Air-cooled scroll chiller controller · BACnet points list

Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe) BACnet points list

Updated 28 October 2026

Short answer

The EWAT-B air-cooled chillers use a MicroTech 4 controller running the "NASH" software. BACnet IP or BACnet MS/TP comes from a POL908/POL904 module or the onboard software option. The list covers unit enable, mode and network setpoints, heat recovery, free cooling, variable primary flow, per-circuit refrigerant and fan data for up to three compressors per circuit, and alarm objects.

This page lists 165 BACnet objects for the Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe) — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
EWAT-B air-cooled chiller (Daikin Applied Europe)
Equipment
Air-cooled scroll chiller controller
Equipment type
Chillers
BACnet objects
165 (33 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
NASH 2.14.A (latest revision listed)
Default device instance
1
Also known as
EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103
Source document
BAS Integration guide - BACnet protocol (EWAT-B) · D-EIGOC00103-22_02EN_EWAT-B · rev. 2024-07
Download CSV 165 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)

Integration in brief

Select network control at the unit (CtrlSource BI 3 then reads Network), enable the chiller with UnitEnableStp, and write the mode, cool setpoint and capacity limit at priority 8. Monitor unit status, leaving water temperature, the generic alarm and the fault code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2UnitEnableStpNetwork enable/disable of the chillerCommand
MV 3UnitModeSetpointNetworkIce / cool / heat / pursuit mode commandCommand
AV 4NetworkCoolTempSetpointLeaving water cool setpoint from the BMSCommand
AV 3NetworkCapacityLimitSetpointCapacity limit from the BMSCommand
BV 8ClearAlarmClear alarms from the networkCommand
BI 3CtrlSourceShows whether network control is activeRead
MV 1UnitStatusChiller run stateRead
AI 2EvapLvgWTempLeaving chilled water temperatureRead
BI 10AlarmOutputAny active alarmRead
AV 905AVFaultAlarmCodeActive fault alarm codeRead

Enable & remote start

CtrlSource (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes UnitEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.

Sensors & values from the BMS

VarFlow'LoadDPres (AI 1905, plant differential pressure) is marked writable for variable primary flow; the guide does not say whether the BMS must supply it.

