Chiller controller · BACnet points list
Daikin Applied MicroTech II Chiller Unit Controller BACnet points list
Updated 4 November 2026
The MicroTech II chiller unit controller connects to BACnet MS/TP or BACnet IP/Ethernet through a BACnet communication module (a LonWorks module also exists). The object list is the same for both: enable, mode, cool/heat/ice setpoints and capacity limit commands, water temperatures and flows, chiller status and mode, refrigerant and oil data per compressor, compressor current/power/voltage, run hours and starts, pump status and alarm objects. Which objects return data depends on the chiller model; a model-support matrix in the doc shows which.
This page lists 128 BACnet objects for the Daikin Applied MicroTech II Chiller Unit Controller — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- MicroTech II Chiller Unit Controller
- Equipment
- Chiller controller
- Equipment type
- Chillers
- BACnet objects
- 128 (9 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 3000
- Also known as
- MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied MicroTech II Chiller Unit Controller
Set the chiller's control source to the network (BAS) at the keypad or touch screen, then write ChillerEnable, the operating mode, the cool setpoint and the capacity limit. Read UnitStatus, ActiveMode, water temperatures, capacity and AlarmDigitalOutput, and use ClearAlarm for clearable alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 41 | ChillerEnable | Enable (1) / disable (0) the chiller | Write |
| MO 45 | ChillerOperationMode | Mode command: 1=Ice, 2=Cool, 3=Heat | Write |
| AO 29 | NetworkCoolTempSetpoint | Leaving chilled water setpoint | Write |
| AO 32 | NetworkCapacityLimitPct | Capacity limit from the BMS, % | Write |
| MI 43 | UnitStatus | Off/Start/Run/Pre-shutdown/Service | Read |
| BI 38 | ChillerLocalRemote | Reads Remote (0) when network control is allowed | Read |
| AI 2 | LvgEvapWaterTempUnit | Leaving chilled water temperature | Read |
| AI 1 | EntEvapWaterTemp | Entering chilled water temperature | Read |
| AI 9 | ChillerCapacity | Running capacity, % | Read |
| BI 40 | AlarmDigitalOutput | Any active alarm | Read |
Enable & remote start
Disable the chiller, set the protocol to the BAS network at the user interface, then set the setpoint source to Network (on centrifugals, Control Source = BAS on the SETPOINTS/MODE screen, password 2001; other models use the passwords in the doc's table). Re-enable the chiller; ChillerEnable (BV 41) then starts and stops it.
Heartbeat & communication loss
The receive-heartbeat and default-value behaviour described in the doc applies to the LonWorks interface only. No BACnet heartbeat point is listed.
Network setup
- MS/TP defaults: device instance 3000, MAC 18, 38400 baud, Max Master 127, Max Info Frames 20; set with Daikin's BACnet Configuration Tool and cycle power afterwards.
- IP module defaults: 172.16.5.8, mask 255.255.0.0, UDP 47808, device instance 3000; settings are changed in the module's web configuration interface (IM 837).
- Device name is MTII Chiller UC plus the device instance; changing the instance changes every object's full reference.
- Use CompSelect (MO 46) and PumpSelect (MO 47) to choose which compressor or pump the 'selected' objects report.
Watch out for
- ClearAlarm (BV 42) can't clear shutdown faults on centrifugals such as low evaporator pressure, high condenser pressure, low oil pressure, freeze protection and high motor temperature; on other models only the flow-loss alarm can be cleared remotely.
- Run-hour objects report hours divided by 10.
- The heat setpoint is ignored while the chiller is in cool mode.
- Many objects only return data on certain chiller types; check the model-support table before mapping.
