- Magnitude WME C-vintage Chiller (MicroTech WME controller)
Chiller controller · BACnet points list
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet points list
Updated 28 October 2026
The MicroTech WME chiller unit controller on C-vintage Magnitude chillers supports BACnet MS/TP, BACnet IP and Modbus through its BAS communication module. The BACnet table is short and focused: water temperatures and flows, per-compressor current, power, voltage and refrigerant data for two compressors, alarm codes, run hours and starts, plus network enable, mode, cool setpoint and capacity limit.
This page lists 68 BACnet objects for the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- Magnitude WME C-vintage Chiller (MicroTech WME controller)
- Equipment
- Chiller controller
- Equipment type
- Chillers
- BACnet objects
- 68 (6 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Chiller application 1.1.6, HMI 1.3.10 or later
- Default device instance
- 9050
- Also known as
- WME-C, Magnitude WME, MicroTech WME, ED 19111
BMS integration notes: Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
At the chiller HMI set Control Source to BAS (for the network enable) and Remote Enable to Enable (for setpoint, mode and capacity limit). The BMS then writes ChillerEnableStp, the cool setpoint and capacity limit, and reads status, water temperatures and alarm codes.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | ChillerEnableStp | Network enable/disable of the chiller | Write |
| MV 3 | ChillerOperationMode | Ice / cool / heat / heat recovery mode command | Write |
| AV 4 | NetworkCoolTempSetpoint | Leaving water cool setpoint from the BMS | Write |
| AV 3 | NetworkCapacityLimitPct | Capacity limit from the BMS | Write |
| BV 8 | ClearAlarm | Clear alarms from the network | Write |
| BI 3 | ChillerLocalRemote | Shows whether network control is active | Read |
| MV 1 | UnitStatus | Chiller run state | Read |
| AI 2 | LvgEvapWaterTempUnit | Leaving chilled water temperature | Read |
| AV 2 | ChillerCapacity | Actual capacity in percent | Read |
| AV 905 | AVFaultAlarmCode | Active fault alarm code | Read |
Enable & remote start
Control Source must be set to BAS at the unit HMI for the controller to use Network Enable (BV 2). For the cool setpoint, mode and capacity limit setpoints, Remote Enable must also be set to Enable at the HMI. Writing Enable to BV 2 only allows a start if other conditions are met.
Network setup
- Default device instance 9050; default device object name Daikin_MicroTech_ plus the instance.
- BACnet IP defaults: IP 192.168.1.10, mask 255.255.255.0, gateway 192.168.1.1, UDP port 47808.
- BACnet MS/TP default baud 38400.
- Network parameters are set at the HMI; see IM 1283 for the communication module.
Watch out for
- Only Cool mode applies to WME-C, although the mode objects list Ice, Heat and Heat Recovery.
- Units (MV 4) changes the units sent to BACnet between English and Metric.
- Some compressor-shutdown alarms cannot be cleared from the network.
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 9 | C1Comp1Current | Compressor Current - Circuit 1 Compressor 1 | A | Read | |
| AI | 10 | C1Comp2Current | Compressor Current - Circuit 1 Compressor 2 | A | Read | |
| AI | 63 | C1Comp1DischargeTemp | Compressor Discharge Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AI | 64 | C1Comp2DischargeTemp | Compressor Discharge Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AI | 81 | C1Comp1DischRefPressure | Compressor Discharge Refrigerant Pressure - Circuit 1 Compressor 1 | psi | Read | |
| AI | 82 | C1Comp2DischRefPressure | Compressor Discharge Refrigerant Pressure - Circuit 1 Compressor 2 | psi | Read | |
| AI | 45 | C1Comp1Kilowatts | Compressor Power - Circuit 1 Compressor 1 | kW | Read | |
| AI | 46 | C1Comp2Kilowatts | Compressor Power - Circuit 1 Compressor 2 | kW | Read | |