Network setup

Watch out for

Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

165 of 165 shown
Type
Multi-state
Access
Show
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe) BACnet Points List
DescriptionStates
BImin3CtrlSourceUnit - Control SourceRead0=Network, 1=Local
BI7EnableOutputUnit - Enabled StateRead0=Disabled, 1=Enabled
BI5RunEnabledUnit - Run AllowedRead0=Off, 1=Allowed
BI6UnitLimitedUnit - Capacity LimitedRead0=NotLimited, 1=Limited
BImin10AlarmOutputUnit - Generic AlarmRead0=NoAlarm, 1=Alarm
BI2EvapWFlowStateEvaporator - Water Flow StateRead0=NoFlow, 1=Flow
BI4UnitOnOffUnit - Operating StateRead0=ThermoOff, 1=ThermoOn
BVmin2UnitEnableStpUnit - Enable SetpointCommand0=Disable, 1=Enable
BVmin8ClearAlarmUnit - Alarm Reset SetpointCommand0=None, 1=Clear
MV2ActModeUnit - Active Operation ModeRead1=Ice, 2=Cool, 3=Heat, 4=Pursuit
AV5ActTempStpUnit - Active Temperature Setpoint°CRead
AV2ActCapacityUnit - Actual Capacity%Read
AV1ActCapacityLimUnit - Active Capacity Limit%Read
MVmin1UnitStatusUnit - StatusRead1=Off, 2=Start, 3=Run, 4=PreShutdown, 5=Service
AI1EvapEntWTempEvaporator Entering Water Temperature°CRead
AImin2EvapLvgWTempEvaporator Leaving Water Temperature°CRead
BV7HeatRec'EnableStpHeat Recovery - Enable SetpointCommand0=Disable, 1=Enable
AI177HeatRec'EntWTempHeat Recovery - Entering Water Temperature°CRead
AI150HeatRec'LvgWTempHeat Recovery - Leaving Water Temperature°CRead
AI5OutdoorAirTempOutside Air Temperature°CRead
AV993AvgCurrentUnit - Average CurrentARead
AV992AvgVoltageUnit - Average VoltageVRead
AV994ActPowerUnit - Active PowerkWRead
AV902AVWarningAlarmUnit Alarm - Warning IndexRead
AV900AVProblemAlarmUnit Alarm - Problem IndexRead
AV901AVFaultAlarmUnit Alarm - Fault IndexRead
AV903AVWarningAlarmCodeUnit Alarm - Warning CodeRead
AV904AVProblemAlarmCodeUnit Alarm - Problem CodeRead
AVmin905AVFaultAlarmCodeUnit Alarm - Fault CodeRead
MVmin3UnitModeSetpointNetworkUnit - Operation Mode SetpointCommand0=NULL, 1=Ice, 2=Cool, 3=Heat, 4=Pursuit
AVmin4NetworkCoolTempSetpointUnit - Cool Temperature Setpoint°CCommand
AV7NetworkIceTempSetpointUnit - Ice Temperature Setpoint°CCommand
AV6NetworkHeatTempSetpointUnit - Heat Temperature Setpoint°CCommand
AVmin3NetworkCapacityLimitSetpointUnit - Capacity Limit Setpoint%Command
AI99C1'CondRefPressureCircuit 1 - Condenser Refrigerant PressurekPaRead
AV34C1'CondSatRefTempCircuit 1 - Condeser Saturated Temperature°CRead
AI141C1'EvapRefPressureCircuit 1 - Evaporator Refrigerant PressurekPaRead
AV68C1'EvapSatRefTempCircuit 1 - Evaporator Saturated Temperature°CRead
AI100C2'CondRefPressureCircuit 2 - Condenser Refrigerant PressurekPaRead
AV35C2'CondSatRefTempCircuit 2 - Condeser Saturated Temperature°CRead
AI142C2'EvapRefPressureCircuit 2 - Evaporator Refrigerant PressurekPaRead
AV69C2'EvapSatRefTempCircuit 2 - Evaporator Saturated Temperature°CRead
MV51C1'ShutdownAlmCircuit 1 - Shutdown AlarmRead1=NoAlarm, 2=Alarm
MV52C2'ShutdownAlmCircuit 2 - Shutdown AlarmRead1=NoAlarm, 2=Alarm
MV54U'ShutdownAlmUnit - Shutdown AlarmRead1=NoAlarm, 2=Alarm
AV49NetworkHeatRecSetpointUnit - Heat Recovery Setpoint°CCommand
MV42HeatRec'StateHeat Recovery - Operating StateRead1=Off, 2=Recirculation, 3=Regulation
AI105C1'Comp1'SuctTempCirc 1 Compressor 1 - Suction Temperature°CRead
AI63C1'Comp1'DischTempCirc 1 Compressor 1 - Discharge Temperature°CRead
AV92C1'Comp1'StartsCirc 1 Compressor 1 - Number of StartsWrite
AV74C1'Comp1'RunHoursCirc 1 Compressor 1 - Number of Running HourshWrite
AV93C1'Comp2'StartsCirc 1 Compressor 2 - Number of StartsWrite
AV75C1'Comp2'RunHoursCirc 1 Compressor 2 - Number of Running HourshWrite
AV94C1'Comp3'StartsCirc 1 Compressor 3 - Number of StartsWrite
AV76C1'Comp3'HoursCirc 1 Compressor 3 - Number of Running HourshWrite
AI108C2'Comp1'SuctTempCirc 2 Compressor 1 - Suction Temperature°CRead
AI66C2'Comp1'DischTempCirc 2 Compressor 1 - Discharge Temperature°CRead
AV95C2'Comp1'StartsCirc 2 Compressor 1 - Number of StartsWrite
AV77C2'Comp1'HoursCirc 2 Compressor 1 - Number of Running HourshWrite
AV96C2'Comp2'StartsCirc 2 Compressor 2 - Number of StartsWrite
AV78C2'Comp2'RunHoursCirc 2 Compressor 2 - Number of Running HourshWrite
AV97C2'Comp3'StartsCirc 2 Compressor 3 - Number of StartsWrite
