Water source heat pump DOAS controller · BACnet points list

Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet points list

Updated 28 October 2026

Short answer

The MicroTech controller on SmartSource DOAS water source heat pumps has BACnet MS/TP built in (LonWorks needs an add-on module and is not listed here). Objects cover space, water, discharge, leaving coil, refrigerant and outdoor readings, outdoor-air changeover, leaving coil, reheat and dewpoint setpoints, duct and building static pressure, compressor timers and run hours, network inputs for space and outdoor temperature, humidity, CO2, entering water temperature, fan speed and DAT reset, occupancy commands, unit state and alarms. The physical binary inputs and outputs are listed as BI 1-8 and BO 1-14.

This page lists 126 BACnet objects for the Daikin Applied MicroTech DOAS WSHP Unit Controller — 54 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech DOAS WSHP Unit Controller
Equipment
Water source heat pump DOAS controller
Equipment type
Heat pumps
BACnet objects
126 (54 writable)
Transport
BACnet MS/TP
Firmware
Application v01.01.00 (PICS)
Default device instance
3101120 (System Minimum Instance 3101000 + MAC 120)
Also known as
SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118
Source document
MicroTech DOAS WSHP Unit Controller Protocol Information (BACnet MS/TP, LonWorks) · ED 19118 · rev. 2021-06
Download CSV 126 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied MicroTech DOAS WSHP Unit Controller

Integration in brief

Give the controller a unique MAC address and device instance, then command occupancy with the override or schedule input and allow the compressors with Compressor Enable. Adjust the leaving coil cooling and discharge heating setpoints if the BMS owns them, and read Unit State, discharge air temperature and Current Alarm. Network inputs are cleared by a controller reset.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 7OccManCmdOccupancy override from the BMSWrite
MV 8OccScheduleOccupancy schedule command (Occ/Unocc/Standby)Write
MV 1NetComprEnableCompressor enable (Null = enabled)Write
AV 4LCTClgSetptLeaving coil temperature setpoint in coolingWrite
AV 5cpDAHtgSetptDischarge air temperature setpoint in heatingWrite
BV 1ClearAlarmClear the current alarmWrite
MV 10UnitStateCurrent operating stateRead
AI 4DATDischarge air temperatureRead
MV 11CurrentAlarmHighest-priority active alarmRead

Enable & remote start

No local/remote switch is described. Network inputs take effect when written: Network Occupancy Override Input (MV 7) overrides the current occupancy, Network Occupancy Schedule Input (MV 8) commands the scheduled mode, and Compressor Enable (MV 1) disables compressor heating and cooling (Null = enabled). Network values override local settings and revert to their defaults after a controller reset.

Heartbeat & communication loss

No BACnet heartbeat. Receive Heartbeat is a LonWorks-only setting. BACnet network inputs stay in place until the controller powers up or resets, then return to the invalid value 32767.

Sensors & values from the BMS

Network Space Temperature Input (AV 18) feeds the effective space temperature (AV 22). Network inputs also exist for outdoor temperature (AV 45), outdoor and space humidity (AV 48, AV 50), space CO2 (AV 52), entering water temperature (AV 113), duct static pressure setpoint (AV 160), fan speed (AV 115, used when Fan Control Type MV 23 is Network) and discharge air temperature reset (AV 148). The local sensor value is used when the network value is not provided.

