VAV terminal unit controller · BACnet points list

Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet points list

Updated 28 October 2026

Short answer

The Daikin VAV controller is a combined damper actuator and DDC controller for pressure-independent VAV boxes, BTL listed as a B-ASC on BACnet MS/TP. It runs one of nine application programs (6630-6637 plus 6684 slave mode), and some object instances change name and meaning with the application. Most objects are AO/BO values stored in EEPROM, so the BAS should write them sparingly.

This page lists 104 BACnet objects for the Daikin Applied Daikin VAV Controller (BACnet MS/TP) — 96 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
Daikin VAV Controller (BACnet MS/TP)
Equipment
VAV terminal unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
104 (96 writable)
Transport
BACnet MS/TP
Firmware
Software 1.2, BACnet firmware BV13 1.0 (PICS)
Default device instance
3101014 (listed default; set with WCIS)
Also known as
Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157
Source document
Daikin VAV Controller BACnet MS/TP Network Integration (Table 4: BACnet Point List) · ED 19157 · rev. April 2026
Download CSV 104 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied Daikin VAV Controller (BACnet MS/TP)

Integration in brief

Address the controller and pick the application with the WCIS software (network settings cannot be set from the BAS). The BAS then switches DAY.NGT for occupancy, adjusts the day setpoints and reads room temperature, airflow and damper position. Keep writes to the AO/BO objects to a minimum because they go to EEPROM.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 29DAY.NGTOccupancy command: 0 = day, 1 = nightWrite
AO 6DAY CLG STPTDay (occupied) cooling setpointWrite
AO 7DAY HTG STPTDay (occupied) heating setpointWrite
BO 5HEAT.COOLCurrent mode: 0 = cool, 1 = heatWrite
AI 4ROOM TEMPRoom temperature from the sensorRead
AO 92CTL STPTSetpoint the temperature loop is usingWrite
AI 35AIR VOLUMEMeasured airflow, CFMRead
AO 49DMPR POS / MTR1 POSDamper position, % (calculated from run time)Write
AO 99ERROR STATUSPower-up error code; 0 = no errorsWrite

Enable & remote start

No separate enable. DAY.NGT (BO 29) selects day or night setpoints and is normally written by the field panel. The controller only controls once an application (6630-6637) is selected; out of the box it runs 6684 slave mode with no control. CTL TEMP (AO 78) and the active flow limits (AO 76, AO 77) follow their normal sources unless overridden.

Sensors & values from the BMS

Room temperature, CO2 and RH come from the wired room unit (AI 4, AI 125, AI 126). CTL TEMP (AO 78) is ROOM TEMP plus RMTMP OFFSET unless it is overridden; the guide gives no timeout for an override.

