- iCM chiller plant manager, option 184 (Daikin Applied Europe)
Chiller plant manager (multi-chiller sequencer) · BACnet points list
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet points list
Updated 28 October 2026
iCM is a software option on a MicroTech 4 chiller that makes it the master of a multi-chiller plant: it stages a master and up to seven slaves and tracks system load, demand limit and the standby unit. Version 5.00 also manages evaporator/condenser pumps (iPM), up to ten cooling towers (iCT) and iSM pump groups. BACnet IP or BACnet MS/TP comes from a POL908/POL904 module or the onboard software option on that controller. Most objects are read-only plant data per chiller; writable ones cover master enable, staging priorities, standby unit, pump and tower network setpoints and alarm resets.
This page lists 462 BACnet objects for the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- iCM chiller plant manager, option 184 (Daikin Applied Europe)
- Equipment
- Chiller plant manager (multi-chiller sequencer)
- Equipment type
- Chillers
- BACnet objects
- 462 (34 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1
- Also known as
- iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03
BMS integration notes: Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Read the plant view from the master chiller: system run state, common leaving water temperature, active setpoint, load and the state of each chiller. Write only the few plant settings exposed (master enable, staging priorities, standby unit, pump/tower network setpoints) and use the alarm reset MVs. Start/stop and setpoints for individual chillers are not in this list.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1324 | MasterEnablingSp | Master unit enable (1 = Disable, 2 = Enable) | Write |
| MV 1448 | EvapPM'ClearAlm | Reset evaporator pump manager alarms (2 = Reset) | Write |
| MV 1100 | SysOpSta | Plant run state (Stop / Run) | Read |
| AI 1103 | CommonLWT | Common leaving chilled water temperature | Read |
| AV 1107 | SysActSp | Active plant setpoint | Read |
| AV 1112 | SystemLoad | Plant load, % | Read |
| MV 1136 | MasterData'State | Master chiller state, incl. Alarm / ComErr | Read |
| MV 1154 | S1State | Slave 1 state; S2State-S7State follow | Read |
| MV 1354 | EvapPM'GenAlm | Evaporator pump manager general alarm | Read |
| MV 1445 | ConfigErrReason | Plant configuration alarm reason (1 = None) | Read |
Enable & remote start
The guide exposes no plant start/stop or plant setpoint object. MasterEnablingSp (MV 1324) enables or disables the master unit, and the per-unit cooling/heating priorities (MV 1325-1340) and StandbyChillerSp (MV 51) set the staging; the guide does not describe how the plant itself is enabled from a BMS.
Sensors & values from the BMS
Pump speed and bypass control take network setpoints (AV 1370/1373/1376/1382/1385 evaporator, AV 1411/1414/1417/1422/1425 condenser) and the tower leaving water control takes iCT'LwtCtrl'SpNtwk (AV 1462); the guide does not say how these are selected over the local values.
Network setup
- BACnet IP comes from the POL908 module or, on MicroTech 4, the onboard BACnet IP software option (enabled under Commissioning > Configuration > Software Options with an unlock password).
- BACnet MS/TP comes from the POL904 module or the onboard BACnet MS/TP software option.
- BACnet IP defaults: device instance 1, UDP port 47808, DHCP off; set Apply Changes = Yes after editing, which restarts the controller.
- BACnet MS/TP module defaults: MAC address 24, 38400 baud, Max Master 127, Max Info Frames 1; the device instance is derived from the production number and date code. Cycle power after changing the address.
- EDE files are regenerated each time the BACnet server starts and can be downloaded by FTP from the POL908; re-export them after any configuration change.
Watch out for
- Several multistate objects use 0 = NULL as the first state; write the real value (e.g. 2 = Enable), not 0.
- Staging priorities (MV 1325-1340, 1-8) and StandbyChillerSp are settings; write them once, not cyclically.
- Slave state objects are named S1State-S7State, not SlaveDataN'State like the other slave objects.
- There is no single plant alarm object: watch the master/slave State MVs, the slave CommErr/Missing BVs, the pump/tower GenAlm MVs and ConfigErrReason.
- The guide prints the same description for several bypass and speed network setpoints; check the object name to tell them apart.
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 1100 | SysOpSta | System Operating State | Read | 0=NULL, 1=Stop, 2=Run | |
| MV | 1101 | SCMType | SCM type | Read | 0=NULL, 1=Mst/Slv, 2=iCM_Std, 3=iCM_Adv | |
| MV | 1102 | ConfigType | Configuration type | Read | 0=NULL, 1=Undef, 2=OnlyC/O, 3=OnlyH/P, 4=C/O_H/P, 5=Only4P, 6=4P_C/O | |
| AImin | 1103 | CommonLWT | System Cooling leaving water temp. | °C | Read | |
| AI | 1104 | HeatLWT | System heating leaving water temp. | °C | Read | |
| AV | 1105 | AvgEEWT | System avg evaporator entering water temp. | °C | Read | |
| AV | 1106 | AvgCEWT | System avg condenser entering water temp. | °C | Read | |
| AV | 151 | SysCtrlTmp | System controlled temp. | °C | Read | |
| AV | 252 | SysCtrlHeat | System controlled heat temp. | °C | Read | |
| AVmin | 1107 | SysActSp | System actual setpoint | °C | Read | |
| AV | 1108 | SysHeatSp | System heat setpoint | °C | Read | |
| MV | 1109 | NextChillerOn | Next chiller on | Read | 0=NULL, 1=None, 2=Master, 3=Slave 1, 4=Slave 2, 5=Slave 3, 6=Slave 4, 7=Slave 5, 8=Slave 6, 9=Slave 7 | |
| MV | 1110 | NextChillerOff | Next chiller off | Read | 0=NULL, 1=None, 2=Master, 3=Slave 1, 4=Slave 2, 5=Slave 3, 6=Slave 4, 7=Slave 5, 8=Slave 6, 9=Slave 7 | |
| MV | 1111 | StandbyChillerVal | Standby chiller Value | Read | 0=NULL, 1=None, 2=Master, 3=Slave 1, 4=Slave 2, 5=Slave 3, 6=Slave 4, 7=Slave 5, 8=Slave 6, 9=Slave 7 | |
| AVmin | 1112 | SystemLoad | System load | % | Read | |
| AV | 1113 | CoolingLoad | Cooling load | % | Read | |
| AV | 1114 | HeatingLoad | Heating load | % | Read | |
| AV | 1115 | SysDemandLimit | System Demand Limit Value | % | Read | |
| MV | 1116 | SysDemandLimitOpSta | System Demand Limit Operating State | Read | 0=NULL, 1=No, 2=Yes | |
| MV | 1117 | EnergyMonConfigured | Energy monitoring configured | Read | 0=NULL, 1=N/Cfgd, 2=Cfgd | |
| MV | 1118 | HeatRecConfigured | Heat recovery configured | Read | 0=NULL, 1=N/Cfgd, 2=Cfgd | |
