Chiller plant manager (multi-chiller sequencer) · BACnet points list

Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet points list

Updated 28 October 2026

Short answer

iCM is a software option on a MicroTech 4 chiller that makes it the master of a multi-chiller plant: it stages a master and up to seven slaves and tracks system load, demand limit and the standby unit. Version 5.00 also manages evaporator/condenser pumps (iPM), up to ten cooling towers (iCT) and iSM pump groups. BACnet IP or BACnet MS/TP comes from a POL908/POL904 module or the onboard software option on that controller. Most objects are read-only plant data per chiller; writable ones cover master enable, staging priorities, standby unit, pump and tower network setpoints and alarm resets.

This page lists 462 BACnet objects for the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
iCM chiller plant manager, option 184 (Daikin Applied Europe)
Equipment
Chiller plant manager (multi-chiller sequencer)
Equipment type
Chillers
BACnet objects
462 (34 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1
Also known as
iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03
Source document
BAS Integration guide - BACnet protocol (iCM, Option 184) · D-EIGOC00110-21_03EN · rev. 2023-11
Download CSV 462 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)

Integration in brief

Read the plant view from the master chiller: system run state, common leaving water temperature, active setpoint, load and the state of each chiller. Write only the few plant settings exposed (master enable, staging priorities, standby unit, pump/tower network setpoints) and use the alarm reset MVs. Start/stop and setpoints for individual chillers are not in this list.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1324MasterEnablingSpMaster unit enable (1 = Disable, 2 = Enable)Write
MV 1448EvapPM'ClearAlmReset evaporator pump manager alarms (2 = Reset)Write
MV 1100SysOpStaPlant run state (Stop / Run)Read
AI 1103CommonLWTCommon leaving chilled water temperatureRead
AV 1107SysActSpActive plant setpointRead
AV 1112SystemLoadPlant load, %Read
MV 1136MasterData'StateMaster chiller state, incl. Alarm / ComErrRead
MV 1154S1StateSlave 1 state; S2State-S7State followRead
MV 1354EvapPM'GenAlmEvaporator pump manager general alarmRead
MV 1445ConfigErrReasonPlant configuration alarm reason (1 = None)Read

Enable & remote start

The guide exposes no plant start/stop or plant setpoint object. MasterEnablingSp (MV 1324) enables or disables the master unit, and the per-unit cooling/heating priorities (MV 1325-1340) and StandbyChillerSp (MV 51) set the staging; the guide does not describe how the plant itself is enabled from a BMS.

Sensors & values from the BMS

Pump speed and bypass control take network setpoints (AV 1370/1373/1376/1382/1385 evaporator, AV 1411/1414/1417/1422/1425 condenser) and the tower leaving water control takes iCT'LwtCtrl'SpNtwk (AV 1462); the guide does not say how these are selected over the local values.

