Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet points list

Updated 6 November 2026

Short answer

The MicroTech II controller on SWP and SWT vertical self-contained units talks BACnet IP or BACnet MS/TP through a communication module (LonWorks is the other option). The table covers unit status, application and occupancy commands, zone and discharge air setpoints, water and air temperatures, duct and building pressure, waterside and airside economizer data, SCC dehumidification, a keypad schedule and calendar, and alarm read and clear objects.

This page lists 67 BACnet objects for the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Equipment
Self-contained unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
67 (30 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Application 1.28
Also known as
ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained
Source document
MicroTech II Vertical Self-Contained Unit Controller Protocol Information, BACnet Networks, LonWorks Networks · ED 15061-6 · rev. 2012-05
Download CSV 67 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)

Integration in brief

Set switch S7 to AUTO and Control Mode to AUTO at the keypad. Leave Occupancy Mode on Auto and command occupancy with the Occupancy Scheduler Input BV at a priority above 15 (e.g. 8). Use Application Mode for on/off, write setpoints as needed and read status, temperatures and the alarm notification values.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 3715Application ModeOff / heat-cool / heat only / cool only / fan onlyWrite
BV 1380Occupancy Scheduler InputOccupied command; write at priority 8, not 15Write
AV 3720Emergency Override Mode FlagNetwork shutdown (1 = off)Write
AV 3765Occupied Cooling SetpointOccupied cooling setpointWrite
AV 3820Occupied Heating SetpointOccupied heating setpointWrite
AV 3840Duct Static Pressure SetpointDuct static pressure setpoint (DAC units)Write
BV 4150Alarm, Faults: Clear AllFault alarm flag; write to clear faultsWrite
AV 3915Unit StatusUnit operating stateRead
AI 135Discharge Air TemperatureDischarge air temperatureRead
AV 5328Alarms-Fault Individual NotificationHighest-priority active fault numberRead

Enable & remote start

Set rocker switch S7 to AUTO and the keypad Control Mode to AUTO (password 4545). Application Mode (AV 3715) then turns the unit off or selects heat/cool, heat only, cool only or fan only; Emergency Override Mode Flag (AV 3720) = 1 shuts it off from the network. Occupancy Mode (AV 3930) is an override and should stay Auto.

Heartbeat & communication loss

The guide's receive heartbeat (occupancy scheduler input, application mode, fan capacity, building static pressure, outdoor, return and space temperature, humidity) is a LonWorks feature with no BACnet equivalent. Over BACnet, an input written with Out_Of_Service TRUE keeps its last value if communication is lost.

Sensors & values from the BMS

Space temperature (AI 120), outdoor air temperature (AI 145) and building static pressure (AI 1425) accept BMS values after Out_Of_Service is set TRUE. Space Setpoint Type (AV 3725) must be Network for network setpoint control on SCC units.

