The MicroTech chiller unit controller exposes a shared BACnet object list across several Daikin Applied chiller families when fitted with the BACnet MS/TP or BACnet IP communication module. The table covers analog inputs, analog values, binary inputs, binary values and multi-state values, with network setpoints (cool, ice, capacity limit, enable, mode) commandable at any priority. Many per-compressor and per-circuit points only exist on certain models, and several alarm points are repeated as separate objects to support intrinsic alarming.

This page lists 433 BACnet objects for the Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator) — 128 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Equipment
Chiller controller
Equipment type
Chillers
BACnet objects
433 (128 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120
Source document
MicroTech Chiller Unit Controller Protocol Information · ED 15120-11 · rev. 2023-10
Download CSV 433 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)

Integration in brief

Set Chiller Local/Network to Network at the unit keypad, then enable the chiller with ChillerEnableStp and write the cool setpoint, mode and capacity limit as needed. Read unit status, leaving water temperature, capacity and the alarm code objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2ChillerEnableStpNetwork enable/disable of the chillerCommand
MV 3ChillerOperationModeIce / cool / heat / heat recovery mode commandCommand
AV 4NetworkCoolTempSetpointLeaving water cool setpoint from the BMSCommand
AV 3NetworkCapacityLimitPctCapacity limit from the BMSCommand
BV 8ClearAlarmClear alarms from the networkCommand
BI 3ChillerLocalRemoteShows whether network control is activeRead
MV 1UnitStatusChiller run stateRead
AI 2LvgEvapWaterTempUnitLeaving chilled water temperatureRead
AV 2ChillerCapacityActual capacity in percentRead
AV 905AVFaultAlarmCodeActive fault alarm codeRead

Enable & remote start

Chiller Local/Network must be set to Network at the unit keypad (it cannot be changed over the network). The BMS then writes ChillerEnableStp (BV 2) = Enable; this only permits the chiller to run when other conditions are satisfied, it does not force a start.

Heartbeat & communication loss

The guide's communication parameter table lists Receive Heartbeat as N/A for BACnet IP and MS/TP; the heartbeat (nciRcvHrtBt) only applies to LonWorks.