Network setup

Watch out for

Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

462 of 462 shown
Type
BinaryMulti-state
Access
Show
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet Points List
DescriptionStates
MVmin1100SysOpStaSystem Operating StateRead0=NULL, 1=Stop, 2=Run
MV1101SCMTypeSCM typeRead0=NULL, 1=Mst/Slv, 2=iCM_Std, 3=iCM_Adv
MV1102ConfigTypeConfiguration typeRead0=NULL, 1=Undef, 2=OnlyC/O, 3=OnlyH/P, 4=C/O_H/P, 5=Only4P, 6=4P_C/O
AImin1103CommonLWTSystem Cooling leaving water temp.°CRead
AI1104HeatLWTSystem heating leaving water temp.°CRead
AV1105AvgEEWTSystem avg evaporator entering water temp.°CRead
AV1106AvgCEWTSystem avg condenser entering water temp.°CRead
AV151SysCtrlTmpSystem controlled temp.°CRead
AV252SysCtrlHeatSystem controlled heat temp.°CRead
AVmin1107SysActSpSystem actual setpoint°CRead
AV1108SysHeatSpSystem heat setpoint°CRead
MV1109NextChillerOnNext chiller onRead0=NULL, 1=None, 2=Master, 3=Slave 1, 4=Slave 2, 5=Slave 3, 6=Slave 4, 7=Slave 5, 8=Slave 6, 9=Slave 7
MV1110NextChillerOffNext chiller offRead0=NULL, 1=None, 2=Master, 3=Slave 1, 4=Slave 2, 5=Slave 3, 6=Slave 4, 7=Slave 5, 8=Slave 6, 9=Slave 7
MV1111StandbyChillerValStandby chiller ValueRead0=NULL, 1=None, 2=Master, 3=Slave 1, 4=Slave 2, 5=Slave 3, 6=Slave 4, 7=Slave 5, 8=Slave 6, 9=Slave 7
AVmin1112SystemLoadSystem load%Read
AV1113CoolingLoadCooling load%Read
AV1114HeatingLoadHeating load%Read
AV1115SysDemandLimitSystem Demand Limit Value%Read
MV1116SysDemandLimitOpStaSystem Demand Limit Operating StateRead0=NULL, 1=No, 2=Yes
MV1117EnergyMonConfiguredEnergy monitoring configuredRead0=NULL, 1=N/Cfgd, 2=Cfgd
MV1118HeatRecConfiguredHeat recovery configuredRead0=NULL, 1=N/Cfgd, 2=Cfgd
MV1119MasterData'ActModeMaster - Actual modeRead0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi
MV1120MasterData'CurrentModeC1Master - Circuit #1 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1121MasterData'LoadC1Master - Circuit #1 Load%Read
AV1122MasterData'StartsC1Master - Circuit #1 No. startsRead
AV1123MasterData'RunHoursC1Master - Circuit #1 Run hoursRead
MV1124MasterData'CurrentModeC2Master - Circuit #2 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1125MasterData'LoadC2Master - Circuit #2 Load%Read
AV1126MasterData'StartsC2Master - Circuit #2 No. startsRead
AV1127MasterData'RunHoursC2Master - Circuit #2 Run hoursRead
AV1128MasterData'CEWTMaster - Condenser entering water temp.°CRead
AV1129MasterData'CLWTMaster - Condenser leaving water temp.°CRead
AV1130MasterData'EEWTMaster - Evaporator entering water temp.°CRead
AV1131MasterData'ELWTMaster - Evaporator leaving water temp.°CRead
AV1132MasterData'LoadMaster - Load%Read
AV1133MasterData'StartsMaster - No. startsRead
AV1134MasterData'RunHoursMaster - Run hoursRead
MV1135MasterData'StandAloneMaster - StandaloneRead0=NULL, 1=No, 2=Yes
MVmin1136MasterData'StateMaster - StateRead0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd
MV1137SlaveData1'ActModeSlave #1 - Actual modeRead0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi
MV1138SlaveData1'CurrentModeC1Slave #1 - Circuit #1 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1139SlaveData1'LoadC1Slave #1 - Circuit #1 Load%Read
AV1140SlaveData1'StartsC1Slave #1 - Circuit #1 No. startsRead
AV1141SlaveData1'RunHoursC1Slave #1 - Circuit #1 Run hoursRead
MV1142SlaveData1'CurrentModeC2Slave #1 - Circuit #2 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1143SlaveData1'LoadC2Slave #1 - Circuit #2 Load%Read
AV1144SlaveData1'StartsC2Slave #1 - Circuit #2 No. startsRead
AV1145SlaveData1'RunHoursC2Slave #1 - Circuit #2 Run hoursRead
AV1146SlaveData1'CEWTSlave #1 - Condenser entering water temp.°CRead
AV1147SlaveData1'CLWTSlave #1 - Condenser leaving water temp.°CRead
AV1148SlaveData1'EEWTSlave #1 - Evaporator entering water temp.°CRead
AV1149SlaveData1'ELWTSlave #1 - Evaporator leaving water temp.°CRead
AV1150SlaveData1'LoadSlave #1 - Load%Read
AV1151SlaveData1'StartsSlave #1 - No. startsRead
AV1152SlaveData1'RunHoursSlave #1 - Run hoursRead
MV1153SlaveData1'StandAloneSlave #1 - StandaloneRead0=NULL, 1=No, 2=Yes
MVmin1154S1StateSlave #1 - StateRead0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd
MV1155SlaveData2'ActModeSlave #2 - Actual modeRead0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi
MV1156SlaveData2'CurrentModeC1Slave #2 - Circuit #1 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1157SlaveData2'LoadC1Slave #2 - Circuit #1 Load%Read
AV1158SlaveData2'StartsC1Slave #2 - Circuit #1 No. startsRead
AV1159SlaveData2'RunHoursC1Slave #2 - Circuit #1 Run hoursRead
MV1160SlaveData2'CurrentModeC2Slave #2 - Circuit #2 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1161SlaveData2'LoadC2Slave #2 - Circuit #2 Load%Read
AV1162SlaveData2'StartsC2Slave #2 - Circuit #2 No. startsRead
AV1163SlaveData2'RunHoursC2Slave #2 - Circuit #2 Run hoursRead
AV1164SlaveData2'CEWTSlave #2 - Condenser entering water temp.°CRead
AV1165SlaveData2'CLWTSlave #2 - Condenser leaving water temp.°CRead
AV1166SlaveData2'EEWTSlave #2 - Evaporator entering water temp.°CRead
AV1167SlaveData2'ELWTSlave #2 - Evaporator leaving water temp.°CRead
AV1168SlaveData2'LoadSlave #2 - Load%Read
AV1169SlaveData2'StartsSlave #2 - No. startsRead
AV1170SlaveData2'RunHoursSlave #2 - Run hoursRead
MV1171SlaveData2'StandAloneSlave #2 - StandaloneRead0=NULL, 1=No, 2=Yes
MV1172S2StateSlave #2 - StateRead0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd
MV1173SlaveData3'ActModeSlave #3 - Actual modeRead0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi
MV1174SlaveData3'CurrentModeC1Slave #3 - Circuit #1 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1175SlaveData3'LoadC1Slave #3 - Circuit #1 Load%Read
AV1176SlaveData3'StartsC1Slave #3 - Circuit #1 No. startsRead
AV1177SlaveData3'RunHoursC1Slave #3 - Circuit #1 Run hoursRead