Network setup

Watch out for

Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

67 of 67 shown
Type
Access
Show
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet Points List
DescriptionStates
AVmin3915Unit StatusUnit StatusRead1=OffNet, 2=Off Sw, 3=OffAlm, 4=Calib, 5=Startup, 6=Recirc, 7=FanOnly, 8=Econo, 9=Cooling, 10=MWU, 11=Heating, 12=MinDAT, 13=UnocEcon, 14=UnocFanO, 15=UnocDAT, 16=UnocClg, 17=UnocHtg, 18=Balance, 19=OffMan, 20=ManCtrl
AV3730Cooling CapacityCooling Capacity%Read
AV3805Heating CapacityHeating Capacity%Read
AV3775Cooling Control StatusCooling Control StatusRead0=All Clg, 1=Econo, 2=Mech Clg, 3=Off Amb, 4=Off Alarm, 5=Off None, 6=Off No Flow, 7=Off Sw, 8=Off Net, 9=Off Man
AV3825Heating Control StatusHeating Control StatusRead0=HtEna, 1=OffAmb, 2=OffAlarm, 3=OffNone, 4=N/A, 5=OffSw, 6=OffNet, 7=OffMan
AVmin3715Application ModeUnit mode command: heat/cool, off, heat only, cool only, fan onlyWrite0=Heat/Cool, 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly
BV3950VAV Box OutputVAV box output state (heat/cool)Read0=Heat, 1=Cool
AV3920OccupancyOccupancyRead0=Occ, 1=Unocc, 2=Tnt Ovrd
AV3930Occupancy ModeOccupancy override; leave on Auto for normal operationWrite0=Occ, 1=Unocc, 2=Tnt Ovrd, 3=Auto
BVmin1380Occupancy Scheduler InputOccupied/unoccupied command used when Occupancy Mode = AutoWrite
AV3925Occupancy SourceOccupancy SourceRead0=None, 1=Int Sched, 2=Net Sched, 3=Occ Mode, 4=Remote Sw, 5=N/A
AVmin3720Emergency Override Mode FlagNetwork shutdown (1 = off, unit status OffNet)Write0=Norm, 1=Off
AV165Control TemperatureControl Temperature°FRead
AImin135Discharge Air TemperatureDischarge Air Temperature°FRead
AI140Return Air TemperatureReturn Air Temperature°FRead
AI120Space TemperatureSpace Temperature°FRead
AI145Outdoor Air TemperatureOutdoor Air Temperature°FRead
AI150Mixed Air TempMixed Air Temp°FRead
AI155Entering Water TempEntering Water Temp°FRead
AI160Leaving Water TempLeaving Water Temp°FRead
BI225Water FlowWater FlowRead0=Yes, 1=No
AV3885Head Pressure SetpointHead Pressure Setpoint°FWrite
BI190Airflow StatusAirflow StatusRead0=Noflo, 1=Flow
BV3935Discharge Fan StatusDischarge Fan StatusRead0=Off, 1=On
BV3945Fan Operation OutputFan Operation OutputRead0=Off, 1=On
AV3895Duct Static PressureDuct Static PressureinH2ORead
AVmin3840Duct Static Pressure SetpointDuct Static Pressure Setpoint (default 1.00" WC)inH2OWrite
AV3845Discharge Fan CapacityDischarge Fan Capacity%Read
AI1425Building Static PressureBuilding Static PressureinH2ORead
AV3750Effective Cooling Enable SetpointEffective Cooling Enable Setpoint°FRead
AVmin3765Occupied Cooling SetpointOccupied Cooling Setpoint (default 75°F)°FWrite
AV3710Control Temperature SourceControl Temperature SourceWrite0=Return, 1=Space, 2=OAT, 3=MAT
AV3900Unoccupied Cooling SetpointUnoccupied Cooling Setpoint (default 85°F)°FWrite
AV3800Effective Heating Enable SetpointEffective Heating Enable Setpoint°FRead
AVmin3820Occupied Heating SetpointOccupied Heating Setpoint (default 70°F)°FWrite
AV3905Unoccupied Heating SetpointUnoccupied Heating Setpoint (default 55°F)°FWrite
AV3745Effective Cooling Discharge SetpointEffective Cooling Discharge Setpoint°FRead
AV3740Discharge Air Cooling SetpointDischarge Air Cooling Setpoint (default 55°F)°FWrite
AV3755Min Discharge Air Cooling SetpointMin Discharge Air Cooling Setpoint (default 55°F)°FWrite
AV3760Max Discharge Air Cooling SetpointMax Discharge Air Cooling Setpoint (default 65°F)°FWrite
AI1320Economizer Valve PositionEconomizer Valve Position%Read
AI1315Outdoor Air Damper PositionOutdoor Air Damper Position%Read
AV3870Effective Min Outdoor Damper Pos SptEffective Min Outdoor Damper Pos Spt%Read
AV3875Outdoor Air Damper Min PositionOutdoor Air Damper Min Position (default 10%)%Write
AV3890Economizer Changeover MethodEconomizer Changeover MethodWrite0=Enthalpy, 1=Dry Bulb
AV3865Economizer Changeover Temp SptEconomizer changeover temperature, dry bulb method (default 60°F)°FWrite
AV3795Effective Heating Discharge SetpointEffective Heating Discharge Setpoint°FRead
AV3790Discharge Air Heating SetpointDischarge Air Heating Setpoint (default 100°F)°FWrite
AV3910Min Discharge Air Temperature LimitMin Discharge Air Temperature Limit (default 55°F)°FWrite
AV3810Min Discharge Air Heating SetpointMin Discharge Air Heating Setpoint (default 60°F)°FWrite
AV3815Max Discharge Air Heating SetpointMax Discharge Air Heating Setpoint (default 120°F)°FWrite
AV3785Dehumidification StatusDehumidification StatusRead0=False, 1=True
AV1505Relative HumidityRelative Humidity%RHRead
AV660Dew Point TemperatureDew Point Temperature°FRead
AV3780Dehumidification MethodDehumidification MethodWrite0=None, 1=RelHum, 2=DewPnt
AV3770Relative Humidity SetpointRelative humidity setpoint, RelHum control (default 50%)%RHWrite
AV3735Dew Point SetpointDew point setpoint, DewPnt control (default 50°F)°FWrite
AV3725Space Setpoint TypeSetpoint source: thermostat or network (SCC units)Write0=Tstat, 1=Network
BV3940Outdoor Air Damper Open/CloseManual force of the outdoor air damper open/closedWrite0=Close, 1=Open
BVmin4150Alarm, Faults: Clear AllFault alarm active; write to clear all faultsWrite
BV4145Alarm, Problems: Clear AllProblem alarm active; write to clear all problemsWrite
BV4140Alarm, Warnings: Clear AllWarning alarm active; write to clear all warningsWrite
AVmin5328Alarms-Fault Individual NotificationHighest-priority active fault alarm numberRead
AV5327Alarms-Problem Individual NotificationHighest-priority active problem alarm numberRead
AV5326Alarms-Warning Individual NotificationHighest-priority active warning alarm numberRead
SCH1385Daily ScheduleKeypad daily schedule; writes Occupancy Scheduler Input at priority 15Read
CAL1390HolidayKeypad holiday date listWrite
Object ID lookup: Daikin Applied MicroTech II self-contained SWP/SWT point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)

