EC fan array controller (air handler) · BACnet points list
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller BACnet points list
Updated 28 October 2026
The MicroTech 4 fan array controller drives up to 20 EC fans (Delta, ebm-papst or Infinitum) over an internal Modbus bus and exposes the array on BACnet MS/TP (RS-485 port 2) or BACnet IP. Points cover demand, duct static and airflow setpoints, array speed, airflow and power, relay and input status, a unit alarm text, and per-fan speed, comm, fault, RPM and alarm-code objects. BACnet can only command the array when its Demand Source is set to BACnet at the HMI.
This page lists 146 BACnet objects for the Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- MicroTech Vision / Skyline EC Fan Array Controller
- Equipment
- EC fan array controller (air handler)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 146 (10 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Application 2506990201 or later (PICS); DSP/CFM setpoint control needs application 2.1 or later
- Default device instance
- Last 4 digits of the MT4 controller serial number
- Also known as
- Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122
BMS integration notes: Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Set the Demand Source to BACnet at the fan controller HMI, then start and stop the array with Unit Control Mode (MV 23) and set capacity with Demand Setpoint (AV 11), or the duct static (AV 9) or airflow (AV 10) setpoint when the array runs in DSP or CFM mode. Read Unit State, fan speed, airflow and the alarm text and relay status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 23 | UnitCtrlMode | Array Auto/Off command (Demand Source must be BACnet) | Write |
| AV 11 | Demand SP | Capacity setpoint, 0-100 % | Write |
| MV 20 | ClearAlarms | Clear resettable alarms (2 = Yes) | Write |
| MV 13 | UnitState | Array operating state | Read |
| MV 5 | DmdSrc | Shows BACnet when the BMS has control | Read |
| AV 4 | AvgFanSpd | Average speed of all fans, rpm | Read |
| AV 8 | TotalAirFl | Total array airflow | Read |
| MV 3 | RO3 Alarm | Alarm relay output (2 = On) | Read |
| CSV 2 | Unit Alarm Info | Highest-priority active alarm text | Read |
Enable & remote start
Demand Source must be configured as BACnet in the Config Array HMI menu (MV 5 shows it). With the HMI Control Mode at Auto, Unit Control Mode (MV 23) toggles the array between Auto and Off; Off at the HMI overrides BACnet. With HMI, 0-10 VDC or 4-20 mA as the demand source, BACnet is read-only monitoring.
Heartbeat & communication loss
No receive heartbeat (listed as not applicable). BACnet values stay at the last valid value on communication loss; invalid network values fall back to defaults.
Network setup
- Device instance defaults to the last 4 digits of the MT4 controller serial number; device name is MT4_DFA_<instance>.
- BACnet MS/TP defaults: MAC 18, 38400 baud, Max Master 127, Max Info Frames 10.
- BACnet IP defaults: 192.168.1.42 / 255.255.255.0, gateway 192.168.1.1, UDP 47808, DHCP off.
- Set addressing in the HMI BMS Communications menus, then set Save Config to Yes; the controller restarts.
- BACnet Units of Measurement (MV 18): SI, US (default) or CA.
Watch out for
- Demand, DSP, airflow and RPM setpoints are linked: writing one re-scales the others.
- Out-of-range setpoint writes are ignored and the last valid value is kept.
- Clear Alarms (MV 20) returns to No after about 3 s; alarms also clear on a power cycle and come back if the cause remains.
- Fire alarm input (BI 1) and safety input (BI 3) read 0 when the alarm is active.
