  3. Daikin Applied
  4. EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)

Air-cooled screw chiller controller · BACnet points list

Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe) BACnet points list

Updated 28 October 2026

Short answer

The EWAD/EWAH and EWFD/EWFH -T/MZD air-cooled chillers use a MicroTech 4 controller running the "ETRA / OMEGA" software. BACnet IP or BACnet MS/TP comes from a POL908/POL904 module or the onboard software option. The list covers unit enable, mode and network setpoints, heat recovery, free cooling, variable primary flow, per-circuit refrigerant data for two circuits with one compressor each, energy monitoring, a shunt active filter and alarm objects.

This page lists 210 BACnet objects for the Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Equipment
Air-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
210 (23 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1
Also known as
EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01
Source document
BAS Integration guide - BACnet protocol (EWAD/H-T/MZD & EWFD/H-T/MZD) · D-EIGOC00103-23_01EN · rev. 2023-12
Download CSV 210 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)

Integration in brief

Select network control at the unit (CtrlSource BI 3 then reads Network), enable the chiller with UnitEnableStp, and write the mode, cool setpoint and capacity limit. Monitor unit status, leaving water temperature, AlarmOutput and the fault index/code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2UnitEnableStpNetwork enable/disable of the chillerWrite
MV 3UnitModeSetpointNetworkIce / cool / heat mode commandWrite
AV 4NetworkCoolTempSetpointLeaving water cool setpoint from the BMSWrite
AV 3NetworkCapacityLimitSetpointCapacity limit from the BMSWrite
BV 8ClearAlarmClear alarms from the networkWrite
BI 3CtrlSourceShows whether network control is activeRead
MV 1UnitStatusChiller run stateRead
AI 2EvapLvgWTempLeaving chilled water temperatureRead
BI 10AlarmOutputAny active alarmRead
AV 905AVFaultAlarmCodeActive fault alarm codeRead

Enable & remote start

CtrlSource (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes UnitEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.

Sensors & values from the BMS

VarFlow'LoadDPres (AI 1905, plant differential pressure) is marked writable for variable primary flow; the guide does not say whether the BMS must supply it.

