Chiller controller · BACnet points list

Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet points list

Updated 28 October 2026

Short answer

This MicroTech controller generation serves the AGZ-F, WMC-E and WMT chillers and talks BACnet MS/TP, BACnet IP or Modbus through its communication module. Besides the usual water temperatures, refrigerant pressures, run hours and network setpoints, it adds alarm module ID, type and payload values for fault, problem and warning alarms, a heat setpoint and a refrigerant type readout.

This page lists 97 BACnet objects for the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Equipment
Chiller controller
Equipment type
Chillers
BACnet objects
97 (8 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
AGZ-F 1.2.0, WMT 1.0.0, WMC-E 1.0.0 application software or later
Default device instance
9050
Also known as
AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131
Source document
MicroTech Unit Controller Protocol Information (Chiller Models AGZ-F, WMC-E, and WMT) · ED 19131-1 · rev. 2026-04
Download CSV 97 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)

Integration in brief

Set Control Source to BAS at the chiller HMI, then use ChillerEnableStp to enable the chiller and write the cool (or heat/ice) setpoint, mode and capacity limit. Monitor unit status, water temperatures, capacity and the alarm index/module objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2ChillerEnableStpNetwork enable/disable of the chillerWrite
MV 3ChillerOperationModeIce / cool / heat / heat recovery mode commandWrite
AV 4NetworkCoolTempSetpointLeaving water cool setpoint from the BMSWrite
AV 3NetworkCapacityLimitPctCapacity limit from the BMSWrite
BV 8ClearAlarmClear alarms from the networkWrite
BI 3ChillerLocalRemoteShows whether network control is activeRead
MV 1UnitStatusChiller run stateRead
AI 2LvgEvapWaterTempUnitLeaving chilled water temperatureRead
AV 2ChillerCapacityActual capacity in percentRead
AV 901AVFaultAlarmActive fault alarm indexRead

Enable & remote start

For AGZ-F, WMC-E and WMT, Control Source must be set to BAS at the unit HMI before the controller uses Network Enable (BV 2), the cool/heat/ice setpoints, the mode setpoint and the capacity limit from the BAS.

