Air handling unit controller · BACnet points list

Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe) BACnet points list

Updated 28 October 2026

Short answer

The ADK digital AHU uses a MicroTech III or MicroTech 4 controller; BACnet IP comes from a POL908 module and BACnet MS/TP from a POL904 module. The list covers air temperatures, humidity, pressures, flows and air quality (including Modbus room probes), damper, fan, coil and valve signals, comfort/economy/boost setpoints, fan and filter alarms, operating mode and source, summer/winter changeover, energy data and bit-coded alarm words for EC fans, valves and room probes. Object instances are fixed but non-sequential.

This page lists 431 BACnet objects for the Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe) — 61 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
431 (61 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1
Also known as
ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05
Source document
BAS integration guide - BACnet protocol (ADK (Digital AHU)) · D-EIGOC00108-22_05EN
Download CSV 431 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)

Integration in brief

Write the operating command to NetworkCtrlBMS, set summer/winter with SuWiNetworkChgover after setting SuWiChgSrc to BMS, and write the comfort cooling/heating setpoints. Read the operating mode and status, supply and controlled temperatures and the general alarm; use the alarm words for fan and valve diagnostics.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 26007NetworkCtrlBMSBMS mode: Auto/Off/On/Ventilation/Economy/BoostWrite
MV 28594SuWiNetworkChgoverSummer/winter command (1 = Winter, 2 = Summer)Write
MV 9493SuWiChgSrcMust be 3 = BMS for the summer/winter commandWrite
AV 8970TmpSpvCoSpvClgComfort cooling setpointWrite
AV 22817TmpSpvCoSpvHtgComfort heating setpointWrite
MV 39130AckAlmPlsAcknowledge all alarms (2 = On)Write
MV 6080ActOpModeOperating mode (Off/On/Ventilation/Economy/Boost)Read
AI 45150SupplyTmpSupply air temperatureRead
AV 52988ActCtrlValTemperature being controlledRead
BO 5714AlmOutHighGeneral alarm (1 = Alarm)Read

Enable & remote start

NetworkCtrlBMS (MV 26007, 1 = Auto, 2 = Off, 3 = On, 4 = Ventilation, 5 = Economy, 6 = Boost) is the BMS operating command; NetworkCtrl (MV 24562) is the on/off source used by a Daikin iTM. ActOpSta (MV 32321) reports 11 = BMS when the network is in control. Summer/winter changeover follows the BMS only when SuWiChgSrc (MV 9493) = 3 (BMS); then write SuWiNetworkChgover (MV 28594).

Heartbeat & communication loss

No BMS heartbeat is described. Fan setpoints SplyFanSpvP2PCommAlm / RtrnFanSpvP2PCommAlm (AV 59879/18352) apply only when the controllers' peer-to-peer link fails.

