Water-cooled screw chiller controller · BACnet points list

Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe) BACnet points list

Updated 28 October 2026

Short answer

The European EWWD/EWWH/EWWS VZ water-cooled screw chillers use a MicroTech controller running the "Adam" software. BACnet IP or BACnet MS/TP is added with a plug-in POL908 or POL904 module, or on MicroTech 4 as an onboard software option. The list covers unit enable, mode and network setpoints, evaporator and condenser water temperatures, per-circuit refrigerant data, compressor VFD values and a large set of individual alarm BVs, plus warning/problem/fault index and code AVs.

This page lists 209 BACnet objects for the Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Equipment
Water-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
209 (14 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1
Also known as
EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101
Source document
BAS Integration guide - BACnet protocol (EWWD(H)(S)_VZ) · D-EIGOC00101-22_02EN_VZ · rev. 2022
Download CSV 209 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)

Integration in brief

Select network control at the unit (CtrlSource BI 3 then reads Network), enable the chiller with UnitEnableStp, and write the mode, cool setpoint and capacity limit at priority 8. Monitor unit status, leaving water temperature, the alarm output and the fault code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2UnitEnableStpNetwork enable/disable of the chillerCommand
MV 3UnitModeSetpointNetworkIce / cool / heat / pursuit mode commandCommand
AV 4NetworkCoolTempSetpointLeaving water cool setpoint from the BMSCommand
AV 3NetworkCapacityLimitSetpointCapacity limit from the BMSCommand
BV 8ClearAlarmClear alarms from the networkCommand
BI 3CtrlSourceShows whether network control is activeRead
MV 1UnitStatusChiller run stateRead
AI 2EvapLvgWTempLeaving chilled water temperatureRead
BI 10AlarmOutputAny active alarmRead
AV 905AVFaultAlarmCodeActive fault alarm codeRead

Enable & remote start

CtrlSource (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes UnitEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.