MV1178SlaveData3'CurrentModeC2Slave #3 - Circuit #2 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1179SlaveData3'LoadC2Slave #3 - Circuit #2 Load%Read
AV1180SlaveData3'StartsC2Slave #3 - Circuit #2 No. startsRead
AV1181SlaveData3'RunHoursC2Slave #3 - Circuit #2 Run hoursRead
AV1182SlaveData3'CEWTSlave #3 - Condenser entering water temp.°CRead
AV1183SlaveData3'CLWTSlave #3 - Condenser leaving water temp.°CRead
AV1184SlaveData3'EEWTSlave #3 - Evaporator entering water temp.°CRead
AV1185SlaveData3'ELWTSlave #3 - Evaporator leaving water temp.°CRead
AV1186SlaveData3'LoadSlave #3 - Load%Read
AV1187SlaveData3'StartsSlave #3 - No. startsRead
AV1188SlaveData3'RunHoursSlave #3 - Run hoursRead
MV1189SlaveData3'StandAloneSlave #3 - StandaloneRead0=NULL, 1=No, 2=Yes
MV1190S3StateSlave #3 - StateRead0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd
MV1191SlaveData4'ActModeSlave #4 - Actual modeRead0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi
MV1192SlaveData4'CurrentModeC1Slave #4 - Circuit #1 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1193SlaveData4'LoadC1Slave #4 - Circuit #1 Load%Read
AV1194SlaveData4'StartsC1Slave #4 - Circuit #1 No. startsRead
AV1195SlaveData4'RunHoursC1Slave #4 - Circuit #1 Run hoursRead
MV1196SlaveData4'CurrentModeC2Slave #4 - Circuit #2 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1197SlaveData4'LoadC2Slave #4 - Circuit #2 Load%Read
AV1198SlaveData4'StartsC2Slave #4 - Circuit #2 No. startsRead
AV1199SlaveData4'RunHoursC2Slave #4 - Circuit #2 Run hoursRead
AV1200SlaveData4'CEWTSlave #4 - Condenser entering water temp.°CRead
AV1201SlaveData4'CLWTSlave #4 - Condenser leaving water temp.°CRead
AV1202SlaveData4'EEWTSlave #4 - Evaporator entering water temp.°CRead
AV1203SlaveData4'ELWTSlave #4 - Evaporator leaving water temp.°CRead
AV1204SlaveData4'LoadSlave #4 - Load%Read
AV1205SlaveData4'StartsSlave #4 - No. startsRead
AV1206SlaveData4'RunHoursSlave #4 - Run hoursRead
MV1207SlaveData4'StandAloneSlave #4 - StandaloneRead0=NULL, 1=No, 2=Yes
MV1208S4StateSlave #4 - StateRead0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd
MV1209SlaveData5'ActModeSlave #5 - Actual modeRead0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi
MV1210SlaveData5'CurrentModeC1Slave #5 - Circuit #1 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1211SlaveData5'LoadC1Slave #5 - Circuit #1 Load%Read
AV1212SlaveData5'StartsC1Slave #5 - Circuit #1 No. startsRead
AV1213SlaveData5'RunHoursC1Slave #5 - Circuit #1 Run hoursRead
MV1214SlaveData5'CurrentModeC2Slave #5 - Circuit #2 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1215SlaveData5'LoadC2Slave #5 - Circuit #2 Load%Read
AV1216SlaveData5'StartsC2Slave #5 - Circuit #2 No. startsRead
AV1217SlaveData5'RunHoursC2Slave #5 - Circuit #2 Run hoursRead
AV1218SlaveData5'CEWTSlave #5 - Condenser entering water temp.°CRead
AV1219SlaveData5'CLWTSlave #5 - Condenser leaving water temp.°CRead
AV1220SlaveData5'EEWTSlave #5 - Evaporator entering water temp.°CRead
AV1221SlaveData5'ELWTSlave #5 - Evaporator leaving water temp.°CRead
AV1222SlaveData5'LoadSlave #5 - Load%Read
AV1223SlaveData5'StartsSlave #5 - No. startsRead
AV1224SlaveData5'RunHoursSlave #5 - Run hoursRead
MV1225SlaveData5'StandAloneSlave #5 - StandaloneRead0=NULL, 1=No, 2=Yes
MV1226S5StateSlave #5 - StateRead0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd
MV1227SlaveData6'ActModeSlave #6 - Actual modeRead0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi
MV1228SlaveData6'CurrentModeC1Slave #6 - Circuit #1 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1229SlaveData6'LoadC1Slave #6 - Circuit #1 Load%Read
AV1230SlaveData6'StartsC1Slave #6 - Circuit #1 No. startsRead
AV1231SlaveData6'RunHoursC1Slave #6 - Circuit #1 Run hoursRead
MV1232SlaveData6'CurrentModeC2Slave #6 - Circuit #2 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1233SlaveData6'LoadC2Slave #6 - Circuit #2 Load%Read
AV1234SlaveData6'StartsC2Slave #6 - Circuit #2 No. startsRead
AV1235SlaveData6'RunHoursC2Slave #6 - Circuit #2 Run hoursRead
AV1236SlaveData6'CEWTSlave #6 - Condenser entering water temp.°CRead
AV1237SlaveData6'CLWTSlave #6 - Condenser leaving water temp.°CRead
AV1238SlaveData6'EEWTSlave #6 - Evaporator entering water temp.°CRead
AV1239SlaveData6'ELWTSlave #6 - Evaporator leaving water temp.°CRead
AV1240SlaveData6'LoadSlave #6 - Load%Read
AV1241SlaveData6'StartsSlave #6 - No. startsRead
AV1242SlaveData6'RunHoursSlave #6 - Run hoursRead
MV1243SlaveData6'StandAloneSlave #6 - StandaloneRead0=NULL, 1=No, 2=Yes
MV1244S6StateSlave #6 - StateRead0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd
MV1245SlaveData7'ActModeSlave #7 - Actual modeRead0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi
MV1246SlaveData7'CurrentModeC1Slave #7 - Circuit #1 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1247SlaveData7'LoadC1Slave #7 - Circuit #1 Load%Read
AV1248SlaveData7'StartsC1Slave #7 - Circuit #1 No. startsRead
AV1249SlaveData7'RunHoursC1Slave #7 - Circuit #1 Run hoursRead
MV1250SlaveData7'CurrentModeC2Slave #7 - Circuit #2 Current modeRead0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd
AV1251SlaveData7'LoadC2Slave #7 - Circuit #2 Load%Read
AV1252SlaveData7'StartsC2Slave #7 - Circuit #2 No. startsRead
AV1253SlaveData7'RunHoursC2Slave #7 - Circuit #2 Run hoursRead
AV1254SlaveData7'CEWTSlave #7 - Condenser entering water temp.°CRead
AV1255SlaveData7'CLWTSlave #7 - Condenser leaving water temp.°CRead
AV1256SlaveData7'EEWTSlave #7 - Evaporator entering water temp.°CRead
AV1257SlaveData7'ELWTSlave #7 - Evaporator leaving water temp.°CRead
AV1258SlaveData7'LoadSlave #7 - Load%Read
AV1259SlaveData7'StartsSlave #7 - No. startsRead
AV1260SlaveData7'RunHoursSlave #7 - Run hoursRead
MV1261SlaveData7'StandAloneSlave #7 - StandaloneRead0=NULL, 1=No, 2=Yes
MV1262S7StateSlave #7 - StateRead0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd
AV1263SysPoweElSystem electrical powerMWRead
AV1264SysPowerThermSystem thermal powerMWRead
AV1265SysCOPSystem COPRead
MV1266MasterData'EnergyMonCfgdMaster - Energy monitoring configuredRead0=NULL, 1=N/Cfgd, 2=Cfgd
AV1267MasterData'PowerThermMaster - Thermal powerkWRead
AV1268MasterData'PowerElMaster - Electrical powerkWRead
AV1270SlaveData1'PowerThermSlave #1 - Thermal powerkWRead
AV1271SlaveData1'PowerElSlave #1 - Electrical powerkWRead
AV1273SlaveData2'PowerThermSlave #2 - Thermal powerkWRead
AV1274SlaveData2'PowerElSlave #2 - Electrical powerkWRead
AV1276SlaveData3'PowerThermSlave #3 - Thermal powerkWRead
AV1277SlaveData3'PowerElSlave #3 - Electrical powerkWRead
AV1279SlaveData4'PowerThermSlave #4 - Thermal powerkWRead
AV1280SlaveData4'PowerElSlave #4 - Electrical powerkWRead
AV1282SlaveData5'PowerThermSlave #5 - Thermal powerkWRead
AV1283SlaveData5'PowerElSlave #5 - Electrical powerkWRead
AV1285SlaveData6'PowerThermSlave #6 - Thermal powerkWRead
AV1286SlaveData6'PowerElSlave #6 - Electrical powerkWRead
AV1288SlaveData7'PowerThermSlave #7 - Thermal powerkWRead
AV1289SlaveData7'PowerElSlave #7 - Electrical powerkWRead
MV1290SysHeatRecOpStaSystem Heat recovery operating stateRead0=NULL, 1=Stop, 2=Run
AV1291AvgHeatRecEWTAverage Heat Recovery Entering Water temp.°CRead
MV1292MasterData'HeatRecCfgdMaster - Heat recovery configuredRead0=NULL, 1=N/Cfgd, 2=Cfgd
MV1293MasterData'HeatRecRunMaster - Heat recovery stateRead0=NULL, 1=Stop, 2=Run
AV1294MasterData'HeatRecEWTMaster - Heat recovery entering water temp.°CRead
MV1295SlaveData1'HeatRecRunSlave #1 - Heat recovery stateRead0=NULL, 1=Stop, 2=Run
AV1296SlaveData1'HeatRecEWTSlave #1 - Heat recovery entering water temp.°CRead
MV1297SlaveData2'HeatRecRunSlave #2 - Heat recovery stateRead0=NULL, 1=Stop, 2=Run
AV1298SlaveData2'HeatRecEWTSlave #2 - Heat recovery entering water temp.°CRead
MV1299SlaveData3'HeatRecRunSlave #3 - Heat recovery stateRead0=NULL, 1=Stop, 2=Run
AV1300SlaveData3'HeatRecEWTSlave #3 - Heat recovery entering water temp.°CRead
MV1301SlaveData4'HeatRecRunSlave #4 - Heat recovery stateRead0=NULL, 1=Stop, 2=Run
AV1302SlaveData4'HeatRecEWTSlave #4 - Heat recovery entering water temp.°CRead
MV1303SlaveData5'HeatRecRunSlave #5 - Heat recovery stateRead0=NULL, 1=Stop, 2=Run
AV1304SlaveData5'HeatRecEWTSlave #5 - Heat recovery entering water temp.°CRead
MV1305SlaveData6'HeatRecRunSlave #6 - Heat recovery stateRead0=NULL, 1=Stop, 2=Run
AV1306SlaveData6'HeatRecEWTSlave #6 - Heat recovery entering water temp.°CRead
MV1307SlaveData7'HeatRecRunSlave #7 - Heat recovery stateRead0=NULL, 1=Stop, 2=Run
AV1308SlaveData7'HeatRecEWTSlave #7 - Heat recovery entering water temp.°CRead
MV1309SysFreeClgStaFreecooling StatusRead0=NULL, 1=Off:Switch, 2=WaitOAT, 3=Run, 4=Off:Alarm
AV1310SysOATSystem Outside Air Temperature°CRead
MV1311MasterData'FreeClgCfgdMaster - Freecooling configuredRead0=NULL, 1=N/Cfgd, 2=Cfgd
MV1312MasterData'FreeClgAvailMaster - Freecooling availableRead0=NULL, 1=N/Avail, 2=Avail
MV1313MasterData'FreeClgModeMaster - Freecooling ModeRead0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All
MV1314SlaveData1'FreeClgModeSlave #1 - Freecooling ModeRead0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All
MV1315SlaveData2'FreeClgModeSlave #2 - Freecooling ModeRead0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All
MV1316SlaveData3'FreeClgModeSlave #3 - Freecooling ModeRead0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All
MV1317SlaveData4'FreeClgModeSlave #4 - Freecooling ModeRead0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All
MV1318SlaveData5'FreeClgModeSlave #5 - Freecooling ModeRead0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All
MV1319SlaveData6'FreeClgModeSlave #6 - Freecooling ModeRead0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All
MV1320SlaveData7'FreeClgModeSlave #7 - Freecooling ModeRead0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All
MV5StandaloneSpStandalone Mode SetpointWrite0=NULL, 1=No, 2=Yes
MVmin1324MasterEnablingSpMaster enablingWrite0=NULL, 1=Disable, 2=Enable
MV1325Master'PriorityMaster - Priority (Cooling mode) (1-8)Write
MV1326Master'PrioHeatMaster - Priority (Heating mode) (1-8)Write
MV1327Slave1'PrioritySlave #1 - Priority (Cooling mode) (1-8)Write
MV1328Slave1'PrioHeatSlave #1 - Priority (Heating mode) (1-8)Write
MV1329Slave2'PrioritySlave #2 - Priority (Cooling mode) (1-8)Write
MV1330Slave2'PrioHeatSlave #2 - Priority (Heating mode) (1-8)Write
MV1331Slave3'PrioritySlave #3 - Priority (Cooling mode) (1-8)Write
MV1332Slave3'PrioHeatSlave #3 - Priority (Heating mode) (1-8)Write
MV1333Slave4'PrioritySlave #4 - Priority (Cooling mode) (1-8)Write
MV1334Slave4'PrioHeatSlave #4 - Priority (Heating mode) (1-8)Write
MV1335Slave5'PrioritySlave #5 - Priority (Cooling mode) (1-8)Write
MV1336Slave5'PrioHeatSlave #5 - Priority (Heating mode) (1-8)Write
MV1337Slave6'PrioritySlave #6 - Priority (Cooling mode) (1-8)Write
MV1338Slave6'PrioHeatSlave #6 - Priority (Heating mode) (1-8)Write
MV1339Slave7'PrioritySlave #7 - Priority (Cooling mode) (1-8)Write
MV1340Slave7'PrioHeatSlave #7 - Priority (Heating mode) (1-8)Write
MV51StandbyChillerSpStandby Unit SetpointWrite0=NULL, 1=No, 2=Auto, 3=Master, 4=Slave 1, 5=Slave 2, 6=Slave 3, 7=Slave 4, 8=Slave 5, 9=Slave 6, 10=Slave 7
MV1341StandbyTmpCompStandby temp compensationWrite0=NULL, 1=No, 2=Yes
MV1342MstUnitTypeMaster - Unit typeRead0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif
MV1343S1UnitTypeSlave #1 - Unit typeRead0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif
MV1344S2UnitTypeSlave #2 - Unit typeRead0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif
MV1345S3UnitTypeSlave #3 - Unit typeRead0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif
MV1346S4UnitTypeSlave #4 - Unit typeRead0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif
MV1347S5UnitTypeSlave #5 - Unit typeRead0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif
MV1348S6UnitTypeSlave #6 - Unit typeRead0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif
MV1349S7UnitTypeSlave #7 - Unit typeRead0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif
AV1350EvapPM'ApplVersEvap PM - Application VersionRead
MV1351EvapPM'NrPumpsCfgdEvap PM - Number of Pump (1-10)Read
MV1352EvapPM'StatusEvap PM - StatusRead0=NULL, 1=Off:Auto, 2=On:Auto, 3=Off:Local, 4=Off:SensAlarm, 5=On:SensAlarm, 6=Off:CommErr, 7=On:CommErr, 8=Configuration, 9=Off:ConfigAlarm
MV1353EvapPM'OpStaEvap PM - Operating stateRead0=NULL, 1=Stop, 2=Run
MVmin1354EvapPM'GenAlmEvap PM - General AlarmRead0=NULL, 1=None, 2=Active
MV1355EvapPM'StatusP1Evap Pump #1 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1356EvapPM'StatusP2Evap Pump #2 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1357EvapPM'StatusP3Evap Pump #3 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1358EvapPM'StatusP4Evap Pump #4 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1359EvapPM'StatusP5Evap Pump #5 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1360EvapPM'StatusP6Evap Pump #6 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1361EvapPM'StatusP7Evap Pump #7 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1362EvapPM'StatusP8Evap Pump #8 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1363EvapPM'StatusP9Evap Pump #9 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1364EvapPM'StatusP10Evap Pump #10 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
AV1365EvapPM'NrPumpRunEvap Pumps - RunningRead
MV1366EvapPM'SpeedEvap Pumps - Speed%Read
MV1367EvapPM'SpdCtrlTypeEvap PM - Speed Control TypeRead0=NULL, 1=Constant, 2=Dtemp, 3=DifPres, 4=AbsPres
AV1368EvapPM'SpdCtrl'DeltaTEvap Speed Control - Delta TempdKRead
AV1369EvapPM'SpdCtrl'DeltaTActSpEvap Speed Control - Actual SetpointdKRead
AV1370EvapPM'SpdCtrl'DeltaTSpNtwkEvap Speed Control - Setpoint NetworkdKWrite
AV1371EvapPM'SpdCtrl'DifPressEvap Speed Control - Differential PressurekPaRead
AV1372EvapPM'SpdCtrl'DifPressActSpEvap Speed Control - Actual SetpointkPaRead
AV1373EvapPM'SpdCtrl'DifPressSpNtwkEvap Speed Control - Setpoint NetworkkPaWrite
AV1374EvapPM'SpdCtrl'AbsPressEvap Speed Control - Absolute PressurekPaRead
AV1375EvapPM'SpdCtrl'AbsPressActSpEvap Speed Control - Actual SetpointkPaRead
AV1376EvapPM'SpdCtrl'AbsPressSpNtwkEvap Speed Control - Setpoint NetworkkPaWrite
AV1377EvapPM'BypVlvOpngEvaporator Bypass Valve - Opening%Read
MV1378EvapPM'BypVlvCtrlTypeEvap PM - Bypass Valve Control TypeRead0=NULL, 1=None, 2=MinDP, 3=Flow, 4=EvapEwt, 5=CondEwt
BV1379EvapPM'BypVlvCtrl'MinDPonUnitEvap Bypass Control - Min Diff Pressure on UnitsRead0=None, 1=Active
AV1380EvapPM'BypVlvCtrl'FlowEvap Bypass Control - Flowl/sRead
AV1381EvapPM'BypVlvCtrl'FlowActSpEvap Bypass Control - Actual Setpointl/sRead
AV1382EvapPM'BypVlvCtrl'FlowSpNtwkEvap Bypass Control - Setpoint Networkl/sWrite
AV1383EvapPM'BypVlvCtrl'EvapEwtEvap Bypass Control - EWT°CRead
AV1384EvapPM'BypVlvCtrl'EvapEwtActSpEvap Bypass Control - Actual Setpoint°CRead
AV1385EvapPM'BypVlvCtrl'EvapEwtSpNtwkEvap Bypass Control - Setpoint Network°CWrite
MV1386Evap PM'EnergyMeterConfiguredEvap PM - Energy Meter ConfiguredRead0=NULL, 1=N/Cfgd, 2=Cfgd
AV1387EvapPM'ActPwrEvap PM - Electrical Active PowerkWRead
BV1388EvapPM'SpdCtrlSens'AlmEvap Pump Manager - Speed Control sensor alarmRead0=None, 1=Active
BV1389EvapPM'AvailPump'AlmEvap Pump Manager - Available pump alarmRead0=None, 1=Active
BV1390EvapPM'Cfg'AlmEvap Pump Manager - Configuration alarmRead0=None, 1=Active
AV1391CondPM'ApplVersCond PM - Application VersionRead
MV1392CondPM'NrPumpsCfgdCond PM - Number of Pump (1-10)Read
MV1393CondPM'StatusCond PM - StatusRead0=NULL, 1=Off:Auto, 2=On:Auto, 3=Off:Local, 4=Off:SensAlarm, 5=On:SensAlarm, 6=Off:CommErr, 7=On:CommErr, 8=Configuration, 9=Off:ConfigAlarm
MV1394CondPM'OpStaCond PM - Operating stateRead0=NULL, 1=Stop, 2=Run
MV1395CondPM'GenAlmCond PM - General AlarmRead0=NULL, 1=None, 2=Active
MV1396CondPM'StatusP1Cond Pump #1 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1397CondPM'StatusP2Cond Pump #2 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1398CondPM'StatusP3Cond Pump #3 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1399CondPM'StatusP4Cond Pump #4 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1400CondPM'StatusP5Cond Pump #5 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1401CondPM'StatusP6Cond Pump #6 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1402CondPM'StatusP7Cond Pump #7 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1403CondPM'StatusP8Cond Pump #8 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1404CondPM'StatusP9Cond Pump #9 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
MV1405CondPM'StatusP10Cond Pump #10 - StatusRead0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg
AV1406CondPM'NrPumpRunCond Pumps - RunningRead
AV1407CondPM'SpeedCond Pumps - Speed%Read
MV1408CondPM'SpdCtrlTypeCond PM - Speed Control TypeRead0=NULL, 1=Constant, 2=Dtemp, 3=DifPres, 4=AbsPres
AV1409CondPM'SpdCtrl'DeltaTCond Speed Control - Delta TempdKRead
AV1410CondPM'SpdCtrl'DeltaTActSpCond Speed Control - Actual SetpointdKRead
AV1411CondPM'SpdCtrl'DeltaTSpNtwkCond Speed Control - Setpoint NetworkdKWrite
AV1412CondPM'SpdCtrl'DifPressCond Speed Control - Differential PressurekPaRead
AV1413CondPM'SpdCtrl'DifPressActSpCond Speed Control - Actual SetpointkPaRead
AV1414CondPM'SpdCtrl'DifPressSpNtwkCond Speed Control - Setpoint NetworkkPaWrite
AV1415CondPM'SpdCtrl'AbsPressCond Speed Control - Absolute PressurekPaRead
AV1416CondPM'SpdCtrl'AbsPressActSpCond Speed Control - Actual SetpointkPaRead
AV1417CondPM'SpdCtrl'AbsPressSpNtwkCond Speed Control - Setpoint NetworkkPaWrite
