VAV terminal unit controller · BACnet points list
Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet points list
Updated 28 October 2026
The Daikin VAV controller is a combined damper actuator and DDC controller for pressure-independent VAV boxes, BTL listed as a B-ASC on BACnet MS/TP. It runs one of nine application programs (6630-6637 plus 6684 slave mode), and some object instances change name and meaning with the application. Most objects are AO/BO values stored in EEPROM, so the BAS should write them sparingly.
This page lists 104 BACnet objects for the Daikin Applied Daikin VAV Controller (BACnet MS/TP) — 96 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- Daikin VAV Controller (BACnet MS/TP)
- Equipment
- VAV terminal unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 104 (96 writable)
- Transport
- BACnet MS/TP
- Firmware
- Software 1.2, BACnet firmware BV13 1.0 (PICS)
- Default device instance
- 3101014 (listed default; set with WCIS)
- Also known as
- Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157
BMS integration notes: Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Address the controller and pick the application with the WCIS software (network settings cannot be set from the BAS). The BAS then switches DAY.NGT for occupancy, adjusts the day setpoints and reads room temperature, airflow and damper position. Keep writes to the AO/BO objects to a minimum because they go to EEPROM.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 29 | DAY.NGT | Occupancy command: 0 = day, 1 = night | Write |
| AO 6 | DAY CLG STPT | Day (occupied) cooling setpoint | Write |
| AO 7 | DAY HTG STPT | Day (occupied) heating setpoint | Write |
| BO 5 | HEAT.COOL | Current mode: 0 = cool, 1 = heat | Write |
| AI 4 | ROOM TEMP | Room temperature from the sensor | Read |
| AO 92 | CTL STPT | Setpoint the temperature loop is using | Write |
| AI 35 | AIR VOLUME | Measured airflow, CFM | Read |
| AO 49 | DMPR POS / MTR1 POS | Damper position, % (calculated from run time) | Write |
| AO 99 | ERROR STATUS | Power-up error code; 0 = no errors | Write |
Enable & remote start
No separate enable. DAY.NGT (BO 29) selects day or night setpoints and is normally written by the field panel. The controller only controls once an application (6630-6637) is selected; out of the box it runs 6684 slave mode with no control. CTL TEMP (AO 78) and the active flow limits (AO 76, AO 77) follow their normal sources unless overridden.
Sensors & values from the BMS
Room temperature, CO2 and RH come from the wired room unit (AI 4, AI 125, AI 126). CTL TEMP (AO 78) is ROOM TEMP plus RMTMP OFFSET unless it is overridden; the guide gives no timeout for an override.
Network setup
- Use WCIS to set CTLR ADDRESS (MAC, use 1-127), device instance, baud, Max Masters and application; these cannot be set from the BAS.
- Defaults: MAC 255, device instance 3101014, baud 38400, Max Masters 127, initial value priority 15.
- First power-up runs application 6684 (slave mode, no control) until an application number is written.
- Run the checkout (CHK OUT, BO 66) after commissioning and read the bit-added result in CHK STATUS (AO 70).
Watch out for
- AO/BO writes go to EEPROM/Flash with a finite write count; do not write setpoints cyclically.
- Object names and meaning of some instances change with the application number.
- Many values are calculated or configuration objects even though they are AO/BO R/W (e.g. DMPR POS, FLOW, CHK STATUS).
- CAL MODULE states are printed as 0=YES, 1=NO, the reverse of the other YES/NO points.
Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AO | 1 | CTLR ADDRESS | MS/TP MAC address of the controller | Write | ||
| AO | 2 | APPLICATION | Application number running in the controller | Write | ||
| AO | 3 | RMTMP OFFSET | Room temperature calibration offset | °F | Write | |
| AImin | 4 | ROOM TEMP | Room temperature sensor reading | °F | Read | |
| BOmin | 5 | HEAT.COOL | Current heating or cooling mode | Write | 0=Cool, 1=Heat | |
| AOmin | 6 | DAY CLG STPT | Day (occupied) cooling setpoint | °F | Write | |
| AOmin | 7 | DAY HTG STPT | Day (occupied) heating setpoint | °F | Write | |
| AO | 8 | NGT CLG STPT | Night (unoccupied) cooling setpoint | °F | Write | |
| AO | 9 | NGT HTG STPT | Night (unoccupied) heating setpoint | °F | Write | |
| AO | 10 | DEW POINT | Dew point calculated from CTL TEMP and RM RH | °F | Write | |
| AO | 11 | RM STPT MIN | Lowest setpoint allowed from the setpoint dial | °F | Write | |
| AO | 12 | RM STPT MAX | Highest setpoint allowed from the setpoint dial | °F | Write | |
| AI | 13 | RM STPT DIAL | Setpoint from the room sensor dial | °F | Read | |
| BO | 14 | STPT DIAL | Use the room sensor setpoint dial (YES/NO) | Write | 0=NO, 1=YES | |
| AI | 15 | AUX TEMP AI 3 / SUPPLY TEMP | AI 3 thermistor reading (supply temp in 6631) | °F | Read | |
| AO | 16 | FLOW START | Heating loop output where flow setpoint starts rising | % | Write | |
| AO | 17 | FLOW END | Heating loop output where flow setpoint starts falling | % | Write | |
| BO | 18 | WALL SWITCH | Monitor a wall switch on the DI input (YES/NO) | Write | 0=NO, 1=YES | |
| BI | 19 | DI OVRD SW | Room sensor override button status | Read | 0=OFF, 1=ON | |
| AO | 20 | OVRD TIME | Override duration in hours | h | Write | |
| BO | 21 | NGT OVRD | Override state (DAY = override timer active) | Write | 0=Day, 1=Night | |
| AO | 22 | REHEAT START | Heating loop output where reheat starts | % | Write | |
| AO | 23 | REHEAT END | Heating loop output where reheat ends | % | Write | |
| BI | 24 | DI 4 | Status of the DI 4 contact | Write | 0=OFF, 1=ON | |
| BI | 25 | DI 3 | Status of the DI 3 contact | Write | 0=OFF, 1=ON | |
| AO | 26 | SERIES OFF | Flow above which the series fan turns on | % | Write | |
| AO | 27 | SERIES OFF | Flow below which the series fan turns off | % | Write | |
| AO | 28 | PARALLEL ON | Flow below which the parallel fan turns on | % | Write | |
| BOmin | 29 | DAY.NGT | Day/night (occupancy) mode, normally set by the BAS | Write | 0=Day, 1=Night | |
| AO | 30 | PARALLEL OFF | Flow above which the parallel fan turns off | % | Write | |
| AO | 31 | CLG FLOW MIN | Minimum airflow in cooling | CFM | Write | |
| AO | 32 | CLG FLOW MAX | Maximum airflow in cooling | CFM | Write | |
| AO | 33 | HTG FLOW MIN | Minimum airflow in heating | CFM | Write | |
| AO | 34 | HTG FLOW MAX | Maximum airflow in heating | CFM | Write | |
| AImin | 35 | AIR VOLUME | Measured airflow | CFM | Read | |
| AO | 36 | FLOW COEFF | Airflow sensor calibration factor | Write | ||
| AO | 37 | MTR3 COMD / VLV2 COMD | Motor 3 / valve 2 command | % | Write | |
| AO | 38 | MTR3 POS / VLV2 POS | Motor 3 / valve 2 position (calculated) | % | Write | |
| AO | 39 | MTR3 TIMING | Motor 3 full-stroke time | s | Write | |
| AO | 40 | NGT FLOW MIN | Optional minimum airflow in night mode | CFM | Write | |
| BO | 41 | DO 1 | Digital output 1 | Write | 0=OFF, 1=ON | |
| BO | 42 | DO 2 | Digital output 2 | Write | 0=OFF, 1=ON | |
| BO | 43 | DO 3 / HEAT STAGE 1 | Digital output 3 / electric heat stage 1 | Write | 0=OFF, 1=ON | |
| BO | 44 | DO 4 / HEAT STAGE 2 | Digital output 4 / electric heat stage 2 | Write | 0=OFF, 1=ON | |
| BO | 45 | DO 5 / HEAT STAGE 3 | Digital output 5 / electric heat stage 3 | Write | 0=OFF, 1=ON | |
| BO | 46 | DO 6 / FAN | Digital output 6 / fan output on fan-powered boxes | Write | 0=OFF, 1=ON | |
| AO | 47 | VENT DMD MIN | Optional ventilation minimum airflow in day mode | CFM | Write | |
| AO | 48 | DMPR COMD / MTR1 COMD | Damper command | % | Write | |
| AOmin | 49 | DMPR POS / MTR1 POS | Damper position (calculated from run time) | % | Write | |
| AI | 50 | AI 4 | AI 4 thermistor reading | °F | Read | |
