Chiller controller · BACnet points list

Daikin Applied MicroTech II Chiller Unit Controller BACnet points list

Updated 4 November 2026

Short answer

The MicroTech II chiller unit controller connects to BACnet MS/TP or BACnet IP/Ethernet through a BACnet communication module (a LonWorks module also exists). The object list is the same for both: enable, mode, cool/heat/ice setpoints and capacity limit commands, water temperatures and flows, chiller status and mode, refrigerant and oil data per compressor, compressor current/power/voltage, run hours and starts, pump status and alarm objects. Which objects return data depends on the chiller model; a model-support matrix in the doc shows which.

This page lists 128 BACnet objects for the Daikin Applied MicroTech II Chiller Unit Controller — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech II Chiller Unit Controller
Equipment
Chiller controller
Equipment type
Chillers
BACnet objects
128 (9 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
3000
Also known as
MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100
Source document
MicroTech II Chiller Unit Controller Protocol Information (LonWorks, BACnet MS/TP) · ED 15062-9 · rev. 2022-08
Download CSV 128 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied MicroTech II Chiller Unit Controller

Integration in brief

Set the chiller's control source to the network (BAS) at the keypad or touch screen, then write ChillerEnable, the operating mode, the cool setpoint and the capacity limit. Read UnitStatus, ActiveMode, water temperatures, capacity and AlarmDigitalOutput, and use ClearAlarm for clearable alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 41ChillerEnableEnable (1) / disable (0) the chillerWrite
MO 45ChillerOperationModeMode command: 1=Ice, 2=Cool, 3=HeatWrite
AO 29NetworkCoolTempSetpointLeaving chilled water setpointWrite
AO 32NetworkCapacityLimitPctCapacity limit from the BMS, %Write
MI 43UnitStatusOff/Start/Run/Pre-shutdown/ServiceRead
BI 38ChillerLocalRemoteReads Remote (0) when network control is allowedRead
AI 2LvgEvapWaterTempUnitLeaving chilled water temperatureRead
AI 1EntEvapWaterTempEntering chilled water temperatureRead
AI 9ChillerCapacityRunning capacity, %Read
BI 40AlarmDigitalOutputAny active alarmRead

Enable & remote start

Disable the chiller, set the protocol to the BAS network at the user interface, then set the setpoint source to Network (on centrifugals, Control Source = BAS on the SETPOINTS/MODE screen, password 2001; other models use the passwords in the doc's table). Re-enable the chiller; ChillerEnable (BV 41) then starts and stops it.

Heartbeat & communication loss

The receive-heartbeat and default-value behaviour described in the doc applies to the LonWorks interface only. No BACnet heartbeat point is listed.

Network setup

Watch out for

Daikin Applied MicroTech II Chiller Unit Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

