- Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Chiller controller · BACnet points list
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller) BACnet points list
Updated 4 November 2026
The QUAD version of the Magnitude WME-C has two refrigerant circuits with two compressors each, and its MicroTech unit controller adds circuit 2 compressor objects, per-compressor Off/Auto commands and alarm module objects to the WME BACnet table. It talks BACnet IP, BACnet MS/TP or Modbus through the BAS communication module. Control works the same as the other WME chillers: network enable, mode, cool setpoint and capacity limit, plus water temperatures, flows, refrigerant data, run hours and alarm indices.
This page lists 99 BACnet objects for the Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- Magnitude WME-C QUAD Chiller (MicroTech WME controller)
- Equipment
- Chiller controller
- Equipment type
- Chillers
- BACnet objects
- 99 (10 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Chiller application 1.0.0 (QUAD) or later
- Default device instance
- 9050
- Also known as
- WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
At the chiller HMI set Control Source to BAS (for the network enable) and Remote Enable to Enable (for setpoint, mode and capacity limit). The BMS then writes ChillerEnableStp, the cool setpoint and capacity limit, and reads status, water temperatures and the alarm index objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | ChillerEnableStp | Network enable/disable of the chiller | Write |
| MV 3 | ChillerOperationMode | Mode command; only 2 = Cool applies on WME | Write |
| AV 4 | NetworkCoolTempSetpoint | Leaving water cool setpoint from the BMS | Write |
| AV 3 | NetworkCapacityLimitPct | Capacity limit from the BMS | Write |
| BV 8 | ClearAlarm | Clear alarms from the network | Write |
| BI 3 | ChillerLocalRemote | Shows whether network control is active | Read |
| MV 1 | UnitStatus | Chiller run state | Read |
| AI 2 | LvgEvapWaterTempUnit | Leaving chilled water temperature | Read |
| AV 2 | ChillerCapacity | Actual capacity in percent | Read |
| AV 901 | AVFaultAlarm | Active fault alarm index | Read |
Enable & remote start
Control Source must be set to BAS at the unit HMI for the controller to use Network Enable (BV 2). For the cool setpoint, mode and capacity limit, Remote Enable must also be set to Enable at the HMI. Writing Enable to BV 2 only allows a start if other conditions are met. Individual compressors can be taken out of service from the network with the Compressor Off/Auto objects (MV 100, 101, 106, 107).
Network setup
- Default device instance 9050; default device object name Daikin_MicroTech_ plus the instance. Cycle power on the BAS module after changing the instance.
- BACnet IP defaults: IP 192.168.1.10, mask 255.255.255.0, gateway 192.168.1.1, UDP port 47808.
- BACnet MS/TP defaults: MAC 1, 38400 baud, Max Master 127, Max Info Frames 10.
- Network parameters are set at the HMI; see IM 1283 for the communication module.
Watch out for
- Only Cool mode applies, although the mode objects list Ice, Heat and Heat Recovery.
- Units (MV 4) changes the units sent to BACnet between English and Metric.
- Compressor Off/Auto objects return to Auto after a controller power cycle.
- WME-C QUAD has no alarm code objects; read the alarm index and alarm module objects.
- Some compressor-shutdown and freeze alarms cannot be cleared from the network.