Network setup

Watch out for

Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

209 of 209 shown
Type
Multi-state
Access
Show
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe) BACnet Points List
DescriptionStates
BImin3CtrlSourceUnit - Control SourceRead0=Network, 1=Local
BI7EnableOutputUnit - Enabled StateRead0=Disabled, 1=Enabled
BI5RunEnabledUnit - Run AllowedRead0=Off, 1=RunAllowed
BI6UnitLimitedUnit - Capacity LimitedRead0=NotLimited, 1=Limited
BImin10AlarmOutputUnit - Alarm OutputRead0=NoAlarm, 1=Alarm
BI2EvapWFlowStateEvaporator - Water Flow StateRead0=NoFlow, 1=Flow
BI1CondWFlowStateCondenser - Water Flow StateRead0=NoFlow, 1=Flow
BI4UnitOnOffUnit - Operating StateRead0=Off, 1=On
BVmin2UnitEnableStpUnit - Enable SetpointCommand0=Disable, 1=Enable
BVmin8ClearAlarmUnit - Alarm Reset SetpointCommand0=None, 1=ClearAlarm
MV2ActModeUnit - Active Operation ModeRead1=Ice, 2=Cool, 3=Heat, 4=Pursuit
AV5ActTempStpUnit - Active Temperature Setpoint°CRead
AV2ActCapacityUnit - Actual Capacity%Read
AV1ActCapacityLimUnit - Active Capacity Limit%Read
MVmin1UnitStatusUnit - StatusRead1=Off, 2=Start, 3=Run, 4=PreShutdown, 5=Service
AI1EvapEntWTempEvaporator Entering Water Temperature°CRead
AImin2EvapLvgWTempEvaporator Leaving Water Temperature°CRead
AI3CondEntWTempCondenser Entering Water Temperature°CRead
AI4CondLvgWTempCondenser Leaving Water Temperature°CRead
AI993AvgCurrentUnit - Average CurrentARead
AV992AvgVoltageUnit - Average VoltageVRead
AV994ActPowerUnit - Active PowerkWRead
AV902AVWarningAlarmUnit Alarm - Warning IndexRead
AV900AVProblemAlarmUnit Alarm - Problem IndexRead
AV901AVFaultAlarmUnit Alarm - Fault IndexRead
AV903AVWarningAlarmCodeUnit Alarm - Warning CodeRead
AV904AVProblemAlarmCodeUnit Alarm - Problem CodeRead
AVmin905AVFaultAlarmCodeUnit Alarm - Fault CodeRead
MVmin3UnitModeSetpointNetworkUnit - Operation Mode SetpointCommand1=Ice, 2=Cool, 3=Heat, 4=Pursuit
AVmin3NetworkCapacityLimitSetpointUnit - Capacity Limit Setpoint%Command
AV7NetworkIceTempSetpointUnit - Ice Temperature Setpoint°CCommand
AVmin4NetworkCoolTempSetpointUnit - Cool Temperature Setpoint°CCommand
AV6NetworkHeatTempSetpointUnit - Heat Temperature Setpoint°CCommand
MV4UnitsUnit - BACnet Measurement unit setpointWrite1=Metric, 2=English
AI99C1.CondRefPressureCircuit 1 - Condenser Refrigerant PressurekPaRead
AV34C1.CondSatRefTempCircuit 1 - Condeser Saturated Temperature°CRead
AI141C1.EvapRefPressureCircuit 1 - Evaporator Refrigerant PressurekPaRead
AV68C1.EvapSatRefTempCircuit 1 - Evaporator Saturated Temperature°CRead
AI100C2.CondRefPressureCircuit 2 - Condenser Refrigerant PressurekPaRead
AV35C2.CondSatRefTempCircuit 2 - Condeser Saturated Temperature°CRead
AI142C2.EvapRefPressureCircuit 2 - Evaporator Refrigerant PressurekPaRead
AV69C2.EvapSatRefTempCircuit 2 - Evaporator Saturated Temperature°CRead
MV51C1.ShutdownAlmCircuit 1 - Shutdown AlarmRead1=NoAlarm, 2=Alarm
MV52C2.ShutdownAlmCircuit 2 - Shutdown AlarmRead1=NoAlarm, 2=Alarm
AI105C1.Comp1.SuctTempCirc 1 Compressor 1 - Suction Temperature°CRead
AI63C1.Comp1.DischTempCirc 1 Compressor 1 - Discharge Temperature°CRead
AV8C1.Comp1.RLAPercentCirc 1 Compressor 1 - RLA Percentage%Read
AI9C1.Comp1.CurrentCirc 1 Compressor 1 - CurrentARead
AI27C1.Comp1.VoltageCirc 1 Compressor 1 - VoltageVRead
AI45C1.Comp1.PowerCirc 1 Compressor 1 - PowerkWRead
