  4. EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)

Heat pump / chiller controller · BACnet points list

Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe) BACnet points list

Updated 7 November 2026

Short answer

The EWYD/H-4Z units use a MicroTech 4 controller with the EVE software. BACnet IP or BACnet MS/TP comes from a POL908/POL904 module or the onboard software option. The list covers unit enable, ice/cool/heat/multipurpose mode, network setpoints and capacity limit, evaporator and condenser water temperatures, two refrigerant circuits with one compressor each, pump status, energy data, variable-flow and noise-reduction objects, and individual alarm BVs plus alarm index/code AVs.

This page lists 201 BACnet objects for the Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Equipment
Heat pump / chiller controller
Equipment type
Chillers
BACnet objects
201 (22 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
EVE 1.00.B
Default device instance
1
Also known as
EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22
Source document
BAS Integration guide - BACnet protocol (EWYD/H-4Z) · D-EIGOC00102-22EN_EWYD-4Z · rev. 2022-02
Download CSV 201 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)

Integration in brief

Select network control at the unit (CtrlSource BI 3 then reads Network), enable the unit with UnitEnableStp, and write the mode, cool/heat setpoints and capacity limit. Monitor unit status, leaving water temperature, AlarmOutput and the fault index/code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2UnitEnableStpNetwork enable/disable of the unitWrite
MV 3UnitModeSetpointNetworkIce / cool / heat / multipurpose mode commandWrite
AV 4NetworkCoolTempSetpointCool water setpoint from the BMSWrite
AV 6NetworkHeatTempSetpointHeat water setpoint from the BMSWrite
AV 3NetworkCapacityLimitSetpointCapacity limit from the BMSWrite
BV 8ClearAlarmClear alarms from the networkWrite
BI 3CtrlSourceShows whether network control is activeRead
MV 1UnitStatusUnit run stateRead
AI 2EvapLvgWTempEvaporator leaving water temperatureRead
BI 10AlarmOutputAny active alarmRead

Enable & remote start

CtrlSource (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes UnitEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.

Sensors & values from the BMS

The variable-flow differential pressure inputs (AI 1905, AI 1907) are marked writable; the guide does not say whether the BMS must supply them.

