Unit ventilator controller (classroom terminal unit) · BACnet points list

Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller BACnet points list

Updated 6 November 2026

Short answer

The MicroTech II unit ventilator controller talks BACnet MS/TP through an optional communication module (LonWorks and N2 Open are the other options). The list has 54 objects: occupied/standby/unoccupied setpoints, damper and economizer settings, occupancy, mode and emergency commands, enables for economizer, compressor and auxiliary heat, sensor values the BAS can override, and status, run-time and fault values. Which objects apply depends on the unit's software model.

This page lists 54 BACnet objects for the Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech II AAF-HermanNelson Unit Ventilator Controller
Equipment
Unit ventilator controller (classroom terminal unit)
Equipment type
VAV boxes & fan coils
BACnet objects
54 (36 writable)
Transport
BACnet MS/TP
Firmware
BACnet module firmware 3.00 and higher (state numbers)
Also known as
ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC
Source document
MicroTech II AAF-HermanNelson Unit Ventilator Unit Controller Protocol Information (BACnet, LonWorks, N2 Open) · ED 15065-5 · rev. 2007-08
Download CSV 54 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller

Integration in brief

Set the MS/TP MAC address on the module's S1 switch, give each controller a unique device instance, then schedule the unit with Occupancy Sensor Input (MO 9) and leave Application Mode on Auto. Write the occupied setpoints only when they change, and read occupancy, controller state, space temperature and the fault value.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 9Occupancy Sensor InputOccupancy command from the BASWrite
MO 2ApplicModeUnit mode; leave on Auto or Null normallyWrite
MO 3EmergOverrideEmergency state command (5 = shutdown)Write
AV 1OccupiedCoolOccupied cooling setpointWrite
AV 4OccupiedHeatOccupied heating setpointWrite
MO 5ResetAlarmReset manual alarmsWrite
MI 3EffectOccupCurrent occupancyRead
AI 11StateMachineController state codeRead
AI 1SpaceTempSpace temperatureWrite
AI 17InAlarmCurrent fault numberRead

Enable & remote start

Occupancy Sensor Input (MO 9) is the object to use for BAS occupancy scheduling; the local bypass button overrides it for the Local Bypass Time (AV 7). Occupancy Override Input (MO 1) has the highest priority and overrides the sensor and tenant override. Application Mode (MO 2) should stay Auto or Null for normal operation.

Sensors & values from the BMS

Space temperature, outdoor temperature, outdoor and space humidity, space CO2 and entering water temperature (AI 1-5, AI 18) can be written by the BAS after setting Out_Of_Service TRUE; a valid value overrides the local sensor.

