- EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Water-cooled chiller controller · BACnet points list
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe) BACnet points list
Updated 7 November 2026
The EWWD-DZ and EWWH-DZ chillers run Daikin's VORTEX software. BACnet IP or BACnet MS/TP comes from a POL908/POL904 module. The list covers chiller enable, local/remote, mode, network cool/heat setpoints and capacity and current limits, water temperatures, per-compressor capacity, speed, IGV position, current, power and temperatures for up to three compressors, pump status, and individual alarm objects plus alarm index/code AVs.
This page lists 164 BACnet objects for the Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
- Equipment
- Water-cooled chiller controller
- Equipment type
- Chillers
- BACnet objects
- 164 (8 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1
- Also known as
- EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Set ChillerLocalRemote to Remote, enable the chiller with ChillerEnableStp and write the mode, cool setpoint and capacity limit. Monitor unit status, leaving water temperature, the general alarm and the fault code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | ChillerEnableStp | Network enable/disable of the chiller | Write |
| BI 3 | ChillerLocalRemote | Local/remote selection (1 = Remote) | Write |
| MV 3 | ChillerOperationMode | Ice / cool / heat / pursuit mode command | Write |
| AV 4 | NetworkCoolTempSetpoint | Leaving water cool setpoint from the BMS | Write |
| AV 3 | NetworkCapacityLimitPct | Capacity limit from the BMS, % | Write |
| BV 8 | ClearAlarm | Clear alarms from the network | Write |
| MV 1 | UnitStatus | Chiller run state | Read |
| AI 2 | LvgEvapWaterTempUnit | Leaving chilled water temperature | Read |
| BI 10 | AlarmDigitalOutput | Unit general alarm | Read |
| AV 905 | AVFaultAlarmCode | Active fault alarm code | Read |
Enable & remote start
ChillerLocalRemote (BI 3, 0 = Local / 1 = Remote) is marked R/W in this guide; with Remote selected the BMS writes ChillerEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.
Network setup
- BACnet IP comes from the POL908 module and BACnet MS/TP from the POL904 module.
- BACnet IP module defaults: device instance 1, UDP port 47808, DHCP off; set Apply Changes = Yes after editing, which restarts the controller.
- BACnet MS/TP module defaults: MAC address 24, 38400 baud, Max Master 127, Max Info Frames 1; the device instance is derived from the production number and date code.
Watch out for
- Alarms come as Warning, Problem and Fault index/code AVs (900-905); the fault code table (Annex 1) is in the guide.
- AV 175 CurrentLimSetpNtw is a current (A) limit; the main BMS capacity limit is AV 3 (%).
- Objects for compressor 3 only apply to three-compressor units.
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | ActiveCapacityLimit | Active Capacity Limit | % | Read | |
| AV | 990 | ActiveEnergy | Active Energy | kW | Read | |
| AV | 5 | ActiveLvgWaterTarget | Active Leaving Water Target | °C | Read | |
| MV | 2 | ActiveMode | Active Mode | Read | 1=Cool, 2=Ice, 3=Heat, 4=Pursuit, 5=Cool/Heat Recovery | |
| BImin | 10 | AlarmDigitalOutput | Unit general alarm | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AVmin | 905 | AVFaultAlarmCode | Active fault code | Read | ||
| AV | 901 | AVFaultAlarmIndex | Active fault index | Read | ||
| AV | 904 | AVProblemAlarmCode | Active problem code | Read | ||
| AV | 900 | AVProblemAlarmIndex | Active problem index | Read | ||
| AV | 903 | AVWarningAlarmCode | Active warning code | Read | ||
| AV | 902 | AVWarningAlarmIndex | Active warning index | Read | ||
| BV | 918 | BadCurrentLimitInput | Bad current limit input | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 513 | BadDemandLimitInput | Bad demand limit input | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 512 | BadSPointOverrideInput | Bad setpoint override input | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 882 | C1ControlBoardOffline | Circuit #1 - Board offline | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 883 | C2ControlBoardOffline | Circuit #2 - Board offline | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 2 | ChillerCapacity | Chiller capacity | % | Read | |
| AI | 993 | ChillerCurrent | Chiller current | A | Read | |
| BI | 7 | ChillerEnableOutput | Chiller enable state | Read | 0=Disable, 1=Enable, 2=NULL | |
