Magnetic bearing centrifugal chiller controller · BACnet points list
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller) BACnet points list
Updated 6 November 2026
The 2010 Magnitude chiller unit controller on single-compressor WME chillers exposes 55 BACnet objects through a BACnet IP, BACnet Ethernet or BACnet MS/TP communication module (LonWorks is the other option). The list covers network enable, mode, cool/heat/ice setpoints and capacity limit, water temperatures and flows, compressor current, voltage, power and refrigerant data, pump status and run hours, and three alarm-number values.
This page lists 55 BACnet objects for the Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- Magnitude WME single-compressor chiller (2010 McQuay unit controller)
- Equipment
- Magnetic bearing centrifugal chiller controller
- Equipment type
- Chillers
- BACnet objects
- 55 (8 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 30003
- Also known as
- ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
At the chiller touch screen set the BAS protocol and then Control Source to BAS. The BMS enables the chiller with ChillerEnableStp, writes mode, cool setpoint and capacity limit, and reads status, water temperatures, the alarm output and the fault alarm number.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | ChillerEnableStp | Network enable/disable of the chiller | Write |
| MV 3 | ChillerOperationMode | Ice / cool / heat mode command | Write |
| AV 4 | NetworkCoolTempSetpoint | Leaving water cool setpoint from the BMS | Write |
| AV 3 | NetworkCapacityLimitPct | Capacity limit from the BMS | Write |
| BV 8 | ClearAlarm | Clear alarms from the network | Write |
| BI 3 | ChillerLocalNetwork | Shows whether network control is active | Read |
| MV 1 | UnitStatus | Chiller run state | Read |
| AI 2 | LvgEvapWaterTempUnit | Leaving chilled water temperature | Read |
| BI 10 | AlarmDigitalOutput | Any active alarm | Read |
| AV 901 | AVFaultAlarm | Highest active fault alarm number | Read |
Enable & remote start
On the OITS panel set Control Source to USER, choose the BAS protocol on the SET/BAS screen, check the chiller runs, then set Control Source to BAS. The BMS then writes ChillerEnableStp (BV 2) and the network mode and setpoints.
Network setup
- BACnet IP defaults: IP 172.15.5.82, mask 255.255.255.0, UDP port 47808, device instance 30003.
- BACnet MS/TP defaults: MAC address 1, 38400 baud, device instance 30003, Max Master 127.
- Device instance (0-4194302) and object name are set on the OITS panel; if the stored instance is invalid the module falls back to 3000 + address.
- MAC address and baud rate can only be set at the OITS panel and must be set before communication starts.
Watch out for
- Alarm values show only the highest-numbered active alarm of each class; 0 means none.
- BV 8 ClearAlarm returns to 0 once the alarms clear. Low evaporator pressure, high condenser pressure, freeze protection and high motor temperature alarms can only be cleared at the chiller.
- MV 4 Units switches the BACnet values between English and metric; set it once.
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 5 | ActiveLvgWaterTarget | Active Setpoint | °F | Read | |
| AV | 2 | ChillerCapacity | Actual Capacity | % | Read | |
| AV | 1 | ActiveCapacityLimit | Active Capacity Limit (Output) | % | Read | |
| AVmin | 3 | NetworkCapacityLimitPct | Capacity Limit Setpoint - Network (default 100%) | % | Write | |
| BI | 7 | ChillerEnable | Chiller Enable Output | Read | 0=Disable, 1=Enable | |
| BVmin | 2 | ChillerEnableStp | Chiller Enable Setpoint | Write | 0=Disable, 1=Enable | |
| BI | 6 | ChillerLimited | Chiller Capacity Limited | Read | 0=Not Limited, 1=Limited | |
| BImin | 3 | ChillerLocalNetwork | Chiller Local/Network | Read | 0=Network, 1=Local | |
| MV | 2 | ActiveMode | Chiller Mode Output | Read | 1=Ice, 2=Cool, 3=Heat | |
