Rooftop unit / air handler controller · BACnet points list
Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet points list
Updated 4 November 2026
The older MicroTech II applied rooftop controller connects to BACnet IP or BACnet MS/TP through a plug-in communication module (LonWorks modules also exist). It exposes a fixed set of standard objects, mostly analog values carrying numbered enumerations, covering unit status, application mode, occupancy, temperatures, duct and building static pressure, fan capacities, zone and discharge setpoints, outdoor air damper, economizer, energy recovery, dehumidification, schedule and alarms.
This page lists 75 BACnet objects for the Daikin Applied MicroTech II Applied Rooftop Unit Controller — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- MicroTech II Applied Rooftop Unit Controller
- Equipment
- Rooftop unit / air handler controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 75 (37 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Last six digits of the main control board serial number
- Also known as
- MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied MicroTech II Applied Rooftop Unit Controller
Set switch S7 to AUTO and Control Mode to AUTO at the keypad. With Occupancy Mode left at Auto, the BMS commands occupancy through the Occupancy Scheduler Input BV at a priority higher than 15, turns the unit off with Application Mode or the Emergency Override flag, and writes setpoints at priority 16.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1455 | Occupancy Scheduler Input | Occupied (1) / unoccupied (0) command from the BMS | Write |
| AV 3610 | Emergency Override Mode Flag | Network shutdown: 1 = Off, 0 = Normal | Write |
| AV 3605 | Application Mode | 0=Auto, 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly | Write |
| AV 3655 | Occupied Cooling Setpoint | Occupied cooling setpoint | Write |
| AV 3710 | Occupied Heating Setpoint | Occupied heating setpoint | Write |
| AV 3630 | Discharge Air Cooling Setpoint | Discharge air cooling setpoint (DAC units) | Write |
| AV 3810 | Unit Status | Current operating state (enumerated) | Read |
| AI 115 | Discharge Air Temperature | Discharge air temperature | Read |
| AV 3790 | Duct Static Pressure | Duct static pressure, in. w.c. | Read |
| BV 4150 | Alarm, Faults: Clear All | Fault alarm active; write 0 to clear | Write |
Enable & remote start
Put rocker switch S7 in AUTO and set Control Mode to AUTO at the keypad (password 4545). Leave Occupancy Mode (AV 3825) at Auto and command occupancy with the Occupancy Scheduler Input (BV 1455). Application Mode (AV 3605) = Off or Emergency Override Mode Flag (AV 3610) = Off shuts the unit down. For network setpoint control set Space Setpoint Type (AV 3615) to Keypad/Network.
Heartbeat & communication loss
No BACnet heartbeat point is given; the receive-heartbeat defaults in the doc apply to the LonWorks network variables. A BACnet value written to an out-of-service input (space, outdoor air temperature, building static pressure) is held at its last value if communication is lost.
Sensors & values from the BMS
Space Temperature (AI 100), Outdoor Air Temperature (AI 125) and Building Static Pressure (AI 1505) accept a BMS value once their Out_Of_Service property is set to TRUE; the controller keeps the last value written if communication is lost. Remote fan capacities are written to AV 3725 / AV 3740 when the matching control flag (AV 3720 / AV 3750) is set to Position.
Network setup
- Communication parameters are changed with MicroTech II ServiceTools, not over the network.
- BACnet IP defaults: IP 172.16.83.46, mask 255.255.0.0, UDP 47808, router 172.16.128.0, network number 1001; no DHCP.
- For BACnet IP the device's Communication Option must be NONE; MSTP (the default) is used for MS/TP and LonWorks.
- MS/TP MAC is set on the 8-position DIP switch of the MS/TP module (default 2 on MS/TP units); default 19200 baud, network number 2001.
- Device instance = last six digits of the main control board serial number; device name MTII RTUC plus the last nine digits.
Watch out for
- The keypad schedule writes the Occupancy Scheduler Input BV at priority 15; command it at a higher priority (e.g. 8) and relinquish at that priority to hand back to the keypad.
- Write analog values at priority 16; a value written at another priority can differ from the one in use after a keypad change.
- Occupancy Mode (AV 3825) is an override, not the normal occupancy command; leave it at Auto.