Network setup

Watch out for

Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

433 of 433 shown
Type
Multi-stateOther
Access
Show
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator) BACnet Points List
DescriptionStates
AI6ChillerCurrentChiller CurrentARead
AI224C1SuctionTemperatureCircuit 1 Suction Refrigerant Temperature°FRead
AI9C1Comp1CurrentCompressor CurrentARead
AI181C1Co1CurrentUnlCompressor Current - Circuit 1 Compressor 1ARead
AI184C1Co1CurrentHoldCompressor CurrentARead
AI10C1Comp2CurrentCompressor Current - Circuit 1 Compressor 2ARead
AI12C2Comp1CurrentCompressor CurrentARead
AI182C2Co1CurrentUnlCompressor Current - Circuit 2 Compressor 1ARead
AI185C2Co1CurrentHoldCompressor CurrentARead
AI15C3Comp1CurrentCompressor CurrentARead
AI183C3Co1CurrentUnlCompressor Current - Circuit 3 Compressor 1ARead
AI186C3Co1CurrentHoldCompressor CurrentARead
AI63C1Comp1DischargeTempCompressor Discharge Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AI64C1Comp2DischargeTempCompressor Discharge Refrigerant Temperature - Circuit 1, Compressor 2°FRead
AI66C2Comp1DischargeTempCompressor Discharge Refrigerant Temperature - Circuit 2 Compressor 1°FRead
AI69C3Comp1DischargeTempCompressor Discharge Refrigerant Temperature - Circuit 3 Compressor 1°FRead
AI72C4Comp1DischargeTempCompressor Discharge Refrigerant Temperature - Circuit 4 Compressor 1°FRead
AI217C1Comp1MotorCurrentPercentCompressor Percent RLA - Circuit 1 Compressor 1%Read
AI286C1Comp2MotorCurrentPercentCompressor Percent RLA - Circuit 1 Compressor 2%Read
AI45C1Comp11KilowattsCompressor Power - Circuit 1 Compressor 1kWRead
AI46C1Comp2KilowattsCompressor Power - Circuit 1 Compressor 2kWRead
AI48C2Comp11KilowattsCompressor Power - Circuit 2 Compressor 1kWRead
AI51C3Comp11KilowattsCompressor Power - Circuit 3 Compressor 1kWRead
AI274C1Comp2MotorGapTempCompressor Motor Case Temperature - Compressor 1 Motor°FRead
AI275C1Comp1MotorCaseTempCompressor Motor Case Temperature - Compressor 2 Motor°FRead
AI268C1Comp1MotorGapTempCompressor Motor Gap Temperature - Compressor 1 Motor°FRead
AI269C1Comp2MotorGapTempCompressor Motor Gap Temperature - Compressor 2 Motor°FRead
AI280C1Comp1RotorPumpTempCompressor Rotor - Compressor 1 Rotor°FRead
AI281C1Comp2RotorPumpTempCompressor Rotor - Compressor 2 Rotor°FRead
AI250C1Comp1StatorTemp1Compressor Stator Temperature - Compressor 1 Stator°FRead
AI251C1Comp2StatorTemp1Compressor Stator Temperature - Compressor 2 Stator°FRead
AI256C1Comp1StatorTemp2Compressor Stator Temperature - Compressor 1 Stator°FRead
AI257C1Comp2StatorTemp2Compressor Stator Temperature - Compressor 2 Stator°FRead
AI262C1Comp1StatorTemp3Compressor Stator Temperature - Compressor 1 Stator Temperature 3°FRead
AI263C1Comp2StatorTemp3Compressor Stator Temperature - Compressor 2 Stator°FRead
AI105C1Comp1SuctionTempCompressor Suction Refrigerant Temperature - Circuit 1 Compressor 1°FRead
AI106C1Comp2SuctionTempCompressor Suction Refrigerant Temperature - Circuit 1 Compressor 2°FRead
AI108C2Comp1SuctionTempCompressor Suction Refrigerant Temperature - Circuit 2 Compressor 1°FRead
AI111C3Comp1SuctionTempCompressor Suction Refrigerant Temperature - Circuit 3 Compressor 1°FRead
AI114C4Comp1SuctionTempCompressor Suction Refrigerant Temperature - Circuit 4 Compressor 1°FRead
AI27C1Comp1VoltageCompressor Voltage - Circuit 1 Compressor 1VRead
AI28C1Comp2VoltageCompressor Voltage - Circuit 1 Compressor 2VRead
AI30C2Comp1VoltageCompressor Voltage - Circuit 2 Compressor 1VRead
AI33C3Comp1VoltageCompressor Voltage - Circuit 3 Compressor 1VRead
AI3EntCondWaterTempCondenser Entering Fluid Temperature°FRead
AI147CondWaterFlowRateCondenser Fluid Flow RateGPMRead
AI4LvgCondWaterTempCondenser Leaving Fluid Temperature°FRead
AI99Cond1RefPressureCondenser Refrigerant PressurepsiRead
AI157Cond1RefPressureInhLoadCondenser Refrigerant Pressure - Condenser 1psiRead
AI161Cond1RefPressureUnloadCondenser Refrigerant PressurepsiRead
AI100Cond2RefPressureCondenser Refrigerant PressurepsiRead
AI158Cond2RefPressureInhLoadCondenser Refrigerant Pressure - Condenser 2psiRead
AI162Cond2RefPressureUnloadCondenser Refrigerant PressurepsiRead
AI101Cond3RefPressureCondenser Refrigerant PressurepsiRead
AI159Cond3RefPressureInhLoadCondenser Refrigerant Pressure - Condenser 3psiRead
AI163Cond3RefPressureUnloadCondenser Refrigerant PressurepsiRead
AI102Cond4RefPressureCondenser Refrigerant PressurepsiRead
AI160Cond4RefPressureInhLoadCondenser Refrigerant Pressure - Condenser 4psiRead
AI164Cond4RefPressureUnloadCondenser Refrigerant PressurepsiRead
AI1EntEvapWaterTempEvaporator Entering Fluid Temperature°FRead
AI148EvapWaterFlowRateEvaporator Fluid Flow RateGPMRead
AImin2LvgEvapWaterTempUnitEvaporator Leaving Fluid Temperature°FRead
AI141C1EvapRefPressureEvaporator Refrigerant PressurepsiRead
AI153C1EvapRefPressureUnloadEvaporator Refrigerant Pressure - Evaporator 1psiRead
AI169C1EvapRefPressureStrtFailEvaporator Refrigerant Pressure - Evaporator 1psiRead
AI173C1EvapRefPressureInhLoadEvaporator Refrigerant PressurepsiRead
AI142C2EvapRefPressureEvaporator Refrigerant PressurepsiRead
AI154C2EvapRefPressureUnloadEvaporator Refrigerant Pressure - Evaporator 2psiRead
AI170C2EvapRefPressureStrtFailEvaporator Refrigerant Pressure - Evaporator 2psiRead
AI174C2EvapRefPressureInhLoadEvaporator Refrigerant PressurepsiRead
AI143C3EvapRefPressureEvaporator Refrigerant PressurepsiRead
AI155C3EvapRefPressureUnloadEvaporator Refrigerant Pressure - Evaporator 3psiRead
AI171C3EvapRefPressureStrtFailEvaporator Refrigerant Pressure - Evaporator 3psiRead
AI175C3EvapRefPressureInhLoadEvaporator Refrigerant PressurepsiRead
AI144C4EvapRefPressureEvaporator Refrigerant PressurepsiRead
AI156C4EvapRefPressureUnloadEvaporator Refrigerant Pressure - Evaporator 4psiRead
AI172C4EvapRefPressureStrtFailEvaporator Refrigerant Pressure - Evaporator 4psiRead
AI176C4EvapRefPressureInhLoadEvaporator Refrigerant PressurepsiRead
AI177HeatRecEntWaterTempHeat Recovery Entering Fluid Temperature°FRead
AI150HeatRecLvgWaterTempHeat Recovery Leaving Fluid Temperature°FRead