Daikin Applied MicroTech II Chiller Unit Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 7 | ActiveLvgWaterTarget | Active Setpoint | °F | Read | |
| AImin | 9 | ChillerCapacity | Actual Capacity | % | Read | |
| AI | 56 | Comp1ActualRPM | Actual RPM, compressor 1 | RPM | Read | |
| AI | 60 | Comp2ActualRPM | Actual RPM, compressor 2 | RPM | Read | |
| AI | 8 | ActiveCapacityLimit | Capacity Limit Output | % | Read | |
| AI | 67 | TotalChillerKW | Total chiller kW (doc prints range as 0-160%) | Read | ||
| AI | 88 | Comp2ActiveCapLimit | Compressor 2 Active Capacity Limit | % | Read | |
| AI | 80 | Comp2Speed | Compressor 2 VFD Speed | % | Read | |
| AI | 51 | Current | Compressor Current, compressor chosen by CompSelect | A | Read | |
| AI | 76 | Comp2Current | Compressor Current, compressor 2 | A | Read | |
| AI | 95 | Comp3Current | Compressor Current, compressor 3 | A | Read | |
| AI | 103 | Comp4Current | Compressor Current, compressor 4 | A | Read | |
| AI | 111 | Comp5Current | Compressor Current, compressor 5 | A | Read | |
| AI | 117 | Comp6Current | Compressor Current, compressor 6 | A | Read | |
| AI | 18 | DischargeTemp | Compressor Discharge Temperature, compressor chosen by CompSelect | °F | Read | |
| AI | 72 | Comp2DischargeTmp | Compressor Discharge Temperature, compressor 2 | °F | Read | |
| AI | 24 | CompMotorCurrentPercent | Compressor Percent RLA, compressor chosen by CompSelect | % | Read | |
| AI | 75 | Comp2CurrentPercent | Compressor Percent RLA, compressor 2 | % | Read | |
| AI | 94 | Comp3CurrentPercent | Compressor Percent RLA, compressor 3 | % | Read | |
| AI | 102 | Comp4CurrentPercent | Compressor Percent RLA, compressor 4 | % | Read | |
| AI | 110 | Comp5CurrentPercent | Compressor Percent RLA, compressor 5 | % | Read | |
| AI | 116 | Comp6CurrentPercent | Compressor Percent RLA, compressor 6 | % | Read | |
| AI | 54 | Kilowatts | Compressor Power, compressor chosen by CompSelect | kW | Read | |
| AI | 77 | Comp2Kilowatts | Compressor Power, compressor 2 | kW | Read | |
| AI | 96 | Comp3Kilowatts | Compressor Power, compressor 3 | kW | Read | |
| AI | 104 | Comp4Kilowatts | Compressor Power, compressor 4 | kW | Read | |
| AI | 112 | Comp5Kilowatts | Compressor Power, compressor 5 | kW | Read | |
| AI | 118 | Comp6Kilowatts | Compressor Power, compressor 6 | kW | Read | |
| AI | 26 | CompHours | Compressor Run Hours, compressor chosen by CompSelect (reads hours/10) | h | Read | |
| AI | 93 | Comp2Hours | Compressor Run Hours, compressor 2 (reads hours/10) | h | Read | |
| AI | 101 | Comp3Hours | Compressor Run Hours, compressor 3 (reads hours/10) | h | Read | |
| AI | 109 | Comp4Hours | Compressor Run Hours, compressor 4 (reads hours/10) | h | Read | |
| AI | 25 | CompStarts | Compressor Starts, compressor chosen by CompSelect | Read | ||
| AI | 92 | Comp2Starts | Compressor Starts, compressor 2 | Read | ||
| AI | 100 | Comp3Starts | Compressor Starts, compressor 3 | Read | ||
| AI | 108 | Comp4Starts | Compressor Starts, compressor 4 | Read | ||
| AI | 123 | CompressorStatus | Compressor Status, compressor chosen by CompSelect | Read | 0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube | |
| AI | 91 | Comp2Status | Compressor Status, compressor 2 | Read | 0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube | |
| AI | 99 | Comp3Status | Compressor Status, compressor 3 | Read | 0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube | |
| AI | 107 | Comp4Status | Compressor Status, compressor 4 | Read | 0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube | |
| AI | 115 | Comp5Status | Compressor Status, compressor 5 | Read | 0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube | |
| AI | 121 | Comp6Status | Compressor Status, compressor 6 | Read | 0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube | |
| AI | 15 | SuctionTemp | Compressor Suction Line Temperature, compressor chosen by CompSelect | °F | Read | |
| AI | 69 | Comp2SuctTemp | Compressor Suction Line Temperature, compressor 2 | °F | Read | |
| AI | 52 | Voltage | Compressor Voltage, compressor chosen by CompSelect | V | Read | |
| AI | 79 | Comp2Voltage | Compressor Voltage, compressor 2 | V | Read | |
| AI | 98 | Comp3Voltage | Compressor Voltage, compressor 3 | V | Read | |
| AI | 106 | Comp4Voltage | Compressor Voltage, compressor 4 | V | Read | |
| AI | 114 | Comp5Voltage | Compressor Voltage, compressor 5 | V | Read | |
| AI | 120 | Comp6Voltage | Compressor Voltage, compressor 6 | V | Read | |
| AI | 3 | EntCondWaterTemp | Condenser Entering Water Temperature | °F | Read | |
| AI | 4 | LvgCondWaterTemp | Condenser Leaving Water Temperature | °F | Read | |
| AI | 28 | CondPumpOperHours | Condenser Pump Run Hours, pump chosen by PumpSelect (reads hours/10) | h | Read | |
| AI | 90 | CondPmp2Hrs | Condenser Pump Run Hours, pump 2 (reads hours/10) | h | Read | |
| AI | 16 | CondPressure | Condenser Refrigerant Pressure, compressor chosen by CompSelect | psi | Read | |
| AI | 74 | Comp2CondPress | Condenser Refrigerant Pressure, compressor 2 | psi | Read | |
| AI | 17 | CondSatTemp | Condenser Saturated Refrigerant Temperature, compressor chosen by CompSelect | °F | Read | |
| AI | 73 | Comp2CondSatTemp | Condenser Saturated Refrigerant Temperature, compressor 2 | °F | Read | |
| AI | 50 | CondWaterFlowRate | Condenser Water Flow Rate | GPM | Read | |
| AI | 63 | Comp1DesignRPM | Design RPM, compressor 1 | RPM | Read | |
| AI | 64 | Comp2DesignRPM | Design RPM, compressor 2 | RPM | Read | |
| AImin | 1 | EntEvapWaterTemp | Evaporator Entering Water Temperature | °F | Read | |
| AImin | 2 | LvgEvapWaterTempUnit | Evaporator Leaving Water Temperature for Unit | °F | Read | |
| AI | 23 | LvgEvapWaterTempComp | Evaporator Leaving Water Temperature for Compressor, compressor chosen by CompSelect | °F | Read | |
| AI | 68 | Comp2EvapLvgWTmp | Evaporator Leaving Water Temperature for Compressor, compressor 2 | °F | Read | |
| AI | 27 | EvapPumpOperHours | Evaporator Pump Run Hours, pump chosen by PumpSelect (reads hours/10) | h | Read | |
| AI | 89 | EvapPmp2Hrs | Evaporator Pump Run Hours, pump 2 (reads hours/10) | h | Read | |
| AI | 13 | EvapPressure | Evaporator Refrigerant Pressure, compressor chosen by CompSelect | psi | Read | |
| AI | 71 | Comp2EvapPress | Evaporator Refrigerant Pressure, compressor 2 | psi | Read | |
| AI | 14 | EvapSatTemp | Evaporator Saturated Refrigerant Temperature, compressor chosen by CompSelect | °F | Read | |
| AI | 70 | Comp2EvapSatRTmp | Evaporator Saturated Refrigerant Temperature, compressor 2 | °F | Read | |
| AI | 49 | EvapWaterFlowRate | Evaporator Water Flow Rate | GPM | Read | |
| AI | 5 | HeatRecEntWaterTemp | Heat Recovery Entering Water Temperature | °F | Read | |
| AI | 6 | HeatRecLvgWaterTemp | Heat Recovery Leaving Water Temperature | °F | Read | |
| AI | 58 | Comp1IGVPercentOpen | IGV Percentage Open, compressor 1 | % | Read | |
| AI | 62 | Comp2IGVPercentOpen | IGV Percentage Open, compressor 2 | % | Read | |
| AI | 66 | Comp1InverterTmp | Inverter Temperature, compressor 1 | °F | Read | |
| AI | 87 | Comp2InverterTmp | Inverter Temperature, compressor 2 | °F | Read | |