Network setup

Watch out for

Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

126 of 126 shown
Type
Access
Show
Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet Points List
DescriptionStates
AI1LocalSpaceTempLocal Space Temperature°FRead
AI2LWTLeaving Water Temperature°FRead
AI3LocalEWTEntering Water Temperature°FRead
AImin4DATDischarge Air Temperature°FRead
AI5LocalSetptAdjLocal Setpoint Adjust°FRead
AI6SuctRefTempSuction Refrigerant Temperature°FRead
AI7LCTLeaving Coil Temperature°FRead
AI8BrownoutBrownout DetectioncountsRead
AI9OutdoorTempOutdoor Air Temperature°FRead
AI10LocalOutdoorRHOutdoor Relative Humidity%Read
AI11LocalIndoorRHIndoor Relative Humidity%Read
AI12LocaSpaceCO2Space CO2ppmRead
AI20BldgStatPressBuilding Static PressureinWCRead
AI22DischRefTempDischarge Refrigerant Temperature°FRead
AI25RefSuctionPSuction Refrigerant PressurepsiRead
AI26RefDischPDischarge Refrigerant PressurepsiRead
AI28LocalAIResetAnalog Input ResetVRead
AV2OATClgSetptOutdoor Air Temperature Cooling Setpoint°FWrite
AVmin4LCTClgSetptLeaving Coil Temperature Cooling Setpoint°FWrite
AVmin5cpDAHtgSetptDischarge Air Temperature Heating Setpoint°FWrite
AV6DuctStatPressDuct Static PressureinWCRead
AV7cpDuctStaticSPDuct Static Pressure SetpointinWCWrite
AV160niDuctStaticPNetwork Duct Static Pressure SetpointinWCWrite
AV8BldgStaticSPBuilding Static Pressure SetpointinWCWrite
AV159niBldgStatPNetwork Buildng Static Pressure SetpointinWCRead
AV9cpBrownoutRefBrownout Reference SetpointcountsWrite
AV10OATHtgSetptOutdoor Air Temperature Heating Setpoint°FWrite
AV12cpLowTempProtSuction Refrigerant Temperature Low Setpoint°FWrite
AV13cpLowTempProtGLSuction Refrigerant Temperature Low Glycol°FWrite
AV151nciLowTempProtDiffSuction Refrigerant Temperature Low Limit Differential°FWrite
AV15cpMinCompOffTmrCompressor Minimum Off TimesWrite
AV16cpMinCompOnTmrCompressor Minimum On TimesWrite
AV18NetworkSpaceTempNetwork Space Temperature Input°FCommand
AV20DewpointDewpoint°FRead
AV22EffectSpaceTempEffective Space Temperature Input°FRead
AV30LowEWTSptGlyEntering Water Temperature Heating Lockout - Glycol°FWrite
AV31LowEWTSptWtrEntering Water Temperature Heating Lockout - Water°FWrite
AV39cpBypassTimeLocal Bypass TimeminWrite
AV40Comp1RunHoursCompressor 1 Run TimehWrite
AV41Comp2RunHoursCompressor 2 Run TimehWrite
AV42OAFlowOutdoor AirflowCFMRead
AV44EffectOutdoorTempEffective Outdoor Air Temperature°FRead
AV45NetworkOutdoorTempNetwork Outdoor Air Temperature Input°FWrite
AV46FanRunHoursTenthsFan Run TimehWrite
AV47EffectOutdoorRHEffective Outdoor Humidity%Read
AV48NetworkOutdoorRHNetwork Outdoor Humidity Input%Write
AV49EffectSpaceRHEffective Space Humidity%Read
AV50NetworkSpaceRHNetwork Space Humidity%Write
AV51EffectSpaceCO2Effective Space CO2ppmRead
AV52NetworkSpaceCO2Network Space CO2 InputppmWrite
AV53DATSetptEffective Discharge Temperature Setpoint°FRead
AV57EffectEWTEffective Entering Water Temperature°FRead
AV58EffLCTSetptEffective Leaving Coil Temperature Setpoint°FRead
AV110LCTLowLimLeaving Coil Temperature Low Limit°FWrite
AV111DATHighLimDischarge Air Temperature High°FWrite
AV113NetworkEWTNetwork Entering Water Temperature Input°FWrite
AV115NetworkFanSpeedCmdNetwork Fan Speed Command%Write
AV116cpFanOnDelayTmrFan On Delay TimersWrite
AV117MinFanOnTimeMinimum Fan On TimesWrite
AV125ElevationElevationftWrite
AV126OATHiLkSetptOutdoor Air Temperature High Lockout Setpoint°FWrite
AV127OATLoLkSetptOutdoor Air Temperature Low Lockout Setpoint°FWrite
AV128SuctSatTempSaturated Suction Refrigerant Temperature (Teg)°FRead
AV129FilterChgHrsSPFilter Change Hours SetpointhWrite
AV130FilterChgHrsFilter Change Hours TimerhWrite
AV134DischSatTempSaturated Discharge Refrigerant Temperature (Tc)°FRead
AV135cpACFMPWM Constant Speed Fan AirflowCFMWrite
AV145ReheatDATSPDischarge Air Temperature Reheat Setpoint°FWrite
AV146DewpointSetptDewpoint Setpoint°FWrite