Network setup

Watch out for

Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

431 of 431 shown
Type
Access
Show
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe) BACnet Points List
DescriptionStates
AImin45150SupplyTmpSupply air temperature°CRead
AI33923RmUTmp1Room unit temperature°CRead
AI28256ReturnAirTmpReturn air temperature°CRead
AI53218OutTmpOutside air temperature°CRead
AI29568PreHeatTempPre-Heating/Pre cooling/Pre coil temperature°CRead
AI40895ExhaustTmpExhaust temperature°CRead
AI20400SupplyPrsSupply air pressurePaRead
AI39576ReturnPrsReturn air pressurePaRead
AI9497SupplyFlowSupply air flowm3/hRead
AI38593ReturnFlowReturn air flowm3/hRead
AI5238HumOutsideOutside air relative humidity%rHRead
AI37799RoomHumRoom relative humidity%rHRead
AI52165SplyHumiditySupply air relative humidity%rHRead
AI63290MT4HumSnsrSupply / Room /Outside humidity sensor (X8)%rHRead
AI3737AirQltyAir quality (CO2) (Nodes)ppmRead
AI21026AirQualityMT4Air quality (CO2) sensor (X8)ppmRead
AI19419ERQ1LoadERQ1 actual load%Read
AI42249ERQ2LoadERQ2 actual load%Read
AI3928ERQ3LoadERQ3 actual load%Read
AI26764ERQ4LoadERQ4 actual load%Read
AI36987ERQGlobalLoadGlobal ERQ actual load%Read
AI4877RoomPressureRoom pressure (Differential transducer) (X8)PaRead
AI20923SupplyFilterStep1FaultSupply filter 1 alarmPaRead
AI25048SupplyFilterStep2FaultSupply filter 2 alarmPaRead
AI29177SupplyFilterStep3FaultSupply filter 2 alarmPaRead
AI286SupplyFilterStep4FaultSupply filter 4 alarmPaRead
AI26220SupplyFilterStep1WarningSupply filter 1 warningPaRead
AI22031SupplyFilterStep2WarningSupply filter 2 warningPaRead
AI17966SupplyFilterStep3WarningSupply filter 3 warningPaRead
AI14025SupplyFilterStep4WarningSupply filter 4 warningPaRead
AI10215ReturnFilterStep1FaultReturn filter 1 alarmPaRead
AI6020ReturnFilterStep2FaultReturn filter 2 alarmPaRead
AI51509ReturnFilterStep1WarningReturn filter 2 warningPaRead
AI63830ReturnFilterStep2WarningReturn filter 2 warningPaRead
AI57540AddTmpX8Optional temp probe 1 (X8)°CRead
AI61669AddTmpX9Optional temp probe 2 (X9)°CRead
AI46565AddTmpX10Optional temp probe 3 (X10)°CRead
AI42436AddTmpX11Optional temp probe 4 (X11)°CRead
AI58004VOCSensorVOC sensorpbmRead
AIAddVOCX8Optional VOC Probe (X8) (guide repeats instance 58004)pbmRead
AI39865SupplyOptPrsSupply optional transducerPaRead
AI39570ReturnOptPrsReturn optional transducerPaRead
AI56674FreshAirDmpFBFresh air damper feedback%Read
AI33657ExhAirDmpFBExhaust air damper feedback%Read
AI1147SupShutOffDmpFBSupply shutoff damper feedback%Read
AI27101RetShutOffDmpFBReturn shutoff damper feedback%Read
AI57985ByPassDmpFBBypass damper feedback%Read
AI61925MixDmpFBMixing damper feedback%Read
AI55386FreshAirDmp2FBFresh air damper 2 feedback%Read
AI30817ExhAirDmp2FBExhaust air damper 2 feedback%Read
AI39694SupShutOffDmp2FBSupply shutoff damper 2 feedback%Read
AI32773RetShutOffDmp2FBReturn shutoff damper 2 feedback%Read
AI64742ByPassDmp2FBBypass damper 2 feedback%Read
AI47796MixDmp2FBMixing damper 2 feedback%Read
AI47536OptSenX1Optional sensor / input (X1)depends on sensor (%rH, ppm, ppb, Pa or °C)Read
AI35283OptSenX2Optional sensor / input (X2)depends on sensor (%rH, ppm, ppb, Pa or °C)Read
AI39410OptSenX3Optional sensor / input (X3)depends on sensor (%rH, ppm, ppb, Pa or °C)Read
AI59669OptSenX4Optional sensor / input (X4)depends on sensor (%rH, ppm, ppb, Pa or °C)Read
AI63796OptSenX5Optional sensor / input (X5)depends on sensor (%rH, ppm, ppb, Pa or °C)Read
AI51543OptSenX6Optional sensor / input (X6)depends on sensor (%rH, ppm, ppb, Pa or °C)Read
AI55670OptSenX7Optional sensor / input (X7)depends on sensor (%rH, ppm, ppb, Pa or °C)Read
AI16005PlenumDpPlenum differential pressurepaRead
AI50932CustomProbeX8Custom name probe (X8)depends on sensor (%rH, ppm, ppb, Pa)Read
AI31285MBRoomProbeTempModbus room probe 1 temperature°CRead
AI63099MBRoomProbe2TempModbus room probe 2 temperature°CRead
AI45848MBRoomProbe3TempModbus room probe 3 temperature°CRead
AI30992MBRoomProbe4TempModbus room probe 4 temperature°CRead
AI15475MBRoomProbe5TempModbus room probe 5 temperature°CRead
AI62422MBRoomProbe6TempModbus room probe 6 temperature°CRead
AI46773MBRoomProbe7TempModbus room probe 7 temperature°CRead
AI30695MBRoomProbe8TempModbus room probe 8 temperature°CRead
AI12932MBRoomProbe9TempModbus room probe 9 temperature°CRead
AI61210MBRoomProbe10TempModbus room probe 10 temperature°CRead
AI52013MBRoomProbeCalTempModbus room temperature calculated°CRead
AI41136MBRoomProbeRelHumModbus room probe 1 relative humidity%rHRead
AI50573MBRoomProbe2RelHumModbus room probe 2 relative humidity%rHRead
AI13756MBRoomProbe3RelHumModbus room probe 3 relative humidity%rHRead
AI50537MBRoomProbe4RelHumModbus room probe 4 relative humidity%rHRead