AV92C1.Comp1.StartsCirc 1 Compressor 1 - Number of StartsWrite
AV74C1.Comp1.RunHoursCirc 1 Compressor 1 - Number of Running HourshWrite
AI108C2.Comp1.SuctTempCirc 2 Compressor 1 - Suction Temperature°CRead
AI66C2.Comp1.DischTempCirc 2 Compressor 1 - Discharge Temperature°CRead
AV11C2.Comp1.RLAPercentCirc 2 Compressor 1 - RLA Percentage%Read
AI12C2.Comp1.CurrentCirc 2 Compressor 1 - CurrentARead
AI30C2.Comp1.VoltageCirc 2 Compressor 1 - VoltageVRead
AI47C2.Comp1.PowerCirc 2 Compressor 1 - PowerkWRead
AV95C2.Comp1.StartsCirc 2 Compressor 1 - Number of StartsWrite
AV77C2.Comp1.HoursCirc 2 Compressor 1 - Number of Running HourshWrite
AV260ThermCapacityPerformance - Unit Thermal CapacitykWRead
AV262ElectPowerPerformance - Unit Power InputkWRead
AV264EERPerformance - Unit EfficiencyRead
AV265integralEERPerformance - Unit Integrated EfficiencyRead
AV261ThermEnergyPerformance - Unit Thermal EnergyMWhRead
AV263ElectEnergyPerformance - Unit Electrical EnergyMWhRead
AV110CondPump1.RunHrsCondenser Pump 1 - Number of Running HourshRead
BI11CondPump1.StatusCondenser Pump 1 - Operating StateRead0=OffRequest, 1=OnRequest
AV111CondPump2.RunHrsCondenser Pump 2 - Number of Running HourshRead
BI12CondPump2.StatusCondenser Pump 2 - Operating StateRead0=OffRequest, 1=OnRequest
AV112EvapPump1.RunHoursEvaporator Pump 1 - Number of Running HourshRead
BI8EvapPump1.StateEvaporator Pump 1 - Operating StateRead0=OffRequest, 1=OnRequest
AV113EvapPump2.RunHoursEvaporator Pump 2 - Number of Running HourshRead
BI9EvapPump2.StateEvaporator Pump 2 - Operating StateRead0=OffRequest, 1=OnRequest
MV317UnitModelUnit - ModelRead1=Centrifugal, 2=Water Cooled, 3=Air Cooled, 4=HeatPump, 5=Reserved, 6=Reserved, 7=Reserved, 8=Reserved, 9=Other
BV500Unit.OFFCndEntWTempFailUnit Alarm - Condenser Entering Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV917Unit.OFFEvapEntWTempFailUnit Alarm - Evaporator Entering Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV503Unit.OFFCndLvgWTempFailUnit Alarm - Condenser Leaving Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV512BadSetpointResetInputUnit Warning - Setpoint Reset Input Out of RangeRead0=NoAlarm, 1=Alarm
BV513BadDemandLimitInputUnit Warning - Demand Limit Input Out of RangeRead0=NoAlarm, 1=Alarm
BV529C1.InhibitPwrLossCircuit 1 Warning - Power Loss while Compressor RunningRead0=NoAlarm, 1=Alarm
BV530C2.InhibitPwrLossCircuit 2 Warning - Power Loss while Compressor RunningRead0=NoAlarm, 1=Alarm
AI535C1.InhibitCondPresHiCircuit 1 Warning - Inhibition for Condenser High PressurekPaRead
AI536C2.InhibitCondPresHiCircuit 2 Warning - Inhibition for Condenser High PressurekPaRead
AI540C1.UnloadCondPresHiCircuit 1 Warning - Unload for Condenser High PressurekPaRead
AI541C2.UnloadCondPresHiCircuit 2 Warning - Unload for Condenser High PressurekPaRead
AI556C1.InhibitEvapPresLowCircuit 1 Warning - Inhibition for Evaporator Low PressurekPaRead
AI557C2.InhibitEvapPresLowCircuit 2 Warning - Inhibition for Evaporator Low PressurekPaRead
AI561C1.UnloadEvapPresLowCircuit 1 Warning - Unload for Evaporator Low PressurekPaRead
AI562C2.UnloadEvapPresLowCircuit 2 Warning - Unload for Evaporator Low PressurekPaRead
AI565C1.Comp1.UnloadCurrentHiCirc 1 Comp 1 Warning - Unload for High CurrentARead
AI567C2.Comp1.UnloadCurrentHiCirc 2 Comp 1 Warning - Unload for High CurrentARead