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Demand Input | Fan Speed Demand Input | % | Read | |
| AI | 2 | DSP Pressure | Duct static pressure sensor | in. w.c. | Read | |
| AI | 3 | CFM Pressure | CFM Differential Pressure Sensor | in. w.c. | Read | |
| BI | 1 | Fire Mode Input | Fire alarm input (0 = fire warning active) | Read | 0=Off, 1=On | |
| BI | 2 | Interlock Input | Interlock Switch Input | Read | 0=Off, 1=On | |
| BI | 3 | Safety Input | Safety (emergency) switch input (0 = open, fans stopped) | Read | 0=Off, 1=On | |
| BI | 4 | Array ON/OFF | Start-Stop (On-Off) Input | Read | 0=Off, 1=On | |
| CSV | 1 | Unit Name | Unit device name (14 characters) | Write | ||
| CSVmin | 2 | Unit Alarm Info | Highest-priority active unit alarm text | Read | ||
| CSV | 3 | Unit SN | Unit serial number (13 characters) | Write | ||
| AV | 1 | AO1 RPM | Fan tracking output AO1 to a secondary array | % | Read | |
| AV | 2 | AO2 CFM | Airflow output AO2, % of max airflow | % | Read | |
| AV | 3 | FanSpdCmd | Fan Speed Command | % | Read | |
| AVmin | 4 | AvgFanSpd | Average Fan Speed | rpm | Read | |
| AV | 5 | TotalFanPwr | Total power of all fans | kW | Read | |
| AV | 6 | FanSpdActCmd | Fan Speed Actual Command | % | Read | |
| AV | 7 | FanNumber | Number of fans running | Read | ||
| AVmin | 8 | TotalAirFl | Total Airflow | cfm | Read | |
| AV | 9 | DSPSP | Duct Static Pressure Setpoint | in. w.c. | Write | |
| AV | 10 | CFMSP | Airflow Setpoint | cfm | Write | |
| AVmin | 11 | Demand SP | Demand Setpoint | % | Write | |
| AV | 12 | MaxRPM | Max RPM | rpm | Read | |
| AV | 14 | Air Flow | Air Flow Nominal | cfm | Read | |
| AV | 15 | RPMSP | Fan Speed RPM Setpoint | rpm | Write | |
| AV | 16 | TrckSpdOffsetSP | Secondary Fan Speed Offset | rpm | Write | |
| AV | 101 | Fan1Spd | Fan 1 Speed | rpm | Read | |
| AV | 102 | Fan2Spd | Fan 2 Speed | rpm | Read | |
| AV | 103 | Fan3Spd | Fan 3 Speed | rpm | Read | |
| AV | 104 | Fan4Spd | Fan 4 Speed | rpm | Read | |
| AV | 105 | Fan5Spd | Fan 5 Speed | rpm | Read | |
| AV | 106 | Fan6Spd | Fan 6 Speed | rpm | Read | |
| AV | 107 | Fan7Spd | Fan 7 Speed | rpm | Read | |
| AV | 108 | Fan8Spd | Fan 8 Speed | rpm | Read | |
| AV | 109 | Fan9Spd | Fan 9 Speed | rpm | Read | |
| AV | 110 | Fan10Spd | Fan 10 Speed | rpm | Read | |
| AV | 111 | Fan11Spd | Fan 11 Speed | rpm | Read | |
| AV | 112 | Fan12Spd | Fan 12 Speed | rpm | Read | |
| AV | 113 | Fan13Spd | Fan 13 Speed | rpm | Read | |
| AV | 114 | Fan14Spd | Fan 14 Speed | rpm | Read | |
| AV | 115 | Fan15Spd | Fan 15 Speed | rpm | Read | |
| AV | 116 | Fan16Spd | Fan 16 Speed | rpm | Read | |
| AV | 117 | Fan17Spd | Fan 17 Speed | rpm | Read | |
| AV | 118 | Fan18Spd | Fan 18 Speed | rpm | Read | |
| AV | 119 | Fan19Spd | Fan 19 Speed | rpm | Read | |
| AV | 120 | Fan20Spd | Fan 20 Speed | rpm | Read | |
| BV | 1 | InterlockFlt | Interlock Alarm | Read | 0=Off, 1=On | |
| BV | 2 | DSPFlt | DSP Alarm | Read | 0=Off, 1=On | |
| BV | 11 | Fan1ComErr | Fan 1 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 12 | Fan2ComErr | Fan 2 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 13 | Fan3ComErr | Fan 3 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 14 | Fan4ComErr | Fan 4 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 15 | Fan5ComErr | Fan 5 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 16 | Fan6ComErr | Fan 6 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 17 | Fan7ComErr | Fan 7 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 18 | Fan8ComErr | Fan 8 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 19 | Fan9ComErr | Fan 9 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 20 | Fan10ComErr | Fan 10 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 21 | Fan11ComErr | Fan 11 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 22 | Fan12ComErr | Fan 12 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 23 | Fan13ComErr | Fan 13 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 24 | Fan14ComErr | Fan 14 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 25 | Fan15ComErr | Fan 15 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 26 | Fan16ComErr | Fan 16 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 27 | Fan17ComErr | Fan 17 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 28 | Fan18ComErr | Fan 18 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 29 | Fan19ComErr | Fan 19 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 30 | Fan20ComErr | Fan 20 Comm Error | Read | 0=OK, 1=Fault | |
