Self-contained unit controller · BACnet points list
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet points list
Updated 6 November 2026
The MicroTech II controller on SWP and SWT vertical self-contained units talks BACnet IP or BACnet MS/TP through a communication module (LonWorks is the other option). The table covers unit status, application and occupancy commands, zone and discharge air setpoints, water and air temperatures, duct and building pressure, waterside and airside economizer data, SCC dehumidification, a keypad schedule and calendar, and alarm read and clear objects.
This page lists 67 BACnet objects for the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
- Equipment
- Self-contained unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 67 (30 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Application 1.28
- Also known as
- ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Set switch S7 to AUTO and Control Mode to AUTO at the keypad. Leave Occupancy Mode on Auto and command occupancy with the Occupancy Scheduler Input BV at a priority above 15 (e.g. 8). Use Application Mode for on/off, write setpoints as needed and read status, temperatures and the alarm notification values.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 3715 | Application Mode | Off / heat-cool / heat only / cool only / fan only | Write |
| BV 1380 | Occupancy Scheduler Input | Occupied command; write at priority 8, not 15 | Write |
| AV 3720 | Emergency Override Mode Flag | Network shutdown (1 = off) | Write |
| AV 3765 | Occupied Cooling Setpoint | Occupied cooling setpoint | Write |
| AV 3820 | Occupied Heating Setpoint | Occupied heating setpoint | Write |
| AV 3840 | Duct Static Pressure Setpoint | Duct static pressure setpoint (DAC units) | Write |
| BV 4150 | Alarm, Faults: Clear All | Fault alarm flag; write to clear faults | Write |
| AV 3915 | Unit Status | Unit operating state | Read |
| AI 135 | Discharge Air Temperature | Discharge air temperature | Read |
| AV 5328 | Alarms-Fault Individual Notification | Highest-priority active fault number | Read |
Enable & remote start
Set rocker switch S7 to AUTO and the keypad Control Mode to AUTO (password 4545). Application Mode (AV 3715) then turns the unit off or selects heat/cool, heat only, cool only or fan only; Emergency Override Mode Flag (AV 3720) = 1 shuts it off from the network. Occupancy Mode (AV 3930) is an override and should stay Auto.
Heartbeat & communication loss
The guide's receive heartbeat (occupancy scheduler input, application mode, fan capacity, building static pressure, outdoor, return and space temperature, humidity) is a LonWorks feature with no BACnet equivalent. Over BACnet, an input written with Out_Of_Service TRUE keeps its last value if communication is lost.
Sensors & values from the BMS
Space temperature (AI 120), outdoor air temperature (AI 145) and building static pressure (AI 1425) accept BMS values after Out_Of_Service is set TRUE. Space Setpoint Type (AV 3725) must be Network for network setpoint control on SCC units.
Network setup
- Defaults: BACnet IP 172.16.83.46, mask 255.255.0.0, UDP 47808; MS/TP MAC 2 (set on the module's dip switches), 19200 baud.
- Device instance = last six digits of the MCB bar-code number; device name MTII SCUC plus the last nine digits.
- Communication parameters are changed with MicroTech II ServiceTools; after changing the communication option do a Reset, Archive and Cold Reset.
Watch out for
- The keypad schedule writes BV 1380 at priority 15; command it at a higher priority and write NULL to give control back.
- Alarm notification AVs show only the highest-priority active alarm of each class.
- Cooling hours and reset-enable objects use proprietary object types that many BMS front ends cannot read.
