Rooftop unit / air handler controller · BACnet points list

Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet points list

Updated 4 November 2026

Short answer

The older MicroTech II applied rooftop controller connects to BACnet IP or BACnet MS/TP through a plug-in communication module (LonWorks modules also exist). It exposes a fixed set of standard objects, mostly analog values carrying numbered enumerations, covering unit status, application mode, occupancy, temperatures, duct and building static pressure, fan capacities, zone and discharge setpoints, outdoor air damper, economizer, energy recovery, dehumidification, schedule and alarms.

This page lists 75 BACnet objects for the Daikin Applied MicroTech II Applied Rooftop Unit Controller — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech II Applied Rooftop Unit Controller
Equipment
Rooftop unit / air handler controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
75 (37 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
Last six digits of the main control board serial number
Also known as
MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060
Source document
MicroTech II Applied Rooftop Unit Controller Protocol Information · ED 15060-13 · rev. 2012-05
Download CSV 75 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied MicroTech II Applied Rooftop Unit Controller

Integration in brief

Set switch S7 to AUTO and Control Mode to AUTO at the keypad. With Occupancy Mode left at Auto, the BMS commands occupancy through the Occupancy Scheduler Input BV at a priority higher than 15, turns the unit off with Application Mode or the Emergency Override flag, and writes setpoints at priority 16.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1455Occupancy Scheduler InputOccupied (1) / unoccupied (0) command from the BMSWrite
AV 3610Emergency Override Mode FlagNetwork shutdown: 1 = Off, 0 = NormalWrite
AV 3605Application Mode0=Auto, 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnlyWrite
AV 3655Occupied Cooling SetpointOccupied cooling setpointWrite
AV 3710Occupied Heating SetpointOccupied heating setpointWrite
AV 3630Discharge Air Cooling SetpointDischarge air cooling setpoint (DAC units)Write
AV 3810Unit StatusCurrent operating state (enumerated)Read
AI 115Discharge Air TemperatureDischarge air temperatureRead
AV 3790Duct Static PressureDuct static pressure, in. w.c.Read
BV 4150Alarm, Faults: Clear AllFault alarm active; write 0 to clearWrite

Enable & remote start

Put rocker switch S7 in AUTO and set Control Mode to AUTO at the keypad (password 4545). Leave Occupancy Mode (AV 3825) at Auto and command occupancy with the Occupancy Scheduler Input (BV 1455). Application Mode (AV 3605) = Off or Emergency Override Mode Flag (AV 3610) = Off shuts the unit down. For network setpoint control set Space Setpoint Type (AV 3615) to Keypad/Network.

Heartbeat & communication loss

No BACnet heartbeat point is given; the receive-heartbeat defaults in the doc apply to the LonWorks network variables. A BACnet value written to an out-of-service input (space, outdoor air temperature, building static pressure) is held at its last value if communication is lost.

Sensors & values from the BMS

Space Temperature (AI 100), Outdoor Air Temperature (AI 125) and Building Static Pressure (AI 1505) accept a BMS value once their Out_Of_Service property is set to TRUE; the controller keeps the last value written if communication is lost. Remote fan capacities are written to AV 3725 / AV 3740 when the matching control flag (AV 3720 / AV 3750) is set to Position.

