Fan coil unit controller · BACnet points list

Daikin Applied MicroTech III Fan Coil Unit Controller BACnet points list

Updated 28 October 2026

Short answer

The MicroTech III fan coil controller joins a BACnet MS/TP trunk through a plug-in BACnet communication module (a LonWorks module is the alternative; only the BACnet objects are listed here). Points cover space, water and discharge temperatures, occupancy setpoints and differentials, valve and economizer tuning, network space temperature and setpoint inputs, occupancy and application mode commands, alarm status and PI loop objects. Configuration (cp...) objects live in non-volatile memory.

This page lists 76 BACnet objects for the Daikin Applied MicroTech III Fan Coil Unit Controller — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech III Fan Coil Unit Controller
Equipment
Fan coil unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
76 (50 writable)
Transport
BACnet MS/TP
Firmware
BACnet module v1.1 or later for Receive Heartbeat and BV 5 (PICS firmware v1.3)
Default device instance
3101000 + MS/TP MAC address (e.g. 3101007)
Also known as
MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135
Source document
MicroTech III Fan Coil Unit Controller Protocol Information (LonWorks / BACnet MS/TP) · ED 15135-6 · rev. 2021-01
Download CSV 76 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied MicroTech III Fan Coil Unit Controller

Integration in brief

Give the module a unique MAC and instance, then command occupancy and application mode and, if the BMS owns the setpoint, write Temperature Setpoint Input after disabling local setpoint adjust. Supply the space or water temperature from the BMS only when needed, and use Receive Heartbeat if overrides must fall back when the BMS goes quiet.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 6OccManCmdOccupancy override from the BMSCommand
MV 9ApplicModeApplication mode (Auto/Heat/Cool/Off/Fan/Economy/Dehumid)Command
AV 37SetpointNetwork reference setpointCommand
BV 1ClearAlarmClear the current alarmWrite
MV 4McQFcuStatusUnit operating statusRead
AV 22EffectSpaceTempSpace temperature used for controlRead
MV 3Fan SpeedCommanded fan speedRead
MV 1CurrentAlarmHighest-priority active alarmRead

Enable & remote start

No local/remote switch is described. Network inputs take effect when written: Application Mode Input (MV 9) overrides the room sensor mode switch, Occupancy Override Input (MV 6) and Occupancy Scheduler Input (MV 7) set occupancy, Energy Hold Off (MV 11) forces standby setpoints. These overrides revert to Null after a controller reboot.

Heartbeat & communication loss

Receive Heartbeat (AV 34, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled, v1.1 and later) is the longest a supported override may go without being rewritten before it reverts to its default. Supported points: AV 35, AV 36, AV 38, MV 7, MV 8, MV 9, MV 10, MV 11 and MV 13. Disabling device communication also triggers the revert.

Sensors & values from the BMS

Write the space temperature to Space Temperature Input (AV 36) and the water temperature to Remote Entering Water Temperature (AV 35); the effective values (AV 22, AV 20) use the local sensors unless these hold valid values. Temperature Setpoint Input (AV 37) sets the occupied/standby reference setpoint once local setpoint adjust is disabled with MV 12 = 1. Temperature Setpoint Offset Input (AV 38) shifts the occupied and standby setpoints. Occupancy Sensor Input (MV 8) accepts a network occupancy sensor.

Network setup

Watch out for

Daikin Applied MicroTech III Fan Coil Unit Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