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 3915 | Unit Status | Unit Status | Read | 1=OffNet, 2=Off Sw, 3=OffAlm, 4=Calib, 5=Startup, 6=Recirc, 7=FanOnly, 8=Econo, 9=Cooling, 10=MWU, 11=Heating, 12=MinDAT, 13=UnocEcon, 14=UnocFanO, 15=UnocDAT, 16=UnocClg, 17=UnocHtg, 18=Balance, 19=OffMan, 20=ManCtrl | |
| AV | 3730 | Cooling Capacity | Cooling Capacity | % | Read | |
| AV | 3805 | Heating Capacity | Heating Capacity | % | Read | |
| AV | 3775 | Cooling Control Status | Cooling Control Status | Read | 0=All Clg, 1=Econo, 2=Mech Clg, 3=Off Amb, 4=Off Alarm, 5=Off None, 6=Off No Flow, 7=Off Sw, 8=Off Net, 9=Off Man | |
| AV | 3825 | Heating Control Status | Heating Control Status | Read | 0=HtEna, 1=OffAmb, 2=OffAlarm, 3=OffNone, 4=N/A, 5=OffSw, 6=OffNet, 7=OffMan | |
| AVmin | 3715 | Application Mode | Unit mode command: heat/cool, off, heat only, cool only, fan only | Write | 0=Heat/Cool, 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly | |
| BV | 3950 | VAV Box Output | VAV box output state (heat/cool) | Read | 0=Heat, 1=Cool | |
| AV | 3920 | Occupancy | Occupancy | Read | 0=Occ, 1=Unocc, 2=Tnt Ovrd | |
| AV | 3930 | Occupancy Mode | Occupancy override; leave on Auto for normal operation | Write | 0=Occ, 1=Unocc, 2=Tnt Ovrd, 3=Auto | |
| BVmin | 1380 | Occupancy Scheduler Input | Occupied/unoccupied command used when Occupancy Mode = Auto | Write | ||
| AV | 3925 | Occupancy Source | Occupancy Source | Read | 0=None, 1=Int Sched, 2=Net Sched, 3=Occ Mode, 4=Remote Sw, 5=N/A | |
| AVmin | 3720 | Emergency Override Mode Flag | Network shutdown (1 = off, unit status OffNet) | Write | 0=Norm, 1=Off | |
| AV | 165 | Control Temperature | Control Temperature | °F | Read | |
| AImin | 135 | Discharge Air Temperature | Discharge Air Temperature | °F | Read | |
| AI | 140 | Return Air Temperature | Return Air Temperature | °F | Read | |
| AI | 120 | Space Temperature | Space Temperature | °F | Read | |
| AI | 145 | Outdoor Air Temperature | Outdoor Air Temperature | °F | Read | |
| AI | 150 | Mixed Air Temp | Mixed Air Temp | °F | Read | |
| AI | 155 | Entering Water Temp | Entering Water Temp | °F | Read | |
| AI | 160 | Leaving Water Temp | Leaving Water Temp | °F | Read | |
| BI | 225 | Water Flow | Water Flow | Read | 0=Yes, 1=No | |
| AV | 3885 | Head Pressure Setpoint | Head Pressure Setpoint | °F | Write | |
| BI | 190 | Airflow Status | Airflow Status | Read | 0=Noflo, 1=Flow | |
| BV | 3935 | Discharge Fan Status | Discharge Fan Status | Read | 0=Off, 1=On | |
| BV | 3945 | Fan Operation Output | Fan Operation Output | Read | 0=Off, 1=On | |
| AV | 3895 | Duct Static Pressure | Duct Static Pressure | inH2O | Read | |
| AVmin | 3840 | Duct Static Pressure Setpoint | Duct Static Pressure Setpoint (default 1.00" WC) | inH2O | Write | |
| AV | 3845 | Discharge Fan Capacity | Discharge Fan Capacity | % | Read | |
| AI | 1425 | Building Static Pressure | Building Static Pressure | inH2O | Read | |
| AV | 3750 | Effective Cooling Enable Setpoint | Effective Cooling Enable Setpoint | °F | Read | |
| AVmin | 3765 | Occupied Cooling Setpoint | Occupied Cooling Setpoint (default 75°F) | °F | Write | |
| AV | 3710 | Control Temperature Source | Control Temperature Source | Write | 0=Return, 1=Space, 2=OAT, 3=MAT | |
| AV | 3900 | Unoccupied Cooling Setpoint | Unoccupied Cooling Setpoint (default 85°F) | °F | Write | |
| AV | 3800 | Effective Heating Enable Setpoint | Effective Heating Enable Setpoint | °F | Read | |
