Water source heat pump controller · BACnet points list

Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor BACnet points list

Updated 28 October 2026

Short answer

SmartSource and Enfinity Large two-compressor heat pumps use a MicroTech III controller (with I/O expansion) that joins BACnet MS/TP through the BACnet communication module. Compared with the single-stage list it adds interstage timers, hydronic and low-EWT setpoints, extra heating stages, fan speed and runtime totalizers, humidistat and fan status inputs. A few objects carry different names on SmartSource and Enfinity Large units.

This page lists 77 BACnet objects for the Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor — 53 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
Equipment
Water source heat pump controller
Equipment type
Heat pumps
BACnet objects
77 (53 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
3101000 + MS/TP MAC address (e.g. 3101007)
Also known as
SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103
Source document
MicroTech III Water Source Heat Pump Unit Controller Protocol Information · ED 15103-9 · rev. 2021-08
Download CSV 77 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor

Integration in brief

Join the heat pump to the MS/TP trunk with a unique MAC and instance, then command occupancy and application mode and supply the space temperature or setpoint from the BMS if needed. Use Receive Heartbeat if overrides must fall back when the BMS goes quiet.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 7OccManCmdOccupancy override from the BMSCommand
MV 10ApplicModeApplication mode (Auto/Heat/Cool/Off/Fan Only/Dehumid)Command
AV 19SetpointNetwork reference setpointCommand
BV 1ClearAlarmClear the current alarmWrite
MV 4McQWSHPStatusUnit operating statusRead
AV 22EffectSpaceTempSpace temperature used for controlRead
AI 2LWTLeaving water temperatureRead
MV 2CurrentAlarmHighest-priority active alarmRead

Enable & remote start

No local/remote switch is described. Network override objects take effect when written: Application Mode Input (MV 10) selects Auto/Heat/Cool/Off/Fan Only/Dehumid, Occupancy Override Input (MV 7) and Occupancy Scheduler Input (MV 8) set occupancy, and Compressor Enable Input (MV 1) permits compressor operation. Overrides revert to their default (Null) values after a controller reboot.

Heartbeat & communication loss

Receive Heartbeat (AV 20, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled) is the maximum time a supported override may go without being rewritten before it reverts to its default. Each supported point has its own timer: AV 18, AV 35, MV 1, MV 8, MV 9, MV 10, MV 11 and MV 12. Send Heartbeat is not supported by the BACnet module; use COV instead.

Sensors & values from the BMS

Write the space temperature to Space Temperature Input (AV 18); Effective Space Temperature (AV 22) uses the local AI 1 sensor unless AV 18 holds a valid value. Temperature Setpoint Input (AV 19) sets the reference setpoint for Occupied/Standby, but local setpoint adjust must first be disabled with MV 14. Temperature Setpoint Offset Input (AV 35) shifts the occupied/standby setpoints. Occupancy Sensor Input (MV 9) accepts a network occupancy sensor. Humidistat Remote Input (MV 16) and Fan ON/Auto Remote Input (MV 3) override the local humidistat and fan switch.