| MV | 1119 | MasterData'ActMode | Master - Actual mode | Read | 0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi | |
| MV | 1120 | MasterData'CurrentModeC1 | Master - Circuit #1 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1121 | MasterData'LoadC1 | Master - Circuit #1 Load | % | Read | |
| AV | 1122 | MasterData'StartsC1 | Master - Circuit #1 No. starts | Read | ||
| AV | 1123 | MasterData'RunHoursC1 | Master - Circuit #1 Run hours | Read | ||
| MV | 1124 | MasterData'CurrentModeC2 | Master - Circuit #2 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1125 | MasterData'LoadC2 | Master - Circuit #2 Load | % | Read | |
| AV | 1126 | MasterData'StartsC2 | Master - Circuit #2 No. starts | Read | ||
| AV | 1127 | MasterData'RunHoursC2 | Master - Circuit #2 Run hours | Read | ||
| AV | 1128 | MasterData'CEWT | Master - Condenser entering water temp. | °C | Read | |
| AV | 1129 | MasterData'CLWT | Master - Condenser leaving water temp. | °C | Read | |
| AV | 1130 | MasterData'EEWT | Master - Evaporator entering water temp. | °C | Read | |
| AV | 1131 | MasterData'ELWT | Master - Evaporator leaving water temp. | °C | Read | |
| AV | 1132 | MasterData'Load | Master - Load | % | Read | |
| AV | 1133 | MasterData'Starts | Master - No. starts | Read | ||
| AV | 1134 | MasterData'RunHours | Master - Run hours | Read | ||
| MV | 1135 | MasterData'StandAlone | Master - Standalone | Read | 0=NULL, 1=No, 2=Yes | |
| MVmin | 1136 | MasterData'State | Master - State | Read | 0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd | |
| MV | 1137 | SlaveData1'ActMode | Slave #1 - Actual mode | Read | 0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi | |
| MV | 1138 | SlaveData1'CurrentModeC1 | Slave #1 - Circuit #1 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1139 | SlaveData1'LoadC1 | Slave #1 - Circuit #1 Load | % | Read | |
| AV | 1140 | SlaveData1'StartsC1 | Slave #1 - Circuit #1 No. starts | Read | ||
| AV | 1141 | SlaveData1'RunHoursC1 | Slave #1 - Circuit #1 Run hours | Read | ||
| MV | 1142 | SlaveData1'CurrentModeC2 | Slave #1 - Circuit #2 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1143 | SlaveData1'LoadC2 | Slave #1 - Circuit #2 Load | % | Read | |
| AV | 1144 | SlaveData1'StartsC2 | Slave #1 - Circuit #2 No. starts | Read | ||
| AV | 1145 | SlaveData1'RunHoursC2 | Slave #1 - Circuit #2 Run hours | Read | ||
| AV | 1146 | SlaveData1'CEWT | Slave #1 - Condenser entering water temp. | °C | Read | |
| AV | 1147 | SlaveData1'CLWT | Slave #1 - Condenser leaving water temp. | °C | Read | |
| AV | 1148 | SlaveData1'EEWT | Slave #1 - Evaporator entering water temp. | °C | Read | |
| AV | 1149 | SlaveData1'ELWT | Slave #1 - Evaporator leaving water temp. | °C | Read | |
| AV | 1150 | SlaveData1'Load | Slave #1 - Load | % | Read | |
| AV | 1151 | SlaveData1'Starts | Slave #1 - No. starts | Read | ||
| AV | 1152 | SlaveData1'RunHours | Slave #1 - Run hours | Read | ||
| MV | 1153 | SlaveData1'StandAlone | Slave #1 - Standalone | Read | 0=NULL, 1=No, 2=Yes | |
| MVmin | 1154 | S1State | Slave #1 - State | Read | 0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd | |
| MV | 1155 | SlaveData2'ActMode | Slave #2 - Actual mode | Read | 0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi | |
| MV | 1156 | SlaveData2'CurrentModeC1 | Slave #2 - Circuit #1 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1157 | SlaveData2'LoadC1 | Slave #2 - Circuit #1 Load | % | Read | |
| AV | 1158 | SlaveData2'StartsC1 | Slave #2 - Circuit #1 No. starts | Read | ||
| AV | 1159 | SlaveData2'RunHoursC1 | Slave #2 - Circuit #1 Run hours | Read | ||
| MV | 1160 | SlaveData2'CurrentModeC2 | Slave #2 - Circuit #2 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1161 | SlaveData2'LoadC2 | Slave #2 - Circuit #2 Load | % | Read | |
| AV | 1162 | SlaveData2'StartsC2 | Slave #2 - Circuit #2 No. starts | Read | ||
| AV | 1163 | SlaveData2'RunHoursC2 | Slave #2 - Circuit #2 Run hours | Read | ||
| AV | 1164 | SlaveData2'CEWT | Slave #2 - Condenser entering water temp. | °C | Read | |
| AV | 1165 | SlaveData2'CLWT | Slave #2 - Condenser leaving water temp. | °C | Read | |
| AV | 1166 | SlaveData2'EEWT | Slave #2 - Evaporator entering water temp. | °C | Read | |
| AV | 1167 | SlaveData2'ELWT | Slave #2 - Evaporator leaving water temp. | °C | Read | |
| AV | 1168 | SlaveData2'Load | Slave #2 - Load | % | Read | |
| AV | 1169 | SlaveData2'Starts | Slave #2 - No. starts | Read | ||
| AV | 1170 | SlaveData2'RunHours | Slave #2 - Run hours | Read | ||
| MV | 1171 | SlaveData2'StandAlone | Slave #2 - Standalone | Read | 0=NULL, 1=No, 2=Yes | |
| MV | 1172 | S2State | Slave #2 - State | Read | 0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd | |
| MV | 1173 | SlaveData3'ActMode | Slave #3 - Actual mode | Read | 0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi | |
| MV | 1174 | SlaveData3'CurrentModeC1 | Slave #3 - Circuit #1 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1175 | SlaveData3'LoadC1 | Slave #3 - Circuit #1 Load | % | Read | |
| AV | 1176 | SlaveData3'StartsC1 | Slave #3 - Circuit #1 No. starts | Read | ||
| AV | 1177 | SlaveData3'RunHoursC1 | Slave #3 - Circuit #1 Run hours | Read | ||
| MV | 1178 | SlaveData3'CurrentModeC2 | Slave #3 - Circuit #2 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1179 | SlaveData3'LoadC2 | Slave #3 - Circuit #2 Load | % | Read | |
| AV | 1180 | SlaveData3'StartsC2 | Slave #3 - Circuit #2 No. starts | Read | ||
| AV | 1181 | SlaveData3'RunHoursC2 | Slave #3 - Circuit #2 Run hours | Read | ||
| AV | 1182 | SlaveData3'CEWT | Slave #3 - Condenser entering water temp. | °C | Read | |
| AV | 1183 | SlaveData3'CLWT | Slave #3 - Condenser leaving water temp. | °C | Read | |
| AV | 1184 | SlaveData3'EEWT | Slave #3 - Evaporator entering water temp. | °C | Read | |
| AV | 1185 | SlaveData3'ELWT | Slave #3 - Evaporator leaving water temp. | °C | Read | |
| AV | 1186 | SlaveData3'Load | Slave #3 - Load | % | Read | |
| AV | 1187 | SlaveData3'Starts | Slave #3 - No. starts | Read | ||
| AV | 1188 | SlaveData3'RunHours | Slave #3 - Run hours | Read | ||
| MV | 1189 | SlaveData3'StandAlone | Slave #3 - Standalone | Read | 0=NULL, 1=No, 2=Yes | |
| MV | 1190 | S3State | Slave #3 - State | Read | 0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd | |
| MV | 1191 | SlaveData4'ActMode | Slave #4 - Actual mode | Read | 0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi | |
| MV | 1192 | SlaveData4'CurrentModeC1 | Slave #4 - Circuit #1 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1193 | SlaveData4'LoadC1 | Slave #4 - Circuit #1 Load | % | Read | |
| AV | 1194 | SlaveData4'StartsC1 | Slave #4 - Circuit #1 No. starts | Read | ||
| AV | 1195 | SlaveData4'RunHoursC1 | Slave #4 - Circuit #1 Run hours | Read | ||
| MV | 1196 | SlaveData4'CurrentModeC2 | Slave #4 - Circuit #2 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1197 | SlaveData4'LoadC2 | Slave #4 - Circuit #2 Load | % | Read | |
| AV | 1198 | SlaveData4'StartsC2 | Slave #4 - Circuit #2 No. starts | Read | ||
| AV | 1199 | SlaveData4'RunHoursC2 | Slave #4 - Circuit #2 Run hours | Read | ||
| AV | 1200 | SlaveData4'CEWT | Slave #4 - Condenser entering water temp. | °C | Read | |
| AV | 1201 | SlaveData4'CLWT | Slave #4 - Condenser leaving water temp. | °C | Read | |
| AV | 1202 | SlaveData4'EEWT | Slave #4 - Evaporator entering water temp. | °C | Read | |
| AV | 1203 | SlaveData4'ELWT | Slave #4 - Evaporator leaving water temp. | °C | Read | |
| AV | 1204 | SlaveData4'Load | Slave #4 - Load | % | Read | |
| AV | 1205 | SlaveData4'Starts | Slave #4 - No. starts | Read | ||
| AV | 1206 | SlaveData4'RunHours | Slave #4 - Run hours | Read | ||
| MV | 1207 | SlaveData4'StandAlone | Slave #4 - Standalone | Read | 0=NULL, 1=No, 2=Yes | |
| MV | 1208 | S4State | Slave #4 - State | Read | 0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd | |
| MV | 1209 | SlaveData5'ActMode | Slave #5 - Actual mode | Read | 0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi | |
| MV | 1210 | SlaveData5'CurrentModeC1 | Slave #5 - Circuit #1 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1211 | SlaveData5'LoadC1 | Slave #5 - Circuit #1 Load | % | Read | |
| AV | 1212 | SlaveData5'StartsC1 | Slave #5 - Circuit #1 No. starts | Read | ||
| AV | 1213 | SlaveData5'RunHoursC1 | Slave #5 - Circuit #1 Run hours | Read | ||
| MV | 1214 | SlaveData5'CurrentModeC2 | Slave #5 - Circuit #2 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1215 | SlaveData5'LoadC2 | Slave #5 - Circuit #2 Load | % | Read | |
| AV | 1216 | SlaveData5'StartsC2 | Slave #5 - Circuit #2 No. starts | Read | ||
| AV | 1217 | SlaveData5'RunHoursC2 | Slave #5 - Circuit #2 Run hours | Read | ||
| AV | 1218 | SlaveData5'CEWT | Slave #5 - Condenser entering water temp. | °C | Read | |
| AV | 1219 | SlaveData5'CLWT | Slave #5 - Condenser leaving water temp. | °C | Read | |
| AV | 1220 | SlaveData5'EEWT | Slave #5 - Evaporator entering water temp. | °C | Read | |
| AV | 1221 | SlaveData5'ELWT | Slave #5 - Evaporator leaving water temp. | °C | Read | |
| AV | 1222 | SlaveData5'Load | Slave #5 - Load | % | Read | |
| AV | 1223 | SlaveData5'Starts | Slave #5 - No. starts | Read | ||
| AV | 1224 | SlaveData5'RunHours | Slave #5 - Run hours | Read | ||
| MV | 1225 | SlaveData5'StandAlone | Slave #5 - Standalone | Read | 0=NULL, 1=No, 2=Yes | |
| MV | 1226 | S5State | Slave #5 - State | Read | 0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd | |
| MV | 1227 | SlaveData6'ActMode | Slave #6 - Actual mode | Read | 0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi | |
| MV | 1228 | SlaveData6'CurrentModeC1 | Slave #6 - Circuit #1 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1229 | SlaveData6'LoadC1 | Slave #6 - Circuit #1 Load | % | Read | |
| AV | 1230 | SlaveData6'StartsC1 | Slave #6 - Circuit #1 No. starts | Read | ||
| AV | 1231 | SlaveData6'RunHoursC1 | Slave #6 - Circuit #1 Run hours | Read | ||
| MV | 1232 | SlaveData6'CurrentModeC2 | Slave #6 - Circuit #2 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1233 | SlaveData6'LoadC2 | Slave #6 - Circuit #2 Load | % | Read | |
| AV | 1234 | SlaveData6'StartsC2 | Slave #6 - Circuit #2 No. starts | Read | ||
| AV | 1235 | SlaveData6'RunHoursC2 | Slave #6 - Circuit #2 Run hours | Read | ||
| AV | 1236 | SlaveData6'CEWT | Slave #6 - Condenser entering water temp. | °C | Read | |
| AV | 1237 | SlaveData6'CLWT | Slave #6 - Condenser leaving water temp. | °C | Read | |
| AV | 1238 | SlaveData6'EEWT | Slave #6 - Evaporator entering water temp. | °C | Read | |
| AV | 1239 | SlaveData6'ELWT | Slave #6 - Evaporator leaving water temp. | °C | Read | |
| AV | 1240 | SlaveData6'Load | Slave #6 - Load | % | Read | |
| AV | 1241 | SlaveData6'Starts | Slave #6 - No. starts | Read | ||
| AV | 1242 | SlaveData6'RunHours | Slave #6 - Run hours | Read | ||
| MV | 1243 | SlaveData6'StandAlone | Slave #6 - Standalone | Read | 0=NULL, 1=No, 2=Yes | |
| MV | 1244 | S6State | Slave #6 - State | Read | 0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd | |
| MV | 1245 | SlaveData7'ActMode | Slave #7 - Actual mode | Read | 0=NULL, 1=Cool, 2=Ice, 3=Heat, 4=Test, 5=Multi | |
| MV | 1246 | SlaveData7'CurrentModeC1 | Slave #7 - Circuit #1 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1247 | SlaveData7'LoadC1 | Slave #7 - Circuit #1 Load | % | Read | |
| AV | 1248 | SlaveData7'StartsC1 | Slave #7 - Circuit #1 No. starts | Read | ||
| AV | 1249 | SlaveData7'RunHoursC1 | Slave #7 - Circuit #1 Run hours | Read | ||
| MV | 1250 | SlaveData7'CurrentModeC2 | Slave #7 - Circuit #2 Current mode | Read | 0=NULL, 1=Off, 2=Water, 3=Cool, 4=Heat, 5=N/Avail, 6=N/Cfgd | |
| AV | 1251 | SlaveData7'LoadC2 | Slave #7 - Circuit #2 Load | % | Read | |
| AV | 1252 | SlaveData7'StartsC2 | Slave #7 - Circuit #2 No. starts | Read | ||
| AV | 1253 | SlaveData7'RunHoursC2 | Slave #7 - Circuit #2 Run hours | Read | ||
| AV | 1254 | SlaveData7'CEWT | Slave #7 - Condenser entering water temp. | °C | Read | |
| AV | 1255 | SlaveData7'CLWT | Slave #7 - Condenser leaving water temp. | °C | Read | |
| AV | 1256 | SlaveData7'EEWT | Slave #7 - Evaporator entering water temp. | °C | Read | |
| AV | 1257 | SlaveData7'ELWT | Slave #7 - Evaporator leaving water temp. | °C | Read | |
| AV | 1258 | SlaveData7'Load | Slave #7 - Load | % | Read | |
| AV | 1259 | SlaveData7'Starts | Slave #7 - No. starts | Read | ||
| AV | 1260 | SlaveData7'RunHours | Slave #7 - Run hours | Read | ||
| MV | 1261 | SlaveData7'StandAlone | Slave #7 - Standalone | Read | 0=NULL, 1=No, 2=Yes | |
| MV | 1262 | S7State | Slave #7 - State | Read | 0=NULL, 1=Off, 2=Run, 3=Alarm, 4=ComErr, 5=N/Avail, 6=N/Cfgd | |
| AV | 1263 | SysPoweEl | System electrical power | MW | Read | |
| AV | 1264 | SysPowerTherm | System thermal power | MW | Read | |
| AV | 1265 | SysCOP | System COP | Read | ||
| MV | 1266 | MasterData'EnergyMonCfgd | Master - Energy monitoring configured | Read | 0=NULL, 1=N/Cfgd, 2=Cfgd | |