AI13656MBRoomProbe5RelHumModbus room probe 5 relative humidity%rHRead
AI13610MBRoomProbe6RelHumModbus room probe 6 relative humidity%rHRead
AI50459MBRoomProbe7RelHumModbus room probe 7 relative humidity%rHRead
AI50337MBRoomProbe8RelHumModbus room probe 8 relative humidity%rHRead
AI13456MBRoomProbe9RelHumModbus room probe 9 relative humidity%rHRead
AI18125MBRoomProbe10RelHumModbus room probe 10 relative humidity%rHRead
AI60264MBRoomProbeCalRelHumModbus room relative humidity calculated%rHRead
AI41521MBRoomProbeCo2Modbus room probe 1 air quality (CO2)ppmRead
AI55000MBRoomProbe2Co2Modbus room probe 2 air quality (CO2 )ppmRead
AI31881MBRoomProbe3Co2Modbus room probe 3 air quality (CO2 )ppmRead
AI7005MBRoomProbe4Co2Modbus room probe 4 air quality (CO2 )ppmRead
AI45324MBRoomProbe5Co2Modbus room probe 5 air quality (CO2 )ppmRead
AI24542MBRoomProbe6Co2Modbus room probe 6 air quality (CO2 )ppmRead
AI62863MBRoomProbe7Co2Modbus room probe 7 air quality (CO2 )ppmRead
AI36982MBRoomProbe8Co2Modbus room probe 8 air quality (CO2 )ppmRead
AI14887MBRoomProbe9Co2Modbus room probe 9 air quality (CO2 )ppmRead
AI35752MBRoomProbe10Co2Modbus room probe 10 air quality (CO2 )ppmRead
AI25873MBRoomProbeCalCo2Modbus room air quality CO2 calculatedppmRead
AI41535MBRoomDewPointModbus room probe 1 dew point°CRead
AI16674MBRoom2DewPointModbus room probe 2 dew point°CRead
AI11879MBRoom3DewPointModbus room probe 3 dew point°CRead
AI12957MBRoom4DewPointModbus room probe 4 dew point°CRead
AI49437MBRoomProbeCalDewPointModbus room dew point calculated°CRead
AI42892CoilTmpCoil temperature°CRead
AI55496CoilHumCoil relative humidity%rHRead
AI25157RoomDewPointRoom dew point°CRead
AI53849OutDewPointOutside dew point°CRead
AI57646SplyDewPointSupply dew point°CRead
AO59037SplyFanVarPosSupply fan output%Read
AO40119ExhFanVarPosReturn fan output%Read
AO39618HumidityCtrlPosHumidifier output%Read
AO37442ElectricalHtgPosElectrical heating output / Post heating%Read
AO33796PostHtgWtrSignalPost heating water output%Read
AO34933PostHtgElecSignalElectrical / Post heating electrical output%Read
AO42156HrecDampPosMixing damper output%Read
AO24312HrecPosRecovery device output%Read
AO30925CoolingPosCooling coil output%Read
AO26209HeatingPosHeating coil output%Read
AO62755FanTempCompPosFan temperature compensation output%Read
AO62468PreHtgPosPre-Heating output%Read
AO18787PreHtgWtrSignalPre heating/Pre cooling/Pre coil water output%Read
AO60586PreHtgElecSignalPre heating electrical output%Read
AO64026SplyShutOffDmpSignalSupply shutoff damper signal%Write
AO59501RtrnShutOffDmpSignalReturn shutoff damper signal%Write
AO50404FreshAirDmpSignalFresh air damper signal%Write
AO40983ExhAirDmpSignalExhaust sir damper signal%Write
AO11376MixAirDmpSignalMixing air damper signal%Write
AO50562ByPassDmpSignalBypass damper signal%Write
AO15147PlenDmpPosPlenum damper signal%Read
AO30192ChillerSpvOutputChiller setpoint output%Read
AO23941SplyFan1SignalSupply fan 1 output signal%Read
AO34055SplyFan2SignalSupply fan 2 output signal%Read
AO15718SplyFan3SignalSupply fan 3 output signal%Read
AO9250SplyFan4SignalSupply fan 4 output signal%Read
AO40003SplyFan5SignalSupply fan 5 output signal%Read
AO17601SplyFan6SignalSupply fan 6 output signal%Read
AO64672SplyFan7SignalSupply fan 7 output signal%Read
AO30281SplyFan8SignalSupply fan 8 output signal%Read
AO57672ExhFan1SignalExhaust fan 1 output signal%Read
AO14794ExhFan2SignalExhaust fan 2 output signal%Read
AO33195ExhFan3SignalExhaust fan 3 output signal%Read
AO39151ExhFan4SignalExhaust fan 4 output signal%Read
AO8334ExhFan5SignalExhaust fan 5 output signal%Read
AO63500ExhFan6SignalExhaust fan 6 output signal%Read
AO16493ExhFan7SignalExhaust fan 7 output signal%Read
AO51844ExhFan8SignalExhaust fan 8 output signal%Read
AV52572SplyFanSpvSt1SpvSupply fan setpoint (summer, when split)m3/h or Pa or %Write
AV57915SplyFanSpvEcSpvSupply fan economy setpoint (summer, when split)m3/h or Pa or %Write
AV46094SplyFanSpvBoostSpvSupply fan boost setpoint (summer, when split)m3/h or Pa or %Write
AV18179SplyFanSpvSt1SpvWiSupply fan setpoint (winter, when split)m3/h or Pa or %Write
AV8881SplyFanSpvEcSpvWiSupply fan economy setpoint (winter, when split)m3/h or Pa or %Write
AV27306SplyFanSpvBoostSpvWiSupply fan boost setpoint (winter, when split)m3/h or Pa or %Write
AV25092SplyFanSpvMaxForceSupply fan max forcem3/h or Pa or %Write
AV45030ExhFanSpvSt1SpvReturn fan setpoint / Room pressure (summer, when split)m3/h or Pa or %Write
AV6118ExhFanSpvEcSpvReturn fan economy setpoint / Room pressure (summer, when split)m3/h or Pa or %Write
AV57303ExhFanSpvBoostSpvReturn fan boost setpoint / Room pressure (summer, when split)m3/h or Pa or %Write