| BVmin | 2 | ChillerEnableStp | Chiller enable setpoint | Write | 0=Disable, 1=Enable, 2=NULL | |
| AV | 994 | ChillerKilowatts | Chiller Kilowatts | kW | Read | |
| BI | 6 | ChillerLimited | Chiller limited | Read | 0=Not limited, 1=limited, 2=NULL | |
| BImin | 3 | ChillerLocalRemote | Chiller Local/Remote | Write | 0=Local, 1=Remote, 2=NULL | |
| MVmin | 3 | ChillerOperationMode | Chiller operating mode setpoint | Write | 1=Ice, 2=Cool, 3=Heat, 4=Pursuit | |
| AV | 992 | ChillerVoltage | Chiller voltage | V | Read | |
| BVmin | 8 | ClearAlarm | Clear alarm | Write | 0=No, 1=Yes, 2=NULL | |
| AV | 131 | Comp1ActCapacity | Comp#1 - Actual capacity | % | Read | |
| AV | 300 | Comp1ActualSpeed | Comp#1 - Actual speed | rpm | Read | |
| BV | 991 | Comp1AlarmActive | Comp#1 - Alarm active | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 8 | Comp1Current | Comp#1 - Current | A | Read | |
| AI | 62 | Comp1DischargeTemp | Comp#1 - Discharge temperature | °C | Read | |
| AI | 191 | Comp1EconomizerPress | Comp#1 - Economizer pressure | kPa | Read | |
| AV | 290 | Comp1IGVPos | Comp#1 - IGV position | % | Read | |
| BV | 961 | Comp1LowDSuperHeat | Comp#1 - Low discharge superheat | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 92 | Comp1OffBmcFault | Comp#1 - Off Bmc fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 100 | Comp1OffCheckVlvFault | Comp#1 - Off Check Valve Fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 606 | Comp1OffCurrentHi | Comp#1 -Off Current High | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 312 | Comp1OffDischPSenf | Comp#1 -Off Discharge pressure sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 694 | Comp1OffDischTempHi | Comp#1 -Off Disch temperature high | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 637 | Comp1OFFMotorTempHi | Comp#1 -Off Motor temperature high | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 304 | Comp1OffSensorFault | Comp#1 -Off sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 316 | Comp1OffSuctPSenf | Comp#1 -Off suction pressure sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 857 | Comp1OFFSuctTempSen | Comp#1 -Off suction temperature sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 948 | Comp1OffVfdCommFail | Comp#1 -Off Vfd communication fail | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 886 | Comp1OffVfdFault | Comp#1 -Off Vfd fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 655 | Comp1OverVoltage | Comp#1 -Over Voltage | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 45 | Comp1Power | Comp#1 -Power | kW | Read | |
| BV | 529 | Comp1RestartDelayPwrLRun | Comp#1 -Restart delay power low while run | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 74 | Comp1RunHours | Comp#1 -Run Hours | h | Read | |
| AV | 92 | Comp1Starts | Comp#1 -Starts | Read | ||
| AI | 105 | Comp1SuctionTemp | Comp#1 -Suction temperature | °C | Read | |
| BV | 661 | Comp1UnderVoltage | Comp#1 -Under Voltage | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 27 | Comp1Voltage | Comp#1 -Voltage | V | Read | |
| AV | 132 | Comp2ActCapacity | Comp#2 -Actual capacity | % | Read | |
| AV | 301 | Comp2ActualSpeed | Comp#2 -Actual Speed | rpm | Read | |
| AV | Comp2AlarmActive | Comp#2 -Alarm Active | Read | 0=No Alarm, 1=Alarm | ||
| AV | 9 | Comp2Current | Comp#2 -Current | A | Read | |
| AI | 63 | Comp2DischargeTemp | Comp#2 -Discharge temperature | °C | Read | |
| AI | 192 | Comp2EconomizerPress | Comp#2 -Economizer pressure | kPa | Read | |
| AV | 291 | Comp2IGVPos | Comp#2 -IGV position | % | Read | |
| BI | 962 | Comp2LowDSuperHeat | Comp#2 -Low discharge superheat | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 93 | Comp2OffBmcFault | Comp#2 -Off Bmc fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 101 | Comp2OffCheckVlvFault | Comp#2 -Off CheckValve fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 323 | Comp2OffCmpFault | Comp#2 -Off Compressor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 607 | Comp2OffCurrentHi | Comp#2 -Off Current high | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 313 | Comp2OffDischPSenf | Comp#2 -Off Discharge pressure sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 695 | Comp2OffDischTempHi | Comp#2 -Off Discharge temperature high | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 638 | Comp2OFFMotorTempHi | Comp#2 -OFF Motor