76 of 76 shown
Type
Other
Access
Show
Daikin Applied MicroTech III Fan Coil Unit Controller BACnet Points List
DescriptionStates
AI1LocalSpaceTempLocal Space Temperature Output°FRead
AI2LocalSetptLocal Setpoint Adjust Output°FRead
AI3EWTLocal Entering Water Temperature°FRead
AI4DischAirTempDischarge Air Temperature°FRead
AI5OutdoorTempOutdoor Air Temperature°FRead
AV1cpOccupied_Cool_SetptOccupied Cooling Setpoint°FWrite
AV2cpStandby_Cool_SetptStandby Cool Setpoint°FWrite
AV3cpUnoccupied_Cool_SetptUnoccupied Cool Setpoint°FWrite
AV4cpOccupied_Heat_SetptOccupied Heat Setpoint°FWrite
AV5cpStandby_Heat_SetptStandby Heat Setpoint°FWrite
AV6cpUnoccupied_Heat_SetptUnoccupied Heat Setpoint°FWrite
AV7cpCoolEnDiffCooling Enable Differential°FWrite
AV8cpCoolIntStgTmrCooling Interstage TimersWrite
AV9cpCoolDBCooling Valve Deadband%Write
AV10cpCoolVlvStrokeCooling Valve Stroke TimesWrite
AV11cpMaxDASptEconomizer Maximum Discharge Air Setpoint°FWrite
AV12cpMinDASptEconomizer Minimum Discharge Air Setpoint°FWrite
AV13cpEconOaEnDiffEconomizer Outdoor Air Enable Differential°FWrite
AV14cpEconOaEnEconomizer Outdoor Air Enable Setpoint°FWrite
AV15cpEconLowMinEconomizer Min Position at Fan Low%Write
AV16cpEconMedMinEconomizer Min Position at Fan Med%Write
AV17cpEconHighMinEconomizer Min Position at Fan High%Write
AV18cpEconDBEconomizer Position Deadband%Write
AV19cpEconStrokeEconomizer Stroke TimesWrite
AV20EffectEWTEffective Entering Water Temperature°FRead
AV21EffectSetptEffective Setpoint Output°FRead
AVmin22EffectSpaceTempEffective Space Temperature Output°FRead
AV23cpEWTFlowTmrEntering Water Temperature Flow Sample Delay TimersWrite
AV24cpEWTSampleTmrEntering Water Temperature Sample Interval TimerminWrite
AV25cpFanMinOffTmrFan Minimum OFF TimersWrite
AV26cpFanMinOnTmrFan Minimum ON TimersWrite
AV27cpHeatEnDiffHeating Enable Differential°FWrite
AV28cpHeatIntStgTmrHeating Interstage TimersWrite
AV29cpHeatDBHeating Valve Deadband%Write
AV30cpHeatVlvStrokeHeating Valve Stroke TimesWrite
AV31cpBypassTimeLocal Bypass Time SetpointminWrite
AV32SetpointShiftSetpoint Shift Output°FRead
AV33cpOccDiffOccupied Setpoint Differential°FWrite
AV34cpRcvHrtBtReceive HeartbeatsWrite
AV35Network_EWTRemote Entering Water Temperature°FCommand
AV36Network_SpaceTempSpace Temperature Input°FCommand
AVmin37SetpointTemperature Setpoint Input°FCommand
AV38SetptOffsetTemperature Setpoint Offset Input°FCommand
AV39cpUnoccDiffUnoccupied Setpoint Differential°FWrite
AV40TerminalLoadTerminal Load Output%Read
AV41cpSptAdjMaxLong Range Setpoint Adjust Maximum°FWrite
AV42cpSptAdjMinLong Range Setpoint Adjust Minimum°FWrite
AV43cpFltrChangeHrsAir Filter Change TimerhWrite
AV411MacAddressMAC address; named MacAddressSwitch when address switch is setWrite
AV412SystemMinInstanceSystem Minimum InstanceWrite
BI1BinaryInBinary Input StatusRead
BVmin1ClearAlarmClear AlarmWrite0=Normal, 1=Clear Alarm
BV2BinaryOutBinary Output StatusRead
BV3UnitAppStatusUnit Application StatusRead
BV4UnitFaultsUnit FaultsRead
BV5SoftJumpersEquipment Configuration (v1.1 and later)Read
MI1FanModeSpdSwFan Mode/Speed StatusRead1=Off, 2=Low, 3=Med, 4=High, 5=Auto, 6=Null (no switch present)
MI2HeatCoolAutoSystem Mode Switch (Heat/Cool/Auto) StatusRead1=Off, 2=Heat, 3=Cool, 4=Auto, 5=Null (no switch present)
MVmin1CurrentAlarmCurrent AlarmRead1=No Alarms, 2=Invalid Equipment Configuration, 3=Emergency Shutdown, 4=Freeze Fault, 5=EWT Sensor Failure, 6=Room Temperature Sensor Failure, 7=IO Expansion Board Com Failure, 8=Condensate Overflow, 9=Outdoor Air Temp Sensor Failure, 10=Discharge Air Temp Sensor Failure, 11=Dirty Air Filter, 12=BB Serial EEPROM Corrupted
MV2PreviousAlarmPrevious AlarmRead1=No Alarms, 2=Invalid Equipment Configuration, 3=Emergency Shutdown, 4=Freeze Fault, 5=EWT Sensor Failure, 6=Room Temperature Sensor Failure, 7=IO Expansion Board Com Failure, 8=Condensate Overflow, 9=Outdoor Air Temp Sensor Fail, 10=Discharge Air Temp Sensor Fail, 11=Dirty Air Filter, 12=Serial EEPROM Corrupted
MVmin3Fan SpeedFan Speed OutputRead1=Off, 2=Low, 3=Medium, 4=High, 5=On
MVmin4McQFcuStatusMcQuay FCU StatusRead1=Off Alarm, 2=Off, 3=Start, 4=Fan Only, 5=Heating, 6=Economizer, 7=Cooling, 8=Dehumid, 9=Null
MV5EffectOccupEffective Occupancy OutputRead1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null
MVmin6OccManCmdOccupancy Override InputCommand1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null
MV7OccScheduleOccupancy Scheduler InputCommand1=Occupied, 2=Unoccupied, 3=Standby, 4=Null
MV8OccSensorOccupancy Sensor InputCommand1=Occupied, 2=Unoccupied, 3=Null
MVmin9ApplicModeApplication Mode InputCommand1=Auto, 2=Heat, 3=Cool, 4=Off, 5=Fan Only, 6=Economy, 7=Dehumid, 8=Null
MV10AuxHeatEnableAuxiliary Heat Enable InputCommand1=Disabled, 2=Enabled, 3=Null
MV11EnergyHoldOffEnergy Hold Off InputCommand1=Normal, 2=Energy Hold Off, 3=Null
MV12cpLocSpEnableRoom Sensor Setpoint Adjust Enable/DisableWrite1=Disabled, 2=Enabled
MV13EconEnableEconomizer Enable InputCommand1=Disabled, 2=Enabled, 3=Null
MV14UnitsUnits (English / Metric)Write1=English (E), 2=Metric (M)
LO1Heat Valve LoopHeating valve PI loop (output = valve position)%Read
LO2Cool Valve LoopCooling valve PI loop (output = valve position)%Read
LO3DASP_LoopEconomizer discharge-air PI loop (output = damper position)%Read
LO4EconPos_LoopEconomizer position PI loop (output = damper position)%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech III Fan Coil Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech III Fan Coil Unit Controller

