- Home
- BACnet points lists
- Daikin Applied
- MicroTech DOAS WSHP Unit Controller
Water source heat pump DOAS controller · BACnet points list
Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet points list
Updated 28 October 2026
The MicroTech controller on SmartSource DOAS water source heat pumps has BACnet MS/TP built in (LonWorks needs an add-on module and is not listed here). Objects cover space, water, discharge, leaving coil, refrigerant and outdoor readings, outdoor-air changeover, leaving coil, reheat and dewpoint setpoints, duct and building static pressure, compressor timers and run hours, network inputs for space and outdoor temperature, humidity, CO2, entering water temperature, fan speed and DAT reset, occupancy commands, unit state and alarms. The physical binary inputs and outputs are listed as BI 1-8 and BO 1-14.
This page lists 126 BACnet objects for the Daikin Applied MicroTech DOAS WSHP Unit Controller — 54 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- MicroTech DOAS WSHP Unit Controller
- Equipment
- Water source heat pump DOAS controller
- Equipment type
- Heat pumps
- BACnet objects
- 126 (54 writable)
- Transport
- BACnet MS/TP
- Firmware
- Application v01.01.00 (PICS)
- Default device instance
- 3101120 (System Minimum Instance 3101000 + MAC 120)
- Also known as
- SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118
BMS integration notes: Daikin Applied MicroTech DOAS WSHP Unit Controller
Give the controller a unique MAC address and device instance, then command occupancy with the override or schedule input and allow the compressors with Compressor Enable. Adjust the leaving coil cooling and discharge heating setpoints if the BMS owns them, and read Unit State, discharge air temperature and Current Alarm. Network inputs are cleared by a controller reset.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 7 | OccManCmd | Occupancy override from the BMS | Write |
| MV 8 | OccSchedule | Occupancy schedule command (Occ/Unocc/Standby) | Write |
| MV 1 | NetComprEnable | Compressor enable (Null = enabled) | Write |
| AV 4 | LCTClgSetpt | Leaving coil temperature setpoint in cooling | Write |
| AV 5 | cpDAHtgSetpt | Discharge air temperature setpoint in heating | Write |
| BV 1 | ClearAlarm | Clear the current alarm | Write |
| MV 10 | UnitState | Current operating state | Read |
| AI 4 | DAT | Discharge air temperature | Read |
| MV 11 | CurrentAlarm | Highest-priority active alarm | Read |
Enable & remote start
No local/remote switch is described. Network inputs take effect when written: Network Occupancy Override Input (MV 7) overrides the current occupancy, Network Occupancy Schedule Input (MV 8) commands the scheduled mode, and Compressor Enable (MV 1) disables compressor heating and cooling (Null = enabled). Network values override local settings and revert to their defaults after a controller reset.
Heartbeat & communication loss
No BACnet heartbeat. Receive Heartbeat is a LonWorks-only setting. BACnet network inputs stay in place until the controller powers up or resets, then return to the invalid value 32767.
Sensors & values from the BMS
Network Space Temperature Input (AV 18) feeds the effective space temperature (AV 22). Network inputs also exist for outdoor temperature (AV 45), outdoor and space humidity (AV 48, AV 50), space CO2 (AV 52), entering water temperature (AV 113), duct static pressure setpoint (AV 160), fan speed (AV 115, used when Fan Control Type MV 23 is Network) and discharge air temperature reset (AV 148). The local sensor value is used when the network value is not provided.
Network setup
- Defaults: MAC address 120 (AV 411), device instance 3101120 = System Minimum Instance (AV 412, default 3101000) + MAC, 38400 baud, Max Master 127, device name DevName.
- MS/TP baud (9600, 19200, 38400 or 76800) is set from the LUI keypad or ServiceTools; speeds above 38400 need tested wiring.
- BACnet is on board; only LonWorks needs an add-on communication module.
Watch out for
- Configuration (cp...) and other non-volatile objects have a limited write life; do not write them cyclically.
- Network inputs return to 32767 (Null) after a controller reset, so the BMS must restore them.
- Some analog objects only hold whole numbers; fractional writes are rounded.
- MV 16 and MV 17 are described as network commands but printed read-only; test writes on the unit before relying on them. MV 17 states follow the range column (6 = Null); the description lists 6 = HtCl and 7 = Null.
- Over BACnet, Current Alarm (MV 11) reads 1 when no alarm is active (LonWorks uses 0).
Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | LocalSpaceTemp | Local Space Temperature | °F | Read | |
| AI | 2 | LWT | Leaving Water Temperature | °F | Read | |
| AI | 3 | LocalEWT | Entering Water Temperature | °F | Read | |
| AImin | 4 | DAT | Discharge Air Temperature | °F | Read | |
| AI | 5 | LocalSetptAdj | Local Setpoint Adjust | °F | Read | |
| AI | 6 | SuctRefTemp | Suction Refrigerant Temperature | °F | Read | |
| AI | 7 | LCT | Leaving Coil Temperature | °F | Read | |
| AI | 8 | Brownout | Brownout Detection | counts | Read | |
| AI | 9 | OutdoorTemp | Outdoor Air Temperature | °F | Read | |
| AI | 10 | LocalOutdoorRH | Outdoor Relative Humidity | % | Read | |
| AI | 11 | LocalIndoorRH | Indoor Relative Humidity | % | Read | |
| AI | 12 | LocaSpaceCO2 | Space CO2 | ppm | Read | |
| AI | 20 | BldgStatPress | Building Static Pressure | inWC | Read | |
| AI | 22 | DischRefTemp | Discharge Refrigerant Temperature | °F | Read | |
| AI | 25 | RefSuctionP | Suction Refrigerant Pressure | psi | Read | |
| AI | 26 | RefDischP | Discharge Refrigerant Pressure | psi | Read | |
| AI | 28 | LocalAIReset | Analog Input Reset | V | Read | |
| AV | 2 | OATClgSetpt | Outdoor Air Temperature Cooling Setpoint | °F | Write | |
| AVmin | 4 | LCTClgSetpt | Leaving Coil Temperature Cooling Setpoint | °F | Write | |
| AVmin | 5 | cpDAHtgSetpt | Discharge Air Temperature Heating Setpoint | °F | Write | |
| AV | 6 | DuctStatPress | Duct Static Pressure | inWC | Read | |
| AV | 7 | cpDuctStaticSP | Duct Static Pressure Setpoint | inWC | Write | |
| AV | 160 | niDuctStaticP | Network Duct Static Pressure Setpoint | inWC | Write | |
| AV | 8 | BldgStaticSP | Building Static Pressure Setpoint | inWC | Write | |
| AV | 159 | niBldgStatP | Network Buildng Static Pressure Setpoint | inWC | Read | |
| AV | 9 | cpBrownoutRef | Brownout Reference Setpoint | counts | Write | |
| AV | 10 | OATHtgSetpt | Outdoor Air Temperature Heating Setpoint | °F | Write | |
| AV | 12 | cpLowTempProt | Suction Refrigerant Temperature Low Setpoint | °F | Write | |
| AV | 13 | cpLowTempProtGL | Suction Refrigerant Temperature Low Glycol | °F | Write | |
| AV | 151 | nciLowTempProtDiff | Suction Refrigerant Temperature Low Limit Differential | °F | Write | |
| AV | 15 | cpMinCompOffTmr | Compressor Minimum Off Time | s | Write | |
| AV | 16 | cpMinCompOnTmr | Compressor Minimum On Time | s | Write | |
| AV | 18 | NetworkSpaceTemp | Network Space Temperature Input | °F | Command | |
| AV | 20 | Dewpoint | Dewpoint | °F | Read | |
| AV | 22 | EffectSpaceTemp | Effective Space Temperature Input | °F | Read | |
| AV | 30 | LowEWTSptGly | Entering Water Temperature Heating Lockout - Glycol | °F | Write | |
| AV | 31 | LowEWTSptWtr | Entering Water Temperature Heating Lockout - Water | °F | Write | |
| AV | 39 | cpBypassTime | Local Bypass Time | min | Write | |
| AV | 40 | Comp1RunHours | Compressor 1 Run Time | h | Write | |
| AV | 41 | Comp2RunHours | Compressor 2 Run Time | h | Write | |
| AV | 42 | OAFlow | Outdoor Airflow | CFM | Read | |
| AV | 44 | EffectOutdoorTemp | Effective Outdoor Air Temperature | °F | Read | |
| AV | 45 | NetworkOutdoorTemp | Network Outdoor Air Temperature Input | °F | Write | |
| AV | 46 | FanRunHoursTenths | Fan Run Time | h | Write | |
| AV | 47 | EffectOutdoorRH | Effective Outdoor Humidity | % | Read | |