Network setup

Watch out for

Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

77 of 77 shown
Type
Access
Show
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor BACnet Points List
DescriptionStates
AI1LocalSpaceTempLocal Space Temperature Output°FRead
AImin2LWTLeaving Water Temperature°FRead
AI3EWTEntering Water Temperature°FRead
AI4DischAirTempDischarge Air Temperature°FRead
AI5LocalSetptLocal Setpoint Adjust Output°FRead
AI6CompSuctionTempCompressor #1 Suction Temperature (Enfinity Large: Comp1SuctionTemp)°FRead
AI7CompDischTempCompressor #2 Suction Temperature (Enfinity Large: Comp2SuctionTemp)°FRead
AI8BrownoutBrownout Voltage ReadingcountsRead
AV1cpOccupied_Cool_SetptOccupied Cooling Setpoint°FWrite
AV2cpStandby_Cool_SetptStandby Cool Setpoint°FWrite
AV3cpUnoccupied_Cool_SetptUnoccupied Cool Setpoint°FWrite
AV4cpOccupied_Heat_SetptOccupied Heat Setpoint°FWrite
AV5cpStandby_Heat_SetptStandby Heat Setpoint°FWrite
AV6cpUnoccupied_Heat_SetptUnoccupied Heat Setpoint°FWrite
AV7cpBypassTimeLocal Bypass Time SetpointminWrite
AV8cpIntStgOffTmrInterstage OFF TimersWrite
AV9cpBrownoutRefBrownout Reference SetpointWrite
AV10cpOccDiffOccupied Setpoint Differential°FWrite
AV11cpLowTempProtGLCompressor Low Suction Temp Protection Setpoint - Glycol°FWrite
AV12cpLowTempProtCompressor Low Suction Temp Protection Setpoint - Water°FWrite
AV13cpLowTmpProtDifCompressor Low Suction Temp Protection Differential°FWrite
AV14cpIntStgOnTmrInterstage ON TimersWrite
AV15cpMinCompOffTmrCompressor Minimum OFF TimersWrite
AV16cpMinCompOnTmrCompressor Minimum ON TimersWrite
AV17cpUnoccDiffUnoccupied Setpoint Differential°FWrite
AV18NetworkSpaceTempSpace Temperature Input°FCommand
AVmin19SetpointTemperature Setpoint Input°FCommand
AV20cpRcvHrtBtReceive HeartbeatsWrite
AV21cpSndHrtBtSend HeartbeatsWrite
AVmin22EffectSpaceTempEffective Space Temperature Output°FRead
AV23EffectSetptEffective Setpoint Output°FRead
AV24SetptShiftSetpoint Shift Output°FRead
AV25cpSptAdjMaxLong Range Setpoint Adjust Maximum°FWrite
AV26cpSptAdjMinLong Range Setpoint Adjust Minimum°FWrite
AV27cpHydroClgOnSptHydronic Cooling ON Setpoint°FWrite
AV28cpHydronicDiffHydronic Setpoint Differential°FWrite
AV29cpLowLwtDiffLow Leaving Water Temp Differential°FWrite
AV30cpLowEwtSptGlyLow EWT Setpoint for Glycol°FWrite
AV31cpLowEwtSptWtrLow EWT Setpoint for Water°FWrite
AV32cpHydroHtgOnSptHydronic Heating ON Setpoint°FWrite
AV33cpStg2SptDiffSecond Stage Setpoint Differential°FWrite
AV34cpLowPresAlmDlyCompressor Low Pressure Alarm DelaysWrite
AV35SetptOffsetTemperature Setpoint Offset Input°FCommand
AV36cpStg3SptDiffThird Stage Heating Setpoint Differential°FWrite
AV37cpStg4SptDiffFourth Stage Heating Setpoint Differential°FWrite
AV38FanSpeedCmdFan Speed Output%Read
AV39FanRunHoursFan Runtime TotalizerhWrite
AV40CompRunHoursCompressor #1 Runtime Totalizer (Enfinity Large: Comp1RunHours)hWrite
AV41CompStartsCompressor #1 Starts Totalizer (Enfinity Large: Comp1Starts)Write
AV42CompHiCapRunHoursCompressor #2 Runtime Totalizer (Enfinity Large: Comp2RunHours)hWrite
AV43CompHiCapStartsCompressor #2 Starts Totalizer (Enfinity Large: Comp2Starts)Write
AV411MacAddressMAC address; named MacAddressSwitch when address switch is setWrite
AV412SystemMinInstanceSystem Minimum InstanceWrite
BI1BinaryInBinary Input StatusRead
BVmin1ClearAlarmClear AlarmWrite0=Normal, 1=Clear Alarm
BV2BinaryOutBinary Output StatusRead
MI1CondOverFlowCondensate Overflow StatusRead1=Dry, 2=Wet, 3=Null (no sensor present)
MI2FanOnAutoFan ON/Auto Switch Status (Room Sensor)Read1=On, 2=Auto, 3=Null (no switch present)
MI3HeatCoolAutoSystem Mode Switch (Heat/Cool/Auto) StatusRead1=Off, 2=Heat, 3=Cool, 4=Auto, 5=Null (no switch present)