| AI | 12 | LiquidLinePress | Liquid Line Refrigerant Pressure | psi | Read | |
| AI | 11 | LiquidLineTemp | Liquid Line Refrigerant Temperature, compressor chosen by CompSelect | °F | Read | |
| AI | 85 | Comp2LiqLineTemp | Liquid Line Refrigerant Temperature, compressor 2 | °F | Read | |
| AI | 55 | Comp1MaxRPM | Maximum RPM, compressor 1 | RPM | Read | |
| AI | 59 | Comp2MaxRPM | Maximum RPM, compressor 2 | RPM | Read | |
| AI | 57 | Comp1MinRPM | Minimum RPM, compressor 1 | RPM | Read | |
| AI | 61 | Comp2MinRPM | Minimum RPM, compressor 2 | RPM | Read | |
| AI | 65 | Comp1MotorCavityTmp | Motor Cavity Temperature, compressor 1 | °F | Read | |
| AI | 86 | Comp2MotorCavityTmp | Motor Cavity Temperature, compressor 2 | °F | Read | |
| AI | 19 | OilFeedPressure | Oil Feed Pressure, compressor chosen by CompSelect | psi | Read | |
| AI | 81 | Comp2OilFeedPress | Oil Feed Pressure, compressor 2 | psi | Read | |
| AI | 21 | OilFeedTemp | Oil Feed Temperature, compressor chosen by CompSelect | °F | Read | |
| AI | 83 | Comp2OilFeedTemp | Oil Feed Temperature, compressor 2 | °F | Read | |
| AI | 20 | OilSumpPressure | Oil Sump Pressure, compressor chosen by CompSelect | psi | Read | |
| AI | 82 | Comp2OilFeedPress | Oil Sump Pressure, compressor 2 | psi | Read | |
| AI | 22 | OilSumpTemp | Oil Sump Temperature, compressor chosen by CompSelect | °F | Read | |
| AI | 84 | Comp2OilSumpTemp | Oil Sump Temperature, compressor 2 | °F | Read | |
| AI | 10 | OutdoorAirTemp | Outdoor Air Temperature | °F | Read | |
| AI | 53 | PowerFactor | Power factor x100, compressor chosen by CompSelect | Read | ||
| AI | 78 | Comp2PowerFactor | Power factor x100, compressor 2 | Read | ||
| AI | 97 | Comp3PowerFactor | Power factor x100, compressor 3 | Read | ||
| AI | 105 | Comp4PowerFactor | Power factor x100, compressor 4 | Read | ||
| AI | 113 | Comp5PowerFactor | Power factor x100, compressor 5 | Read | ||
| AI | 119 | Comp6PowerFactor | Power factor x100, compressor 6 | Read | ||
| AOmin | 32 | NetworkCapacityLimitPct | Capacity Limit Setpoint | % | Write | |
| AOmin | 29 | NetworkCoolTempSetpoint | Cool Setpoint | °F | Write | |
| AO | 31 | NetworkHeatTempSetpoint | Heat Setpoint | °F | Write | |
| AO | 30 | NetworkIceTempSetpoint | Ice Setpoint | °F | Write | |
| BImin | 40 | AlarmDigitalOutput | Alarm Digital Output | Read | 0=No Alarm, 1=Alarm | |
| BI | 39 | ChillerLimited | Chiller Limited | Read | 0=Not Limited (Inactive), 1=Limited (Active) | |
| BImin | 38 | ChillerLocalRemote | Chiller Local/Remote | Read | 0=Remote, 1=Local | |
| BI | 35 | CondWaterFlowStatus | Condenser Flow Switch Status | Read | 0=No Flow (Inactive), 1=Flow (Active) | |
| BI | 37 | CondPumpState | Condenser Water Pump Status | Read | 0=OFF (Inactive), 1=ON (Active) | |
| BI | 34 | EvapWaterFlowStatus | Evaporator Flow Switch Status | Read | 0=No Flow (Inactive), 1=Flow (Active) | |
| BI | 36 | EvapPumpState | Evaporator Water Pump Status | Read | 0=OFF (Inactive), 1=ON (Active) | |
| BI | 33 | UnitOFF | Run Enabled | Read | 0=Off (Inactive), 1=Run Allowed (Active) | |
| BVmin | 41 | ChillerEnable | Chiller Enable | Write | 0=OFF (Disable), 1=ON (Enable) | |
| BV | 42 | ClearAlarm | Clear Alarm | Write | 0=Normal, 1=Clear Alarm | |
| MI | 44 | ActiveMode | Chiller Mode Output | Read | 1=Ice, 2=Cool, 3=Heat | |
| MImin | 43 | UnitStatus | Chiller Status | Read | 1=Off, 2=Start, 3=Run, 4=Pre-shutdown, 5=Service | |
| MI | 48 | DaikinChillerType | Chiller Type | Read | 1=AGZS, 2=AGZD, 3=WGZD/TGZD, 4=WSC/WDC, 5=AGSU, 6=ACZS, 7=ACZD, 8=WMC, 9=WGSD, 10=AGSD, 11=AGZS, 12=AGZDU, 13=WGZU, 14=ACZSU, 15=ACZDU | |