| AV | 48 | NetworkOutdoorRH | Network Outdoor Humidity Input | % | Write | |
| AV | 49 | EffectSpaceRH | Effective Space Humidity | % | Read | |
| AV | 50 | NetworkSpaceRH | Network Space Humidity | % | Write | |
| AV | 51 | EffectSpaceCO2 | Effective Space CO2 | ppm | Read | |
| AV | 52 | NetworkSpaceCO2 | Network Space CO2 Input | ppm | Write | |
| AV | 53 | DATSetpt | Effective Discharge Temperature Setpoint | °F | Read | |
| AV | 57 | EffectEWT | Effective Entering Water Temperature | °F | Read | |
| AV | 58 | EffLCTSetpt | Effective Leaving Coil Temperature Setpoint | °F | Read | |
| AV | 110 | LCTLowLim | Leaving Coil Temperature Low Limit | °F | Write | |
| AV | 111 | DATHighLim | Discharge Air Temperature High | °F | Write | |
| AV | 113 | NetworkEWT | Network Entering Water Temperature Input | °F | Write | |
| AV | 115 | NetworkFanSpeedCmd | Network Fan Speed Command | % | Write | |
| AV | 116 | cpFanOnDelayTmr | Fan On Delay Timer | s | Write | |
| AV | 117 | MinFanOnTime | Minimum Fan On Time | s | Write | |
| AV | 125 | Elevation | Elevation | ft | Write | |
| AV | 126 | OATHiLkSetpt | Outdoor Air Temperature High Lockout Setpoint | °F | Write | |
| AV | 127 | OATLoLkSetpt | Outdoor Air Temperature Low Lockout Setpoint | °F | Write | |
| AV | 128 | SuctSatTemp | Saturated Suction Refrigerant Temperature (Teg) | °F | Read | |
| AV | 129 | FilterChgHrsSP | Filter Change Hours Setpoint | h | Write | |
| AV | 130 | FilterChgHrs | Filter Change Hours Timer | h | Write | |
| AV | 134 | DischSatTemp | Saturated Discharge Refrigerant Temperature (Tc) | °F | Read | |
| AV | 135 | cpACFM | PWM Constant Speed Fan Airflow | CFM | Write | |
| AV | 145 | ReheatDATSP | Discharge Air Temperature Reheat Setpoint | °F | Write | |
| AV | 146 | DewpointSetpt | Dewpoint Setpoint | °F | Write | |
| AV | 158 | LocalAiDatReset | Discharge Air Temperature Reset | V | Read | |
| AV | 148 | NetworkDATReset | Network Discharge Temperature Reset Input | °F | Write | |
| AV | 149 | ClgMinDATRst | Minimum Cooling Discharge Air Temperature Reset Setpoint | °F | Write | |
| AV | 150 | HtgMaxDATRst | Maximum Heating Discharge Air Temperature Reset Setpoint | °F | Write | |
| AV | 152 | UnitStatusPriHeat | Unit Status - Primary Heating Output | % | Read | |
| AV | 153 | UnitStatusCool | Unit Status - Cooling Output | % | Read | |
| AV | 154 | UnitStatusFan | Unit Status - Fan Output | % | Read | |
| AV | 155 | UnitStatusSecHeat | Unit Status - Secondary Heating Output | % | Read | |
| AV | 156 | Comp1Starts | Compressor 1 Starts | Read | ||
| AV | 157 | Comp2Starts | Compressor 2 Starts | Read | ||
| AV | 411 | MacAddress | BACnet MS/TP MAC Address | Write | ||
| AV | 412 | SystemMinInstance | Device Instance Number | Write | ||
| BVmin | 1 | ClearAlarm | Clear Alarm | Write | 0=None, 1=Clear | |
| BV | 3 | ResetFilter | Reset Filter | Write | 0=None, 1=Clear | |
| MI | 1 | CondOverFlow | Condensate Overflow Status | Read | 1=Dry, 2=Wet, 3=Null | |
| MVmin | 1 | NetComprEnable | Compressor Enable | Write | 1=Disable, 2=Enable, 3=Null | |
| MV | 3 | NetTimeRst | Run Timer Reset | Write | 0=None, 1=RstCmp1, 2=RstCmp2, 3=RstFan, 4=All | |
| MV | 4 | UnitStatusMode | Unit Status Mode | Read | 0=Heat, 1=Cool, 2=PreCool, 3=Off, 4=FanOnly, 5=Dehum, 6=Calibrate, 7=Auto | |
| MV | 5 | Previous Alarm | Previous Alarm | Read | ||
