Unit ventilator controller (classroom air handler) · BACnet points list

Daikin Applied MicroTech Unit Ventilator Controller BACnet points list

Updated 28 October 2026

Short answer

The MicroTech UV controller has BACnet MS/TP built in (LonWorks needs an add-on module and is not listed here). Objects cover local and network space, water, discharge and outdoor readings, occupancy setpoints and differentials, compressor, valve, damper, economizer and electric heat tuning, PI loop gains, network inputs for space temperature, setpoint, humidity, CO2 and fan speed, occupancy, application mode and emergency commands, unit state and the current alarm. Many objects only apply to certain unit configurations (compressor, hydronic, electric heat, economizer).

This page lists 187 BACnet objects for the Daikin Applied MicroTech Unit Ventilator Controller — 127 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech Unit Ventilator Controller
Equipment
Unit ventilator controller (classroom air handler)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
187 (127 writable)
Transport
BACnet MS/TP
Firmware
Application 1.05.00 (PICS)
Default device instance
3101120 (System Minimum Instance 3101000 + MAC 120)
Also known as
MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110
Source document
MicroTech Unit Ventilator Unit Controller Protocol Information (BACnet MS/TP, LonWorks) · ED 19110-6 · rev. 2022-03
Download CSV 187 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied MicroTech Unit Ventilator Controller

Integration in brief

Give the controller a unique MAC address and device instance, then command occupancy, application mode and, if the BMS owns it, the network setpoint. Read Unit State, the effective space temperature and Current Alarm. Network overrides are cleared by a controller reset, so the BMS has to rewrite them.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 7OccManCmdOccupancy override from the BMSWrite
MV 8OccScheduleOccupancy schedule command (Occ/Unocc/Standby)Write
MV 21EmergOverrideEmergency mode (Normal/Shutdown/Purge/Fire...)Command
MV 17NetworkApplicModeApplication mode (Auto/Heat/Cool/Off/Fan_Only/Dehumid)Write
AV 19NetworkSetpointNetwork reference setpointCommand
BV 1ClearAlarmClear the current alarmWrite
MV 42UnitStateCurrent operating stateRead
AV 22EffectSpaceTempSpace temperature used for controlRead
AV 38FanSpeedFan speed output, 0-100 %Read
MV 2CurrentAlarmHighest-priority active alarmRead

Enable & remote start

No local/remote switch is described. Network inputs take effect when written: Occupancy Override Input (MV 7) overrides the other occupancy inputs, Occupancy Scheduler Input (MV 8) sets the scheduled mode, Application Mode (MV 17) limits heating/cooling/dehumidification, Emergency Override (MV 21) forces an emergency mode, and Compressor Enable (MV 1) permits compressor operation (Null = enabled). All of these revert to their defaults after a controller reset.

Heartbeat & communication loss

No BACnet heartbeat. Receive Heartbeat is a LonWorks-only setting. BACnet network overrides stay in place until the controller resets, then revert to their defaults.

Sensors & values from the BMS

Network Space Temperature Input (AV 18) replaces the local sensor when valid; Effective Space Temperature (AV 22) shows the value in use. Network Temperature Setpoint Input (AV 19) sets the reference setpoint and AV 35 offsets it; AV 129-132 shift the occupied and standby setpoints. Network inputs also exist for outdoor temperature (AV 45), outdoor and space humidity (AV 48, AV 50), space CO2 (AV 52), entering water temperature (AV 113), minimum OA damper position (AV 70) and fan speed (AV 115).