| MOmin | 45 | ChillerOperationMode | Chiller Mode Setpoint | Write | 1=Ice, 2=Cool, 3=Heat | |
| MO | 46 | CompSelect | Compressor Select | Write | 1-6 = compressor number | |
| MO | 47 | PumpSelect | Pump Select | Write | 1=Pump 1, 2=Pump 2 | |
| AI | 901 | AIFaultAlarm | Fault Alarms index number (analog form) | Read | ||
| MI | 901 | MSIFaultAlarm | Fault Alarms index number (multistate form) | Read | ||
| AI | 900 | AIProblemAlarm | Problem Alarms index number (analog form) | Read | ||
| MI | 900 | MSIProblemAlarm | Problem Alarms index number (multistate form) | Read | ||
| AI | 902 | AIWarningAlarm | Warning Alarms index number (analog form) | Read | ||
| MI | 902 | MSIWarningAlarm | Warning Alarms index number (multistate form) | Read |
No points match these filters.
Object ID lookup: Daikin Applied MicroTech II Chiller Unit Controller point IDs by name
AI7ActiveLvgWaterTargetAI9ChillerCapacityAI56Comp1ActualRPMAI60Comp2ActualRPMAI8ActiveCapacityLimitAI67TotalChillerKWAI88Comp2ActiveCapLimitAI80Comp2SpeedAI51CurrentAI76Comp2CurrentAI95Comp3CurrentAI103Comp4CurrentAI111Comp5CurrentAI117Comp6CurrentAI18DischargeTempAI72Comp2DischargeTmpAI24CompMotorCurrentPercentAI75Comp2CurrentPercentAI94Comp3CurrentPercentAI102Comp4CurrentPercentAI110Comp5CurrentPercentAI116Comp6CurrentPercentAI54KilowattsAI77Comp2KilowattsAI96Comp3KilowattsAI104Comp4KilowattsAI112Comp5KilowattsAI118Comp6KilowattsAI26CompHoursAI93Comp2HoursAI101Comp3HoursAI109Comp4HoursAI25CompStartsAI92Comp2StartsAI100Comp3StartsAI108Comp4StartsAI123CompressorStatusAI91Comp2StatusAI99Comp3StatusAI107Comp4StatusAI115Comp5StatusAI121Comp6StatusAI15SuctionTempAI69Comp2SuctTempAI52VoltageAI79Comp2VoltageAI98Comp3VoltageAI106Comp4VoltageAI114Comp5VoltageAI120Comp6VoltageAI3EntCondWaterTempAI4LvgCondWaterTempAI28CondPumpOperHoursAI90CondPmp2HrsAI16CondPressureAI74Comp2CondPressAI17CondSatTempAI73Comp2CondSatTempAI50CondWaterFlowRateAI63Comp1DesignRPMAI64Comp2DesignRPMAI1EntEvapWaterTempAI2LvgEvapWaterTempUnitAI23LvgEvapWaterTempCompAI68Comp2EvapLvgWTmpAI27EvapPumpOperHoursAI89EvapPmp2HrsAI13EvapPressureAI71Comp2EvapPressAI14EvapSatTempAI70Comp2EvapSatRTmpAI49EvapWaterFlowRateAI5HeatRecEntWaterTempAI6HeatRecLvgWaterTempAI58Comp1IGVPercentOpenAI62Comp2IGVPercentOpenAI66Comp1InverterTmpAI87Comp2InverterTmpAI12LiquidLinePressAI11LiquidLineTempAI85Comp2LiqLineTempAI55Comp1MaxRPMAI59Comp2MaxRPMAI57Comp1MinRPMAI61Comp2MinRPMAI65Comp1MotorCavityTmpAI86Comp2MotorCavityTmpAI19OilFeedPressureAI81Comp2OilFeedPressAI21OilFeedTempAI83Comp2OilFeedTempAI20OilSumpPressureAI82Comp2OilFeedPressAI22OilSumpTempAI84Comp2OilSumpTempAI10OutdoorAirTempAI53PowerFactorAI78Comp2PowerFactorAI97Comp3PowerFactorAI105Comp4PowerFactorAI113Comp5PowerFactorAI119Comp6PowerFactorAO32NetworkCapacityLimitPctAO29NetworkCoolTempSetpointAO31NetworkHeatTempSetpointAO30NetworkIceTempSetpointBI40AlarmDigitalOutputBI39ChillerLimitedBI38ChillerLocalRemoteBI35CondWaterFlowStatusBI37CondPumpStateBI34EvapWaterFlowStatusBI36EvapPumpStateBI33UnitOFFBV41ChillerEnableBV42ClearAlarmMI44ActiveModeMI43UnitStatusMI48DaikinChillerTypeMO45ChillerOperationModeMO46CompSelectMO47PumpSelectAI901AIFaultAlarmMI901MSIFaultAlarmAI900AIProblemAlarmMI900MSIProblemAlarmAI902AIWarningAlarmMI902MSIWarningAlarm
Integration notes
- ED 15062-9 (BACnet MS/TP + LonWorks) and ED 15100-5 (BACnet IP/Ethernet) print the same 128 objects with the same instances and object names; the IP doc adds a Variable Index column for the web configuration interface.