AI218C1LiqLineRefTempLiquid Line Refrigerant Temperature°FRead
AI165C1Comp1OilFeedPressOil Feed Pressure - Circuit 1 Compressor 1psiRead
AI166C2Comp1OilFeedPressOil Feed Pressure - Circuit 2 Compressor 1psiRead
AI167C3Comp1OilFeedPressOil Feed Pressure - Circuit 3 Compressor 1psiRead
AI168C4Comp1OilFeedPressOil Feed Pressure - Circuit 4 Compressor 1psiRead
AI5OutdoorAirTempOutdoor Air Temperature°FRead
AI149OutdoorAirTempLowOutdoor Air Temperature°FRead
AI81C1Comp1DischRefPressureRefrigerant Discharge Pressure - Compressor 1 DischargepsiRead
AI82C1Comp2DischRefPressureRefrigerant Discharge Pressure - Compressor 2 DischargepsiRead
AI123C1Comp1SuctionPressureRefrigerant Suction Pressure - Compressor 1 Suction RefrigerantpsiRead
AI124C1Comp2SuctionPressureRefrigerant Suction Pressure - Compressor 2 Suction RefrigerantpsiRead
AI8ChillerKilowattsTotal KilowattskWRead
AI178C1Co1VfdTempVFD Temp - Circuit 1 Compressor 1°FRead
AI179C2Co1VfdTempVFD Temp - Circuit 2 Compressor 1°FRead
AI180C3Co1VfdTempVFD Temp - Circuit 3 Compressor 1°FRead
AV1ActiveCapacityLimitActive Capacity Limit Output%Read
AV5ActiveLvgWaterTargetActive Setpoint°FRead
AVmin2ChillerCapacityActual Capacity%Read
AVmin905AVFaultAlarmCodeAlarm Code - FaultRead
AV904AVProblemAlarmCodeAlarm Code - ProblemsRead
AV903AVWarningAlarmCodeAlarm Code - WarningsRead
AV901AVFaultAlarmAlarm Index - FaultRead
AV900AVProblemAlarmAlarm Index - ProblemsRead
AV902AVWarningAlarmAlarm Index - WarningsRead
AVmin3NetworkCapacityLimitPctCapacity Limit Setpoint - Network%Command
AVmin4NetworkCoolTempSetpointCool Setpoint - Network°FCommand
AV121C1Comp1LiftPressureCompressor Lift Pressure - Compressor 1psiRead
AV122C1Comp2LiftPressureCompressor Lift Pressure - Compressor 2psiRead
AV115C1Comp1LiftTempCompressor Lift Temperature - Compressor 1°FRead
AV116C1Comp2LiftTempCompressor Lift Temperature - Compressor 2°FRead
AV8C1Comp1MotorCurrentCompressor Percent RLA - Circuit 1 Compressor 1%Read
AV9C1Comp2MotorCurrentCompressor Percent RLA - Circuit 1 Compressor 2%Read
AV11C2Comp1MotorCurrentCompressor Percent RLA - Circuit 2 Compressor 1%Read
AV14C3Comp1MotorCurrentCompressor Percent RLA - Circuit 3 Compressor 1%Read
AV74C1Comp1HoursCompressor Run Hours - Circuit 1 Compressor 1hRead
AV75C1Comp2HoursCompressor Run Hours - Circuit 1 Compressor 2hRead
AV76C1Comp3HoursCompressor Run Hours - Circuit 1 Compressor 3hRead
AV77C2Comp1HoursCompressor Run Hours - Circuit 2 Compressor 1hRead
AV78C2Comp2HoursCompressor Run Hours - Circuit 2 Compressor 2hRead
AV79C2Comp3HoursCompressor Run Hours - Circuit 2 Compressor 3hRead
AV80C3Comp1HoursCompressor Run Hours - Circuit 3 Compressor 1hRead
AV83C4Comp1HoursCompressor Run Hours - Circuit 4 Compressor 1hRead
AV92C1Comp1StartsCompressor Starts - Circuit 1 Compressor 1Read
AV93C1Comp2StartsCompressor Starts - Circuit 1 Compressor 2Read
AV94C1Comp3StartsCompressor Starts - Circuit 1 Compressor 3Read
AV95C2Comp1StartsCompressor Starts - Circuit 2 Compressor 1Read
AV96C2Comp2StartsCompressor Starts - Circuit 2 Compressor 2Read
AV97C2Comp3StartsCompressor Starts - Circuit 2 Compressor 3Read
AV98C3Comp1StartsCompressor Starts - Circuit 3 Compressor 1Read
AV101C4Comp1StartsCompressor Starts - Circuit 4 Compressor 1Read
AV110CondPump1RunHoursCondenser Pump Run Hours - Condenser Pump 1 Run HourshRead
AV111CondPump2RunHoursCondenser Pump Run Hours - Condenser Pump 2 Run HourshRead
AV44Cond1SatRefTempCondenser Saturated Refrigerant Temperature - Condenser 1°FRead
AV45Cond2SatRefTempCondenser Saturated Refrigerant Temperature - Condenser 2°FRead
AV46Cond3SatRefTempCondenser Saturated Refrigerant Temperature - Condenser 3°FRead
AV47Cond4SatRefTempCondenser Saturated Refrigerant Temperature - Condenser 4°FRead
AV68C1EvapSatRefTempEvaporator Saturated Refrigerant Temperature - Evaporator 1°FRead
AV69C2EvapSatRefTempEvaporator Saturated Refrigerant Temperature - Evaporator 2°FRead
AV70C3EvapSatRefTempEvaporator Saturated Refrigerant Temperature - Evaporator 3°FRead
AV71C4EvapSatRefTempEvaporator Saturated Refrigerant Temperature - Evaporator 4°FRead
AV112EvapPump1OperHoursEvaporator Pump Run Hours - Pump 1hRead
AV113EvapPump2OperHoursEvaporator Pump Run Hours - Pump 2hRead
AV7NetworkIceTempSetpointIce Setpoint - Network°FCommand
AV114ChillerKilowattsTotal chiller kilowatts (AWV and WME only)kWRead
BI6ChillerLimitedChiller Capacity LimitedRead0=Not Limited (Inactive), 1=Limited (Active)
BI7ChillerEnableOutputChiller Enable OutputRead0=Disable (Inactive), 1=Enable (Active)
BImin3ChillerLocalRemoteChiller Local/NetworkRead0=Network, 1=Local
BI4UnitOnOffChiller ON/OFFRead0=Chiller OFF, 1=Chiller ON
BI163C1Cmp1UnavailableCompressor Unavailable - Circuit 1Read0=Available, 1=Unavailable
BI165C2Cmp1UnavailableCompressor Unavailable - Circuit 2Read0=Available, 1=Unavailable
BI1CondWaterFlowStatusCondenser Flow Switch StatusRead0=No Flow (Inactive), 1=Flow (Active)
BI11CondPump1StateCondenser Pump 1 StatusRead0=Pump OFF Request, 1=Pump ON Request
BI12CondPump2StateCondenser Pump 2 StatusRead0=Pump OFF Request, 1=Pump ON Request
BI2EvapWaterFlowStatusEvaporator Flow Switch StatusRead0=No Flow (Inactive), 1=Flow (Active)
BI8EvapPump1StateEvaporator Pump Status - Pump 1Read0=Pump OFF Request, 1=Pump ON Request
BI9EvapPump2StateEvaporator Pump Status - Pump 2Read0=Pump OFF Request, 1=Pump ON Request
BI5RunEnabledRun EnabledRead0=OFF (Inactive), 1=Run Allowed (Active)
BVmin2ChillerEnableStpChiller Enable SetpointCommand0=Disable (Inactive), 1=Enable
BVmin8ClearAlarmClear Alarm - NetworkCommand0=Normal, 1=Clear Alarm
MV2ActiveModeChiller Mode OutputRead1=Ice, 2=Cool, 3=Heat, 4=Cool/Heat Recovery, 5=Defrost
MVmin3ChillerOperationModeChiller Mode Setpoint - NetworkCommand1=Ice*, 2=Cool*, 3=Heat, 4=Cool/Heat Recovery, 5=Defrost
MVmin1UnitStatusChiller StatusRead1=OFF, 2=Start, 3=Run, 4=Preshutdown, 5=Service
MV4UnitsUnitsWrite1=Metric, 2=English
MV6WsEconStpWaterside Economizer Enable SetpointWrite1=Disable, 2=Enable
MV5WsEconStateWaterside Economizer StateRead1=Off, 2=Mech, 3=Hybrid, 4=WsEcon