AV158LocalAiDatResetDischarge Air Temperature ResetVRead
AV148NetworkDATResetNetwork Discharge Temperature Reset Input°FWrite
AV149ClgMinDATRstMinimum Cooling Discharge Air Temperature Reset Setpoint°FWrite
AV150HtgMaxDATRstMaximum Heating Discharge Air Temperature Reset Setpoint°FWrite
AV152UnitStatusPriHeatUnit Status - Primary Heating Output%Read
AV153UnitStatusCoolUnit Status - Cooling Output%Read
AV154UnitStatusFanUnit Status - Fan Output%Read
AV155UnitStatusSecHeatUnit Status - Secondary Heating Output%Read
AV156Comp1StartsCompressor 1 StartsRead
AV157Comp2StartsCompressor 2 StartsRead
AV411MacAddressBACnet MS/TP MAC AddressWrite
AV412SystemMinInstanceDevice Instance NumberWrite
BVmin1ClearAlarmClear AlarmWrite0=None, 1=Clear
BV3ResetFilterReset FilterWrite0=None, 1=Clear
MI1CondOverFlowCondensate Overflow StatusRead1=Dry, 2=Wet, 3=Null
MVmin1NetComprEnableCompressor EnableWrite1=Disable, 2=Enable, 3=Null
MV3NetTimeRstRun Timer ResetWrite0=None, 1=RstCmp1, 2=RstCmp2, 3=RstFan, 4=All
MV4UnitStatusModeUnit Status ModeRead0=Heat, 1=Cool, 2=PreCool, 3=Off, 4=FanOnly, 5=Dehum, 6=Calibrate, 7=Auto
MV5Previous AlarmPrevious AlarmRead
MV6EffectOccupEffective OccupancyRead1=Occ, 2=Unocc, 3=Bypass, 4=Standby, 5=Null
MVmin7OccManCmdNetwork Occupancy Override InputWrite1=Occ, 2=Unocc, 3=Bypass, 4=Standby, 5=Null
MVmin8OccScheduleNetwork Occupancy Schedule InputWrite1=Occ, 2=Unocc, 3=Standby, 4=Null
MV9OccSensorOccupancy SensorRead1=Occ, 2=Unocc, 3=Null
MVmin10UnitStateUnit StateRead1=Powerup, 2=Initialize, 3=Calibration, 4=Off, 5=Start, 6=FanOnly, 7=Prepare_Cool, 8=Cooling, 9=Prepare_Dehum, 10=Dehum, 11=Prepare_Heat, 12=Heating, 13=Defrost, 14=Alarm, 15=AlarmOff, 16=Comp_Shutdown, 17=Immediate_Shutdown, 18=Vacuum
MVmin11CurrentAlarmCurrent AlarmRead
MV13PumpRequestPump Request OutputRead1=Inactive, 2=Active
MV16ncpDehumEnableDehumidification EnableRead1=Disabled, 2=Enabled, 3=Null
MV17NetApplicModeApplication ModeRead1=Auto, 2=Off, 3=FanOnly, 4=Heat, 5=Cool, 6=Null
MV19SetpointMethodCooling Setpoint MethodWrite1=Economy, 2=Precision, 3=Dehum
MV20EffectHeatCoolEffective Heat/CoolRead1=Auto, 2=Off, 3=FanOnly, 4=Heat, 5=Cool, 6=Dehum, 7=Invalid
MV21OALockoutEnOutdoor Air Lockout EnableWrite1=Disable, 2=Enable
MV22FilterChgHrsEnFilter Change Hours EnableWrite1=Disable, 2=Enable
MV23FanCtrlMethodFan Control TypeWrite1=Const, 2=DSP, 3=BSP, 4=CO2, 5=AI_Reset, 6=Network
MV24UnitStatusAlarmUnit Status - In AlarmRead
MV25TrendRateTrend RateWrite1=None, 2=OccChange, 3=1Minute, 4=10Min, 5=Hourly, 6=Daily
BI1biHighPressureHigh pressure switch input (BI-1, 24 VAC)Read
BI2biFreezeStatFreeze stat input (BI-2, 24 VAC)Read
BI3biLoPress-PMPhase monitor / low pressure input (BI-3, 24 VAC)Read
BI4BI-4Spare input BI-4, not usedRead
BI5biDirtyFilterDirty filter switch (BI-5, dry contact)Read
BI6biERFbkEnergy recovery feedback switch (BI-6, dry contact)Read
BI7biUnoccupiedUnoccupied input from room sensor (BI-7, 24 VAC)Read
BI8biShutdownEmergency shutdown input (BI-8, dry contact)Read
BO1boFanOutputFan enable output (DO1)Read
BO2boCCHeat1Crankcase heater output (DO2)Read
BO3bo3Configurable output DO3 (default None)Read
BO4boReversingValveReversing valve output (DO4, not used)Read
BO5boFaultOutFault output (DO5)Read
BO6boEREnableEnergy recovery enable output (DO6)Read
BO7boOADamperOutside air damper output (DO7)Read
BO8boPumpWater loop pump request / isolation valve (DO8)Read
BO9boC1LowCompressor 1 low stage (DO9)Read
BO10boC1HighCompressor 1 high stage (DO10)Read
BO11boC2LowCompressor 2 low stage (DO11)Read
BO12boC2HighCompressor 2 high stage (DO12)Read
BO13boPreheatPreheat output (DO13, configurable)Read
BO14bo14_VirtualConfigurable virtual output DO14 (default None)Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech DOAS WSHP Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech DOAS WSHP Unit Controller