- Clear alarms by class by writing the Clear All BV from Alarm (1) to Normal (0); it reads Alarm again if the condition is still present.
- Individual alarm-number objects differ between 100-series and 200-series application software.
Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 3810 | Unit Status | Unit operating state | Read | 0=OffUnoc, 1=OffNet, 2=Off Sw, 3=OffAlm, 4=Calib, 5=Startup, 6=Recirc, 7=FanOnly, 8=Econo, 9=Cooling, 10=MWU, 11=Heating, 12=MinDAT, 13=UnocEcon, 14=UnocFanO, 15=UnocDAT, 16=UnocClg, 17=UnocHtg, 18=Balance, 19=OffMan, 20=ManCtrl | |
| AV | 3620 | Cooling Capacity | Cooling capacity feedback | % | Read | |
| AV | 3695 | Heating Capacity | Heating capacity feedback | % | Read | |
| AV | 3665 | Cooling Control Status | Cooling control status | Read | 0=All Clg, 1=Econo, 2=Mech Clg, 3=Off Amb, 4=Off Alarm, 5=Off None, 6=Off Bal, 7=Off Sw, 8=Off Net, 9=Off Man | |
| AV | 3715 | Heating Control Status | Heating control status | Read | 0=HtEna, 1=OffAmb, 2=OffAlarm, 3=OffNone, 4=N/A, 5=OffSw, 6=OffNet, 7=OffMan | |
| AVmin | 3605 | Application Mode | Application mode command | Write | 0=Auto, 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly | |
| BO | 265 | VAV Box Output | VAV box output (MCB BO 12) state | Read | 0=Off, 1=On | |
| AV | 3815 | Occupancy | Effective occupancy | Read | 0=Occ, 1=Unocc, 2=Bypass | |
| AV | 3825 | Occupancy Mode | Occupancy override; leave at Auto normally | Write | 0=Occ, 1=Unocc, 2=Bypass, 3=Auto | |
| BVmin | 1455 | Occupancy Scheduler Input | Occupied/unoccupied command when Occupancy Mode = Auto | Write | 0=Unoccupied, 1=Occupied | |
| AV | 3820 | Occupancy Source | Where the occupancy command comes from | Read | 0=None, 1=Int Sched, 2=Net Sched, 3=Occ Mode, 4=Remote Sw, 5=N/A | |
| AVmin | 3610 | Emergency Override Mode Flag | Network shutdown flag | Write | 0=Norm, 1=Off | |
| AV | 135 | Control Temperature | Temperature used for control | °F | Read | |
| AImin | 115 | Discharge Air Temperature | Discharge air temperature | °F | Read | |
| AI | 120 | Return Air Temperature | Return air temperature | °F | Read | |
| AI | 100 | Space Temperature | Space temperature (writable with Out_Of_Service set) | °F | Write | |
| AI | 125 | Outdoor Air Temperature | Outdoor air temperature (writable with Out_Of_Service set) | °F | Write | |
| AI | 130 | Entering Fan Temperature | Entering fan temperature | °F | Read | |
| BI | 160 | Airflow Status | Discharge airflow switch | Read | 0=Noflo, 1=Flow | |
| BO | 255 | Discharge Fan Status | Discharge fan command | Read | 0=Off, 1=On | |
| BO | 260 | Return Fan Status | Return or exhaust fan command | Read | 0=Off, 1=On | |
| BO | 250 | Fan Operation Output | Fans-on relay output (MCB BO 3) | Read | 0=Off, 1=On | |
| AVmin | 3790 | Duct Static Pressure | Duct static pressure (lower of two sensors) | in. w.c. | Read | |
| AV | 3730 | Duct Static Pressure Setpoint | Duct static pressure setpoint, default 1.00 | in. w.c. | Write | |
| AV | 3735 | Discharge Fan Capacity | Discharge fan capacity | % | Read | |
| AI | 1505 | Building Static Pressure | Building static pressure (writable with Out_Of_Service set) | in. w.c. | Write | |
| AV | 3755 | Building Static Pressure Setpoint | Building static pressure setpoint, default 0.050 | in. w.c. | Write | |
| AV | 3745 | Return Fan Capacity | Return or exhaust fan capacity | % | Read | |
| AV | 3640 | Effective Cooling Enable Setpoint | Zone cooling enable setpoint in use | °F | Read | |
| AVmin | 3655 | Occupied Cooling Setpoint | Occupied cooling setpoint, default 75 | °F | Write | |
| AV | 3600 | Control Temperature Source | Control temperature source | Write | 0=Return, 1=Space, 2=OAT | |