Network setup

Watch out for

Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

210 of 210 shown
Type
Multi-state
Access
Show
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe) BACnet Points List
DescriptionStates
BImin3CtrlSourceUnit - Control SourceRead0=Network, 1=Local
BI7EnableOutputUnit - Enabled StateRead0=Disabled, 1=Enabled
BI5RunEnabledUnit - Run AllowedRead0=Off, 1=Allowed
BI6UnitLimitedUnit - Capacity LimitedRead0=NotLimited, 1=Limited
BImin10AlarmOutputUnit - Alarm OutputRead0=NoAlarm, 1=Alarm
BI2EvapWFlowStateEvaporator - Water Flow StateRead0=NoFlow, 1=Flow
BI4UnitOnOffUnit - Operating StateRead0=ThermoOff, 1=ThermoOn
BVmin2UnitEnableStpUnit - Enable SetpointWrite0=Disable, 1=Enable
BVmin8ClearAlarmUnit - Alarm Reset SetpointWrite0=None, 1=Clear
MV2ActModeUnit - Active Operation ModeRead1=Ice, 2=Cool, 3=Heat
AV5ActTempStpUnit - Active Temperature Setpoint°CRead
AV2ActCapacityUnit - Actual Capacity%Read
AV1ActCapacityLimUnit - Active Capacity Limit%Read
MVmin1UnitStatusUnit - StatusRead1=Off, 2=Start, 3=Run, 4=PreShutdown, 5=Service
AI1EvapEntWTempEvaporator Entering Water Temperature°CRead
AImin2EvapLvgWTempEvaporator Leaving Water Temperature°CRead
BV7HeatRec'EnableStpHeat Recovery - Enable SetpointWrite0=Disable, 1=Enable
AI177HeatRec'EntWTempHeat Recovery - Entering Water Temperature°CRead
AI150HeatRec'LvgWTempHeat Recovery - Leaving Water Temperature°CRead
AI5OutdoorAirTempOutside Air Temperature°CRead
AI993AvgCurrentUnit - Average CurrentARead
AV992AvgVoltageUnit - Average VoltageVRead
AV994ActPowerUnit - Active PowerkWRead
AV902AVWarningAlarmUnit Alarm - Warning IndexRead
AV900AVProblemAlarmUnit Alarm - Problem IndexRead
AV901AVFaultAlarmUnit Alarm - Fault IndexRead
AV903AVWarningAlarmCodeUnit Alarm - Warning CodeRead
AV904AVProblemAlarmCodeUnit Alarm - Problem CodeRead
AVmin905AVFaultAlarmCodeUnit Alarm - Fault CodeRead
MVmin3UnitModeSetpointNetworkUnit - Operation Mode SetpointWrite0=NULL, 1=Ice, 2=Cool, 3=Heat
AVmin4NetworkCoolTempSetpointUnit - Cool Temperature Setpoint°CWrite
AV7NetworkIceTempSetpointUnit - Ice Temperature Setpoint°CWrite
AV6NetworkHeatTempSetpointUnit - Heat Temperature Setpoint°CWrite
AVmin3NetworkCapacityLimitSetpointUnit - Capacity Limit Setpoint%Write
AI99C1'CondRefPressureCircuit 1 - Condenser Refrigerant PressurekPaRead
AV34C1'CondSatRefTempCircuit 1 - Condeser Saturated Temperature°CRead
AI141C1'EvapRefPressureCircuit 1 - Evaporator Refrigerant PressurekPaRead
AV68C1'EvapSatRefTempCircuit 1 - Evaporator Saturated Temperature°CRead
AI100C2'CondRefPressureCircuit 2 - Condenser Refrigerant PressurekPaRead
AV35C2'CondSatRefTempCircuit 2 - Condeser Saturated Temperature°CRead
AI142C2'EvapRefPressureCircuit 2 - Evaporator Refrigerant PressurekPaRead
AV69C2'EvapSatRefTempCircuit 2 - Evaporator Saturated Temperature°CRead
MV51C1'ShutdownAlmCircuit 1 - Shutdown AlarmRead1=NoAlarm, 2=Alarm
MV52C2'ShutdownAlmCircuit 2 - Shutdown AlarmRead1=NoAlarm, 2=Alarm
MV54U'ShutAlmUnit - Shutdown AlarmRead1=NoAlarm, 2=Alarm
AV49NetworkHeatRecSetpointHeat Recovery - Temperature Setpoint°CWrite
MV42HeatRec'StateHeat Recovery - Operating StateRead1=Off, 2=Recirculation, 3=Regulation