Network setup

Watch out for

Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

201 of 201 shown
Type
Multi-state
Access
Show
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe) BACnet Points List
DescriptionStates
BImin3CtrlSourceUnit - Control SourceRead0=Network, 1=Local
BI7EnableOutputUnit - Enabled StateRead0=Disabled, 1=Enabled
BI5RunEnabledUnit - Run AllowedRead0=Off, 1=Allowed
BI6UnitLimitedUnit - Capacity LimitedRead0=NotLimited, 1=Limited
BImin10AlarmOutputUnit - Alarm OutputRead0=None, 1=Alarm
BI2EvapWFlowStateEvaporator - Water Flow StateRead0=NoFlow, 1=Flow
MVCondWFlowStateCondenser - Water Flow StateRead1=NoFlow, 2=Flow
BI4UnitOnOffUnit - Operating StateRead0=Thermo On, 1=Thermo Off
BVmin2UnitEnableStpUnit - Enable SetpointWrite0=Disable, 1=Enable
BVmin8ClearAlarmUnit - Alarm Reset SetpointWrite0=None, 1=ClearAlarm
MV2ActModeUnit - Active Operation ModeRead1=Ice, 2=Cool, 3=Heat, 4=Multipurpose
AV5ActTempStpUnit - Active Temperature Setpoint°CRead
AV2ActCapacityUnit - Actual Capacity%Read
AV1ActCapacityLimUnit - Active Capacity Limit%Read
MVmin1UnitStatusUnit - StatusRead1=Off, 2=Start, 3=Run, 4=PreShutdown, 5=Service
AI1EvapEntWTempEvaporator Entering Water Temperature°CRead
AImin2EvapLvgWTempEvaporator Leaving Water Temperature°CRead
AI3CondEntWTempCondenser Entering Water Temperature°CRead
AI4CondLvgWTempCondenser Leaving Water Temperature°CRead
AI5OutdoorAirTempOutside Air Temperature°CRead
AI993AvgCurrentUnit - Average CurrentARead
AV992AvgVoltageUnit - Average VoltageVRead
AV994ActPowerUnit - Active PowerkWRead
AV902AVWarningAlarmUnit Alarm - Warning IndexRead
AV900AVProblemAlarmUnit Alarm - Problem IndexRead
AV901AVFaultAlarmUnit Alarm - Fault IndexRead
AV903AVWarningAlarmCodeUnit Alarm - Warning CodeRead
AV904AVProblemAlarmCodeUnit Alarm - Problem CodeRead
AV905AVFaultAlarmCodeUnit Alarm - Fault CodeRead
MVmin3UnitModeSetpointNetworkUnit - Operation Mode SetpointWrite1=Ice, 2=Cool, 3=Heat, 4=MultiP
AVmin4NetworkCoolTempSetpointUnit - Cool Temperature Setpoint°CWrite
AV7NetworkIceTempSetpointUnit - Ice Temperature Setpoint°CWrite
AVmin6NetworkHeatTempSetpointUnit - Heat Temperature Setpoint°CWrite
AVmin3NetworkCapacityLimitSetpointUnit - Capacity Limit Setpoint%Write
AI99C1'CondRefPressureCircuit 1 - Condenser Refrigerant PressurekPaRead
AV34C1'CondSatRefTempCircuit 1 - Condenser Saturated Temperature°CRead
AI141C1'EvapRefPressureCircuit 1 - Evaporator Refrigerant PressurekPaRead
AV68C1'EvapSatRefTempCircuit 1 - Evaporator Saturated Temperature°CRead
AI100C2'CondRefPressureCircuit 2 - Condenser Refrigerant PressurekPaRead
AV35C2'CondSatRefTempCircuit 2 - Condenser Saturated Temperature°CRead
AI142C2'EvapRefPressureCircuit 2 - Evaporator Refrigerant PressurekPaRead
AV69C2'EvapSatRefTempCircuit 2 - Evaporator Saturated Temperature°CRead
MV51C1'ShutdownAlmCircuit 1 - Shutdown AlarmRead1=NoAlarm, 2=Alarm
MV52C2'ShutdownAlmCircuit 2 - Shutdown AlarmRead1=NoAlarm, 2=Alarm
AI105C1'Comp1'SuctTempCirc 1 Compressor 1 - Suction Temperature°CRead
AI63C1'Comp1'DischTempCirc 1 Compressor 1 - Discharge Temperature°CRead
AV8C1'Comp1'RLAPercentCirc 1 Compressor 1 - RLA Percentage%Read