Network setup

Watch out for

Daikin Applied MicroTech Unit Ventilator Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

187 of 187 shown
Type
Binary
Access
Show
Daikin Applied MicroTech Unit Ventilator Controller BACnet Points List
DescriptionStates
AI1LocalSpaceTempLocal Space Temperature°FRead
AI2LWTLeaving Water Temperature°FRead
AI3EWTEntering Water Temperature°FRead
AI4DischAirTempDischarge Air Temperature°FRead
AI5LocalSetptLocal Setpoint Adjust Output°FRead
AI6Comp1SuctTempIndoor Coil Temperature°FRead
AI8LineVoltageBrownout DetectioncountsRead
AI9OutdoorTempOutdoor Air Temperature°FRead
AI10OutdoorRHOutdoor Relative Humidity%Read
AI11IndoorRHIndoor Relative Humidity%Read
AI12SpaceCO2Space CO2ppmRead
AI13ReturnAirTempReturn Air Temperature°FRead
AV1Occupied_Cool_SetptOccupied Cooling Setpoint°FWrite
AV2Standby_Cool_SetptStandby Cooling Setpoint°FWrite
AV3Unoccupied_Cool_SetptUnoccupied Cooling Setpoint°FWrite
AV4Occupied_Heat_SetptOccupied Heating Setpoint°FWrite
AV5Standby_Heat_SetptStandby Heating Setpoint°FWrite
AV6Unoccupied_Heat_SetptUnoccupied Heating Setpoint°FWrite
AV7BypassTimeLocal Bypass Time SetpointminWrite
AV9BrownoutRefBrownout Reference SetpointcountsWrite
AV10OccDiffOccupied Setpoint Differential°FWrite
AV12LowTempProtLow Suction Line Temperature Protection Setpoint°FWrite
AV13LowTmpProtDifLow Suction Temperature Protection Differential°FWrite
AV15MinCompOffTmrCompressor Minimum Off TimersWrite
AV16MinCompOnTmrCompressor Minimum On TimersWrite
AV17UnoccDiffUnoccupied Setpoint Differential°FWrite
AV18NetworkSpaceTempNetwork Space Temperature Input°FCommand
AVmin19NetworkSetpointNetwork Temperature Setpoint Input°FCommand
AVmin22EffectSpaceTempEffective Space Temperature°FRead
AV23EffectSetptEffective Setpoint°FRead
AV24SetptShiftTemperature Setpoint Shift°FRead
AV35SetptOffsetTemperature Setpoint Offset°FCommand
AV114ControlTempControl Temperature°FRead
AVmin38FanSpeedFan Speed%Read
AV40CompRunHoursTenthsCompressor Run TimehRead
AV44EffectOutdoorTempEffective Outdoor Air Temperature°FRead
AV45NetworkOutdoorTempNetwork Outdoor Air Temperature Input°FWrite
AV46FanRunHoursTenthsFan Run TimehRead
AV47EffectOutdoorRHEffective Outdoor Humidity%Read
AV48NetworkOutdoorRHNetwork Outdoor Humidity Input%Write
AV49EffectSpaceRHEffective Space Humidity%Read
AV50NetworkSpaceRHNetwork Space Humidity Input%Write
AV51EffectSpaceCO2Effective Space CO2ppmRead
AV52NetworkSpaceCO2Network Space CO2 InputppmWrite
AV53DATSetptDischarge Air Temperature Setpoint°FRead
AV118DischargeAirTempDischarge Air Temperature°FRead
AV54NetworkDATClgSetptNetwork Discharge Temperature Cooling Setpoint Input°FWrite
AV119DATClgSetptDischarge Air Temperature Cooling Setpoint°FRead
AV55NetworkDATHtgSetptNetwork Discharge Temperature Heating Setpoint Input°FWrite
AV120DATHtgSetptDischarge Air Temperature Heating Setpoint°FRead
AV56OADamperOutdoor Air Damper Position%Read
AV113NetworkEWTEntering Water Temperature Input°FWrite
