  4. MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)

Rooftop unit controller · BACnet points list

Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) BACnet points list

Updated 7 November 2026

Short answer

The 2026 edition of the MicroTech Applied Air integration guide adds Rebel DPS with R-32, refrigeration-only (ROC) units and DCSA split condensing systems to the Rebel Applied list. It joins BACnet IP or BACnet MS/TP through a plug-in communication module. Compared with the 2022 Rebel Applied list it adds a third refrigerant circuit, A2L refrigerant sensor objects, VFD fan options, defrost and occupancy-source status, and many new compressor event BIs, and drops the power and IAQ monitoring objects. Most writable inputs only apply when AHU Loc/Net (MV 19) is Network at the HMI.

This page lists 445 BACnet objects for the Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) — 96 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Equipment
Rooftop unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
445 (96 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Application 2506036306, BACnet firmware 11.78 (PICS)
Also known as
Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8
Source document
MicroTech Applied Air Network Integration Guide, BACnet and LonWorks Communication Protocols · ED 19117-8 · rev. 2026-06
Download CSV 445 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)

Integration in brief

Set AHU Loc/Net to Network at the HMI, then drive the unit with Occupancy Mode or Current State, plus Application Mode and the occupied setpoints. Use Emergency Override to stop the unit from the network, and read Unit State, unit status, capacities, temperatures and the alarm objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 7OccManCmdOccupancy mode command (Occ/Unocc/TntOvrd/Standby/Auto)Write
MV 8CurrentStateOccupancy Scheduler Input when Occupancy Mode is AutoWrite
MV 10EmergOverrideNetwork shutdown (Off) / NormalWrite
MV 5ApplicCmdApplication mode (off/heat/cool/fan only/auto)Write
AV 10OccCoolSPOccupied cooling setpointWrite
AV 12OccHeatSPOccupied heating setpointWrite
MV 19AHULoc/NetMust read Network for network inputs to applyRead
MV 15UnitStateCurrent operating stateRead
AI 1DischAirTempDischarge air temperatureRead
AV 29ActiveFaultHighest-priority active fault number, 0 = noneRead

Enable & remote start

AHU Loc/Net (MV 19) must be set to Network at the HMI (it is read-only over BACnet) for most network inputs to apply. Occupancy is then commanded with Occupancy Mode (MV 7) or, when MV 7 is Auto, Current State (MV 8). Emergency Override (MV 10) = Off shuts the unit off (Unit Status OffNet) and only writing Normal restarts it. Application Mode (MV 5) only acts when Control Mode is Auto, which is set at the HMI. Cooling, heating and economizer can be enabled or capped from the network with AV 36/37, AV 38/39 and AV 34/35 (Ctrl Mode = Auto).

Heartbeat & communication loss

No BACnet heartbeat (Receive Heartbeat is listed as N/A for BACnet IP and MS/TP). Values written by the BAS stay at the last valid value if communication is lost; an invalid network value makes the controller use its default, and network sensor inputs fall back to the local sensor.

Sensors & values from the BMS

Space Temperature Input (AV 31) and Outdoor Air Temperature Input (AV 32) take network temperatures and revert to the local sensor if the network value becomes unreliable. Network inputs also exist for space humidity (AV 20/21), space CO2 (AV 33), supply and return fan capacity (AV 24/25) and outdoor air damper minimum and maximum position (AV 17/55). A LonWorks value takes precedence over the BACnet one if both are present.

