Chiller controller · BACnet points list
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet points list
Updated 28 October 2026
This MicroTech controller generation serves the AGZ-F, WMC-E and WMT chillers and talks BACnet MS/TP, BACnet IP or Modbus through its communication module. Besides the usual water temperatures, refrigerant pressures, run hours and network setpoints, it adds alarm module ID, type and payload values for fault, problem and warning alarms, a heat setpoint and a refrigerant type readout.
This page lists 97 BACnet objects for the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
- Equipment
- Chiller controller
- Equipment type
- Chillers
- BACnet objects
- 97 (8 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- AGZ-F 1.2.0, WMT 1.0.0, WMC-E 1.0.0 application software or later
- Default device instance
- 9050
- Also known as
- AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131
BMS integration notes: Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Set Control Source to BAS at the chiller HMI, then use ChillerEnableStp to enable the chiller and write the cool (or heat/ice) setpoint, mode and capacity limit. Monitor unit status, water temperatures, capacity and the alarm index/module objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | ChillerEnableStp | Network enable/disable of the chiller | Write |
| MV 3 | ChillerOperationMode | Ice / cool / heat / heat recovery mode command | Write |
| AV 4 | NetworkCoolTempSetpoint | Leaving water cool setpoint from the BMS | Write |
| AV 3 | NetworkCapacityLimitPct | Capacity limit from the BMS | Write |
| BV 8 | ClearAlarm | Clear alarms from the network | Write |
| BI 3 | ChillerLocalRemote | Shows whether network control is active | Read |
| MV 1 | UnitStatus | Chiller run state | Read |
| AI 2 | LvgEvapWaterTempUnit | Leaving chilled water temperature | Read |
| AV 2 | ChillerCapacity | Actual capacity in percent | Read |
| AV 901 | AVFaultAlarm | Active fault alarm index | Read |
Enable & remote start
For AGZ-F, WMC-E and WMT, Control Source must be set to BAS at the unit HMI before the controller uses Network Enable (BV 2), the cool/heat/ice setpoints, the mode setpoint and the capacity limit from the BAS.
Network setup
- Default device instance 9050; device object name defaults to Daikin_MicroTech_ plus the instance.
- BACnet IP default UDP port 47808.
- Network parameters are set at the HMI; see IM 1283 for the communication module.
Watch out for
- Setpoint ranges differ between AGZ-F and WMT/WMC-E.
- Point availability differs per model (see the AGZ-F/WMT/WMC-E matrix in the guide).
- Alarm details come as index, module ID, module type and payload objects per alarm class.
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 9 | C1Comp1Current | Compressor Current - Circuit 1 Compressor 1 | A | Read | |
| AI | 10 | C1Comp2Current | Compressor Current - Circuit 1 Compressor 2 | A | Read | |
| AI | 45 | C1Comp1Kilowatts | Compressor Power - Circuit 1 Compressor 1 | kW | Read | |
| AI | 46 | C1Comp2Kilowatts | Compressor Power - Circuit 1 Compressor 2 | kW | Read | |
| AI | 27 | C1Comp1Voltage | Compressor Voltage - Circuit 1 Compressor 1 | V | Read | |
| AI | 28 | C1Comp2Voltage | Compressor Voltage - Circuit 1 Compressor 2 | V | Read | |
| AI | 3 | EntCondWaterTemp | Condenser Entering Fluid Temperature | °F | Read | |
| AI | 147 | CondWaterFlowRate | Condenser Flow Rate | GPM | Read | |
| AI | 4 | LvgCondWaterTemp | Condenser Leaving Fluid Temperature | °F | Read | |
| AI | 99 | Cond1RefPressure | Condenser Refrigerant Pressure - Circuit 1 | psi | Read | |
| AI | 100 | Cond2RefPressure | Condenser Refrigerant Pressure - Circuit 2 | psi | Read | |
| AI | 81 | C1Comp1DischRefPressure | Discharge Refrigerant Pressure - Circuit 1 Compressor 1 | psi | Read | |
| AI | 82 | C1Comp2DischRefPressure | Discharge Refrigerant Pressure - Circuit 1 Compressor 2 | psi | Read | |
| AI | 63 | C1Comp1DischargeTemp | Discharge Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AI | 64 | C1Comp2DischargeTemp | Discharge Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AI | 66 | C2Comp1DischargeTemp | Discharge Refrigerant Temperature - Circuit 2 Compressor 1 | °F | Read | |
| AI | 1 | EntEvapWaterTemp | Evaporator Entering Fluid Temperature | °F | Read | |
| AI | 148 | EvapWaterFlowRate | Evaporator Flow Rate | GPM | Read | |
| AImin | 2 | LvgEvapWaterTempUnit | Evaporator Leaving Fluid Temperature | °F | Read | |
| AI | 141 | C1EvapRefPressure | Evaporator Refrigerant Pressure - Circuit 1 | psi | Read | |