AI105C1'Comp1'SuctTempCirc 1 Compressor 1 - Suction Temperature°CRead
AI63C1'Comp1'DischTempCirc 1 Compressor 1 - Discharge Temperature°CRead
AV8C1'Comp1'RLAPercentCirc 1 Compressor 1 - RLA Percentage%Read
AI9C1'Comp1'CurrentCirc 1 Compressor 1 - CurrentARead
AV45C1'Comp1'PowerCirc 1 Compressor 1 - PowerkWRead
AV92C1'Comp1'StartsCirc 1 Compressor 1 - Number of StartsWrite
AV74C1'Comp1'RunHoursCirc 1 Compressor 1 - Number of Running HourshWrite
AI108C2'Comp1'SuctTempCirc 2 Compressor 1 - Suction Temperature°CRead
AI66C2'Comp1'DischTempCirc 2 Compressor 1 - Discharge Temperature°CRead
AV11C2'Comp1'RLAPercentCirc 2 Compressor 1 - RLA Percentage%Read
AI12C2'Comp1'CurrentCirc 2 Compressor 1 - CurrentARead
AV48C2'Comp1'PowerCirc 2 Compressor 1 - PowerkWRead
AV95C2'Comp1'StartsCirc 2 Compressor 1 - Number of StartsWrite
AV77C2'Comp1'HoursCirc 2 Compressor 1 - Number of Running HourshWrite
BV28Freecool'EnableStpFreecooling - Enable SetpointWrite0=Disable, 1=Enable
MV31Freecool'StatusFreecooling - StatusRead1=Unit Off, 2=FC Full, 3=FC Mix, 4=Mech
MV32Freecool'EnabledFreeccoling - Enabled StateRead1=No, 2=Yes
BV258AntivacStaAntiVacuum Protection StateRead0=No, 1=Yes
AV260ThermCapacityPerformance - Unit Thermal CapacitykWRead
AV262ElectPowerPerformance - Unit Power InputkWRead
AV264EERPerformance - Unit EfficiencyRead
AV265integralEERPerformance - Unit Integrated EfficiencyRead
AV261ThermEnergyPerformance - Unit Thermal EnergyMWhRead
AV263ElectEnergyPerformance - Unit Electrical EnergyMWhRead
AV273FreecoolThermCapPerformance - Freecooling Thermal CapacitykWRead
AV275MechThermCapPerformance - Mechanical Thermal CapacitykWRead
AV277FreecoolCapPercPerformance - Percentage of Freecooling Capacity%Read
AV296EvapPump'SpeedEvaporator Pump - Speed%Read
AV112EvapPump1'RunHoursEvaporator Pump 1 - Number of Running HoursRead
BI8EvapPump1'StateEvaporator Pump 1 - Operating StateRead0=Stop, 1=Run
AV113EvapPump2'RunHoursEvaporator Pump 2 - Number of Running HoursRead
BI9EvapPump2'StateEvaporator Pump 2 - Operating StateRead0=Stop, 1=Run
AV310EvapPump'ElectPwrEvaporator Pump - Electrical PowerkWRead
AV312EvapDifPresEvaporator Differential PressurekPaRead
AV314EvaporatorEstWaterFlowEvaporator Estimated Water Flowkg/sRead
AV322EvapPump'ElectSpdRpmEvaporator Pump - Speed RPMrpmRead
MV4UnitsUnit - BACnet Measurement unit setpointWrite1=Metric, 2=English
MV317UnitModelUnit - ModelRead1=Centrifugal, 2=Water Cooled, 3=Air Cooled, 4=HeatPump, 5=Reserved, 6=Reserved, 7=Reserved, 8=Reserved, 9=Other
MV318SafetyModeSetpointUnit - Safety Mode SetpointRead0=Off, 1=On
MV319SafetyModeStateUnit - Safety Mode StateRead0=Off, 1=On
BV917Unit'OFFEvapEntWTempFailUnit Alarm - Evaporator Entering Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV512BadSetpointResetInputUnit Warning - Setpoint Reset Input Out of RangeRead0=NoAlarm, 1=Alarm
BV513BadDemandLimitInputUnit Warning - Demand Limit Input Out of RangeRead0=NoAlarm, 1=Alarm
BV529C1'InhibitPwrLossCircuit 1 Warning - Power Loss while Compressor RunningRead0=NoAlarm, 1=Alarm
BV530C2'InhibitPwrLossCircuit 2 Warning - Power Loss while Compressor RunningRead0=NoAlarm, 1=Alarm