| AO | 51 | MTR1 TIMING | Motor 1 full-stroke time | s | Write | |
| AO | 52 | MTR2 COMD / VLV COMD / VLV1 COMD | Motor 2 / water valve command | % | Write | |
| AO | 53 | MTR2 POS / VLV POS / VLV1 POS | Motor 2 / water valve position (calculated) | % | Write | |
| AO | 54 | STPT SPAN | Warmer/cooler setpoint span for the room unit (0 = absolute) | °F | Write | |
| AO | 55 | MTR2 TIMING | Motor 2 full-stroke time | s | Write | |
| AO | 56 | DMPR ROT ANG / DPR1 ROT ANG | Damper rotation angle | Write | ||
| AO | 57 | DPR2 ROT ANG | Damper 2 (hot duct) rotation angle | Write | ||
| AO | 58 | MTR SETUP | Motor 1 and 2 setup code | Write | ||
| AO | 59 | DO DIR.REV | Direct/reverse setup code for the DOs | Write | ||
| AO | 60 | HEAT FLOW | Flow required before electric heat is enabled | % | Write | |
| AO | 61 | COOL TEMP | Discharge temp that switches to cooling (6631) | °F | Write | |
| AO | 62 | HEAT TEMP | Discharge temp that switches to heating (6631) | °F | Write | |
| AO | 63 | CLG P GAIN | Cooling loop proportional gain | Write | ||
| AO | 64 | CLG l GAIN | Cooling loop integral gain | Write | ||
| AO | 65 | CLG D GAIN | Cooling loop derivative gain | Write | ||
| BO | 66 | CHK OUT | Start the built-in checkout procedure | Write | 0=OFF, 1=ON | |
| AO | 67 | HTG P GAIN | Heating loop proportional gain | Write | ||
| AO | 68 | HTG l GAIN | Heating loop integral gain | Write | ||
| AO | 69 | HTG D GAIN | Heating loop derivative gain | Write | ||
| AO | 70 | CHK STATUS | Checkout result code (bit-added) | Write | ||
| AO | 71 | FLOW P GAIN | Flow loop proportional gain | Write | ||
| AO | 72 | FLOW l GAIN | Flow loop integral gain | Write | ||
| AO | 73 | FLOW D GAIN | Flow loop derivative gain | Write | ||
| AO | 74 | FLOW BIAS | Flow loop bias | % | Write | |
| AO | 75 | FLOW | Airflow as a percent of CTL FLOW MAX | % | Write | |
| AO | 76 | CTL FLOW MIN | Active minimum airflow limit | CFM | Write | |
| AO | 77 | CTL FLOW MAX | Active maximum airflow limit | CFM | Write | |
| AO | 78 | CTL TEMP | Temperature used for control (ROOM TEMP + offset) | °F | Write | |
| AO | 79 | CLG LOOPOUT | Cooling loop output | % | Write | |
| AO | 80 | HTG LOOPOUT | Heating loop output | % | Write | |
| AO | 81 | AVG HEAT OUT | Electric heat demand across stages (0-300 %) | % | Write | |
| AO | 82 | STAGE MAX | Heating loop value for full-duty electric heat | % | Write | |
| AO | 83 | STAGE FAN / STAGE MIN | Valve opening before the fan starts / stage minimum | % | Write | |
| AO | 84 | AOV 1 | Analog output 1 (0-10 V) | V | Write | |
| AO | 85 | SWITCH LIMIT | Loop output below which heat/cool can change over | % | Write | |
| AO | 86 | SWITCH TIME | Minimum time between heat/cool changeovers | min | Write | |
| BO | 87 | CAL MODULE | Use Autozero modules for calibration (YES/NO) | Write | 0=YES, 1=NO | |
| AO | 88 | STAGE COUNT / VALVE COUNT | Number of electric heat stages / heating valves | Write | ||
| AO | 89 | STAGE TIME | Electric reheat cycle time | min | Write | |
| AO | 90 | SWITCH DBAND | Temperature deadband for heat/cool changeover | °F | Write | |
| AOmin | 92 | CTL STPT | Active temperature setpoint | °F | Write | |
| AO | 93 | FLOW STPT | Flow loop setpoint | % | Write | |
| BO | 94 | CAL AIR | Start an airflow sensor calibration | Write | 0=NO, 1=YES | |
| AO | 95 | CAL SETUP | Calibration trigger option code | Write | ||
| AO | 96 | CAL TIMER | Interval between timed calibrations | h | Write | |
| AO | 97 | DUCT AREA | Duct area at the airflow sensor | ft² | Write | |
| AO | 98 | LOOP TIME | Control loop interval | s | Write | |
| AOmin | 99 | ERROR STATUS | Power-up error code (0 = no errors) | Write | ||
| AO | 102 | AOV 1 CLOSE | AO voltage for valve fully closed | V | Write | |
| AO | 103 | AOV 1 OPEN | AO voltage for valve fully open | V | Write | |
| AO | 124 | SENSOR SEL | Room unit and thermistor type selection (additive) | Write | ||
| AI | 125 | RM CO2 | Room CO2 level | ppm | Read | |
| AI | 126 | RM RH | Room relative humidity | % | Read | |
| BO | 127 | PPCL STATE | Custom PPCL program loaded or empty | Write | 0=EMPTY, 1=LOADED |
No points match these filters.