AV33574ExhFanSpvSt1SpvWiReturn fan setpoint / Room pressure (winter, when split)m3/h or Pa or %Write
AV44853ExhFanSpvEcSpvWiReturn fan economy setpoint / Room pressure (winter, when split)m3/h or Pa or %Write
AV50429ExhFanSpvBoostSpvWiReturn fan boost setpoint / Room pressure (winter, when split)m3/h or Pa or %Write
AV2525ExhFanSpvMaxForceReturn fan max forcem3/h or Pa or %Write
AV56628SplyFanActValSupply fan actual valuem3/h or Pa or %Read
AV59694ExhFanActValReturn fan actual valuem3/h or Pa or %Read
AV46589SplyFanActSpvSupply fan actual setpointm3/h or Pa or %Read
AV33255ExhFanActSpvReturn fan actual setpointm3/h or Pa or %Read
AV22649AirQSpvAir quality setpointppmWrite
AV16390OutHumAbsOutside air absolute humidityg/kgRead
AV17315RmHumAbsRoom air absolute humidityg/kgRead
AV13958SplyHumAbsSupply air absolute humidityg/kgRead
AV61369RmEnthRoom enthalpykJ/kgRead
AV57226OutEnthOutside enthalpykJ/kgRead
AV6972SplyEnthSupply enthalpykJ/kgRead
AV11342HumSpvRelSpvDehumDehumidification setpoint relative / Absolute%rH or g/kgWrite
AV10627HumSpvRelSpvHumHumidification setpoint relative / Absolute%rH or g/kgWrite
AV28118SplyHumLimSpSupply humidity limitation setpoint%rHWrite
AV38385ActCtrlValHumActual controlled humidity%rHRead
AVmin8970TmpSpvCoSpvClgCooling setpoint°CWrite
AVmin22817TmpSpvCoSpvHtgHeating setpoint°CWrite
AV61866TmpSpvEcSpvClgEconomy cooling setpoint°CWrite
AV35713TmpSpvEcSpvHtgEconomy heating setpoint°CWrite
AV61325TmpSpvBoostSpvClgBoost cooling setpoint°CWrite
AV38310TmpSpvBoostSpvHtgBoost Heating setpoint°CWrite
AV4018ActMainSpvHtgActual heating setpoint (depending on actual control mode)°CRead
AV30105ActMainSpvClgActual cooling setpoint (depending on actual control mode)°CRead
AV56276ActTempSetptActive temperature setpoint°CRead
AVmin52988ActCtrlValActual controlled temperature°CRead
AV6627PreHtgSpvPre heating setpoint°CWrite
AV56374PreClgSpvPre cooling setpoint°CWrite
AV41552HrecDampminFrshAirMinimum fresh air%Write
AV24338SuWiSwtchCheckOutTmpDampdOutside air temp damped°CRead
AV1206RoomUnitsOccTmRoom unit presence timehWrite
AV8926Room Unit OffsetRoom unit temperature setpoint offset°CWrite
AV753MaxSupplyTempSuMaximum supply temperature limit in summer mode°CWrite
AV7560MaxSupplyTempWiMaximum supply temperature limit in winter mode°CWrite
AV18262MinSupplyTempSuMinimum supply temperature limit in summer mode°CWrite
AV22575MinSupplyTempWiMinimum supply temperature limit in winter mode°CWrite
AV47818SupplyFanRunHoursRunning hours of supply fanhRead
AV52983ReturnFanRunHoursRunning hours of return fanhRead
AV19448SetpPursuitTemperature setpoint for pursuit mode°CWrite
AV14969VOCSpvVOC setpointpbmWrite
AV23744EcoSetpPursuitTemperature setpoint for Eco-Pursuit mode°CWrite
AV41319BoostSetpPursuitTemperature setpoint for Boost-Pursuit mode°CWrite
AV12721BandPursuitPursuit Band°CWrite
AV15422DmpDelayTimeDamper delay time (Duty standby)sWrite
AV15627RotationTimeFan rotation time (Duty standby)hWrite
AV39920SupplyFan1TimeDispSupply fan 1 time (Duty standby)hRead
AV46772SupplyFan2TimeDispSupply fan 2 time (Duty standby)hRead
AV14875ReturnFan1TimeDispReturn fan 1 time (Duty standby)hRead
AV5983ReturnFan2TimeDispReturn fan 2 time (Duty standby)hRead
AV17984Sintra.PlenumOnSpvPlenum setpoint in Sintra On modepaWrite
AV31367Sintra.PlenumBoostSpvPlenum setpoint in Sintra boost modepaWrite
AV41687SplyFanSpv.SintraBoostSupply fan setpoint in Sintra boost modem3/hWrite
AV26354ExhFanSpv.SintraBoostReturn fan setpoint in Sintra boost modem3/hWrite
AV40525MBRoomProbeAbsHumModbus room probe 1 absolute humidityg/kgRead
AV64368MBRoomProbe2AbsHumModbus room probe 2 absolute humidityg/kgRead
AV2881MBRoomProbe3AbsHumModbus room probe 3 absolute humidityg/kgRead
AV64404MBRoomProbe4AbsHumModbus room probe 4 absolute humidityg/kgRead
AV54677MBRoomProbeCalAbsHumModbus room probe absolute humidity calculatedg/kgRead
AV54939MBRoomProbeEnthModbus room probe 1 enthalpykJ/kgRead
AV13702MBRoomProbe2EnthModbus room probe 2 enthalpykJ/kgRead
AV23235MBRoomProbe3EnthModbus room probe 3 enthalpykJ/kgRead
AV17977MBRoomProbe4EnthModbus room probe 4 enthalpykJ/kgRead
AV46521MBRoomProbeCalEnthalpyModbus room probe enthalpy calculatedkJ/kgRead
AV38866HtgValveAbsFlowHeating valve absolute flow (Modbus)l/hRead
AV54493ClgValveAbsFlowCooling valve absolute flow (Modbus)l/hRead
AV64348Clg2ValveAbsFlowCooling valve 2 absolute flow (Modbus)l/hRead
AV49765ClgHtgValveAbsFlowCooling/heating valve absolute flow (Modbus)l/hRead
AV8550PreHValveAbsFlowPre heating/Pre cooling/Pre coil valve absolute flow (Modbus)l/hRead
AV44988PostHValveAbsFlowPost heating/Pre cooling/Pre coil valve absolute flow (Modbus)l/hRead
AV15887HtgValveInTmpHeating valve fluid inlet temperature°CRead