How many BACnet points does the Daikin Applied MicroTech DOAS WSHP Unit Controller have?

This list has 126 BACnet objects: 17 analog inputs, 64 analog values, 8 binary inputs, 14 binary outputs, 2 binary values, 1 multi-state input, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet points are writable?

54 of the 126 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech DOAS WSHP Unit Controller BACnet documentation?

The source is MicroTech DOAS WSHP Unit Controller Protocol Information (BACnet MS/TP, LonWorks) (ED 19118), revision 2021-06, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20DOAS%20WSHP%20Unit%20Controller%20Protocol%20Tech-Sheet%20Daikin%20ED%2019118.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech DOAS WSHP Unit Controller?

Start with MV 7 OccManCmd (Occupancy override from the BMS); MV 8 OccSchedule (Occupancy schedule command (Occ/Unocc/Standby)); MV 1 NetComprEnable (Compressor enable (Null = enabled)); AV 4 LCTClgSetpt (Leaving coil temperature setpoint in cooling); AV 5 cpDAHtgSetpt (Discharge air temperature setpoint in heating); BV 1 ClearAlarm (Clear the current alarm); MV 10 UnitState (Current operating state); AI 4 DAT (Discharge air temperature); MV 11 CurrentAlarm (Highest-priority active alarm).

How do I enable BMS control of the Daikin Applied MicroTech DOAS WSHP Unit Controller?

No local/remote switch is described. Network inputs take effect when written: Network Occupancy Override Input (MV 7) overrides the current occupancy, Network Occupancy Schedule Input (MV 8) commands the scheduled mode, and Compressor Enable (MV 1) disables compressor heating and cooling (Null = enabled). Network values override local settings and revert to their defaults after a controller reset.

Does the Daikin Applied MicroTech DOAS WSHP Unit Controller need a BACnet heartbeat or have a communication timeout?

No BACnet heartbeat. Receive Heartbeat is a LonWorks-only setting. BACnet network inputs stay in place until the controller powers up or resets, then return to the invalid value 32767.

Can the BMS supply sensor values to the Daikin Applied MicroTech DOAS WSHP Unit Controller?

Network Space Temperature Input (AV 18) feeds the effective space temperature (AV 22). Network inputs also exist for outdoor temperature (AV 45), outdoor and space humidity (AV 48, AV 50), space CO2 (AV 52), entering water temperature (AV 113), duct static pressure setpoint (AV 160), fan speed (AV 115, used when Fan Control Type MV 23 is Network) and discharge air temperature reset (AV 148). The local sensor value is used when the network value is not provided.

How do I check these points on the real MicroTech DOAS WSHP Unit Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech DOAS WSHP Unit Controller Protocol Information (BACnet MS/TP, LonWorks) · ED 19118 · rev. 2021-06. Object names, instances and units are reproduced as published; descriptions are our own.