Rooftop unit controller · BACnet points list
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet points list
Updated 6 November 2026
The MicroTech II MPS controller on Maverick II rooftop units talks BACnet IP, BACnet Ethernet or BACnet MS/TP through a MicroTech II communication module (LonWorks is the other option). The table covers unit status, application and occupancy commands, occupied/unoccupied setpoints, discharge air and duct and building static pressure control, network sensor inputs, cool/heat/economizer enables and alarm read and clear. Several network inputs are guarded by a receive heartbeat.
This page lists 56 BACnet objects for the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
- Equipment
- Rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 56 (32 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- MPS application 1.10 and later
- Default device instance
- 3001
- Also known as
- Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Set Control Mode to AUTO and the network Type at the keypad. Turn the unit on and off with Application Mode (or shut it down with Emergency Override), schedule it with the occupancy scheduler input, write the setpoints and keep the heartbeat-guarded inputs refreshed. Read unit status, temperatures and the current alarm number.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1002 | ApplicCmd | Off / heat only / cool only / fan only / auto | Write |
| MV 1011 | OccState | Occupancy schedule state from the BMS | Write |
| AV 1003 | EmergOverride | Network shutdown (4 = shut down, 0 = normal) | Write |
| AV 6 | OccCoolSP | Occupied cooling setpoint | Write |
| AV 8 | OccHeatSetpt | Occupied heating setpoint | Write |
| AV 1004 | DuctStaticSPInput | Duct static pressure setpoint (DAC units) | Write |
| BV 4 | ClearAllAlarms | Write 1 to clear all alarms | Write |
| MV 1025 | UnitStatus | Unit operating state | Read |
| AV 10 | EffectDATemp | Discharge air temperature | Read |
| AV 1019 | Alarm | Highest-priority active alarm number | Read |
Enable & remote start
At the keypad (password 4545) set Control Mode to AUTO and Network Config Type to the BACnet network in use. Application Mode (MV 1002) then switches the unit off or between auto, heat only, cool only and fan only; it has no effect unless Control Mode is Auto. Emergency Override (AV 1003) = 4 shuts the unit down from the network. For network scheduling set Occupancy Mode to Auto at the keypad and write the occupancy scheduler input.
Heartbeat & communication loss
Receive Heartbeat (AV 5, default 30 s; 0 keeps network values after a comm loss, which Daikin advises against) guards the occupancy scheduler input, application mode, building static pressure, fan capacity, space and outdoor temperature, IAQ and the cool/heat/economizer enable inputs. If they are not rewritten in time they revert to the sensor value, normal operation or, for some, keep the last value until power is cycled.
Sensors & values from the BMS
Space Temperature Input (AV 4), Outdoor Air Temperature Input (AV 3), Building Static Pressure Input (AV 1005) and Space IAQ Input (AV 1010) take BMS values; Effective values (AV 15, 13, 1020, 1031) show what the unit uses. Keep writing them within the heartbeat time.
Network setup
- Defaults: device instance 3001; BACnet IP 172.16.5.8 /16, UDP 47808, router 0.0.0.0; BACnet MS/TP MAC 0, 38400 baud, Max Master 127, Max Info Frames 1.
- Device object name is MTIIUC_MPS plus the device instance; the alpha part and the UDP port change only with the BACnet Communication Module Configuration Tool (UM 855).
- Network parameters are set from the keypad Network Config menu (password 4545).
Watch out for
- Alarm AV 1019 shows only the highest-priority active alarm: 1-99 warning, 100-199 problem, 200-255 fault.
- Clear one alarm by writing its number to AV 1029 (e.g. 250 for an emergency fault).
- Some network inputs keep their last value after the heartbeat expires until power is cycled; send them again after a restart.