| AV | 1267 | MasterData'PowerTherm | Master - Thermal power | kW | Read | |
| AV | 1268 | MasterData'PowerEl | Master - Electrical power | kW | Read | |
| AV | 1270 | SlaveData1'PowerTherm | Slave #1 - Thermal power | kW | Read | |
| AV | 1271 | SlaveData1'PowerEl | Slave #1 - Electrical power | kW | Read | |
| AV | 1273 | SlaveData2'PowerTherm | Slave #2 - Thermal power | kW | Read | |
| AV | 1274 | SlaveData2'PowerEl | Slave #2 - Electrical power | kW | Read | |
| AV | 1276 | SlaveData3'PowerTherm | Slave #3 - Thermal power | kW | Read | |
| AV | 1277 | SlaveData3'PowerEl | Slave #3 - Electrical power | kW | Read | |
| AV | 1279 | SlaveData4'PowerTherm | Slave #4 - Thermal power | kW | Read | |
| AV | 1280 | SlaveData4'PowerEl | Slave #4 - Electrical power | kW | Read | |
| AV | 1282 | SlaveData5'PowerTherm | Slave #5 - Thermal power | kW | Read | |
| AV | 1283 | SlaveData5'PowerEl | Slave #5 - Electrical power | kW | Read | |
| AV | 1285 | SlaveData6'PowerTherm | Slave #6 - Thermal power | kW | Read | |
| AV | 1286 | SlaveData6'PowerEl | Slave #6 - Electrical power | kW | Read | |
| AV | 1288 | SlaveData7'PowerTherm | Slave #7 - Thermal power | kW | Read | |
| AV | 1289 | SlaveData7'PowerEl | Slave #7 - Electrical power | kW | Read | |
| MV | 1290 | SysHeatRecOpSta | System Heat recovery operating state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1291 | AvgHeatRecEWT | Average Heat Recovery Entering Water temp. | °C | Read | |
| MV | 1292 | MasterData'HeatRecCfgd | Master - Heat recovery configured | Read | 0=NULL, 1=N/Cfgd, 2=Cfgd | |
| MV | 1293 | MasterData'HeatRecRun | Master - Heat recovery state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1294 | MasterData'HeatRecEWT | Master - Heat recovery entering water temp. | °C | Read | |
| MV | 1295 | SlaveData1'HeatRecRun | Slave #1 - Heat recovery state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1296 | SlaveData1'HeatRecEWT | Slave #1 - Heat recovery entering water temp. | °C | Read | |
| MV | 1297 | SlaveData2'HeatRecRun | Slave #2 - Heat recovery state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1298 | SlaveData2'HeatRecEWT | Slave #2 - Heat recovery entering water temp. | °C | Read | |
| MV | 1299 | SlaveData3'HeatRecRun | Slave #3 - Heat recovery state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1300 | SlaveData3'HeatRecEWT | Slave #3 - Heat recovery entering water temp. | °C | Read | |
| MV | 1301 | SlaveData4'HeatRecRun | Slave #4 - Heat recovery state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1302 | SlaveData4'HeatRecEWT | Slave #4 - Heat recovery entering water temp. | °C | Read | |
| MV | 1303 | SlaveData5'HeatRecRun | Slave #5 - Heat recovery state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1304 | SlaveData5'HeatRecEWT | Slave #5 - Heat recovery entering water temp. | °C | Read | |
| MV | 1305 | SlaveData6'HeatRecRun | Slave #6 - Heat recovery state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1306 | SlaveData6'HeatRecEWT | Slave #6 - Heat recovery entering water temp. | °C | Read | |
| MV | 1307 | SlaveData7'HeatRecRun | Slave #7 - Heat recovery state | Read | 0=NULL, 1=Stop, 2=Run | |
| AV | 1308 | SlaveData7'HeatRecEWT | Slave #7 - Heat recovery entering water temp. | °C | Read | |
| MV | 1309 | SysFreeClgSta | Freecooling Status | Read | 0=NULL, 1=Off:Switch, 2=WaitOAT, 3=Run, 4=Off:Alarm | |
| AV | 1310 | SysOAT | System Outside Air Temperature | °C | Read | |
| MV | 1311 | MasterData'FreeClgCfgd | Master - Freecooling configured | Read | 0=NULL, 1=N/Cfgd, 2=Cfgd | |
| MV | 1312 | MasterData'FreeClgAvail | Master - Freecooling available | Read | 0=NULL, 1=N/Avail, 2=Avail | |
| MV | 1313 | MasterData'FreeClgMode | Master - Freecooling Mode | Read | 0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All | |
| MV | 1314 | SlaveData1'FreeClgMode | Slave #1 - Freecooling Mode | Read | 0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All | |
| MV | 1315 | SlaveData2'FreeClgMode | Slave #2 - Freecooling Mode | Read | 0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All | |
| MV | 1316 | SlaveData3'FreeClgMode | Slave #3 - Freecooling Mode | Read | 0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All | |
| MV | 1317 | SlaveData4'FreeClgMode | Slave #4 - Freecooling Mode | Read | 0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All | |
| MV | 1318 | SlaveData5'FreeClgMode | Slave #5 - Freecooling Mode | Read | 0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All | |
| MV | 1319 | SlaveData6'FreeClgMode | Slave #6 - Freecooling Mode | Read | 0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All | |
| MV | 1320 | SlaveData7'FreeClgMode | Slave #7 - Freecooling Mode | Read | 0=NULL, 1=Mech_All, 2=Start_FC, 3=Mech+FC, 4=FC_All | |
| MV | 5 | StandaloneSp | Standalone Mode Setpoint | Write | 0=NULL, 1=No, 2=Yes | |
| MVmin | 1324 | MasterEnablingSp | Master enabling | Write | 0=NULL, 1=Disable, 2=Enable | |
| MV | 1325 | Master'Priority | Master - Priority (Cooling mode) (1-8) | Write | ||
| MV | 1326 | Master'PrioHeat | Master - Priority (Heating mode) (1-8) | Write | ||
| MV | 1327 | Slave1'Priority | Slave #1 - Priority (Cooling mode) (1-8) | Write | ||
| MV | 1328 | Slave1'PrioHeat | Slave #1 - Priority (Heating mode) (1-8) | Write | ||
| MV | 1329 | Slave2'Priority | Slave #2 - Priority (Cooling mode) (1-8) | Write | ||
| MV | 1330 | Slave2'PrioHeat | Slave #2 - Priority (Heating mode) (1-8) | Write | ||
| MV | 1331 | Slave3'Priority | Slave #3 - Priority (Cooling mode) (1-8) | Write | ||
| MV | 1332 | Slave3'PrioHeat | Slave #3 - Priority (Heating mode) (1-8) | Write | ||
| MV | 1333 | Slave4'Priority | Slave #4 - Priority (Cooling mode) (1-8) | Write | ||
| MV | 1334 | Slave4'PrioHeat | Slave #4 - Priority (Heating mode) (1-8) | Write | ||
| MV | 1335 | Slave5'Priority | Slave #5 - Priority (Cooling mode) (1-8) | Write | ||
| MV | 1336 | Slave5'PrioHeat | Slave #5 - Priority (Heating mode) (1-8) | Write | ||
| MV | 1337 | Slave6'Priority | Slave #6 - Priority (Cooling mode) (1-8) | Write | ||
| MV | 1338 | Slave6'PrioHeat | Slave #6 - Priority (Heating mode) (1-8) | Write | ||
| MV | 1339 | Slave7'Priority | Slave #7 - Priority (Cooling mode) (1-8) | Write | ||
| MV | 1340 | Slave7'PrioHeat | Slave #7 - Priority (Heating mode) (1-8) | Write | ||
| MV | 51 | StandbyChillerSp | Standby Unit Setpoint | Write | 0=NULL, 1=No, 2=Auto, 3=Master, 4=Slave 1, 5=Slave 2, 6=Slave 3, 7=Slave 4, 8=Slave 5, 9=Slave 6, 10=Slave 7 | |