AI9C1'Comp1'CurrentCirc 1 Compressor 1 - CurrentARead
AV45C1'Comp1'PowerCirc 1 Compressor 1 - PowerkWRead
AV92C1'Comp1'StartsCirc 1 Compressor 1 - Number of StartsWrite
AV74C1'Comp1'RunHoursCirc 1 Compressor 1 - Number of Running HourshWrite
AI108C2'Comp1'SuctTempCirc 2 Compressor 1 - Suction Temperature°CRead
AI66C2'Comp1'DischTempCirc 2 Compressor 1 - Discharge Temperature°CRead
AV11C2'Comp1'RLAPercentCirc 2 Compressor 1 - RLA Percentage%Read
AI12C2'Comp1'CurrentCirc 2 Compressor 1 - CurrentARead
AV47C2'Comp1'PowerCirc 2 Compressor 1 - PowerkWRead
AV95C2'Comp1'StartsCirc 2 Compressor 1 - Number of StartsWrite
AV77C2'Comp1'HoursCirc 2 Compressor 1 - Number of Running HourshWrite
AV295CondPump'SpeedCondenser Pump - Speed%Read
AV296EvapPump'SpeedEvaporator Pump - Speed%Read
AV110CondPump1'RunHrsCondenser Pump 1 - Number of Running HoursRead
BI11CondPump1'StatusCondenser Pump 1 - Operating StateRead0=Stop, 1=Run
AV111CondPump2'RunHrsCondenser Pump 2 - Number of Running HoursRead
BI12CondPump2'StatusCondenser Pump 2 - Operating StateRead0=Stop, 1=Run
AV112EvapPump1'RunHoursEvaporator Pump 1 - Number of Running HoursRead
BI8EvapPump1'StateEvaporator Pump 1 - Operating StateRead0=Stop, 1=Run
AV113EvapPump2'RunHoursEvaporator Pump 2 - Number of Running HoursRead
BI9EvapPump2'StateEvaporator Pump 2 - Operating StateRead0=Stop, 1=Run
MV4UnitsUnit - BACnet Measurement unit setpointWrite1=Metric, 2=English
MV317UnitModelUnit - ModelRead1=Centrifugal, 2=Water Cooled, 3=Air Cooled, 4=HeatPump, 5=Reserved, 6=Reserved, 7=Reserved, 8=Reserved, 9=Other
MV151Cir1OperatingModeCircuit 1 - Actual ModeRead1=Water, 2=Chiller, 3=Heat Pump, 4=Defrost
MV139Cir2OperatingModeCircuit 2 - Actual ModeRead1=Water, 2=Chiller, 3=Heat Pump, 4=Defrost
BV500Unit'OFFCndEntWTempFailUnit Alarm - Condenser Entering Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV917Unit'OFFEvapEntWTempFailUnit Alarm - Evaporator Entering Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV503Unit'OFFCndLvgWTempFailUnit Alarm - Condenser Leaving Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV512BadSetpointResetInputUnit Warning - Setpoint Reset Input Out of RangeRead0=NoAlarm, 1=InAlarm
BV513BadDemandLimitInputUnit Warning - Demand Limit Input Out of RangeRead0=NoAlarm, 1=InAlarm
BV529C1'InhibitPwrLossCircuit 1 Warning - Power Loss while Compressor RunningRead0=NoAlarm, 1=InAlarm
BV530C2'InhibitPwrLossCircuit 2 Warning - Power Loss while Compressor RunningRead0=NoAlarm, 1=InAlarm
BV533Unit'InhibitOATLowUnit Warning - Inhibition for Low Ambient TemperatureRead0=NoAlarm, 1=InAlarm
BV548CondPump1'FaultCondenser Pump 1 - FaultRead0=NoAlarm, 1=InAlarm
BV549CondPump2'FaultCondenser Pump 2 - FaultRead0=NoAlarm, 1=InAlarm
BV575EvapPump1'FaultEvaporator Pump 1 - FaultRead0=NoAlarm, 1=InAlarm
BV576EvapPump2'FaultEvaporator Pump 2 - FaultRead0=NoAlarm, 1=InAlarm
BV599C1'Comp1'OFFPresRatioLowCirc 1 Comp 1 Alarm - Low Pressure RatioRead0=NoAlarm, 1=InAlarm
BV601C2'Comp1'OFFPresRatioLowCirc 2 Comp 1 Alarm - Low Pressure RatioRead0=NoAlarm, 1=InAlarm
BV605Unit'OFFOATempSenFailUnit Alarm - Outside Air Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV606C1'Comp1'OFFCurrentHiCirc 1 Comp 1 Alarm - High Motor CurrentRead0=NoAlarm, 1=InAlarm