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 1025 | UnitStatus | Unit Status | Read | 1=Off, 2=Startup, 3=Recirc, 4=Fan Only, 5=MinDAT, 6=Heating, 7=Economizer, 8=Cooling | |
| AV | 1016 | CoolOutput | Cooling Capacity | % | Read | |
| AV | 1015 | HeatOutput | Primary Heating Capacity | % | Read | |
| MV | 1023 | CoolStatus | Cooling Status | Read | 1=Enabled, 2=None, 3=Off Manual, 4=Off Net, 5=Off Alarm, 6=Off Ambient | |
| MV | 1024 | HeatStatus | Heating Status | Read | 1=Enabled, 2=None, 3=Off Manual, 4=Off Net, 6=Off Ambient | |
| MV | 1022 | EconStatus | Economizer Status | Read | 1=Enabled, 2=None, 3=Off Manual, 4=Off Net, 6=Off Ambient | |
| AV | 1017 | EconOutput | Outdoor Air Damper Position | % | Read | |
| MV | 1014 | EffectOcc | Occupancy | Read | 1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby | |
| MVmin | 1011 | OccState | Occupancy scheduler input: current state | Write | 1=Occupied, 2=Unoccupied, 4=Standby, 5=Auto | |
| MV | 1012 | NextOccState | Occupancy scheduler input: next state | Write | 1=Occupied, 2=Unoccupied, 4=Standby, 5=Auto | |
| AV | 1013 | TimeToNextOccState | Occupancy scheduler input: time to next state (default 0 seconds) | s | Write | |
| AVmin | 10 | EffectDATemp | Discharge Air Temperature | °F | Read | |
| AV | 14 | EffectRAT | Return Air Temperature | °F | Read | |
| AV | 15 | EffectSpaceT | Space Temperature | °F | Read | |
| AV | 13 | EffectOAT | Outdoor Air Temperature | °F | Read | |
| AV | 16 | LocalOAT | Local outdoor air temperature sensor reading | °F | Read | |
| AV | 17 | LocalSpaceT | Local space temperature sensor reading | °F | Read | |
| AV | 1021 | EffectDuctStaticP | Duct Static Pressure | inH2O | Read | |
| AV | 1018 | FanOutput | Discharge Fan Capacity | % | Read | |
| AV | 1020 | EffectBldgStaticP | Building Static Pressure | inH2O | Read | |
| AV | 1006 | BldgStaticSPInput | Building Static Pressure Setpoint (default 0.050” WC) | inH2O | Write | |
| AV | 1030 | ExhFanCap | Exhaust Fan Capacity | % | Read | |
| AV | 2 | MinDATClgSetpt | Minimum Discharge Air Cooling Setpoint (default 55°F) | °F | Write | |
| AV | 12 | EffectSetpt | Effective setpoint used for heat/cool enable | °F | Read | |
| AVmin | 6 | OccCoolSP | Occupied Cooling Setpoint (default 72°F) | °F | Write | |
| AV | 7 | UnoccCoolSetpt | Unoccupied Cooling Setpoint (default 85°F) | °F | Write | |
| AVmin | 8 | OccHeatSetpt | Occupied Heating Setpoint (default 68°F) | °F | Write | |
| AV | 9 | UnoccHeatSetpt | Unoccupied Heating Setpoint (default 55°F) | °F | Write | |
| AV | 19 | MaxDATHtgSetpt | Max Discharge Air Heating Setpoint (default 113°F/45°C) | °F | Write | |
| AV | 18 | DAHtgSetpt | Discharge Air Heating Setpoint | °F | Write | |
| AV | 11 | EffectDATSetpt | Effective Discharge Air Temperature Setpoint | °F | Read | |
| AV | 1009 | OAMinPos | Outdoor Air Damper Minimum Position Input (default 10%) | % | Write | |
| AV | 1031 | EffectSpaceCO2 | Space CO2 | ppm | Read | |
| AV | 1028 | EconEnaPercent | Economizer enable, percent form | % | Write | |
| BV | 3 | EconEnable | Economizer enable, on/off form | Write | ||
| AV | 1032 | AppVersion | Application Version | Read | ||
| AV | 1007 | SupFanCapInput | Remote Discharge Fan Capacity Setpoint (default 0%) | % | Write | |
| MVmin | 1002 | ApplicCmd | Application Mode | Write | 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly, 5=Auto | |
| MV | 1001 | OccManCmd | Occupancy Mode | Write | 1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Auto | |
| AVmin | 1003 | EmergOverride | Network emergency override (4 = shut down) | Write | 0=Normal, 4=Shutdown | |
| AVmin | 1004 | DuctStaticSPInput | Duct Static Pressure Setpoint (default 1.00” WC) | inH2O | Write | |
| AV | 4 | SpaceTempInput | Space Temperature Input | °F | Write | |
| AV | 3 | OutdoorTempInput | Outdoor Air Temperature Input | °F | Write | |
| AV | 1 | DAClgSetpt | Discharge air cooling setpoint from the network (DAC) | °F | Write | |
| AV | 1005 | BldgStaticPressInput | Building static pressure from the network | inH2O | Write | |
| AV | 1008 | ExhFanCapInput | Exhaust Fan Capacity Input | % | Write | |
| BV | 2 | HeatEnable | Primary heat enable, on/off form | Write | ||
| AV | 1027 | HeatEnaPercent | Primary heat enable, percent form | % | Write | |
| BV | 1 | CoolEnable | Primary cool enable, on/off form | Write | ||
| AV | 1026 | CoolEnaPercent | Primary cool enable, percent form | % | Write | |
| AV | 1010 | SpaceIAQInput | Space IAQ Input | Write | ||
| AV | 5 | ReceiveHrtBt | Receive heartbeat time for network inputs (default 30 s) | s | Write | |
| AVmin | 1019 | Alarm | Highest-priority active alarm number (0 = none) | Read | ||
| BVmin | 4 | ClearAllAlarms | Write 1 to clear all active alarms | Write | ||
| AV | 1029 | ClearOneAlarm | Write an alarm number to clear that alarm | Write | ||
| BV | 5 | ExhFanOn_Off | Exhaust Fan Status | Read |
No points match these filters.