| MV | 1341 | StandbyTmpComp | Standby temp compensation | Write | 0=NULL, 1=No, 2=Yes | |
| MV | 1342 | MstUnitType | Master - Unit type | Read | 0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif | |
| MV | 1343 | S1UnitType | Slave #1 - Unit type | Read | 0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif | |
| MV | 1344 | S2UnitType | Slave #2 - Unit type | Read | 0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif | |
| MV | 1345 | S3UnitType | Slave #3 - Unit type | Read | 0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif | |
| MV | 1346 | S4UnitType | Slave #4 - Unit type | Read | 0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif | |
| MV | 1347 | S5UnitType | Slave #5 - Unit type | Read | 0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif | |
| MV | 1348 | S6UnitType | Slave #6 - Unit type | Read | 0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif | |
| MV | 1349 | S7UnitType | Slave #7 - Unit type | Read | 0=NULL, 1=Undef, 2=AC C/O Screw, 3=AC H/P Screw, 4=Polyfun Screw, 5=Undef, 6=WC C/O Screw, 7=WC H/P Screw, 8=AC C/O Scroll, 9=AC H/P Scroll, 10=Polyfun Scroll, 11=Undef, 12=Undef, 13=WC C/O Scroll, 14=WC H/P Scroll, 15=WC C/O Centrif, 16=WC H/P Centrif | |
| AV | 1350 | EvapPM'ApplVers | Evap PM - Application Version | Read | ||
| MV | 1351 | EvapPM'NrPumpsCfgd | Evap PM - Number of Pump (1-10) | Read | ||
| MV | 1352 | EvapPM'Status | Evap PM - Status | Read | 0=NULL, 1=Off:Auto, 2=On:Auto, 3=Off:Local, 4=Off:SensAlarm, 5=On:SensAlarm, 6=Off:CommErr, 7=On:CommErr, 8=Configuration, 9=Off:ConfigAlarm | |
| MV | 1353 | EvapPM'OpSta | Evap PM - Operating state | Read | 0=NULL, 1=Stop, 2=Run | |
| MVmin | 1354 | EvapPM'GenAlm | Evap PM - General Alarm | Read | 0=NULL, 1=None, 2=Active | |
| MV | 1355 | EvapPM'StatusP1 | Evap Pump #1 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1356 | EvapPM'StatusP2 | Evap Pump #2 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1357 | EvapPM'StatusP3 | Evap Pump #3 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1358 | EvapPM'StatusP4 | Evap Pump #4 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1359 | EvapPM'StatusP5 | Evap Pump #5 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1360 | EvapPM'StatusP6 | Evap Pump #6 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1361 | EvapPM'StatusP7 | Evap Pump #7 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1362 | EvapPM'StatusP8 | Evap Pump #8 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1363 | EvapPM'StatusP9 | Evap Pump #9 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1364 | EvapPM'StatusP10 | Evap Pump #10 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| AV | 1365 | EvapPM'NrPumpRun | Evap Pumps - Running | Read | ||
| MV | 1366 | EvapPM'Speed | Evap Pumps - Speed | % | Read | |
| MV | 1367 | EvapPM'SpdCtrlType | Evap PM - Speed Control Type | Read | 0=NULL, 1=Constant, 2=Dtemp, 3=DifPres, 4=AbsPres | |
| AV | 1368 | EvapPM'SpdCtrl'DeltaT | Evap Speed Control - Delta Temp | dK | Read | |
| AV | 1369 | EvapPM'SpdCtrl'DeltaTActSp | Evap Speed Control - Actual Setpoint | dK | Read | |
| AV | 1370 | EvapPM'SpdCtrl'DeltaTSpNtwk | Evap Speed Control - Setpoint Network | dK | Write | |
| AV | 1371 | EvapPM'SpdCtrl'DifPress | Evap Speed Control - Differential Pressure | kPa | Read | |
| AV | 1372 | EvapPM'SpdCtrl'DifPressActSp | Evap Speed Control - Actual Setpoint | kPa | Read | |
| AV | 1373 | EvapPM'SpdCtrl'DifPressSpNtwk | Evap Speed Control - Setpoint Network | kPa | Write | |
| AV | 1374 | EvapPM'SpdCtrl'AbsPress | Evap Speed Control - Absolute Pressure | kPa | Read | |
| AV | 1375 | EvapPM'SpdCtrl'AbsPressActSp | Evap Speed Control - Actual Setpoint | kPa | Read | |
| AV | 1376 | EvapPM'SpdCtrl'AbsPressSpNtwk | Evap Speed Control - Setpoint Network | kPa | Write | |
| AV | 1377 | EvapPM'BypVlvOpng | Evaporator Bypass Valve - Opening | % | Read | |
| MV | 1378 | EvapPM'BypVlvCtrlType | Evap PM - Bypass Valve Control Type | Read | 0=NULL, 1=None, 2=MinDP, 3=Flow, 4=EvapEwt, 5=CondEwt | |
| BV | 1379 | EvapPM'BypVlvCtrl'MinDPonUnit | Evap Bypass Control - Min Diff Pressure on Units | Read | 0=None, 1=Active | |
| AV | 1380 | EvapPM'BypVlvCtrl'Flow | Evap Bypass Control - Flow | l/s | Read | |
| AV | 1381 | EvapPM'BypVlvCtrl'FlowActSp | Evap Bypass Control - Actual Setpoint | l/s | Read | |
| AV | 1382 | EvapPM'BypVlvCtrl'FlowSpNtwk | Evap Bypass Control - Setpoint Network | l/s | Write | |
| AV | 1383 | EvapPM'BypVlvCtrl'EvapEwt | Evap Bypass Control - EWT | °C | Read | |
| AV | 1384 | EvapPM'BypVlvCtrl'EvapEwtActSp | Evap Bypass Control - Actual Setpoint | °C | Read | |
| AV | 1385 | EvapPM'BypVlvCtrl'EvapEwtSpNtwk | Evap Bypass Control - Setpoint Network | °C | Write | |
| MV | 1386 | Evap PM'EnergyMeterConfigured | Evap PM - Energy Meter Configured | Read | 0=NULL, 1=N/Cfgd, 2=Cfgd | |
| AV | 1387 | EvapPM'ActPwr | Evap PM - Electrical Active Power | kW | Read | |
| BV | 1388 | EvapPM'SpdCtrlSens'Alm | Evap Pump Manager - Speed Control sensor alarm | Read | 0=None, 1=Active | |
| BV | 1389 | EvapPM'AvailPump'Alm | Evap Pump Manager - Available pump alarm | Read | 0=None, 1=Active | |
| BV | 1390 | EvapPM'Cfg'Alm | Evap Pump Manager - Configuration alarm | Read | 0=None, 1=Active | |
| AV | 1391 | CondPM'ApplVers | Cond PM - Application Version | Read | ||
| MV | 1392 | CondPM'NrPumpsCfgd | Cond PM - Number of Pump (1-10) | Read | ||
| MV | 1393 | CondPM'Status | Cond PM - Status | Read | 0=NULL, 1=Off:Auto, 2=On:Auto, 3=Off:Local, 4=Off:SensAlarm, 5=On:SensAlarm, 6=Off:CommErr, 7=On:CommErr, 8=Configuration, 9=Off:ConfigAlarm | |
| MV | 1394 | CondPM'OpSta | Cond PM - Operating state | Read | 0=NULL, 1=Stop, 2=Run | |
| MV | 1395 | CondPM'GenAlm | Cond PM - General Alarm | Read | 0=NULL, 1=None, 2=Active | |
| MV | 1396 | CondPM'StatusP1 | Cond Pump #1 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1397 | CondPM'StatusP2 | Cond Pump #2 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1398 | CondPM'StatusP3 | Cond Pump #3 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1399 | CondPM'StatusP4 | Cond Pump #4 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1400 | CondPM'StatusP5 | Cond Pump #5 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1401 | CondPM'StatusP6 | Cond Pump #6 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1402 | CondPM'StatusP7 | Cond Pump #7 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1403 | CondPM'StatusP8 | Cond Pump #8 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1404 | CondPM'StatusP9 | Cond Pump #9 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| MV | 1405 | CondPM'StatusP10 | Cond Pump #10 - Status | Read | 0=NULL, 1=Off, 2=On, 3=ManOn, 4=ManOff, 5=Alm, 6=Test, 7=N/Cfg | |