Network setup

Watch out for

Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

54 of 54 shown
Type
Access
Show
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller BACnet Points List
DescriptionStates
AVmin1OccupiedCoolOccupied cooling setpoint, 61-86 °F°FWrite
AV2StandbyCoolStandby cooling setpoint, 61-86 °F°FWrite
AV3UnoccupiedCoolUnoccupied cooling setpoint, 61-86 °F°FWrite
AVmin4OccupiedHeatOccupied heating setpoint, 50-82 °F°FWrite
AV5StandbyHeatStandby heating setpoint, 50-82 °F°FWrite
AV6UnoccupiedHeatUnoccupied heating setpoint, 50-82 °F°FWrite
AV7BypassTimeTime the unit stays in bypass, 0-240 minminWrite
AV8OAMinPosOutside air damper minimum position at high fan speed%Write
AV9OAMinPosMedSpeedOutside air damper minimum position at medium fan speed%Write
AV10OAMinPosLowSpeedOutside air damper minimum position at low fan speed%Write
AV11SpaceCO2LimSpace CO2 maximum limitppmWrite
AV12Economizer OA Temp SetpointOutdoor temperature below which economizing is allowed°FWrite
AV13EconDBDiffIndoor/outdoor air temperature differential for economizer°FWrite
AV14OAEnthSeptOutdoor air enthalpy setpoint for economizerBtu/lbWrite
AV15EconEnthDiffIndoor/outdoor air enthalpy differential for economizerBtu/lbWrite
AV16SpaceRHSetptSpace humidity setpoint%Write
AV17UVAppVersionApplication software revisionWrite
AO1SetptOffsetShifts occupied heating and cooling setpoints, -18 to +18 °F°FWrite
MO1OccManCmdHighest-priority occupancy override (overrides sensor and tenant override)Write1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null
MOmin2ApplicModeUnit mode command; Auto or Null for normal operationWrite1=Auto, 2=Heat, 4=Cool, 5=Night Purge, 7=Off, 9=Emergency Heat, 10=Fan Only, 15=Null
MOmin3EmergOverrideEmergency state commandWrite1=Normal, 2=Pressurized, 3=Depressurized, 4=Purge, 5=Shutdown, 6=Fire, 7=Null
MO4ResetFilterReset the filter alarmWrite1=Reset Object, 2=Clear, 3=Null
MOmin5ResetAlarmReset manual alarmsWrite1=Reset Object, 2=Clear, 3=Null
MO6EconEnableEnable or disable the economizerWrite1=Disable, 2=Enable, 3=Null
MO8AuxHeatEnableEnable or disable auxiliary heatWrite1=Off, 2=On, 3=Null
MOmin9Occupancy Sensor InputOccupancy command from the BAS (use this for scheduling)Write1=Occupied, 2=Unoccupied, 5=Null
MI1FanSpeedCurrent fan speedRead1=Off, 3=Low Speed, 4=Medium Speed, 5=High Speed, 6=Null
MI2HeatCoolCurrent controller mode (writable only when out of service)Write1=Auto, 2=Heat, 4=Cool, 5=Night Purge, 7=Off, 9=Emergency Heat, 10=Fan Only, 15=Null
MImin3EffectOccupCurrent occupancyRead1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null
MI4EnergyHoldOffStops heating and cooling, keeps freeze/overheat protectionWrite1=Disable, 2=Enable, 3=Null
AImin1SpaceTempSpace temperature; write (out of service) to override the sensor°FWrite
AI2OutdoorTempOutdoor air temperature; writable when out of service°FWrite
AI3OutdoorRHOutdoor air humidity; writable when out of service%Write
AI4Space Humidity InputSpace humidity; writable when out of service%Write
AI5SpaceCO2Space CO2; writable when out of serviceppmWrite
AI6DischAirTempDischarge air temperature°FRead
AI7EffectSetptActive heating or cooling setpoint°FRead
AI8LocalSetptSetpoint adjustment from the local room sensor°FWrite
AI9DATSetptCalculated discharge air setpoint°FRead
AI10OADamperOutside air damper position%Read
MO7ComprEnableEnable or disable compressor operationWrite1=Off, 2=On, 3=Null
AImin11StateMachineUnit ventilator controller stateRead49=Econ_Mech, 50=Mech_Cool, 51=Econ, 52=DA Heat, 53=Heat, 54=DeHumid, 55=Full_Heat, 56=Night_Purge, 57=Off, 65=Fan_Only, 66=(Heat)Can't Heat, 67=Can't Cool, 68=(Emergency Heat) Can't Heat, 69=Heat Low Limit, 70=Cool Low Limit
AI12FanRunTimeSpace fan run timehRead
AI13BinaryOut1Bit-coded status of binary outputs 1-7Read
AI14BinaryOut2Bit-coded status of outputs 8-9 and expansion outputs 1-2Read
AI15BinaryOut3Bit-coded status of expansion outputs 6-8Read
AI16BinaryIn1Bit-coded status of binary inputs 1, 3-6, 12Read
AImin17InAlarmCurrent fault numberRead1=Space T. Sens. Fail, 2=DX Press Fault, 3=Comp. Env. Fault, 4=Dis Air DX LowLimit, 5=Cond. Overflow, 6=Space Coil DX T. Sens., 7=Outdoor T. Sens, 8=Dis Air Temp Sens., 9=Outdoor Coil DX T.Sensor or Water Coil DX T. Sens, 10=Water-out T. Sensor Source or Water T. Sens, 11=Space RH Sens, 12=Outdoor RH Sens., 13=Space CO2 Sens., 14=Source Water Inadequate, 15=Freeze Stat, 16=Change Filter
AI18SourceTempEntering (source) water temperature; writable when out of service°FWrite
AI19WaterOutTempLeaving water temperature°FRead
AI20ComprRunTimeCompressor run timehRead
AI21FBPDamperFace and bypass damper position%Read
AI22HotWaterHeating or CW/HW valve position (modulating valve)%Read
AI23ColdWaterChilled water valve position (modulating valve)%Read
Object ID lookup: Daikin Applied MicroTech II unit ventilator point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech II AAF-HermanNelson Unit Ventilator Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller

How many BACnet points does the Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller have?

This list has 54 BACnet objects: 23 analog inputs, 1 analog output, 17 analog values, 4 multi-state inputs, 9 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller BACnet points are writable?

36 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller BACnet documentation?

The source is MicroTech II AAF-HermanNelson Unit Ventilator Unit Controller Protocol Information (BACnet, LonWorks, N2 Open) (ED 15065-5), revision 2007-08, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15065-5.pdf.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller?

Start with MO 9 Occupancy Sensor Input (Occupancy command from the BAS); MO 2 ApplicMode (Unit mode; leave on Auto or Null normally); MO 3 EmergOverride (Emergency state command (5 = shutdown)); AV 1 OccupiedCool (Occupied cooling setpoint); AV 4 OccupiedHeat (Occupied heating setpoint); MO 5 ResetAlarm (Reset manual alarms); MI 3 EffectOccup (Current occupancy); AI 11 StateMachine (Controller state code); AI 1 SpaceTemp (Space temperature); AI 17 InAlarm (Current fault number).

How do I enable BMS control of the Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller?

Occupancy Sensor Input (MO 9) is the object to use for BAS occupancy scheduling; the local bypass button overrides it for the Local Bypass Time (AV 7). Occupancy Override Input (MO 1) has the highest priority and overrides the sensor and tenant override. Application Mode (MO 2) should stay Auto or Null for normal operation.

Can the BMS supply sensor values to the Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller?

Space temperature, outdoor temperature, outdoor and space humidity, space CO2 and entering water temperature (AI 1-5, AI 18) can be written by the BAS after setting Out_Of_Service TRUE; a valid value overrides the local sensor.

How do I check these points on the real MicroTech II AAF-HermanNelson Unit Ventilator Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.