BV608C2'Comp1'OFFCurrentHiCirc 2 Comp 1 Alarm - High Motor CurrentRead0=NoAlarm, 1=InAlarm
BV637C1'Comp1'OFFMotorTempHiCirc 1 Comp 1 Alarm - High Motor TemperatureRead0=NoAlarm, 1=InAlarm
BV639C2'Comp1'OFFMotorTempHiCirc 2 Comp 1 Alarm - High Motor TemperatureRead0=NoAlarm, 1=InAlarm
BV668C1'OFFCondPresFailCircuit 1 Alarm - Condenser Pressure Sensor FaultRead0=NoAlarm, 1=InAlarm
BV670C2'OFFCondPresFailCircuit 2 Alarm - Condenser Pressure Sensor FaultRead0=NoAlarm, 1=InAlarm
BV989Unit'OFFCondLvgWTempLowUnit Alarm - Condenser Water FreezeRead0=NoAlarm, 1=InAlarm
BV674Unit'OFFCondFlowLossUnit Alarm - Condenser Water Flow LossRead0=NoAlarm, 1=InAlarm
BV676C1'OFFCondPresHiCircuit 1 Alarm - Condenser High PressureRead0=NoAlarm, 1=InAlarm
BV678C2'OFFCondPresHiCircuit 2 Alarm - Condenser High PressureRead0=NoAlarm, 1=InAlarm
BV688C1'OFFDischTempFailCircuit 1 Alarm - Discharge Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV690C2'OFFDischTempFailCircuit 2 Alarm - Discharge Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV694C1'Comp1'OFFDischTempHiCirc 1 Comp 1 Alarm - High Discharge TemperatureRead0=NoAlarm, 1=InAlarm
BV696C2'Comp1'OFFDischTempHiCirc 2 Comp 1 Alarm - High Discharge TemperatureRead0=NoAlarm, 1=InAlarm
BV701Unit'OFFEvapFlowLossUnit Alarm - Evaporator Water Flow LossRead0=NoAlarm, 1=InAlarm
BV702Unit'OFFEvapLvgWTempLowUnit Alarm - Evaporator Water FreezeRead0=NoAlarm, 1=InAlarm
BV704C1'OFFEvapPresLowCircuit 1 Alarm - Evaporator Pressure LowRead0=NoAlarm, 1=InAlarm
BV706C2'OFFEvapPresLowCircuit 2 Alarm - Evaporator Pressure LowRead0=NoAlarm, 1=InAlarm
BV711C1'OFFEvapPresFailCircuit 1 Alarm - Evaporator Pressure Sensor FailureRead0=NoAlarm, 1=InAlarm
BV713C2'OFFEvapPresFailCircuit 2 Alarm - Evaporator Pressure Sensor FailureRead0=NoAlarm, 1=InAlarm
BV742C1'OFFRestartsAlmCircuit 1 Alarm - Too many restartRead0=NoAlarm, 1=InAlarm
BV744C2'OFFRestartsAlmCircuit 2 Alarm - Too many restartRead0=NoAlarm, 1=InAlarm
BV748Unit'OFFEvapLvgWTempFailUnit Alarm - Evaporator Leaving Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV760C1'OFFMechPressHiCircuit 1 Alarm - Mechanical High PressureRead0=NoAlarm, 1=InAlarm
BV762C2'OFFMechPressHiCircuit 2 Alarm - Mechanical High PressureRead0=NoAlarm, 1=InAlarm
BV796C1'OFFOilFilterPresHiCircuit 1 Alarm - Oil Filter High PressureRead0=NoAlarm, 1=InAlarm
BV798C2'OFFOilFilterPresHiCircuit 2 Alarm - Oil Filter High PressureRead0=NoAlarm, 1=InAlarm
BV802C1'OFFOilPresFailCircuit 1 Alarm - Oil Pressure Sensor FailureRead0=NoAlarm, 1=InAlarm
BV804C2'OFFOilPresFailCircuit 2 Alarm - Oil Pressure Sensor FailureRead0=NoAlarm, 1=InAlarm
BV735C1'OFFLiquidTsenfCircuit 1 Alarm - Liquid Temperature Sensor FailureRead0=NoAlarm, 1=InAlarm
BV737C2'OFFLiquidTsenfCircuit 2 Alarm - Liquid Temperature Sensor FailureRead0=NoAlarm, 1=InAlarm
BV820Unit'OFFPhaseVoltageUnit Alarm - Phase VoltageRead0=NoAlarm, 1=InAlarm
BV978C1'OFFOverVoltageCircuit 1 Alarm - OverVoltageRead0=NoAlarm, 1=InAlarm
BV982C2'OFFOverVoltageCircuit 2 Alarm - OverVoltageRead0=NoAlarm, 1=InAlarm
BV979C1'OFFUnderVoltageCircuit 1 Alarm - UnderVoltageRead0=NoAlarm, 1=InAlarm