| AV | 1406 | CondPM'NrPumpRun | Cond Pumps - Running | Read | ||
| AV | 1407 | CondPM'Speed | Cond Pumps - Speed | % | Read | |
| MV | 1408 | CondPM'SpdCtrlType | Cond PM - Speed Control Type | Read | 0=NULL, 1=Constant, 2=Dtemp, 3=DifPres, 4=AbsPres | |
| AV | 1409 | CondPM'SpdCtrl'DeltaT | Cond Speed Control - Delta Temp | dK | Read | |
| AV | 1410 | CondPM'SpdCtrl'DeltaTActSp | Cond Speed Control - Actual Setpoint | dK | Read | |
| AV | 1411 | CondPM'SpdCtrl'DeltaTSpNtwk | Cond Speed Control - Setpoint Network | dK | Write | |
| AV | 1412 | CondPM'SpdCtrl'DifPress | Cond Speed Control - Differential Pressure | kPa | Read | |
| AV | 1413 | CondPM'SpdCtrl'DifPressActSp | Cond Speed Control - Actual Setpoint | kPa | Read | |
| AV | 1414 | CondPM'SpdCtrl'DifPressSpNtwk | Cond Speed Control - Setpoint Network | kPa | Write | |
| AV | 1415 | CondPM'SpdCtrl'AbsPress | Cond Speed Control - Absolute Pressure | kPa | Read | |
| AV | 1416 | CondPM'SpdCtrl'AbsPressActSp | Cond Speed Control - Actual Setpoint | kPa | Read | |
| AV | 1417 | CondPM'SpdCtrl'AbsPressSpNtwk | Cond Speed Control - Setpoint Network | kPa | Write | |
| AV | 1418 | CondPM'BypVlvOpng | Condenser Bypass Valve - Opening | % | Read | |
| MV | 1419 | CondPM'BypValveCtrlType | Cond PM - Bypass Valve Control Type | Read | 0=NULL, 1=None, 2=MinDP, 3=Flow, 4=EvapEwt, 5=CondEwt | |
| AV | 1420 | CondPM'BypVlvCtrl'Flow | Cond Bypass Control - Flow | l/s | Read | |
| AV | 1421 | CondPM'BypVlvCtrl'FlowActSp' | Cond Bypass Control - Active Setpoint | l/s | Read | |
| AV | 1422 | CondPM'BypVlvCtrl'FlowSpNtwk | Cond Speed Control - Setpoint Network | l/s | Write | |
| AV | 1423 | CondPM'BypVlvCtrl'CondEwt | Cond Bypass Control - EWT | °C | Read | |
| AV | 1424 | CondPM'BypVlvCtrl'CondEwtActSp | Cond Bypass Control - Actual Setpoint | °C | Read | |
| AV | 1425 | CondPM'BypVlvCtrl'CondEwtSpNtwk | Cond Bypass Control - Setpoint Network | °C | Write | |
| MV | 1426 | CondPM'EnergyMeterConfigured | Cond PM - Energy Meter configured | Read | 0=NULL, 1=N/Cfgd, 2=Cfgd | |
| AV | 1427 | CondPM'ActPwr | Cond PM - Electrical Active Power | kW | Read | |
| BV | 1428 | CondPM'SpdCtrlSens'Alm | Cond Pump Manager - Speed Control sensor alarm | Read | 0=None, 1=Active | |
| BV | 1429 | CondPM'AvailPump'Alm | Cond Pump Manager - Available pump alarm | Read | 0=None, 1=Active | |
| BV | 1430 | CondPM'Cfg'Alm | Cond Pump Manager - Configuration alarm | Read | 0=None, 1=Active | |
| BV | 1431 | SlaveMstMissing | Slave - Master Missing | Read | 0=None, 1=Active | |
| BV | 1432 | SlaveMstDisconnect | Slave - Master Disconnected | Read | 0=No, 1=Yes | |
| BV | 20 | SlaveMstCommErr | Slave - Master Communication Error | Read | 0=None, 1=Active | |
| BV | 1433 | HeatLWTSenf | Common Leaving Hot water temp. sensor fault | Read | 0=None, 1=Active | |
| BV | 502 | CommonLWTSenf | Common Leaving water temp. sensor fault | Read | 0=None, 1=Active | |
| BV | 21 | S1CommErr | Slave #1 - Communication Error | Read | 0=None, 1=Active | |
| BV | 1434 | S1Missing | Slave #1 - Missing | Read | 0=No, 1=Yes | |
| BV | 22 | S2CommErr | Slave #2 - Communication Error | Read | 0=None, 1=Active | |
| BV | 1435 | S2Missing | Slave #2 - Missing | Read | 0=No, 1=Yes | |
| BV | 23 | S3CommErr | Slave #3 - Communication Error | Read | 0=None, 1=Active | |
| BV | 1436 | S3Missing | Slave #3 - Missing | Read | 0=No, 1=Yes | |
| BV | 1437 | S4CommErr | Slave #4 - Communication Error | Read | 0=None, 1=Active | |
| BV | 1438 | S4Missing | Slave #4 - Missing | Read | 0=No, 1=Yes | |
| BV | 1439 | S5CommErr | Slave #5 - Communication Error | Read | 0=None, 1=Active | |
| BV | 1440 | S5Missing | Slave #5 - Missing | Read | 0=No, 1=Yes | |
| BV | 1441 | S6CommErr | Slave #6 - Communication Error | Read | 0=None, 1=Active | |
| BV | 1442 | S6Missing | Slave #6 - Missing | Read | 0=No, 1=Yes | |
| BV | 1443 | S7CommErr | Slave #7 - Communication Error | Read | 0=None, 1=Active | |
| BV | 1444 | S7Missing | Slave #7 - Missing | Read | 0=No, 1=Yes | |
| MVmin | 1445 | ConfigErrReason | Configuration Alarm | Read | 0=NULL, 1=None, 2=ModeErr, 3=ComprErr, 4=CooledErr, 5=UnitNotDef, 6=iCMtypeErr | |
| BV | 1446 | EnergyMonConfigErr | Energy monitoring configuration Error | Read | 0=None, 1=Active | |
| BV | 1447 | HeatRecConfigErr | Heat recovery configuration Error | Read | 0=None, 1=Active | |
| MVmin | 1448 | EvapPM'ClearAlm | Evap PM - Clear Alarm setpoint | Write | 0=NULL, 1=---, 2=Reset | |
| MV | 1449 | CondPM'ClearAlm | Cond PM - Clear Alarm setpoint | Write | 0=NULL, 1=---, 2=Reset | |
| MV | 1450 | iCT'NrTowersCfgd | iCT - Tower Number (1-10) | Read | ||
| MV | 1451 | iCT'Status | iCT - Status | Read | 0=NULL, 1=Off:Auto, 2=On:Auto, 3=Off:Local, 4=Off:SensAlarm, 5=On:SensAlarm, 6=Off:CommErr, 7=On:CommErr, 8=Configuration, 9=Off:ConfigAlarm | |
| MV | 1452 | iCT'OpSta | iCT - Operating State | Read | 0=NULL, 1=Stop, 2=Run | |
| MV | 1453 | iCT'GenAlm | iCT - General Alarm | Read | 0=NULL, 1=None, 2=Active | |
| AV | 1454 | iCT'NrTwrRun | iCT - Number of Running Tower | Read | ||
| MV | 1455 | iCT'NxOnTwr | iCT - Next On Tower (0-10) | Read | ||
| MV | 1456 | iCT'NxOffTwr | iCT - Next Off Tower | Read | 0=NULL, 1=None, 2=CT1, 3=CT2, 4=CT3, 5=CT4, 6=CT5, 7=CT6, 8=CT7, 9=CT8, 10=CT9, 11=CT10 | |
| AV | 1457 | iCT'Lwt | iCT - Leaving Water Termperature | °C | Read | |
| BV | 1458 | iCT'LwtSens'Alm' | iCT - LWT sernsor Alarm | Read | 0=None, 1=Active | |
| MV | 1459 | iCT'LwtSpRstType | iCT LWT Control - Setpoint Reset type | Read | 0=NULL, 1=None, 2=Ouside Air T, 3=Web Bulb T | |
| AV | 1460 | iCT'LwtCtrl'ActSp | iCT LWT Control - Actual Setpoint | °C | Read | |
| AV | 1461 | iCT'LwtCtrl'SpLoc | iCT LWT Control - Setpoint iCM | °C | Read | |
| AV | 1462 | iCT'LwtCtrl'SpNtwk | iCT LWT Control - Setpoint Network | °C | Write | |
| AV | 1463 | iCT'Toa | iCT - Outside Air Temperature | °C | Read | |
| AV | 1464 | iCT'HuR | iCT - Outside Relative Humidity | %r.H | Read | |
| AV | 1465 | iCT'LwtCtrl'Twb | iCT - Outside Wet Bulb Temperature | °C | Read | |