| AI | 142 | C2EvapRefPressure | Evaporator Refrigerant Pressure - Circuit 2 | psi | Read | |
| AI | 177 | HeatRecEntWaterTemp | Heat Recovery Entering Fluid Temperature | °F | Read | |
| AI | 150 | HeatRecLvgWaterTemp | Heat Recovery Leaving Fluid Temperature | °F | Read | |
| AI | 218 | C1LiqLineRefTemp | Liquid Line Refrigerant Temperature - Circuit 1 | °F | Read | |
| AI | 5 | OutdoorAirTemp | Outdoor Air Temperature | °F | Read | |
| AI | 123 | C1Comp1SuctionPressure | Suction Refrigerant Pressure - Circuit 1 Compressor 1 | psi | Read | |
| AI | 124 | C1Comp2SuctionPressure | Suction Refrigerant Pressure - Circuit 1 Compressor 2 | psi | Read | |
| AI | 105 | C1Comp1SuctionTemp | Suction Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AI | 106 | C1Comp2SuctionTemp | Suction Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AI | 224 | C1SuctionTemperature | Suction Refrigerant Temperature - Circuit 1 | °F | Read | |
| AI | 225 | C2SuctionTemperature | Suction Refrigerant Temperature - Circuit 2 | °F | Read | |
| AV | 1 | ActiveCapacityLimit | Active Capacity Limit Output | % | Read | |
| AV | 5 | ActiveLvgWaterTarget | Active Setpoint | °F | Read | |
| AVmin | 2 | ChillerCapacity | Actual Capacity | % | Read | |
| AVmin | 901 | AVFaultAlarm | Alarm Index | Read | ||
| AV | 900 | AVProblemAlarm | Alarm Index | Read | ||
| AV | 902 | AVWarningAlarm | Alarm Index | Read | ||
| AV | 910 | AVFaultModID | Alarm Module ID | Read | ||
| AV | 907 | AVProblemModID | Alarm Module ID | Read | ||
| AV | 913 | AVWarningModID | Alarm Module ID | Read | ||
| AV | 911 | AVFaultModPayload | Alarm Module Payload | Read | ||
| AV | 908 | AVProblemModPayload | Alarm Module Payload | Read | ||
| AV | 914 | AVWarningModPayload | Alarm Module Payload | Read | ||
| AV | 909 | AVFaultModType | Alarm Module Type | Read | ||
| AV | 906 | AVProblemModType | Alarm Module Type | Read | ||
| AV | 912 | AVWarningModType | Alarm Module Type | Read | ||
| AVmin | 3 | NetworkCapacityLimitPct | Capacity Limit Setpoint - Network | % | Write | |
| AV | 8 | C1Comp1MotorCurrentPercent | Compressor Percent RLA - Circuit 1 Compressor 1 | % | Read | |
| AV | 9 | C1Comp2MotorCurrentPercent | Compressor Percent RLA - Circuit 1 Compressor 2 | % | Read | |
| AV | 74 | C1Comp1Hours | Compressor Run Hours - Circuit 1 Compressor 1 | h | Read | |
| AV | 75 | C1Comp2Hours | Compressor Run Hours - Circuit 1 Compressor 2 | h | Read | |
| AV | 76 | C1Comp3Hours | Compressor Run Hours - Circuit 1 Compressor 3 | h | Read | |
| AV | 77 | C2Comp1Hours | Compressor Run Hours - Circuit 2 Compressor 1 | h | Read | |
| AV | 78 | C2Comp2Hours | Compressor Run Hours - Circuit 2 Compressor 2 | h | Read | |
| AV | 79 | C2Comp3Hours | Compressor Run Hours - Circuit 2 Compressor 3 | h | Read | |
| AV | 92 | C1Comp1Starts | Compressor Starts - Circuit 1 Compressor 1 | Read | ||
| AV | 93 | C1Comp2Starts | Compressor Starts - Circuit 1 Compressor 2 | Read | ||
| AV | 94 | C1Comp3Hours | Compressor Starts - Circuit 1 Compressor 3 | Read | ||
| AV | 95 | C2Comp1Starts | Compressor Starts - Circuit 2 Compressor 1 | Read | ||
| AV | 96 | C2Comp2Starts | Compressor Starts - Circuit 2 Compressor 2 | Read | ||
| AV | 97 | C2Comp3Hours | Compressor Starts - Circuit 2 Compressor 3 | Read | ||
| AV | 110 | CondPump1RunHours | Condenser Pump Run Hours - Condenser Pump 1 | h | Read | |
| AV | 111 | CondPump2RunHours | Condenser Pump Run Hours - Condenser Pump 2 | h | Read | |
| AV | 44 | Cond1SatRefTemp | Condenser Saturated Refrigerant Temperature - Circuit 1 | °F | Read | |
| AV | 45 | Cond2SatRefTemp | Condenser Saturated Refrigerant Temperature - Circuit 2 | °F | Read | |
| AVmin | 4 | NetworkCoolTempSetpoint | Cool Setpoint - Network | °F | Write | |
| AV | 26 | C1Comp1DischSatRefTemp | Discharge Saturated Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AV | 27 | C1Comp2DischSatRefTemp | Discharge Saturated Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AV | 112 | EvapPump1OperHours | Evaporator Pump Run Hours - Evaporator Pump 1 | h | Read | |
| AV | 113 | EvapPump2OperHours | Evaporator Pump Run Hours - Evaporator Pump 2 | h | Read | |
| AV | 68 | C1EvapSatRefTemp | Evaporator Saturated Refrigerant Temperature - Circuit 1 | °F | Read | |
| AV | 69 | C2EvapSatRefTemp | Evaporator Saturated Refrigerant Temperature - Circuit 2 | °F | Read | |
| AV | 7 | NetworkIceTempSetpoint | Ice Setpoint - Network | °F | Write | |
| AV | 6 | NetworkHeatTempSetpoint | Heat Setpoint - Network | °F | Write | |