Network setup

Watch out for

Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

97 of 97 shown
Type
Multi-state
Access
Show
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet Points List
DescriptionStates
AI9C1Comp1CurrentCompressor Current - Circuit 1 Compressor 1ARead
AI10C1Comp2CurrentCompressor Current - Circuit 1 Compressor 2ARead
AI45C1Comp1KilowattsCompressor Power - Circuit 1 Compressor 1kWRead
AI46C1Comp2KilowattsCompressor Power - Circuit 1 Compressor 2kWRead
AI27C1Comp1VoltageCompressor Voltage - Circuit 1 Compressor 1VRead
AI28C1Comp2VoltageCompressor Voltage - Circuit 1 Compressor 2VRead
AI3EntCondWaterTempCondenser Entering Fluid Temperature°FRead
AI147CondWaterFlowRateCondenser Flow RateGPMRead
AI4LvgCondWaterTempCondenser Leaving Fluid Temperature°FRead
AI99Cond1RefPressureCondenser Refrigerant Pressure - Circuit 1psiRead
AI100Cond2RefPressureCondenser Refrigerant Pressure - Circuit 2psiRead
AI81C1Comp1DischRefPressureDischarge Refrigerant Pressure - Circuit 1 Compressor 1psiRead
AI82C1Comp2DischRefPressureDischarge Refrigerant Pressure - Circuit 1 Compressor 2psiRead
AI63C1Comp1DischargeTempDischarge Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AI64C1Comp2DischargeTempDischarge Refrigerant Temperature - Circuit 1 Compressor 2°FRead
AI66C2Comp1DischargeTempDischarge Refrigerant Temperature - Circuit 2 Compressor 1°FRead
AI1EntEvapWaterTempEvaporator Entering Fluid Temperature°FRead
AI148EvapWaterFlowRateEvaporator Flow RateGPMRead
AImin2LvgEvapWaterTempUnitEvaporator Leaving Fluid Temperature°FRead
AI141C1EvapRefPressureEvaporator Refrigerant Pressure - Circuit 1psiRead
AI142C2EvapRefPressureEvaporator Refrigerant Pressure - Circuit 2psiRead
AI177HeatRecEntWaterTempHeat Recovery Entering Fluid Temperature°FRead
AI150HeatRecLvgWaterTempHeat Recovery Leaving Fluid Temperature°FRead
AI218C1LiqLineRefTempLiquid Line Refrigerant Temperature - Circuit 1°FRead
AI5OutdoorAirTempOutdoor Air Temperature°FRead
AI123C1Comp1SuctionPressureSuction Refrigerant Pressure - Circuit 1 Compressor 1psiRead
AI124C1Comp2SuctionPressureSuction Refrigerant Pressure - Circuit 1 Compressor 2psiRead
AI105C1Comp1SuctionTempSuction Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AI106C1Comp2SuctionTempSuction Refrigerant Temperature - Circuit 1 Compressor 2°FRead
AI224C1SuctionTemperatureSuction Refrigerant Temperature - Circuit 1°FRead
AI225C2SuctionTemperatureSuction Refrigerant Temperature - Circuit 2°FRead
AV1ActiveCapacityLimitActive Capacity Limit Output%Read
AV5ActiveLvgWaterTargetActive Setpoint°FRead
AVmin2ChillerCapacityActual Capacity%Read
AVmin901AVFaultAlarmAlarm IndexRead
AV900AVProblemAlarmAlarm IndexRead
AV902AVWarningAlarmAlarm IndexRead
AV910AVFaultModIDAlarm Module IDRead
AV907AVProblemModIDAlarm Module IDRead
AV913AVWarningModIDAlarm Module IDRead
AV911AVFaultModPayloadAlarm Module PayloadRead
AV908AVProblemModPayloadAlarm Module PayloadRead
AV914AVWarningModPayloadAlarm Module PayloadRead
AV909AVFaultModTypeAlarm Module TypeRead
AV906AVProblemModTypeAlarm Module TypeRead
AV912AVWarningModTypeAlarm Module TypeRead
AVmin3NetworkCapacityLimitPctCapacity Limit Setpoint - Network%Write
AV8C1Comp1MotorCurrentPercentCompressor Percent RLA - Circuit 1 Compressor 1%Read
AV9C1Comp2MotorCurrentPercentCompressor Percent RLA - Circuit 1 Compressor 2%Read
AV74C1Comp1HoursCompressor Run Hours - Circuit 1 Compressor 1hRead
AV75C1Comp2HoursCompressor Run Hours - Circuit 1 Compressor 2hRead
AV76C1Comp3HoursCompressor Run Hours - Circuit 1 Compressor 3hRead
AV77C2Comp1HoursCompressor Run Hours - Circuit 2 Compressor 1hRead
AV78C2Comp2HoursCompressor Run Hours - Circuit 2 Compressor 2hRead
AV79C2Comp3HoursCompressor Run Hours - Circuit 2 Compressor 3hRead
AV92C1Comp1StartsCompressor Starts - Circuit 1 Compressor 1Read
AV93C1Comp2StartsCompressor Starts - Circuit 1 Compressor 2Read
AV94C1Comp3HoursCompressor Starts - Circuit 1 Compressor 3Read
AV95C2Comp1StartsCompressor Starts - Circuit 2 Compressor 1Read
AV96C2Comp2StartsCompressor Starts - Circuit 2 Compressor 2Read
AV97C2Comp3HoursCompressor Starts - Circuit 2 Compressor 3Read
AV110CondPump1RunHoursCondenser Pump Run Hours - Condenser Pump 1hRead
AV111CondPump2RunHoursCondenser Pump Run Hours - Condenser Pump 2hRead
AV44Cond1SatRefTempCondenser Saturated Refrigerant Temperature - Circuit 1°FRead