AV58838HtgValveOutTmpHeating valve fluid outlet temperature°CRead
AV59262ClgValveInTmpCooling valve fluid inlet temperature°CRead
AV52866ClgValveOutTmpCooling valve fluid outlet temperature°CRead
AV2228Clg2ValveInTmpCooling valve 2 fluid inlet temperature°CRead
AV2115Clg2ValveOutTmpCooling valve 2 fluid outlet temperature°CRead
AV35870ClgHtgValveInTmpCooling/heating valve fluid inlet temperature°CRead
AV29519ClgHtgValveOutTmpCooling/heating valve fluid outlet temperature°CRead
AV51832PreValveInTmpPre coil valve fluid inlet temperature°CRead
AV15693PreValveOutTmpPre coil valve fluid outlet temperature°CRead
AV5967PostHValveInTmpPost heating valve fluid inlet temperature°CRead
AV4253PostHValveOutTmpPost heating valve fluid outlet temperature°CRead
AV62887HtggValveHtgPowerHeating valve heating powerkWRead
AV7700ClgValveClgPowerCooling valve cooling powerkWRead
AV44838ClgValve2ClgPowerCooling valve 2 cooling powerkWRead
AV49842ClgHtgValveClgPowerCooling/heating valve cooling powerkWRead
AV40269ClgHtgValveHtgPowerCooling/heating valve heating powerkWRead
AV41596PreValveClgPowerPre coil valve cooling powerkWRead
AV64899PreValveHtgPowerPre coil valve heating powerkWRead
AV11315PostHValveHtgPowerPost heating valve heating powerkWRead
AV51306HtgValveHtgEnergyHeating valve heating energykWhRead
AV14127ClgValveClgEnergyCooling valve cooling energykWhRead
AV45781ClgValve2ClgEnergyCooling valve 2 cooling energykWhRead
AV39902ClgHtgValveClgEnergyCooling/heating valve cooling energykWhRead
AV53188ClgHtgValveHtgEnergyCooling/heating valve heating energykWhRead
AV14712PreValveClgEnergyPre coil valve cooling energykWhRead
AV28002PreValveHtgEnergyPre coil valve heating energykWhRead
AV1598PostHValveHtgEnergyPost heating valve heating energykWhRead
AV49851HtgValveRelPosHeating valve position%Read
AV7114ClgValveRelPosCooling valve position%Read
AV62464Clg2ValveRelPosCooling valve 2 position%Read
AV28842ClgHtgValveRelPosCooling/heating valve position%Read
AV14028PreValveRelPosPre coil valve position%Read
AV60411PostHValveRelPosPost heating valve position%Read
AV32329SplyFan1SpeedSupply fan 1 speed (Modbus)RPMRead
AV42699SplyFan2SpeedSupply fan 2 speed (Modbus)RPMRead
AV19654SplyFan3SpeedSupply fan 3 speed (Modbus)RPMRead
AV2030SplyFan4SpeedSupply fan 4 speed (Modbus)RPMRead
AV49039SplyFan5SpeedSupply fan 5 speed (Modbus)RPMRead
AV26381SplyFan6SpeedSupply fan 6 speed (Modbus)RPMRead
AV57196SplyFan7SpeedSupply fan 7 speed (Modbus)RPMRead
AV21893SplyFan8SpeedSupply fan 8 speed (Modbus)RPMRead
AV32910RtrnFan1SpeedReturn fan 1 speed (Modbus)RPMRead
AV22540RtrnFan2SpeedReturn fan 2 speed (Modbus)RPMRead
AV34071RtrnFan3SpeedReturn fan 3 speed (Modbus)RPMRead
AV63785RtrnFan4SpeedReturn fan 4 speed (Modbus)RPMRead
AV16712RtrnFan5SpeedReturn fan 5 speed (Modbus)RPMRead
AV39370RtrnFan6SpeedReturn fan 6 speed (Modbus)RPMRead
AV8619RtrnFan7SpeedReturn fan 7 speed (Modbus)RPMRead
AV43842RtrnFan8SpeedReturn fan 8 speed (Modbus)RPMRead
AV59879SplyFanSpvP2PCommAlmSupply fan setpoint during peer-to-peer communication alarmm3/h or Pa or %Write
AV18352RtrnFanSpvP2PCommAlmReturn fan setpoint during peer-to-peer communication alarmm3/h or Pa or %Write
BI21294HtgFrstDtctrHeating frost monitorRead0=OK, 1=Alarm
BI47847HtgPmpAlmHeating pump alarmRead0=OK, 1=Alarm
BI4964ElHtgAlmElectrical heating / post electrical heating alarmRead0=OK, 1=Alarm
BI62931HRecAlmRecovery device alarmRead0=OK, 1=Alarm
BI40242ClgPmpAlmCooling pump alarmRead0=OK, 1=Alarm
BI28757SplyFanAlmSupply fan alarmRead0=OK, 1=Alarm
BI24461Sply2FanAlmSupply fan 2 alarmRead0=OK, 1=Alarm
BI59372Sply3FanAlmSupply fan 3 alarmRead0=OK, 1=Alarm
BI65192Sply4FanAlmSupply fan 4 alarmRead0=OK, 1=Alarm
BI18121Sply5FanAlmSupply fan 5 alarmRead0=OK, 1=Alarm
BI40523Sply6FanAlmSupply fan 6 alarmRead0=OK, 1=Alarm
BI9770Sply7FanAlmSupply fan 7 alarmRead0=OK, 1=Alarm
BI44227Sply8FanAlmSupply fan 8 alarmRead0=OK, 1=Alarm
BI55865ExhFanAlmExhaust fan alarmRead0=OK, 1=Alarm
BI10029Exh2FanAlmExhaust fan 2 alarmRead0=OK, 1=Alarm
BI40780Exh3FanAlmExhaust fan 3 alarmRead0=OK, 1=Alarm
BI34312Exh4FanAlmExhaust fan 4 alarmRead0=OK, 1=Alarm
BI15977Exh5FanAlmExhaust fan 5 alarmRead0=OK, 1=Alarm
BI59115Exh6FanAlmExhaust fan 6 alarmRead0=OK, 1=Alarm
BI24202Exh7FanAlmExhaust fan 7 alarmRead0=OK, 1=Alarm
BI54371Exh8FanAlmExhaust fan 8 alarmRead0=OK, 1=Alarm
BI13699FilterAlmFilter alarmRead0=OK, 1=Alarm
BI49203SplyFilterAlmSupply filter alarmRead0=OK, 1=Alarm
BI45320ExhFilterAlmExhaust filter alarmRead0=OK, 1=Alarm
BI28514FireAlmFire alarmRead0=OK, 1=Alarm
BI11643ExtCtrl1Unit Enable SwitchRead0=Standby, 1=On
BI9864EmergencyStopEmergency stopRead0=Alarm, 1=OK
BI19724ERQ1OnOffERQ 1 On/Off stateRead0=Off, 1=On