Network setup

Watch out for

Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

104 of 104 shown
Type
Access
Show
Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet Points List
DescriptionStates
AO1CTLR ADDRESSMS/TP MAC address of the controllerWrite
AO2APPLICATIONApplication number running in the controllerWrite
AO3RMTMP OFFSETRoom temperature calibration offset°FWrite
AImin4ROOM TEMPRoom temperature sensor reading°FRead
BOmin5HEAT.COOLCurrent heating or cooling modeWrite0=Cool, 1=Heat
AOmin6DAY CLG STPTDay (occupied) cooling setpoint°FWrite
AOmin7DAY HTG STPTDay (occupied) heating setpoint°FWrite
AO8NGT CLG STPTNight (unoccupied) cooling setpoint°FWrite
AO9NGT HTG STPTNight (unoccupied) heating setpoint°FWrite
AO10DEW POINTDew point calculated from CTL TEMP and RM RH°FWrite
AO11RM STPT MINLowest setpoint allowed from the setpoint dial°FWrite
AO12RM STPT MAXHighest setpoint allowed from the setpoint dial°FWrite
AI13RM STPT DIALSetpoint from the room sensor dial°FRead
BO14STPT DIALUse the room sensor setpoint dial (YES/NO)Write0=NO, 1=YES
AI15AUX TEMP AI 3 / SUPPLY TEMPAI 3 thermistor reading (supply temp in 6631)°FRead
AO16FLOW STARTHeating loop output where flow setpoint starts rising%Write
AO17FLOW ENDHeating loop output where flow setpoint starts falling%Write
BO18WALL SWITCHMonitor a wall switch on the DI input (YES/NO)Write0=NO, 1=YES
BI19DI OVRD SWRoom sensor override button statusRead0=OFF, 1=ON
AO20OVRD TIMEOverride duration in hourshWrite
BO21NGT OVRDOverride state (DAY = override timer active)Write0=Day, 1=Night
AO22REHEAT STARTHeating loop output where reheat starts%Write
AO23REHEAT ENDHeating loop output where reheat ends%Write
BI24DI 4Status of the DI 4 contactWrite0=OFF, 1=ON
BI25DI 3Status of the DI 3 contactWrite0=OFF, 1=ON
AO26SERIES OFFFlow above which the series fan turns on%Write
AO27SERIES OFFFlow below which the series fan turns off%Write
AO28PARALLEL ONFlow below which the parallel fan turns on%Write
BOmin29DAY.NGTDay/night (occupancy) mode, normally set by the BASWrite0=Day, 1=Night
AO30PARALLEL OFFFlow above which the parallel fan turns off%Write
AO31CLG FLOW MINMinimum airflow in coolingCFMWrite
AO32CLG FLOW MAXMaximum airflow in coolingCFMWrite
AO33HTG FLOW MINMinimum airflow in heatingCFMWrite
AO34HTG FLOW MAXMaximum airflow in heatingCFMWrite
AImin35AIR VOLUMEMeasured airflowCFMRead
AO36FLOW COEFFAirflow sensor calibration factorWrite
AO37MTR3 COMD / VLV2 COMDMotor 3 / valve 2 command%Write
AO38MTR3 POS / VLV2 POSMotor 3 / valve 2 position (calculated)%Write
AO39MTR3 TIMINGMotor 3 full-stroke timesWrite
AO40NGT FLOW MINOptional minimum airflow in night modeCFMWrite
BO41DO 1Digital output 1Write0=OFF, 1=ON
BO42DO 2Digital output 2Write0=OFF, 1=ON
BO43DO 3 / HEAT STAGE 1Digital output 3 / electric heat stage 1Write0=OFF, 1=ON
BO44DO 4 / HEAT STAGE 2Digital output 4 / electric heat stage 2Write0=OFF, 1=ON
BO45DO 5 / HEAT STAGE 3Digital output 5 / electric heat stage 3Write0=OFF, 1=ON
BO46DO 6 / FANDigital output 6 / fan output on fan-powered boxesWrite0=OFF, 1=ON
AO47VENT DMD MINOptional ventilation minimum airflow in day modeCFMWrite
AO48DMPR COMD / MTR1 COMDDamper command%Write
AOmin49DMPR POS / MTR1 POSDamper position (calculated from run time)%Write
AI50AI 4AI 4 thermistor reading°FRead
AO51MTR1 TIMINGMotor 1 full-stroke timesWrite
AO52MTR2 COMD / VLV COMD / VLV1 COMDMotor 2 / water valve command%Write
AO53MTR2 POS / VLV POS / VLV1 POSMotor 2 / water valve position (calculated)%Write
AO54STPT SPANWarmer/cooler setpoint span for the room unit (0 = absolute)°FWrite
AO55MTR2 TIMINGMotor 2 full-stroke timesWrite
AO56DMPR ROT ANG / DPR1 ROT ANGDamper rotation angleWrite
AO57DPR2 ROT ANGDamper 2 (hot duct) rotation angleWrite
AO58MTR SETUPMotor 1 and 2 setup codeWrite
AO59DO DIR.REVDirect/reverse setup code for the DOsWrite
AO60HEAT FLOWFlow required before electric heat is enabled%Write
AO61COOL TEMPDischarge temp that switches to cooling (6631)°FWrite
AO62HEAT TEMPDischarge temp that switches to heating (6631)°FWrite
AO63CLG P GAINCooling loop proportional gainWrite
AO64CLG l GAINCooling loop integral gainWrite
AO65CLG D GAINCooling loop derivative gainWrite
BO66CHK OUTStart the built-in checkout procedureWrite0=OFF, 1=ON
AO67HTG P GAINHeating loop proportional gainWrite
AO68HTG l GAINHeating loop integral gainWrite
AO69HTG D GAINHeating loop derivative gainWrite
AO70CHK STATUSCheckout result code (bit-added)Write
AO71FLOW P GAINFlow loop proportional gainWrite
AO72FLOW l GAINFlow loop integral gainWrite
AO73FLOW D GAINFlow loop derivative gainWrite
AO74FLOW BIASFlow loop bias%Write
AO75FLOWAirflow as a percent of CTL FLOW MAX%Write
AO76CTL FLOW MINActive minimum airflow limitCFMWrite
AO77CTL FLOW MAXActive maximum airflow limitCFMWrite
AO78CTL TEMPTemperature used for control (ROOM TEMP + offset)°FWrite
AO79CLG LOOPOUTCooling loop output%Write
AO80HTG LOOPOUTHeating loop output%Write
AO81AVG HEAT OUTElectric heat demand across stages (0-300 %)%Write
AO82STAGE MAXHeating loop value for full-duty electric heat%Write
AO83STAGE FAN / STAGE MINValve opening before the fan starts / stage minimum%Write
AO84AOV 1Analog output 1 (0-10 V)VWrite
AO85SWITCH LIMITLoop output below which heat/cool can change over%Write
AO86SWITCH TIMEMinimum time between heat/cool changeoversminWrite
BO87CAL MODULEUse Autozero modules for calibration (YES/NO)Write0=YES, 1=NO
AO88STAGE COUNT / VALVE COUNTNumber of electric heat stages / heating valvesWrite
AO89STAGE TIMEElectric reheat cycle timeminWrite
AO90SWITCH DBANDTemperature deadband for heat/cool changeover°FWrite
AOmin92CTL STPTActive temperature setpoint°FWrite
AO93FLOW STPTFlow loop setpoint%Write
BO94CAL AIRStart an airflow sensor calibrationWrite0=NO, 1=YES
AO95CAL SETUPCalibration trigger option codeWrite
AO96CAL TIMERInterval between timed calibrationshWrite
AO97DUCT AREADuct area at the airflow sensorft²Write
AO98LOOP TIMEControl loop intervalsWrite
AOmin99ERROR STATUSPower-up error code (0 = no errors)Write
AO102AOV 1 CLOSEAO voltage for valve fully closedVWrite
AO103AOV 1 OPENAO voltage for valve fully openVWrite
AO124SENSOR SELRoom unit and thermistor type selection (additive)Write
AI125RM CO2Room CO2 levelppmRead
AI126RM RHRoom relative humidity%Read
BO127PPCL STATECustom PPCL program loaded or emptyWrite0=EMPTY, 1=LOADED