AV1418CondPM'BypVlvOpngCondenser Bypass Valve - Opening%Read
MV1419CondPM'BypValveCtrlTypeCond PM - Bypass Valve Control TypeRead0=NULL, 1=None, 2=MinDP, 3=Flow, 4=EvapEwt, 5=CondEwt
AV1420CondPM'BypVlvCtrl'FlowCond Bypass Control - Flowl/sRead
AV1421CondPM'BypVlvCtrl'FlowActSp'Cond Bypass Control - Active Setpointl/sRead
AV1422CondPM'BypVlvCtrl'FlowSpNtwkCond Speed Control - Setpoint Networkl/sWrite
AV1423CondPM'BypVlvCtrl'CondEwtCond Bypass Control - EWT°CRead
AV1424CondPM'BypVlvCtrl'CondEwtActSpCond Bypass Control - Actual Setpoint°CRead
AV1425CondPM'BypVlvCtrl'CondEwtSpNtwkCond Bypass Control - Setpoint Network°CWrite
MV1426CondPM'EnergyMeterConfiguredCond PM - Energy Meter configuredRead0=NULL, 1=N/Cfgd, 2=Cfgd
AV1427CondPM'ActPwrCond PM - Electrical Active PowerkWRead
BV1428CondPM'SpdCtrlSens'AlmCond Pump Manager - Speed Control sensor alarmRead0=None, 1=Active
BV1429CondPM'AvailPump'AlmCond Pump Manager - Available pump alarmRead0=None, 1=Active
BV1430CondPM'Cfg'AlmCond Pump Manager - Configuration alarmRead0=None, 1=Active
BV1431SlaveMstMissingSlave - Master MissingRead0=None, 1=Active
BV1432SlaveMstDisconnectSlave - Master DisconnectedRead0=No, 1=Yes
BV20SlaveMstCommErrSlave - Master Communication ErrorRead0=None, 1=Active
BV1433HeatLWTSenfCommon Leaving Hot water temp. sensor faultRead0=None, 1=Active
BV502CommonLWTSenfCommon Leaving water temp. sensor faultRead0=None, 1=Active
BV21S1CommErrSlave #1 - Communication ErrorRead0=None, 1=Active
BV1434S1MissingSlave #1 - MissingRead0=No, 1=Yes
BV22S2CommErrSlave #2 - Communication ErrorRead0=None, 1=Active
BV1435S2MissingSlave #2 - MissingRead0=No, 1=Yes
BV23S3CommErrSlave #3 - Communication ErrorRead0=None, 1=Active
BV1436S3MissingSlave #3 - MissingRead0=No, 1=Yes
BV1437S4CommErrSlave #4 - Communication ErrorRead0=None, 1=Active
BV1438S4MissingSlave #4 - MissingRead0=No, 1=Yes
BV1439S5CommErrSlave #5 - Communication ErrorRead0=None, 1=Active
BV1440S5MissingSlave #5 - MissingRead0=No, 1=Yes
BV1441S6CommErrSlave #6 - Communication ErrorRead0=None, 1=Active
BV1442S6MissingSlave #6 - MissingRead0=No, 1=Yes
BV1443S7CommErrSlave #7 - Communication ErrorRead0=None, 1=Active
BV1444S7MissingSlave #7 - MissingRead0=No, 1=Yes
MVmin1445ConfigErrReasonConfiguration AlarmRead0=NULL, 1=None, 2=ModeErr, 3=ComprErr, 4=CooledErr, 5=UnitNotDef, 6=iCMtypeErr
BV1446EnergyMonConfigErrEnergy monitoring configuration ErrorRead0=None, 1=Active
BV1447HeatRecConfigErrHeat recovery configuration ErrorRead0=None, 1=Active
MVmin1448EvapPM'ClearAlmEvap PM - Clear Alarm setpointWrite0=NULL, 1=---, 2=Reset
MV1449CondPM'ClearAlmCond PM - Clear Alarm setpointWrite0=NULL, 1=---, 2=Reset
MV1450iCT'NrTowersCfgdiCT - Tower Number (1-10)Read
MV1451iCT'StatusiCT - StatusRead0=NULL, 1=Off:Auto, 2=On:Auto, 3=Off:Local, 4=Off:SensAlarm, 5=On:SensAlarm, 6=Off:CommErr, 7=On:CommErr, 8=Configuration, 9=Off:ConfigAlarm
MV1452iCT'OpStaiCT - Operating StateRead0=NULL, 1=Stop, 2=Run
MV1453iCT'GenAlmiCT - General AlarmRead0=NULL, 1=None, 2=Active
AV1454iCT'NrTwrRuniCT - Number of Running TowerRead
MV1455iCT'NxOnTwriCT - Next On Tower (0-10)Read
MV1456iCT'NxOffTwriCT - Next Off TowerRead0=NULL, 1=None, 2=CT1, 3=CT2, 4=CT3, 5=CT4, 6=CT5, 7=CT6, 8=CT7, 9=CT8, 10=CT9, 11=CT10
AV1457iCT'LwtiCT - Leaving Water Termperature°CRead
BV1458iCT'LwtSens'Alm'iCT - LWT sernsor AlarmRead0=None, 1=Active
MV1459iCT'LwtSpRstTypeiCT LWT Control - Setpoint Reset typeRead0=NULL, 1=None, 2=Ouside Air T, 3=Web Bulb T
AV1460iCT'LwtCtrl'ActSpiCT LWT Control - Actual Setpoint°CRead
AV1461iCT'LwtCtrl'SpLociCT LWT Control - Setpoint iCM°CRead
AV1462iCT'LwtCtrl'SpNtwkiCT LWT Control - Setpoint Network°CWrite
AV1463iCT'ToaiCT - Outside Air Temperature°CRead
AV1464iCT'HuRiCT - Outside Relative Humidity%r.HRead
AV1465iCT'LwtCtrl'TwbiCT - Outside Wet Bulb Temperature°CRead
MV1466iCT'Twr1'StatusCooling Tower 1 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1467iCT'Twr1'FanStaCooling Tower 1 - Fan StatusRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1468iCT'Twr1'FanSpeedCooling Tower 1 - Fan Speed%Read
MV1469iCT'Twr1'InVlvStaCooling Tower 1 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1470iCT'Twr1'LwtCooling Tower 1 - LWT°CRead
BV1471iCT'Twr1'LwtSens'AlmCooling Tower 1 - LWT AlarmRead0=None, 1=Active
MV1472iCT'Twr2'StatusCooling Tower 2 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1473iCT'Twr2'FanStaCooling Tower 2 - Fan StatusRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1474iCT'Twr2'FanSpeedCooling Tower 2 - Fan Speed%Read
MV1475iCT'Twr2'InVlvStaCooling Tower 2 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1476iCT'Twr2'LwtCooling Tower 2 - LWT°CRead
BV1477iCT'Twr2'LwtSens'AlmCooling Tower 2 - LWT AlarmRead0=None, 1=Active
MV1478iCT'Twr3'StatusCooling Tower 3 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1479iCT'Twr3'FanStaCooling Tower 3 - Fan StatusRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1480iCT'Twr3'FanSpeedCooling Tower 3 - Fan Speed%Read
MV1481iCT'Twr3'InVlvStaCooling Tower 3 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1482iCT'Twr3'LwtCooling Tower 3 - LWT°CRead
BV1483iCT'Twr3'LwtSens'AlmCooling Tower 3 - LWT AlarmRead0=None, 1=Active
MV1484iCT'Twr4'StatusCooling Tower 4 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1485iCT'Twr4'FanStaCooling Tower 4 - Fan StausRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1486iCT'Twr4'FanSpeedCooling Tower 4 - Fan Speed%Read
MV1487iCT'Twr4'InVlvStaCooling Tower 4 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1488iCT'Twr4'LwtCooling Tower 4 - LWT°CRead
BV1489iCT'Twr4'LwtSens'AlmCooling Tower 4 - LWT AlarmRead0=None, 1=Active
MV1490iCT'Twr5'StatusCooling Tower 5 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1491iCT'Twr5'FanStaCooling Tower 5 - Fan StausRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1492iCT'Twr5'FanSpeedCooling Tower 5 - Fan Speed%Read