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 9 | C1Comp1Current | Compressor Current - Circuit 1 Compressor 1 | A | Read | |
| AI | 10 | C1Comp2Current | Compressor Current - Circuit 1 Compressor 2 | A | Read | |
| AI | 12 | C2Comp1Current | Compressor Current - Circuit 2 Compressor 1 | A | Read | |
| AI | 13 | C2Comp2Current | Compressor Current - Circuit 2 Compressor 2 | A | Read | |
| AI | 63 | C1Comp1DischargeTemp | Compressor Discharge Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AI | 64 | C1Comp2DischargeTemp | Compressor Discharge Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AI | 66 | C2Comp1DischargeTemp | Compressor Discharge Refrigerant Temperature - Circuit 2 Compressor 1 | °F | Read | |
| AI | 67 | C2Comp2DischargeTemp | Compressor Discharge Refrigerant Temperature - Circuit 2 Compressor 2 | °F | Read | |
| AI | 81 | C1Comp1DischRefPressure | Compressor Discharge Refrigerant Pressure - Circuit 1 Compressor 1 | psi | Read | |
| AI | 82 | C1Comp2DischRefPressure | Compressor Discharge Refrigerant Pressure - Circuit 1 Compressor 2 | psi | Read | |
| AI | 84 | C2Comp1DischargeRefPressure | Compressor Discharge Refrigerant Pressure - Circuit 2 Compressor 1 | psi | Read | |
| AI | 85 | C2Comp2DischargeRefPressure | Compressor Discharge Refrigerant Pressure - Circuit 2 Compressor 2 | psi | Read | |
| AI | 45 | C1Comp1Kilowatts | Compressor Power - Circuit 1 Compressor 1 | kW | Read | |
| AI | 46 | C1Comp2Kilowatts | Compressor Power - Circuit 1 Compressor 2 | kW | Read | |
| AI | 48 | C2Comp1Kilowatts | Compressor Power - Circuit 2 Compressor 1 | kW | Read | |
| AI | 49 | C2Comp2Kilowatts | Compressor Power - Circuit 2 Compressor 2 | kW | Read | |
| AI | 105 | C1Comp1SuctionTemp | Compressor Suction Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AI | 106 | C1Comp2SuctionTemp | Compressor Suction Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AI | 108 | C2Comp1SuctionTemp | Compressor Suction Refrigerant Temperature - Circuit 2 Compressor 1 | °F | Read | |
| AI | 109 | C2Comp2SuctionTemp | Compressor Suction Refrigerant Temperature - Circuit 2 Compressor 2 | °F | Read | |
| AI | 123 | C1Comp1SuctionPressure | Compressor Suction Refrigerant Pressure - Circuit 1 Compressor 1 | psi | Read | |
| AI | 124 | C1Comp2SuctionPressure | Compressor Suction Refrigerant Pressure - Circuit 1 Compressor 2 | psi | Read | |
| AI | 126 | C2Comp1SuctionPressure | Compressor Suction Refrigerant Pressure - Circuit 2 Compressor 1 | psi | Read | |
| AI | 127 | C2Comp2SuctionPressure | Compressor Suction Refrigerant Pressure - Circuit 2 Compressor 2 | psi | Read | |
| AI | 27 | C1Comp1Voltage | Compressor Voltage - Circuit 1 Compressor 1 | V | Read | |
| AI | 28 | C1Comp2Voltage | Compressor Voltage - Circuit 1 Compressor 2 | V | Read | |
| AI | 30 | C2Comp1Voltage | Compressor Voltage - Circuit 2 Compressor 1 | V | Read | |
| AI | 31 | C2Comp2Voltage | Compressor Voltage - Circuit 2 Compressor 2 | V | Read | |
| AI | 3 | EntCondWaterTemp | Condenser Entering Fluid Temperature | °F | Read | |
| AI | 147 | CondWaterFlowRate | Condenser Fluid Flow Rate | GPM | Read | |
| AI | 4 | LvgCondWaterTemp | Condenser Leaving Fluid Temperature | °F | Read | |
| AI | 99 | Cond1RefPressure | Condenser Refrigerant Pressure - Circuit 1 | psi | Read | |
| AI | 1 | EntEvapWaterTemp | Evaporator Entering Fluid Temperature | °F | Read | |
| AI | 148 | EvapWaterFlowRate | Evaporator Fluid Flow Rate | GPM | Read | |
| AImin | 2 | LvgEvapWaterTempUnit | Evaporator Leaving Fluid Temperature | °F | Read | |
| AI | 141 | C1EvapRefPressure | Evaporator Refrigerant Pressure - Circuit 1 | psi | Read | |
| AI | 218 | C1LiqLineRefTemp | Liquid Line Refrigerant Temperature - Circuit 1 | °F | Read | |