AV57EffectEWTEffective Entering Water Temperature°FRead
AV58FBDamperFace and Bypass Damper Position%Read
AV59HotWaterModulating Hot Water Valve Position%Read
AV60ColdWaterModulating Cold Water Valve Position%Read
AV61OAMinPosOAD Minimum Position%Write
AV62OAMinPosMedSpeedOAD Minimum Position Medium Speed%Write
AV63OAMinPosLowSpeedOAD Minimum Position Low Speed%Write
AV64SpaceCO2LimSpace CO2 LimitppmWrite
AV65EconOADiffSetptEconomizer Outdoor Differential Setpoint°FWrite
AV66EconDBDiffEconomizer Dry Bulb Temperature Differential°FWrite
AV67EconEnthSetptEconomizer Enthalpy SetpointBTU/lbWrite
AV68EconEnthDiffEconomizer IA/OA Enthalpy DifferentialBTU/lbWrite
AV69SpaceRHSetptSpace Humidity Setpoint%Write
AV70NetworkOAMinPosNetwork Minimum Outdoor Air Damper Position%Write
AV71SetpointSetpoint°FRead
AV115NetworkFanSpeedNetwork Fan Speed Input%Write
AV116AuxHeatOnDiffAuxiliary Heat On Differential°FWrite
AV117AuxHeatOffDiffAuxiliary Heat Off Differential°FWrite
AV121ASHPDefrostTimeAir Source Heat Pump Defrost TimeminWrite
AV122LWTempLeaving Water Temperature°FRead
AV123LuiSetptOffsetKeypad Setpoint Offset°FRead
AV124OALockoutSetptOutdoor Air Lockout Setpoint°FWrite
AV125OutdoorEnthalpyOutdoor EnthalpyBTU/lbRead
AV126IndoorEnthalpyIndoor EnthalpyBTU/lbRead
AV127OATSPEconomizer Outdoor Temperature Setpoint°FWrite
AV128EmergHtgSetptEmergency Heating Setpoint°FWrite
AV129OccCoolSetptShiftNetwork Occupied Cooling Setpoint Shift Input°FWrite
AV130StandbyCoolSetptShiftNetwork Standby Cooling Setpoint Shift Input°FWrite
AV131OccHeatSetptShiftNetwork Occupied Heating Setpoint Shift Input°FWrite
AV132StandbyHeatSetptShiftNetwork Standby Heating Setpoint Shift Input°FWrite
AV133ExhStartPosExhaust Fan Outdoor Air Damper Setpoint Position%Write
AV134FilterChangeHoursFilter Change HourshWrite
AV135FanChgsPerHourFan Changer Per HourWrite
AV136DisAirMechLowLimMechanical Cooling Discharge Air Temperature Low Limit°FWrite
AV137DisAirHighLimDischarge Air Temperature High Limit°FWrite
AV138ComprMtrValveTimeMotorized Isolation Valve Time DelaysWrite
AV139FanOffDelaySpace Fan Off DelaysWrite
AV140CompClgOATLockoutSetptCompressor Cooling Outdoor Air Temperature Lockout°FWrite
AV141ComprHtgOATLockCompressor Heating Outdoor Air Temperature Lockout°FWrite
AV142CompHtgEWTLockCompressor Heating Entering Water Temperature Lockout°FWrite
AV143AirTemperingDiffAir Tempering Differential°FWrite
AV144SourceTempDiffEntering Water Temperature Differential°FWrite
AV145OAMinPosExhaustOAD Minimum Position - Exhaust Interlock%Write
AV146EOCLowOASetptEnd of Cycle Low Outdoor Air Setpoint°FWrite
AV147IACoilDXTempIndoor Air/DX Coil Temperature°FRead
AV148OACoilDXTempOutdoor Air/DX Coil Temperature°FRead
AV149BreakPointAutoLowFan Speed Low Break Point%Write
AV150BreakPointAutoMediumFan Speed Medium Break Point%Write
AV151BreakpointAutoHighFan Speed High Break Point%Write
AV152BreakpointAutoDiffFan Speed Break Point Differential%Write
AV153DATCoolSetptDischarge Air Temperature Cooling Setpoint°FWrite