AV79C2'Comp3'RunHoursCirc 2 Compressor 3 - Number of Running HourshWrite
BV28Freecool'EnableStpFreecooling - Enable SetpointCommand0=Disable, 1=Enable
MV31Freecool'StatusFreecooling - StatusRead1=Off, 2=Start, 3=Mixed, 4=FreeCooling, 5=Mechanical
MV32Freecool'EnabledFreeccoling - Enabled StateRead1=Disabled, 2=Enabled
MV29Freecool'C1ModeFreecooling - Circuit 1 ModeRead1=Mechanical, 2=Switching, 3=Switching, 4=FreeCooling, 5=FC Pumpdown, 6=FC Off
MV30Freecool'C2ModeFreecooling - Circuit 2 ModeRead1=Mechanical, 2=Switching, 3=Switching, 4=FreeCooling, 5=FC Pumpdown, 6=FC Off
AV296EvapPump'SpeedEvaporator Pump - Speed%Read
AV112EvapPump1'RunHoursEvaporator Pump 1 - Number of Running HourshRead
BI8EvapPump1'StateEvaporator Pump 1 - Operating StateRead0=Stop, 1=Run
AV113EvapPump2'RunHoursEvaporator Pump 2 - Number of Running HourshRead
BI9EvapPump2'StateEvaporator Pump 2 - Operating StateRead0=Stop, 1=Run
MV4UnitsUnit - BACnet Measurement unit setpointWrite1=Metric, 2=English
MV317UnitModelUnit - ModelRead1=Centrifugal, 2=Water Cooled, 3=Air Cooled, 4=HeatPump, 5=Reserved, 6=Reserved, 7=Reserved, 8=Reserved, 9=Other
BV917Unit'OFFEvapEntWTempFailUnit Alarm - Evaporator Entering Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV512BadSetpointResetInputUnit Warning - Setpoint Reset Input Out of RangeRead0=NoAlarm, 1=Alarm
BV513BadDemandLimitInputUnit Warning - Demand Limit Input Out of RangeRead0=NoAlarm, 1=Alarm
AI540C1'UnloadCondPresHiCircuit 1 Warning - Unload for Condenser High PressureRead0=NoAlarm, 1=Alarm
AI541C2'UnloadCondPresHiCircuit 2 Warning - Unload for Condenser High PressureRead0=NoAlarm, 1=Alarm
AI556C1'InhibitEvapPresLowCircuit 1 Warning - Inhibition for Evaporator Low PressureRead0=NoAlarm, 1=Alarm
AI557C2'InhibitEvapPresLowCircuit 2 Warning - Inhibition for Evaporator Low PressureRead0=NoAlarm, 1=Alarm
AI561C1'UnloadEvapPresLowCircuit 1 Warning - Unload for Evaporator Low PressureRead0=NoAlarm, 1=Alarm
AI562C2'UnloadEvapPresLowCircuit 2 Warning - Unload for Evaporator Low PressureRead0=NoAlarm, 1=Alarm
BV575EvapPump1'FaultEvaporator Pump 1 - FaultRead0=NoAlarm, 1=Alarm
BV576EvapPump2'FaultEvaporator Pump 2 - FaultRead0=NoAlarm, 1=Alarm
BV605Unit'OFFOATempSenFailUnit Alarm - Outside Air Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV625C1'Comp1'OFFMtrProtectCirc 1 Comp 1 Alarm - Motor ProtectionRead0=NoAlarm, 1=Alarm
BV626C1'Comp2'OFFMtrProtectCirc 1 Comp 2 Alarm - Motor ProtectionRead0=NoAlarm, 1=Alarm
BV627C2'Comp1'OFFMtrProtectCirc 2 Comp 1 Alarm - Motor ProtectionRead0=NoAlarm, 1=Alarm
BV628C2'Comp2'OFFMtrProtectCirc 2 Comp 2 Alarm - Motor ProtectionRead0=NoAlarm, 1=Alarm
BV629C1'Comp3'OFFMtrProtectCirc 1 Comp 3 Alarm - Motor ProtectionRead0=NoAlarm, 1=Alarm
BV630C2'Comp3'OFFMtrProtectCirc 2 Comp 3 Alarm - Motor ProtectionRead0=NoAlarm, 1=Alarm
BV668C1'OFFCondPresFailCircuit 1 Alarm - Condenser Pressure Sensor FaultRead0=NoAlarm, 1=Alarm
BV670C2'OFFCondPresFailCircuit 2 Alarm - Condenser Pressure Sensor FaultRead0=NoAlarm, 1=Alarm
BV676C1'OFFCondPresHiCircuit 1 Alarm - Condenser High PressureRead0=NoAlarm, 1=Alarm
BV678C2'OFFCondPresHiCircuit 2 Alarm - Condenser High PressureRead0=NoAlarm, 1=Alarm
BV688C1'OFFDischTempFailCircuit 1 Alarm - Discharge Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV690C2'OFFDischTempFailCircuit 2 Alarm - Discharge Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV701Unit'OFFEvapFlowLossUnit Alarm - Evaporator Water Flow LossRead0=NoAlarm, 1=Alarm
BV702Unit'OFFEvapLvgWTempLowUnit Alarm - Evaporator Water FreezeRead0=NoAlarm, 1=Alarm
BV704C1'OFFEvapPresLowCircuit 1 Alarm - Evaporator Pressure LowRead0=NoAlarm, 1=Alarm
BV706C2'OFFEvapPresLowCircuit 2 Alarm - Evaporator Pressure LowRead0=NoAlarm, 1=Alarm
BV711C1'OFFEvapPresFailCircuit 1 Alarm - Evaporator Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV713C2'OFFEvapPresFailCircuit 2 Alarm - Evaporator Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV742C1'OFFRestartsAlmCircuit 1 Alarm - Too many restartRead0=NoAlarm, 1=Alarm
BV744C2'OFFRestartsAlmCircuit 2 Alarm - Too many restartRead0=NoAlarm, 1=Alarm
BV748Unit'OFFEvapLvgWTempFailUnit Alarm - Evaporator Leaving Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV760C1'OFFMechPressHiCircuit 1 Alarm - Mechanical High PressureRead0=NoAlarm, 1=Alarm