BI10AlarmDigitalOutputAlarm Digital OutputRead0=No Alarm, 1=Alarm
BV533StartInhbtAmbTempLowAmbient Temperature Low ProblemCommand0=No Alarm, 1=In Alarm
BV17AlarmLimitCtrlrCommFailAlarm/Limit Controller Communication FailureCommand0=No Alarm, 1=In Alarm
BV676C1OFF CondPressHiCIRCUIT SHUTDOWN - Condenser Pressure High Trip Circuit 1 FaultCommand0=No Alarm, 1=In Alarm
BV678C2OFFCondPressHiCIRCUIT SHUTDOWN - Condenser Pressure High Trip Circuit 2 FaultCommand0=No Alarm, 1=In Alarm
BV668C1CondPsenfCIRCUIT SHUTDOWN - Condenser Pressure Sensor Circuit 1 FaultCommand0=No Alarm, 1=In Alarm
BV670C2CondPsenfCIRCUIT SHUTDOWN - Condenser Pressure Sensor Circuit 2 FaultCommand0=No Alarm, 1=In Alarm
BV751Evap1FreezeProtectCIRCUIT SHUTDOWN - Evaporator 1 Freeze Protection FaultCommand0=No Alarm, 1=In Alarm
BV752Evap2FreezeProtectCIRCUIT SHUTDOWN - Evaporator 2 Freeze Protection FaultCommand0=No Alarm, 1=In Alarm
BV711C1EvapPsenfCIRCUIT SHUTDOWN - Evaporator Pressure Sensor Circuit 1 FaultCommand0=No Alarm, 1=In Alarm
BV713C2EvapPsenfCIRCUIT SHUTDOWN - Evaporator Pressure Sensor Circuit 2 FaultCommand0=No Alarm, 1=In Alarm
BV704C1LowEvPrCIRCUIT SHUTDOWN - Low Evaporator Pressure Trip Circuit 1 FaultCommand0=No Alarm, 1=In Alarm
BV706C2LowEvPrCIRCUIT SHUTDOWN - Low Evaporator Pressure Trip Circuit 2 FaultCommand0=No Alarm, 1=In Alarm
BV35C1OffMainPhaseLossCIRCUIT SHUTDOWN - Mains PVM Fault 1Command0=No Alarm, 1=Alarm
BV36C2OffMainPhaseLossCIRCUIT SHUTDOWN - Mains PVM Fault 2Command0=No Alarm, 1=Alarm
BI18C1HighPressCIRCUIT SHUTDOWN - Mechanical High Pressure Alarm Circuit 1Command0=Normal, 1=In Alarm
BV27C1OffMtrEarthLkgCIRCUIT SHUTDOWN - Motor Earth Fault 1Command0=No Alarm, 1=Alarm
BV28C2OffMtrEarthLkgCIRCUIT SHUTDOWN - Motor Earth Fault 2Command0=No Alarm, 1=Alarm
BI13C1MotorProtectCIRCUIT SHUTDOWN - Motor Protector Trip Circuit 1Command0=Normal, 1=In Alarm
BV31C1OffMtrPhaseLossCIRCUIT SHUTDOWN - Motor PVM Fault 1Command0=No Alarm, 1=Alarm
BV32C2OffMtrPhaseLossCIRCUIT SHUTDOWN - Motor PVM Fault 2Command0=No Alarm, 1=Alarm
BI24C1NbrRestartsCIRCUIT SHUTDOWN - Number of Compressor Re-Starts Exceeded Circuit 1Command0=No Alarm, 1=In Alarm
BV23C1OffCtrlCardTmpHiCIRCUIT SHUTDOWN - VFD Control Card High Temperature 1Command0=No Alarm, 1=Alarm
BV24C2OffCtrlCardTmpHiCIRCUIT SHUTDOWN - VFD Control Card High Temperature 2Command0=No Alarm, 1=Alarm
BV9C1OffCmpCtrlrComFailCompressor Controller Communication Failed - Circuit 1Command0=No Alarm, 1=Alarm
BV10C2OffCmpCtrlrComFailCompressor Controller Communication Failed - Circuit 2Command0=No Alarm, 1=Alarm
BV942C1Cmp1OffVfdTempHiCOMP SHUTDOWN - COMPRESSOR VFD Over Heat 1 FaultCommand0=No Alarm, 1=In Alarm
BV944C2Cmp1OffVfdTempHiCOMP SHUTDOWN - COMPRESSOR VFD Over Heat 2 FaultCommand0=No Alarm, 1=In Alarm
BV946C3Cmp1OffVfdTempHiCOMP SHUTDOWN - COMPRESSOR VFD Over Heat 3 FaultCommand0=No Alarm, 1=In Alarm
BV680C3Comp1OFFCondPressHiCOMP SHUTDOWN - Condenser Pressure High Circuit 3 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV681C4Comp1OFFCondPressHiCOMP SHUTDOWN - Condenser Pressure High Circuit 4 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV672C3Comp1OFFCondPressSenCOMP SHUTDOWN - Condenser Pressure Sensor Circuit 3 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV673C4Comp1OFFCondPressSenCOMP SHUTDOWN - Condenser Pressure Sensor Circuit 4 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BI41C1GroundFaultCircuit 1 Ground Fault ProtectionCommand0=No Alarm, 1=In Alarm
BI42C2GroundFaultCircuit 2 Ground Fault ProtectionCommand0=No Alarm, 1=In Alarm
BV606C1Cmp1OffCurrentHiCOMP SHUTDOWN - Current Overload Trip Fault, circuit 1 compressor 1Command0=No Alarm, 1=In Alarm
BV607C1Cmp2OffCurrentHiCOMP SHUTDOWN - Current Overload Trip Fault, circuit 1 compressor 2Command0=No Alarm, 1=In Alarm
BV608C1Cmp1OffCurrentHiCOMP SHUTDOWN - Current Overload Trip Fault, circuit 2 (name printed as C1Cmp1)Command0=No Alarm, 1=In Alarm
BV610C3Cmp1OffCurrentHiCOMP SHUTDOWN - Current Overload Trip Fault, circuit 3 compressor 1Command0=No Alarm, 1=In Alarm
BV694C1Comp1OFFDischTempHiCOMP SHUTDOWN - Discharge Temp High Circuit 1 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV696C2Comp1OFFDischTempHiCOMP SHUTDOWN - Discharge Temp High Circuit 2 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV698C3Comp1OFFDischTempHiCOMP SHUTDOWN - Discharge Temp High Circuit 3 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV699C4Comp1OFFDischTempHiCOMP SHUTDOWN - Discharge Temp High Circuit 4 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV688C1Comp1OFFDischTempSenCOMP SHUTDOWN - Discharge Temperature Sensor Circuit 1 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV690C2Comp1OFFDischTempSenCOMP SHUTDOWN - Discharge Temperature Sensor Circuit 2 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV692C3Comp1OFFDischTempSenCOMP SHUTDOWN - Discharge Temperature Sensor Circuit 3 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV693C4Comp1OFFDischTempSenCOMP SHUTDOWN - Discharge Temperature Sensor Circuit 4 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV708C3Comp1OFFEvapPressLowCOMP SHUTDOWN - Evaporator Pressure Low Circuit 3 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV709C4Comp1OFFEvapPressLowCOMP SHUTDOWN - Evaporator Pressure Low Circuit 4 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV715C3Comp1OFFEvapPressSenCOMP SHUTDOWN - Evaporator Pressure Sensor Circuit 3 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV716C4Comp1OFFEvapPressSenCOMP SHUTDOWN - Evaporator Pressure Sensor Circuit 4 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV802C1Comp1OFFOilFeedPSenCOMP SHUTDOWN - Oil Feed Pressure Sensor Circuit 1 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV804C2Comp1OFFOilFeedPSenCOMP SHUTDOWN - Oil Feed Pressure Sensor Circuit 2 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV806C3Comp1OFFOilFeedPSenCOMP SHUTDOWN - Oil Feed Pressure Sensor Circuit 3 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV807C4Comp1OFFOilFeedPSenCOMP SHUTDOWN - Oil Feed Pressure Sensor Circuit 4 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV605UnitOFFOATempSenFailCOMP SHUTDOWN - Outside Air Temperature Sensor FaultCommand0=No Alarm, 1=In Alarm