MV1493iCT'Twr5'InVlvStaCooling Tower 5 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1494iCT'Twr5'LwtCooling Tower 5 - LWT°CRead
BV1495iCT'Twr5'LwtSens'AlmCooling Tower 5 - LWT AlarmRead0=None, 1=Active
MV1496iCT'Twr6'StatusCooling Tower 6 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1497iCT'Twr6'FanStaCooling Tower 6 - Fan StausRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1498iCT'Twr6'FanSpeedCooling Tower 6 - Fan Speed%Read
MV1499iCT'Twr6'InVlvStaCooling Tower 6 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1500iCT'Twr6'LwtCooling Tower 6 - LWT°CRead
BV1501iCT'Twr6'LwtSens'AlmCooling Tower 6 - LWT AlarmRead0=None, 1=Active
MV1502iCT'Twr7'StatusCooling Tower 7 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1503iCT'Twr7'FanStaCooling Tower 7 - Fan StausRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1504iCT'Twr7'FanSpeedCooling Tower 7 - Fan Speed%Read
MV1505iCT'Twr7'InVlvStaCooling Tower 7 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1506iCT'Twr7'LwtCooling Tower 7 - LWT°CRead
BV1507iCT'Twr7'LwtSens'AlmCooling Tower 7 - LWT AlarmRead0=None, 1=Active
MV1508iCT'Twr8'StatusCooling Tower 8 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1509iCT'Twr8'FanStaCooling Tower 8 - Fan StausRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1510iCT'Twr8'FanSpeedCooling Tower 8 - Fan Speed%Read
MV1511iCT'Twr8'InVlvStaCooling Tower 8 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1512iCT'Twr8'LwtCooling Tower 8 - LWT°CRead
BV1513iCT'Twr8'LwtSens'AlmCooling Tower 8 - LWT AlarmRead0=None, 1=Active
MV1514iCT'Twr9'StatusCooling Tower 9 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1515iCT'Twr9'FanStaCooling Tower 9 - Fan StausRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1516iCT'Twr9'FanSpeedCooling Tower 9 - Fan Speed%Read
MV1517iCT'Twr9'InVlvStaCooling Tower 9 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1518iCT'Twr9'LwtCooling Tower 9 - LWT°CRead
BV1519iCT'Twr9'LwtSens'AlmCooling Tower 9 - LWT AlarmRead0=None, 1=Active
MV1520iCT'Twr10'StatusCooling Tower 10 - StatusRead0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr
MV1521iCT'Twr10'FanStaCooling Tower 10 - Fan StausRead0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test
AV1522iCT'Twr10'FanSpeedCooling Tower 10 - Fan Speed%Read
MV1523iCT'Twr10'InVlvStaCooling Tower 10 - Inlet Valve StatusRead0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test
AV1524iCT'Twr10'LwtCooling Tower 10 - LWT°CRead
BV1525iCT'Twr10'LwtSens'AlmCooling Tower 10 - LWT AlarmRead0=None, 1=Active
MV1526iCT'ClearAlmiCT - Clear AlarmWrite0=NULL, 1=---, 2=Reset
BV1527MasterComm'iCT'Comm'AlmiCT - CommErrorRead0=None, 1=Active
BV1528iCT'BrdsMBComm'AlmiCT - Borads CommErrorRead0=None, 1=Active
MV1529ModeChgovrMngtMode Changeover managementRead0=NULL, 1=N/Mngd, 2=Mngd
MV1530DefrMngtDefrost ManagementRead0=NULL, 1=N/Mngd, 2=Mngd
MV1531MasterData'DfrstOpStaC1Master - Circuit #1 DefrostRead0=NULL, 1=None, 2=Defrost
MV1532MasterData'DfrstOpStaC2Master - Circuit #2 DefrostRead0=NULL, 1=None, 2=Defrost
MV1533SlaveData1'DfrstOpStaC1Slave #1 - Circuit #1 DefrostRead0=NULL, 1=None, 2=Defrost
MV1534SlaveData1'DfrstOpStaC2Slave #1 - Circuit #2 DefrostRead0=NULL, 1=None, 2=Defrost
MV1535SlaveData2'DfrstOpStaC1Slave #2 - Circuit #1 DefrostRead0=NULL, 1=None, 2=Defrost
MV1536SlaveData2'DfrstOpStaC2Slave #2 - Circuit #2 DefrostRead0=NULL, 1=None, 2=Defrost
MV1537SlaveData3'DfrstOpStaC1Slave #3 - Circuit #1 DefrostRead0=NULL, 1=None, 2=Defrost
MV1538SlaveData3'DfrstOpStaC2Slave #3 - Circuit #2 DefrostRead0=NULL, 1=None, 2=Defrost
MV1539SlaveData4'DfrstOpStaC1Slave #4 - Circuit #1 DefrostRead0=NULL, 1=None, 2=Defrost
MV1540SlaveData4'DfrstOpStaC2Slave #4 - Circuit #2 DefrostRead0=NULL, 1=None, 2=Defrost
MV1541SlaveData5'DfrstOpStaC1Slave #5 - Circuit #1 DefrostRead0=NULL, 1=None, 2=Defrost
MV1542SlaveData5'DfrstOpStaC2Slave #5 - Circuit #2 DefrostRead0=NULL, 1=None, 2=Defrost
MV1543SlaveData6'DfrstOpStaC1Slave #6 - Circuit #1 DefrostRead0=NULL, 1=None, 2=Defrost
MV1544SlaveData6'DfrstOpStaC2Slave #6 - Circuit #2 DefrostRead0=NULL, 1=None, 2=Defrost
MV1545SlaveData7'DfrstOpStaC1Slave #7 - Circuit #1 DefrostRead0=NULL, 1=None, 2=Defrost
MV1546SlaveData7'DfrstOpStaC2Slave #7 - Circuit #2 DefrostRead0=NULL, 1=None, 2=Defrost
AV1551iSM'TotCoolThermPwriSMs - Total cooling thermal powerkWRead
AV1553iSM'TotHeatThermPwriSMs - Total heating thermal powerkWRead
MV1555iSM01'PmpGrp01'StatusiSM01 - Pump Group 1 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1556iSM01'PmpGrp02'StatusiSM01 - Pump Group 2 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1557iSM01'PmpGrp03'StatusiSM01 - Pump Group 3 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1558iSM01'PmpGrp04'StatusiSM01 - Pump Group 4 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1559iSM02'PmpGrp01'StatusiSM02 - Pump Group 1 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1560iSM02'PmpGrp02'StatusiSM03 - Pump Group 2 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1561iSM02'PmpGrp03'StatusiSM02 - Pump Group 3 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1562iSM02'PmpGrp04'StatusiSM02 - Pump Group 4 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1563iSM03'PmpGrp01'StatusiSM03 - Pump Group 1 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1564iSM03'PmpGrp02'StatusiSM03 - Pump Group 2 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1565iSM03'PmpGrp03'StatusiSM03 - Pump Group 3 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
MV1566iSM03'PmpGrp04'StatusiSM02 - Pump Group 4 - StatusRead0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network
BV1567iCM1st'ComErriCM2ndiCM Expanded: BACnet Communication error w/2ndRead0=None, 1=Active
BV1568iCM2nd'ComErriCM1stiCM Expanded: BACnet Communication error w/1stRead0=None, 1=Active