| MVmin | 3 | ChillerOperationMode | Chiller Mode Setpoint - Network | Write | 1=Ice, 2=Cool, 3=Heat | |
| BI | 4 | UnitOFF | Chiller On Off | Read | 0=Chiller Off, 1=Chiller On | |
| MVmin | 1 | UnitStatus | Chiller Status BACnet | Read | 1=Off, 2=Start, 3=Run, 4=Preshutdown, 5=Service | |
| AI | 9 | C1Comp1Current | Compressor Average Current | A | Read | |
| AI | 81 | C1Comp1DischRefPressure | Compressor Discharge Refrigerant Pressure | psi | Read | |
| AI | 63 | C1Comp1DischargeTemp | Compressor Discharge Refrigerant Temperature | °F | Read | |
| AV | 26 | C1Comp1DischSatRefTemp | Compressor Discharge Saturated Refrigerant Temperature | °F | Read | |
| AV | 8 | C1Comp1MotorCurrentPercent | Compressor Percent RLA | % RLA | Read | |
| AI | 45 | C1Comp1Kilowatts | Compressor Power | kW | Read | |
| AV | 74 | C1Comp1Hours | Compressor Run Hours | Read | ||
| AV | 92 | C1Comp1Starts | Compressor Starts | Read | ||
| AI | 105 | C1Comp1SuctionTemp | Compressor Suction Refrigerant Temperature | °F | Read | |
| AI | 27 | C1Comp1Voltage | Compressor Average Voltage | V | Read | |
| AI | 3 | EntCondWaterTemp | Condenser Entering Water Temperature | °F | Read | |
| BI | 1 | CondWaterFlowStatus | Condenser Flow Switch Status | Read | 0=No Flow, 1=Flow | |
| AI | 4 | LvgCondWaterTemp | Condenser Leaving Water Temperature | °F | Read | |
| AV | 110 | CondPump1RunHours | Condenser Pump #1 Run Hours | Read | ||
| AV | 111 | CondPump2RunHours | Condenser Pump #2 Run Hours | Read | ||
| AI | 99 | Cond1RefPressure | Condenser Refrigerant Pressure | psi | Read | |
| AV | 44 | Cond1SatRefTemp | Condenser Saturated Refrigerant Temperature | °F | Read | |
| AI | 123 | C1Comp1SuctionPressure | Compressor Suction Refrigerant Pressure | psi | Read | |
| AV | 50 | C1Comp1SuctSatTemp | Compressor Suction Saturated Refrigerant Temperature | °F | Read | |
| AI | 147 | CondWaterFlowRate | Condenser Water Flow Rate | gpm | Read | |
| BI | 11 | CondPump1State | Condenser Pump #1 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 12 | CondPump2State | Condenser Pump #2 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| AVmin | 4 | NetworkCoolTempSetpoint | Cool Setpoint - Network (default 44°F) | °F | Write | |
| AI | 1 | EntEvapWaterTemp | Evaporator Entering Water Temperature | °F | Read | |
| BI | 2 | EvapWaterFlowStatus | Evaporator Flow Switch Status | Read | 0=No Flow, 1=Flow | |
| AImin | 2 | LvgEvapWaterTempUnit | Evaporator Leaving Water Temperature | °F | Read | |
| AV | 112 | EvapPump1OperHours | Evaporator Pump #1 Run Hours | Read | ||
| AV | 113 | EvapPump2OperHours | Evaporator Pump #2 Run Hours | Read | ||
| AI | 148 | EvapWaterFlowRate | Evaporator Water Flow Rate | gpm | Read | |
| BI | 8 | EvapPump1State | Evaporator Pump #1 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 9 | EvapPump2State | Evaporator Pump #2 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| AI | 149 | HeatRecEntWaterTemp | Heat Recovery Entering Water Temperature | °F | Read | |
| AI | 150 | HeatRecLvgWaterTemp | Heat Recovery Leaving Water Temperature | °F | Read | |
| AV | 6 | NetworkHeatTempSetpoint | Heat Setpoint - Network (default 134.96°F) | °F | Write | |
| AV | 7 | NetworkIceTempSetpoint | Ice Setpoint - Network (default 25°F) | °F | Write | |
| AI | 5 | OutdoorAirTemp | Outdoor Air Temperature | °F | Read | |
| BI | 5 | UnitOFF | Run Enabled | Read | 0=OFF, 1=Run Allowed | |
| MV | 4 | Units | Units | Write | 1=English(IP), 2=Metric(SI) | |
| BImin | 10 | AlarmDigitalOutput | Alarm Digital Output | Read | 0=No Alarm, 1=Alarm | |
| AVmin | 901 | AVFaultAlarm | Highest active fault alarm number (0 = none) | Read | ||
| AV | 900 | AVProblemAlarm | Highest active problem alarm number (0 = none) | Read | ||
| AV | 902 | AVWarningAlarm | Highest active warning alarm number (0 = none) | Read | ||
| BVmin | 8 | ClearAlarm | Clear Alarm Network | Write | 0=Normal (Default), 1=Clear Alarm |
No points match these filters.