- Points that ask for 'the selected compressor' or 'the selected pump' return data for whatever CompSelect (MO 46) or PumpSelect (MO 47) is set to; other compressors and pumps also have their own fixed objects.
- Run-hour values (compressor and pump hours) must be multiplied by 10 to get actual hours.
- AI 82 (oil sump pressure, compressor 2) is printed with the object name Comp2OilFeedPress, the same as AI 81; kept as printed.
- Ranges list both English and SI units; English units are shown here.
- Object availability depends on chiller model (centrifugal, scroll, screw, Turbocor/WMC).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech II Chiller Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied MicroTech II Chiller Unit Controller
How many BACnet points does the Daikin Applied MicroTech II Chiller Unit Controller have?
This list has 128 BACnet objects: 105 analog inputs, 4 analog outputs, 8 binary inputs, 2 binary values, 6 multi-state inputs, 3 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied MicroTech II Chiller Unit Controller BACnet points are writable?
9 of the 128 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied MicroTech II Chiller Unit Controller BACnet documentation?
The source is MicroTech II Chiller Unit Controller Protocol Information (LonWorks, BACnet MS/TP) (ED 15062-9), revision 2022-08, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/Daikin_ED_15062-9_MTII_Chiller_Unit_Controller_Protocol_Info_Tech_Sheet.pdf/.
What are the minimum BACnet points to integrate the Daikin Applied MicroTech II Chiller Unit Controller?
Start with BV 41 ChillerEnable (Enable (1) / disable (0) the chiller); MO 45 ChillerOperationMode (Mode command: 1=Ice, 2=Cool, 3=Heat); AO 29 NetworkCoolTempSetpoint (Leaving chilled water setpoint); AO 32 NetworkCapacityLimitPct (Capacity limit from the BMS, %); MI 43 UnitStatus (Off/Start/Run/Pre-shutdown/Service); BI 38 ChillerLocalRemote (Reads Remote (0) when network control is allowed); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); AI 1 EntEvapWaterTemp (Entering chilled water temperature); AI 9 ChillerCapacity (Running capacity, %); BI 40 AlarmDigitalOutput (Any active alarm).
How do I enable BMS control of the Daikin Applied MicroTech II Chiller Unit Controller?
Disable the chiller, set the protocol to the BAS network at the user interface, then set the setpoint source to Network (on centrifugals, Control Source = BAS on the SETPOINTS/MODE screen, password 2001; other models use the passwords in the doc's table). Re-enable the chiller; ChillerEnable (BV 41) then starts and stops it.
Does the Daikin Applied MicroTech II Chiller Unit Controller need a BACnet heartbeat or have a communication timeout?
The receive-heartbeat and default-value behaviour described in the doc applies to the LonWorks interface only. No BACnet heartbeat point is listed.
How do I check these points on the real MicroTech II Chiller Unit Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: MicroTech II Chiller Unit Controller Protocol Information (LonWorks, BACnet MS/TP) · ED 15062-9 · rev. 2022-08. Object names, instances and units are reproduced as published; descriptions are our own.