| AV | 3795 | Unoccupied Cooling Setpoint | Unoccupied cooling setpoint, default 85 | °F | Write | |
| AV | 3690 | Effective Heating Enable Setpoint | Zone heating enable setpoint in use | °F | Read | |
| AVmin | 3710 | Occupied Heating Setpoint | Occupied heating setpoint, default 70 | °F | Write | |
| AV | 3800 | Unoccupied Heating Setpoint | Unoccupied heating setpoint, default 55 | °F | Write | |
| AV | 3635 | Effective Cooling Discharge Setpoint | Discharge cooling setpoint in use | °F | Read | |
| AVmin | 3630 | Discharge Air Cooling Setpoint | Discharge air cooling setpoint, default 55 | °F | Write | |
| AV | 3645 | Min Discharge Air Cooling Setpoint | Minimum discharge cooling setpoint (reset) | °F | Write | |
| AV | 3650 | Max Discharge Air Cooling Setpoint | Maximum discharge cooling setpoint (reset) | °F | Write | |
| AI | 460 | Outdoor Air Damper Position | Outdoor air damper position | % | Read | |
| AV | 3765 | Effective Min Outdoor Damper Pos Spt | Minimum OA damper position in use | % | Read | |
| AV | 3780 | Outdoor Air Flow | Outdoor airflow (DesignFlow option) | CFM | Read | |
| AV | 3775 | Outdoor Air Damper Min Position | Outdoor air damper minimum position, default 10 | % | Write | |
| AV | 3770 | Min Outdoor Airflow/Damper Position | Minimum OA airflow/damper setting with DesignFlow | Write | ||
| AV | 3785 | Economizer Changeover Method | Economizer changeover method | Write | 0=Enthalpy, 1=Dry Bulb | |
| AV | 3760 | Economizer Changeover Temp Spt | Dry-bulb economizer changeover temperature | °F | Write | |
| AV | 3685 | Effective Heating Discharge Setpoint | Discharge heating setpoint in use | °F | Read | |
| AV | 3680 | Discharge Air Heating Setpoint | Discharge air heating setpoint, default 100 | °F | Write | |
| AV | 3805 | Min Discharge Air Temperature Limit | Minimum discharge air temperature limit | °F | Write | |
| AV | 3700 | Min Discharge Air Heating Setpoint | Minimum discharge heating setpoint (reset) | °F | Write | |
| AV | 3705 | Max Discharge Air Heating Setpoint | Maximum discharge heating setpoint (reset) | °F | Write | |
| AV | 4210 | Energy Recovery Exhaust Temperature | Energy recovery exhaust temperature | °F | Read | |
| AV | 4205 | Energy Recovery Supply Temperature | Energy recovery supply temperature | °F | Read | |
| AV | 3675 | Dehumidification Status | Dehumidification active | Read | ||
| AI | 805 | Relative Humidity | Space relative humidity (optional sensor) | %RH | Read | |
| AV | 810 | Dew Point Temperature | Calculated dew point | °F | Read | |
| AV | 3670 | Relative Humidity Control Type | Dehumidification control type | Write | 0=None, 1=RelHum, 2=DewPnt | |
| AV | 3660 | Relative Humidity Setpoint | Relative humidity setpoint | %RH | Write | |
| AV | 3625 | Dew Point Setpoint | Dew point setpoint | °F | Write | |
| SCH | 1460 | Daily Schedule | Keypad daily schedule object | Read | ||
| CAL | 1465 | Holidays | Keypad holiday calendar | Write | ||
| AV | 3720 | Remote Discharge Fan Cap Control Flag | Discharge fan capacity control method | Write | 0=Duct Pres, 1=Position | |
| AV | 3725 | Remote Discharge Fan Capacity Spt | Remote discharge fan capacity, default 25 | % | Write | |
| AV | 3750 | Remote Return Fan Cap. Control Flag | Return fan capacity control method | Write | 0=None, 1=Tracking, 2=Bldg Press, 3=Position | |
| AV | 3740 | Remote Return Fan Capacity Spt | Remote return fan capacity, default 25 | % | Write | |
| AV | 3615 | Space Setpoint Type | Setpoint source: thermostat or keypad/network | Write | 0=Tstat, 1=Keypad/Network | |
| BVmin | 4150 | Alarm, Faults: Clear All | Fault alarm active; write Normal to clear | Write | 0=Normal, 1=Alarm | |