BV548CondPump1.FaultCondenser Pump 1 - FaultRead0=NoAlarm, 1=Alarm
BV549CondPump2.FaultCondenser Pump 2 - FaultRead0=NoAlarm, 1=Alarm
BV575EvapPump1.FaultEvaporator Pump 1 - FaultRead0=NoAlarm, 1=Alarm
BV576EvapPump2.FaultEvaporator Pump 2 - FaultRead0=NoAlarm, 1=Alarm
BV599C1.Comp1.OFFPresRatioLowCirc 1 Comp 1 Alarm - Low Pressure RatioRead0=NoAlarm, 1=Alarm
BV601C2.Comp1.OFFPresRatioLowCirc 2 Comp 1 Alarm - Low Pressure RatioRead0=NoAlarm, 1=Alarm
BV606C1.Comp1.OFFCurrentHiCirc 1 Comp 1 Alarm - High Motor CurrentRead0=NoAlarm, 1=Alarm
BV608C2.Comp1.OFFCurrentHiCirc 2 Comp 1 Alarm - High Motor CurrentRead0=NoAlarm, 1=Alarm
BV637C1.Comp1.OFFMotorTempHiCirc 1 Comp 1 Alarm - High Motor TemperatureRead0=NoAlarm, 1=Alarm
BV639C2.Comp1.OFFMotorTempHiCirc 2 Comp 1 Alarm - High Motor TemperatureRead0=NoAlarm, 1=Alarm
BV668C1.OFFCondPresFailCircuit 1 Alarm - Condenser Pressure Sensor FaultRead0=NoAlarm, 1=Alarm
BV670C2.OFFCondPresFailCircuit 2 Alarm - Condenser Pressure Sensor FaultRead0=NoAlarm, 1=Alarm
BV989Unit.OFFCondLvgWTempLowUnit Alarm - Condenser Water FreezeRead0=NoAlarm, 1=Alarm
BV674Unit.OFFCondFlowLossUnit Alarm - Condenser Water Flow LossRead0=NoAlarm, 1=Alarm
BV676C1.OFFCondPresHiCircuit 1 Alarm - Condenser High PressureRead0=NoAlarm, 1=Alarm
BV678C2.OFFCondPresHiCircuit 2 Alarm - Condenser High PressureRead0=NoAlarm, 1=Alarm
BV688C1.OFFDischTempFailCircuit 1 Alarm - Discharge Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV690C2.OFFDischTempFailCircuit 2 Alarm - Discharge Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV694C1.Comp1.OFFDischTempHiCirc 1 Comp 1 Alarm - High Discharge TemperatureRead0=NoAlarm, 1=Alarm
BV696C2.Comp1.OFFDischTempHiCirc 2 Comp 1 Alarm - High Discharge TemperatureRead0=NoAlarm, 1=Alarm
BV701Unit.OFFEvapFlowLossUnit Alarm - Evaporator Water Flow LossRead0=NoAlarm, 1=Alarm
BV702Unit.OFFEvapLvgWTempLowUnit Alarm - Evaporator Water FreezeRead0=NoAlarm, 1=Alarm
BV704C1.OFFEvapPresLowCircuit 1 Alarm - Evaporator Pressure LowRead0=NoAlarm, 1=Alarm
BV706C2.OFFEvapPresLowCircuit 2 Alarm - Evaporator Pressure LowRead0=NoAlarm, 1=Alarm
BV711C1.OFFEvapPresFailCircuit 1 Alarm - Evaporator Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV713C2.OFFEvapPresFailCircuit 2 Alarm - Evaporator Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV742C1.OFFRestartsAlmCircuit 1 Alarm - Too many restartRead0=NoAlarm, 1=Alarm
BV744C2.OFFRestartsAlmCircuit 2 Alarm - Too many restartRead0=NoAlarm, 1=Alarm
BV748Unit.OFFEvapLvgWTempFailUnit Alarm - Evaporator Leaving Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV760C1.OFFMechPressHiCircuit 1 Alarm - Mechanical High PressureRead0=NoAlarm, 1=Alarm
BV762C2.OFFMechPressHiCircuit 2 Alarm - Mechanical High PressureRead0=NoAlarm, 1=Alarm
BV790C1.OFFOilLevelLowCircuit 1 Alarm - Oil Level LowRead0=NoAlarm, 1=Alarm
BV792C2.OFFOilLevelLowCircuit 2 Alarm - Oil Level LowRead0=NoAlarm, 1=Alarm
BV796C1.OFFOilFilterPresHiCircuit 1 Alarm - Oil Filter High PressureRead0=NoAlarm, 1=Alarm
BV798C2.OFFOilFilterPresHiCircuit 2 Alarm - Oil Filter High PressureRead0=NoAlarm, 1=Alarm
BV802C1.OFFOilPresFailCircuit 1 Alarm - Oil Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV804C2.OFFOilPresFailCircuit 2 Alarm - Oil Pressure Sensor FailureRead0=NoAlarm, 1=Alarm
BV735C1.OFFLiquidTsenfCircuit 1 Alarm - Liquid Temperature Sensor FailureRead0=NoAlarm, 1=Alarm