BV533Unit'InhibitOATLowUnit Warning - Inhibition for Low Ambient TemperatureRead0=NoAlarm, 1=Alarm
BV575EvapPump1'FaultEvaporator Pump 1 - FaultRead0=NoAlarm, 1=Alarm
BV576EvapPump2'FaultEvaporator Pump 2 - FaultRead0=NoAlarm, 1=Alarm
BV599C1'Comp1'OFFPresRatioLowCirc 1 Comp 1 Alarm - Low Pressure RatioRead0=NoAlarm, 1=Alarm
BV601C2'Comp1'OFFPresRatioLowCirc 2 Comp 1 Alarm - Low Pressure RatioRead0=NoAlarm, 1=Alarm
BV605Unit'OFFOATempSenFailUnit Alarm - Outside Air Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV606C1'Comp1'OFFCurrentHiCirc 1 Comp 1 Alarm - High Motor CurrentRead0=NoAlarm, 1=Alarm
BV608C2'Comp1'OFFCurrentHiCirc 2 Comp 1 Alarm - High Motor CurrentRead0=NoAlarm, 1=Alarm
BV637C1'Comp1'OFFMotorTempHiCirc 1 Comp 1 Alarm - High Motor TemperatureRead0=NoAlarm, 1=Alarm
BV639C2'Comp1'OFFMotorTempHiCirc 2 Comp 1 Alarm - High Motor TemperatureRead0=NoAlarm, 1=Alarm
BV668C1'OFFCondPresFailCircuit 1 Alarm - Condenser Pressure Sensor FaultRead0=NoAlarm, 1=Alarm
BV670C2'OFFCondPresFailCircuit 2 Alarm - Condenser Pressure Sensor FaultRead0=NoAlarm, 1=Alarm
BV676C1'OFFCondPresHiCircuit 1 Alarm - Condenser High PressureRead0=NoAlarm, 1=Alarm
BV678C2'OFFCondPresHiCircuit 2 Alarm - Condenser High PressureRead0=NoAlarm, 1=Alarm
BV688C1'OFFDischTempFailCircuit 1 Alarm - Discharge Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV690C2'OFFDischTempFailCircuit 2 Alarm - Discharge Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV694C1'Comp1'OFFDischTempHiCirc 1 Comp 1 Alarm - High Discharge TemperatureRead0=NoAlarm, 1=Alarm
BV696C2'Comp1'OFFDischTempHiCirc 2 Comp 1 Alarm - High Discharge TemperatureRead0=NoAlarm, 1=Alarm
BV701Unit'OFFEvapFlowLossUnit Alarm - Evaporator Water Flow LossRead0=NoAlarm, 1=Alarm
BV702Unit'OFFEvapLvgWTempLowUnit Alarm - Evaporator Water FreezeRead0=NoAlarm, 1=Alarm
BV704C1'OFFEvapPresLowCircuit 1 Alarm - Evaporator Pressure LowRead0=NoAlarm, 1=Alarm
BV706C2'OFFEvapPresLowCircuit 2 Alarm - Evaporator Pressure LowRead0=NoAlarm, 1=Alarm
BV711C1'OFFEvapPresFailCircuit 1 Alarm - Evaporator Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV713C2'OFFEvapPresFailCircuit 2 Alarm - Evaporator Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV742C1'OFFRestartsAlmCircuit 1 Alarm - Too many restartRead0=NoAlarm, 1=Alarm
BV744C2'OFFRestartsAlmCircuit 2 Alarm - Too many restartRead0=NoAlarm, 1=Alarm
BV748Unit'OFFEvapLvgWTempFailUnit Alarm - Evaporator Leaving Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV760C1'OFFMechPressHiCircuit 1 Alarm - Mechanical High PressureRead0=NoAlarm, 1=Alarm
BV762C2'OFFMechPressHiCircuit 2 Alarm - Mechanical High PressureRead0=NoAlarm, 1=Alarm
BV796C1'OFFOilFilterPresHiCircuit 1 Alarm - Oil Filter High PressureRead0=NoAlarm, 1=Alarm
BV798C2'OFFOilFilterPresHiCircuit 2 Alarm - Oil Filter High PressureRead0=NoAlarm, 1=Alarm
BV802C1'OFFOilPresFailCircuit 1 Alarm - Oil Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV804C2'OFFOilPresFailCircuit 2 Alarm - Oil Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV820Unit'OFFPhaseVoltageUnit Alarm - Phase VoltageRead0=NoAlarm, 1=Alarm
BV978C1'OFFOverVoltageCircuit 1 Alarm - OverVoltageRead0=NoAlarm, 1=Alarm
BV982C2'OFFOverVoltageCircuit 2 Alarm - OverVoltageRead0=NoAlarm, 1=Alarm
