Generic I/O controller · BACnet points list

Daikin Applied MicroTech III Generic I/O Panel BACnet points list

Updated 6 November 2026

Short answer

A general-purpose MicroTech III controller with fixed I/O used in Daikin's Delivered VAV System. Over BACnet MS/TP it exposes its six analog inputs, five universal analog outputs, six digital inputs and ten digital outputs as objects, plus five PID loops (one per analog output) with setpoint, tuning and input selection. There is no equipment logic beyond that, so what each point means depends on the job wiring.

This page lists 58 BACnet objects for the Daikin Applied MicroTech III Generic I/O Panel — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech III Generic I/O Panel
Equipment
Generic I/O controller
Equipment type
Other equipment
BACnet objects
58 (58 writable)
Transport
BACnet MS/TP
Firmware
2508022100 and later
Default device instance
3101120
Also known as
ED 19014, Generic I/O Panel, MicroTech III GIO, POL904
Source document
MicroTech III Generic I/O Panel Protocol Information, BACnet Networks · ED 19014 · rev. 2011-07
Download CSV 58 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied MicroTech III Generic I/O Panel

Integration in brief

The panel ships pre-configured for the Delivered VAV System, so normally the BMS only reads its I/O. Outputs (AO, BO) are commandable. Inputs, PID settings (AV) and the PID input and units selectors (MSV) are writable only while Out_Of_Service is true.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1AI1Universal output X1 commandCommand
BO 1DO1Digital output DO1 commandCommand
AV 5X1SetpointPID setpoint for output X1Write
AI 1AI1Hardware input AI1Write
BI 1DI1Digital input DI1Write

Sensors & values from the BMS

Inputs (AI, BI) can be written only after setting Out_Of_Service true.

Network setup

Watch out for

Daikin Applied MicroTech III Generic I/O Panel BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

58 of 58 shown
Type
Multi-state
Access
Show
Daikin Applied MicroTech III Generic I/O Panel BACnet Points List
DescriptionStates
AImin1AI1Hardware input 1 valueWrite
AI2AI2Hardware input 2 valueWrite
AI3AI3Hardware input 3 valueWrite
AI4X6Hardware input X6 valueWrite
AI5X7Hardware input X7 valueWrite
AI6X8Hardware input X8 valueWrite
AOmin1AI1Universal hardware output X1Command
AO2X2Universal hardware output X2Command
AO3X3Universal hardware output X3Command
AO4X4Universal hardware output X4Command
AO5X5Universal hardware output X5Command
AV1X1DerivativePID loop derivative for output X1Write
AV2X1IntegralTimePID loop integral time for output X1Write
AV3X1PropbandPID loop propband for output X1Write
AV4X1DeadbandPID loop deadband for output X1Write
AVmin5X1SetpointPID loop setpoint for output X1Write
AV6X2DerivativePID loop derivative for output X2Write
AV7X2IntegralTimePID loop integral time for output X2Write
AV8X2PropbandPID loop propband for output X2Write
AV9X2DeadbandPID loop deadband for output X2Write
AV10X2SetpointPID loop setpoint for output X2Write
AV11X3DerivativePID loop derivative for output X3Write
AV12X3IntegralTimePID loop integral time for output X3Write
AV13X3PropbandPID loop propband for output X3Write
AV14X3DeadbandPID loop deadband for output X3Write
AV15X3SetpointPID loop setpoint for output X3Write
AV16X4DerivativePID loop derivative for output X4Write
AV17X4IntegralTimePID loop integral time for output X4Write
AV18X4PropbandPID loop propband for output X4Write
AV19X4DeadbandPID loop deadband for output X4Write
AV20X4SetpointPID loop setpoint for output X4Write
AV21X5DerivativePID loop derivative for output X5Write
AV22X5IntegralTimePID loop integral time for output X5Write
AV23X5PropbandPID loop propband for output X5Write
AV24X5DeadbandPID loop deadband for output X5Write
AV25X5SetpointPID loop setpoint for output X5Write
BImin1DI1Hardware digital input DI1Write0=Off, 1=On
BI2DI2Hardware digital input DI2Write0=Off, 1=On
BI3DI3Hardware digital input DI3Write0=Off, 1=On
BI4DI4Hardware digital input DI4Write0=Off, 1=On
BI5DI5Hardware digital input DI5Write0=Off, 1=On
BI6DI6Hardware digital input DI6Write0=Off, 1=On
BOmin1DO1Hardware digital output DO1Command0=Off, 1=On
BO2DO2Hardware digital output DO2Command0=Off, 1=On
BO3DO3Hardware digital output DO3Command0=Off, 1=On
BO4DO4Hardware digital output DO4Command0=Off, 1=On
BO5DO5Hardware digital output DO5Command0=Off, 1=On
BO6DO6Hardware digital output DO6Command0=Off, 1=On
BO7DO7Hardware digital output DO7Command0=Off, 1=On
BO8DO8Hardware digital output DO8Command0=Off, 1=On
BO9DO9Hardware digital output DO9Command0=Off, 1=On
BO10DO10Hardware digital output DO10Command0=Off, 1=On
MV1UnitSupportUnits sent to BACnet (metric or English)Write1=Metric, 2=English
MV2X1PIDInputPID loop input for output X1Write1=None, 2=X6, 3=X7, 4=X8
MV3X2PIDInputPID loop input for output X2Write1=None, 2=X6, 3=X7, 4=X8
MV4X3PIDInputPID loop input for output X3Write1=None, 2=X6, 3=X7, 4=X8
MV5X4PIDInputPID loop input for output X4Write1=None, 2=X6, 3=X7, 4=X8
MV6X5PIDInputPID loop input for output X5Write1=None, 2=X6, 3=X7, 4=X8
Object ID lookup: Daikin Applied MicroTech III Generic I/O point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech III Generic I/O Panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech III Generic I/O Panel

How many BACnet points does the Daikin Applied MicroTech III Generic I/O Panel have?

This list has 58 BACnet objects: 6 analog inputs, 5 analog outputs, 25 analog values, 6 binary inputs, 10 binary outputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech III Generic I/O Panel BACnet points are writable?

58 of the 58 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech III Generic I/O Panel BACnet documentation?

The source is MicroTech III Generic I/O Panel Protocol Information, BACnet Networks (ED 19014), revision 2011-07, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED19014.pdf.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech III Generic I/O Panel?

Start with AO 1 AI1 (Universal output X1 command); BO 1 DO1 (Digital output DO1 command); AV 5 X1Setpoint (PID setpoint for output X1); AI 1 AI1 (Hardware input AI1); BI 1 DI1 (Digital input DI1).

Can the BMS supply sensor values to the Daikin Applied MicroTech III Generic I/O Panel?

Inputs (AI, BI) can be written only after setting Out_Of_Service true.

How do I check these points on the real MicroTech III Generic I/O Panel?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.