AV154DATHeatSetptDischarge Air Temperature Heating Setpoint°FWrite
AV155PWMLowFanPWM Fan Low Speed%Write
AV156PWMMediumFanPWM Fan Medium Speed%Write
AV157PWMHighFanPWM Fan High Speed%Write
AV158EwFlowTimerEntering Water Flow TimersWrite
AV159RATReturn Air Temperature Setpoint°FRead
AV160OutdoorCoilTempOutdoor Coil Temperature°FRead
AV72SZVavPropGainSingle-zone VAV PI loop proportional gainWrite
AV73SZVavIntegGainSingle-zone VAV PI loop integral gainWrite
AV74SZVavMinFanMinimum Fan Output%Write
AV75SZVavMaxFanMaximum Fan Output%Write
AV76SZVavMaxDeltaTempMaximum Temperature Differential°FWrite
AV77SZVavFanSpeedPIFan Speed Output%Read
AV78ClgPropGainCooling PI loop proportional gainWrite
AV79ClgIntegGainCooling PI loop integral gainWrite
AV80ClgMinPosMinimum Cooling Position%Write
AV81ClgMaxDeltaTempMaximum Cooling Temperature Differential°FWrite
AV82ClgMaxPosMaximum Cooling Position%Write
AV83ColdWaterPIChilled Water Valve Position%Read
AV84HtgPropGainHeating PI loop proportional gainWrite
AV85HtgIntegGainHeating PI loop integral gainWrite
AV86HtgMinPosMinimum Heating Position%Write
AV87HtgMaxDeltaTempMaximum Heating Temperature Differential°FWrite
AV88HtgMaxPosMaximum Heating Position%Write
AV89HotWaterPIHot Water Valve Position%Read
AV90FBDamperPropGainFace and bypass damper PI loop proportional gainWrite
AV91FBDamperIntegGainFace and bypass damper PI loop integral gainWrite
AV92FBP_PIOutFace and Bypass Damper Position Output%Read
AV93HtgElectPropGainElectric heat PI loop proportional gainWrite
AV94HtgElectIntegGainElectric heat PI loop integral gainWrite
AV95ElectDatLLPIOutElectric Heat Discharge Air Temperature Low Limit Output%Read
AV96ElectDehumPIOutElectric Heat Dehumidification Output%Read
AV101CO2PropGainCO2 PI loop proportional gainWrite
AV102CO2IntegGainCO2 PI loop integral gainWrite
AV112NetworkMinDATSetptNetwork Minimum Discharge Air Temperature Setpoint Input°FWrite
AV103OADPosCO2Outdoor Air Damper Position%Read
AV104EconPropGainEconomizer PI loop proportional gainWrite
AV105EconIntegTimeEconomizer PI loop integral gainWrite
AV106FreeCoolingPILoopOutOutdoor Air Damper Position%Read
AV107OADLLPropGainOA damper low limit PI loop proportional gainWrite
AV108OADLLIntegGainOA damper low limit PI loop integral gainWrite
AV109OADLLPiOutOutdoor Air Damper Low Limit Differential%Read
AV111OAMaxPosMaximum Outdoor Damper Position%Write
AV411MacAddressBACnet MAC AddressWrite
AV412SystemMinInstanceBACnet Minimum Instance NumberWrite
BVmin1ClearAlarmClear AlarmWrite0=None, 1=Clear Alarm
BV3ResetFilterReset FilterWrite0=None, 1=Clear Alarm
MI1CondOverFlowCondensate Overflow StatusRead1=Dry, 2=Wet, 3=Null
MI4HumidistatHumidistatRead1=Notdehumidify, 2=Dehumidify
MV1NetworkComprEnableCompressor EnableWrite1=Disable, 2=Enable, 3=Null
MVmin2CurrentAlarmCurrent AlarmRead
MV6EffectOccupEffective Occupancy OutputRead1=Occ, 2=Unocc, 3=Bypass, 4=Standby, 5=Null
MVmin7OccManCmdOccupancy Override InputWrite1=Occ, 2=Unocc, 3=Bypass, 4=Standby, 5=Null
