Air handling unit controller · BACnet points list

Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe) BACnet points list

Updated 7 November 2026

Short answer

The Compact air handler (Fujin Comfort software) takes a POL908 module for BACnet IP or a POL904 module for BACnet MS/TP. The list covers temperatures, filter and fan pressures, humidity, CO2 and IEQ sensors, damper, fan, coil and humidifier signals, comfort and economy setpoints for temperature, flow, pressure, humidity and air quality, filter, fan-communication, ERQ and R-32 leak alarms, outputs, a unit status multistate, network on/off and cool/heat commands and alarm classes. Object instances are fixed but non-sequential.

This page lists 121 BACnet objects for the Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
121 (34 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN
Source document
BAS Integration Guide - BACnet protocol (Compact, Fujin Comfort) · D-EIGOC00101-25_00EN
Download CSV 121 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)

Integration in brief

Set Ctrl Source to Network at the unit, then write NetworkCtrl for on/off/ventilation/economy and SuWiNetworkChgover for cool/heat, plus the comfort setpoints. Read UnitStatusMS, the controlled and supply temperatures and the global alarm output.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 24562NetworkCtrlNetwork on/off/ventilation/economy/schedulerWrite
MV 28594SuWiNetworkChgoverCool/heat command from the BMSWrite
AV 8970TmpSpvCoSpvClgMain cooling setpointWrite
AV 22817TmpSpvCoSpvHtgMain heating setpointWrite
AV 50820SplyFanFlowSetpSupply fan flow setpoint, m3/hWrite
MV 58347UnitStatusMSUnit status (why the unit runs or stops)Read
AV 52988ActCtrlValTemperature being controlledWrite
AI 19757TempSplySupply air temperatureRead
BO 48570GlblAlrmSwtcGlobal alarm outputRead

Enable & remote start

Control over the network needs the unit control source set to Network at the keypad (Main Menu > Ctrl Source = Network; default Local). NetworkCtrl (MV 24562) then commands Off/On/Ventilation/Economy/Scheduler and SuWiNetworkChgover (MV 28594) sets cool or heat.