temperature high | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 305 | Comp2OffSensorFault | Comp#2 -Off sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 317 | Comp2OffSuctPSenf | Comp#2 -Off suction pressure sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 858 | Comp2OFFSuctTempSen | Comp#2 -Off suction temperature sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 949 | Comp2OffVfdCommFail | Comp#2 -Off Vfd communication fail | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 887 | Comp2OffVfdFault | Comp#2 -Off Vfd fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 656 | Comp2OverVoltage | Comp#2 -Over Voltage | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 46 | Comp2Power | Comp#2 -Power | kW | Read | |
| AV | 75 | Comp2RunHours | Comp#2 -Run Hours | h | Read | |
| AV | 93 | Comp2Starts | Comp#2 -Starts | Read | ||
| AI | 106 | Comp2SuctionTemp | Comp#2 -Suction temperature | °C | Read | |
| BV | 662 | Comp2UnderVoltage | Comp#2 -Under voltage | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 28 | Comp2Voltage | Comp#2 -Voltage | V | Read | |
| AV | 133 | Comp3ActCapacity | Comp#3 -Actual capacity | % | Read | |
| AV | 302 | Comp3ActualSpeed | Comp#3 -Actual Speed | rpm | Read | |
| BV | 993 | Comp3AlarmActive | Comp#3 -Alarm Active | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 10 | Comp3Current | Comp#3 -Current | A | Read | |
| AI | 64 | Comp3DischargeTemp | Comp#3 -Discharge temperature | °C | Read | |
| AI | 193 | Comp3EconomizerPress | Comp#3 -Economizer pressure | kPa | Read | |
| AV | 292 | Comp3IGVPos | Comp#3 -IGV position | % | Read | |
| BV | 965 | Comp3LowDSuperHeat | Comp#3 -Low discharge superheat | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 94 | Comp3OffBmcFault | Comp#3 -Off Bmc fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 102 | Comp3OffCheckVlvFault | Comp#3 -Off CheckValve fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 324 | Comp3OffCmpFault | Comp#3 -Off Compressor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 609 | Comp3OffCurrentHi | Comp#3 -Off Current high | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 314 | Comp3OffDischPSenf | Comp#3 -Off Discharge pressure sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 698 | Comp3OffDischTempHi | Comp#3 -Off Discharge temperature high | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 641 | Comp3OFFMotorTempHi | Comp#3 -OFF Motor temperature high | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 306 | Comp3OffSensorFault | Comp#3 -Off sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 318 | Comp3OffSuctPSenf | Comp#3 -Off suction pressure sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 861 | Comp3OFFSuctTempSen | Comp#3 -Off suction temperature sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 952 | Comp3OffVfdCommFail | Comp#3 -Off Vfd communication fail | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 890 | Comp3OffVfdFault | Comp#3 -Off Vfd fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 659 | Comp3OverVoltage | Comp#3 -Over Voltage | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 47 | Comp3Power | Comp#3 -Power | kW | Read | |
| AV | 76 | Comp3RunHours | Comp#3 -Run Hours | h | Read | |
| AV | 94 | Comp3Starts | Comp#3 -Starts | Read | ||
| AI | 107 | Comp3SuctionTemp | Comp#3 -Suction temperature | °C | Read | |
| BV | 665 | Comp3UnderVoltage | Comp#3 -Under voltage | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 29 | Comp3Voltage | Comp#3 -Voltage | V | Read | |
| BV | 674 | CondenserFlowLoss | Unit - Off condenser flow loss | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 989 | CondenserFreeze | Unit - Off condenser freeze | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AI | 3 | CondEntWTemp | Condenser entering water temperature | °C | Read | |
| BV | 500 | CondEWTSensorFault | Condenser entering water temperature sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| MV | CondFlowSwStatus | Condenser flow switch status | Read | 1=Off, 2=On | ||
| AI | 4 | CondLeavWTemp | Condenser leaving water temperature | °C | Read | |
| BV | 503 | CondLWTSensorFault | Condenser leaving water temperature sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 548 | CondPump1Fault | Condenser pump #1 fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 110 | CondPump1RunHrs | Condenser pump #1 run hours | h | Read | |
