Rooftop unit controller · BACnet points list

Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet points list

Updated 6 November 2026

Short answer

The MicroTech II MPS controller on Maverick II rooftop units talks BACnet IP, BACnet Ethernet or BACnet MS/TP through a MicroTech II communication module (LonWorks is the other option). The table covers unit status, application and occupancy commands, occupied/unoccupied setpoints, discharge air and duct and building static pressure control, network sensor inputs, cool/heat/economizer enables and alarm read and clear. Several network inputs are guarded by a receive heartbeat.

This page lists 56 BACnet objects for the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Equipment
Rooftop unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
56 (32 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
MPS application 1.10 and later
Default device instance
3001
Also known as
Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS
Source document
MicroTech II McQuay Maverick II Rooftop Unit Controller Protocol Information, BACnet Networks, LonWorks Networks · ED 15102-3 · rev. 2010-02
Download CSV 56 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)

Integration in brief

Set Control Mode to AUTO and the network Type at the keypad. Turn the unit on and off with Application Mode (or shut it down with Emergency Override), schedule it with the occupancy scheduler input, write the setpoints and keep the heartbeat-guarded inputs refreshed. Read unit status, temperatures and the current alarm number.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1002ApplicCmdOff / heat only / cool only / fan only / autoWrite
MV 1011OccStateOccupancy schedule state from the BMSWrite
AV 1003EmergOverrideNetwork shutdown (4 = shut down, 0 = normal)Write
AV 6OccCoolSPOccupied cooling setpointWrite
AV 8OccHeatSetptOccupied heating setpointWrite
AV 1004DuctStaticSPInputDuct static pressure setpoint (DAC units)Write
BV 4ClearAllAlarmsWrite 1 to clear all alarmsWrite
MV 1025UnitStatusUnit operating stateRead
AV 10EffectDATempDischarge air temperatureRead
AV 1019AlarmHighest-priority active alarm numberRead

Enable & remote start

At the keypad (password 4545) set Control Mode to AUTO and Network Config Type to the BACnet network in use. Application Mode (MV 1002) then switches the unit off or between auto, heat only, cool only and fan only; it has no effect unless Control Mode is Auto. Emergency Override (AV 1003) = 4 shuts the unit down from the network. For network scheduling set Occupancy Mode to Auto at the keypad and write the occupancy scheduler input.

Heartbeat & communication loss

Receive Heartbeat (AV 5, default 30 s; 0 keeps network values after a comm loss, which Daikin advises against) guards the occupancy scheduler input, application mode, building static pressure, fan capacity, space and outdoor temperature, IAQ and the cool/heat/economizer enable inputs. If they are not rewritten in time they revert to the sensor value, normal operation or, for some, keep the last value until power is cycled.

Sensors & values from the BMS

Space Temperature Input (AV 4), Outdoor Air Temperature Input (AV 3), Building Static Pressure Input (AV 1005) and Space IAQ Input (AV 1010) take BMS values; Effective values (AV 15, 13, 1020, 1031) show what the unit uses. Keep writing them within the heartbeat time.

