Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet points list

Updated 28 October 2026

Short answer

The MicroTech WME chiller unit controller on C-vintage Magnitude chillers supports BACnet MS/TP, BACnet IP and Modbus through its BAS communication module. The BACnet table is short and focused: water temperatures and flows, per-compressor current, power, voltage and refrigerant data for two compressors, alarm codes, run hours and starts, plus network enable, mode, cool setpoint and capacity limit.

This page lists 68 BACnet objects for the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
Magnitude WME C-vintage Chiller (MicroTech WME controller)
Equipment
Chiller controller
Equipment type
Chillers
BACnet objects
68 (6 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Chiller application 1.1.6, HMI 1.3.10 or later
Default device instance
9050
Also known as
WME-C, Magnitude WME, MicroTech WME, ED 19111
Source document
MicroTech WME, C-vintage Chiller Unit Controller Protocol Information · ED 19111-1 · rev. 2020-05
Download CSV 68 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)

Integration in brief

At the chiller HMI set Control Source to BAS (for the network enable) and Remote Enable to Enable (for setpoint, mode and capacity limit). The BMS then writes ChillerEnableStp, the cool setpoint and capacity limit, and reads status, water temperatures and alarm codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2ChillerEnableStpNetwork enable/disable of the chillerWrite
MV 3ChillerOperationModeIce / cool / heat / heat recovery mode commandWrite
AV 4NetworkCoolTempSetpointLeaving water cool setpoint from the BMSWrite
AV 3NetworkCapacityLimitPctCapacity limit from the BMSWrite
BV 8ClearAlarmClear alarms from the networkWrite
BI 3ChillerLocalRemoteShows whether network control is activeRead
MV 1UnitStatusChiller run stateRead
AI 2LvgEvapWaterTempUnitLeaving chilled water temperatureRead
AV 2ChillerCapacityActual capacity in percentRead
AV 905AVFaultAlarmCodeActive fault alarm codeRead

Enable & remote start

Control Source must be set to BAS at the unit HMI for the controller to use Network Enable (BV 2). For the cool setpoint, mode and capacity limit setpoints, Remote Enable must also be set to Enable at the HMI. Writing Enable to BV 2 only allows a start if other conditions are met.