Network setup

Watch out for

Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

445 of 445 shown
Type
Multi-stateOther
Access
Show
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) BACnet Points List
DescriptionStates
MVmin15UnitStateUnit StateRead1=Off, 2=Start, 3=Recirc, 4=FanOnly, 5=MinDAT, 6=Htg, 7=Econo, 8=Clg
MV1DaikinStatusUnit StatusRead1=Enable, 2=OffMan, 3=OffManCtrl, 4=OffNet, 5=OffAlm, 6=OffRetry, 7=OffPassVnt, 8=OffSnsrCfg, 9=OffEvac
MV2ClgStatusCooling StatusRead1=Enabled, 2=None, 3=OffAmb, 4=OffAlm, 5=OffNet, 6=OffMan, 7=NA, 8=CfgErr
AV36CoolEnablePrimary Cool EnableWrite-1=Null, 0=Off (Disabled), 1=Enable
AV37CoolEnablePctPrimary Cool Enable%Write
MV3EconoStatusEconomizer StatusRead1=Enabled, 2=None, 3=OffAmb, 4=OffAlm, 5=OffNet, 6=OffMan, 7=OffDehum, 8=CfgErr
AV34EconEnableEconomizer EnableWrite-1=Null, 0=Off (Disabled), 1=Enable
AV35EconEnablePctEconomizer Enable%Write
MV4PrimaryHtgStatusHeating StatusRead1=Enabled, 2=None, 3=OffAmb, 4=OffAlm, 5=OffNet, 6=OffMan, 7=OffDehum, 8=CfgErr
MV27SecondaryHtgStatusSecondary Heating StatusRead1=Enabled, 2=None, 3=OffAmb, 4=OffAlm, 5=OffNet, 6=OffMan, 7=NA, 8=NA
AV38HeatEnablePrimary Heat EnableWrite-1=Null, 0=Off (Disabled), 1=Enable
AV39HeatEnablePctPrimary Heat Enable%Write
AV16EconCapacityOutdoor Air Damper Position%Read
MVmin5ApplicCmdApplication ModeWrite1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly, 5=Auto, 6=NA
MVmin10EmergOverrideEmergency OverrideWrite1=Normal, 2=Off
MV16UnitSupportBACnet Units of MeasurementWrite1=Metric, 2=English
MV14VAVBoxOutputVAV Box Output StatusRead1=Heat, 2=Cool
MVmin19AHULoc/NetUnit Local/Network ControlRead1=Network, 2=Local
MV21DehumStatusDehumidification StatusRead1=Inactive, 2=Active
MV22DemandShedNetwork Demand Shed EnableWrite1=Inactive, 2=Auto, 3=Manual
MV23MWUStatusMorning Warmup StatusRead1=Inactive, 2=Active
MV24FreeClgStatusFree Cooling StatusRead1=Unavail, 2=Avail
MV25RemSptSrcRemote Setpoint SourceWrite1=None, 2=AI, 3=QMX1, 4=QMX2, 5=QMX3
MV49DefrostStatusDefrost StatusRead1=Inactive, 2=Active
AI21FilterPress1Filter Pressure InputinWCRead
AI22FilterPress2Filter Pressure InputinWCRead
AI23FilterPress3Filter Pressure InputinWCRead
MV6EffectOccupOccupancy StatusRead1=Occ, 2=Unocc, 3=TntOvrd
MV46OccSrcOccupancy SourceRead1=None, 2=NetSchd, 3=IntSchd, 4=OneEvnt, 5=RemoteSw, 6=NetManCmd, 7=OccMode, 8=TstatTO, 9=ManTO, 10=UnitDsbld
MV47UnoccSrcUnoccupancy SourceRead1=UnoccDehum, 2=UnoccClg, 3=UnoccHtg, 4=IntOptStrt, 5=NetOptStrt, 6=IntPurge, 7=NetPurge, 8=None, 9=A2LSnsrPrb, 10=A2LLeakPrb
MV48MinOASrcMinimum Outdoor Air SourceRead1=VentLmt, 2=OAFlw, 3=ExtAI, 4=CO2, 5=PM25, 6=TVOC, 7=Network, 8=BSP, 9=RstTLmt, 10=MaxPos, 11=HiDwpt, 12=FanDiff, 13=ZeroOA
MVmin7OccManCmdOccupancy Mode (Network)Write1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby, 5=Auto
MVmin8CurrentStateCurrent StateWrite1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby, 5=NA
MV9NextStateNext StateWrite1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby, 5=NA
AV3TimeToNextStateTime to Next StateWrite
AV53MaxPurgeTimeMaximum Purge TimeminWrite
AI3EffSpaceTempEffective Space Temperature°FRead
AV31SpaceTempInputSpace Temperature Input°FWrite
AI4SpaceTemp1Space Temperature Sensor 1°FRead
AI5SpaceTemp2Space Temperature Sensor 2°FRead
AI6SpaceTemp3Space Temperature Sensor 3°FRead
AI2RATempReturn Air Temperature Sensor°FRead
MV20CtrlTempSrcControl Temp SourceWrite1=RAT, 2=Space, 3=OAT, 4=None
AI14ControlTempControl Temperature°FRead
AI8OutdoorTempEffective Outdoor Air Temperature°FRead
AV5LocalOATempOutdoor Air Temperature°FRead
AV32OutdoorTempInputOutdoor Air Temperature Input°FWrite
AV26EffDATempSPEffective Discharge Air Temperature Setpoint°FRead
AImin1DischAirTempDischarge Air Temperature Sensor°FRead
AI7EFT_LCTEntering Fan/Leaving Coil Temperature Sensor°FRead
AI50C1DischLnTemp1Discharge Line Refrigerant Temperature Circuit 1°FRead
AI69C1DischLnTemp3Discharge Line Refrigerant Temperature Circuit 1°FRead
AI70C1DischLnTemp5Discharge Line Refrigerant Temperature Circuit 1°FRead
AI60C2DischLnTempDischarge Line Refrigerant Temperature Circuit 2°FRead
AI71C2DischLnTemp4Discharge Line Refrigerant Temperature Circuit 2°FRead
AI72C2DischLnTemp6Discharge Line Refrigerant Temperature Circuit 2°FRead
AI54C1RefLiqLnTempLiquid Line Refrigerant Temperature Circuit 1°FRead
AI64C2RefLiqLnTempLiquid Line Refrigerant Temperature Circuit 2°FRead
AI55VCmp1TempVariable Compressor 1 Temperature°FRead
AI65VCmp2TempVariable Compressor 2 Temperature°FRead
AI135VCmp3TempVariable Compressor 3 Temperature°FRead
AI56C1FCmp1TempFixed Compressor 1 Temperature Circuit 1°FRead
AI57C1FCmp3TempFixed Compressor 3 Temperature Circuit 1°FRead
AI58C1FCmp5TempFixed Compressor 5 Temperature Circuit 1°FRead
AI66C2FCmp2TempFixed Compressor 2 Temperature Circuit 2°FRead
AI67C2FCmp4TempFixed Compressor 4 Temperature Circuit 2°FRead
AI68C2FCmp6TempFixed Compressor 6 Temperature Circuit 2°FRead
AI136C3FCmp1TempFixed Compressor 1 Temperature Circuit 3°FRead