Network setup

Watch out for

Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

75 of 75 shown
Type
Access
Show
Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet Points List
DescriptionStates
AVmin3810Unit StatusUnit operating stateRead0=OffUnoc, 1=OffNet, 2=Off Sw, 3=OffAlm, 4=Calib, 5=Startup, 6=Recirc, 7=FanOnly, 8=Econo, 9=Cooling, 10=MWU, 11=Heating, 12=MinDAT, 13=UnocEcon, 14=UnocFanO, 15=UnocDAT, 16=UnocClg, 17=UnocHtg, 18=Balance, 19=OffMan, 20=ManCtrl
AV3620Cooling CapacityCooling capacity feedback%Read
AV3695Heating CapacityHeating capacity feedback%Read
AV3665Cooling Control StatusCooling control statusRead0=All Clg, 1=Econo, 2=Mech Clg, 3=Off Amb, 4=Off Alarm, 5=Off None, 6=Off Bal, 7=Off Sw, 8=Off Net, 9=Off Man
AV3715Heating Control StatusHeating control statusRead0=HtEna, 1=OffAmb, 2=OffAlarm, 3=OffNone, 4=N/A, 5=OffSw, 6=OffNet, 7=OffMan
AVmin3605Application ModeApplication mode commandWrite0=Auto, 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly
BO265VAV Box OutputVAV box output (MCB BO 12) stateRead0=Off, 1=On
AV3815OccupancyEffective occupancyRead0=Occ, 1=Unocc, 2=Bypass
AV3825Occupancy ModeOccupancy override; leave at Auto normallyWrite0=Occ, 1=Unocc, 2=Bypass, 3=Auto
BVmin1455Occupancy Scheduler InputOccupied/unoccupied command when Occupancy Mode = AutoWrite0=Unoccupied, 1=Occupied
AV3820Occupancy SourceWhere the occupancy command comes fromRead0=None, 1=Int Sched, 2=Net Sched, 3=Occ Mode, 4=Remote Sw, 5=N/A
AVmin3610Emergency Override Mode FlagNetwork shutdown flagWrite0=Norm, 1=Off
AV135Control TemperatureTemperature used for control°FRead
AImin115Discharge Air TemperatureDischarge air temperature°FRead
AI120Return Air TemperatureReturn air temperature°FRead
AI100Space TemperatureSpace temperature (writable with Out_Of_Service set)°FWrite
AI125Outdoor Air TemperatureOutdoor air temperature (writable with Out_Of_Service set)°FWrite
AI130Entering Fan TemperatureEntering fan temperature°FRead
BI160Airflow StatusDischarge airflow switchRead0=Noflo, 1=Flow
BO255Discharge Fan StatusDischarge fan commandRead0=Off, 1=On
BO260Return Fan StatusReturn or exhaust fan commandRead0=Off, 1=On
BO250Fan Operation OutputFans-on relay output (MCB BO 3)Read0=Off, 1=On
AVmin3790Duct Static PressureDuct static pressure (lower of two sensors)in. w.c.Read
AV3730Duct Static Pressure SetpointDuct static pressure setpoint, default 1.00in. w.c.Write
AV3735Discharge Fan CapacityDischarge fan capacity%Read
AI1505Building Static PressureBuilding static pressure (writable with Out_Of_Service set)in. w.c.Write
AV3755Building Static Pressure SetpointBuilding static pressure setpoint, default 0.050in. w.c.Write
AV3745Return Fan CapacityReturn or exhaust fan capacity%Read
AV3640Effective Cooling Enable SetpointZone cooling enable setpoint in use°FRead
AVmin3655Occupied Cooling SetpointOccupied cooling setpoint, default 75°FWrite
AV3600Control Temperature SourceControl temperature sourceWrite0=Return, 1=Space, 2=OAT
AV3795Unoccupied Cooling SetpointUnoccupied cooling setpoint, default 85°FWrite
AV3690Effective Heating Enable SetpointZone heating enable setpoint in use°FRead
AVmin3710Occupied Heating SetpointOccupied heating setpoint, default 70°FWrite
AV3800Unoccupied Heating SetpointUnoccupied heating setpoint, default 55°FWrite
AV3635Effective Cooling Discharge SetpointDischarge cooling setpoint in use°FRead
AVmin3630Discharge Air Cooling SetpointDischarge air cooling setpoint, default 55°FWrite
AV3645Min Discharge Air Cooling SetpointMinimum discharge cooling setpoint (reset)°FWrite
AV3650Max Discharge Air Cooling SetpointMaximum discharge cooling setpoint (reset)°FWrite
AI460Outdoor Air Damper PositionOutdoor air damper position%Read
AV3765Effective Min Outdoor Damper Pos SptMinimum OA damper position in use%Read
AV3780Outdoor Air FlowOutdoor airflow (DesignFlow option)CFMRead
AV3775Outdoor Air Damper Min PositionOutdoor air damper minimum position, default 10%Write
AV3770Min Outdoor Airflow/Damper PositionMinimum OA airflow/damper setting with DesignFlowWrite
AV3785Economizer Changeover MethodEconomizer changeover methodWrite0=Enthalpy, 1=Dry Bulb
AV3760Economizer Changeover Temp SptDry-bulb economizer changeover temperature°FWrite
AV3685Effective Heating Discharge SetpointDischarge heating setpoint in use°FRead
AV3680Discharge Air Heating SetpointDischarge air heating setpoint, default 100°FWrite
AV3805Min Discharge Air Temperature LimitMinimum discharge air temperature limit°FWrite
AV3700Min Discharge Air Heating SetpointMinimum discharge heating setpoint (reset)°FWrite
AV3705Max Discharge Air Heating SetpointMaximum discharge heating setpoint (reset)°FWrite
AV4210Energy Recovery Exhaust TemperatureEnergy recovery exhaust temperature°FRead
AV4205Energy Recovery Supply TemperatureEnergy recovery supply temperature°FRead
AV3675Dehumidification StatusDehumidification activeRead
AI805Relative HumiditySpace relative humidity (optional sensor)%RHRead
AV810Dew Point TemperatureCalculated dew point°FRead
AV3670Relative Humidity Control TypeDehumidification control typeWrite0=None, 1=RelHum, 2=DewPnt
AV3660Relative Humidity SetpointRelative humidity setpoint%RHWrite
AV3625Dew Point SetpointDew point setpoint°FWrite
SCH1460Daily ScheduleKeypad daily schedule objectRead
CAL1465HolidaysKeypad holiday calendarWrite
AV3720Remote Discharge Fan Cap Control FlagDischarge fan capacity control methodWrite0=Duct Pres, 1=Position
AV3725Remote Discharge Fan Capacity SptRemote discharge fan capacity, default 25%Write
AV3750Remote Return Fan Cap. Control FlagReturn fan capacity control methodWrite0=None, 1=Tracking, 2=Bldg Press, 3=Position
AV3740Remote Return Fan Capacity SptRemote return fan capacity, default 25%Write
AV3615Space Setpoint TypeSetpoint source: thermostat or keypad/networkWrite0=Tstat, 1=Keypad/Network
BVmin4150Alarm, Faults: Clear AllFault alarm active; write Normal to clearWrite0=Normal, 1=Alarm
BV4145Alarm, Problems: Clear AllProblem alarm active; write Normal to clearWrite0=Normal, 1=Alarm
BV4140Alarm, Warnings: Clear AllWarning alarm active; write Normal to clearWrite0=Normal, 1=Alarm
AV4862Alarms-Fault Individual NotificationHighest active fault number (100-series software)Read
AV4861Alarms-Problem Individual NotificationHighest active problem number (100-series software)Read
AV4863Alarms-Warning Individual NotificationHighest active warning number (100-series software)Read
AV4870Alarms-Fault Individual NotificationHighest active fault number (200-series software)Read
AV4872Alarms-Problem Individual NotificationHighest active problem number (200-series software)Read
AV4873Alarms-Warning Individual NotificationHighest active warning number (200-series software)Read
Object ID lookup: Daikin Applied MicroTech II Applied Rooftop Unit Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech II Applied Rooftop Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech II Applied Rooftop Unit Controller