| AI | 219 | C2LiqLineRefTemp | Liquid Line Refrigerant Temperature - Circuit 2 | °F | Read | |
| AV | 1 | ActiveCapacityLimit | Active Capacity Limit Output | % | Read | |
| AV | 5 | ActiveLvgWaterTarget | Active Setpoint | °F | Read | |
| AVmin | 2 | ChillerCapacity | Actual Capacity | % | Read | |
| AVmin | 901 | AVFaultAlarm | Alarm Index - Fault | Read | ||
| AV | 902 | AVWarningAlarm | Alarm Index - Warning | Read | ||
| AV | 910 | AVFaultModID | Alarm Module ID - Fault | Read | ||
| AV | 913 | AVWarningModID | Alarm Module ID - Warning | Read | ||
| AV | 911 | AVFaultModPayload | Alarm Module Payload - Fault | Read | ||
| AV | 914 | AVWarningModPayload | Alarm Module Payload - Warning | Read | ||
| AV | 909 | AVFaultModType | Alarm Module Type - Fault | Read | ||
| AV | 912 | AVWarningModType | Alarm Module Type - Warning | Read | ||
| AVmin | 3 | NetworkCapacityLimitPct | Capacity Limit Setpoint - Network | % | Write | |
| AV | 26 | C1Comp1DischSatRefTemp | Compressor Discharge Saturated Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AV | 27 | C1Comp2DischSatRefTemp | Compressor Discharge Saturated Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AV | 29 | C2Comp1DischSatRefTemp | Compressor Discharge Saturated Refrigerant Temperature - Circuit 2 Compressor 1 | °F | Read | |
| AV | 30 | C2Comp2DischSatRefTemp | Compressor Discharge Saturated Refrigerant Temperature - Circuit 2 Compressor 2 | °F | Read | |
| AV | 8 | C1Comp1MotorCurrentPercent | Compressor Percent RLA - Circuit 1 Compressor 1 | % | Read | |
| AV | 9 | C1Comp2MotorCurrentPercent | Compressor Percent RLA - Circuit 1 Compressor 2 | % | Read | |
| AV | 11 | C2Comp1MotorCurrentPercent | Compressor Percent RLA - Circuit 2 Compressor 1 | % | Read | |
| AV | 12 | C2Comp2MotorCurrentPercent | Compressor Percent RLA - Circuit 2 Compressor 2 | % | Read | |
| AV | 74 | C1Comp1Hours | Compressor Run Hours - Circuit 1 Compressor 1 | h | Read | |
| AV | 75 | C1Comp2Hours | Compressor Run Hours - Circuit 1 Compressor 2 | h | Read | |
| AV | 50 | C1Comp1SuctSatTemp | Compressor Suction Saturated Refrigerant Temperature - Circuit 1 Compressor 1 | °F | Read | |
| AV | 51 | C1Comp2SuctSatTemp | Compressor Suction Saturated Refrigerant Temperature - Circuit 1 Compressor 2 | °F | Read | |
| AV | 53 | C2Comp1SuctSatTemp | Compressor Suction Saturated Refrigerant Temperature - Circuit 2 Compressor 1 | °F | Read | |
| AV | 54 | C2Comp2SuctSatTemp | Compressor Suction Saturated Refrigerant Temperature - Circuit 2 Compressor 2 | °F | Read | |
| AV | 92 | C1Comp1Starts | Compressor Starts - Circuit 1 Compressor 1 | Read | ||
| AV | 93 | C1Comp2Starts | Compressor Starts - Circuit 1 Compressor 2 | Read | ||
| AV | 110 | CondPump1RunHours | Condenser Pump Run Hours - Condenser Pump 1 | h | Read | |
| AV | 111 | CondPump2RunHours | Condenser Pump Run Hours - Condenser Pump 2 | h | Read | |
| AV | 44 | Cond1SatRefTemp | Condenser Saturated Refrigerant Temperature - Circuit 1 | °F | Read | |
| AVmin | 4 | NetworkCoolTempSetpoint | Cool Setpoint - Network | °F | Write | |
| AV | 112 | EvapPump1OperHours | Evaporator Pump Run Hours - Evaporator Pump 1 | h | Read | |
| AV | 113 | EvapPump2OperHours | Evaporator Pump Run Hours - Evaporator Pump 2 | h | Read | |
| AV | 68 | C1EvapSatRefTemp | Evaporator Saturated Refrigerant Temperature - Circuit 1 | °F | Read | |
| BVmin | 2 | ChillerEnableStp | Chiller Enable Setpoint | Write | 0=Disable (Inactive), 1=Enable | |
| BVmin | 8 | ClearAlarm | Clear Alarm - Network | Write | 0=Normal, 1=Clear Alarm | |
| BI | 10 | AlarmDigitalOutput | Alarm Digital Output | Read | 0=No Alarm, 1=Alarm | |
| BI | 6 | ChillerLimited | Chiller Capacity Limited | Read | 0=Not Limited, 1=Limited | |