AV45Cond2SatRefTempCondenser Saturated Refrigerant Temperature - Circuit 2°FRead
AVmin4NetworkCoolTempSetpointCool Setpoint - Network°FWrite
AV26C1Comp1DischSatRefTempDischarge Saturated Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AV27C1Comp2DischSatRefTempDischarge Saturated Refrigerant Temperature - Circuit 1 Compressor 2°FRead
AV112EvapPump1OperHoursEvaporator Pump Run Hours - Evaporator Pump 1hRead
AV113EvapPump2OperHoursEvaporator Pump Run Hours - Evaporator Pump 2hRead
AV68C1EvapSatRefTempEvaporator Saturated Refrigerant Temperature - Circuit 1°FRead
AV69C2EvapSatRefTempEvaporator Saturated Refrigerant Temperature - Circuit 2°FRead
AV7NetworkIceTempSetpointIce Setpoint - Network°FWrite
AV6NetworkHeatTempSetpointHeat Setpoint - Network°FWrite
AV50C1Comp1SuctSatTempSuction Saturated Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AV51C1Comp2SuctSatTempSuction Saturated Refrigerant Temperature - Circuit 1 Compressor 2°FRead
BVmin2ChillerEnableStpChiller Enable SetpointWrite0=Disable (Inactive), 1=Enable
BVmin8ClearAlarmClear Alarm - NetworkWrite0=Normal, 1=Clear Alarm
BI10AlarmDigitalOutputAlarm Digital OutputRead0=No Alarm, 1=Alarm
BI6ChillerLimitedChiller Capacity LimitedRead0=Not Limited, 1=Limited
BI7ChillerEnableOutputChiller Enable OutputRead0=Disable, 1=Enable
BImin3ChillerLocalRemoteChiller Local/NetworkRead0=Network, 1=Local
BI4UnitOnOffChiller On/OffRead0=Chiller Off, 1=Chiller On
BI163C1Cmp1UnavailableCompressor Unavailable - Circuit 1 Compressor 1Read0=Available, 1=Unavailable
BI164C1Cmp2UnavailableCompressor Unavailable - Circuit 1 Compressor 2Read0=Available, 1=Unavailable
BI1CondWaterFlowStatusCondenser Flow Switch StatusRead0=No Flow, 1=Flow
BI11CondPump1StateCondenser Pump Status - Pump 1Read0=Pump Off Request, 1=Pump On Request
BI12CondPump2StateCondenser Pump Status - Pump 2Read0=Pump Off Request, 1=Pump On Request
BI2EvapWaterFlowStatusEvaporator Flow Switch StatusRead0=No Flow, 1=Flow
BI8EvapPump1StateEvaporator Pump Status - Pump 1Read0=Pump Off Request, 1=Pump On Request
BI9EvapPump2StateEvaporator Pump Status - Pump 2Read0=Pump Off Request, 1=Pump On Request
BI5RunEnabledRun EnabledRead0=Off, 1=Run Allowed
MV2ActiveModeChiller Mode OutputRead1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY
MVmin3ChillerOperationModeChiller Mode Setpoint - NetworkWrite1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY
MVmin1UnitStatusChiller StatusRead1=OFF, 2=START, 3=RUN, 4=PRESHUTDOWN, 5=SERVICE
MV7RefrigerantTypeRefrigerant TypeRead1=R22, 2=R134a, 3=R407c, 4=R410a, 5=R32, 6=R454C, 7=R513A, 8=R515B, 9=R1233zd(E), 10=R1234ze(E)
MV4UnitsUnitsWrite1=Metric, 2=English

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)

How many BACnet points does the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) have?

This list has 97 BACnet objects: 31 analog inputs, 45 analog values, 14 binary inputs, 2 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet points are writable?

8 of the 97 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet documentation?

The source is MicroTech Unit Controller Protocol Information (Chiller Models AGZ-F, WMC-E, and WMT) (ED 19131-1), revision 2026-04, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019131-1.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)?

Start with BV 2 ChillerEnableStp (Network enable/disable of the chiller); MV 3 ChillerOperationMode (Ice / cool / heat / heat recovery mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitPct (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 ChillerLocalRemote (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); AV 2 ChillerCapacity (Actual capacity in percent); AV 901 AVFaultAlarm (Active fault alarm index).

How do I enable BMS control of the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)?

For AGZ-F, WMC-E and WMT, Control Source must be set to BAS at the unit HMI before the controller uses Network Enable (BV 2), the cool/heat/ice setpoints, the mode setpoint and the capacity limit from the BAS.

How do I check these points on the real MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech Unit Controller Protocol Information (Chiller Models AGZ-F, WMC-E, and WMT) · ED 19131-1 · rev. 2026-04. Object names, instances and units are reproduced as published; descriptions are our own.