How many BACnet points does the Daikin Applied MicroTech II Applied Rooftop Unit Controller have?

This list has 75 BACnet objects: 8 analog inputs, 56 analog values, 1 binary input, 4 binary outputs, 4 binary values, 1 calendar, 1 schedule. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet points are writable?

37 of the 75 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech II Applied Rooftop Unit Controller BACnet documentation?

The source is MicroTech II Applied Rooftop Unit Controller Protocol Information (ED 15060-13), revision 2012-05, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15060-13.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech II Applied Rooftop Unit Controller?

Start with BV 1455 Occupancy Scheduler Input (Occupied (1) / unoccupied (0) command from the BMS); AV 3610 Emergency Override Mode Flag (Network shutdown: 1 = Off, 0 = Normal); AV 3605 Application Mode (0=Auto, 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly); AV 3655 Occupied Cooling Setpoint (Occupied cooling setpoint); AV 3710 Occupied Heating Setpoint (Occupied heating setpoint); AV 3630 Discharge Air Cooling Setpoint (Discharge air cooling setpoint (DAC units)); AV 3810 Unit Status (Current operating state (enumerated)); AI 115 Discharge Air Temperature (Discharge air temperature); AV 3790 Duct Static Pressure (Duct static pressure, in. w.c); BV 4150 Alarm, Faults: Clear All (Fault alarm active; write 0 to clear).

How do I enable BMS control of the Daikin Applied MicroTech II Applied Rooftop Unit Controller?

Put rocker switch S7 in AUTO and set Control Mode to AUTO at the keypad (password 4545). Leave Occupancy Mode (AV 3825) at Auto and command occupancy with the Occupancy Scheduler Input (BV 1455). Application Mode (AV 3605) = Off or Emergency Override Mode Flag (AV 3610) = Off shuts the unit down. For network setpoint control set Space Setpoint Type (AV 3615) to Keypad/Network.

Does the Daikin Applied MicroTech II Applied Rooftop Unit Controller need a BACnet heartbeat or have a communication timeout?

No BACnet heartbeat point is given; the receive-heartbeat defaults in the doc apply to the LonWorks network variables. A BACnet value written to an out-of-service input (space, outdoor air temperature, building static pressure) is held at its last value if communication is lost.

Can the BMS supply sensor values to the Daikin Applied MicroTech II Applied Rooftop Unit Controller?

Space Temperature (AI 100), Outdoor Air Temperature (AI 125) and Building Static Pressure (AI 1505) accept a BMS value once their Out_Of_Service property is set to TRUE; the controller keeps the last value written if communication is lost. Remote fan capacities are written to AV 3725 / AV 3740 when the matching control flag (AV 3720 / AV 3750) is set to Position.

How do I check these points on the real MicroTech II Applied Rooftop Unit Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech II Applied Rooftop Unit Controller Protocol Information · ED 15060-13 · rev. 2012-05. Object names, instances and units are reproduced as published; descriptions are our own.