Integration notes
- Some instances carry a different object name per application (e.g. BO 46 is DO 6 or FAN); those are shown as 'name A / name B'.
- The source prints the AO 2 name as 'APPLICATIONOFF'; elsewhere it is called APPLICATION.
- AO 26 and AO 27 are both printed as SERIES OFF (AO 26 is the series fan on threshold).
- Gain objects are printed as CLG l GAIN, HTG l GAIN and FLOW l GAIN (lowercase L) and kept as printed.
- Points marked as 'unbundled' in the guide are the ones meant to be exposed individually to a BAS; the rest stay bundled in the application.
- Writable AO/BO objects are stored in EEPROM/Flash with a limited write life.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Daikin VAV Controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied Daikin VAV Controller (BACnet MS/TP)
How many BACnet points does the Daikin Applied Daikin VAV Controller (BACnet MS/TP) have?
This list has 104 BACnet objects: 7 analog inputs, 79 analog outputs, 3 binary inputs, 15 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet points are writable?
96 of the 104 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied Daikin VAV Controller (BACnet MS/TP) BACnet documentation?
The source is Daikin VAV Controller BACnet MS/TP Network Integration (Table 4: BACnet Point List) (ED 19157), revision April 2026, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019157%20Daikin%20VAV%20Controller%20BACnet%20Protocol%20Document.pdf/.
What are the minimum BACnet points to integrate the Daikin Applied Daikin VAV Controller (BACnet MS/TP)?
Start with BO 29 DAY.NGT (Occupancy command: 0 = day, 1 = night); AO 6 DAY CLG STPT (Day (occupied) cooling setpoint); AO 7 DAY HTG STPT (Day (occupied) heating setpoint); BO 5 HEAT.COOL (Current mode: 0 = cool, 1 = heat); AI 4 ROOM TEMP (Room temperature from the sensor); AO 92 CTL STPT (Setpoint the temperature loop is using); AI 35 AIR VOLUME (Measured airflow, CFM); AO 49 DMPR POS / MTR1 POS (Damper position, % (calculated from run time)); AO 99 ERROR STATUS (Power-up error code; 0 = no errors).
How do I enable BMS control of the Daikin Applied Daikin VAV Controller (BACnet MS/TP)?
No separate enable. DAY.NGT (BO 29) selects day or night setpoints and is normally written by the field panel. The controller only controls once an application (6630-6637) is selected; out of the box it runs 6684 slave mode with no control. CTL TEMP (AO 78) and the active flow limits (AO 76, AO 77) follow their normal sources unless overridden.
Can the BMS supply sensor values to the Daikin Applied Daikin VAV Controller (BACnet MS/TP)?
Room temperature, CO2 and RH come from the wired room unit (AI 4, AI 125, AI 126). CTL TEMP (AO 78) is ROOM TEMP plus RMTMP OFFSET unless it is overridden; the guide gives no timeout for an override.
How do I check these points on the real Daikin VAV Controller (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00
Source: Daikin VAV Controller BACnet MS/TP Network Integration (Table 4: BACnet Point List) · ED 19157 · rev. April 2026. Object names, instances and units are reproduced as published; descriptions are our own.