| AVmin | 3820 | Occupied Heating Setpoint | Occupied Heating Setpoint (default 70°F) | °F | Write | |
| AV | 3905 | Unoccupied Heating Setpoint | Unoccupied Heating Setpoint (default 55°F) | °F | Write | |
| AV | 3745 | Effective Cooling Discharge Setpoint | Effective Cooling Discharge Setpoint | °F | Read | |
| AV | 3740 | Discharge Air Cooling Setpoint | Discharge Air Cooling Setpoint (default 55°F) | °F | Write | |
| AV | 3755 | Min Discharge Air Cooling Setpoint | Min Discharge Air Cooling Setpoint (default 55°F) | °F | Write | |
| AV | 3760 | Max Discharge Air Cooling Setpoint | Max Discharge Air Cooling Setpoint (default 65°F) | °F | Write | |
| AI | 1320 | Economizer Valve Position | Economizer Valve Position | % | Read | |
| AI | 1315 | Outdoor Air Damper Position | Outdoor Air Damper Position | % | Read | |
| AV | 3870 | Effective Min Outdoor Damper Pos Spt | Effective Min Outdoor Damper Pos Spt | % | Read | |
| AV | 3875 | Outdoor Air Damper Min Position | Outdoor Air Damper Min Position (default 10%) | % | Write | |
| AV | 3890 | Economizer Changeover Method | Economizer Changeover Method | Write | 0=Enthalpy, 1=Dry Bulb | |
| AV | 3865 | Economizer Changeover Temp Spt | Economizer changeover temperature, dry bulb method (default 60°F) | °F | Write | |
| AV | 3795 | Effective Heating Discharge Setpoint | Effective Heating Discharge Setpoint | °F | Read | |
| AV | 3790 | Discharge Air Heating Setpoint | Discharge Air Heating Setpoint (default 100°F) | °F | Write | |
| AV | 3910 | Min Discharge Air Temperature Limit | Min Discharge Air Temperature Limit (default 55°F) | °F | Write | |
| AV | 3810 | Min Discharge Air Heating Setpoint | Min Discharge Air Heating Setpoint (default 60°F) | °F | Write | |
| AV | 3815 | Max Discharge Air Heating Setpoint | Max Discharge Air Heating Setpoint (default 120°F) | °F | Write | |
| AV | 3785 | Dehumidification Status | Dehumidification Status | Read | 0=False, 1=True | |
| AV | 1505 | Relative Humidity | Relative Humidity | %RH | Read | |
| AV | 660 | Dew Point Temperature | Dew Point Temperature | °F | Read | |
| AV | 3780 | Dehumidification Method | Dehumidification Method | Write | 0=None, 1=RelHum, 2=DewPnt | |
| AV | 3770 | Relative Humidity Setpoint | Relative humidity setpoint, RelHum control (default 50%) | %RH | Write | |
| AV | 3735 | Dew Point Setpoint | Dew point setpoint, DewPnt control (default 50°F) | °F | Write | |
| AV | 3725 | Space Setpoint Type | Setpoint source: thermostat or network (SCC units) | Write | 0=Tstat, 1=Network | |
| BV | 3940 | Outdoor Air Damper Open/Close | Manual force of the outdoor air damper open/closed | Write | 0=Close, 1=Open | |
| BVmin | 4150 | Alarm, Faults: Clear All | Fault alarm active; write to clear all faults | Write | ||
| BV | 4145 | Alarm, Problems: Clear All | Problem alarm active; write to clear all problems | Write | ||
| BV | 4140 | Alarm, Warnings: Clear All | Warning alarm active; write to clear all warnings | Write | ||
| AVmin | 5328 | Alarms-Fault Individual Notification | Highest-priority active fault alarm number | Read | ||
| AV | 5327 | Alarms-Problem Individual Notification | Highest-priority active problem alarm number | Read | ||
| AV | 5326 | Alarms-Warning Individual Notification | Highest-priority active warning alarm number | Read | ||
| SCH | 1385 | Daily Schedule | Keypad daily schedule; writes Occupancy Scheduler Input at priority 15 | Read | ||
| CAL | 1390 | Holiday | Keypad holiday date list | Write |
No points match these filters.