MI4HumidistatHumidistat Sensor StatusRead1=Not Humid (Inactive 24VAC Input), 2=Is Humid (Active 24VAC Input), 3=Null
MI5FanRunStatusFan Running OutputRead1=Fan is off, 2=Fan is running
MV1ComprEnableCompressor Enable InputCommand1=Disabled, 2=Enabled, 3=Null (compressors are enabled)
MVmin2CurrentAlarmCurrent AlarmReadSmartSource: 1=No Alarms, 2=IO Exp Communication Fail, 3=Invalid Configuration, 4=Low Voltage Brownout, 5=Comp High Pressure, 6=Comp Low Pressure, 7=Comp Suction Temp Snsr Fail, 8=Comp Low Suction Temp, 9=Freeze Fault Detect, 10=Room Temp Sensor Fail, 11=Enter Water Temp Snsr Fail, 12=Leaving Water Temp Snsr Fail, 13=Condensate Overflow, 14=Low Entering Water Temp, 15=Serial EEPROM Corrupted, 16=Wtrside Econ Low Temp Cutout | Enfinity Large: 1=No Alarms, 2=IO Exp Communication Fail, 3=Invalid Configuration, 4=Low Voltage Brownout, 5=Comp #1 High Pressure, 6=Comp #2 High Pressure, 7=Comp #1 Low Pressure, 8=Comp #2 Low Pressure, 9=Comp #1 Suctn Temp Snsr Fail, 10=Comp #2 Suctn Temp Snsr Fail, 11=Comp #1 Low Suction Temp, 12=Comp #2 Low Suction Temp, 13=Freeze Fault Detect, 14=Room Temp Sensor Fail, 15=Entering Water Temp Sensor Fail, 16=Leaving Water Temp Snsr Fail, 17=Condensate Overflow, 18=Low Entering Water Temp, 19=Serial EEPROM Corrupted, 20=Wtrside Econ Low Temp Cutout
MV3RemoteFanOnAutoFan ON/Auto Remote InputCommand1=Fan Auto, 2=Fan On (forces fan on), 3=Null (no override)
MVmin4McQWSHPStatusMcQuay WSHP StatusRead1=Off Alarm, 2=Off, 3=Start, 4=Fan Only (fan is allowed to operate), 5=Prepare to Heat, 6=Heating, 7=Prepare to Cool, 8=Cooling, 9=Prepare to Dehumidify, 10=Dehumidification
MV5PreviousAlarmPrevious AlarmReadSmartSource: 1=No Alarms, 2=IO Exp Communication Fail, 3=Invalid Configuration, 4=Low Voltage Brownout, 5=Comp High Pressure, 6=Comp Low Pressure, 7=Comp Suction Temp Snsr Fail, 8=Comp Low Suction Temp, 9=Freeze Fault Detect, 10=Room Temp Sensor Fail, 11=Enter Water Temp Snsr Fail, 12=Leaving Water Temp Snsr Fail, 13=Condensate Overflow, 14=Low Entering Water Temp, 15=Serial EEPROM Corrupted, 16=Wtrside Econ Low Temp Cutout | Enfinity Large: 1=No Alarms, 2=IO Exp Communication Fail, 3=Invalid Configuration, 4=Low Voltage Brownout, 5=Comp #1 High Pressure, 6=Comp #2 High Pressure, 7=Comp #1 Low Pressure, 8=Comp #2 Low Pressure, 9=Comp #1 Suctn Temp Snsr Fail, 10=Comp #2 Suctn Temp Snsr Fail, 11=Comp #1 Low Suction Temp, 12=Comp #2 Low Suction Temp, 13=Freeze Fault Detect, 14=Room Temp Sensor Fail, 15=Entering Water Temp Sensor Fail, 16=Leaving Water Temp Snsr Fail, 17=Condensate Overflow, 18=Low Entering Water Temp, 19=Serial EEPROM Corrupted, 20=Wtrside Econ Low Temp Cutout
MV6EffectOccupEffective Occupancy OutputRead1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null
MVmin7OccManCmdOccupancy Override InputCommand1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null
MV8OccScheduleOccupancy Scheduler InputCommand1=Occupied, 2=Unoccupied, 3=Standby, 4=Null
MV9OccSensorOccupancy Sensor InputCommand1=Occupied, 2=Unoccupied, 3=Null
MVmin10ApplicModeApplication Mode InputCommand1=Auto, 2=Heat, 3=Cool, 4=Off, 5=Fan Only, 6=Dehumid, 7=Null
MV11AuxHeatEnableAuxiliary Heat Enable InputCommand1=Disabled, 2=Enabled, 3=Null
MV12EnergyHoldOffEnergy Hold Off InputCommand1=Normal, 2=Energy Hold Off, 3=Null
MV13PumpRequestPump Request OutputRead1=No Request for Flow, 2=Request for Flow, 3=Null
MV14cpLocSpEnableRoom Sensor Setpoint Adjust Enable/DisableWrite1=Disabled, 2=Enabled
MV15UnitsUnits (English/Metric)Write1=English (E), 2=Metric (M)
MV16RemoteHumidistatHumidistat Remote InputCommand1=No Dehumid Request, 2=Request Dehumidification, 3=Null