MVmin8OccScheduleOccupancy Scheduler InputWrite1=Occ, 2=Unocc, 3=Standby, 4=Null
MV9OccSensorOccupancy Sensor InputWrite1=Occ, 2=Unocc, 3=Null
MV12EnergyHoldOffEnergy Hold Off InputWrite1=Normal, 2=Energy Hold, 3=Null
MV13PumpRequestPump Request OutputRead1=Inactive, 2=Active
MV15UnitsUnits (English/Metric)Write1=Imperial (English), 2=SI (Metric)
MV16DehumidEnableDehumidification EnableWrite1=Disable, 2=Enable, 3=Null
MVmin17NetworkApplicModeApplication ModeWrite1=Auto, 2=Heat, 3=Cool, 4=Night_Purge, 5=Off, 6=Emerg_Heat, 7=Fan_Only, 8=Dehumid, 9=Null
MV20EffectHeatCoolEffective Heat/CoolRead1=Auto, 2=Heat, 3=Cool, 4=Night_Purge, 5=Off, 6=Emerg_Heat, 7=Fan_Only, 8=Dehumid, 9=Null
MVmin21EmergOverrideEmergency OverrideCommand1=Normal, 2=Pressurize, 3=Depressurize, 4=Purge, 5=Shutdown, 6=Fire, 7=Invalid
MV22NetworkEconEnableEconomizer EnableCommand1=Disable, 2=Enable, 3=Null
MV23RemoteSetpointAdjTypRemote Sensor AdjustmentWrite1=DIFF, 2=ABS
MV24AuxiliaryHeatAuxiliary Heat EnableCommand1=Disable, 2=Enable, 3=Null
MV25AuxHeatReverseAuxiliary Heat ReverseWrite1=Direct, 2=Reversed
MV26OALockoutEnableOutdoor Air Lockout EnableWrite1=Disable, 2=Enable
MV27RSSystemModeStatusRoom Sensor Mode StatusRead1=Not_Present, 2=Cool, 3=Auto, 4=Heat
MV28RSFanSpeedStatusRoom Sensor Fan SpeedRead1=Auto, 2=High, 3=Medium, 4=Low, 5=Off
MV29EmergHtgEnableEmergency Heating EnableWrite1=Disable, 2=Enable
MV30FilterChangeEnableFilter Change EnableWrite1=Disable, 2=Enable
MV31AirTemperingModeAir Tempering ModeWrite1=Inactive, 2=Active
MV32FanCyclingFan CyclingWrite1=Continuous, 2=Cycling
MV33FanTimeResetFan Run Time ResetWrite1=Dont_Reset, 2=Reset
MV34ComprTimeResetCompressor Run Time ResetWrite1=Dont_Reset, 2=Reset
MV35AirTemperingEnableAir Tempering EnableWrite1=Disable, 2=Enable
MV38EconStategyEconomizer StrategyWrite1=None, 2=Diff_Temp, 3=Outdoor_Enth, 4=Enth_Compare
MV39ControlTempSourceControl Temperature SourceWrite1=Space, 2=RAT, 3=AISR_Avg
MV40FanControlSelectIndoor Fan Control SelectWrite1=Single_DAT, 2=CO2, 3=AI_Input
MV41SpaceCO2EnableSpace CO2 EnableWrite1=Disable, 2=Enable
MVmin42UnitStateUnit StateRead1=Powerup, 2=Off, 3=Fan_Only, 4=Off_Alarm, 5=Defrost, 6=Night_Purge, 7=Low_Limit, 8=Lvg_Elect_Heat, 9=Prep_To_Heat, 10=Comp_Heat_1, 11=Comp_Heat_2, 12=Elect_Heat_1, 13=Elect_Heat_2, 14=Elect_Heat_3, 15=Hydro_Heat, 16=Hyd_Heat_Elect_1, 17=Hyd_Heat_Elect_2, 18=Hyd_Heat_Elect_3, 19=Comp_Heat_2_Elect_Heat_1, 20=Comp_Heat_2_Elect_Heat_2, 21=Comp_Heat_2_Elect_Heat_3, 22=Prep_Dehumid, 23=Dehumid_Water, 24=Dehumid_Comp_1, 25=Dehumid_Comp_2, 26=Comp_Cool_1, 27=Comp_Cool_2, 28=Air_Econo, 29=Econo_Comp_1, 30=Econo_Comp_2, 31=Air_Econo_Water, 32=Water_Cool, 33=Prep_To_Cool, 34=Reheat, 35=Reheat_Low_Limit, 36=Emerg_Heat
MV43EnergyHoldOffStatusEnergy Hold Off StatusRead1=Allow, 2=Hold_Off
MV44SetptMethodSetpoint MethodWrite1=Easy, 2=Advanced
MV45SpaceTempSensInstSpace Temperature Sensor InstalledWrite1=Not_Installed, 2=Installed