| MV | 6 | EffectOccup | Effective Occupancy | Read | 1=Occ, 2=Unocc, 3=Bypass, 4=Standby, 5=Null | |
| MVmin | 7 | OccManCmd | Network Occupancy Override Input | Write | 1=Occ, 2=Unocc, 3=Bypass, 4=Standby, 5=Null | |
| MVmin | 8 | OccSchedule | Network Occupancy Schedule Input | Write | 1=Occ, 2=Unocc, 3=Standby, 4=Null | |
| MV | 9 | OccSensor | Occupancy Sensor | Read | 1=Occ, 2=Unocc, 3=Null | |
| MVmin | 10 | UnitState | Unit State | Read | 1=Powerup, 2=Initialize, 3=Calibration, 4=Off, 5=Start, 6=FanOnly, 7=Prepare_Cool, 8=Cooling, 9=Prepare_Dehum, 10=Dehum, 11=Prepare_Heat, 12=Heating, 13=Defrost, 14=Alarm, 15=AlarmOff, 16=Comp_Shutdown, 17=Immediate_Shutdown, 18=Vacuum | |
| MVmin | 11 | CurrentAlarm | Current Alarm | Read | ||
| MV | 13 | PumpRequest | Pump Request Output | Read | 1=Inactive, 2=Active | |
| MV | 16 | ncpDehumEnable | Dehumidification Enable | Read | 1=Disabled, 2=Enabled, 3=Null | |
| MV | 17 | NetApplicMode | Application Mode | Read | 1=Auto, 2=Off, 3=FanOnly, 4=Heat, 5=Cool, 6=Null | |
| MV | 19 | SetpointMethod | Cooling Setpoint Method | Write | 1=Economy, 2=Precision, 3=Dehum | |
| MV | 20 | EffectHeatCool | Effective Heat/Cool | Read | 1=Auto, 2=Off, 3=FanOnly, 4=Heat, 5=Cool, 6=Dehum, 7=Invalid | |
| MV | 21 | OALockoutEn | Outdoor Air Lockout Enable | Write | 1=Disable, 2=Enable | |
| MV | 22 | FilterChgHrsEn | Filter Change Hours Enable | Write | 1=Disable, 2=Enable | |
| MV | 23 | FanCtrlMethod | Fan Control Type | Write | 1=Const, 2=DSP, 3=BSP, 4=CO2, 5=AI_Reset, 6=Network | |
| MV | 24 | UnitStatusAlarm | Unit Status - In Alarm | Read | ||
| MV | 25 | TrendRate | Trend Rate | Write | 1=None, 2=OccChange, 3=1Minute, 4=10Min, 5=Hourly, 6=Daily | |
| BI | 1 | biHighPressure | High pressure switch input (BI-1, 24 VAC) | Read | ||
| BI | 2 | biFreezeStat | Freeze stat input (BI-2, 24 VAC) | Read | ||
| BI | 3 | biLoPress-PM | Phase monitor / low pressure input (BI-3, 24 VAC) | Read | ||
| BI | 4 | BI-4 | Spare input BI-4, not used | Read | ||
| BI | 5 | biDirtyFilter | Dirty filter switch (BI-5, dry contact) | Read | ||
| BI | 6 | biERFbk | Energy recovery feedback switch (BI-6, dry contact) | Read | ||
| BI | 7 | biUnoccupied | Unoccupied input from room sensor (BI-7, 24 VAC) | Read | ||
| BI | 8 | biShutdown | Emergency shutdown input (BI-8, dry contact) | Read | ||
| BO | 1 | boFanOutput | Fan enable output (DO1) | Read | ||
| BO | 2 | boCCHeat1 | Crankcase heater output (DO2) | Read | ||
| BO | 3 | bo3 | Configurable output DO3 (default None) | Read | ||
| BO | 4 | boReversingValve | Reversing valve output (DO4, not used) | Read | ||
| BO | 5 | boFaultOut | Fault output (DO5) | Read | ||
| BO | 6 | boEREnable | Energy recovery enable output (DO6) | Read | ||
| BO | 7 | boOADamper | Outside air damper output (DO7) | Read | ||
| BO | 8 | boPump | Water loop pump request / isolation valve (DO8) | Read | ||
| BO | 9 | boC1Low | Compressor 1 low stage (DO9) | Read | ||
| BO | 10 | boC1High | Compressor 1 high stage (DO10) | Read | ||
| BO | 11 | boC2Low | Compressor 2 low stage (DO11) | Read | ||
| BO | 12 | boC2High | Compressor 2 high stage (DO12) | Read | ||
| BO | 13 | boPreheat | Preheat output (DO13, configurable) | Read | ||
| BO | 14 | bo14_Virtual | Configurable virtual output DO14 (default None) | Read |
No points match these filters.