BV979C1'OFFUnderVoltageCircuit 1 Alarm - UnderVoltageRead0=NoAlarm, 1=Alarm
BV981C2'OFFUnderVoltageCircuit 2 Alarm - UnderVoltageRead0=NoAlarm, 1=Alarm
BV857C1'Comp1'OFFSuctTempFailCirc 1 Comp 1 Alarm - Suction Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV859C2'Comp1'OFFSuctTempSenCirc 2 Comp 1 Alarm - Suction Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV911C1'OFFNoPressStartCircuit 1 Alarm - No Pressure at StartRead0=NoAlarm, 1=Alarm
BV912C2'OFFNoPressStartCircuit 2 Alarm - No Pressure at StartRead0=NoAlarm, 1=Alarm
BV723C1'OFFBoardOfflineController Alarm - Circuit 1 Board OfflineRead0=NoAlarm, 1=Alarm
BV724C2'OFFBoardOfflineController Alarm - Circuit 2 Board OfflineRead0=NoAlarm, 1=Alarm
BV515Unit'PowerRestoreUnit - Power RestoreRead0=NoAlarm, 1=Alarm
BV516C1'FailPumpdownCircuit 1 Alarm - Pumpdown FailureRead0=NoAlarm, 1=Alarm
BV517C2'FailPumpdownCircuit 2 Alarm - Pumpdown FailureRead0=NoAlarm, 1=Alarm
BV924Unit'ExternalEventUnit Alarm - External EventRead0=NoAlarm, 1=Alarm
BV925Unit'OFFBoardOfflineController Alarm - Unit Board OfflineRead0=NoAlarm, 1=Alarm
BV905C1'OFFNoPresChgAtStartCircuit 1 Alarm - No Pressure change at StartRead0=NoAlarm, 1=Alarm
BV906C2'OFFNoPresChgAtStartCircuit 2 Alarm - No Pressure change at StartRead0=NoAlarm, 1=Alarm
BVC1'Comp1'OFFVfdFaultCirc 1 Compr 1 Alarm - VFD Fault (guide repeats instance 762)Read0=NoAlarm, 1=Alarm
BV888C2'Comp1'OFFVfdFaultCirc 2 Compr 1 Alarm - VFD FaultRead0=NoAlarm, 1=Alarm
BV942C1'Comp1'OFFVfdTempHiCirc 1 Compr 1 Alarm - VFD High TemperatureRead0=NoAlarm, 1=Alarm
BV944C2'Comp1'OFFVfdTempHiCirc 2 Compr 1 Alarm - VFD High TemperatureRead0=NoAlarm, 1=Alarm
BV948C1'Comp1'OFFVfdCommFailCirc 1 Compr 1 Alarm - VFD Communication FailureRead0=NoAlarm, 1=Alarm
BV950C2'Comp1'OFFVfdCommFailCirc 2 Compr 1 Alarm - VFD Communication FailureRead0=NoAlarm, 1=Alarm
BV921EmergencyStopAlarmUnit Alarm - Emergency Stop SwitchRead0=NoAlarm, 1=Alarm
BV922EvapWTempInvertedUnit Alarm - Evaporator Temperature Sensors InvertedRead0=NoAlarm, 1=Alarm
BV923Unit'OFFExternalAlarmUnit Alarm - External AlarmRead0=NoAlarm, 1=Alarm
BV961C1'Comp1'DischSHeatLowCirc 1 Compr 1 Problem - Low Discharge SuperheatRead0=NoAlarm, 1=Alarm
BV963C2'Comp1'DischSHeatLowCirc 2 Compr 1 Problem - Low Discharge SuperheatRead0=NoAlarm, 1=Alarm
BV918BadCurrentLimitInputUnit Warning - Curennt Limit Input Out Of RangeRead0=NoAlarm, 1=Alarm
BV919Unit'OFFOptBoardOfflineController Alarm - Option Board OfflineRead0=NoAlarm, 1=Alarm
BV844C1'OFFGasLeakageCircuit 1 Alarm - Gas LeakageRead0=NoAlarm, 1=Alarm
BV845C2'OFFGasLeakageCircuit 2 Alarm - Gas LeakageRead0=NoAlarm, 1=Alarm
AI187SwitchBoxTempUnit - Electrical Panel Temperature°CRead
BV983Unit'SwitchBoxSensFaultUnit Warning - Electrical Panel Temp Sensor FaultRead0=NoAlarm, 1=Alarm
BV984Unit'SwitchBoxTempHighUnit Warning - Electrical Panel High TemperatureRead0=NoAlarm, 1=Alarm
BV837Unit'OFFFanBoardOfflineController Alarm - Fan Board OfflineRead0=NoAlarm, 1=Alarm
BV838C1'FanAlmCircuit 1 Alarm - Fan FaultRead0=NoAlarm, 1=Alarm
BV839C2'FanAlmCircuit 2 Alarm - Fan FaultRead0=NoAlarm, 1=Alarm
AV951SAFGridVoltageShunt Active Filter – Grid VoltageVRead