BV981C2'OFFUnderVoltageCircuit 2 Alarm - UnderVoltageRead0=NoAlarm, 1=InAlarm
BV857C1'Comp1'OFFSuctTempFailCirc 1 Comp 1 Alarm - Suction Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV859C2'Comp1'OFFSuctTempSenCirc 2 Comp 1 Alarm - Suction Temperature Sensor FaultRead0=NoAlarm, 1=InAlarm
BV911C1'OFFNoPressStartCircuit 1 Alarm - No Pressure at StartRead0=NoAlarm, 1=InAlarm
BV912C2'OFFNoPressStartCircuit 2 Alarm - No Pressure at StartRead0=NoAlarm, 1=InAlarm
BV723C1'OFFBoardOfflineController Alarm - Circuit 1 Board OfflineRead0=NoAlarm, 1=InAlarm
BV724C2'OFFBoardOfflineController Alarm - Circuit 2 Board OfflineRead0=NoAlarm, 1=InAlarm
BV726C1'OFFEXVBoardOfflineController Alarm - Expansion Valve 1 Board OfflineRead0=NoAlarm, 1=InAlarm
BV727C2'OFFEXVBoardOfflineController Alarm - Expansion Valve 2 Board OfflineRead0=NoAlarm, 1=InAlarm
BV515Unit'PowerRestoreUnit - Power RestoreRead0=NoAlarm, 1=InAlarm
BV516C1'FailPumpdownCircuit 1 Alarm - Pumpdown FailureRead0=NoAlarm, 1=InAlarm
BV517C2'FailPumpdownCircuit 2 Alarm - Pumpdown FailureRead0=NoAlarm, 1=InAlarm
BV924Unit'ExternalEventUnit Alarm - External EventRead0=NoAlarm, 1=InAlarm
BV925Unit'OFFBoardOfflineController Alarm - Unit Board OfflineRead0=NoAlarm, 1=InAlarm
BV905C1'OFFNoPresChgAtStartCircuit 1 Alarm - No Pressure change at StartRead0=NoAlarm, 1=InAlarm
BV906C2'OFFNoPresChgAtStartCircuit 2 Alarm - No Pressure change at StartRead0=NoAlarm, 1=InAlarm
BVC1'Comp1'OFFVfdFaultCirc 1 Compr 1 Alarm - VFD FaultRead0=NoAlarm, 1=InAlarm
BV888C2'Comp1'OFFVfdFaultCirc 2 Compr 1 Alarm - VFD FaultRead0=NoAlarm, 1=InAlarm
BV942C1'Comp1'OFFVfdTempHiCirc 1 Compr 1 Alarm - VFD High TemperatureRead0=NoAlarm, 1=InAlarm
BV944C2'Comp1'OFFVfdTempHiCirc 2 Compr 1 Alarm - VFD High TemperatureRead0=NoAlarm, 1=InAlarm
BV948C1'Comp1'OFFVfdCommFailCirc 1 Compr 1 Alarm - VFD Communication FailureRead0=NoAlarm, 1=InAlarm
BV950C2'Comp1'OFFVfdCommFailCirc 2 Compr 1 Alarm - VFD Communication FailureRead0=NoAlarm, 1=InAlarm
BV921EmergencyStopAlarmUnit Alarm - Emergency Stop SwitchRead0=NoAlarm, 1=InAlarm
BV922EvapWTempInvertedUnit Alarm - Evaporator Temperature Sensors InvertedRead0=NoAlarm, 1=InAlarm
BV923Unit'OFFExternalAlarmUnit Alarm - External AlarmRead0=NoAlarm, 1=InAlarm
BV961C1'Comp1'DischSHeatLowCirc 1 Compr 1 Problem - Low Discharge SuperheatRead0=NoAlarm, 1=InAlarm
BV963C2'Comp1'DischSHeatLowCirc 2 Compr 1 Problem - Low Discharge SuperheatRead0=NoAlarm, 1=InAlarm
BV918BadCurrentLimitInputUnit Warning - Current Limit Input Out Of RangeRead0=NoAlarm, 1=InAlarm
BV919Unit'OFFOptBoardOfflineController Alarm - Option Board OfflineRead0=NoAlarm, 1=InAlarm
BV844C1'OFFGasLeakageCircuit 1 Alarm - Gas LeakageRead0=NoAlarm, 1=InAlarm
BV845C2'OFFGasLeakageCircuit 2 Alarm - Gas LeakageRead0=NoAlarm, 1=InAlarm
AI187SwitchBoxTempUnit - Electrical Panel Temperature°CRead
BV983Unit'SwitchBoxSensFaultUnit Warning - Electrical Panel Temp Sensor FaultRead0=NoAlarm, 1=InAlarm
BV984Unit'SwitchBoxTempHighUnit Warning - Electrical Panel High TemperatureRead0=NoAlarm, 1=InAlarm
BV837Unit'OFFFanBoardOfflineController Alarm - Fan Board OfflineRead0=NoAlarm, 1=InAlarm
BV838C1'FanAlmCircuit 1 Alarm - Fan FaultRead0=NoAlarm, 1=InAlarm