BV655C1OffOverVoltageCOMPRESSOR SHUTDOWN - Overvoltage 1Command0=No Alarm, 1=Alarm
BV657C2OffOverVoltageCOMPRESSOR SHUTDOWN - Overvoltage 2Command0=No Alarm, 1=Alarm
BV857C1Comp1OFFSuctTempSenCOMP SHUTDOWN - Suction Temp Sensor Circuit 1 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV859C2Comp1OFFSuctTempSenCOMP SHUTDOWN - Suction Temp Sensor Circuit 2 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV861C3Comp1OFFSuctTempSenCOMP SHUTDOWN - Suction Temp Sensor Circuit 3 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV862C4Comp1OFFSuctTempSenCOMP SHUTDOWN - Suction Temp Sensor Circuit 4 Compressor 1 FaultCommand0=No Alarm, 1=In Alarm
BV661C1OffUnderVoltageCOMPRESSOR SHUTDOWN - Undervoltage 1Command0=No Alarm, 1=Alarm
BV663C2OffUnderVoltageCOMPRESSOR SHUTDOWN - Undervoltage 2Command0=No Alarm, 1=Alarm
BI70C1Co1HighVfdCurrentCompressor VFD Current High 1Command0=No Alarm, 1=In Alarm
BI71C2Co1HighVfdCurrentCompressor VFD Current High 2Command0=No Alarm, 1=In Alarm
BV925UnitBoardOfflineController Board Offline Fault, unit boardCommand0=No Alarm, 1=In Alarm
BV882C1ControlBoardOfflineController Board 1 Offline FaultCommand0=No Alarm, 1=In Alarm
BV883C2ControlBoardOfflineController Board 2 Offline FaultCommand0=No Alarm, 1=In Alarm
BV884C3ControlBoardOfflineController Board 3 Offline FaultCommand0=No Alarm, 1=In Alarm
BV885C4ControlBoardOfflineController Board 4 Offline FaultCommand0=No Alarm, 1=In Alarm
BI46DcFanCtrlCommFailDC Fan Controller Comm FailureCommand0=Normal, 1=In Alarm
BI64C1DcFanFaultDC Fan Fault 1Command0=Normal, 1=In Alarm
BI65C2DcFanFaultDC Fan Fault 2Command0=Normal, 1=In Alarm
BI47EconExvCommFailEconomizer EXV Comm FailureCommand0=Normal, 1=In Alarm
AI234C1EconRefPressEconomizer Refrigerant Pressure Sensor Fault 1Command0=Normal, 1=In Alarm
AI235C2EconRefPressEconomizer Refrigerant Pressure Sensor Fault 2Command0=Normal, 1=In Alarm
AI238C1EconRefTempEconomizer Temperature Sensor Fault 1Command0=Normal, 1=In Alarm
AI239C2EconRefTempEconomizer Temperature Sensor Fault 2Command0=Normal, 1=In Alarm
BV917EvapEntWTempSensorFailEvaporator Entering Water Temperature Sensor FaultCommand0=No Alarm, 1=In Alarm
BV501EvapEntWTempSensorFailEvaporator Entering Water Temperature Sensor WarningCommand0=No Alarm, 1=In Alarm
BI45EvapExvCommFailEvaporator EXV Comm FailureCommand0=No Alarm, 1=In Alarm
BI56C1EvapExvMtrFaultEvaporator EXV Motor Error 1Command0=No Alarm, 1=In Alarm
BI57C2EvapExvMtrFaultEvaporator EXV Motor Error 2Command0=No Alarm, 1=In Alarm
BV749EvpLvgWTmp1SensorFailEvaporator Leaving Water Temperature 1 Sensor FaultCommand0=No Alarm, 1=In Alarm
BV750EvpLvgWTmp2SensorFailEvaporator Leaving Water Temperature 2 Sensor FaultCommand0=No Alarm, 1=In Alarm
BV13C1OffEXVCrtlrComFailEXV Controller Communication Failed - Circuit 1Command0=No Alarm, 1=Alarm
BV14C2OffEXVCrtlrComFailEXV Controller Communication Failed - Circuit 2Command0=No Alarm, 1=Alarm
BV578C1Cmp1HoldAmpsHiINHIBIT LOAD - Compressor Motor Current High 1 ProblemCommand0=No Alarm, 1=In Alarm
BV580C2Cmp1HoldAmpsHiINHIBIT LOAD - Compressor Motor Current High 2 ProblemCommand0=No Alarm, 1=In Alarm
BV582C3Cmp1HoldAmpsHiINHIBIT LOAD - Compressor Motor Current High 3 ProblemCommand0=No Alarm, 1=In Alarm
BV535C1InhbtLoadCondPressHiINHIBIT LOAD - Condenser Pressure High Circuit 1 ProblemCommand0=No Alarm, 1=In Alarm
BV536C2InhbtLoadCondPressHiINHIBIT LOAD - Condenser Pressure High Circuit 2 ProblemCommand0=No Alarm, 1=In Alarm
BV537C3InhbtLoadCondPressHiINHIBIT LOAD - Condenser Pressure High Circuit 3 ProblemCommand0=No Alarm, 1=In Alarm
BV538C4InhbtLoadCondPressHiINHIBIT LOAD - Condenser Pressure High Circuit 4 ProblemCommand0=No Alarm, 1=In Alarm
BV556C1InhbtLoadEvapPressLoINHIBIT LOAD - Evap Pressure Low 1 ProblemCommand0=No Alarm, 1=In Alarm
BV557C2InhbtLoadEvapPressLoINHIBIT LOAD - Evap Pressure Low 2 ProblemCommand0=No Alarm, 1=In Alarm
BV558C3InhbtLoadEvapPressLoINHIBIT LOAD - Evap Pressure Low 3 ProblemCommand0=No Alarm, 1=In Alarm
BV559C4InhbtLoadEvapPressLoINHIBIT LOAD - Evap Pressure Low 4 ProblemCommand0=No Alarm, 1=In Alarm
BI48C1Cmp1LowPr DiffOrRatioLow Pressure Difference or Ratio, circuit 1 compressor 1Command0=No Alarm, 1=In Alarm
BI49C2Cmp1LowPr DiffOrRatioLow Pressure Difference or Ratio, circuit 2 compressor 1Command0=No Alarm, 1=In Alarm
BI52C1Cmp1MultiStartFailMultistart Fail Compressor 1Command0=No Alarm, 1=In Alarm
BI53C2Cmp1MultiStartFailMultistart Fail Compressor 2Command0=No Alarm, 1=In Alarm
BV575EvPumpFault1PUMP 2 START ATTEMPTED - Evaporator Pump 1 FailureCommand0=No Alarm, 1=In Alarm
BV576EvPumpFault2PUMP 1 START ATTEMPTED - Evaporator Pump 2 FailureCommand0=No Alarm, 1=In Alarm
BI149RpdRestoreCommFailRapid Restore Module Communication FailureCommand0=No Alarm, 1=In Alarm
BI40UnitGroundFaultUnit Ground Fault ProtectionCommand0=No Alarm, 1=Alarm
BV565C1Cmp1UnloadAmpsHiUNLOAD - Compressor Motor Current High 1 ProblemCommand0=No Alarm, 1=In Alarm
BV567C2Cmp1UnloadAmpsHiUNLOAD - Compressor Motor Current High 2 ProblemCommand0=No Alarm, 1=In Alarm
BV569C3Cmp1UnloadAmpsHiUNLOAD - Compressor Motor Current High 3 ProblemCommand0=No Alarm, 1=In Alarm
BV540C1UnloadCondPressHiUNLOAD - Condenser Pressure High 1 ProblemCommand0=No Alarm, 1=In Alarm
BV541C2UnloadCondPressHiUNLOAD - Condenser Pressure High 2 ProblemCommand0=No Alarm, 1=In Alarm
BV542C3UnloadCondPressHiUNLOAD - Condenser Pressure High 3 ProblemCommand0=No Alarm, 1=In Alarm
BV543C4UnloadCondPressHiUNLOAD - Condenser Pressure High 4 ProblemCommand0=No Alarm, 1=In Alarm
BV22UnitOffCndLvgWTempSen/UnitOffCndEntWTempSenUNIT SHUTDOWN - Condenser LWT or EWT Low (Freeze)Command0=No Alarm, 1=In Alarm
BV748UnitOFFEvapLvgWTempSenUNIT SHUTDOWN - Evaportator Leaving Water Temperature Sensor FaultCommand0=No Alarm, 1=In Alarm
BV702UnitOffEvpLvgWTempSen/UnitEvapWaterTempSenUNIT SHUTDOWN - Evaporator LWT or EWT Low (Freeze)Command0=No Alarm, 1=In Alarm