128 of 128 shown
Type
Access
Show
Daikin Applied MicroTech II Chiller Unit Controller BACnet Points List
DescriptionStates
AI7ActiveLvgWaterTargetActive Setpoint°FRead
AImin9ChillerCapacityActual Capacity%Read
AI56Comp1ActualRPMActual RPM, compressor 1RPMRead
AI60Comp2ActualRPMActual RPM, compressor 2RPMRead
AI8ActiveCapacityLimitCapacity Limit Output%Read
AI67TotalChillerKWTotal chiller kW (doc prints range as 0-160%)Read
AI88Comp2ActiveCapLimitCompressor 2 Active Capacity Limit%Read
AI80Comp2SpeedCompressor 2 VFD Speed%Read
AI51CurrentCompressor Current, compressor chosen by CompSelectARead
AI76Comp2CurrentCompressor Current, compressor 2ARead
AI95Comp3CurrentCompressor Current, compressor 3ARead
AI103Comp4CurrentCompressor Current, compressor 4ARead
AI111Comp5CurrentCompressor Current, compressor 5ARead
AI117Comp6CurrentCompressor Current, compressor 6ARead
AI18DischargeTempCompressor Discharge Temperature, compressor chosen by CompSelect°FRead
AI72Comp2DischargeTmpCompressor Discharge Temperature, compressor 2°FRead
AI24CompMotorCurrentPercentCompressor Percent RLA, compressor chosen by CompSelect%Read
AI75Comp2CurrentPercentCompressor Percent RLA, compressor 2%Read
AI94Comp3CurrentPercentCompressor Percent RLA, compressor 3%Read
AI102Comp4CurrentPercentCompressor Percent RLA, compressor 4%Read
AI110Comp5CurrentPercentCompressor Percent RLA, compressor 5%Read
AI116Comp6CurrentPercentCompressor Percent RLA, compressor 6%Read
AI54KilowattsCompressor Power, compressor chosen by CompSelectkWRead
AI77Comp2KilowattsCompressor Power, compressor 2kWRead
AI96Comp3KilowattsCompressor Power, compressor 3kWRead
AI104Comp4KilowattsCompressor Power, compressor 4kWRead
AI112Comp5KilowattsCompressor Power, compressor 5kWRead
AI118Comp6KilowattsCompressor Power, compressor 6kWRead
AI26CompHoursCompressor Run Hours, compressor chosen by CompSelect (reads hours/10)hRead
AI93Comp2HoursCompressor Run Hours, compressor 2 (reads hours/10)hRead
AI101Comp3HoursCompressor Run Hours, compressor 3 (reads hours/10)hRead
AI109Comp4HoursCompressor Run Hours, compressor 4 (reads hours/10)hRead
AI25CompStartsCompressor Starts, compressor chosen by CompSelectRead
AI92Comp2StartsCompressor Starts, compressor 2Read
AI100Comp3StartsCompressor Starts, compressor 3Read
AI108Comp4StartsCompressor Starts, compressor 4Read
AI123CompressorStatusCompressor Status, compressor chosen by CompSelectRead0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube
AI91Comp2StatusCompressor Status, compressor 2Read0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube
AI99Comp3StatusCompressor Status, compressor 3Read0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube
AI107Comp4StatusCompressor Status, compressor 4Read0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube
AI115Comp5StatusCompressor Status, compressor 5Read0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube
AI121Comp6StatusCompressor Status, compressor 6Read0=Off, 1=Start Oil Pump, 2=Interlock/Prelube, 3=Run, 4=Shutdown, 5=Postlube
AI15SuctionTempCompressor Suction Line Temperature, compressor chosen by CompSelect°FRead
AI69Comp2SuctTempCompressor Suction Line Temperature, compressor 2°FRead
AI52VoltageCompressor Voltage, compressor chosen by CompSelectVRead
AI79Comp2VoltageCompressor Voltage, compressor 2VRead
AI98Comp3VoltageCompressor Voltage, compressor 3VRead
AI106Comp4VoltageCompressor Voltage, compressor 4VRead
AI114Comp5VoltageCompressor Voltage, compressor 5VRead
AI120Comp6VoltageCompressor Voltage, compressor 6VRead
AI3EntCondWaterTempCondenser Entering Water Temperature°FRead
AI4LvgCondWaterTempCondenser Leaving Water Temperature°FRead
AI28CondPumpOperHoursCondenser Pump Run Hours, pump chosen by PumpSelect (reads hours/10)hRead
AI90CondPmp2HrsCondenser Pump Run Hours, pump 2 (reads hours/10)hRead
AI16CondPressureCondenser Refrigerant Pressure, compressor chosen by CompSelectpsiRead
AI74Comp2CondPressCondenser Refrigerant Pressure, compressor 2psiRead
AI17CondSatTempCondenser Saturated Refrigerant Temperature, compressor chosen by CompSelect°FRead
AI73Comp2CondSatTempCondenser Saturated Refrigerant Temperature, compressor 2°FRead
AI50CondWaterFlowRateCondenser Water Flow RateGPMRead
AI63Comp1DesignRPMDesign RPM, compressor 1RPMRead
AI64Comp2DesignRPMDesign RPM, compressor 2RPMRead
AImin1EntEvapWaterTempEvaporator Entering Water Temperature°FRead
AImin2LvgEvapWaterTempUnitEvaporator Leaving Water Temperature for Unit°FRead
AI23LvgEvapWaterTempCompEvaporator Leaving Water Temperature for Compressor, compressor chosen by CompSelect°FRead