Network setup

Watch out for

Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

121 of 121 shown
Type
Multi-state
Access
Show
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe) BACnet Points List
DescriptionStates
AI10863TempOutdOutdoor temperature°CRead
AI13351TempOutdOptOutdoor temperature optional°CRead
AImin19757TempSplySupply temperature°CRead
AI16754TempSplyOptSupply temperature optional°CRead
AI12945TempRtrnReturn temperature°CRead
AI17444TempExhtExhaust temperature°CRead
AI62672TempRoomRoom temperature°CRead
AI15651PresOutdFltrOutdoor filter pressurePaRead
AI8734PresOutdPrFlOptOutdoor pre-filter optional pressurePaRead
AI23316PresRtrnFltrReturn filter pressurePaRead
AI4028PresRtrnFltrOptReturn filter optional pressurePaRead
AI61819PresSplyFltrOptSupply filter optional pressurePaRead
AI62083PresRecvRecovery pressurePaRead
AI21736PresSplyFanSupply fan pressurePaRead
AI64433PresRtrnFanReturn fan pressurePaRead
AI29985PresSplyFanOptSupply fan pressure optionalPaRead
AI20651PresRtrnFanOptReturn fan pressure optionalPaRead
AI37231HumdOutdOutdoor humidity%rHRead
AI63021HumdSplySupply humidity%rHRead
AI35217HumdRtrnReturn humidity%rHRead
AI63516CO2RtrnReturn CO2ppmRead
AI21570IEQTempRtrnIEQ return temperature°CRead
AI61250IEQHumdRtrnIEQ return humidity%rHRead
AI59257IEQCO2IEQ CO2ppmRead
AI54715IEQPM25IEQ PM25µg/m3Read
AI14348IEQPM10IEQ PM10µg/m3Read
AI7794IEQVOCIEQ VOCppbRead
AO3813BypaDmprSgnlBypass damper signal%Read
AO3072MixgDmprSgnlMixing damper signal%Read
AO60281SplyFan1SgnlSupply fan 1 signal%Read
AO24143PostCoilISgnlPost coil I signal%Read
AO8872RtrnFan1SgnlReturn fan 1 signal%Read
AO51554PrehCoilSgnlOptPre heating coil signal optional%Read
AO3600OuExDmprSgnlOutdoor/Exhaust damper signal%Read
AO25396CombCoilSgnlCombined coil signal%Read
AO40866PostCoilIISgnlPost coil II signal%Read
AO5070HumdSgnlHumidification signal%Read
AVmin8970TmpSpvCoSpvClgMain cool setpoint°CWrite
AVmin22817TmpSpvCoSpvHtgMain heat setpoint°CWrite
AV9220MainCoolSetpEconMain cool setpoint economy°CWrite
AV31739MainHeatSetpEconMain heat setpoint economy°CWrite
AV35815SplyTSetpMinSupply temperature setpoint minimum°CWrite
AV28857SplyTSetpMaxSupply temperature setpoint maximum°CWrite
AVmin50820SplyFanFlowSetpSupply fan flow setpointm3/hWrite
AV62777SplyFanFlowSetpEconSupply fan flow setpoint economym3/hWrite
AV14403RtrnFanFlowSetpReturn fan flow setpointm3/hWrite
AV27465RtrnFanFlowSetpEconReturn fan flow setpoint economym3/hWrite
AV8237SplyFanFlowMinSupply fan flow setpoint minimumm3/hWrite
AV56179SplyFanFlowMaxSupply fan flow setpoint maximumm3/hWrite
AV22461RtrnFanFlowMinReturn fan flow setpoint minimumm3/hWrite
AV44259RtrnFanFlowMaxReturn fan flow setpoint Maximumm3/hWrite
AV28940SplyFanPresSetpSupply fan Pressure setpointPaWrite
AV51006SplyFanPresSetpEconSupply fan Pressure setpoint economyPaWrite
AV36811RtrnFanPresSetpReturn fan Pressure setpointPaWrite
AV22862RtrnFanPresSetpEconReturn fan Pressure setpoint economyPaWrite
AV61085MainHumdSetpMain humidification setpoint%rHWrite
AV39494MainHumdSetpEconMain humidification setpoint economy%rHWrite
AV40417MainDhumSetpMain dehumidification setpoint%rHWrite
AV61062MainDhumSetpEconMain dehumidification setpoint economy%rHWrite
AV42868CO2SetpAir quality setpointppmWrite
AV2656RecvTempDfrsEvalRecovery defrost temperature°CWrite
AV7056SplyNtrlZoneSupply neutral zone°CWrite
AV8180RecvTimeDfrsRecovery time defrostminWrite
AV19322FanDfrsFactFan defrost factor%Write
AV25173RecvDlayDfrsEvalRecovery delay defrostsWrite
AV39517RecvDfrsSplyThrsRecovery defrost supply threshold°CWrite
AV20464UnitStatusUnit statusRead
AV4779WinterPreheatingTimeWinter pre heating timeminWrite
AV61112WinterPreheatThrhWinter pre heating threshold°CWrite
AVmin52988ActCtrlValActual temp°CWrite
BI18594FrstSwtcFrost switchRead0=Passive, 1=Active
BI40060FireAlrmFire alarmRead0=Passive, 1=Active
BI56526UnitSwtcUnit switchRead0=Off, 1=On
BI42108CmEcSwtcComfort/Economy switchRead0=Comfort, 1=Economy
BI54908CoHeSwtcCool/heat switchRead0=Cool, 1=Heat
BI62777CombPumpAlrmCombined pump alarmRead0=Passive, 1=Active
BI794HumdAlrmHumidifier alarmRead0=Passive, 1=Active
BI48824PostCoilIIAlrmPost coil II alarmRead0=Passive, 1=Active
BI30669PostCoilIAlrmPost coil I alarmRead0=Passive, 1=Active
BI15735RecvFrstRecovery frostRead0=OK, 1=Fault
BI2056PrehPumpAlrmPre-heat pump alarmRead0=Passive, 1=Active
BI47896PrehElectAlrmPre-heat electric alarmRead0=Passive, 1=Active
BI42202ERQ1AlrmERQ 1 alarmRead0=Passive, 1=Active
BI2302R32LeakageR32 leakage alarmRead0=Passive, 1=Active
BI19983ERQ1DfrsSwtcERQ 1 defrostRead0=Passive, 1=Active
BI7198SplyFltrOptFaultSupply optional filter faultRead0=Passive, 1=Active
BI29473SplyFltrOptWarnSupply optional filter warningRead0=Passive, 1=Active
BI56935RtrnFltrFaultReturn filter faultRead0=Passive, 1=Active
BI12152RtrnFltrWarnReturn filter warningRead0=Passive, 1=Active
BI54735RtrnFltrOptFaultReturn filter optional faultRead0=Passive, 1=Active
BI36326RtrnFltrOptWarnReturn filter optional warningRead0=Passive, 1=Active
BI58631OutdFltrFaultOutdoor filter faultRead0=Passive, 1=Active
BI18767OutdFltrWarnOutdoor filter warningRead0=Passive, 1=Active
BI33280OutdPrFlOptFaultOutdoor pre filter optional faultRead0=Passive, 1=Active
BI41028OutdPrFlOptWarnOutdoor pre filter optional warningRead0=Passive, 1=Active
BI40552SplyFanCommAlrmSupply fan communication alarmRead0=Passive, 1=Active
BI24751RtrnFanCommAlrmReturn fan communication alarmRead0=Passive, 1=Active
BO5718UnitRunSwtcUnit run switchRead0=Passive, 1=Active
BO6135CombPumpCmndCombined pump commandRead0=Passive, 1=Active
BO54908CoHeSwtcCool/Heat switchRead0=Passive, 1=Active
BOmin48570GlblAlrmSwtcGlobal alarm switchRead0=Passive, 1=Active
BO59991HumdCmndHumidifier commandRead0=Passive, 1=Active
BO61396ShutDmprCmndShutoff damper commandRead0=Passive, 1=Active
BO19863ERQ1CmndERQ commandRead0=Passive, 1=Active
BO24765ERQ1CoHeSwtcERQ 1 Cool/Heat switchRead0=Cool, 1=Heat
BO55004LowFlowAlrmLow flow alarmRead0=Passive, 1=Active
BO51260PrehElecCmndPre-heat electric commandRead0=Passive, 1=Active
BO60102PrehPumpCmndPre-heat pump commandRead0=Passive, 1=Active
BO29159PostCoilICmndPost coil I commandRead0=Passive, 1=Active
BO57656PostCoilIICmndPost coil II commandRead0=Passive, 1=Active
MVmin58347UnitStatusMSUnit status multistateRead0=Off, 1=Off by fire alarm, 2=Off by alarm, 3=Off by recovery frost, 7=Post ventilation, 9=Off by DI switch, 12=Pre heating, 20=Off by BMS, 21=On, 22=Ventilation, 23=Economy, 24=Test, 25=Off by scheduler, 26=On by scheduler, 27=Ventilation, 28=Economy
MV6080ActOpModeActual Operating modeRead1=Stop, 2=Start
MV19336DOShutDmprDO Shutoff dampersRead1=Off, 2=On
MV35320AOShutDmprAO Shutoff dampersRead1=Off, 2=On
MVmin24562NetworkCtrlUnit Status BMSWrite1=Off, 2=On, 3=Ventilation, 4=Economy, 5=Scheduler
MV24616SuWiSwtchCheckStateCool/Heat stateRead1=Cool, 2=Heat
MVmin28594SuWiNetworkChgoverCool/Heat BMSWrite1=Cool, 2=Heat
MV46769AlmCl0Alarm class 0Read1=Normal, 2=Alarm
MV42640AlmCl1Alarm class 1Read1=Normal, 2=Alarm
MV38643AlmCl2Alarm class 2Read1=Normal, 2=Alarm
MV34514AlmCl3Alarm class 3Read1=Normal, 2=Alarm
Object ID lookup: Daikin Applied Compact air handler, Fujin Comfort software point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Compact air handler, Fujin Comfort software (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)