BV561C1UnloadEvapPressLowUNLOAD - Evap Pressure Low 1 ProblemCommand0=No Alarm, 1=In Alarm
BV562C2UnloadEvapPressLowUNLOAD - Evap Pressure Low 2 ProblemCommand0=No Alarm, 1=In Alarm
BV563C3UnloadEvapPressLowUNLOAD - Evap Pressure Low 3 ProblemCommand0=No Alarm, 1=In Alarm
BV564C4UnloadEvapPressLowUNLOAD - Evap Pressure Low 4 ProblemCommand0=No Alarm, 1=In Alarm
NC1NC1-FaultsNotification class for faultsRead
NC2NC1-ProblemsNotification class for problemsRead
NC3NC1-WarningsNotification class for warningsRead
BV918BadCurrentLimitInputBad Current Limit InputRead
BV513BadDemandLimitInputBad Demand Limit InputRead
BV512BadSPointOverrideInputBad Setpoint Override InputRead
BI979ProcessBusFailureChiller Network Communication FailureRead
BV516C1FailedPumpdownCircuit 1 Failed PumpdownRead
BV517C2FailedPumpdownCircuit 2 Failed PumpdownRead
BV518C3FailedPumpdownCircuit 3 Failed PumpdownRead
BV519C4FailedPumpdownCircuit 4 Failed PumpdownRead
BV924UnitExternalEventExternal EventRead
BI132C1Co1IgvPositionWarnIGV Position Warning, circuit 1 compressor 1Read
BI133C1Co2IgvPositionWarnIGV Position Warning, circuit 1 compressor 2Read
BI976C1RefrigChargeLow Refrigerant Charge - Circuit 1Read
BI977C2RefrigChargeLow Refrigerant Charge - Circuit 2Read
BI978C3RefrigChargeLow Refrigerant Charge - Circuit 3Read
BV919OptionCtrlrCommFailOption Controller Communication FailedRead
BI196LowSourceTempWarnUnit Low Source Temperature WarningRead
BV515UnitPowerRestoreUnit Power RestoreRead
BI134C1Co1VfdOvrhtWarnVFD Cooling Fin Overheat Warning, circuit 1 compressor 1Read
BI135C1Co2VfdOvrhtWarnVFD Cooling Fin Overheat Warning, circuit 1 compressor 2Read
BV529C1RestartDelayPwrLRunPower Loss While Running Circuit 1Read
BV530C2RestartDelayPwrLRunPower Loss While Running Circuit 2Read
BV531C3RestartDelayPwrLRunPower Loss While Running Circuit 3Read
BV532C4RestartDelayPwrLRunPower Loss While Running Circuit 4Read
BI170WseEwtSenfWaterside Economizer EWT Sensor FaultRead
BI169WseValvePrblmWaterside Economizer Valve ProblemRead
BV968C1OffPvmGfpCIRCUIT SHUTDOWN - PVM GFP Circuit 1 FaultRead
BV969C2OffPvmGfpCIRCUIT SHUTDOWN - PVM GFP Circuit 2 FaultRead
BV742C1Comp1OFFNbrRestartsCOMP LOCKOUT - Number of Allowed Re-Starts Exceeded Circuit 1 Comp 1Read
BV744C2Comp1OFFNbrRestartsCOMP LOCKOUT-Number of Allowed Re-Starts Exceeded Circuit 2 Comp 1Read
BV746C3Comp1OFFNbrRestartsCOMP LOCKOUT - Number of Allowed Re-Starts Exceeded Circuit 3 Comp 1Read
BV747C4Comp1OFFNbrRestartsCOMP LOCKOUT - Number of Allowed Re-Starts Exceeded Circuit 4 Comp 1Read
AI151EvapLWT1CIRCUIT SHUTDOWN - Evaporator 1 Freeze ProtectionRead
AI152EvapLWT2CIRCUIT SHUTDOWN - Evaporator 2 Freeze ProtectionRead
BV948C1Cmp1OffVfdCommFailCOMP SHUTDOWN - COM ERROR With COMPRESSOR VFD Circuit 1 Comp 1Read
BV950C2Cmp1OffVfdCommFailCOMP SHUTDOWN - COM ERROR With COMPRESSOR VFD Circuit 2 Comp 1Read
BV952C3Cmp1OffVfdCommFailCOMP SHUTDOWN - COM ERROR With COMPRESSOR VFD Circuit 3 Comp 1Read
BV886C1Cmp1OffVfdFaultCOMP SHUTDOWN - COMPRESSOR VFD Fault Circuit 1 Comp 1Read
BV888C2Cmp1OffVfdFaultCOMP SHUTDOWN - COMPRESSOR VFD Fault Circuit 2 Comp 1Read
BV890C3Cmp1OffVfdFaultCOMP SHUTDOWN - COMPRESSOR VFD Fault Circuit 3 Comp 1Read
BV961C1Co1LowDischSHAlmCOMP SHUTDOWN - Low Discharge Superheat Circuit 1 Comp 1Read
BV963C2Co1LowDischSHAlmCOMP SHUTDOWN - Low Discharge Superheat Circuit 2 Comp 1Read
BV965C3Co1LowDischSHAlmCOMP SHUTDOWN - Low Discharge Superheat Circuit 3 Comp 1Read
BV599C1Comp1OFFLoPressRatioCOMP SHUTDOWN - Low Pressure Ratio Circuit 1 Comp1Read
BV601C2Comp1OFFLoPressRatioCOMP SHUTDOWN - Low Pressure Ratio Circuit 2 Comp1Read
BV603C3Comp1OFFLoPressRatioCOMP SHUTDOWN - Low Pressure Ratio Circuit 3 Comp1Read
BV604C4Comp1OFFLoPressRatioCOMP SHUTDOWN - Low Pressure Ratio Circuit 4 Comp1Read
BV625C1Cmp1OffMtrProtectCOMP SHUTDOWN - Motor Protector Trip Circuit 1 Comp 1Read
BV627C2Cmp1OffMtrProtectCOMP SHUTDOWN - Motor Protector Trip Circuit 2 Comp 1Read
BV876C1Comp1OFFMechLoPressCOMP SHUTDOWN - Mechanical Low Pressure Trip Circuit 1 Comp 1Read
BV878C2Comp1OFFMechLoPressCOMP SHUTDOWN - Mechanical Low Pressure Trip Circuit 2 Comp 1Read
BV880C3Comp1OFFMechLoPressCOMP SHUTDOWN - Mechanical Low Pressure Trip Circuit 3 Comp 1Read
BV881C4Comp1OFFMechLoPressCOMP SHUTDOWN - Mechanical Low Pressure Trip Circuit 4 Comp 1Read
BV637C1Comp1OFFMotorTempHiCOMP SHUTDOWN - Motor Temperature High Circuit 1 Comp 1Read
BV639C2Comp1OFFMotorTempHiCOMP SHUTDOWN - Motor Temperature High Circuit 2 Comp 1Read
BV641C3Comp1OFFMotorTempHiCOMP SHUTDOWN - Motor Temperature High Circuit 3 Comp 1Read
BV642C4Comp1OFFMotorTempHiCOMP SHUTDOWN - Motor Temperature High Circuit 4 Comp 1Read
BV899C1Comp1OFFMotorTSensCOMP SHUTDOWN - Motor Temp Sensor Fault Circuit 1 Comp 1Read
BV901C2Comp1OFFMotorTSensCOMP SHUTDOWN - Motor Temp Sensor Fault Circuit 2 Comp 1Read
BV903C3Comp1OFFMotorTSensCOMP SHUTDOWN - Motor Temp Sensor Fault Circuit 3 Comp 1Read
BV904C4Comp1OFFMotorTSensCOMP SHUTDOWN - Motor Temp Sensor Fault Circuit 4 Comp 1Read
BV905C1CompNoPressChStartCOMP SHUTDOWN - No Pressure Change After Start Circuit 1Read
BV906C2CompNoPressChStartCOMP SHUTDOWN - No Pressure Change After Start Circuit 2Read
BV907C3CompNoPressChStartCOMP SHUTDOWN - No Pressure Change After Start Circuit 3Read
BV908C4CompNoPressChStartCOMP SHUTDOWN - No Pressure Change After Start Circuit 4Read
BV911C1CompNoPressStartCOMP SHUTDOWN - No Pressure at Startup Circuit 1Read
BV912C2CompNoPressStartCOMP SHUTDOWN - No Pressure at Startup Circuit 2Read
BV913C3CompNoPressStartCOMP SHUTDOWN - No Pressure at Startup Circuit 3Read
BV914C4CompNoPressStartCOMP SHUTDOWN - No Pressure at Startup Circuit 4Read
BV760C1Comp1OFFHighPressCOMP SHUTDOWN - Mechanical High Pressure Trip Circuit 1 Comp 1Read
BV762C2Comp1OFFHighPressCOMP SHUTDOWN - Mechanical High Pressure Trip Circuit 2 Comp 1Read
BV764C3Comp1OFFHighPressCOMP SHUTDOWN - Mechanical High Pressure Trip Circuit 3 Comp 1Read
BV765C4Comp1OFFHighPressCOMP SHUTDOWN - Mechanical High Pressure Trip Circuit 4 Comp 1Read
BV796C1Comp1OFFOilFilterPHiCOMP SHUTDOWN - Oil Delta Pressure High Circuit 1 Comp 1Read
