- Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Air handling unit controller · BACnet points list
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe) BACnet points list
Updated 28 October 2026
The Modular Light (ALB) air handler uses a MicroTech III or MicroTech 4 controller; BACnet IP comes from a POL908 module and BACnet MS/TP from a POL904 module. The short list covers air temperatures, pressures and flows, fan and coil outputs, fan, temperature, humidity and air-quality setpoints, fan and alarm status, operating mode and summer/winter changeover. Object instances are fixed but non-sequential.
This page lists 81 BACnet objects for the Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 81 (18 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1
- Also known as
- Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00
BMS integration notes: Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Write NetworkCtrl to run or stop the unit, set summer/winter with SuWiNetworkChgover after setting SuWiChgSrc to BMS, and adjust the fan, economy, humidity and air-quality setpoints as needed. Read the operating mode and status, supply and controlled temperatures and the general alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 24562 | NetworkCtrl | Network on/off (1 = Off, 2 = On) | Write |
| MV 28594 | SuWiNetworkChgover | Summer/winter command (1 = Winter, 2 = Summer) | Write |
| MV 9493 | SuWiChgSrc | Must be 3 = BMS for the summer/winter command | Write |
| AV 52572 | SplyFanSpvSt1Spv | Supply fan setpoint (units per SplyEngUnit) | Write |
| MV 39130 | AckAlmPls | Acknowledge all alarms (2 = On) | Write |
| MV 6080 | ActOpMode | Operating mode (Off/On/Ventilation/Economy/Standby) | Read |
| MV 32321 | ActOpSta | Why the unit runs or stops (e.g. 11 = BMS) | Read |
| AI 45150 | SupplyTmp | Supply air temperature | Read |
| AV 52988 | ActCtrlVal | Temperature being controlled | Read |
| BO 5714 | AlmOutHigh | General alarm (1 = Alarm) | Read |
Enable & remote start
NetworkCtrl (MV 24562, "Network source", 1 = Off / 2 = On) is the writable on/off object; ActOpSta (MV 32321) reports 11 = BMS when the network is in control. Summer/winter changeover follows the BMS only when SuWiChgSrc (MV 9493) = 3 (BMS); then write SuWiNetworkChgover (MV 28594). The guide gives no further procedure.
Network setup
- BACnet IP comes from a POL908 module and BACnet MS/TP from a POL904 module plugged onto the MicroTech controller.
- BACnet IP defaults: device instance 1, UDP port 47808, DHCP off; set Apply Changes = Yes after editing, which restarts the controller.
- BACnet MS/TP module defaults: MAC address 24, 38400 baud, Max Master 127, Max Info Frames 1; the device instance is derived from the production number and date code. Cycle power after changing the address.
- Object instances are fixed, non-sequential numbers (e.g. SupplyTmp = AI 45150); map by instance, not by position.
- EDE files are regenerated each time the BACnet server starts and can be downloaded by FTP from the POL908; re-export them after any configuration change.
Watch out for
- Objects only appear when the AHU configuration uses them (fans, coils, recovery, humidity, air quality).
- Engineering units of fan setpoints follow SplyEngUnit / ExhEngUnit (%, Pa or m3/h) and humidity units follow HumEngUnit.
- Multistate commands are 1-based (1 = Off, 2 = On); 0 is not a valid state.
- AckAlmPls (MV 39130) acknowledges every alarm in the controller at once.
- Only the economy cooling/heating setpoints (AV 61866/35713) are writable here; the active setpoints (AV 4018/30105/56276) are read-only.
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 45150 | SupplyTmp | Supply air temperature | °C | Read | |
| AI | 33923 | RmUTmp1 | Room unit temperature | °C | Read | |
| AI | 28256 | ReturnAirTmp | Return air temperature | °C | Read | |
| AI | 53218 | OutTmp | Outside air temperature | °C | Read | |
| AI | 29568 | PreHeatTemp | Pre-Heating temperature | °C | Read | |
| AI | 40895 | ExhaustTmp | Exhaust temperature | °C | Read | |
| AI | 20400 | SupplyPrs | Supply air pressure | Pa | Read | |
| AI | 39576 | ReturnPrs | Return air pressure | Pa | Read | |
| AI | 9497 | SupplyFlow | Supply air flow | m3/h | Read | |
| AI | 38593 | ReturnFlow | Return air flow | m3/h | Read | |