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor

How many BACnet points does the Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor have?

This list has 77 BACnet objects: 8 analog inputs, 45 analog values, 1 binary input, 2 binary values, 5 multi-state inputs, 16 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor BACnet points are writable?

53 of the 77 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor BACnet documentation?

The source is MicroTech III Water Source Heat Pump Unit Controller Protocol Information (ED 15103-9), revision 2021-08, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20III%20WSHP%20Unit%20Controller%20Protocol%20Information%20Daikin%20ED%2015103.pdf.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor?

Start with MV 7 OccManCmd (Occupancy override from the BMS); MV 10 ApplicMode (Application mode (Auto/Heat/Cool/Off/Fan Only/Dehumid)); AV 19 Setpoint (Network reference setpoint); BV 1 ClearAlarm (Clear the current alarm); MV 4 McQWSHPStatus (Unit operating status); AV 22 EffectSpaceTemp (Space temperature used for control); AI 2 LWT (Leaving water temperature); MV 2 CurrentAlarm (Highest-priority active alarm).

How do I enable BMS control of the Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor?

No local/remote switch is described. Network override objects take effect when written: Application Mode Input (MV 10) selects Auto/Heat/Cool/Off/Fan Only/Dehumid, Occupancy Override Input (MV 7) and Occupancy Scheduler Input (MV 8) set occupancy, and Compressor Enable Input (MV 1) permits compressor operation. Overrides revert to their default (Null) values after a controller reboot.

Does the Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor need a BACnet heartbeat or have a communication timeout?

Receive Heartbeat (AV 20, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled) is the maximum time a supported override may go without being rewritten before it reverts to its default. Each supported point has its own timer: AV 18, AV 35, MV 1, MV 8, MV 9, MV 10, MV 11 and MV 12. Send Heartbeat is not supported by the BACnet module; use COV instead.

Can the BMS supply sensor values to the Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor?

Write the space temperature to Space Temperature Input (AV 18); Effective Space Temperature (AV 22) uses the local AI 1 sensor unless AV 18 holds a valid value. Temperature Setpoint Input (AV 19) sets the reference setpoint for Occupied/Standby, but local setpoint adjust must first be disabled with MV 14. Temperature Setpoint Offset Input (AV 35) shifts the occupied/standby setpoints. Occupancy Sensor Input (MV 9) accepts a network occupancy sensor. Humidistat Remote Input (MV 16) and Fan ON/Auto Remote Input (MV 3) override the local humidistat and fan switch.

How do I check these points on the real MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech III Water Source Heat Pump Unit Controller Protocol Information · ED 15103-9 · rev. 2021-08. Object names, instances and units are reproduced as published; descriptions are our own.