| BV | 4145 | Alarm, Problems: Clear All | Problem alarm active; write Normal to clear | Write | 0=Normal, 1=Alarm | |
| BV | 4140 | Alarm, Warnings: Clear All | Warning alarm active; write Normal to clear | Write | 0=Normal, 1=Alarm | |
| AV | 4862 | Alarms-Fault Individual Notification | Highest active fault number (100-series software) | Read | ||
| AV | 4861 | Alarms-Problem Individual Notification | Highest active problem number (100-series software) | Read | ||
| AV | 4863 | Alarms-Warning Individual Notification | Highest active warning number (100-series software) | Read | ||
| AV | 4870 | Alarms-Fault Individual Notification | Highest active fault number (200-series software) | Read | ||
| AV | 4872 | Alarms-Problem Individual Notification | Highest active problem number (200-series software) | Read | ||
| AV | 4873 | Alarms-Warning Individual Notification | Highest active warning number (200-series software) | Read |
No points match these filters.
Object ID lookup: Daikin Applied MicroTech II Applied Rooftop Unit Controller point IDs by name
AV3810Unit StatusAV3620Cooling CapacityAV3695Heating CapacityAV3665Cooling Control StatusAV3715Heating Control StatusAV3605Application ModeBO265VAV Box OutputAV3815OccupancyAV3825Occupancy ModeBV1455Occupancy Scheduler InputAV3820Occupancy SourceAV3610Emergency Override Mode FlagAV135Control TemperatureAI115Discharge Air TemperatureAI120Return Air TemperatureAI100Space TemperatureAI125Outdoor Air TemperatureAI130Entering Fan TemperatureBI160Airflow StatusBO255Discharge Fan StatusBO260Return Fan StatusBO250Fan Operation OutputAV3790Duct Static PressureAV3730Duct Static Pressure SetpointAV3735Discharge Fan CapacityAI1505Building Static PressureAV3755Building Static Pressure SetpointAV3745Return Fan CapacityAV3640Effective Cooling Enable SetpointAV3655Occupied Cooling SetpointAV3600Control Temperature SourceAV3795Unoccupied Cooling SetpointAV3690Effective Heating Enable SetpointAV3710Occupied Heating SetpointAV3800Unoccupied Heating SetpointAV3635Effective Cooling Discharge SetpointAV3630Discharge Air Cooling SetpointAV3645Min Discharge Air Cooling SetpointAV3650Max Discharge Air Cooling SetpointAI460Outdoor Air Damper PositionAV3765Effective Min Outdoor Damper Pos SptAV3780Outdoor Air FlowAV3775Outdoor Air Damper Min PositionAV3770Min Outdoor Airflow/Damper PositionAV3785Economizer Changeover MethodAV3760Economizer Changeover Temp SptAV3685Effective Heating Discharge SetpointAV3680Discharge Air Heating SetpointAV3805Min Discharge Air Temperature LimitAV3700Min Discharge Air Heating SetpointAV3705Max Discharge Air Heating SetpointAV4210Energy Recovery Exhaust TemperatureAV4205Energy Recovery Supply TemperatureAV3675Dehumidification StatusAI805Relative HumidityAV810Dew Point TemperatureAV3670Relative Humidity Control TypeAV3660Relative Humidity SetpointAV3625Dew Point SetpointSCH1460Daily ScheduleCAL1465HolidaysAV3720Remote Discharge Fan Cap Control FlagAV3725Remote Discharge Fan Capacity SptAV3750Remote Return Fan Cap. Control FlagAV3740Remote Return Fan Capacity SptAV3615Space Setpoint TypeBV4150Alarm, Faults: Clear AllBV4145Alarm, Problems: Clear AllBV4140Alarm, Warnings: Clear AllAV4862Alarms-Fault Individual NotificationAV4861Alarms-Problem Individual NotificationAV4863Alarms-Warning Individual NotificationAV4870Alarms-Fault Individual NotificationAV4872Alarms-Problem Individual NotificationAV4873Alarms-Warning Individual Notification
Integration notes
- Five rows in the main table use Daikin proprietary object types (Runtime Totalization for cooling hours, and Application objects for the cooling and heating reset enables); they are left out.