BV737C2.OFFLiquidTsenfCircuit 2 Alarm - Liquid Temperature Sensor FailureRead0=NoAlarm, 1=Alarm
BV820Unit.OFFPhaseVoltageUnit Alarm - Phase VoltageRead0=NoAlarm, 1=Alarm
BV821C1.Comp1.OFFStarterFaultCirc 1 Comp 1 Alarm - Starter FaultRead0=NoAlarm, 1=Alarm
BV823C2.Comp1.OFFStarterFaultCirc 2 Comp 1 Alarm - Starter FaultRead0=NoAlarm, 1=Alarm
BV978C1.OFFOverVoltageCircuit 1 Alarm - OverVoltageRead0=NoAlarm, 1=Alarm
BV982C2.OFFOverVoltageCircuit 2 Alarm - OverVoltageRead0=NoAlarm, 1=Alarm
BV979C1.OFFUnderVoltageCircuit 1 Alarm - UnderVoltageRead0=NoAlarm, 1=Alarm
BV981C2.OFFUnderVoltageCircuit 2 Alarm - UnderVoltageRead0=NoAlarm, 1=Alarm
BV857C1.Comp1.OFFSuctTempFailCirc 1 Comp 1 Alarm - Suction Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV859C2.Comp1.OFFSuctTempSenCirc 2 Comp 1 Alarm - Suction Temperature Sensor FaultRead0=NoAlarm, 1=Alarm
BV911C1.OFFNoPressStartCircuit 1 Alarm - No Pressure at StartRead0=NoAlarm, 1=Alarm
BV912C2.OFFNoPressStartCircuit 2 Alarm - No Pressure at StartRead0=NoAlarm, 1=Alarm
BV876C1.OFFMechPresLowCircuit 1 Alarm - Mechanical Low PressureRead0=NoAlarm, 1=Alarm
BV878C2.OFFMechPresLowCircuit 2 Alarm - Mechanical Low PressureRead0=NoAlarm, 1=Alarm
BV723C1.OFFBoardOfflineController Alarm - Circuit 1 Board OfflineRead0=NoAlarm, 1=Alarm
BV724C2.OFFBoardOfflineController Alarm - Circuit 2 Board OfflineRead0=NoAlarm, 1=Alarm
BV726C1.OFFEXVBoardOfflineController Alarm - Expansion Valve 1 Board OfflineRead0=NoAlarm, 1=Alarm
BV727C2.OFFEXVBoardOfflineController Alarm - Expansion Valve 2 Board OfflineRead0=NoAlarm, 1=Alarm
BV729C2.OFFCompBoardOfflineController Alarm - Compressor 1 Board OfflineRead0=NoAlarm, 1=Alarm
BV730C2.OFFCompBoardOfflineController Alarm - Compressor 2 Board OfflineRead0=NoAlarm, 1=Alarm
BV899C1.Comp1.OFFMotorTempFailCirc 1 Comp1 Alarm - Motor Temperature Sesnor FaultRead0=NoAlarm, 1=Alarm
BV901C2.Comp1.OFFMotorTempFailCirc 2 Comp1 Alarm - Motor Temperature Sesnor FaultRead0=NoAlarm, 1=Alarm
BV515Unit.PowerRestoreUnit - Power RestoreRead0=NoAlarm, 1=Alarm
BV516C1.FailPumpdownCircuit 1 Alarm - Pumpdown FailureRead0=NoAlarm, 1=Alarm
BV517C2.FailPumpdownCircuit 2 Alarm - Pumpdown FailureRead0=NoAlarm, 1=Alarm
BV924Unit.ExternalEventUnit Alarm - External EventRead0=NoAlarm, 1=Alarm
BV905C1.OFFNoPresChgAtStartCircuit 1 Alarm - No Pressure change at StartRead0=NoAlarm, 1=Alarm
BV906C2.OFFNoPresChgAtStartCircuit 2 Alarm - No Pressure change at StartRead0=NoAlarm, 1=Alarm
BV926C1OFFPhaseVoltageCircuit 1 Alarm - Pahse VoltageRead0=NoAlarm, 1=Alarm
BV927C2OFFPhaseVoltageCircuit 2 Alarm - Pahse VoltageRead0=NoAlarm, 1=Alarm
BV886C1.Comp1.OFFVfdFaultCirc 1 Compr 1 Alarm - VFD FaultRead0=NoAlarm, 1=Alarm
BV888C2.Comp1.OFFVfdFaultCirc 2 Compr 1 Alarm - VFD FaultRead0=NoAlarm, 1=Alarm
BV942C1.Comp1.OFFVfdTempHiCirc 1 Compr 1 Alarm - VFD High TemperatureRead0=NoAlarm, 1=Alarm
BV944C2.Comp1.OFFVfdTempHiCirc 2 Compr 1 Alarm - VFD High TemperatureRead0=NoAlarm, 1=Alarm
BV948C1.Comp1.OFFVfdCommFailCirc 1 Compr 1 Alarm - VFD Communication FailureRead0=NoAlarm, 1=Alarm
BV950C2.Comp1.OFFVfdCommFailCirc 2 Compr 1 Alarm - VFD Communication FailureRead0=NoAlarm, 1=Alarm
AI578C1.Comp1.HoldAmpsHiCirc 1 Comp 1 Warning - Inhibition for High Current AbsorptionRead0=NoAlarm, 1=Alarm