| AI | 37799 | RoomHum | Room humidity relative | %rH | Read | |
| AI | 3737 | AirQuality | Air quality (CO2) | ppm | Read | |
| AO | 59037 | SplyFanVarPos | Supply fan output | % | Read | |
| AO | 40119 | ExhFanVarPos | Return fan output | % | Read | |
| AO | 37442 | ElectricalHtgPos | Electrical heating / Post heating output | % | Read | |
| AO | 5922 | HrecPos | Recovery device output | % | Read | |
| AO | 30925 | CoolingPos | Cooling coil output | % | Read | |
| AO | 26209 | HeatingPos | Heating coil output | % | Read | |
| AO | 62755 | FanTempCompPos | Fan temperature compensation output | % | Read | |
| AVmin | 52572 | SplyFanSpvSt1Spv | Supply fan setpoint | m3/h or Pa | Write | |
| AV | 57915 | SplyFanSpvEcSpv | Supply fan economy setpoint | m3/h or Pa | Write | |
| AV | 25092 | SplyFanSpvMaxForce | Supply fan max force | m3/h or Pa | Write | |
| AV | 45030 | ExhFanSpvSt1Spv | Return fan setpoint | m3/h or Pa | Write | |
| AV | 6118 | ExhFanSpvEcSpv | Return fan economy setpoint | m3/h or Pa | Write | |
| AV | 2525 | ExhFanSpvMaxForce | Return fan max force | m3/h or Pa | Write | |
| AV | 56628 | SplyFanActVal | Supply fan actual value | m3/h or Pa | Read | |
| AV | 59694 | ExhFanActVal | Return fan actual value | m3/h or Pa | Read | |
| AV | 46589 | SplyFanActSpv | Supply fan actual setpoint | m3/h or Pa | Read | |
| AV | 33255 | ExhFanActSpv | Return fan actual setpoint | m3/h or Pa | Read | |
| AV | 22649 | AirQSpv | Air quality setpoint | ppm | Write | |
| AV | 61866 | TmpSpvEcSpvClg | Economy cooling setpoint | °C | Write | |
| AV | 35713 | TmpSpvEcSpvHtg | Economy heating setpoint | °C | Write | |
| AV | 4018 | ActMainSpvHtg | Actual heating setpoint (depending on actual control mode) | °C | Read | |
| AV | 30105 | ActMainSpvClg | Actual cooling setpoint (depending on actual control mode) | °C | Read | |
| AV | 56276 | ActTempSetpt | Active temperature setpoint | °C | Read | |
| AVmin | 52988 | ActCtrlVal | Actual controlled temperature | °C | Read | |
| AV | 11342 | HumSpvRelSpvDehum | Dehumidification setpoint relative | %rH | Write | |
| AV | 10627 | HumSpvRelSpvHum | Humidification setpoint relative | %rH | Write | |
| AV | 40393 | ActMainSpvHum | Actual humidification setpoint relative | %rH | Read | |
| AV | 47998 | ActMainSpvDeh | Actual dehumidification setpoint relative | %rH | Read | |
| AV | 61369 | RmEnth | Room enthalpy | kJ/kg | Read | |
| AV | 17315 | RmHumAbs | Room humidity absolute | g/kg | Read | |
| AV | 38385 | ActCtrlValHum | Actual controlled humidity | %rH | Read | |
| AV | 24338 | SuWiSwtchCheckOutTmpDampd | Outside air temp damped | °C | Read | |
| AV | 1206 | RoomUnitsOccTm | Room unit presence time | h | Write | |
| AV | 8926 | RoomUnitOffset | Room unit temperature setpoint offset | °C | Write | |
| AV | 10236 | AirQCmpPrVal | Air quality compensation values | % | Read | |
| BI | 28757 | SplyFanAlm | Supply fan alarm | Read | 0=OK, 1=Alarm | |
| BI | 55865 | ExhFanAlm | Exhaust fan alarm | Read | 0=OK, 1=Alarm | |
| BI | 28514 | FireAlm | Fire alarm | Read | 0=OK, 1=Alarm | |
| BI | 13699 | FilterAlm | Filter alarm | Read | 0=OK, 1=Alarm | |
| BI | 11643 | ExtCtrl1 | Unit Enable Switch | Read | 0=Standby, 1=On | |
| BI | 9864 | EmergencyStop | Emergency stop | Read | 0=Alarm, 1=OK | |
| BO | 6170 | DamperSplyOnOff | Fresh air damper command | Read | 0=Off, 1=On | |
| BO | 18044 | HumidityCtrlCmdOnOff | Humidifier command | Read | 0=Off, 1=On | |
| BO | 10276 | CoolingPmpCmdOnOff | Cooling pump command | Read | 0=Off, 1=On | |
| BO | 10264 | HeatingPmpCmdOnOff | Heating pump command | Read | 0=Off, 1=On | |
| BOmin | 5714 | AlmOutHigh | AHU General alarm output | Read | 0=Normal, 1=Alarm | |
| SCH | 31059 | ScheduleSt | Time scheduler actual state | Read | 1=Off, 2=On, 3=Ventilation, 4=Economy | |
| MO | 21928 | SplyFanCmdSt | Supply fan command | Read | 1=Off, 2=On | |
| MO | 14719 | ExhFanCmdSt | Exhaust fan command | Read | 1=Off, 2=On | |
| MVmin | 6080 | ActOpMode | Actual operating mode | Read | 1=Off, 2=On, 3=Ventilation, 4=Economy, 5=Standby | |
| MVmin | 32321 | ActOpSta | Present unit status | Read | 1=N/A, 2=Fire, 3=Emergency, 4=Fault, 5=Alarm, 6=Fire damper test, 7=Manual, 8=Panel switch, 9=Local switch, 10=N/A, 11=BMS, 12=Scheduler, 13=Occupancy, 14=N/A, 15=N/A, 16=N/A, 17=Ready | |