How many BACnet points does the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) have?

This list has 67 BACnet objects: 10 analog inputs, 45 analog values, 2 binary inputs, 8 binary values, 1 calendar, 1 schedule. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet points are writable?

30 of the 67 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) BACnet documentation?

The source is MicroTech II Vertical Self-Contained Unit Controller Protocol Information, BACnet Networks, LonWorks Networks (ED 15061-6), revision 2012-05, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15061-6.pdf.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)?

Start with AV 3715 Application Mode (Off / heat-cool / heat only / cool only / fan only); BV 1380 Occupancy Scheduler Input (Occupied command; write at priority 8, not 15); AV 3720 Emergency Override Mode Flag (Network shutdown (1 = off)); AV 3765 Occupied Cooling Setpoint (Occupied cooling setpoint); AV 3820 Occupied Heating Setpoint (Occupied heating setpoint); AV 3840 Duct Static Pressure Setpoint (Duct static pressure setpoint (DAC units)); BV 4150 Alarm, Faults: Clear All (Fault alarm flag; write to clear faults); AV 3915 Unit Status (Unit operating state); AI 135 Discharge Air Temperature (Discharge air temperature); AV 5328 Alarms-Fault Individual Notification (Highest-priority active fault number).

How do I enable BMS control of the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)?

Set rocker switch S7 to AUTO and the keypad Control Mode to AUTO (password 4545). Application Mode (AV 3715) then turns the unit off or selects heat/cool, heat only, cool only or fan only; Emergency Override Mode Flag (AV 3720) = 1 shuts it off from the network. Occupancy Mode (AV 3930) is an override and should stay Auto.

Does the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT) need a BACnet heartbeat or have a communication timeout?

The guide's receive heartbeat (occupancy scheduler input, application mode, fan capacity, building static pressure, outdoor, return and space temperature, humidity) is a LonWorks feature with no BACnet equivalent. Over BACnet, an input written with Out_Of_Service TRUE keeps its last value if communication is lost.

Can the BMS supply sensor values to the Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)?

Space temperature (AI 120), outdoor air temperature (AI 145) and building static pressure (AI 1425) accept BMS values after Out_Of_Service is set TRUE. Space Setpoint Type (AV 3725) must be Network for network setpoint control on SCC units.

How do I check these points on the real MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech II Vertical Self-Contained Unit Controller Protocol Information, BACnet Networks, LonWorks Networks · ED 15061-6 · rev. 2012-05. Object names, instances and units are reproduced as published; descriptions are our own.