| BI | 7 | ChillerEnableOutput | Chiller Enable Output | Read | 0=Disable, 1=Enable | |
| BImin | 3 | ChillerLocalRemote | Chiller Local/Network | Read | 0=Network, 1=Local | |
| BI | 4 | UnitOnOff | Chiller On/Off | Read | 0=Chiller Off, 1=Chiller On | |
| BI | 163 | C1Cmp1Unavailable | Compressor Unavailable - Circuit 1 Compressor 1 | Read | 0=Available, 1=Unavailable | |
| BI | 164 | C1Cmp2Unavailable | Compressor Unavailable - Circuit 1 Compressor 2 | Read | 0=Available, 1=Unavailable | |
| BI | 165 | C2Cmp1Unavailable | Compressor Unavailable - Circuit 2 Compressor 1 | Read | 0=Available, 1=Unavailable | |
| BI | 166 | C2Cmp2Unavailable | Compressor Unavailable - Circuit 2 Compressor 2 | Read | 0=Available, 1=Unavailable | |
| BI | 1 | CondWaterFlowStatus | Condenser Flow Switch Status | Read | 0=No Flow, 1=Flow | |
| BI | 11 | CondPump1State | Condenser Pump 1 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 12 | CondPump2State | Condenser Pump 2 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 2 | EvapWaterFlowStatus | Evaporator Flow Switch Status | Read | 0=No Flow, 1=Flow | |
| BI | 8 | EvapPump1State | Evaporator Pump1 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 9 | EvapPump2State | Evaporator Pump2 Status | Read | 0=Pump Off Request, 1=Pump On Request | |
| BI | 5 | RunEnabled | Run Enabled | Read | 0=Off, 1=Run Allowed | |
| MV | 2 | ActiveMode | Chiller Mode Output | Read | 1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY | |
| MVmin | 3 | ChillerOperationMode | Chiller Mode Setpoint - Network | Write | 1=ICE, 2=COOL, 3=HEAT, 4=COOL/HEAT RECOVERY | |
| MVmin | 1 | UnitStatus | Chiller Status | Read | 1=OFF, 2=START, 3=RUN, 4=PRESHUTDOWN, 5=SERVICE | |
| MV | 4 | Units | Units | Write | 1=Metric, 2=English | |
| MV | 100 | C1Comp1OffAuto | Compressor Off/Auto - Circuit 1 Compressor 1 | Write | Off, Auto | |
| MV | 101 | C1Comp2OffAuto | Compressor Off/Auto - Circuit 1 Compressor 2 | Write | Off, Auto | |
| MV | 106 | C2Comp1OffAuto | Compressor Off/Auto - Circuit 2 Compressor 1 | Write | Off, Auto | |
| MV | 107 | C2Comp2OffAuto | Compressor Off/Auto - Circuit 2 Compressor 2 | Write | Off, Auto |
No points match these filters.
Object ID lookup: Daikin Applied Magnitude WME-C QUAD Chiller point IDs by name
AI9C1Comp1CurrentAI10C1Comp2CurrentAI12C2Comp1CurrentAI13C2Comp2CurrentAI63C1Comp1DischargeTempAI64C1Comp2DischargeTempAI66C2Comp1DischargeTempAI67C2Comp2DischargeTempAI81C1Comp1DischRefPressureAI82C1Comp2DischRefPressureAI84C2Comp1DischargeRefPressureAI85C2Comp2DischargeRefPressureAI45C1Comp1KilowattsAI46C1Comp2KilowattsAI48C2Comp1KilowattsAI49C2Comp2KilowattsAI105C1Comp1SuctionTempAI106C1Comp2SuctionTempAI108C2Comp1SuctionTempAI109C2Comp2SuctionTempAI123C1Comp1SuctionPressureAI124C1Comp2SuctionPressureAI126C2Comp1SuctionPressureAI127C2Comp2SuctionPressureAI27C1Comp1VoltageAI28C1Comp2VoltageAI30C2Comp1VoltageAI31C2Comp2VoltageAI3EntCondWaterTempAI147CondWaterFlowRateAI4LvgCondWaterTempAI99Cond1RefPressureAI1EntEvapWaterTempAI148EvapWaterFlowRateAI2LvgEvapWaterTempUnitAI141C1EvapRefPressureAI218C1LiqLineRefTempAI219C2LiqLineRefTempAV1ActiveCapacityLimitAV5ActiveLvgWaterTargetAV2ChillerCapacityAV901AVFaultAlarmAV902AVWarningAlarmAV910AVFaultModIDAV913AVWarningModIDAV911AVFaultModPayloadAV914AVWarningModPayloadAV909AVFaultModTypeAV912AVWarningModTypeAV3NetworkCapacityLimitPctAV26C1Comp1DischSatRefTempAV27C1Comp2DischSatRefTempAV29C2Comp1DischSatRefTempAV30C2Comp2DischSatRefTempAV8C1Comp1MotorCurrentPercentAV9C1Comp2MotorCurrentPercentAV11C2Comp1MotorCurrentPercentAV12C2Comp2MotorCurrentPercentAV74C1Comp1HoursAV75C1Comp2HoursAV50C1Comp1SuctSatTempAV51C1Comp2SuctSatTempAV53C2Comp1SuctSatTempAV54C2Comp2SuctSatTempAV92