AV952SAFGridActivePowerShunt Active Filter – Grid Active PowerkWRead
AV953SAFGridPowerFactorShunt Active Filter – Grid Power FactorRead
AV954SAFGridTDDiShunt Active Filter – Grid TDDi%Read
AV1800C2'Comp1'ActCapacityCirc 2 Compressor 1 - Actual Capacity%Read
MV440C2'Comp1'OffAutoStpCirc 2 Compressor 1 - OffAuto SetpointWrite1=Off, 2=Auto
BV1802C2'Comp1'FullLoadStaCirc 2 Compressor 1 - Full Load StateRead0=Normal, 1=Full Load
AV148C2'Comp1'VfdOutputCirc 2 Compressor 1 - VFD OutputrpmRead
BV1806C2'Comp1'AlarmCirc 2 Compressor 1 - Alarm ActiveRead0=NoAlarm, 1=Alarm
AI166C2'Comp1'OilFeedPressCirc 2 Compressor 1 - Oil Feed PressurekPaRead
BV441C2'Comp1'StateCirc 2 Compressor 1 - Operating StateRead0=Stop, 1=Run
AV1840C1'Comp1'ActCapacityCirc 1 Compressor 1 - Actual Capacity%Read
MV430C1'Comp1'OffAutoStpCirc 1 Compressor 1 - OffAuto SetpointWrite1=Off, 2=Auto
BV1842C1'Comp1'FullLoadStaCirc 1 Compressor 1 - Full Load StateRead0=Normal, 1=Full Load
AV1845C1'Comp1'ActSpeedCirc 1 Compressor 1 - VFD OutputrpmRead
BV1846C1'Comp1'AlarmCirc 1 Compressor 1 - Alarm ActiveRead0=NoAlarm, 1=Alarm
AI165C1'Comp1'OilFeedPressCirc 1 Compressor 1 - Oil Feed PressurekPaRead
BV431C1'Comp1'StateCirc 1 Compressor 1 - Operating StateRead0=Stop, 1=Run
MV1854RefrigTypeUnit - Refrigerant typeRead1=R22, 2=R134a, 3=R407c, 4=R410a, 5=R1234ze, 5=resv3
AV1855NrCircuitsUnit - Number of CircuitsRead
AV1856NrCompressorsUnit - Number of CompressorsRead
AV1896C2'EvapSuperheatStpValCircuit 2 - Evaporator Superheat Active SetpointdKRead
AV1897C1'EvapSuperheatStpValCircuit 1 - Evaporator Superheat Active SetpointdKRead
AV1898C2'EvapSuperheatCircuit 2 - Evaporator Superheat TemperaturedKRead
AV1899C1'EvapSuperheatCircuit 1 - Evaporator Superheat TemperaturedKRead
AV990ActEnergyUnit - Active EnergykWhRead
AV991PowerFactorUnit - Power FactorRead
AV995NetworkCurrentLimitSetpointUnit - Current Limit SetpointAWrite
AI1905VarFlow'LoadDPresVariable Flow - Plant Differential PressurekPaWrite
MV1906VarFlow'WBypVlvStaVaribale Flow - Water Bypass Valve StateRead1=Closed, 2=Opened
AV1909VarFlow'LoadDPresStptVaribale Flow - Plant Differential Pressure setpointkPaWrite
AV1911VarFlow'DeltaTempVariable Flow - Plant Delta TemperaturedKRead
AV1913VarFlow'DeltaTempStpVariable Flow - Plant Delta Temperature SetpointdKWrite
AV1915VarFlow'FixSpeedStpVariable Flow - Fixed Speed 1 Setpoint%Write
AV208C2'ExpValvePosCircuit 2 - Expansion Valve Position%Read
AV209C2'FanSpeedCircuit 2 - Fan Speed%Read
AV210C2'CondApproachCircuit 2 - Condenser Approach TemperaturedKRead
AV211C2'EvapApproachCircuit 2 - Evaporator Approach TemperaturedKRead
AV1997C2'FanStatusCircuit 2 - Fan StagingRead1=Off, 2=Run
AV168C1'ExpValvePosCircuit 1 - Expansion Valve Position%Read
AV169C1'FanSpeedCircuit 1 - Fan Speed%Read
AV170C1'CondApproachCircuit 1 - Condenser Approach TemperaturedKRead
AV171C1'EvapApproachCircuit 1 - Evaporator Approach TemperaturedKRead
AVC1'FanStatusCircuit 1 - Fan Staging (guide repeats instance 1997)Read1=Off, 2=Run
BV1998NoiseReductEnableSetpointNoise Reduction - Enable SetpointWrite0=Auto, 1=Reducing
BV2000NoiseReductStateNoise Reduction - Operating StateRead0=Normal, 1=Reduced