| AI | 105 | C1Comp1SuctionTemp | Compressor Suction Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AI | 106 | C1Comp2SuctionTemp | Compressor Suction Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AI | 123 | C1Comp1SuctionPressure | Compressor Suction Refrigerant Pressure - Circuit 1 Compressor 1 | psi | Read | |
| AI | 124 | C1Comp2SuctionPressure | Compressor Suction Refrigerant Pressure - Circuit 1 Compressor 2 | psi | Read | |
| AI | 27 | C1Comp1Voltage | Compressor Voltage - Circuit 1 Compressor 1 | V | Read | |
| AI | 28 | C1Comp2Voltage | Compressor Voltage - Circuit 1 Compressor 2 | V | Read | |
| AI | 3 | EntCondWaterTemp | Condenser Entering Fluid Temperature | °F | Read | |
| AI | 147 | CondWaterFlowRate | Condenser Fluid Flow Rate | GPM | Read | |
| AI | 4 | LvgCondWaterTemp | Condenser Leaving Fluid Temperature | °F | Read | |
| AI | 99 | Cond1RefPressure | Condenser Refrigerant Pressure - Circuit 1 | psi | Read | |
| AI | 1 | EntEvapWaterTemp | Evaporator Entering Fluid Temperature | °F | Read | |
| AI | 148 | EvapWaterFlowRate | Evaporator Fluid Flow Rate | GPM | Read | |
| AImin | 2 | LvgEvapWaterTempUnit | Evaporator Leaving Fluid Temperature | °F | Read | |
| AI | 141 | C1EvapRefPressure | Evaporator Refrigerant Pressure - Circuit 1 | psi | Read | |
| AI | 218 | C1LiqLineRefTemp | Liquid Line Refrigerant Temperature - Circuit 1 | °F | Read | |
| AV | 1 | ActiveCapacityLimit | Active Capacity Limit Output | % | Read | |
| AV | 5 | ActiveLvgWaterTarget | Active Setpoint | °F | Read | |
| AVmin | 2 | ChillerCapacity | Actual Capacity | % | Read | |
| AVmin | 905 | AVFaultAlarmCode | Alarm Code - Fault | Read | ||
| AV | 903 | AVWarningAlarmCode | Alarm Code - Warning | Read | ||
| AV | 901 | AVFaultAlarm | Alarm Index - Fault | Read | ||
| AV | 902 | AVWarningAlarm | Alarm Index - Warning | Read | ||
| AVmin | 3 | NetworkCapacityLimitPct | Capacity Limit Setpoint - Network | % | Write | |
| AV | 26 | C1Comp1DischSatRefTemp | Compressor Discharge Saturated Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AV | 27 | C1Comp2DischSatRefTemp | Compressor Discharge Saturated Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AV | 8 | C1Comp1MotorCurrentPercent | Compressor Percent RLA - Circuit 1 Compressor 1 | % | Read | |
| AV | 9 | C1Comp2MotorCurrentPercent | Compressor Percent RLA - Circuit 1 Compressor 2 | % | Read | |
| AV | 74 | C1Comp1Hours | Compressor Run Hours - Circuit 1 Compressor 1 | h | Read | |
| AV | 75 | C1Comp2Hours | Compressor Run Hours - Circuit 1 Compressor 2 | h | Read | |
| AV | 50 | C1Comp1SuctSatTemp | Compressor Suction Saturated Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AV | 51 | C1Comp2SuctSatTemp | Compressor Suction Saturated Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AV | 92 | C1Comp1Starts | Compressor Starts - Circuit 1 Compressor 1 | Read | ||
| AV | 93 | C1Comp2Starts | Compressor Starts - Circuit 1 Compressor 2 | Read | ||
| AV | 110 | CondPump1RunHours | Condenser Pump Run Hours - Condenser Pump 1 | h | Read | |
| AV | 111 | CondPump2RunHours | Condenser Pump Run Hours - Condenser Pump 2 | h | Read | |
| AV | 44 | Cond1SatRefTemp | Condenser Saturated Refrigerant Temperature - Circuit 1 | °F | Read | |
| AVmin | 4 | NetworkCoolTempSetpoint | Cool Setpoint - Network | °F | Write | |
| AV | 112 | EvapPump1OperHours | Evaporator Pump Run Hours - Evaporator Pump 1 | h | Read | |
| AV | 113 | EvapPump2OperHours | Evaporator Pump Run Hours - Evaporator Pump 2 | h | Read | |
| AV | 68 | C1EvapSatRefTemp | Evaporator Saturated Refrigerant Temperature - Circuit 1 | °F | Read | |
| BVmin | 2 | ChillerEnableStp | Chiller Enable Setpoint | Write | 0=Disable (Inactive), 1=Enable | |
| BVmin | 8 | ClearAlarm | Clear Alarm - Network | Write | 0=Normal, 1=Clear Alarm | |
| BI | 10 | AlarmDigitalOutput | Alarm Digital Output | Read | 0=No Alarm, 1=Alarm | |
| BI | 6 | ChillerLimited | Chiller Capacity Limited | Read | 0=Not Limited, 1=Limited | |