BV798C2Comp1OFFOilFilterPHiCOMP SHUTDOWN - Oil Delta Pressure High Circuit 2 Comp 1Read
BV800C3Comp1OFFOilFilterPHiCOMP SHUTDOWN - Oil Delta Pressure High Circuit 3 Comp 1Read
BV801C4Comp1OFFOilFilterPHiCOMP SHUTDOWN - Oil Delta Pressure High Circuit 4 Comp 1Read
BI973C1OffRefrigChargeCOMP SHUTDOWN - Refrig Charge Circuit 1Read
BI974C2OffRefrigChargeCOMP SHUTDOWN - Refrig Charge Circuit 2Read
BI975C3OffRefrigChargeCOMP SHUTDOWN - Refrig Charge Circuit 3Read
BV930C1Comp1SlidePosSenfCOMP SHUTDOWN - Slide Position Sensor Circuit 1, Comp 1Read
BV932C2Comp1SlidePosSenfCOMP SHUTDOWN - Slide Position Sensor Circuit 2, Comp 1Read
BV934C3Comp1SlidePosSenfCOMP SHUTDOWN - Slide Position Sensor Circuit 3, Comp 1Read
BV935C4Comp1SlidePosSenfCOMP SHUTDOWN - Slide Position Sensor Circuit 4, Comp 1Read
BV821C1Comp1OFFStarterFaultCOMP SHUTDOWN - Starter Fault COMP Circuit 1 Comp 1Read
BV823C2Comp1OFFStarterFaultCOMP SHUTDOWN - Starter Fault COMP Circuit 2 Comp 1Read
BV825C3Comp1OFFStarterFaultCOMP SHUTDOWN - Starter Fault COMP Circuit 3 Comp 1Read
BV826C4Comp1OFFStarterFaultCOMP SHUTDOWN - Starter Fault COMP Circuit 4 Comp 1Read
BI172C1Cmp1OilFeedLossCompressor Oil Feed Loss - Circuit 1, Compressor 1Read
BI174C2Cmp1OilFeedLossCompressor Oil Feed Loss - Circuit 2, Compressor 1Read
BI78C1Co1DidNotStartCOMPRESSOR SHUTDOWN - Compressor Does Not Start, circuit 1 compressor 1Read
BI79C1Co2DidNotStartCOMPRESSOR SHUTDOWN - Compressor Does Not Start, circuit 1 compressor 2Read
BI90C1Co1NoCompStopAlmCOMPRESSOR SHUTDOWN - Compressor Did Not Stop, circuit 1 compressor 1Read
BI91C1Co2NoCompStopAlmCOMPRESSOR SHUTDOWN - Compressor Did Not Stop, circuit 1 compressor 2Read
BI76C1Co1DischPressHighCOMPRESSOR SHUTDOWN - Discharge Pressure High, circuit 1 compressor 1Read
BI77C1Co2DischPressHighCOMPRESSOR SHUTDOWN - Discharge Pressure High, circuit 1 compressor 2Read
BI98C1Co1EnRelayOffFltCOMPRESSOR SHUTDOWN - Enable Relay Off Fault, circuit 1 compressor 1Read
BI99C1Co2EnRelayOffFltCOMPRESSOR SHUTDOWN - Enable Relay Off Fault, circuit 1 compressor 2Read
BI94C1Co1IGVDriverFltCOMPRESSOR SHUTDOWN - IGV Driver Fault, circuit 1 compressor 1Read
BI95C1Co2IGVDriverFltCOMPRESSOR SHUTDOWN - IGV Driver Fault, circuit 1 compressor 2Read
BI96C1Co1IGVCalibFltCOMPRESSOR SHUTDOWN - IGV Calibration Fault, circuit 1 compressor 1Read
BI97C1Co2IGVCalibFltCOMPRESSOR SHUTDOWN - IGV Calibration Fault, circuit 1 compressor 2Read
BI130C1Co1IPSOverTmpCOMPRESSOR SHUTDOWN - IPS Over Temperature, circuit 1 compressor 1Read
BI131C1Co2IPSOverTmpCOMPRESSOR SHUTDOWN - IPS Over Temperature, circuit 1 compressor 2Read
BI84C1Co1RtrPmpShtLowCOMPRESSOR SHUTDOWN - Low Rotor Pump Superheat, circuit 1 compressor 1Read
BI85C1Co2RtrPmpShtLowCOMPRESSOR SHUTDOWN - Low Rotor Pump Superheat, circuit 1 compressor 2Read
BI92C1Co1MBCFaultCOMPRESSOR SHUTDOWN - MBC Fault, circuit 1 compressor 1Read
BI93C1Co2MBCFaultCOMPRESSOR SHUTDOWN - MBC Fault, circuit 1 compressor 2Read
BI122C1Co1MBCMdbsComFltCOMPRESSOR SHUTDOWN - MBC Modbus Communication Fault, circuit 1 compressor 1Read
BI123C1Co2MBCMdbsComFltCOMPRESSOR SHUTDOWN - MBC Modbus Communication Fault, circuit 1 compressor 2Read
BI126C1Co1MBCOrbitErrorCOMPRESSOR SHUTDOWN - MBC Orbit Error, circuit 1 compressor 1Read
BI127C1Co2MBCOrbitErrorCOMPRESSOR SHUTDOWN - MBC Orbit Error, circuit 1 compressor 2Read
BI82C1Co1MtrGapTempHighCOMPRESSOR SHUTDOWN - Motor Gap Temperature High, circuit 1 compressor 1Read
BI83C1Co2MtrGapTempHighCOMPRESSOR SHUTDOWN - Motor Gap Temperature High, circuit 1 compressor 2Read
BI88C1Co1MotorSpeedFltCOMPRESSOR SHUTDOWN - Motor Speed Fail, circuit 1 compressor 1Read
BI89C1Co2MotorSpeedFltCOMPRESSOR SHUTDOWN - Motor Speed Fail, circuit 1 compressor 2Read
BI128C1Co1PrimaryPwrFailCOMPRESSOR SHUTDOWN - Primary Power Fail, circuit 1 compressor 1Read
BI129C1Co2PrimaryPwrFailCOMPRESSOR SHUTDOWN - Primary Power Fail, circuit 1 compressor 2Read
BI80C1Co1StatorTempHighCOMPRESSOR SHUTDOWN - Stator Temperature High, circuit 1 compressor 1Read
BI81C1Co2StatorTempHighCOMPRESSOR SHUTDOWN - Stator Temperature High, circuit 1 compressor 2Read
BI74C1Co1SuctPressLowCOMPRESSOR SHUTDOWN - Suction Pressure Low, circuit 1 compressor 1Read
BI75C1Co2SuctPressLowCOMPRESSOR SHUTDOWN - Suction Pressure Low, circuit 1 compressor 2Read
BI86C1Co1SurgeTempAlmCOMPRESSOR SHUTDOWN - Surge Temperature, circuit 1 compressor 1Read
BI87C1Co2SurgeTempAlmCOMPRESSOR SHUTDOWN - Surge Temperature, circuit 1 compressor 2Read
BI124C1Co1VFDMdbsComFltCOMPRESSOR SHUTDOWN - VFD Modbus Communication Fault, circuit 1 compressor 1Read
BI125C1Co2VFDMdbsComFltCOMPRESSOR SHUTDOWN - VFD Modbus Communication Fault, circuit 1 compressor 2Read
BV11Comp3CntrlrCommFailCOMP Controller Communication Failed Circuit 3Read
BV12Comp4CntrlrCommFailCOMP Controller Communication Failed Circuit 4Read
BV15EXVCntrlr3CommFailEXV Controller Communication Failed Circuit 3Read
BV16EXVCntrlr4CommFailEXV Controller Communication Failed Circuit 4Read
BV18FanCrtlr1and2ComFailFan Controller Communication Failed Circuit 1 & 2Read
BV19FanCrtlr3ComFailFan Controller Communication Failed Circuit 3Read
BV20FanCrtlr4ComFailFan Controller Communication Failed Circuit 4Read
BV21FanCrtlr3and4ComFailFan Controller Communication Failed Circuit 3 & 4Read
BV820UnitOFFPhaseVoltageSHUTDOWN - Phase Voltage Protection - UnitRead
BV926C1OFFPhaseVoltageSHUTDOWN - Phase Voltage Protection Circuit 1Read
BV927C2OFFPhaseVoltageSHUTDOWN - Phase Voltage Protection Circuit 2Read
BV928C3OFFPhaseVoltageSHUTDOWN - Phase Voltage Protection Circuit 3Read
BV929C4OFFPhaseVoltageSHUTDOWN - Phase Voltage Protection Circuit 4Read
BV701UnitOFFEvapWaterFlowUNIT SHUTDOWN - Evaporator Water Flow LossRead
BV921EmergencyStopAlarmUNIT STOP - Emergency Stop AlarmRead
BV922EvapWTempInvertedUNIT STOP - Evaporator Water Temperatures InvertedRead
BV923ExternalAlarmUNIT STOP - External AlarmRead
BV967UnitOffPvmGfpUNIT STOP - PVM GFP FaultRead
BI171WseValveFaultWaterside Economizer valve faultRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)