AI580C2.Comp1.HoldAmpsHiCirc 2 Comp 1 Warning - Inhibition for High Current AbsorptionRead0=NoAlarm, 1=Alarm
BV921EmergencyStopAlarmUnit Alarm - Emergency Stop SwitchRead0=NoAlarm, 1=Alarm
BV922EvapWTempInvertedUnit Alarm - Evaporator Temperature Sensors InvertedRead0=NoAlarm, 1=Alarm
BV923Unit.OFFExternalAlarmUnit Alarm - External AlarmRead0=NoAlarm, 1=Alarm
BV961C1.Comp1.DischSHeatLowCirc 1 Compr 1 Problem - Low Discharge SuperheatRead0=NoAlarm, 1=Alarm
BV963C2.Comp1.DischSHeatLowCirc 2 Compr 1 Problem - Low Discharge SuperheatRead0=NoAlarm, 1=Alarm
BV918BadCurrentLimitInputUnit Warning - Curennt Limit Input Out Of RangeRead0=NoAlarm, 1=Alarm
BV830C1.OFFVFDCardTempHiCircuit 1 Alarm - VFD Card High TemperatureRead0=NoAlarm, 1=Alarm
BV831C2.OFFVFDCardTempHiCircuit 2 Alarm - VFD Card High TemperatureRead0=NoAlarm, 1=Alarm
BV988LeakAlarmUnit Warning - Gas LeakageRead0=NoAlarm, 1=Alarm
BV980EnergyMtrCommFailController Alarm - Energy Meter Communication FailureRead0=NoAlarm, 1=Alarm
BV904Unit.OFFRestartBoardOfflineController Alarm - Rapid Restart Board OfflineRead0=NoAlarm, 1=Alarm
BVUnit.OFFMarineBoardOfflineController Alarm - Marine Board Offline (guide repeats instance 904)Read0=NoAlarm, 1=Alarm
AV1800C2.Comp1.ActCapacityCirc 2 Compressor 1 - Actual Capacity%Read
MV440C2.Comp1.OffAutoStpCirc 2 Compressor 1 - OffAuto SetpointWrite1=Off, 2=Auto
BV1802C2.Comp1.FullLoadStaCirc 2 Compressor 1 - Full Load StateRead0=Normal, 1=Full Load
AV148C2.Comp1.VfdOutputCirc 2 Compressor 1 - VFD Output%Read
AI166C2.Comp1.OilFeedPressCirc 2 Compressor 1 - Oil Feed PressurekPaRead
MV1811C2.Comp1.OilLevelStaCirc 2 Compressor 1 - Oil Level StateRead1=Off, 2=On
BV441C2.Comp1.StateCirc 2 Compressor 1 - Operating StateRead0=Off, 1=On
AV1840C1.Comp1.ActCapacityCirc 1 Compressor 1 - Actual Capacity%Read
MV430C1.Comp1.OffAutoStpCirc 1 Compressor 1 - OffAuto SetpointWrite1=Off, 2=Auto
BV1842C1.Comp1.FullLoadStaCirc 1 Compressor 1 - Full Load StateRead0=Normal, 1=Full Load
AV1845C1.Comp1.ActSpeedCirc 1 Compressor 1 - VFD OutputHzRead
AI165C1.Comp1.OilFeedPressCirc 1 Compressor 1 - Oil Feed PressurekPaRead
MV1851C1.Comp1.OilLevelStaCirc 1 Compressor 1 - Oil Level StateRead1=Off, 2=On
BV431C1.Comp1.StateCirc 1 Compressor 1 - Operating StateRead0=Off, 1=On
MV1854RefrigTypeUnit - Refrigerant typeRead1=R22, 2=R134a, 3=R407c, 4=R410a, 5=R1234ze, 6=resv3, 7=R513a
AV1855NrCircuitsUnit - Number of CircuitsRead
AV1857UnitTonsUnit - Number of TonskWRead
AV1896C2.EvapSuperheatStpValCircuit 2 - Evaporator Superheat Active SetpointdKRead
AV1897C1.EvapSuperheatStpValCircuit 1 - Evaporator Superheat Active SetpointdKRead
AV1898C2.EvapSuperheatCircuit 2 - Evaporator Superheat TemperaturedKRead
AV1899C1.EvapSuperheatCircuit 1 - Evaporator Superheat TemperaturedKRead
AV990ActEnergyUnit - Active EnergykWhRead
AV991PowerFactorUnit - Power FactorRead
AV208C2.ExpValvePosCircuit 2 - Expansion Valve Position%Read
AV210C2.CondApproachCircuit 2 - Condenser Approach TemperaturedKRead
AV211C2.EvapApproachCircuit 2 - Evaporator Approach TemperaturedKRead
AV168C1.ExpValvePosCircuit 1 - Expansion Valve Position%Read
AV170C1.CondApproachCircuit 1 - Condenser Approach TemperaturedKRead
AV171C1.EvapApproachCircuit 1 - Evaporator Approach TemperaturedKRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EWWD-VZ water-cooled screw chiller (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)