BV762C2'OFFMechPressHiCircuit 2 Alarm - Mechanical High PressureRead0=NoAlarm, 1=Alarm
BV857C1'Comp1'OFFSuctTempFailCirc 1 Comp 1 Alarm - Suction Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV859C2'Comp1'OFFSuctTempSenCirc 2 Comp 1 Alarm - Suction Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV723C1'OFFBoardOfflineController Alarm - Circuit 1 Board OfflineRead0=NoAlarm, 1=Alarm
BV724C2'OFFBoardOfflineController Alarm - Circuit 2 Board OfflineRead0=NoAlarm, 1=Alarm
BV516C1'FailPumpdownCircuit 1 Alarm - Pumpdown FailureRead0=NoAlarm, 1=Alarm
BV517C2'FailPumpdownCircuit 2 Alarm - Pumpdown FailureRead0=NoAlarm, 1=Alarm
BV924Unit'ExternalEventUnit Alarm - External EventRead0=NoAlarm, 1=Alarm
BV905C1'OFFNoPresChgAtStartCircuit 1 Alarm - No Pressure change at StartRead0=NoAlarm, 1=Alarm
BV906C2'OFFNoPresChgAtStartCircuit 2 Alarm - No Pressure change at StartRead0=NoAlarm, 1=Alarm
BV923Unit'OFFExternalAlarmUnit Alarm - External AlarmRead0=NoAlarm, 1=Alarm
BV967Unit'OFFPhaseVoltageUnit Alarm - Wrong Phase VoltageRead0=NoAlarm, 1=Alarm
BV844C1'OFFGasLeakageCircuit 1 Alarm - Gas LeakageRead0=NoAlarm, 1=Alarm
BV845C2'OFFGasLeakageCircuit 2 Alarm - Gas LeakageRead0=NoAlarm, 1=Alarm
AI187SwitchBoxTempUnit - Electrical Panel Temperature°CRead
BV983Unit'SwitchBoxSensFaultUnit Warning - Electrical Panel Temp Sensor FaultRead0=NoAlarm, 1=Alarm
BV984Unit'SwitchBoxTempHighUnit Warning - Electrical Panel High TemperatureRead0=NoAlarm, 1=Alarm
MV1775C2'Comp3'OffAutoStpCirc 2 Compressor 3 - OffAuto SetpointWrite1=Off, 2=Auto
BV1786C2'Comp3'StateCirc 2 Compressor 3 - Operating StateRead0=Off, 1=On
MV445C2'Comp2'OffAutoStpCirc 2 Compressor 2 - OffAuto SetpointWrite1=Off, 2=Auto
BV446C2'Comp2'StateCirc 2 Compressor 2 - Operating StateRead0=Off, 1=On
AV1800C2'Comp1'ActCapacityCirc 2 Compressor 1 - Actual Capacity%Read
MV440C2'Comp1'OffAutoStpCirc 2 Compressor 1 - OffAuto SetpointWrite1=Off, 2=Auto
BV441C2'Comp1'StateCirc 2 Compressor 1 - Operating StateRead0=Off, 1=On
MV1814C1'Comp3'OffAutoStpCirc 1 Compressor 3 - OffAuto SetpointWrite1=Off, 2=Auto
BV434C1'Comp3'StateCirc 1 Compressor 3 - Operating StateRead0=Off, 1=On
MV435C1'Comp2'OffAutoStpCirc 1 Compressor 2 - OffAuto SetpointWrite1=Off, 2=Auto
BV436C1'Comp2'StateCirc 1 Compressor 2 - Operating StateRead0=Off, 1=On
AV1840C1'Comp1'ActCapacityCirc 1 Compressor 1 - Actual Capacity%Read
MV430C1'Comp1'OffAutoStpCirc 1 Compressor 1 - OffAuto SetpointWrite1=Off, 2=Auto
BV431C1'Comp1'StateCirc 1 Compressor 1 - Operating StateRead0=Off, 1=On
AV1855NrCircuitsUnit - Number of CircuitsRead
AV1856NrCompressorsUnit - Number of CompressorsRead
AV1857UnitTonsUnit - Number of TonstonsRead
AV1896C2'EvapSuperheatStpValCircuit 2 - Evaporator Superheat Active SetpointdKRead
AV1897C1'EvapSuperheatStpValCircuit 1 - Evaporator Superheat Active SetpointdKRead
AV1898C2'EvapSuperheatCircuit 2 - Evaporator Superheat TemperaturedKRead
AV1899C1'EvapSuperheatCircuit 1 - Evaporator Superheat TemperaturedKRead
AV990ActEnergyUnit - Active EnergykWhRead
AV991PowerFactorUnit - Power FactorRead
AI1905VarFlow'LoadDPresVariable Flow - Plant Differential PressurekPaWrite
MV1906VarFlow'WBypVlvStaVaribale Flow - Water Bypass Valve StateRead1=Closed, 2=Opened
AV1909VarFlow'LoadDPresStptVaribale Flow - Plant Differential Pressure setpointkPaWrite
AV1911VarFlow'DeltaTempVariable Flow - Plant Delta TemperaturedKRead
AV1913VarFlow'DeltaTempStpVariable Flow - Plant Delta Temperature SetpointdKWrite
AV1915VarFlow'EvapFixSpeedStpVariable Flow - Evaporator Fixed Speed Setpoint%Write
AV208C2'ExpValvePosCircuit 2 - Expansion Valve Position%Read
AV209C2'FanSpeedCircuit 2 - Fan Speed%Read
AV210C2'CondApproachCircuit 2 - Condenser Approach TemperaturedKRead
AV211C2'EvapApproachCircuit 2 - Evaporator Approach TemperaturedKRead
AVC2'FanStatusCircuit 2 - Fan Staging (guide repeats instance 1997)Read
AV168C1'ExpValvePosCircuit 1 - Expansion Valve Position%Read
AV169C1'FanSpeedCircuit 1 - Fan Speed%Read
AV170C1'CondApproachCircuit 1 - Condenser Approach TemperaturedKRead
AV171C1'EvapApproachCircuit 1 - Evaporator Approach TemperaturedKRead
AV1997C1'FanStatusCircuit 1 - Fan StagingRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EWAT-B air-cooled chiller (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)