BV839C2'FanAlmCircuit 2 Alarm - Fan FaultRead0=NoAlarm, 1=InAlarm
AV1800C2'Comp1'ActCapacityCirc 2 Compressor 1 - Actual Capacity%Read
MV440C2'Comp1'OffAutoStpCirc 2 Compressor 1 - OffAuto SetpointWrite1=Off, 2=Auto
BV1802C2'Comp1'FullLoadStaCirc 2 Compressor 1 - Full Load StateRead0=Normal, 1=Full Load
AI166C2'Comp1'OilFeedPressCirc 2 Compressor 1 - Oil Feed PressurekPaRead
BV441C2'Comp1'StateCirc 2 Compressor 1 - Operating StateRead0=Off, 1=On
AV1840C1'Comp1'ActCapacityCirc 1 Compressor 1 - Actual Capacity%Read
MV430C1'Comp1'OffAutoStpCirc 1 Compressor 1 - OffAuto SetpointWrite1=Off, 2=Auto
BV1842C1'Comp1'FullLoadStaCirc 1 Compressor 1 - Full Load StateRead0=Normal, 1=Full Load
AI165C1'Comp1'OilFeedPressCirc 1 Compressor 1 - Oil Feed PressurekPaRead
BV431C1'Comp1'StateCirc 1 Compressor 1 - Operating StateRead0=Off, 1=On
MV1854RefrigTypeUnit - Refrigerant typeRead1=R22, 2=R134a, 3=R407c, 4=R410a, 5=resv1, 6=resv2, 7=resv3
AV1855NrCircuitsUnit - Number of CircuitsRead
AV1856NrCompressorsUnit - Number of CompressorsRead
AV1896C2'EvapSuperheatStpValCircuit 2 - Evaporator Superheat Active SetpointdKRead
AV1897C1'EvapSuperheatStpValCircuit 1 - Evaporator Superheat Active SetpointdKRead
AV1898C2'EvapSuperheatCircuit 2 - Evaporator Superheat TemperaturedKRead
AV1899C1'EvapSuperheatCircuit 1 - Evaporator Superheat TemperaturedKRead
AV990ActEnergyUnit - Active EnergykWhRead
AV991PowerFactorUnit - Power FactorRead
AV995NetworkCurrentLimitSetpointUnit - Current Limit SetpointAWrite
AI1905VarFlow'LoadDPresVariable Flow - Plant Differential PressurekPaWrite
MV1906VarFlow'WBypVlvStaVariable Flow - Water Bypass Valve StateRead1=Closed, 2=Opened
AI1907VarFlow'HotLoadDPresVariable Flow - Heat Plant Differential PressurekPaWrite
MV1908VarFlow'HotWBypVlvStaVariable Flow - Heat Water Bypass Valve StateRead1=Closed, 2=Opened
AV1909VarFlow'LoadDPresStptVariable Flow - Plant Differential Pressure setpointkPaWrite
AV1910VarFlow'HotLoadDPresStptVariable Flow - Heat Plant Differential Pressure setpointkPaWrite
AI1911VarFlow'DeltaTempVariable Flow - Plant Delta TemperaturedKRead
AI1912VarFlow'HotDeltaTempVariable Flow - Heat Plant Delta TemperaturedKRead
AV1913VarFlow'DeltaTempStpVariable Flow - Plant Delta Temperature SetpointdKWrite
AV1914VarFlow'HotDeltaTempStpVariable Flow - Heat Plant Delta Temperature SetpointdKWrite
AV208C2'ExpValvePosCircuit 2 - Expansion Valve Position%Read
AV209C2'FanSpeedCircuit 2 - Fan Speed%Read
AV210C2'CondApproachCircuit 2 - Condenser Approach TemperaturedKRead
AV211C2'EvapApproachCircuit 2 - Evaporator Approach TemperaturedKRead
AV1997C2'FanStatusCircuit 2 - Fan StagingRead
AV168C1'ExpValvePosCircuit 1 - Expansion Valve Position%Read
AV169C1'FanSpeedCircuit 1 - Fan Speed%Read
AV170C1'CondApproachCircuit 1 - Condenser Approach TemperaturedKRead
AV171C1'EvapApproachCircuit 1 - Evaporator Approach TemperaturedKRead
AVC1'FanStatusCircuit 1 - Fan StagingRead
BV1998NoiseReductEnableSetpointNoise Reduction - Enable SetpointWrite0=Auto, 1=Enable
BV2000NoiseReductStateNoise Reduction - Operating StateRead0=Off, 1=On
Object ID lookup: Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)