| AV | 50 | C1Comp1SuctSatTemp | Suction Saturated Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AV | 51 | C1Comp2SuctSatTemp | Suction Saturated Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| BVmin | 2 | ChillerEnableStp | Chiller Enable Setpoint | Write | 0=Disable (Inactive), 1=Enable | |
| BVmin | 8 | ClearAlarm | Clear Alarm - Network | Write | 0=Normal, 1=Clear Alarm | |
| BI | 10 | AlarmDigitalOutput | Alarm Digital Output | Read | 0=No Alarm, 1=Alarm | |
| BI | 6 | ChillerLimited | Chiller Capacity Limited | Read | 0=Not Limited, 1=Limited | |
| BI | 7 | ChillerEnableOutput | Chiller Enable Output | Read | 0=Disable, 1=Enable | |
| BImin | 3 | ChillerLocalRemote | Chiller Local/Network | Read | 0=Network, 1=Local | |
| BI | 4 | UnitOnOff | Chiller On/Off | Read | 0=Chiller Off, 1=Chiller On | |
| BI | 163 | C1Cmp1Unavailable | Compressor Unavailable - Circuit 1 Compressor 1 | Read | 0=Available, 1=Unavailable | |
| BI | 164 | C1Cmp2Unavailable | Compressor Unavailable - Circuit 1 Compressor 2 | Read | 0=Available, 1=Unavailable | |
| BI | 1 | CondWaterFlowStatus | Condenser Flow Switch Status | Read | 0=No Flow, 1=Flow | |
| BI | 11 | CondPump1State | Condenser Pump Status - Pump 1 | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 12 | CondPump2State | Condenser Pump Status - Pump 2 | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 2 | EvapWaterFlowStatus | Evaporator Flow Switch Status | Read | 0=No Flow, 1=Flow | |
| BI | 8 | EvapPump1State | Evaporator Pump Status - Pump 1 | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 9 | EvapPump2State | Evaporator Pump Status - Pump 2 | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 5 | RunEnabled | Run Enabled | Read | 0=Off, 1=Run Allowed | |
| MV | 2 | ActiveMode | Chiller Mode Output | Read | 1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY | |
| MVmin | 3 | ChillerOperationMode | Chiller Mode Setpoint - Network | Write | 1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY | |
| MVmin | 1 | UnitStatus | Chiller Status | Read | 1=OFF, 2=START, 3=RUN, 4=PRESHUTDOWN, 5=SERVICE | |
| MV | 7 | RefrigerantType | Refrigerant Type | Read | 1=R22, 2=R134a, 3=R407c, 4=R410a, 5=R32, 6=R454C, 7=R513A, 8=R515B, 9=R1233zd(E), 10=R1234ze(E) | |
| MV | 4 | Units | Units | Write | 1=Metric, 2=English |
No points match these filters.
Integration notes
- Point availability depends on chiller model and configuration (for example heat setpoint and heat recovery points).
- Starts objects AV 94 and AV 97 are printed with the names C1Comp3Hours and C2Comp3Hours; names kept as printed.
- Network setpoints only take effect when the control source is set to BAS at the HMI.
- Setpoint ranges differ between AGZ-F and WMT/WMC-E; check the unit before writing.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
How many BACnet points does the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) have?
This list has 97 BACnet objects: 31 analog inputs, 45 analog values, 14 binary inputs, 2 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet points are writable?
8 of the 97 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT) BACnet documentation?
The source is MicroTech Unit Controller Protocol Information (Chiller Models AGZ-F, WMC-E, and WMT) (ED 19131-1), revision 2026-04, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019131-1.pdf/.
What are the minimum BACnet points to integrate the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)?
Start with BV 2 ChillerEnableStp (Network enable/disable of the chiller); MV 3 ChillerOperationMode (Ice / cool / heat / heat recovery mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitPct (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 ChillerLocalRemote (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); AV 2 ChillerCapacity (Actual capacity in percent); AV 901 AVFaultAlarm (Active fault alarm index).
How do I enable BMS control of the Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)?
For AGZ-F, WMC-E and WMT, Control Source must be set to BAS at the unit HMI before the controller uses Network Enable (BV 2), the cool/heat/ice setpoints, the mode setpoint and the capacity limit from the BAS.
How do I check these points on the real MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00
Source: MicroTech Unit Controller Protocol Information (Chiller Models AGZ-F, WMC-E, and WMT) · ED 19131-1 · rev. 2026-04. Object names, instances and units are reproduced as published; descriptions are our own.