How many BACnet points does the Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe) have?

This list has 165 BACnet objects: 21 analog inputs, 61 analog values, 9 binary inputs, 54 binary values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe) BACnet points are writable?

33 of the 165 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe) BACnet documentation?

The source is BAS Integration guide - BACnet protocol (EWAT-B) (D-EIGOC00103-22_02EN_EWAT-B), revision 2024-07, published free by Daikin Applied at https://www.daikin.co.uk/content/dam/document-library/installation-manuals/as/air-cooled-chiller/ewat-b-ss/EWAT-B_BAS%20Integration%20Guide%20BACNet_D-EIGOC00107-24_02_English.pdf.

What are the minimum BACnet points to integrate the Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)?

Start with BV 2 UnitEnableStp (Network enable/disable of the chiller); MV 3 UnitModeSetpointNetwork (Ice / cool / heat / pursuit mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitSetpoint (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 CtrlSource (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 EvapLvgWTemp (Leaving chilled water temperature); BI 10 AlarmOutput (Any active alarm); AV 905 AVFaultAlarmCode (Active fault alarm code).

How do I enable BMS control of the Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)?

CtrlSource (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes UnitEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.

Can the BMS supply sensor values to the Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)?

VarFlow'LoadDPres (AI 1905, plant differential pressure) is marked writable for variable primary flow; the guide does not say whether the BMS must supply it.

How do I check these points on the real EWAT-B air-cooled chiller (Daikin Applied Europe)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: BAS Integration guide - BACnet protocol (EWAT-B) · D-EIGOC00103-22_02EN_EWAT-B · rev. 2024-07. Object names, instances and units are reproduced as published; descriptions are our own.