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)

How many BACnet points does the Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe) have?

This list has 210 BACnet objects: 20 analog inputs, 75 analog values, 9 binary inputs, 89 binary values, 17 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe) BACnet points are writable?

23 of the 210 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe) BACnet documentation?

The source is BAS Integration guide - BACnet protocol (EWAD/H-T/MZD & EWFD/H-T/MZD) (D-EIGOC00103-23_01EN), revision 2023-12, published free by Daikin Applied at https://www.daikin.co.uk/content/dam/document-library/installation-manuals/EWAD-(M.T)ZD.EWAH-(M.T)ZD.EWFD-(M.T)ZD.EWFH-(M.T)ZD_BAS%20Integration%20Guide%20BACnet_D-EIGOC00103-23_01_English.pdf.

What are the minimum BACnet points to integrate the Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)?

Start with BV 2 UnitEnableStp (Network enable/disable of the chiller); MV 3 UnitModeSetpointNetwork (Ice / cool / heat mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitSetpoint (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 CtrlSource (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 EvapLvgWTemp (Leaving chilled water temperature); BI 10 AlarmOutput (Any active alarm); AV 905 AVFaultAlarmCode (Active fault alarm code).

How do I enable BMS control of the Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)?

CtrlSource (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes UnitEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.

Can the BMS supply sensor values to the Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)?

VarFlow'LoadDPres (AI 1905, plant differential pressure) is marked writable for variable primary flow; the guide does not say whether the BMS must supply it.

How do I check these points on the real EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.