| BV | 51 | Fan1Fault | Fan 1 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 52 | Fan2Fault | Fan 2 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 53 | Fan3Fault | Fan 3 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 54 | Fan4Fault | Fan 4 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 55 | Fan5Fault | Fan 5 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 56 | Fan6Fault | Fan 6 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 57 | Fan7Fault | Fan 7 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 58 | Fan8Fault | Fan 8 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 59 | Fan9Fault | Fan 9 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 60 | Fan10Fault | Fan 10 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 61 | Fan11Fault | Fan 11 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 62 | Fan12Fault | Fan 12 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 63 | Fan13Fault | Fan 13 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 64 | Fan14Fault | Fan 14 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 65 | Fan15Fault | Fan 15 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 66 | Fan16Fault | Fan 16 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 67 | Fan17Fault | Fan 17 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 68 | Fan18Fault | Fan 18 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 69 | Fan19Fault | Fan 19 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 70 | Fan20Fault | Fan 20 Fault Status | Read | 0=OK, 1=Fault | |
| BV | 101 | Fan1RPMAlm | Fan 1 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 102 | Fan2RPMAlm | Fan 2 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 103 | Fan3RPMAlm | Fan 3 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 104 | Fan4RPMAlm | Fan 4 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 105 | Fan5RPMAlm | Fan 5 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 106 | Fan6RPMAlm | Fan 6 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 107 | Fan7RPMAlm | Fan 7 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 108 | Fan8RPMAlm | Fan 8 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 109 | Fan9RPMAlm | Fan 9 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 110 | Fan10RPMAlm | Fan 10 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 111 | Fan11RPMAlm | Fan 11 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 112 | Fan12RPMAlm | Fan 12 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 113 | Fan13RPMAlm | Fan 13 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 114 | Fan14RPMAlm | Fan 14 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 115 | Fan15RPMAlm | Fan 15 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 116 | Fan16RPMAlm | Fan 16 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 117 | Fan17RPMAlm | Fan 17 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 118 | Fan18RPMAlm | Fan 18 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 119 | Fan19RPMAlm | Fan 19 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| BV | 120 | Fan20RPMAlm | Fan 20 RPM Alarm Status | Read | 0=OK, 1=Fault | |
| MV | 1 | UnitMode | Unit Mode | Read | 1=Off, 2=Normal, 3=Manual, 4=Manual Off | |
| MV | 2 | RO1 Ready | Fan Ready to Run Output | Read | 1=Off, 2=On | |
| MVmin | 3 | RO3 Alarm | Fan Array Alarm Output | Read | 1=Off, 2=On | |
| MV | 4 | RO2 Running | Fan Run Status Output | Read | 1=Off, 2=On | |
| MVmin | 5 | DmdSrc | Demand Source | Read | 1=0-10 VDC, 2=4-20mA, 3=BACnet, 4=HMI | |
| MV | 6 | AdaptiveSpd | Adaptive Speed | Read | 1=No, 2=Yes | |
| MV | 7 | FireAlmEnable | Fire Alarm Input Enable | Read | 1=FireAlm Disabled, 2=FireAlm Enabled | |
| MV | 8 | InterlockEnable | Interlock Input Enable | Read | 1=Interlock Switch Disabled, 2=Interlock Switch Enabled | |
| MV | 9 | SafetyInputEnable | Safety Alarm Input Enable | Read | 1=AlmIn Disabled, 2=AlmIn Enabled | |
| MV | 10 | StartSiglEnEff | On/Off (Start-Stop) Input Enable | Read | 1=Start Switch Disabled, 2=Start Switch Enabled | |
| MV | 12 | CtrlModeCfg | Control Mode | Read | 1=Dmd RPM, 2=Dmd CFM, 3=Dmd DuctP, 4=Fan Tracking | |
| MVmin | 13 | UnitState | Unit State | Read | 1=Off, 2=Ready, 3=Running, 4=Manual, 5=Alarm, 6=Emergency Warning, 7=Emergency Alarm, 8=Run with Alarm, 9=Off with Alarm, 10=DmdSigLow | |
| MV | 14 | DSPAlm | DSP Alarm | Read | 1=Off, 2=On | |
| MV | 15 | InterlockAlm | Interlock Alarm | Read | 1=Off, 2=On | |
| MV | 16 | UnitCtrlModeHMI | Unit Control Mode HMI | Read | 1=Off, 2=Auto | |
| MV | 18 | BNUnitSystem | BACnet Units of Measurement | Write | 1=SI, 2=US, 3=CA | |
| MVmin | 20 | ClearAlarms | Clear Alarms | Write | 1=No, 2=Yes | |
| MV | 21 | ManualMode | Manual Mode | Read | 1=Off, 2=Normal, 3=Manual | |
| MVmin | 23 | UnitCtrlMode | Unit Control Mode | Write | 1=Off, 2=Auto | |