| MV | 1466 | iCT'Twr1'Status | Cooling Tower 1 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1467 | iCT'Twr1'FanSta | Cooling Tower 1 - Fan Status | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1468 | iCT'Twr1'FanSpeed | Cooling Tower 1 - Fan Speed | % | Read | |
| MV | 1469 | iCT'Twr1'InVlvSta | Cooling Tower 1 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1470 | iCT'Twr1'Lwt | Cooling Tower 1 - LWT | °C | Read | |
| BV | 1471 | iCT'Twr1'LwtSens'Alm | Cooling Tower 1 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1472 | iCT'Twr2'Status | Cooling Tower 2 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1473 | iCT'Twr2'FanSta | Cooling Tower 2 - Fan Status | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1474 | iCT'Twr2'FanSpeed | Cooling Tower 2 - Fan Speed | % | Read | |
| MV | 1475 | iCT'Twr2'InVlvSta | Cooling Tower 2 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1476 | iCT'Twr2'Lwt | Cooling Tower 2 - LWT | °C | Read | |
| BV | 1477 | iCT'Twr2'LwtSens'Alm | Cooling Tower 2 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1478 | iCT'Twr3'Status | Cooling Tower 3 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1479 | iCT'Twr3'FanSta | Cooling Tower 3 - Fan Status | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1480 | iCT'Twr3'FanSpeed | Cooling Tower 3 - Fan Speed | % | Read | |
| MV | 1481 | iCT'Twr3'InVlvSta | Cooling Tower 3 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1482 | iCT'Twr3'Lwt | Cooling Tower 3 - LWT | °C | Read | |
| BV | 1483 | iCT'Twr3'LwtSens'Alm | Cooling Tower 3 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1484 | iCT'Twr4'Status | Cooling Tower 4 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1485 | iCT'Twr4'FanSta | Cooling Tower 4 - Fan Staus | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1486 | iCT'Twr4'FanSpeed | Cooling Tower 4 - Fan Speed | % | Read | |
| MV | 1487 | iCT'Twr4'InVlvSta | Cooling Tower 4 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1488 | iCT'Twr4'Lwt | Cooling Tower 4 - LWT | °C | Read | |
| BV | 1489 | iCT'Twr4'LwtSens'Alm | Cooling Tower 4 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1490 | iCT'Twr5'Status | Cooling Tower 5 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1491 | iCT'Twr5'FanSta | Cooling Tower 5 - Fan Staus | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1492 | iCT'Twr5'FanSpeed | Cooling Tower 5 - Fan Speed | % | Read | |
| MV | 1493 | iCT'Twr5'InVlvSta | Cooling Tower 5 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1494 | iCT'Twr5'Lwt | Cooling Tower 5 - LWT | °C | Read | |
| BV | 1495 | iCT'Twr5'LwtSens'Alm | Cooling Tower 5 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1496 | iCT'Twr6'Status | Cooling Tower 6 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1497 | iCT'Twr6'FanSta | Cooling Tower 6 - Fan Staus | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1498 | iCT'Twr6'FanSpeed | Cooling Tower 6 - Fan Speed | % | Read | |
| MV | 1499 | iCT'Twr6'InVlvSta | Cooling Tower 6 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1500 | iCT'Twr6'Lwt | Cooling Tower 6 - LWT | °C | Read | |
| BV | 1501 | iCT'Twr6'LwtSens'Alm | Cooling Tower 6 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1502 | iCT'Twr7'Status | Cooling Tower 7 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1503 | iCT'Twr7'FanSta | Cooling Tower 7 - Fan Staus | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1504 | iCT'Twr7'FanSpeed | Cooling Tower 7 - Fan Speed | % | Read | |
| MV | 1505 | iCT'Twr7'InVlvSta | Cooling Tower 7 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1506 | iCT'Twr7'Lwt | Cooling Tower 7 - LWT | °C | Read | |
| BV | 1507 | iCT'Twr7'LwtSens'Alm | Cooling Tower 7 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1508 | iCT'Twr8'Status | Cooling Tower 8 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1509 | iCT'Twr8'FanSta | Cooling Tower 8 - Fan Staus | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1510 | iCT'Twr8'FanSpeed | Cooling Tower 8 - Fan Speed | % | Read | |
| MV | 1511 | iCT'Twr8'InVlvSta | Cooling Tower 8 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1512 | iCT'Twr8'Lwt | Cooling Tower 8 - LWT | °C | Read | |
| BV | 1513 | iCT'Twr8'LwtSens'Alm | Cooling Tower 8 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1514 | iCT'Twr9'Status | Cooling Tower 9 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1515 | iCT'Twr9'FanSta | Cooling Tower 9 - Fan Staus | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1516 | iCT'Twr9'FanSpeed | Cooling Tower 9 - Fan Speed | % | Read | |
| MV | 1517 | iCT'Twr9'InVlvSta | Cooling Tower 9 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1518 | iCT'Twr9'Lwt | Cooling Tower 9 - LWT | °C | Read | |
| BV | 1519 | iCT'Twr9'LwtSens'Alm | Cooling Tower 9 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1520 | iCT'Twr10'Status | Cooling Tower 10 - Status | Read | 0=NULL, 1=Off, 2=Start, 3=Run, 4=ManOn, 5=ManOff, 6=Alarm, 7=Test, 8=N/Cfgd, 9=ComErr | |
| MV | 1521 | iCT'Twr10'FanSta | Cooling Tower 10 - Fan Staus | Read | 0=NULL, 1=Stop, 2=Run, 3=ManON, 4=ManOFF, 5=Alarm, 6=Test | |
| AV | 1522 | iCT'Twr10'FanSpeed | Cooling Tower 10 - Fan Speed | % | Read | |
| MV | 1523 | iCT'Twr10'InVlvSta | Cooling Tower 10 - Inlet Valve Status | Read | 0=NULL, 1=Close, 2=Open, 3=ManOpen, 4=ManClose, 5=Alarm, 6=Test | |
| AV | 1524 | iCT'Twr10'Lwt | Cooling Tower 10 - LWT | °C | Read | |
| BV | 1525 | iCT'Twr10'LwtSens'Alm | Cooling Tower 10 - LWT Alarm | Read | 0=None, 1=Active | |
| MV | 1526 | iCT'ClearAlm | iCT - Clear Alarm | Write | 0=NULL, 1=---, 2=Reset | |
| BV | 1527 | MasterComm'iCT'Comm'Alm | iCT - CommError | Read | 0=None, 1=Active | |
| BV | 1528 | iCT'BrdsMBComm'Alm | iCT - Borads CommError | Read | 0=None, 1=Active | |
| MV | 1529 | ModeChgovrMngt | Mode Changeover management | Read | 0=NULL, 1=N/Mngd, 2=Mngd | |
| MV | 1530 | DefrMngt | Defrost Management | Read | 0=NULL, 1=N/Mngd, 2=Mngd | |