BI33772ERQ2OnOffERQ 2 On/Off stateRead0=Off, 1=On
BI50764ERQ3OnOffERQ 3 On/Off stateRead0=Off, 1=On
BI3597ERQ4OnOffERQ 4 On/Off stateRead0=Off, 1=On
BI48775ERQ1DefrostERQ 1 Defrost stateRead0=No Defrost, 1=Defrost
BI30450ERQ2DefrostERQ 2 Defrost stateRead0=No Defrost, 1=Defrost
BI12577ERQ3DefrostERQ 3 Defrost stateRead0=No Defrost, 1=Defrost
BI63033ERQ4DefrostERQ 4 Defrost stateRead0=No Defrost, 1=Defrost
BI610ERQ 1 alarmERQ 1 alarmRead0=OK, 1=Alarm
BI16951ERQ 2 alarmERQ 2 alarmRead0=OK, 1=Alarm
BI1943ERQ 3 alarmERQ 3 alarmRead0=OK, 1=Alarm
BI53206ERQ 4 alarmERQ 4 alarmRead0=OK, 1=Alarm
BI14492PreHtgWtrPmpOnOffPre heating/Pre cooling/Pre coil pump commandRead1=Off, 2=On
BI47780PostHtgWtrPmpOnOffPost heating pump commandRead1=Off, 2=On
BI43256ElFilAlmElectrostatic filter alarmRead0=OK, 1=Alarm
BI48254R32Leakage1R32 leakage 1 alarmRead0=OK, 1=Alarm
BI35869R32Leakage2R32 leakage 2 alarmRead0=OK, 1=Alarm
BI39996R32Leakage3R32 leakage 3 alarmRead0=OK, 1=Alarm
BI60635R32Leakage4R32 leakage 4 alarmRead0=OK, 1=Alarm
BI41645LowFlowThrAlmLow flow threshold alarmRead0=OK, 1=Alarm
BI57484ElectricalPreheatingFaultPre-heating electrical alarmRead0=OK, 1=Alarm
BI23983FreshAirDmpFBDevAlmFresh air damper feedback deviation alarmRead0=OK, 1=Alarm
BI17725ExhAirDmpFBDevAlmExhaust air damper feedback deviation alarmRead0=OK, 1=Alarm
BI17941SplyShutoffFBDevAlmSupply shutoff air damper feedback deviation alarmRead0=OK, 1=Alarm
BI55397RtrnShutoffFBDevAlmReturn shutoff air damper feedback deviation alarmRead0=OK, 1=Alarm
BI25342ByPassDmpFBDevAlmBypass damper feedback deviation alarmRead0=OK, 1=Alarm
BI33492MixingDmpFBDevAlmMixing damper feedback deviation alarmRead0=OK, 1=Alarm
BI4205FreshAirDmp2FBDevAlmFresh air damper 2 feedback deviation alarmRead0=OK, 1=Alarm
BI9540ExhAirDmp2FBDevAlmExhaust air damper 2 feedback deviation alarmRead0=OK, 1=Alarm
BI46351SplyShutoffFB2DevAlmSupply shutoff air damper 2 feedback deviation alarmRead0=OK, 1=Alarm
BI42872RtrnShutoffFB2DevAlmReturn shutoff air damper 2feedback deviation alarmRead0=OK, 1=Alarm
BI34513ByPassDmpFBDevAlmBypass damper 2 feedback deviation alarmRead0=OK, 1=Alarm
BI20991MixingDmpFBDevAlmMixing damper 2 feedback deviation alarmRead0=OK, 1=Alarm
BI24475SplyFanDevAlmSupply fan Setpoint deviation alarmRead0=OK, 1=Alarm
BI58195ExhFanDevAlmReturn fan Setpoint deviation alarmRead0=OK, 1=Alarm
BI45683TempDevAlmTemperature setpoint deviation alarmRead0=OK, 1=Alarm
BI11277HumDevAlmHumidification setpoint deviation alarmRead0=OK, 1=Alarm
BI21916DehumDevAlmDehumidification setpoint deviation alarmRead0=OK, 1=Alarm
BI65517SplyTmpDevAlmSupply temperature deviation alarmRead0=OK, 1=Alarm
BI1642PreHtgWtrPmpAlmPre heating pump alarmRead0=OK, 1=Alarm
BI12835PostWtrPmpAlmPost heating pump alarmRead0=OK, 1=Alarm
BI26521ClgHtgPmpAlmCooling heating pump alarmRead0=OK, 1=Alarm
BI41868GenAlmAHU General alarmRead0=Normal, 1=Alarm
BI39271UVLampFeedbackUV lamp feedback alarmRead0=Normal, 1=Alarm
BI23880P2PCommAlmPeer-to-peer communication alarmRead0=Normal, 1=Alarm
BO6170DamperSplyOnOffFresh air damper commandRead0=Off, 1=On
BO18044HumidityCtrlCmdOnOffHumidifier commandRead0=Off, 1=On
BO10276CoolingPmpCmdOnOffCooling pump commandRead0=Off, 1=On
BO10264HeatingPmpCmdOnOffHeating pump commandRead0=Off, 1=On
BOmin5714AlmOutHighAHU General alarm outputRead0=Normal, 1=Alarm
SCH31059ScheduleStTime scheduler actual stateRead1=Off, 2=On, 3=Ventilation, 4=Economy, 5=Boost
MO21928SplyFanCmdStSupply fan commandRead1=Off, 2=On
MO14719ExhFanCmdStExhaust fan commandRead1=Off, 2=On
MVmin6080ActOpModeActual operating modeRead1=Off, 2=On, 3=Ventilation, 4=Economy, 5=Boost
MV32321ActOpStaPresent unit statusRead1=NA, 2=Fire, 3=Emergency, 4=Fault, 5=Manual, 6=NA, 7=Alarm, 8=Panel switch, 9=Local Switch, 10=NA, 11=BMS, 12=Schedular, 13=Occupancy, 14=NA, 15=NA, 16=NA, 17=Ready, 18=P2P
MVmin39130AckAlmPlsAlarm acknowledge (acknowledges all alarms)Write1=Off, 2=On
MV24616SuWiSwtchCheckStateSummer Winter modeRead1=Winter, 2=Summer
MV46769AlmCl0Danger alarm (A)Read1=Normal, 2=On
MV42640AlmCl1Critical alarm (A)Read1=Normal, 2=On
MV38643AlmCl2Low alarm (B)Read1=Normal, 2=On
MV34514AlmCl3Warning alarm (C)Read1=Normal, 2=On
MV24562NetworkCtrlNetwork source (iTM)Write1=Off, 2=On
MVmin26007NetworkCtrlBMSNetwork sourceWrite1=Auto, 2=Off, 3=On, 4=Ventilation, 5=Economy, 6=Boost
MVmin28594SuWiNetworkChgoverSummer/Winter network changeover commandWrite1=Winter, 2=Summer
MV59712FireDamperCmdFire damper commandRead1=Close, 2=Open
MV43819ExhEngUnitReturn air engineering UnitRead1=%, 2=Pa, 3=m3/h
MV54155SplyEngUnitSupply air engineering UnitRead1=%, 2=Pa, 3=m3/h
MV13725HumEngUnitHumidity engineering unitRead1=%rH, 2=g/kg
MV25214Pre-Htg ElectricalPre-heating electrical commandRead1=Off, 2=Step 1, 3=Step 2