AI137C3FCmp3TempFixed Compressor 3 Temperature Circuit 3°FRead
AI138C3FCmp5TempFixed Compressor 5 Temperature Circuit 3°FRead
MV104SAFTypeSupply Air Fan TypeRead1=Anlg, 2=1M, 3=2M, 4=3M, 5=4M, 6=6M, 7=8M, 8=9M, 9=SAFVFD, 10=8M4S, 11=8M8S
MV28SAF1StatusSupply Air Fan 1-6 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV
MV29SAF2StatusSupply Air Fan 1-6 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV
MV30SAF3StatusSupply Air Fan 1-6 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV
MV31SAF4StatusSupply Air Fan 1-6 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV
MV32SAF5StatusSupply Air Fan 1-6 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV
MV33SAF6StatusSupply Air Fan 1-6 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV
MV11SupFanCtrlSupply Fan Capacity ControlWrite1=DSP, 2=Spd/Net, 3=1ZnVAV, 4=BSP, 5=CO2, 6=Flow, 7=CAV
AV7SAFDSPSptSupply Fan Duct Static Pressure Setpoint (DSP)inWCWrite
MV112StaticPSensDuct Static Pressure SensorRead1=NA:NA, 2=DSP:NA, 3=DSP:DSP, 4=DSP:BSP, 5=BSP:NA, 6=NA:DSP, 7=NA:BSP
AV8SAFBSPSptSupply Fan Building Static Pressure (BSP) SetpointinWCWrite
AV24SupFanCapNetInSupply Fan Capacity Input%Write
AI10SAFCapEffective Supply Fan Capacity%Read
AI19SAFDSPSupply Fan Duct Static PressureinWCRead
AI29SAFFlowSupply Fan AirflowCFMRead
AV56SAFFlowSptSupply Fan Flow SetpointCFMWrite
MV110SAFFlowInputSupply Fan Flow InputRead1=None, 2=1Fan, 3=2Fan, 4=3Fan, 5=4Fan, 6=6Fan
AV58SAFOAFlowSptSupply Fan Outdoor Air Flow SetpointCFMWrite
MV105RFEFTypeReturn Air Fan TypeRead1=None, 2=RFAnlg, 3=EFAnlg, 4=1ECMRF, 5=2ECMRF, 6=3ECMRF, 7=4ECMRF, 8=1ECMEF, 9=2ECMEF, 10=3ECMEF, 11=4ECMEF, 12=RFVFD, 13=EFVFD
AV25RFEFCapNetInReturn Fan Capacity Input%Write
AI20RAFDSPReturn Fan Duct Static PressureinWCRead
AI9BldgStatPressBuilding Static Pressure SensorinWCRead
AV9BldgStaticSPBuilding Static Pressure SetpointinWCWrite
AI18RFEFCapReturn Fan Capacity%Read
AI24ExhPSPExhaust Air Plenum Static PressureinWCRead
AI30RFEFFlowReturnFan AirflowCFMRead
MV12ExhRetFanCtrlReturn Fan Capacity ControlWrite1=CAV, 2=BSP, 3=Tracking, 4=DSP, 5=Speed, 6=Flow, 7=OAD, 8=FlowDiff
MV37RFEF1StatusReturn Fan 1-4 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AOV, 20=AU
MV38RFEF2StatusReturn Fan 1-4 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AOV, 20=AU
MV39RFEF3StatusReturn Fan 1-4 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AOV, 20=AU
MV40RFEF4StatusReturn Fan 1-4 StatusRead1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AOV, 20=AU
MV111RFEFFlowInputReturnFan Flow InputRead1=None, 2=1Fan, 3=2Fan, 4=3Fan
AV57RFEFFlowSptReturn/Exhaust Fan Flow SetpointCFMWrite
AV59RAFDSPSptReturn Air Fan DSP SetpointinWCWrite
AV60EFFPSPSptEffective Exhaust Plenum Static Pressure SetpointinWCRead
MV116RefrigTypeRefrigerant TypeRead1=None, 2=R410A, 3=R32, 4=R32HP, 5=R32HP75, 6=R32HP50, 7=R32HP25, 8=R32HP0
AV1ClgCapacityUnit Cooling Capacity%Read
AV14DAClgSetptDischarge Air Cooling Setpoint°FWrite
AV15DefaultDATClgSetptMinimum Discharge Air Cooling Setpoint°FWrite
AV6DATEconSptDischarge Air Temperature Economizer Setpoint°FWrite
AVmin10OccCoolSPOccupied Cooling Setpoint°FWrite
AV11UnoccCoolSetptUnoccupied Cooling Setpoint°FWrite
AV45ReheatCapacityReheat Capacity%Read
MV115EHGBPCfgElectronic Hot Gas Bypass InputRead1=None, 2=Circ12, 3=Circ1, 4=Circ2
MV103HtgTypeHeating TypeRead1=None, 2=F&BP, 3=HW_Stm, 4=MG1StgL, 5=MG1StgL, 6=MG1StgL, 7=MG1StgH, 8=MG1StgH, 9=MG2StgL, 10=MG3StgL, 11=MG2StgH, 12=MG3StgH, 13=2StgE, 14=2StgG, 15=4StgE, 16=4StgG, 17=SCR, 18=SCRSRht, 19=Not used, 20=MG4StgL, 21=MG4StgH
AV2PrimaryHtgCapPrimary Heating Capacity%Read
AV22SecondaryHtgCapSecondary Heating Capacity%Read
AVmin12OccHeatSPOccupied Heating Setpoint°FWrite
AV13UnoccHeatSetptUnoccupied Heating Setpoint°FWrite
AV18DAHtgSetptDischarge Air Heating Setpoint (No Electric Heat)°FWrite
AV19DefaultDATHtgSetptMaximum Discharge Air Heating Setpoint (No Electric Heat)°FWrite
AV153MaximumHeatRiseMaximum Heat RiseRead
MV107ReheatTypeReheat TypeRead1=None, 2=PriHtg, 3=PriHtBP, 4=MHG, 5=MHGBP, 6=HG_LSC, 7=HGLSCBP, 8=DXBP, 9=MLSC
AI11SpaceRH1Relative Humidity Sensor 1%Read
AI12SpaceRH2Relative Humidity Sensor 2%Read
AV20SpaceRH1NetInRelative Humidity Input 1%Write
AV21SpaceRH2NetInRelative Humidity Input 2%Write
AV40Humidity1SPHumidity Sensor 1 Setpoint Input%Write
AV41Humidity2SPHumidity Sensor 2 Setpoint Input%Write
AV42Dewpoint1SPDewpoint Setpoint 1°FWrite
AV43Dewpoint2SPDewpoint Setpoint 2°FWrite
AI25RARelHumReturn Air Relative Humidity%Read
AI26RADewpointReturn Air Dewpoint°FRead
AI27OARelHumOutdoor Air Relative Humidity%Read
AI28OADewpointOutdoor Air Dewpoint°FRead
AV47MinLCTSptMinimum Leaving Coil Temperature Setpoint°FWrite
AV48DXBPMinLCTSptDX Coil Bypass Minimum Leaving Coil Temperature Setpoint°FWrite
AV49MaxLCTSptMaximum Leaving Coil Temperature Setpoint°FWrite
AV50DXBPMaxLCTSptDX Coil Bypass Maximum Leaving Coil Temperature Setpoint°FWrite
AV51LCTSetpointLeaving Coil Temperature Setpoint°FWrite
AV52DXBPLCTSetpointLeaving Coil Temperature Setpoint°FWrite