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Daikin VAV Controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied Daikin VAV Controller (BACnet MS/TP)

How many BACnet points does the Daikin Applied Daikin VAV Controller (BACnet MS/TP) have?

This list has 104 BACnet objects: 7 analog inputs, 79 analog outputs, 3 binary inputs, 15 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet points are writable?

96 of the 104 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet documentation?

The source is Daikin VAV Controller BACnet MS/TP Network Integration (Table 4: BACnet Point List) (ED 19157), revision April 2026, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019157%20Daikin%20VAV%20Controller%20BACnet%20Protocol%20Document.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied Daikin VAV Controller (BACnet MS/TP)?

Start with BO 29 DAY.NGT (Occupancy command: 0 = day, 1 = night); AO 6 DAY CLG STPT (Day (occupied) cooling setpoint); AO 7 DAY HTG STPT (Day (occupied) heating setpoint); BO 5 HEAT.COOL (Current mode: 0 = cool, 1 = heat); AI 4 ROOM TEMP (Room temperature from the sensor); AO 92 CTL STPT (Setpoint the temperature loop is using); AI 35 AIR VOLUME (Measured airflow, CFM); AO 49 DMPR POS / MTR1 POS (Damper position, % (calculated from run time)); AO 99 ERROR STATUS (Power-up error code; 0 = no errors).

How do I enable BMS control of the Daikin Applied Daikin VAV Controller (BACnet MS/TP)?

No separate enable. DAY.NGT (BO 29) selects day or night setpoints and is normally written by the field panel. The controller only controls once an application (6630-6637) is selected; out of the box it runs 6684 slave mode with no control. CTL TEMP (AO 78) and the active flow limits (AO 76, AO 77) follow their normal sources unless overridden.

Can the BMS supply sensor values to the Daikin Applied Daikin VAV Controller (BACnet MS/TP)?

Room temperature, CO2 and RH come from the wired room unit (AI 4, AI 125, AI 126). CTL TEMP (AO 78) is ROOM TEMP plus RMTMP OFFSET unless it is overridden; the guide gives no timeout for an override.

How do I check these points on the real Daikin VAV Controller (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: Daikin VAV Controller BACnet MS/TP Network Integration (Table 4: BACnet Point List) · ED 19157 · rev. April 2026. Object names, instances and units are reproduced as published; descriptions are our own.