MV58176Electrical Heating State/Post HeatingElectrical heating commandRead1=Off, 2=Step 1, 3=Step 2
MV9333ClgDxStagesCooling Dx actual stageRead1=Off, 2=Stage 1, 3=Stage 2
MV1708CommTestEnEnable TestWrite1=No, 2=Yes
MVmin9493SuWiChgSrcSet source for summer/winter changeoverWrite1=Auto, 2=HMI, 3=BMS (BACnet)
MV12316TimeSchedStIndicates time scheduler active modeRead1=On, 2=Off, 3=Ventilation, 4=Economy, 5=Boost
MV28279ActFanStepIndicates the active fan stepRead1=Off, 2=Stage 1, 3=Stage 2, 4=Stage 3
MV28561ActCtrlModeIndicates mode for the regulation controlRead1=Room, 2=Exhaust, 3=Supply
MV33544OpModeTspCopyUnitPlsCopy Monday time schedule to all weekdaysWrite1=Off, 2=On
MV59471ElFilAlmTypeElectrostatic filter alarm typeWrite1=Warning, 2=Fault
MV21786SintraModeSwitchSintra modeWrite1=Off, 2=On, 3=Boost
MV45073SplyFan1OnSupply fan 1 On/Off statusRead1=Off, 2=On
MV46777SplyFan2OnSupply fan 2 On/Off statusRead1=Off, 2=On
MV33641RtrnFan1OnReturn fan 1 On/Off statusRead1=Off, 2=On
MV51337RtrnFan2OnReturn fan 2 On/Off statusRead1=Off, 2=On
MV32789UVlampOnOffUV lamp On/Off stateRead1=Off, 2=On
PIV8565SplyFan1AlmWord1Supply fan 1 alarm word 1 (bit-coded, guide table A)Read
PIV4374SplyFan1AlmWord2Supply fan 1 alarm word 2 (bit-coded, guide table A)Read
PIV61136SplyFan2AlmWord1Supply fan 2 alarm word 1 (bit-coded, guide table A)Read
PIV57011SplyFan2AlmWord2Supply fan 2 alarm word 2 (bit-coded, guide table A)Read
PIV49808SplyFan3AlmWord1Supply fan 3 alarm word 1 (bit-coded, guide table A)Read
PIV62195SplyFan3AlmWord2Supply fan 3 alarm word 2 (bit-coded, guide table A)Read
PIV25019SplyFan4AlmWord1Supply fan 4 alarm word 1 (bit-coded, guide table A)Read
PIV20952SplyFan4AlmWord2Supply fan 4 alarm word 2 (bit-coded, guide table A)Read
PIV9432SplyFan5AlmWord1Supply fan 5 alarm word 1 (bit-coded, guide table A)Read
PIV5307SplyFan5AlmWord2Supply fan 5 alarm word 2 (bit-coded, guide table A)Read
PIV60285SplyFan6AlmWord1Supply fan 6 alarm word 1 (bit-coded, guide table A)Read
PIV56094SplyFan6AmWord2Supply fan 6 alarm word 2 (bit-coded, guide table A)Read
PIV44574SplyFan7AlmWord1Supply fan 7 alarm word 1 (bit-coded, guide table A)Read
PIV40573SplyFan7AlmWord2Supply fan 7 alarm word 2 (bit-coded, guide table A)Read
PIV28492SplyFan8AlmWord1Supply fan 8 alarm word 1 (bit-coded, guide table A)Read
PIV24367SplyFan8AlmWord2Supply fan 8 alarm word 2 (bit-coded, guide table A)Read
PIV25606RtrnFan1AlmWord1Return fan 1 alarm word 1 (bit-coded, guide table A)Read
PIV21605RtrnFan1AlmWord2Return fan 1 alarm word 2 (bit-coded, guide table A)Read
PIV43939RtrnFan2AlmWord1Return fan 2 alarm word 1 (bit-coded, guide table A)Read
PIV39872RtrnFan2AlmWord2Return fan 2 alarm word 2 (bit-coded, guide table A)Read
PIV43505RtrnFan3AlmWord1Return fan 3 alarm word 1 (bit-coded, guide table A)Read
PIV39314RtrnFan3AlmWord2Return fan 3 alarm word 2 (bit-coded, guide table A)Read
PIV9416RtrnFan4AlmWord1Return fan 4 alarm word 1 (bit-coded, guide table A)Read
PIV5291RtrnFan4AlmWord2Return fan 4 alarm word 2 (bit-coded, guide table A)Read
PIV25003RtrnFan5AlmWord1Return fan 5 alarm word 1 (bit-coded, guide table A)Read
PIV20936RtrnFan5AlmWord2Return fan 5 alarm word 2 (bit-coded, guide table A)Read
PIV44558RtrnFan6AlmWord1Return fan 6 alarm word 1 (bit-coded, guide table A)Read
PIV40557RtrnFan6AmWord2Return fan 6 alarm word 2 (bit-coded, guide table A)Read
PIV60269RtrnFan7AlmWord1Return fan 7 alarm word 1 (bit-coded, guide table A)Read
PIVRtrnFan7AlmWord2Return fan 7 alarm word 2 (bit-coded, guide table A) (guide repeats instance 56094)Read
PIV10815RtrnFan8AlmWord1Return fan 8 alarm word 1 (bit-coded, guide table A)Read
PIV6748RtrnFan8AlmWord2Return fan 8 alarm word 2 (bit-coded, guide table A)Read
PIV43306MBRoomProbeAlmRoom probe alarm word (bit-coded, guide table C)Read
PIV12119MBRoomProbe2AlmRoom probe 2 alarm word (bit-coded, guide table C)Read
PIV11298MBRoomProbe3AlmRoom probe 3 alarm word (bit-coded, guide table C)Read
PIV9321MBRoomProbe4AlmRoom probe 4 alarm word (bit-coded, guide table C)Read
PIV25133HtgValveAlmWordHeating valve alarm word (bit-coded, guide table B)Read
PIV54881ClgValveAlmWordCooling valve alarm word (bit-coded, guide table B)Read
PIV26451Clg2ValveAlmWordCooling 2 valve alarm word (bit-coded, guide table B)Read
PIV2759ClgHtgValveAlmWordCooling/heating valve alarm word (bit-coded, guide table B)Read
PIV27145PreHValveAlmWordPre heating valve alarm word (bit-coded, guide table B)Read
PIV48057PostHValveAlmWordPost heating valve alarm word (bit-coded, guide table B)Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ADK digital air handler, DSTREAM controls (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)