- The detail pages also describe other runtime-hour objects of the same proprietary type; they are not included.
- Space Temperature (AI 100), Outdoor Air Temperature (AI 125) and Building Static Pressure (AI 1505) are marked R** in the table: a BMS can write a network value to them after setting Out_Of_Service to TRUE; if communication is then lost the controller keeps the last value written.
- Many multi-state settings are analog values carrying an enumeration number (for example Application Mode AV 3605).
- Two sets of individual alarm objects exist: AV 4861-4863 for 100-series application software v1.44 and later, AV 4870, 4872 and 4873 for 200-series v2.07/2.08.
- Points marked N/A in the SCC or DAC column apply only to the other control type (zone temperature control vs discharge air control).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech II Applied Rooftop Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied MicroTech II Applied Rooftop Unit Controller
How many BACnet points does the Daikin Applied MicroTech II Applied Rooftop Unit Controller have?
This list has 75 BACnet objects: 8 analog inputs, 56 analog values, 1 binary input, 4 binary outputs, 4 binary values, 1 calendar, 1 schedule. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet points are writable?
37 of the 75 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet documentation?
The source is MicroTech II Applied Rooftop Unit Controller Protocol Information (ED 15060-13), revision 2012-05, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15060-13.pdf/.
What are the minimum BACnet points to integrate the Daikin Applied MicroTech II Applied Rooftop Unit Controller?
Start with BV 1455 Occupancy Scheduler Input (Occupied (1) / unoccupied (0) command from the BMS); AV 3610 Emergency Override Mode Flag (Network shutdown: 1 = Off, 0 = Normal); AV 3605 Application Mode (0=Auto, 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly); AV 3655 Occupied Cooling Setpoint (Occupied cooling setpoint); AV 3710 Occupied Heating Setpoint (Occupied heating setpoint); AV 3630 Discharge Air Cooling Setpoint (Discharge air cooling setpoint (DAC units)); AV 3810 Unit Status (Current operating state (enumerated)); AI 115 Discharge Air Temperature (Discharge air temperature); AV 3790 Duct Static Pressure (Duct static pressure, in. w.c); BV 4150 Alarm, Faults: Clear All (Fault alarm active; write 0 to clear).
How do I enable BMS control of the Daikin Applied MicroTech II Applied Rooftop Unit Controller?
Put rocker switch S7 in AUTO and set Control Mode to AUTO at the keypad (password 4545). Leave Occupancy Mode (AV 3825) at Auto and command occupancy with the Occupancy Scheduler Input (BV 1455). Application Mode (AV 3605) = Off or Emergency Override Mode Flag (AV 3610) = Off shuts the unit down. For network setpoint control set Space Setpoint Type (AV 3615) to Keypad/Network.
Does the Daikin Applied MicroTech II Applied Rooftop Unit Controller need a BACnet heartbeat or have a communication timeout?
No BACnet heartbeat point is given; the receive-heartbeat defaults in the doc apply to the LonWorks network variables. A BACnet value written to an out-of-service input (space, outdoor air temperature, building static pressure) is held at its last value if communication is lost.
Can the BMS supply sensor values to the Daikin Applied MicroTech II Applied Rooftop Unit Controller?
Space Temperature (AI 100), Outdoor Air Temperature (AI 125) and Building Static Pressure (AI 1505) accept a BMS value once their Out_Of_Service property is set to TRUE; the controller keeps the last value written if communication is lost. Remote fan capacities are written to AV 3725 / AV 3740 when the matching control flag (AV 3720 / AV 3750) is set to Position.
How do I check these points on the real MicroTech II Applied Rooftop Unit Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: MicroTech II Applied Rooftop Unit Controller Protocol Information · ED 15060-13 · rev. 2012-05. Object names, instances and units are reproduced as published; descriptions are our own.