MV41NetworkResetMinimum Outdoor Air ResetWrite1=No, 2=Yes
MV102DamperTypeDamper TypeRead1=None, 2=30A, 3=100A, 4=Econ, 5=EconFDD, 6=100wRec
MV101OAFanCtrlOutdoor Air Fan ControlRead1=None, 2=OnOffT, 3=OnOffP, 4=VarVFD, 5=VarECM1, 6=VarECM2, 7=VarDK1, 8=VarDK2
AV17MinOAPosNetInOutdoor Air Damper Minimum Position Input%Write
AV55MaxOAPosOutdoor Air Damper Maximum Position%Read
MV108ExtOAInputExternal Outdoor Air InputRead1=None, 2=ExtVDC, 3=ExtmA, 4=CO2VDC, 5=CO2mA, 6=CO2QMX+, 7=IAQMB
MV109OAFlowInputOutdoor Air Flow InputRead1=None, 2=VDC, 3=mA
AV44OAFlowOutdoor AirflowCFMRead
AV46OAFlowSptOutdoor Airflow SetpointCFMWrite
MV113SpaceTConfigSpace Temperature SensorRead1=None, 2=1AI, 3=2AI, 4=3AI, 5=1QMXS, 6=2QMXS, 7=3QMXS, 8=1QMX+, 9=2QMX+, 10=3QMX+
AI13SpaceCO2Space CO2ppmRead
AV33SpaceIAQNetInSpace IAQ (CO2) InputppmWrite
MV17PassiveVentPassive VentilationWrite1=Off, 2=On
MV106EnergyRecEnergy RecoveryRead1=None, 2=CS, 3=CSRH, 4=ECM1, 5=ECM2, 6=VFD, 7=Anlg
MV18ERWhlOnOffEnergy Recovery Wheel StatusRead1=Off, 2=On
AI15ERWheelCapEnergy Recovery Wheel Capacity%Read
AI16ERLWTEnergy Recovery Leaving Wheel Temperature°FRead
AI17EREWTEnergy Recovery Entering Wheel Temperature°FRead
AV100SupplyFanHrsSupply Fan HourshWrite
AV101RF_EFHrsReturn Fan HourshWrite
AV102ReheatHrsReheat HourshWrite
AV103CoolingHrsCooling HourshWrite
AV104C1Comp1HrsCompressor 1 Hours Circuit 1hWrite
AV105C2Comp2HrsCompressor 2 Hours Circuit 2hWrite
AV106C1Comp3HrsCompressor 3 Hours Circuit 1hWrite
AV107C2Comp4HrsCompressor 4 Hours Circuit 2hWrite
AV108C1Comp5HrsCompressor 5 Hours Circuit 1hWrite
AV109C2Comp6HrsCompressor 6 Hours Circuit 2hWrite
AV112HeatingHrsHeating HourshWrite
AV113EconoHrsEconomizer HourshWrite
AV114TenantORHrsTenant Override HourshWrite
AV115DehumHrsDehumidification HourshWrite
AV116ERWhlHrsEnergy Recovery HourshWrite
AV117VarCmp1HrsVariable Compressor 1 HourshWrite
AV118VarCmp2HrsVariable Compressor 2 HourshWrite
AV119VarCmp3HrsVariable Compressor 3 HourshWrite
AV121SCRPrehtHrsSCR Preheat HourshWrite
AV122UVLightHrsUV Light HourshWrite
AV125C3FCmp1HrsCompressor 1 Hours Circuit 3hWrite
AV126C3FCmp3HrsCompressor 3 Hours Circuit 3hWrite
AV127C3FCmp5HrsCompressor 5 Hours Circuit 3hWrite
AV30AlarmValueAlarm ValueRead
AV27ActiveWarningWarning AlarmRead
MV13ClearAlarmsClear AlarmsWrite1=No, 2=ClrFlts, 3=ClrPrblms, 4=ClrWrngs, 5=ClrAllAlms
AV28ActiveProblemProblem AlarmRead
AI52C1RefSuctionPSuction Refrigerant Pressure Circuit 1psiRead
AI62C2RefSuctionPSuction Refrigerant Pressure Circuit 2psiRead
AI51C1SucnRefTempSuction Line Refrigerant Temperature Circuit 1°FRead
AI61C2SucnRefTempSuction Line Refrigerant Temperature Circuit 2°FRead
AI53C1RefDischPDischarge Refrigerant Pressure Circuit 1psiRead
AI63C2RefDischPDischarge Refrigerant Pressure Circuit 2psiRead
AI120SSH1Suction Superheat Circuit 1°FRead
AI125SSH2Suction Superheat Circuit 2°FRead
AI121DSH1Discharge Superheat Circuit 1°FRead
AI126DSH2Discharge Superheat Circuit 2°FRead
AI122Subcooling1Subcooling Circuit 1°FRead
AI127Subcooling2Subcooling Circuit 2°FRead
AI128SSH3Suction Superheat Circuit 3°FRead
AI129DSH3Discharge Superheat Circuit 3°FRead
AI130Subcooling3Subcooling Circuit 3°FRead
AI131C3SucnRefTempSuction Refrigerant Temperature Circuit 3°FRead
AI132C3RefSuctionPSuction Refrigerant Pressure Circuit 3psiRead
AI133C3RefDischPDischarge Refrigerant Pressure Circuit 3psiRead
AI134C3RefLiqLnTempLiquid Line Refrigerant Temperature Circuit 3°FRead
AI139C3DischLnTemp1Discharge Line Refrigerant Temperature 1 Circuit 3°FRead
AI140C3DischLnTemp3Discharge Line Refrigerant Temperature 3 Circuit 3°FRead
AI141C3DischLnTemp5Discharge Line Refrigerant Temperature 5 Circuit 3°FRead
MV100CtrlTypeControl TypeRead1=Zone, 2=DTC, 3=1ZnVAV, 4=RO_FC, 5=RO_FCGE, 6=RO_DCSA
AV151BNNumVarCompsFixed CompressorsRead
AV150BNNumFixedCmpsVariable CompressorsRead
AV152BNNumClgCirCompressor CircuitsRead
AV154UnitSizeUnit SizeRead
MV114MonitorPkgsMonitoring PackagesRead1=None, 2=RefSys
MV117UnitVoltageUnit VoltageRead1=208_60Hz, 2=230_60Hz, 3=460_60Hz, 4=575_60Hz
MV118PreheatTypePreheat TypeRead1=None, 2=HW_Stm, 3=F&BP, 4=SCR
MV119EVTypeExpansion Valve TypeRead1=NA/TXV, 2=DFETS, 3=DFCol, 4=FJPAM2, 5=FJPAM3, 6=Spln, 7=Fj2/Fj3, 8=Fj3/Fj2, 9=DFC/Fj2, 10=DFC/Fj3, 11=Spr/Fj2, 12=Spr/Fj3, 13=Spr/DFC, 14=Fj2/Spr, 15=Fj3/Spr, 16=DFC/Spr
MV120IOConfigI/O ConfigurationRead0=RebApp, 1=Rebel, 2=DCSA
AV155SensorCfgSensor ConfigRead
BI50GenericDI1Generic digital input X1 (expansion I/O board)Read0=Open, 1=Closed
BI51GenericDI2Generic digital input X2 (expansion I/O board)Read0=Open, 1=Closed
BI52GenericDI3Generic digital input X3 (expansion I/O board)Read0=Open, 1=Closed
BI53GenericDI4Generic digital input X4 (expansion I/O board)Read0=Open, 1=Closed
BI54GenericDI5Generic digital input X5 (expansion I/O board)Read0=Open, 1=Closed
BI55GenericDI6Generic digital input X6 (expansion I/O board)Read0=Open, 1=Closed
BI56GenericDI7Generic digital input X7 (expansion I/O board)Read0=Open, 1=Closed
BI57GenericDI8Generic digital input X8 (expansion I/O board)Read0=Open, 1=Closed