How many BACnet points does the Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe) have?

This list has 431 BACnet objects: 106 analog inputs, 38 analog outputs, 134 analog values, 72 binary inputs, 5 binary outputs, 2 multi-state outputs, 1 schedule, 31 multi-state values, 42 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe) BACnet points are writable?

61 of the 431 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe) BACnet documentation?

The source is BAS integration guide - BACnet protocol (ADK (Digital AHU)) (D-EIGOC00108-22_05EN), published free by Daikin Applied at https://www.daikinapplied.uk/hubfs/portale-documentale/D_EIGOC00108_22_05EN_ADK.pdf.

What are the minimum BACnet points to integrate the Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)?

Start with MV 26007 NetworkCtrlBMS (BMS mode: Auto/Off/On/Ventilation/Economy/Boost); MV 28594 SuWiNetworkChgover (Summer/winter command (1 = Winter, 2 = Summer)); MV 9493 SuWiChgSrc (Must be 3 = BMS for the summer/winter command); AV 8970 TmpSpvCoSpvClg (Comfort cooling setpoint); AV 22817 TmpSpvCoSpvHtg (Comfort heating setpoint); MV 39130 AckAlmPls (Acknowledge all alarms (2 = On)); MV 6080 ActOpMode (Operating mode (Off/On/Ventilation/Economy/Boost)); AI 45150 SupplyTmp (Supply air temperature); AV 52988 ActCtrlVal (Temperature being controlled); BO 5714 AlmOutHigh (General alarm (1 = Alarm)).

How do I enable BMS control of the Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)?

NetworkCtrlBMS (MV 26007, 1 = Auto, 2 = Off, 3 = On, 4 = Ventilation, 5 = Economy, 6 = Boost) is the BMS operating command; NetworkCtrl (MV 24562) is the on/off source used by a Daikin iTM. ActOpSta (MV 32321) reports 11 = BMS when the network is in control. Summer/winter changeover follows the BMS only when SuWiChgSrc (MV 9493) = 3 (BMS); then write SuWiNetworkChgover (MV 28594).

Does the Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe) need a BACnet heartbeat or have a communication timeout?

No BMS heartbeat is described. Fan setpoints SplyFanSpvP2PCommAlm / RtrnFanSpvP2PCommAlm (AV 59879/18352) apply only when the controllers' peer-to-peer link fails.

How do I check these points on the real ADK digital air handler, DSTREAM controls (Daikin Applied Europe)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: BAS integration guide - BACnet protocol (ADK (Digital AHU)) · D-EIGOC00108-22_05EN. Object names, instances and units are reproduced as published; descriptions are our own.