Integration notes
- BACnet MS/TP only; the same guide also covers an optional LonWorks module, which is not listed here.
- BI 1-8 and BO 1-14 are named with the configurable parameter names that the I/O parameter tables list against each BI/BO instance (BI 4 is unused); the tables give no access, so read-only is shown. Several outputs can be reassigned at the keypad or in ServiceTools.
- Network inputs return to the invalid value 32767 (Null) after a controller power-up or reset.
- Configuration (cp...) and other non-volatile objects have a limited write life; non-volatile values are saved every 20 minutes.
- Current Alarm (MV 11), Previous Alarm (MV 5) and Unit Status - In Alarm (MV 24) return alarm numbers 1-45 from the guide's alarm table.
- Dehumidification Enable (MV 16), Application Mode (MV 17) and Occupancy Sensor (MV 9) are described as network inputs but printed read-only (R) in the guide.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech DOAS WSHP Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied MicroTech DOAS WSHP Unit Controller
How many BACnet points does the Daikin Applied MicroTech DOAS WSHP Unit Controller have?
This list has 126 BACnet objects: 17 analog inputs, 64 analog values, 8 binary inputs, 14 binary outputs, 2 binary values, 1 multi-state input, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet points are writable?
54 of the 126 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet documentation?
The source is MicroTech DOAS WSHP Unit Controller Protocol Information (BACnet MS/TP, LonWorks) (ED 19118), revision 2021-06, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20DOAS%20WSHP%20Unit%20Controller%20Protocol%20Tech-Sheet%20Daikin%20ED%2019118.pdf/.
What are the minimum BACnet points to integrate the Daikin Applied MicroTech DOAS WSHP Unit Controller?
Start with MV 7 OccManCmd (Occupancy override from the BMS); MV 8 OccSchedule (Occupancy schedule command (Occ/Unocc/Standby)); MV 1 NetComprEnable (Compressor enable (Null = enabled)); AV 4 LCTClgSetpt (Leaving coil temperature setpoint in cooling); AV 5 cpDAHtgSetpt (Discharge air temperature setpoint in heating); BV 1 ClearAlarm (Clear the current alarm); MV 10 UnitState (Current operating state); AI 4 DAT (Discharge air temperature); MV 11 CurrentAlarm (Highest-priority active alarm).
How do I enable BMS control of the Daikin Applied MicroTech DOAS WSHP Unit Controller?
No local/remote switch is described. Network inputs take effect when written: Network Occupancy Override Input (MV 7) overrides the current occupancy, Network Occupancy Schedule Input (MV 8) commands the scheduled mode, and Compressor Enable (MV 1) disables compressor heating and cooling (Null = enabled). Network values override local settings and revert to their defaults after a controller reset.
Does the Daikin Applied MicroTech DOAS WSHP Unit Controller need a BACnet heartbeat or have a communication timeout?
No BACnet heartbeat. Receive Heartbeat is a LonWorks-only setting. BACnet network inputs stay in place until the controller powers up or resets, then return to the invalid value 32767.
Can the BMS supply sensor values to the Daikin Applied MicroTech DOAS WSHP Unit Controller?
Network Space Temperature Input (AV 18) feeds the effective space temperature (AV 22). Network inputs also exist for outdoor temperature (AV 45), outdoor and space humidity (AV 48, AV 50), space CO2 (AV 52), entering water temperature (AV 113), duct static pressure setpoint (AV 160), fan speed (AV 115, used when Fan Control Type MV 23 is Network) and discharge air temperature reset (AV 148). The local sensor value is used when the network value is not provided.
How do I check these points on the real MicroTech DOAS WSHP Unit Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00
Source: MicroTech DOAS WSHP Unit Controller Protocol Information (BACnet MS/TP, LonWorks) · ED 19118 · rev. 2021-06. Object names, instances and units are reproduced as published; descriptions are our own.