| BI | 11 | CondPump1Status | Condenser pump #1 status | Read | 0=PumpOffRequest, 1=PumpOnRequest, 2=NULL | |
| BV | 549 | CondPump2Fault | Condenser pump #2 fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 111 | CondPump2RunHrs | Condenser pump #2 run hours | h | Read | |
| BI | 12 | CondPump2Status | Condenser pump #2 status | Read | 0=PumpOffRequest, 1=PumpOnRequest, 2=NULL | |
| AI | 99 | CondRefPressure | Condensig refrigerant pressure | kPa | Read | |
| AI | 44 | CondSatRefTemp | Condensing saturated refrigerant temperature | °C | Read | |
| AV | 178 | CPMState | CPM State | Read | ||
| AV | 175 | CurrentLimSetpNtw | Current Limit setpoint network | A | Write | |
| BV | 921 | EmergencyStopAlarm | Emergency Stop Alarm | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 980 | EnergyMtrCommFail | Energy Meter communication failt | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AI | 1 | EntEvapWaterTemp | Evaporator entering water temperature | °C | Read | |
| AI | 161 | EvapApproachT | Evaporator Approach temperature | °C | Read | |
| BV | 917 | EvapEntWTempSensorFail | Evaporator entering water temperature sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 167 | EvapExvPos | Evaporator EEXV position | Read | ||
| BV | 575 | EvapPump1Fault | Evaporator Pump#1 fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 112 | EvapPump1RunHours | Evaporator Pump#1 run hours | h | Read | |
| BI | 8 | EvapPump1Status | Evaporator Pump#1 status | Read | 0=PumpOffRequest, 1=PumpOnRequest, 2=NULL | |
| BV | 576 | EvapPump2Fault | Evaporator Pump#2 fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 113 | EvapPump2RunHours | Evaporator Pump#2 run hours | h | Read | |
| BI | 9 | EvapPump2Status | Evaporator Pump#2 status | Read | 0=PumpOffRequest, 1=PumpOnRequest, 2=NULL | |
| BI | 2 | EvapWaterFlowStatus | Evaporator water flow status | Read | 0=No flow, 1=Flow | |
| BV | 922 | EvapWTempInverted | Evaporator water temperature inverted | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 923 | ExternalAlarm | External Alarm | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 924 | ExternalEvent | External Event | Read | 0=No Event, 1=Event, 2=NULL | |
| AV | 6 | HeatSetpNetwork | Heat setpoint network | °C | Write | |
| BV | 988 | LeakAlarm | Refrigerant leakage alarm | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AI | 218 | LiqLineRefTemp | Liquid refrigerant line temperature | °C | Read | |
| AImin | 2 | LvgEvapWaterTempUnit | Evaporator leaving water temperature | °C | Read | |
| AV | 500 | McQ_Chiller | McQ_Chiller | Read | ||
| AVmin | 3 | NetworkCapacityLimitPct | Capacity limit percentage network | % | Write | |
| AVmin | 4 | NetworkCoolTempSetpoint | Cool setpoint network | °C | Write | |
| AV | 171 | NumberOfCircuits | Number of circuits | Read | ||
| AV | 173 | NumberOfTons | Number of tons | Read | ||
| BV | 919 | OptionCtrlrCommFail | Option controller communication fail | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| AV | 991 | PowerFactor | Power Factor | Read | ||
| MV | 6 | RefrigerantType | Refrigerant type | Read | 1=R22, 2=R134a, 3=R407c, 4=R410a, 5=R1234ze, 6=R513a | |
| BI | 5 | RunEnabled | Run Enabled | Read | 0=Disable, 1=Enable, 2=NULL | |
| AI | 160 | UnitCondApproachT | Condenser Approach temperature | °C | Read | |
| AI | 141 | UnitEvapRefPressure | Evaporating refrigerant pressure | kPa | Read | |
| AI | 68 | UnitEvapSatRefTemp | Evaporating refrigerant saturated temperature | °C | Read | |
| BV | 592 | UnitExpAlarm | Unit I/O expansion alarm | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 668 | UnitOFFCondPressSen | Unit - Off Condensing pressure sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 702 | UnitOFFEvapLvgWTempLo | Unit - Off evaporator leaving water temperature low | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 748 | UnitOFFEvapLvgWTempSen | Unit - Off evaporator leaving water temperature sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 711 | UnitOFFEvapPressSen | Unit Off evaporating pressure sensor fault | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BV | 760 | UnitOFFHighPress | Unit - Off High pressure | Read | 0=No Alarm, 1=Alarm, 2=NULL | |
| BI | 4 | UnitOnOff | Unit On/Off status | Read | 0=Off, 1=On, 2=NULL | |
| MVmin | 1 | UnitStatus | Unit Status | Read | 1=Off, 2=Start, 3=Run, 4=Pre Shutdown, 5=Service |
No points match these filters.