| MV | 1531 | MasterData'DfrstOpStaC1 | Master - Circuit #1 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1532 | MasterData'DfrstOpStaC2 | Master - Circuit #2 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1533 | SlaveData1'DfrstOpStaC1 | Slave #1 - Circuit #1 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1534 | SlaveData1'DfrstOpStaC2 | Slave #1 - Circuit #2 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1535 | SlaveData2'DfrstOpStaC1 | Slave #2 - Circuit #1 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1536 | SlaveData2'DfrstOpStaC2 | Slave #2 - Circuit #2 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1537 | SlaveData3'DfrstOpStaC1 | Slave #3 - Circuit #1 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1538 | SlaveData3'DfrstOpStaC2 | Slave #3 - Circuit #2 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1539 | SlaveData4'DfrstOpStaC1 | Slave #4 - Circuit #1 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1540 | SlaveData4'DfrstOpStaC2 | Slave #4 - Circuit #2 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1541 | SlaveData5'DfrstOpStaC1 | Slave #5 - Circuit #1 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1542 | SlaveData5'DfrstOpStaC2 | Slave #5 - Circuit #2 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1543 | SlaveData6'DfrstOpStaC1 | Slave #6 - Circuit #1 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1544 | SlaveData6'DfrstOpStaC2 | Slave #6 - Circuit #2 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1545 | SlaveData7'DfrstOpStaC1 | Slave #7 - Circuit #1 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| MV | 1546 | SlaveData7'DfrstOpStaC2 | Slave #7 - Circuit #2 Defrost | Read | 0=NULL, 1=None, 2=Defrost | |
| AV | 1551 | iSM'TotCoolThermPwr | iSMs - Total cooling thermal power | kW | Read | |
| AV | 1553 | iSM'TotHeatThermPwr | iSMs - Total heating thermal power | kW | Read | |
| MV | 1555 | iSM01'PmpGrp01'Status | iSM01 - Pump Group 1 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1556 | iSM01'PmpGrp02'Status | iSM01 - Pump Group 2 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1557 | iSM01'PmpGrp03'Status | iSM01 - Pump Group 3 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1558 | iSM01'PmpGrp04'Status | iSM01 - Pump Group 4 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1559 | iSM02'PmpGrp01'Status | iSM02 - Pump Group 1 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1560 | iSM02'PmpGrp02'Status | iSM03 - Pump Group 2 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1561 | iSM02'PmpGrp03'Status | iSM02 - Pump Group 3 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1562 | iSM02'PmpGrp04'Status | iSM02 - Pump Group 4 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1563 | iSM03'PmpGrp01'Status | iSM03 - Pump Group 1 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1564 | iSM03'PmpGrp02'Status | iSM03 - Pump Group 2 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1565 | iSM03'PmpGrp03'Status | iSM03 - Pump Group 3 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| MV | 1566 | iSM03'PmpGrp04'Status | iSM02 - Pump Group 4 - Status | Read | 0=NULL, 1=Off: Auto, 2=On: Auto, 3=Off: Local, 4=Off: SensAlarm, 5=On: SensAlarm, 6=Off: CommErr, 7=On: CommErr, 8=ConfigStatus, 9=Off: ConfigAlm, 10=Test, 11=Off: Remote, 12=Off: Network | |
| BV | 1567 | iCM1st'ComErriCM2nd | iCM Expanded: BACnet Communication error w/2nd | Read | 0=None, 1=Active | |
| BV | 1568 | iCM2nd'ComErriCM1st | iCM Expanded: BACnet Communication error w/1st | Read | 0=None, 1=Active |
No points match these filters.
Integration notes
- The guide does not spell out "iCM"; Daikin's product pages call it the Intelligent Chiller Manager. It is the plant-manager software (option 184) running on the master chiller.
- SCMType (MV 1101) shows the plant type: Master/Slave, iCM Standard or iCM Advanced. Slave, energy, heat recovery, free-cooling, pump, tower, defrost and iSM objects only apply when configured.
- Each chiller's own unit objects (enable, setpoints, alarms) are on its own controller; this list is the plant-level view.
- The guide prints multistate objects as MSV; they are listed here as MV. Rows printed "as <other object>" are given that object's state texts or units.
- Revision 11/2023 matches iCM software 5.00 (adds iCT cooling towers, system heat recovery, free cooling, defrost, iSM and iCM Expanded).
- Units "°Dc" in the guide are shown as dK; counters and ranges are shown without units.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the iCM chiller plant manager, option 184 (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
How many BACnet points does the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) have?
This list has 462 BACnet objects: 2 analog inputs, 212 analog values, 43 binary values, 205 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet points are writable?
34 of the 462 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe) BACnet documentation?
The source is BAS Integration guide - BACnet protocol (iCM, Option 184) (D-EIGOC00110-21_03EN), revision 2023-11, published free by Daikin Applied at https://my.daikin.eu/content/dam/document-library/installation-manuals/iCM_BAS%20Integration%20Guid%20BACNet_D-EIGOC00110-21_English.pdf.
What are the minimum BACnet points to integrate the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)?
Start with MV 1324 MasterEnablingSp (Master unit enable (1 = Disable, 2 = Enable)); MV 1448 EvapPM'ClearAlm (Reset evaporator pump manager alarms (2 = Reset)); MV 1100 SysOpSta (Plant run state (Stop / Run)); AI 1103 CommonLWT (Common leaving chilled water temperature); AV 1107 SysActSp (Active plant setpoint); AV 1112 SystemLoad (Plant load, %); MV 1136 MasterData'State (Master chiller state, incl. Alarm / ComErr); MV 1154 S1State (Slave 1 state; S2State-S7State follow); MV 1354 EvapPM'GenAlm (Evaporator pump manager general alarm); MV 1445 ConfigErrReason (Plant configuration alarm reason (1 = None)).
How do I enable BMS control of the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)?
The guide exposes no plant start/stop or plant setpoint object. MasterEnablingSp (MV 1324) enables or disables the master unit, and the per-unit cooling/heating priorities (MV 1325-1340) and StandbyChillerSp (MV 51) set the staging; the guide does not describe how the plant itself is enabled from a BMS.
Can the BMS supply sensor values to the Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)?
Pump speed and bypass control take network setpoints (AV 1370/1373/1376/1382/1385 evaporator, AV 1411/1414/1417/1422/1425 condenser) and the tower leaving water control takes iCT'LwtCtrl'SpNtwk (AV 1462); the guide does not say how these are selected over the local values.
How do I check these points on the real iCM chiller plant manager, option 184 (Daikin Applied Europe)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00
Source: BAS Integration guide - BACnet protocol (iCM, Option 184) · D-EIGOC00110-21_03EN · rev. 2023-11. Object names, instances and units are reproduced as published; descriptions are our own.