AI68Comp2EvapLvgWTmpEvaporator Leaving Water Temperature for Compressor, compressor 2°FRead
AI27EvapPumpOperHoursEvaporator Pump Run Hours, pump chosen by PumpSelect (reads hours/10)hRead
AI89EvapPmp2HrsEvaporator Pump Run Hours, pump 2 (reads hours/10)hRead
AI13EvapPressureEvaporator Refrigerant Pressure, compressor chosen by CompSelectpsiRead
AI71Comp2EvapPressEvaporator Refrigerant Pressure, compressor 2psiRead
AI14EvapSatTempEvaporator Saturated Refrigerant Temperature, compressor chosen by CompSelect°FRead
AI70Comp2EvapSatRTmpEvaporator Saturated Refrigerant Temperature, compressor 2°FRead
AI49EvapWaterFlowRateEvaporator Water Flow RateGPMRead
AI5HeatRecEntWaterTempHeat Recovery Entering Water Temperature°FRead
AI6HeatRecLvgWaterTempHeat Recovery Leaving Water Temperature°FRead
AI58Comp1IGVPercentOpenIGV Percentage Open, compressor 1%Read
AI62Comp2IGVPercentOpenIGV Percentage Open, compressor 2%Read
AI66Comp1InverterTmpInverter Temperature, compressor 1°FRead
AI87Comp2InverterTmpInverter Temperature, compressor 2°FRead
AI12LiquidLinePressLiquid Line Refrigerant PressurepsiRead
AI11LiquidLineTempLiquid Line Refrigerant Temperature, compressor chosen by CompSelect°FRead
AI85Comp2LiqLineTempLiquid Line Refrigerant Temperature, compressor 2°FRead
AI55Comp1MaxRPMMaximum RPM, compressor 1RPMRead
AI59Comp2MaxRPMMaximum RPM, compressor 2RPMRead
AI57Comp1MinRPMMinimum RPM, compressor 1RPMRead
AI61Comp2MinRPMMinimum RPM, compressor 2RPMRead
AI65Comp1MotorCavityTmpMotor Cavity Temperature, compressor 1°FRead
AI86Comp2MotorCavityTmpMotor Cavity Temperature, compressor 2°FRead
AI19OilFeedPressureOil Feed Pressure, compressor chosen by CompSelectpsiRead
AI81Comp2OilFeedPressOil Feed Pressure, compressor 2psiRead
AI21OilFeedTempOil Feed Temperature, compressor chosen by CompSelect°FRead
AI83Comp2OilFeedTempOil Feed Temperature, compressor 2°FRead
AI20OilSumpPressureOil Sump Pressure, compressor chosen by CompSelectpsiRead
AI82Comp2OilFeedPressOil Sump Pressure, compressor 2psiRead
AI22OilSumpTempOil Sump Temperature, compressor chosen by CompSelect°FRead
AI84Comp2OilSumpTempOil Sump Temperature, compressor 2°FRead
AI10OutdoorAirTempOutdoor Air Temperature°FRead
AI53PowerFactorPower factor x100, compressor chosen by CompSelectRead
AI78Comp2PowerFactorPower factor x100, compressor 2Read
AI97Comp3PowerFactorPower factor x100, compressor 3Read
AI105Comp4PowerFactorPower factor x100, compressor 4Read
AI113Comp5PowerFactorPower factor x100, compressor 5Read
AI119Comp6PowerFactorPower factor x100, compressor 6Read
AOmin32NetworkCapacityLimitPctCapacity Limit Setpoint%Write
AOmin29NetworkCoolTempSetpointCool Setpoint°FWrite
AO31NetworkHeatTempSetpointHeat Setpoint°FWrite
AO30NetworkIceTempSetpointIce Setpoint°FWrite
BImin40AlarmDigitalOutputAlarm Digital OutputRead0=No Alarm, 1=Alarm
BI39ChillerLimitedChiller LimitedRead0=Not Limited (Inactive), 1=Limited (Active)
BImin38ChillerLocalRemoteChiller Local/RemoteRead0=Remote, 1=Local
BI35CondWaterFlowStatusCondenser Flow Switch StatusRead0=No Flow (Inactive), 1=Flow (Active)
BI37CondPumpStateCondenser Water Pump StatusRead0=OFF (Inactive), 1=ON (Active)
BI34EvapWaterFlowStatusEvaporator Flow Switch StatusRead0=No Flow (Inactive), 1=Flow (Active)
BI36EvapPumpStateEvaporator Water Pump StatusRead0=OFF (Inactive), 1=ON (Active)
BI33UnitOFFRun EnabledRead0=Off (Inactive), 1=Run Allowed (Active)
BVmin41ChillerEnableChiller EnableWrite0=OFF (Disable), 1=ON (Enable)
BV42ClearAlarmClear AlarmWrite0=Normal, 1=Clear Alarm
MI44ActiveModeChiller Mode OutputRead1=Ice, 2=Cool, 3=Heat
MImin43UnitStatusChiller StatusRead1=Off, 2=Start, 3=Run, 4=Pre-shutdown, 5=Service
MI48DaikinChillerTypeChiller TypeRead1=AGZS, 2=AGZD, 3=WGZD/TGZD, 4=WSC/WDC, 5=AGSU, 6=ACZS, 7=ACZD, 8=WMC, 9=WGSD, 10=AGSD, 11=AGZS, 12=AGZDU, 13=WGZU, 14=ACZSU, 15=ACZDU
MOmin45ChillerOperationModeChiller Mode SetpointWrite1=Ice, 2=Cool, 3=Heat
MO46CompSelectCompressor SelectWrite1-6 = compressor number
MO47PumpSelectPump SelectWrite1=Pump 1, 2=Pump 2
AI901AIFaultAlarmFault Alarms index number (analog form)Read
MI901MSIFaultAlarmFault Alarms index number (multistate form)Read
AI900AIProblemAlarmProblem Alarms index number (analog form)Read
MI900MSIProblemAlarmProblem Alarms index number (multistate form)Read
AI902AIWarningAlarmWarning Alarms index number (analog form)Read
MI902MSIWarningAlarmWarning Alarms index number (multistate form)Read
Object ID lookup: Daikin Applied MicroTech II Chiller Unit Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech II Chiller Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech II Chiller Unit Controller