How many BACnet points does the Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator) have?

This list has 433 BACnet objects: 101 analog inputs, 49 analog values, 87 binary inputs, 187 binary values, 3 notification classs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator) BACnet points are writable?

128 of the 433 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator) BACnet documentation?

The source is MicroTech Chiller Unit Controller Protocol Information (ED 15120-11), revision 2023-10, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20Unit%20Controller%20LonWorks-BACnet%20Tech%20Sheet%20-%20ED%2015120-11.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)?

Start with BV 2 ChillerEnableStp (Network enable/disable of the chiller); MV 3 ChillerOperationMode (Ice / cool / heat / heat recovery mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitPct (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 ChillerLocalRemote (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); AV 2 ChillerCapacity (Actual capacity in percent); AV 905 AVFaultAlarmCode (Active fault alarm code).

How do I enable BMS control of the Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)?

Chiller Local/Network must be set to Network at the unit keypad (it cannot be changed over the network). The BMS then writes ChillerEnableStp (BV 2) = Enable; this only permits the chiller to run when other conditions are satisfied, it does not force a start.

Does the Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator) need a BACnet heartbeat or have a communication timeout?

The guide's communication parameter table lists Receive Heartbeat as N/A for BACnet IP and MS/TP; the heartbeat (nciRcvHrtBt) only applies to LonWorks.

How do I check these points on the real MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech Chiller Unit Controller Protocol Information · ED 15120-11 · rev. 2023-10. Object names, instances and units are reproduced as published; descriptions are our own.