Object ID lookup: Daikin Applied Magnitude WME (2010) point IDs by name
AV5ActiveLvgWaterTargetAV2ChillerCapacityAV1ActiveCapacityLimitAV3NetworkCapacityLimitPctBI7ChillerEnableBV2ChillerEnableStpBI6ChillerLimitedBI3ChillerLocalNetworkMV2ActiveModeMV3ChillerOperationModeBI4UnitOFFMV1UnitStatusAI9C1Comp1CurrentAI81C1Comp1DischRefPressureAI63C1Comp1DischargeTempAV26C1Comp1DischSatRefTempAV8C1Comp1MotorCurrentPercentAI45C1Comp1KilowattsAV74C1Comp1HoursAV92C1Comp1StartsAI105C1Comp1SuctionTempAI27C1Comp1VoltageAI3EntCondWaterTempBI1CondWaterFlowStatusAI4LvgCondWaterTempAV110CondPump1RunHoursAV111CondPump2RunHoursAI99Cond1RefPressureAV44Cond1SatRefTempAI123C1Comp1SuctionPressureAV50C1Comp1SuctSatTempAI147CondWaterFlowRateBI11CondPump1StateBI12CondPump2StateAV4NetworkCoolTempSetpointAI1EntEvapWaterTempBI2EvapWaterFlowStatusAI2LvgEvapWaterTempUnitAV112EvapPump1OperHoursAV113EvapPump2OperHoursAI148EvapWaterFlowRateBI8EvapPump1StateBI9EvapPump2StateAI149HeatRecEntWaterTempAI150HeatRecLvgWaterTempAV6NetworkHeatTempSetpointAV7NetworkIceTempSetpointAI5OutdoorAirTempBI5UnitOFFMV4UnitsBI10AlarmDigitalOutputAV901AVFaultAlarmAV900AVProblemAlarmAV902AVWarningAlarmBV8ClearAlarm
Integration notes
- This is the older single-compressor WME document (April 2010). The C-vintage WME list (ED 19111-1) shares 49 of these 55 instances (4 with different names); this one adds heat and ice network setpoints, heat recovery temperatures, outdoor air temperature and a problem-alarm value.
- Object names come from the guide's detailed point pages; the summary table lists only property names.
- BI 4 (Chiller On Off) and BI 5 (Run Enabled) are both printed with the object name UnitOFF.
- The summary table lists the compressor discharge saturated temperature as AV 26; its detail page shows it as an Analog Input.
- The alarm section of the guide also mentions a BO 5 alarm output and a BV 42 ClearAlarm; the point table and detail pages use BI 10 AlarmDigitalOutput and BV 8 ClearAlarm, which are listed here.
- BACnet Ethernet (ISO 8802-3) is also offered as a module option.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Magnitude WME single-compressor chiller (2010 McQuay unit controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
How many BACnet points does the Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller) have?
This list has 55 BACnet objects: 17 analog inputs, 20 analog values, 12 binary inputs, 2 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller) BACnet points are writable?
8 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller) BACnet documentation?
The source is Magnitude Chiller Unit Controller Protocol Information, BACnet Networks (MS/TP, IP, Ethernet), LonWorks Networks (ED 15117), revision 2010-04, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15117.pdf.
What are the minimum BACnet points to integrate the Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)?
Start with BV 2 ChillerEnableStp (Network enable/disable of the chiller); MV 3 ChillerOperationMode (Ice / cool / heat mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitPct (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 ChillerLocalNetwork (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); BI 10 AlarmDigitalOutput (Any active alarm); AV 901 AVFaultAlarm (Highest active fault alarm number).
How do I enable BMS control of the Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)?
On the OITS panel set Control Source to USER, choose the BAS protocol on the SET/BAS screen, check the chiller runs, then set Control Source to BAS. The BMS then writes ChillerEnableStp (BV 2) and the network mode and setpoints.
How do I check these points on the real Magnitude WME single-compressor chiller (2010 McQuay unit controller)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: Magnitude Chiller Unit Controller Protocol Information, BACnet Networks (MS/TP, IP, Ethernet), LonWorks Networks · ED 15117 · rev. 2010-04. Object names, instances and units are reproduced as published; descriptions are our own.