| BI | 7 | ChillerEnableOutput | Chiller Enable Output | Read | 0=Disable, 1=Enable | |
| BImin | 3 | ChillerLocalRemote | Chiller Local/Network | Read | 0=Network, 1=Local | |
| BI | 4 | UnitOnOff | Chiller On/Off | Read | 0=Chiller Off, 1=Chiller On | |
| BI | 163 | C1Cmp1Unavailable | Compressor Unavailable - Circuit 1 Compressor 1 | Read | 0=Available, 1=Unavailable | |
| BI | 164 | C2Cmp2Unavailable | Compressor Unavailable - Circuit 2 Compressor 2 | Read | 0=Available, 1=Unavailable | |
| BI | 1 | CondWaterFlowStatus | Condenser Flow Switch Status | Read | 0=No Flow, 1=Flow | |
| BI | 11 | CondPump1State | Condenser Pump 1 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 12 | CondPump2State | Condenser Pump 2 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 2 | EvapWaterFlowStatus | Evaporator Flow Switch Status | Read | 0=No Flow, 1=Flow | |
| BI | 8 | EvapPump1State | Evaporator Pump1 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 9 | EvapPump2State | Evaporator Pump2 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 5 | RunEnabled | Run Enabled | Read | 0=Off, 1=Run Allowed | |
| MV | 2 | ActiveMode | Chiller Mode Output | Read | 1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY | |
| MVmin | 3 | ChillerOperationMode | Chiller Mode Setpoint - Network | Write | 1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY | |
| MVmin | 1 | UnitStatus | Chiller Run Mode | Read | 1=OFF, 2=START, 3=RUN, 4=PRESHUTDOWN, 5=SERVICE | |
| MV | 4 | Units | Units | Write | 1=Metric, 2=English |
No points match these filters.
Integration notes
- Default device object name is Daikin_MicroTech_ followed by the device instance.
- Network enable, mode and setpoints are only used when the control source is set to BAS at the HMI.
- Only Cool mode applies to WME-C even though the mode objects list Ice, Heat and Heat Recovery.
- Units (MV 4) switches the values sent to BACnet between English and Metric; English is the default.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Magnitude WME C-vintage Chiller (MicroTech WME controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
How many BACnet points does the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) have?
This list has 68 BACnet objects: 23 analog inputs, 25 analog values, 14 binary inputs, 2 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet points are writable?
6 of the 68 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet documentation?
The source is MicroTech WME, C-vintage Chiller Unit Controller Protocol Information (ED 19111-1), revision 2020-05, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20WME%20Chiller%20Unit%20Controller%20Protocol%20Information%20-%20ED%2019111-1.pdf.
What are the minimum BACnet points to integrate the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)?
Start with BV 2 ChillerEnableStp (Network enable/disable of the chiller); MV 3 ChillerOperationMode (Ice / cool / heat / heat recovery mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitPct (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 ChillerLocalRemote (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); AV 2 ChillerCapacity (Actual capacity in percent); AV 905 AVFaultAlarmCode (Active fault alarm code).
How do I enable BMS control of the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)?
Control Source must be set to BAS at the unit HMI for the controller to use Network Enable (BV 2). For the cool setpoint, mode and capacity limit setpoints, Remote Enable must also be set to Enable at the HMI. Writing Enable to BV 2 only allows a start if other conditions are met.
How do I check these points on the real Magnitude WME C-vintage Chiller (MicroTech WME controller)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00
Source: MicroTech WME, C-vintage Chiller Unit Controller Protocol Information · ED 19111-1 · rev. 2020-05. Object names, instances and units are reproduced as published; descriptions are our own.