BO1GenericBO1Generic digital output DO1 (expansion I/O board)Write0=Off, 1=On
BO2GenericBO2Generic digital output DO2 (expansion I/O board)Write0=Off, 1=On
BO3GenericBO3Generic digital output DO3 (expansion I/O board)Write0=Off, 1=On
BO4GenericBO4Generic digital output DO4 (expansion I/O board)Write0=Off, 1=On
AI150GenericInput1Generic analog input X1 (0-10 VDC, 4-20 mA or NTC10K)Read
AI151GenericInput2Generic analog input X2 (0-10 VDC, 4-20 mA or NTC10K)Read
AI152GenericInput3Generic analog input X3 (0-10 VDC, 4-20 mA or NTC10K)Read
AI153GenericInput4Generic analog input X4 (0-10 VDC, 4-20 mA or NTC10K)Read
AI154GenericInput5Generic analog input X5 (0-10 VDC, 4-20 mA or NTC10K)Read
AI155GenericInput6Generic analog input X6 (0-10 VDC, 4-20 mA or NTC10K)Read
AI156GenericInput7Generic analog input X7 (0-10 VDC, 4-20 mA or NTC10K)Read
AI157GenericInput8Generic analog input X8 (0-10 VDC, 4-20 mA or NTC10K)Read
AO1Generic VDC A01Generic analog output X1, 0-10 VDC (expansion I/O board)VWrite
AO2Generic VDC A02Generic analog output X2, 0-10 VDC (expansion I/O board)VWrite
AO3Generic VDC A03Generic analog output X3, 0-10 VDC (expansion I/O board)VWrite
AO4Generic VDC A04Generic analog output X4, 0-10 VDC (expansion I/O board)VWrite
AO5Generic VDC A05Generic analog output X5, 0-10 VDC (expansion I/O board)VWrite
AO6Generic VDC A06Generic analog output X6, 0-10 VDC (expansion I/O board)VWrite
AO7Generic VDC A07Generic analog output X7, 0-10 VDC (expansion I/O board)VWrite
AO8Generic VDC A08Generic analog output X8, 0-10 VDC (expansion I/O board)VWrite
AO9Generic mA AO1Generic analog output X1, 0-20 mA (expansion I/O board)mAWrite
AO10Generic mA AO2Generic analog output X2, 0-20 mA (expansion I/O board)mAWrite
AO11Generic mA AO3Generic analog output X3, 0-20 mA (expansion I/O board)mAWrite
AO12Generic mA AO4Generic analog output X4, 0-20 mA (expansion I/O board)mAWrite
AVmin29ActiveFaultFault Alarm (highest-priority active fault)Read
NC1FaultsNotification class for faultsRead
NC2ProblemsNotification class for problemsRead
NC3WarningsNotification class for warningsRead
NC4EventsNotification class for eventsRead
BI1AirFlwFltAirflow Fault (208)Read0=Normal, 1=In Alarm
BI2AirFlwStatusAirflow statusRead0=NoFlow, 1=Flow
BI3FilterSwMain Filter Switch InputRead0=Open, 1=Closed
BI5FilterWrnMain Filter Warning (24)Read
BI4FilterSw2Final Filter Switch InputRead0=Open, 1=Closed
BI6FilterWrn2Final Filter Warning (25)Read
BI7ERWheelWrnEnergy Wheel Warning (58)Read0=Normal, 1=In Alarm
BI8HiRATFltHigh Return Air Temperature Fault (220)Read0=Normal, 1=In Alarm
BI9OverEconoWrnOver Economizing Warning (50)Read0=Normal, 1=In Alarm
BI10UnderEconoWrnUnder Economizing Warning (52)Read0=Normal, 1=In Alarm
BI11ExcessOAWrnExcess Outdoor Air Warning (54)Read0=Normal, 1=In Alarm
BI12OADStuckWrnOutdoor Air Damper Stuck Warning (56)Read0=Normal, 1=In Alarm
BI13RetExhFanWrnReturn / Exhaust Fan Warning (34)Read0=Normal, 1=In Alarm
BI14FreezeStatFreeze Fault (252)Read0=Open, 1=Closed
BI15FreezePrbFreeze Problem (198)Read0=Normal, 1=In Alarm
BI16HeatFailPrbHeat Fail Problem (199)Read0=Normal, 1=In Alarm
BI17DuctHiLmtSwDuct High Limit Fault (224)Read0=Open, 1=Closed
BI18EmergencyOffSwEmergency Off Fault (250)Read0=Open, 1=Closed
BI19RefrigSnsrPrbRefrigerant Sensor Problem (134)Read
BI20RefigLeakPrbRefrigerant Leak Problem (133)Read
BI21HiDwptClgDsbdPrbHigh Dewpint Cooling Disable Problem (61)Read
BI22HiDwptClgDsbdFltHigh Dewpint Cooling Disable Fault (205)Read
BI23CondOverflowPrbCondensate Overflow Problem (62)Read
BI24RemRhtDsbldRemote Condenser Reheat Disable Problem (73)Read
BI25RemCmpsDsbldRemote Condenser Disable Problem (63)Read
BI100C1HiPressPrbHigh Pressure Problem Circuit 1 (165)Read0=Normal, 1=In Alarm
BI200C2HiPressPrbHigh Pressure Problem Circuit 2 (166)Read0=Normal, 1=In Alarm
BI300C3HiPressPrbHigh Pressure Problem Circuit 3 (167)Read0=Normal, 1=In Alarm
BI101C1LoPressPrbLow Pressure Problem Circuit 1 (160)Read0=Normal, 1=In Alarm
BI201C2LoPressPrbLow Pressure Problem Circuit 2 (161)Read0=Normal, 1=In Alarm
BI301C3LoPressPrbLow Pressure Problem Circuit 3 (162)Read0=Normal, 1=In Alarm
BI102C1LoDPPrbLow Discharge Pressure Problem Circuit 1 (170)Read0=Normal, 1=In Alarm
BI202C2LoDPPrbLow Discharge Pressure Problem Circuit 2 (171)Read0=Normal, 1=In Alarm
BI302C3LoDPPrbLow Discharge Pressure Problem Circuit 3 (172)Read0=Normal, 1=In Alarm
BI103C1OAFPrbOutdoor Air Fan 1 Problem (130)Read0=Normal, 1=In Alarm
BI203C2OAFPrbOutdoor Air Fan 2 Problem (131)Read0=Normal, 1=In Alarm
BI303C3OAFPrbOutdoor Air Fan 3 Problem (132)Read0=Normal, 1=In Alarm
BI104C1IFBCommPrbInverter Compressor Board (IFB) 1 Problem (190)Read0=Normal, 1=In Alarm
BI204C2IFBCommPrbInverter Compressor Board (IFB) 2 Problem (191)Read0=Normal, 1=In Alarm
BI304C3IFBCommPrbInverter Compressor Board (IFB) 3 Problem (189)Read0=Normal, 1=In Alarm
BI105C1ChargeLossPrbCharge Loss Problem Circuit 1 (150)Read0=Normal, 1=In Alarm
BI205C2ChargeLossPrbCharge Loss Problem Circuit 2 (151)Read0=Normal, 1=In Alarm