How many BACnet points does the Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe) have?

This list has 121 BACnet objects: 27 analog inputs, 10 analog outputs, 33 analog values, 27 binary inputs, 13 binary outputs, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe) BACnet points are writable?

34 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe) BACnet documentation?

The source is BAS Integration Guide - BACnet protocol (Compact, Fujin Comfort) (D-EIGOC00101-25_00EN), published free by Daikin Applied at https://easyspec.daikin.fr/Easyspec/2-BASE_WEB/4-CTA/Documentations/A3_COMP_R/Manuel%20Adressage%20Com/COM_A3_COMP_R.zip.

What are the minimum BACnet points to integrate the Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)?

Start with MV 24562 NetworkCtrl (Network on/off/ventilation/economy/scheduler); MV 28594 SuWiNetworkChgover (Cool/heat command from the BMS); AV 8970 TmpSpvCoSpvClg (Main cooling setpoint); AV 22817 TmpSpvCoSpvHtg (Main heating setpoint); AV 50820 SplyFanFlowSetp (Supply fan flow setpoint, m3/h); MV 58347 UnitStatusMS (Unit status (why the unit runs or stops)); AV 52988 ActCtrlVal (Temperature being controlled); AI 19757 TempSply (Supply air temperature); BO 48570 GlblAlrmSwtc (Global alarm output).

How do I enable BMS control of the Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)?

Control over the network needs the unit control source set to Network at the keypad (Main Menu > Ctrl Source = Network; default Local). NetworkCtrl (MV 24562) then commands Off/On/Ventilation/Economy/Scheduler and SuWiNetworkChgover (MV 28594) sets cool or heat.

How do I check these points on the real Compact air handler, Fujin Comfort software (Daikin Applied Europe)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: BAS Integration Guide - BACnet protocol (Compact, Fujin Comfort) · D-EIGOC00101-25_00EN. Object names, instances and units are reproduced as published; descriptions are our own.