Object ID lookup: Daikin Applied MicroTech II self-contained SWP/SWT point IDs by name
AV3915Unit StatusAV3730Cooling CapacityAV3805Heating CapacityAV3775Cooling Control StatusAV3825Heating Control StatusAV3715Application ModeBV3950VAV Box OutputAV3920OccupancyAV3930Occupancy ModeBV1380Occupancy Scheduler InputAV3925Occupancy SourceAV3720Emergency Override Mode FlagAV165Control TemperatureAI135Discharge Air TemperatureAI140Return Air TemperatureAI120Space TemperatureAI145Outdoor Air TemperatureAI150Mixed Air TempAI155Entering Water TempAI160Leaving Water TempBI225Water FlowAV3885Head Pressure SetpointBI190Airflow StatusBV3935Discharge Fan StatusBV3945Fan Operation OutputAV3895Duct Static PressureAV3840Duct Static Pressure SetpointAV3845Discharge Fan CapacityAI1425Building Static PressureAV3750Effective Cooling Enable SetpointAV3765Occupied Cooling SetpointAV3710Control Temperature SourceAV3900Unoccupied Cooling SetpointAV3800Effective Heating Enable SetpointAV3820Occupied Heating SetpointAV3905Unoccupied Heating SetpointAV3745Effective Cooling Discharge SetpointAV3740Discharge Air Cooling SetpointAV3755Min Discharge Air Cooling SetpointAV3760Max Discharge Air Cooling SetpointAI1320Economizer Valve PositionAI1315Outdoor Air Damper PositionAV3870Effective Min Outdoor Damper Pos SptAV3875Outdoor Air Damper Min PositionAV3890Economizer Changeover MethodAV3865Economizer Changeover Temp SptAV3795Effective Heating Discharge SetpointAV3790Discharge Air Heating SetpointAV3910Min Discharge Air Temperature LimitAV3810Min Discharge Air Heating SetpointAV3815Max Discharge Air Heating SetpointAV3785Dehumidification StatusAV1505Relative HumidityAV660Dew Point TemperatureAV3780Dehumidification MethodAV3770Relative Humidity SetpointAV3735Dew Point SetpointAV3725Space Setpoint TypeBV3940Outdoor Air Damper Open/CloseBV4150Alarm, Faults: Clear AllBV4145Alarm, Problems: Clear AllBV4140Alarm, Warnings: Clear AllAV5328Alarms-Fault Individual NotificationAV5327Alarms-Problem Individual NotificationAV5326Alarms-Warning Individual NotificationSCH1385Daily ScheduleCAL1390Holiday
Integration notes
- Names are the point names from the guide's BACnet table; the guide does not print separate object names for them.
- Six table rows use Daikin proprietary object types (runtime totalization for cooling hours, and application objects for the cooling/heating reset enables and OA ambient); they are left out.
- Space Temperature (AI 120), Outdoor Air Temperature (AI 145), Building Static Pressure (AI 1425) and Water Flow (BI 225) are marked R*: a BMS may write them after setting Out_Of_Service to TRUE.
- Most multistate settings are analog values carrying an enumeration number (e.g. Application Mode AV 3715).
- Points marked NA for SCC or DAC apply only to the other control type; dehumidification objects are SCC only.
- The device instance is factory set to the last six digits of the main control board bar-code number.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
How many BACnet points does the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) have?
This list has 67 BACnet objects: 10 analog inputs, 45 analog values, 2 binary inputs, 8 binary values, 1 calendar, 1 schedule. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet points are writable?
30 of the 67 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet documentation?
The source is MicroTech II Vertical Self-Contained Unit Controller Protocol Information, BACnet Networks, LonWorks Networks (ED 15061-6), revision 2012-05, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15061-6.pdf.
What are the minimum BACnet points to integrate the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)?
Start with AV 3715 Application Mode (Off / heat-cool / heat only / cool only / fan only); BV 1380 Occupancy Scheduler Input (Occupied command; write at priority 8, not 15); AV 3720 Emergency Override Mode Flag (Network shutdown (1 = off)); AV 3765 Occupied Cooling Setpoint (Occupied cooling setpoint); AV 3820 Occupied Heating Setpoint (Occupied heating setpoint); AV 3840 Duct Static Pressure Setpoint (Duct static pressure setpoint (DAC units)); BV 4150 Alarm, Faults: Clear All (Fault alarm flag; write to clear faults); AV 3915 Unit Status (Unit operating state); AI 135 Discharge Air Temperature (Discharge air temperature); AV 5328 Alarms-Fault Individual Notification (Highest-priority active fault number).
How do I enable BMS control of the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)?
Set rocker switch S7 to AUTO and the keypad Control Mode to AUTO (password 4545). Application Mode (AV 3715) then turns the unit off or selects heat/cool, heat only, cool only or fan only; Emergency Override Mode Flag (AV 3720) = 1 shuts it off from the network. Occupancy Mode (AV 3930) is an override and should stay Auto.
Does the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) need a BACnet heartbeat or have a communication timeout?
The guide's receive heartbeat (occupancy scheduler input, application mode, fan capacity, building static pressure, outdoor, return and space temperature, humidity) is a LonWorks feature with no BACnet equivalent. Over BACnet, an input written with Out_Of_Service TRUE keeps its last value if communication is lost.
Can the BMS supply sensor values to the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)?
Space temperature (AI 120), outdoor air temperature (AI 145) and building static pressure (AI 1425) accept BMS values after Out_Of_Service is set TRUE. Space Setpoint Type (AV 3725) must be Network for network setpoint control on SCC units.
How do I check these points on the real MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: MicroTech II Vertical Self-Contained Unit Controller Protocol Information, BACnet Networks, LonWorks Networks · ED 15061-6 · rev. 2012-05. Object names, instances and units are reproduced as published; descriptions are our own.