Network setup

Watch out for

Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

56 of 56 shown
Type
AnalogBinaryMulti-state
Access
Show
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet Points List
DescriptionStates
MVmin1025UnitStatusUnit StatusRead1=Off, 2=Startup, 3=Recirc, 4=Fan Only, 5=MinDAT, 6=Heating, 7=Economizer, 8=Cooling
AV1016CoolOutputCooling Capacity%Read
AV1015HeatOutputPrimary Heating Capacity%Read
MV1023CoolStatusCooling StatusRead1=Enabled, 2=None, 3=Off Manual, 4=Off Net, 5=Off Alarm, 6=Off Ambient
MV1024HeatStatusHeating StatusRead1=Enabled, 2=None, 3=Off Manual, 4=Off Net, 6=Off Ambient
MV1022EconStatusEconomizer StatusRead1=Enabled, 2=None, 3=Off Manual, 4=Off Net, 6=Off Ambient
AV1017EconOutputOutdoor Air Damper Position%Read
MV1014EffectOccOccupancyRead1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby
MVmin1011OccStateOccupancy scheduler input: current stateWrite1=Occupied, 2=Unoccupied, 4=Standby, 5=Auto
MV1012NextOccStateOccupancy scheduler input: next stateWrite1=Occupied, 2=Unoccupied, 4=Standby, 5=Auto
AV1013TimeToNextOccStateOccupancy scheduler input: time to next state (default 0 seconds)sWrite
AVmin10EffectDATempDischarge Air Temperature°FRead
AV14EffectRATReturn Air Temperature°FRead
AV15EffectSpaceTSpace Temperature°FRead
AV13EffectOATOutdoor Air Temperature°FRead
AV16LocalOATLocal outdoor air temperature sensor reading°FRead
AV17LocalSpaceTLocal space temperature sensor reading°FRead
AV1021EffectDuctStaticPDuct Static PressureinH2ORead
AV1018FanOutputDischarge Fan Capacity%Read
AV1020EffectBldgStaticPBuilding Static PressureinH2ORead
AV1006BldgStaticSPInputBuilding Static Pressure Setpoint (default 0.050” WC)inH2OWrite
AV1030ExhFanCapExhaust Fan Capacity%Read
AV2MinDATClgSetptMinimum Discharge Air Cooling Setpoint (default 55°F)°FWrite
AV12EffectSetptEffective setpoint used for heat/cool enable°FRead
AVmin6OccCoolSPOccupied Cooling Setpoint (default 72°F)°FWrite
AV7UnoccCoolSetptUnoccupied Cooling Setpoint (default 85°F)°FWrite
AVmin8OccHeatSetptOccupied Heating Setpoint (default 68°F)°FWrite
AV9UnoccHeatSetptUnoccupied Heating Setpoint (default 55°F)°FWrite
AV19MaxDATHtgSetptMax Discharge Air Heating Setpoint (default 113°F/45°C)°FWrite
AV18DAHtgSetptDischarge Air Heating Setpoint°FWrite
AV11EffectDATSetptEffective Discharge Air Temperature Setpoint°FRead
AV1009OAMinPosOutdoor Air Damper Minimum Position Input (default 10%)%Write
AV1031EffectSpaceCO2Space CO2ppmRead
AV1028EconEnaPercentEconomizer enable, percent form%Write
BV3EconEnableEconomizer enable, on/off formWrite
AV1032AppVersionApplication VersionRead
AV1007SupFanCapInputRemote Discharge Fan Capacity Setpoint (default 0%)%Write
MVmin1002ApplicCmdApplication ModeWrite1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly, 5=Auto
MV1001OccManCmdOccupancy ModeWrite1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Auto
AVmin1003EmergOverrideNetwork emergency override (4 = shut down)Write0=Normal, 4=Shutdown
AVmin1004DuctStaticSPInputDuct Static Pressure Setpoint (default 1.00” WC)inH2OWrite
AV4SpaceTempInputSpace Temperature Input°FWrite
AV3OutdoorTempInputOutdoor Air Temperature Input°FWrite
AV1DAClgSetptDischarge air cooling setpoint from the network (DAC)°FWrite
AV1005BldgStaticPressInputBuilding static pressure from the networkinH2OWrite
AV1008ExhFanCapInputExhaust Fan Capacity Input%Write
BV2HeatEnablePrimary heat enable, on/off formWrite
AV1027HeatEnaPercentPrimary heat enable, percent form%Write
BV1CoolEnablePrimary cool enable, on/off formWrite
AV1026CoolEnaPercentPrimary cool enable, percent form%Write
AV1010SpaceIAQInputSpace IAQ InputWrite
AV5ReceiveHrtBtReceive heartbeat time for network inputs (default 30 s)sWrite
AVmin1019AlarmHighest-priority active alarm number (0 = none)Read
BVmin4ClearAllAlarmsWrite 1 to clear all active alarmsWrite
AV1029ClearOneAlarmWrite an alarm number to clear that alarmWrite
BV5ExhFanOn_OffExhaust Fan StatusRead
Object ID lookup: Daikin Applied Maverick II MPS rooftop point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)

How many BACnet points does the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) have?

This list has 56 BACnet objects: 42 analog values, 5 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet points are writable?

32 of the 56 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet documentation?

The source is MicroTech II McQuay Maverick II Rooftop Unit Controller Protocol Information, BACnet Networks, LonWorks Networks (ED 15102-3), revision 2010-02, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15102-3.pdf.

What are the minimum BACnet points to integrate the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)?

Start with MV 1002 ApplicCmd (Off / heat only / cool only / fan only / auto); MV 1011 OccState (Occupancy schedule state from the BMS); AV 1003 EmergOverride (Network shutdown (4 = shut down, 0 = normal)); AV 6 OccCoolSP (Occupied cooling setpoint); AV 8 OccHeatSetpt (Occupied heating setpoint); AV 1004 DuctStaticSPInput (Duct static pressure setpoint (DAC units)); BV 4 ClearAllAlarms (Write 1 to clear all alarms); MV 1025 UnitStatus (Unit operating state); AV 10 EffectDATemp (Discharge air temperature); AV 1019 Alarm (Highest-priority active alarm number).

How do I enable BMS control of the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)?

At the keypad (password 4545) set Control Mode to AUTO and Network Config Type to the BACnet network in use. Application Mode (MV 1002) then switches the unit off or between auto, heat only, cool only and fan only; it has no effect unless Control Mode is Auto. Emergency Override (AV 1003) = 4 shuts the unit down from the network. For network scheduling set Occupancy Mode to Auto at the keypad and write the occupancy scheduler input.

Does the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) need a BACnet heartbeat or have a communication timeout?

Receive Heartbeat (AV 5, default 30 s; 0 keeps network values after a comm loss, which Daikin advises against) guards the occupancy scheduler input, application mode, building static pressure, fan capacity, space and outdoor temperature, IAQ and the cool/heat/economizer enable inputs. If they are not rewritten in time they revert to the sensor value, normal operation or, for some, keep the last value until power is cycled.

Can the BMS supply sensor values to the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)?

Space Temperature Input (AV 4), Outdoor Air Temperature Input (AV 3), Building Static Pressure Input (AV 1005) and Space IAQ Input (AV 1010) take BMS values; Effective values (AV 15, 13, 1020, 1031) show what the unit uses. Keep writing them within the heartbeat time.

How do I check these points on the real Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech II McQuay Maverick II Rooftop Unit Controller Protocol Information, BACnet Networks, LonWorks Networks · ED 15102-3 · rev. 2010-02. Object names, instances and units are reproduced as published; descriptions are our own.