Object ID lookup: Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software point IDs by name
AV1ActiveCapacityLimitAV990ActiveEnergyAV5ActiveLvgWaterTargetMV2ActiveModeBI10AlarmDigitalOutputAV905AVFaultAlarmCodeAV901AVFaultAlarmIndexAV904AVProblemAlarmCodeAV900AVProblemAlarmIndexAV903AVWarningAlarmCodeAV902AVWarningAlarmIndexBV918BadCurrentLimitInputBV513BadDemandLimitInputBV512BadSPointOverrideInputBV882C1ControlBoardOfflineBV883C2ControlBoardOfflineAV2ChillerCapacityAI993ChillerCurrentBI7ChillerEnableOutputBV2ChillerEnableStpAV994ChillerKilowattsBI6ChillerLimitedBI3ChillerLocalRemoteMV3ChillerOperationModeAV992ChillerVoltageBV8ClearAlarmAV131Comp1ActCapacityAV300Comp1ActualSpeedBV991Comp1AlarmActiveAV8Comp1CurrentAI62Comp1DischargeTempAI191Comp1EconomizerPressAV290Comp1IGVPosBV961Comp1LowDSuperHeatBV92Comp1OffBmcFaultBV100Comp1OffCheckVlvFaultBV606Comp1OffCurrentHiBV312Comp1OffDischPSenfBV694Comp1OffDischTempHiBV637Comp1OFFMotorTempHiBV304Comp1OffSensorFaultBV316Comp1OffSuctPSenfBV857Comp1OFFSuctTempSenBV948Comp1OffVfdCommFailBV886Comp1OffVfdFaultBV655Comp1OverVoltageAV45Comp1PowerBV529Comp1RestartDelayPwrLRunAV74Comp1RunHoursAV92Comp1StartsAI105Comp1SuctionTempBV661Comp1UnderVoltageAV27Comp1VoltageAV132Comp2ActCapacityAV301Comp2ActualSpeedAV9Comp2CurrentAI63Comp2DischargeTempAI192Comp2EconomizerPressAV291Comp2IGVPosBI962Comp2LowDSuperHeatBI93Comp2OffBmcFaultBI101Comp2OffCheckVlvFaultBI323Comp2OffCmpFaultBV607Comp2OffCurrentHiBV313Comp2OffDischPSenfBI695Comp2OffDischTempHiBI638Comp2OFFMotorTempHiBI305Comp2OffSensorFaultBI317Comp2OffSuctPSenfBI858Comp2OFFSuctTempSenBV949Comp2OffVfdCommFailBV887Comp2OffVfdFaultBV656Comp2OverVoltageAV46Comp2PowerAV75Comp2RunHoursAV93Comp2StartsAI106Comp2SuctionTempBV662Comp2UnderVoltageAV28Comp2VoltageAV133Comp3ActCapacityAV302Comp3ActualSpeedBV993Comp3AlarmActiveAV10Comp3CurrentAI64Comp3DischargeTempAI193Comp3EconomizerPressAV292Comp3IGVPosBV965Comp3LowDSuperHeatBV94Comp3OffBmcFaultBV102Comp3OffCheckVlvFaultBV324Comp3OffCmpFaultBV609Comp3OffCurrentHiBV314Comp3OffDischPSenfBI698Comp3OffDischTempHiBV641Comp3OFFMotorTempHiBV306Comp3OffSensorFaultBV318Comp3OffSuctPSenfBV861Comp3OFFSuctTempSenBV952Comp3OffVfdCommFailBV890Comp3OffVfdFaultBV659Comp3OverVoltageAV47Comp3PowerAV76Comp3RunHoursAV94Comp3StartsAI107Comp3SuctionTempBV665Comp3UnderVoltageAV29Comp3VoltageBV674CondenserFlowLossBV989CondenserFreezeAI3CondEntWTempBV500CondEWTSensorFaultAI4CondLeavWTempBV503CondLWTSensorFaultBV548CondPump1FaultAV110CondPump1RunHrsBI11CondPump1StatusBV549CondPump2FaultAV111CondPump2RunHrsBI12CondPump2StatusAI99CondRefPressureAI44CondSatRefTempAV178CPMStateAV175CurrentLimSetpNtwBV921EmergencyStopAlarmBV980EnergyMtrCommFailAI1EntEvapWaterTempAI161EvapApproachTBV917EvapEntWTempSensorFailAV167EvapExvPosBV575EvapPump1FaultAV112EvapPump1RunHoursBI8EvapPump1StatusBV576EvapPump2FaultAV113EvapPump2RunHoursBI9EvapPump2StatusBI2EvapWaterFlowStatusBV922EvapWTempInvertedBV923ExternalAlarmBV924ExternalEventAV6HeatSetpNetworkBV988LeakAlarmAI218LiqLineRefTempAI2LvgEvapWaterTempUnitAV500McQ_ChillerAV3NetworkCapacityLimitPctAV4NetworkCoolTempSetpointAV171NumberOfCircuitsAV173NumberOfTonsBV919OptionCtrlrCommFailAV991PowerFactorMV6RefrigerantTypeBI5RunEnabledAI160UnitCondApproachTAI141UnitEvapRefPressureAI68UnitEvapSatRefTempBV592UnitExpAlarmBV668UnitOFFCondPressSenBV702UnitOFFEvapLvgWTempLoBV748UnitOFFEvapLvgWTempSenBV711UnitOFFEvapPressSenBV760UnitOFFHighPressBI4UnitOnOffMV1UnitStatus