| MVmin | 39130 | AckAlmPls | Alarm acknowledge (acknowledges all alarms) | Write | 1=Off, 2=On | |
| MV | 24616 | SuWiSwtchCheckState | Summer Winter mode | Read | 1=Winter, 2=Summer | |
| MV | 46769 | AlmCl0 | Danger alarm (A) | Read | 1=Normal, 2=On | |
| MV | 42640 | AlmCl1 | Critical alarm (A) | Read | 1=Normal, 2=On | |
| MV | 38643 | AlmCl2 | Low alarm (B) | Read | 1=Normal, 2=On | |
| MV | 34514 | AlmCl3 | Warning alarm (C) | Read | 1=Normal, 2=On | |
| MVmin | 24562 | NetworkCtrl | Network source | Write | 1=Off, 2=On | |
| MVmin | 28594 | SuWiNetworkChgover | Summer/Winter network changeover command | Write | 1=Winter, 2=Summer | |
| MV | 43819 | ExhEngUnit | Return air engineering Unit | Read | 1=%, 2=Pa, 3=m3/h | |
| MV | 54155 | SplyEngUnit | Supply air engineering Unit | Read | 1=%, 2=Pa, 3=m3/h | |
| MV | 13725 | HumEngUnit | Humidity engineering unit | Read | 1=%rH, 2=g/kg | |
| MV | 25214 | Pre-Htg Electrical | Pre-heating electrical command | Read | 1=Off, 2=Step 1, 3=Step 2 | |
| MV | 41370 | Electrical Heating State | Electrical heating command | Read | 1=Off, 2=Step 1, 3=Step 2 | |
| MVmin | 9493 | SuWiChgSrc | Set source for summer/winter changeover | Write | 1=Auto, 2=HMI, 3=BMS (BACnet) | |
| MV | 12316 | TimeSchedSt | Indicates time scheduler active mode | Read | 1=On, 2=Off, 3=Ventilation, 4=Economy | |
| MV | 28279 | ActFanStep | Indicates the active fan step | Read | 1=Off, 2=Stage 1, 3=Stage 2, 4=Stage 3 | |
| MV | 28561 | ActCtrlMode | Indicates mode for the regulation control | Read | 1=Room, 2=Exhaust, 3=Supply | |
| MV | 33544 | OpModeTspCopyUnitPls | Copy Monday time schedule to all weekdays | Write | 1=Off, 2=On |
No points match these filters.
Integration notes
- Which objects exist depends on the AHU configuration.
- The cover names the control software EvoLVE; the page footers say Airstream.
- AV 30105 ActMainSpvClg is printed twice; it is listed once.
- ScheduleSt (31059) is printed in its own Schedule table with Off/On/Ventilation/Economy states; it is listed as SCH.
- The guide also covers connecting a Daikin iTM (intelligent Touch Manager) over BACnet IP.
- The ADK digital AHU (DSTREAM) guide uses the same instance numbers for the shared objects and adds many more.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
How many BACnet points does the Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe) have?
This list has 81 BACnet objects: 12 analog inputs, 7 analog outputs, 28 analog values, 6 binary inputs, 5 binary outputs, 2 multi-state outputs, 1 schedule, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe) BACnet points are writable?
18 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe) BACnet documentation?
The source is BAS Integration Guide - BACnet protocol (Modular Light (ALB)) (D-EIGOC00106-26_00EN), published free by Daikin Applied at https://www.daikinapplied.eu/hubfs/portale-documentale/D_EIGOC00106_26_00EN_ALB.pdf.
What are the minimum BACnet points to integrate the Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)?
Start with MV 24562 NetworkCtrl (Network on/off (1 = Off, 2 = On)); MV 28594 SuWiNetworkChgover (Summer/winter command (1 = Winter, 2 = Summer)); MV 9493 SuWiChgSrc (Must be 3 = BMS for the summer/winter command); AV 52572 SplyFanSpvSt1Spv (Supply fan setpoint (units per SplyEngUnit)); MV 39130 AckAlmPls (Acknowledge all alarms (2 = On)); MV 6080 ActOpMode (Operating mode (Off/On/Ventilation/Economy/Standby)); MV 32321 ActOpSta (Why the unit runs or stops (e.g. 11 = BMS)); AI 45150 SupplyTmp (Supply air temperature); AV 52988 ActCtrlVal (Temperature being controlled); BO 5714 AlmOutHigh (General alarm (1 = Alarm)).
How do I enable BMS control of the Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)?
NetworkCtrl (MV 24562, "Network source", 1 = Off / 2 = On) is the writable on/off object; ActOpSta (MV 32321) reports 11 = BMS when the network is in control. Summer/winter changeover follows the BMS only when SuWiChgSrc (MV 9493) = 3 (BMS); then write SuWiNetworkChgover (MV 28594). The guide gives no further procedure.
How do I check these points on the real Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122
Source: BAS Integration Guide - BACnet protocol (Modular Light (ALB)) · D-EIGOC00106-26_00EN. Object names, instances and units are reproduced as published; descriptions are our own.