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the iCM chiller plant manager, option 184 (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)

How many BACnet points does the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) have?

This list has 462 BACnet objects: 2 analog inputs, 212 analog values, 43 binary values, 205 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet points are writable?

34 of the 462 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet documentation?

The source is BAS Integration guide - BACnet protocol (iCM, Option 184) (D-EIGOC00110-21_03EN), revision 2023-11, published free by Daikin Applied at https://my.daikin.eu/content/dam/document-library/installation-manuals/iCM_BAS%20Integration%20Guid%20BACNet_D-EIGOC00110-21_English.pdf.

What are the minimum BACnet points to integrate the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)?

Start with MV 1324 MasterEnablingSp (Master unit enable (1 = Disable, 2 = Enable)); MV 1448 EvapPM'ClearAlm (Reset evaporator pump manager alarms (2 = Reset)); MV 1100 SysOpSta (Plant run state (Stop / Run)); AI 1103 CommonLWT (Common leaving chilled water temperature); AV 1107 SysActSp (Active plant setpoint); AV 1112 SystemLoad (Plant load, %); MV 1136 MasterData'State (Master chiller state, incl. Alarm / ComErr); MV 1154 S1State (Slave 1 state; S2State-S7State follow); MV 1354 EvapPM'GenAlm (Evaporator pump manager general alarm); MV 1445 ConfigErrReason (Plant configuration alarm reason (1 = None)).

How do I enable BMS control of the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)?

The guide exposes no plant start/stop or plant setpoint object. MasterEnablingSp (MV 1324) enables or disables the master unit, and the per-unit cooling/heating priorities (MV 1325-1340) and StandbyChillerSp (MV 51) set the staging; the guide does not describe how the plant itself is enabled from a BMS.

Can the BMS supply sensor values to the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)?

Pump speed and bypass control take network setpoints (AV 1370/1373/1376/1382/1385 evaporator, AV 1411/1414/1417/1422/1425 condenser) and the tower leaving water control takes iCT'LwtCtrl'SpNtwk (AV 1462); the guide does not say how these are selected over the local values.

How do I check these points on the real iCM chiller plant manager, option 184 (Daikin Applied Europe)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: BAS Integration guide - BACnet protocol (iCM, Option 184) · D-EIGOC00110-21_03EN · rev. 2023-11. Object names, instances and units are reproduced as published; descriptions are our own.