ECO_B_FRead
BV226ALM_VI_DIAG_A_ALERTVI_DIAG_A_ALERTRead
BV227ALM_VI_DIAG_B_ALERTVI_DIAG_B_ALERTRead
TL1TL_STATUSRun StatusWrite
TL2TL_SP_SELSetpoint SelectWrite
TL3TL_DEM_LIMActive Demand Limit ValWrite
TL4TL_COOL_EWTEvap Entering FluidWrite
TL5TL_COOL_LWTEvap Leaving FluidWrite
TL6TL_OATOutdoor Air TemperatureWrite
TL7TL_SCT_ASaturated Cond Tmp Cir AWrite
TL8TL_SST_ASaturated Suction Temp AWrite
TL9TL_DGT_ADischarge Gas Temp Cir AWrite
TL10TL_CP_TMP_AMotor Temperature Cir AWrite
TL11TL_ECO_T_AEXV Eco. Tmp Cir AWrite
TL12TL_SCT_BSaturated Cond Tmp Cir BWrite
TL13TL_SST_BSaturated Suction Temp BWrite
TL14TL_DGT_BDischarge Gas Temp Cir BWrite
TL15TL_CP_TMP_BMotor Temperature Cir BWrite
TL16TL_ECO_T_BEXV Eco. Tmp Cir BWrite
TL17TL_ECO_P_AEconomizer Pressure AWrite
TL18TL_ECO_P_BEconomizer Pressure BWrite
TL19TL_OIL_L_AOil Level Input AWrite
TL20TL_OIL_L_BOil Level Input BWrite
TL21TL_HR_MACHMachine Operating HoursWrite
TL22TL_st_machMachine StartsWrite
TL23TL_HR_CP_ACompressor A HoursWrite
TL24TL_st_cp_aCompressor A StartsWrite
TL25TL_HR_CP_BCompressor B HoursWrite
TL26TL_st_cp_bCompressor B StartsWrite
TL27TL_drv_pwraCir A Drive PowerWrite
TL28TL_drv_IaCir A Drive AmpsWrite
TL29TL_drv_FaCir A Drive FrequencyWrite
TL30TL_drv_pwrbCir B Drive PowerWrite
TL31TL_drv_IbCir B Drive AmpsWrite
TL32TL_drv_FbCir B Drive FrequencyWrite
TL33TL_drv_pwrTotal Comp Drive PowerWrite
TL34TL_ov_exv_aEXV Override Circuit AWrite
TL35TL_EXV_AEXV Position Circuit AWrite
TL36TL_ov_exv_bEXV Override Circuit BWrite
TL37TL_EXV_BEXV Position Circuit BWrite
TL38TL_ctrl_wtControled Water TempWrite
TL39TL_overridaOverride Capacity Nb AWrite
TL40TL_cap_pc_aEstimated Capacity AWrite
TL41TL_overridbOverride Capacity Nb BWrite
TL42TL_cap_pc_bEstimated Capacity BWrite
TL43TL_eco_aEXV Eco Position Cir AWrite
TL44TL_eco_bEXV Eco Position Cir BWrite
TL45TL_fan_f_aFan Freq Cir AWrite
TL46TL_fan_f_bFan Freq Cir BWrite
TL47TL_fd_pwra1Fan Drive Power A1Write
TL48TL_fd_pwra2Fan Drive Power A2Write
TL49TL_fd_pwrb1Fan Drive Power B1Write
TL50TL_fd_pwrb2Fan Drive Power B2Write
TL51TL_fd_pwrTotal Fan Drive PowerWrite
Object ID lookup: Carrier AquaForce 30XV 140-500 Series B, Carrier Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)

How many BACnet points does the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) have?

This list has 837 BACnet objects: 559 analog values, 227 binary values, 51 trend logs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet points are writable?

71 of the 837 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T) BACnet documentation?

The source is AquaForce 30XV140-500, Series B Variable Speed Air-Cooled Liquid Chillers with Greenspeed Intelligence and Carrier Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E, BACnet IP Points) (30XV-3T), revision 6-19, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/06/30XV-3T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)?

Start with BV 123 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 129 GENUNIT_CHIL_OCC_wr (Network occupied command); AV 557 GENUNIT_CTRL_PNT_wr (Leaving water control point from the BMS); AV 558 GENUNIT_DEM_LIM_wr (Demand limit command); AV 20 GENUNIT_CTRL_TYP (Control type: Local, Network or Remote); AV 21 GENUNIT_STATUS (Running status); AV 30 TEMP_COOL_LWT (Leaving chilled water temperature); AV 29 TEMP_COOL_EWT (Entering chilled water temperature); AV 24 GENUNIT_CAP_T (Percent total capacity); AV 109 ALARMRST_ALM (Unit alarm state).

How do I enable BMS control of the Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)?

Put the unit under network control (Network machine control method); start/stop and occupancy are then written to the _wr objects.

How do I check these points on the real AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaForce 30XV140-500, Series B Variable Speed Air-Cooled Liquid Chillers with Greenspeed Intelligence and Carrier Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E, BACnet IP Points) · 30XV-3T · rev. 6-19. Object names, instances and units are reproduced as published; descriptions are our own.