How many BACnet points does the Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe) have?

This list has 209 BACnet objects: 33 analog inputs, 53 analog values, 12 binary inputs, 99 binary values, 12 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe) BACnet points are writable?

14 of the 209 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe) BACnet documentation?

The source is BAS Integration guide - BACnet protocol (EWWD(H)(S)_VZ) (D-EIGOC00101-22_02EN_VZ), revision 2022, published free by Daikin Applied at https://www.daikinapplied.eu/hubfs/portale-documentale/D_EIGOC00101_22_02EN_VZ.pdf.

What are the minimum BACnet points to integrate the Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)?

Start with BV 2 UnitEnableStp (Network enable/disable of the chiller); MV 3 UnitModeSetpointNetwork (Ice / cool / heat / pursuit mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitSetpoint (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 CtrlSource (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 EvapLvgWTemp (Leaving chilled water temperature); BI 10 AlarmOutput (Any active alarm); AV 905 AVFaultAlarmCode (Active fault alarm code).

How do I enable BMS control of the Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)?

CtrlSource (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes UnitEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.

How do I check these points on the real EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: BAS Integration guide - BACnet protocol (EWWD(H)(S)_VZ) · D-EIGOC00101-22_02EN_VZ · rev. 2022. Object names, instances and units are reproduced as published; descriptions are our own.