How many BACnet points does the Daikin Applied MicroTech II Chiller Unit Controller have?

This list has 128 BACnet objects: 105 analog inputs, 4 analog outputs, 8 binary inputs, 2 binary values, 6 multi-state inputs, 3 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech II Chiller Unit Controller BACnet points are writable?

9 of the 128 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech II Chiller Unit Controller BACnet documentation?

The source is MicroTech II Chiller Unit Controller Protocol Information (LonWorks, BACnet MS/TP) (ED 15062-9), revision 2022-08, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/Daikin_ED_15062-9_MTII_Chiller_Unit_Controller_Protocol_Info_Tech_Sheet.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech II Chiller Unit Controller?

Start with BV 41 ChillerEnable (Enable (1) / disable (0) the chiller); MO 45 ChillerOperationMode (Mode command: 1=Ice, 2=Cool, 3=Heat); AO 29 NetworkCoolTempSetpoint (Leaving chilled water setpoint); AO 32 NetworkCapacityLimitPct (Capacity limit from the BMS, %); MI 43 UnitStatus (Off/Start/Run/Pre-shutdown/Service); BI 38 ChillerLocalRemote (Reads Remote (0) when network control is allowed); AI 2 LvgEvapWaterTempUnit (Leaving chilled water temperature); AI 1 EntEvapWaterTemp (Entering chilled water temperature); AI 9 ChillerCapacity (Running capacity, %); BI 40 AlarmDigitalOutput (Any active alarm).

How do I enable BMS control of the Daikin Applied MicroTech II Chiller Unit Controller?

Disable the chiller, set the protocol to the BAS network at the user interface, then set the setpoint source to Network (on centrifugals, Control Source = BAS on the SETPOINTS/MODE screen, password 2001; other models use the passwords in the doc's table). Re-enable the chiller; ChillerEnable (BV 41) then starts and stops it.

Does the Daikin Applied MicroTech II Chiller Unit Controller need a BACnet heartbeat or have a communication timeout?

The receive-heartbeat and default-value behaviour described in the doc applies to the LonWorks interface only. No BACnet heartbeat point is listed.

How do I check these points on the real MicroTech II Chiller Unit Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech II Chiller Unit Controller Protocol Information (LonWorks, BACnet MS/TP) · ED 15062-9 · rev. 2022-08. Object names, instances and units are reproduced as published; descriptions are our own.