Integration notes
- AV 992 is printed for both ChillerVoltage and Comp2AlarmActive; MV 1 is printed for both UnitStatus and CondFlowSwStatus; the object without a confirmed instance is listed without one.
- Four rows print an invalid object type and are left out: Comp1OffCmpFault (type "CS", instance 322), UnitOFFEvapWaterFlow (701), UnitOFFPhaseVoltage (820) and UnitPwrRestore (515), which print type "0".
- Several compressor 2 and 3 alarm objects are printed as BI where the matching compressor 1 object is a BV; types are kept as printed.
- Binary alarm objects list a third state "2 = NULL" in the guide.
- Daikin France (Easyspec) publishes this guide as a PDF inside a zip together with the Modbus guide.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
How many BACnet points does the Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe) have?
This list has 164 BACnet objects: 21 analog inputs, 51 analog values, 21 binary inputs, 66 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe) BACnet points are writable?
8 of the 164 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe) BACnet documentation?
The source is BAS Integration guide - BACnet protocol (EWWD-DZ / EWWH-DZ) (D-EIGOC00103-21EN-DZ), published free by Daikin Applied at https://easyspec.daikin.fr/Easyspec/2-BASE_WEB/3-Eau%20Glacee%20%26%20VC/Documentations/P_EWWH-DZ/Manuel%20adressage%20com/COM_P_EWWH-DZ.zip.
What are the minimum BACnet points to integrate the Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)?
Start with BV 2 ChillerEnableStp (Network enable/disable of the chiller); BI 3 ChillerLocalRemote (Local/remote selection (1 = Remote)); MV 3 ChillerOperationMode (Ice / cool / heat / pursuit mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitPct (Capacity limit from the BMS, %); BV 8 ClearAlarm (Clear alarms from the network); MV 1 UnitStatus (Chiller run state); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); BI 10 AlarmDigitalOutput (Unit general alarm); AV 905 AVFaultAlarmCode (Active fault alarm code).
How do I enable BMS control of the Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)?
ChillerLocalRemote (BI 3, 0 = Local / 1 = Remote) is marked R/W in this guide; with Remote selected the BMS writes ChillerEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.
How do I check these points on the real EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: BAS Integration guide - BACnet protocol (EWWD-DZ / EWWH-DZ) · D-EIGOC00103-21EN-DZ. Object names, instances and units are reproduced as published; descriptions are our own.