How many BACnet points does the Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe) have?

This list has 201 BACnet objects: 23 analog inputs, 58 analog values, 11 binary inputs, 94 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe) BACnet points are writable?

22 of the 201 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe) BACnet documentation?

The source is BAS Integration guide - BACnet protocol (EWYD/H-4Z) (D-EIGOC00102-22EN_EWYD-4Z), revision 2022-02, published free by Daikin Applied at https://easyspec.daikin.fr/Easyspec/2-BASE_WEB/3-Eau%20Glacee%20%26%20VC/Documentations/J_EWYS-4Z/Manuel%20adressage%20com/COM_J_EWYS-4Z.zip.

What are the minimum BACnet points to integrate the Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)?

Start with BV 2 UnitEnableStp (Network enable/disable of the unit); MV 3 UnitModeSetpointNetwork (Ice / cool / heat / multipurpose mode command); AV 4 NetworkCoolTempSetpoint (Cool water setpoint from the BMS); AV 6 NetworkHeatTempSetpoint (Heat water setpoint from the BMS); AV 3 NetworkCapacityLimitSetpoint (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 CtrlSource (Shows whether network control is active); MV 1 UnitStatus (Unit run state); AI 2 EvapLvgWTemp (Evaporator leaving water temperature); BI 10 AlarmOutput (Any active alarm).

How do I enable BMS control of the Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)?

CtrlSource (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes UnitEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.

Can the BMS supply sensor values to the Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)?

The variable-flow differential pressure inputs (AI 1905, AI 1907) are marked writable; the guide does not say whether the BMS must supply them.

How do I check these points on the real EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.