Network setup

Watch out for

Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

68 of 68 shown
Type
Multi-state
Access
Show
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet Points List
DescriptionStates
AI9C1Comp1CurrentCompressor Current - Circuit 1 Compressor 1ARead
AI10C1Comp2CurrentCompressor Current - Circuit 1 Compressor 2ARead
AI63C1Comp1DischargeTempCompressor Discharge Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AI64C1Comp2DischargeTempCompressor Discharge Refrigerant Temperature - Circuit 1 Compressor 2°FRead
AI81C1Comp1DischRefPressureCompressor Discharge Refrigerant Pressure - Circuit 1 Compressor 1psiRead
AI82C1Comp2DischRefPressureCompressor Discharge Refrigerant Pressure - Circuit 1 Compressor 2psiRead
AI45C1Comp1KilowattsCompressor Power - Circuit 1 Compressor 1kWRead
AI46C1Comp2KilowattsCompressor Power - Circuit 1 Compressor 2kWRead
AI105C1Comp1SuctionTempCompressor Suction Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AI106C1Comp2SuctionTempCompressor Suction Refrigerant Temperature - Circuit 1 Compressor 2°FRead
AI123C1Comp1SuctionPressureCompressor Suction Refrigerant Pressure - Circuit 1 Compressor 1psiRead
AI124C1Comp2SuctionPressureCompressor Suction Refrigerant Pressure - Circuit 1 Compressor 2psiRead
AI27C1Comp1VoltageCompressor Voltage - Circuit 1 Compressor 1VRead
AI28C1Comp2VoltageCompressor Voltage - Circuit 1 Compressor 2VRead
AI3EntCondWaterTempCondenser Entering Fluid Temperature°FRead
AI147CondWaterFlowRateCondenser Fluid Flow RateGPMRead
AI4LvgCondWaterTempCondenser Leaving Fluid Temperature°FRead
AI99Cond1RefPressureCondenser Refrigerant Pressure - Circuit 1psiRead
AI1EntEvapWaterTempEvaporator Entering Fluid Temperature°FRead
AI148EvapWaterFlowRateEvaporator Fluid Flow RateGPMRead
AImin2LvgEvapWaterTempUnitEvaporator Leaving Fluid Temperature°FRead
AI141C1EvapRefPressureEvaporator Refrigerant Pressure - Circuit 1psiRead
AI218C1LiqLineRefTempLiquid Line Refrigerant Temperature - Circuit 1°FRead
AV1ActiveCapacityLimitActive Capacity Limit Output%Read
AV5ActiveLvgWaterTargetActive Setpoint°FRead
AVmin2ChillerCapacityActual Capacity%Read
AVmin905AVFaultAlarmCodeAlarm Code - FaultRead
AV903AVWarningAlarmCodeAlarm Code - WarningRead
AV901AVFaultAlarmAlarm Index - FaultRead
AV902AVWarningAlarmAlarm Index - WarningRead
AVmin3NetworkCapacityLimitPctCapacity Limit Setpoint - Network%Write
AV26C1Comp1DischSatRefTempCompressor Discharge Saturated Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AV27C1Comp2DischSatRefTempCompressor Discharge Saturated Refrigerant Temperature - Circuit 1 Compressor 2°FRead
AV8C1Comp1MotorCurrentPercentCompressor Percent RLA - Circuit 1 Compressor 1%Read
AV9C1Comp2MotorCurrentPercentCompressor Percent RLA - Circuit 1 Compressor 2%Read
AV74C1Comp1HoursCompressor Run Hours - Circuit 1 Compressor 1hRead
AV75C1Comp2HoursCompressor Run Hours - Circuit 1 Compressor 2hRead
AV50C1Comp1SuctSatTempCompressor Suction Saturated Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AV51C1Comp2SuctSatTempCompressor Suction Saturated Refrigerant Temperature - Circuit 1 Compressor 2°FRead
AV92C1Comp1StartsCompressor Starts - Circuit 1 Compressor 1Read
AV93C1Comp2StartsCompressor Starts - Circuit 1 Compressor 2Read
AV110CondPump1RunHoursCondenser Pump Run Hours - Condenser Pump 1hRead
AV111CondPump2RunHoursCondenser Pump Run Hours - Condenser Pump 2hRead
AV44Cond1SatRefTempCondenser Saturated Refrigerant Temperature - Circuit 1°FRead
AVmin4NetworkCoolTempSetpointCool Setpoint - Network°FWrite
AV112EvapPump1OperHoursEvaporator Pump Run Hours - Evaporator Pump 1hRead
AV113EvapPump2OperHoursEvaporator Pump Run Hours - Evaporator Pump 2hRead
AV68C1EvapSatRefTempEvaporator Saturated Refrigerant Temperature - Circuit 1°FRead
BVmin2ChillerEnableStpChiller Enable SetpointWrite0=Disable (Inactive), 1=Enable
BVmin8ClearAlarmClear Alarm - NetworkWrite0=Normal, 1=Clear Alarm
BI10AlarmDigitalOutputAlarm Digital OutputRead0=No Alarm, 1=Alarm
BI6ChillerLimitedChiller Capacity LimitedRead0=Not Limited, 1=Limited
BI7ChillerEnableOutputChiller Enable OutputRead0=Disable, 1=Enable
BImin3ChillerLocalRemoteChiller Local/NetworkRead0=Network, 1=Local
BI4UnitOnOffChiller On/OffRead0=Chiller Off, 1=Chiller On
BI163C1Cmp1UnavailableCompressor Unavailable - Circuit 1 Compressor 1Read0=Available, 1=Unavailable
BI164C2Cmp2UnavailableCompressor Unavailable - Circuit 2 Compressor 2Read0=Available, 1=Unavailable
BI1CondWaterFlowStatusCondenser Flow Switch StatusRead0=No Flow, 1=Flow
BI11CondPump1StateCondenser Pump 1 StatusRead0=Pump Off Request, 1=Pump On Request
BI12CondPump2StateCondenser Pump 2 StatusRead0=Pump Off Request, 1=Pump On Request
BI2EvapWaterFlowStatusEvaporator Flow Switch StatusRead0=No Flow, 1=Flow
BI8EvapPump1StateEvaporator Pump1 StatusRead0=Pump Off Request, 1=Pump On Request
BI9EvapPump2StateEvaporator Pump2 StatusRead0=Pump Off Request, 1=Pump On Request
BI5RunEnabledRun EnabledRead0=Off, 1=Run Allowed
MV2ActiveModeChiller Mode OutputRead1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY
MVmin3ChillerOperationModeChiller Mode Setpoint - NetworkWrite1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY
MVmin1UnitStatusChiller Run ModeRead1=OFF, 2=START, 3=RUN, 4=PRESHUTDOWN, 5=SERVICE
MV4UnitsUnitsWrite1=Metric, 2=English

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Magnitude WME C-vintage Chiller (MicroTech WME controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)

How many BACnet points does the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) have?

This list has 68 BACnet objects: 23 analog inputs, 25 analog values, 14 binary inputs, 2 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet points are writable?

6 of the 68 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller) BACnet documentation?

The source is MicroTech WME, C-vintage Chiller Unit Controller Protocol Information (ED 19111-1), revision 2020-05, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20WME%20Chiller%20Unit%20Controller%20Protocol%20Information%20-%20ED%2019111-1.pdf.

What are the minimum BACnet points to integrate the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)?

Start with BV 2 ChillerEnableStp (Network enable/disable of the chiller); MV 3 ChillerOperationMode (Ice / cool / heat / heat recovery mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitPct (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 ChillerLocalRemote (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); AV 2 ChillerCapacity (Actual capacity in percent); AV 905 AVFaultAlarmCode (Active fault alarm code).

How do I enable BMS control of the Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)?

Control Source must be set to BAS at the unit HMI for the controller to use Network Enable (BV 2). For the cool setpoint, mode and capacity limit setpoints, Remote Enable must also be set to Enable at the HMI. Writing Enable to BV 2 only allows a start if other conditions are met.

How do I check these points on the real Magnitude WME C-vintage Chiller (MicroTech WME controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.