| MV | 101 | Fan1AlmCode | Fan 1 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 102 | Fan2AlmCode | Fan 2 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 103 | Fan3AlmCode | Fan 3 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 104 | Fan4AlmCode | Fan 4 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 105 | Fan5AlmCode | Fan 5 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 106 | Fan6AlmCode | Fan 6 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 107 | Fan7AlmCode | Fan 7 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 108 | Fan8AlmCode | Fan 8 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 109 | Fan9AlmCode | Fan 9 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 110 | Fan10AlmCode | Fan 10 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 111 | Fan11AlmCode | Fan 11 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 112 | Fan12AlmCode | Fan 12 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 113 | Fan13AlmCode | Fan 13 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 114 | Fan14AlmCode | Fan 14 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 115 | Fan15AlmCode | Fan 15 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 116 | Fan16AlmCode | Fan 16 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 117 | Fan17AlmCode | Fan 17 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 118 | Fan18AlmCode | Fan 18 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 119 | Fan19AlmCode | Fan 19 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online | |
| MV | 120 | Fan20AlmCode | Fan 20 alarm code (states depend on fan make) | Read | Delta fans: 1=Offline, 2=Hall, 3=OC, 4=ACOV, 5=ACUV, 6=EEPROM, 7=POC, 8=PL, 9=OV, 10=UV, 11=Lock, 12=OT, 13=RRP, 14=RPMErr, 15=Online; ebm-papst fans: 1=Offline, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=BLK, 7=SKF, 8=PHA, 9=UzL, 10=UzH, 11=UeL, 12=UeH, 13=nLim, 14=RLC, 15=RPMErr, 16=Online; Infinitum fans: 1=Offln, 2=DCOC, 3=OC, 4=VPh, 5=MtrPD, 6=UART, 7=IPh, 8=GDUV, 9=DCOV, 10=DCUV, 11=Lock, 12=OT, 13=GD, 14=RPMEr, 15=Online |
No points match these filters.
Integration notes
- Per-fan objects (AV 101-120, BV 11-30, BV 51-70, BV 101-120, MV 101-120) only exist for the configured number of fans.
- Fan alarm code states (MV 101-120) differ by fan make: Delta, ebm-papst or Infinitum.
- Active control needs Demand Source = BACnet (MV 5 reads BACnet); otherwise the BACnet objects are monitor-only.
- DSP, CFM and fan tracking control are not in application 2.0 and earlier.
- Total Fan Power (AV 5) is in kW but the object carries no units property.
- Manual mode set at the HMI reverts to Normal after 60 minutes or a power cycle.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech Vision / Skyline EC Fan Array Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
How many BACnet points does the Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller have?
This list has 146 BACnet objects: 3 analog inputs, 35 analog values, 4 binary inputs, 62 binary values, 39 multi-state values, 3 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller BACnet points are writable?
10 of the 146 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller BACnet documentation?
The source is MicroTech Vision and Skyline EC Fan Array Controller - Network Integration Guide (BACnet MS/TP and BACnet IP) (ED 19122-3), revision 2025-10, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019122-3%20MicroTech%20Vision_Skyline%20EC%20Fan%20Controller%20Protocol%20Document.pdf.
What are the minimum BACnet points to integrate the Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller?
Start with MV 23 UnitCtrlMode (Array Auto/Off command (Demand Source must be BACnet)); AV 11 Demand SP (Capacity setpoint, 0-100 %); MV 20 ClearAlarms (Clear resettable alarms (2 = Yes)); MV 13 UnitState (Array operating state); MV 5 DmdSrc (Shows BACnet when the BMS has control); AV 4 AvgFanSpd (Average speed of all fans, rpm); AV 8 TotalAirFl (Total array airflow); MV 3 RO3 Alarm (Alarm relay output (2 = On)); CSV 2 Unit Alarm Info (Highest-priority active alarm text).
How do I enable BMS control of the Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller?
Demand Source must be configured as BACnet in the Config Array HMI menu (MV 5 shows it). With the HMI Control Mode at Auto, Unit Control Mode (MV 23) toggles the array between Auto and Off; Off at the HMI overrides BACnet. With HMI, 0-10 VDC or 4-20 mA as the demand source, BACnet is read-only monitoring.
Does the Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller need a BACnet heartbeat or have a communication timeout?
No receive heartbeat (listed as not applicable). BACnet values stay at the last valid value on communication loss; invalid network values fall back to defaults.
How do I check these points on the real MicroTech Vision / Skyline EC Fan Array Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00
Source: MicroTech Vision and Skyline EC Fan Array Controller - Network Integration Guide (BACnet MS/TP and BACnet IP) · ED 19122-3 · rev. 2025-10. Object names, instances and units are reproduced as published; descriptions are our own.