C1Comp1StartsAV93C1Comp2StartsAV110CondPump1RunHoursAV111CondPump2RunHoursAV44Cond1SatRefTempAV4NetworkCoolTempSetpointAV112EvapPump1OperHoursAV113EvapPump2OperHoursAV68C1EvapSatRefTempBV2ChillerEnableStpBV8ClearAlarmBI10AlarmDigitalOutputBI6ChillerLimitedBI7ChillerEnableOutputBI3ChillerLocalRemoteBI4UnitOnOffBI163C1Cmp1UnavailableBI164C1Cmp2UnavailableBI165C2Cmp1UnavailableBI166C2Cmp2UnavailableBI1CondWaterFlowStatusBI11CondPump1StateBI12CondPump2StateBI2EvapWaterFlowStatusBI8EvapPump1StateBI9EvapPump2StateBI5RunEnabledMV2ActiveModeMV3ChillerOperationModeMV1UnitStatusMV4UnitsMV100C1Comp1OffAutoMV101C1Comp2OffAutoMV106C2Comp1OffAutoMV107C2Comp2OffAuto
Integration notes
- ED 19111-4 covers WME C and D vintage and WME-C QUAD in one table. The C/D-vintage subset matches the WME C-vintage list (ED 19111-1); this entry is the QUAD set.
- The alarm code objects AV 903 and AV 905 are left out: the doc says WME-C QUAD does not use alarm codes. Use the alarm index and alarm module objects instead.
- Per the doc's model table the alarm module objects (AV 909-914) and Compressor Off/Auto (MV 100, 101, 106, 107) apply to QUAD; Off/Auto on a WME-C needs application code 1.2.4 or newer.
- Only Cool mode applies even though the mode objects list Ice, Heat and Heat Recovery.
- Units (MV 4) switches the values sent to BACnet between English and Metric; English is the default.
- Run hours and starts are listed only for circuit 1 compressors; condenser and evaporator pump hours for pumps 1 and 2.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Magnitude WME-C QUAD Chiller (MicroTech WME controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
How many BACnet points does the Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller) have?
This list has 99 BACnet objects: 38 analog inputs, 35 analog values, 16 binary inputs, 2 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller) BACnet points are writable?
10 of the 99 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller) BACnet documentation?
The source is MicroTech Unit Controller Protocol Information - Chiller Model WME, C and D-Vintage, and WME-C QUAD (ED 19111-4), revision 2026-03, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/19111-4.pdf.
What are the minimum BACnet points to integrate the Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)?
Start with BV 2 ChillerEnableStp (Network enable/disable of the chiller); MV 3 ChillerOperationMode (Mode command; only 2 = Cool applies on WME); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 3 NetworkCapacityLimitPct (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 ChillerLocalRemote (Shows whether network control is active); MV 1 UnitStatus (Chiller run state); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); AV 2 ChillerCapacity (Actual capacity in percent); AV 901 AVFaultAlarm (Active fault alarm index).
How do I enable BMS control of the Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)?
Control Source must be set to BAS at the unit HMI for the controller to use Network Enable (BV 2). For the cool setpoint, mode and capacity limit, Remote Enable must also be set to Enable at the HMI. Writing Enable to BV 2 only allows a start if other conditions are met. Individual compressors can be taken out of service from the network with the Compressor Off/Auto objects (MV 100, 101, 106, 107).
How do I check these points on the real Magnitude WME-C QUAD Chiller (MicroTech WME controller)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: MicroTech Unit Controller Protocol Information - Chiller Model WME, C and D-Vintage, and WME-C QUAD · ED 19111-4 · rev. 2026-03. Object names, instances and units are reproduced as published; descriptions are our own.