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech Unit Ventilator Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech Unit Ventilator Controller

How many BACnet points does the Daikin Applied MicroTech Unit Ventilator Controller have?

This list has 187 BACnet objects: 12 analog inputs, 136 analog values, 2 binary values, 2 multi-state inputs, 35 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech Unit Ventilator Controller BACnet points are writable?

127 of the 187 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech Unit Ventilator Controller BACnet documentation?

The source is MicroTech Unit Ventilator Unit Controller Protocol Information (BACnet MS/TP, LonWorks) (ED 19110-6), revision 2022-03, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20UV%20Unit%20Controller%20Protocol%20Information%20ED%2019110-6.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech Unit Ventilator Controller?

Start with MV 7 OccManCmd (Occupancy override from the BMS); MV 8 OccSchedule (Occupancy schedule command (Occ/Unocc/Standby)); MV 21 EmergOverride (Emergency mode (Normal/Shutdown/Purge/Fire...)); MV 17 NetworkApplicMode (Application mode (Auto/Heat/Cool/Off/Fan_Only/Dehumid)); AV 19 NetworkSetpoint (Network reference setpoint); BV 1 ClearAlarm (Clear the current alarm); MV 42 UnitState (Current operating state); AV 22 EffectSpaceTemp (Space temperature used for control); AV 38 FanSpeed (Fan speed output, 0-100 %); MV 2 CurrentAlarm (Highest-priority active alarm).

How do I enable BMS control of the Daikin Applied MicroTech Unit Ventilator Controller?

No local/remote switch is described. Network inputs take effect when written: Occupancy Override Input (MV 7) overrides the other occupancy inputs, Occupancy Scheduler Input (MV 8) sets the scheduled mode, Application Mode (MV 17) limits heating/cooling/dehumidification, Emergency Override (MV 21) forces an emergency mode, and Compressor Enable (MV 1) permits compressor operation (Null = enabled). All of these revert to their defaults after a controller reset.

Does the Daikin Applied MicroTech Unit Ventilator Controller need a BACnet heartbeat or have a communication timeout?

No BACnet heartbeat. Receive Heartbeat is a LonWorks-only setting. BACnet network overrides stay in place until the controller resets, then revert to their defaults.

Can the BMS supply sensor values to the Daikin Applied MicroTech Unit Ventilator Controller?

Network Space Temperature Input (AV 18) replaces the local sensor when valid; Effective Space Temperature (AV 22) shows the value in use. Network Temperature Setpoint Input (AV 19) sets the reference setpoint and AV 35 offsets it; AV 129-132 shift the occupied and standby setpoints. Network inputs also exist for outdoor temperature (AV 45), outdoor and space humidity (AV 48, AV 50), space CO2 (AV 52), entering water temperature (AV 113), minimum OA damper position (AV 70) and fan speed (AV 115).

How do I check these points on the real MicroTech Unit Ventilator Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech Unit Ventilator Unit Controller Protocol Information (BACnet MS/TP, LonWorks) · ED 19110-6 · rev. 2022-03. Object names, instances and units are reproduced as published; descriptions are our own.