BI305C3ChargeLossPrbCharge Loss Problem Circuit 3 (152)Read0=Normal, 1=In Alarm
BI106C1LoChargePrbLow Refrigerant Charge Problem Circuit 1 (145)Read0=Normal, 1=In Alarm
BI206C2LoChargePrbLow Refrigerant Charge Problem Circuit 2 (146)Read0=Normal, 1=In Alarm
BI306C3LoChargePrbLow Refrigerant Charge Problem Circuit 3 (147)Read0=Normal, 1=In Alarm
BI107C1HiVCmpTPrbHigh Variable Speed Compressor Temperature Problem Circuit 1 (175)Read0=Normal, 1=In Alarm
BI207C2HiVCmpTPrbHigh Variable Speed Compressor Temperature Problem Circuit 2 (176)Read0=Normal, 1=In Alarm
BI307C3HiVCmpTPrbHigh Variable Speed Compressor Temperature Problem Circuit 3 (177)Read0=Normal, 1=In Alarm
BI108C1VarCompPrbVariable Speed Compressor Problem Circuit 1 (110)Read0=Normal, 1=In Alarm
BI208C2VarCompPrbVariable Speed Compressor Problem Circuit 2 (111)Read0=Normal, 1=In Alarm
BI308C3VarCompPrbVariable Speed Compressor Problem Circuit 3 (112)Read0=Normal, 1=In Alarm
BI109C1LoDischSHPrbLow Discharge Superheat Problem Circuit 1 (155)Read0=Normal, 1=In Alarm
BI209C2LoDischSHPrbLow Discharge Superheat Problem Circuit 2 (156)Read0=Normal, 1=In Alarm
BI309C3LoDischSHPrbLow Discharge Superheat Problem Circuit 3 (157)Read0=Normal, 1=In Alarm
BI110C1HiDischSHPrbHigh Discharge Superheat Problem Circuit 1 (185)Read0=Normal, 1=In Alarm
BI210C2HiDischSHPrbHigh Discharge Superheat Problem Circuit 2 (186)Read0=Normal, 1=In Alarm
BI310C3HiDischSHPrbHigh Discharge Superheat Problem Circuit 3 (187)Read0=Normal, 1=In Alarm
BI111C1HiDLTmpPrbHigh Discharge Line Temperature Problem Circuit 1 (120)Read0=Normal, 1=In Alarm
BI211C2HiDLTmpPrbHigh Discharge Line Temperature Problem Circuit 2 (121)Read0=Normal, 1=In Alarm
BI311C3HiDLTmpPrbHigh Discharge Line Temperature Problem Circuit 3 (122)Read0=Normal, 1=In Alarm
BI112C1EVPrbExpansion Valve Problem Circuit 1 (125)Read0=Normal, 1=In Alarm
BI212C2EVPrbExpansion Valve Problem Circuit 2 (126)Read0=Normal, 1=In Alarm
BI312C3EVPrbExpansion Valve Problem Circuit 3 (127)Read0=Normal, 1=In Alarm
BI113MHGRhtVlv1PrbModulating Hot Gas Reheat Valve 1 Problem (101)Read0=Normal, 1=In Alarm
BI213MHGRhtVlv2PrbModulating Hot Gas Reheat Valve 2 Problem (102)Read0=Normal, 1=In Alarm
BI114C14WVPrbFour-Way Valve Problem Circuit 1 (107)Read0=Normal, 1=In Alarm
BI214C24WVPrbFour-Way Valve Problem Circuit 2 (108)Read0=Normal, 1=In Alarm
BI314C34WVPrbFour-Way Valve Problem Circuit 3 (95)Read0=Normal, 1=In Alarm
BI40FanRetryEvntFan Retry EventRead
BI41TenantOREvntTenant Override EventRead
BI42PassVentEvntPassive Ventilation Active EventRead
BI43ReheatLmtgEvntReheat Limiting ControlRead
BI44HtRiseLmtgEvntHeat Rise Limiting EventRead
BI45BkUpRhtActEvntBackup Reheat Active EventRead
BI46HPEmrgHtEvntHeat Pump Emergency Heat EventRead
BI141C1FinTULEvntFin Temperature Unload Event Circuit 1Read
BI241C2FinTULEvntFin Temperature Unload Event Circuit 2Read
BI341C3FinTULEvntFin Temperature Unload Event Circuit 3Read
BI142C1HCRULEvntHigh Compression Ratio Unloading Event Circuit 1Read
BI242C2HCRULEvntHigh Compression Ratio Unloading Event Circuit 2Read
BI342C3HCRULEvntHigh Compression Ratio Unloading Event Circuit 3Read
BI144VCmp1HDLTULEvntHigh Discharge Line Temperature Unload Event Circuit 1Read
BI174C1HDLT3ULEvntHigh Discharge Line Temperature Unload Event Circuit 1Read
BI175C1HDLT5ULEvntHigh Discharge Line Temperature Unload Event Circuit 1Read
BI145C1HiAmpULEvntHigh Current Unload Event Circuit 1Read
BI245C2HiAmpULEvntHigh Current Unload Event Circuit 2Read
BI345C3HiAmpULEvntHigh Current Unload Event Circuit 3Read
BI149C1HPULEvntHigh Pressure Unload Event Circuit 1Read
BI249C2HPULEvntHigh Pressure Unload Event Circuit 2Read
BI349C3HPULEvntHigh Pressure Unload Event Circuit 3Read
BI151C1LDPULEvntLow Differential Pressure Unload Event Circuit 1Read
BI251C2LDPULEvntLow Differential Pressure Unload Event Circuit 2Read
BI351C3LDPULEvntLow Differential Pressure Unload Event Circuit 3Read
BI152C1LoDSHDsbEvntLow Discharge Superheat Disable Event Circuit 1Read
BI252C2LoDSHDsbEvntLow Discharge Superheat Disable Event Circuit 2Read
BI352C3LoDSHDsbEvntLow Discharge Superheat Disable Event Circuit 3Read
BI155C1LPULEvntLow Pressure Unload Event Circuit 1Read
BI255C2LPULEvntLow Pressure Unload Event Circuit 2Read
BI355C3LPULEvntLow Pressure Unload Event Circuit 3Read
BI157C1ReqULEvntUnload Request Event Circuit 1Read
BI257C2ReqULEvntUnload Request Event Circuit 2Read
BI357C3ReqULEvntUnload Request Event Circuit 3Read
BI160C1HiAmbLmtgEvntHigh Ambient Limiting Control Circuit 1Read
BI260C2HiAmbLmtgEvntHigh Ambient Limiting Control Circuit 2Read
BI360C3HiAmbLmtgEvntHigh Ambient Limiting Control Circuit 3Read
BI161C1LoSSH_EvntLow Suction Superheat Event Circuit 1Read
BI261C2LoSSH_EvntLow Suction Superheat Event Circuit 2Read
BI361C3LoSSH_EvntLow Suction Superheat Event Circuit 3Read
BI162C1HiSSH_EvntHigh Suction Superheat Event Circuit 1Read
BI262C2HiSSH_EvntHigh Suction Superheat Event Circuit 2Read
BI362C3HiSSH_EvntHigh Suction Superheat Event Circuit 3Read
BI163C1LoDSH_EvntLow Discharge Superheat Event Circuit 1Read