How many BACnet points does the Daikin Applied MicroTech III Fan Coil Unit Controller have?

This list has 76 BACnet objects: 5 analog inputs, 45 analog values, 1 binary input, 5 binary values, 4 loops, 2 multi-state inputs, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech III Fan Coil Unit Controller BACnet points are writable?

50 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech III Fan Coil Unit Controller BACnet documentation?

The source is MicroTech III Fan Coil Unit Controller Protocol Information (LonWorks / BACnet MS/TP) (ED 15135-6), revision 2021-01, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20III%20FCU%20Unit%20Controller%20Protocol%20Information%20Daikin%20ED%2015135-6.pdf.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech III Fan Coil Unit Controller?

Start with MV 6 OccManCmd (Occupancy override from the BMS); MV 9 ApplicMode (Application mode (Auto/Heat/Cool/Off/Fan/Economy/Dehumid)); AV 37 Setpoint (Network reference setpoint); BV 1 ClearAlarm (Clear the current alarm); MV 4 McQFcuStatus (Unit operating status); AV 22 EffectSpaceTemp (Space temperature used for control); MV 3 Fan Speed (Commanded fan speed); MV 1 CurrentAlarm (Highest-priority active alarm).

How do I enable BMS control of the Daikin Applied MicroTech III Fan Coil Unit Controller?

No local/remote switch is described. Network inputs take effect when written: Application Mode Input (MV 9) overrides the room sensor mode switch, Occupancy Override Input (MV 6) and Occupancy Scheduler Input (MV 7) set occupancy, Energy Hold Off (MV 11) forces standby setpoints. These overrides revert to Null after a controller reboot.

Does the Daikin Applied MicroTech III Fan Coil Unit Controller need a BACnet heartbeat or have a communication timeout?

Receive Heartbeat (AV 34, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled, v1.1 and later) is the longest a supported override may go without being rewritten before it reverts to its default. Supported points: AV 35, AV 36, AV 38, MV 7, MV 8, MV 9, MV 10, MV 11 and MV 13. Disabling device communication also triggers the revert.

Can the BMS supply sensor values to the Daikin Applied MicroTech III Fan Coil Unit Controller?

Write the space temperature to Space Temperature Input (AV 36) and the water temperature to Remote Entering Water Temperature (AV 35); the effective values (AV 22, AV 20) use the local sensors unless these hold valid values. Temperature Setpoint Input (AV 37) sets the occupied/standby reference setpoint once local setpoint adjust is disabled with MV 12 = 1. Temperature Setpoint Offset Input (AV 38) shifts the occupied and standby setpoints. Occupancy Sensor Input (MV 8) accepts a network occupancy sensor.

How do I check these points on the real MicroTech III Fan Coil Unit Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech III Fan Coil Unit Controller Protocol Information (LonWorks / BACnet MS/TP) · ED 15135-6 · rev. 2021-01. Object names, instances and units are reproduced as published; descriptions are our own.