Object ID lookup: Daikin Applied Maverick II MPS rooftop point IDs by name
MV1025UnitStatusAV1016CoolOutputAV1015HeatOutputMV1023CoolStatusMV1024HeatStatusMV1022EconStatusAV1017EconOutputMV1014EffectOccMV1011OccStateMV1012NextOccStateAV1013TimeToNextOccStateAV10EffectDATempAV14EffectRATAV15EffectSpaceTAV13EffectOATAV16LocalOATAV17LocalSpaceTAV1021EffectDuctStaticPAV1018FanOutputAV1020EffectBldgStaticPAV1006BldgStaticSPInputAV1030ExhFanCapAV2MinDATClgSetptAV12EffectSetptAV6OccCoolSPAV7UnoccCoolSetptAV8OccHeatSetptAV9UnoccHeatSetptAV19MaxDATHtgSetptAV18DAHtgSetptAV11EffectDATSetptAV1009OAMinPosAV1031EffectSpaceCO2AV1028EconEnaPercentBV3EconEnableAV1032AppVersionAV1007SupFanCapInputMV1002ApplicCmdMV1001OccManCmdAV1003EmergOverrideAV1004DuctStaticSPInputAV4SpaceTempInputAV3OutdoorTempInputAV1DAClgSetptAV1005BldgStaticPressInputAV1008ExhFanCapInputBV2HeatEnableAV1027HeatEnaPercentBV1CoolEnableAV1026CoolEnaPercentAV1010SpaceIAQInputAV5ReceiveHrtBtAV1019AlarmBV4ClearAllAlarmsAV1029ClearOneAlarmBV5ExhFanOn_Off
Integration notes
- Object names are the short codes from the guide's full BACnet references (MTIIUC_MPS#########.Name); the point table itself prints longer property names, used here as descriptions.
- Points marked N/A for SCC (zone control) only apply to DAC (discharge air control) units, e.g. duct static pressure and discharge air cooling setpoints.
- Effective Setpoint Output AV 12 is printed twice in the table (cooling and heating rows); it is one object.
- The detail page for Current Alarm shows no instance; the alarm section of the guide names it AV 1019.
- Local Space Temperature (AV 17) and Local OA Temperature (AV 16) have no type or instance in the summary table; they come from their detail pages.
- BACnet Ethernet is also offered as a module option.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
How many BACnet points does the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) have?
This list has 56 BACnet objects: 42 analog values, 5 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet points are writable?
32 of the 56 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) BACnet documentation?
The source is MicroTech II McQuay Maverick II Rooftop Unit Controller Protocol Information, BACnet Networks, LonWorks Networks (ED 15102-3), revision 2010-02, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15102-3.pdf.
What are the minimum BACnet points to integrate the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)?
Start with MV 1002 ApplicCmd (Off / heat only / cool only / fan only / auto); MV 1011 OccState (Occupancy schedule state from the BMS); AV 1003 EmergOverride (Network shutdown (4 = shut down, 0 = normal)); AV 6 OccCoolSP (Occupied cooling setpoint); AV 8 OccHeatSetpt (Occupied heating setpoint); AV 1004 DuctStaticSPInput (Duct static pressure setpoint (DAC units)); BV 4 ClearAllAlarms (Write 1 to clear all alarms); MV 1025 UnitStatus (Unit operating state); AV 10 EffectDATemp (Discharge air temperature); AV 1019 Alarm (Highest-priority active alarm number).
How do I enable BMS control of the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)?
At the keypad (password 4545) set Control Mode to AUTO and Network Config Type to the BACnet network in use. Application Mode (MV 1002) then switches the unit off or between auto, heat only, cool only and fan only; it has no effect unless Control Mode is Auto. Emergency Override (AV 1003) = 4 shuts the unit down from the network. For network scheduling set Occupancy Mode to Auto at the keypad and write the occupancy scheduler input.
Does the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS) need a BACnet heartbeat or have a communication timeout?
Receive Heartbeat (AV 5, default 30 s; 0 keeps network values after a comm loss, which Daikin advises against) guards the occupancy scheduler input, application mode, building static pressure, fan capacity, space and outdoor temperature, IAQ and the cool/heat/economizer enable inputs. If they are not rewritten in time they revert to the sensor value, normal operation or, for some, keep the last value until power is cycled.
Can the BMS supply sensor values to the Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)?
Space Temperature Input (AV 4), Outdoor Air Temperature Input (AV 3), Building Static Pressure Input (AV 1005) and Space IAQ Input (AV 1010) take BMS values; Effective values (AV 15, 13, 1020, 1031) show what the unit uses. Keep writing them within the heartbeat time.
How do I check these points on the real Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: MicroTech II McQuay Maverick II Rooftop Unit Controller Protocol Information, BACnet Networks, LonWorks Networks · ED 15102-3 · rev. 2010-02. Object names, instances and units are reproduced as published; descriptions are our own.