BI263C2LoDSH_EvntLow Discharge Superheat Event Circuit 2Read
BI363C3LoDSH_EvntLow Discharge Superheat Event Circuit 3Read
BI164C1HiDSH_EvntHigh Discharge Superheat Event Circuit 1Read
BI264C2HiDSH_EvntHigh Discharge Superheat Event Circuit 2Read
BI364C3HiDSH_EvntHigh Discharge Superheat Event Circuit 3Read
BI165C1LoSubCl_EvntLow Subcooling Event Circuit 1Read
BI265C2LoSubCl_EvntLow Subcooling Event Circuit 2Read
BI365C3LoSubCl_EvntLow Subcooling Event Circuit 3Read
BI166C1HiSubCl_EvntHigh Subcooling Event Circuit 1Read
BI266C2HiSubCl_EvntHigh Subcooling Event Circuit 2Read
BI366C3HiSubCl_EvntHigh Subcooling Event Circuit 3Read
BI167C1LoT_EvntLow Tc Event Circuit 1Read
BI267C2LoT_EvntLow Tc Event Circuit 2Read
BI367C3LoT_EvntLow Tc Event Circuit 3Read
BI168C1HiT_EvntHigh Tc Event Circuit 1Read
BI268C2HiT_EvntHigh Tc Event Circuit 2Read
BI368C3HiT_EvntHigh Tc Event Circuit 3Read
BI169C1LoTeg_EvntLow Te Event Circuit 1Read
BI269C2LoTeg_EvntLow Te Event Circuit 2Read
BI369C3LoTeg_EvntLow Te Event Circuit 3Read
BI170C1HiTe_EvntHigh Te Event Circuit 1Read
BI270C2HiTe_EvntHigh Te Event Circuit 2Read
BI370C3HiTe_EvntHigh Te Event Circuit 3Read
BI171C1HiDRT_EvntHigh Discharge Refrigerant Temperature Event Circuit 1Read
BI271C2HiDRT_EvntHigh Discharge Refrigerant Temperature Event Circuit 2Read
BI371C3HiDRT_EvntHigh Discharge Refrigerant Temperature Event Circuit 3Read
BI172C1HiSR_EvntHigh Suction Return Temperature Event Circuit 1Read
BI272C2HiSR_EvntHigh Suction Return Temperature Event Circuit 2Read
BI372C3HiSR_EvntHigh Suction Return Temperature Event Circuit 3Read
BI173C1LowOilPrvntEvntLow Oil Prevention Event Circuit 1Read
BI273C2LowOilPrvntEvntLow Oil Prevention Event Circuit 2Read
BI373C3LowOilPrvntEvntLow Oil Prevention Event Circuit 3Read
BI244VCmp2HDLTULEvntHigh Discharge Line Temperature Unload Event Circuit 2Read
BI274C2HDLT4ULEvntHigh Discharge Line Temperature Unload Event Circuit 2Read
BI275C2HDLT6ULEvntHigh Discharge Line Temperature Unload Event Circuit 2Read
BI344VCmp3HDLTULEvntHigh Discharge Line Temperature Unload Event Circuit 3Read
BI374C3HDLT3ULEvntHigh Discharge Line Temperature Unload Event Circuit 3Read
BI375C3HDLT5ULEvntHigh Discharge Line Temperature Unload Event Circuit 3Read
BI176C1OilRetActvEvntOil Return Event Circuit 1Read
BI276C2OilRetActvEvntOil Return Event Circuit 2Read
BI376C3OilRetActvEvntOil Return Event Circuit 3Read
BI177C1HiSSHRHOvrdEvntHigh Suction Superheat Reheat Override Event Circuit 1Read
BI277C2HiSSHRHOvrdEvntHigh Suction Superheat Reheat Override Event Circuit 2Read
BI140C1EVISyncSBEvntExpansion Valve Synchronization Standby Event Circuit 1Read
BI240C2EVISyncSBEvntExpansion Valve Synchronization Standby Event Circuit 2Read
BI340C3EVSyncSBEvntExpansion Valve Synchronization Standby Event Circuit 3Read
BI143C1HDLTSBEvntHigh Discharge Line Temperature Sensor Standby Event Circuit 1Read
BI243C2HDLTSBEvntHigh Discharge Line Temperature Sensor Standby Event Circuit 2Read
BI343C3HDLTSBEvntHigh Discharge Line Temperature Sensor Standby Event Circuit 3Read
BI146C1HiDSHSBEvntHigh Discharge Superheat Standby Event Circuit 1Read
BI246C2HiDSHSBEvntHigh Discharge Superheat Standby Event Circuit 2Read
BI346C3HiDSHSBEvntHigh Discharge Superheat Standby Event Circuit 3Read
BI147C1HiTSBEvntCompressor Body High Temperature Standby Event Circuit 1Read
BI247C2HiTSBEvntCompressor Body High Temperature Standby Event Circuit 2Read
BI347C3HiTSBEvntCompressor Body High Temperature Standby Event Circuit 3Read
BI148C1HPSBEvntHigh Pressure Standby Event Circuit 1Read
BI248C2HPSBEvntHigh Pressure Standby Event Circuit 2Read
BI348C3HPSBEvntHigh Pressure Standby Event Circuit 3Read
BI150C1LDPSBEvntLow Pressure Differential Pressure Standby Event Circuit 1Read
BI250C2LDPSBEvntLow Pressure Differential Pressure Standby Event Circuit 2Read
BI350C3LDPSBEvntLow Pressure Differential Pressure Standby Event Circuit 3Read
BI154C1LPSBEvntLow Pressure Standby Event Circuit 1Read
BI254C2LPSBEvntLow Pressure Standby Event Circuit 2Read
BI354C3LPSBEvntLow Pressure Standby Event Circuit 3Read
BI156C1OAFSBEvntOutdoor Air Fan Standby Event Circuit 1Read
BI256C2OAFSBEvntOutdoor Air Fan Standby Event Circuit 2Read
BI356C3OAFSBEvntOutdoor Air Fan Standby Event Circuit 3Read
BI158C1VCmpPrbSBEvntVariable Compressor Problem Standby Event Circuit 1Read
BI258C2VCmpPrbSBEvntVariable Compressor Problem Standby Event Circuit 2Read
BI358C3VCmpPrbSBEvntVariable Compressor Problem Standby Event Circuit 3Read
BI159C1VCmpReqSBEvntVariable Compressor Request Standby Event Circuit 1Read
BI259C2VCmpReqSBEvntVariable Compressor Request Standby Event Circuit 2Read
BI359C3VCmpReqSBEvntVariable Compressor Request Standby Event Circuit 3Read
BI178C1OAFReqSB_EvntOutdoor Air Fan Request for Standby Event Circuit 1Read
BI278C2OAFReqSB_EvntOutdoor Air Fan Request for Standby Event Circuit 2Read
BI378C3OAFReqSB_EvntOutdoor Air Fan Request for Standby Event Circuit 3Read
Object ID lookup: Daikin Applied MicroTech Applied Air Unit Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)

How many BACnet points does the Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) have?

This list has 445 BACnet objects: 80 analog inputs, 12 analog outputs, 86 analog values, 197 binary inputs, 4 binary outputs, 4 notification classs, 62 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) BACnet points are writable?

96 of the 445 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) BACnet documentation?

The source is MicroTech Applied Air Network Integration Guide, BACnet and LonWorks Communication Protocols (ED 19117-8), revision 2026-06, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019117-8%20MicroTech%20Applied%20Air%20Systems%20Unit%20Controller%20Protocol%20Document.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)?

Start with MV 7 OccManCmd (Occupancy mode command (Occ/Unocc/TntOvrd/Standby/Auto)); MV 8 CurrentState (Occupancy Scheduler Input when Occupancy Mode is Auto); MV 10 EmergOverride (Network shutdown (Off) / Normal); MV 5 ApplicCmd (Application mode (off/heat/cool/fan only/auto)); AV 10 OccCoolSP (Occupied cooling setpoint); AV 12 OccHeatSP (Occupied heating setpoint); MV 19 AHULoc/Net (Must read Network for network inputs to apply); MV 15 UnitState (Current operating state); AI 1 DischAirTemp (Discharge air temperature); AV 29 ActiveFault (Highest-priority active fault number, 0 = none).

How do I enable BMS control of the Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)?

AHU Loc/Net (MV 19) must be set to Network at the HMI (it is read-only over BACnet) for most network inputs to apply. Occupancy is then commanded with Occupancy Mode (MV 7) or, when MV 7 is Auto, Current State (MV 8). Emergency Override (MV 10) = Off shuts the unit off (Unit Status OffNet) and only writing Normal restarts it. Application Mode (MV 5) only acts when Control Mode is Auto, which is set at the HMI. Cooling, heating and economizer can be enabled or capped from the network with AV 36/37, AV 38/39 and AV 34/35 (Ctrl Mode = Auto).

Does the Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC) need a BACnet heartbeat or have a communication timeout?

No BACnet heartbeat (Receive Heartbeat is listed as N/A for BACnet IP and MS/TP). Values written by the BAS stay at the last valid value if communication is lost; an invalid network value makes the controller use its default, and network sensor inputs fall back to the local sensor.

Can the BMS supply sensor values to the Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)?

Space Temperature Input (AV 31) and Outdoor Air Temperature Input (AV 32) take network temperatures and revert to the local sensor if the network value becomes unreliable. Network inputs also exist for space humidity (AV 20/21), space CO2 (AV 33), supply and return fan capacity (AV 24/25) and outdoor air damper minimum and maximum position (AV 17/55). A LonWorks value takes precedence over the BACnet one if both are present.

How do I check these points on the real MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech Applied Air Network Integration Guide, BACnet and LonWorks Communication Protocols · ED 19117-8 · rev. 2026-06. Object names, instances and units are reproduced as published; descriptions are our own.