Variable frequency drive (HVAC) · BACnet points list

Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

The MD5 VFD speaks native BACnet MS/TP on its built-in RS-485 port (embedded fieldbus). The object list is fixed: relay and digital input status, relay and analog output commands, run/stop, direction, run enable and override commands, two references, drive measurements, energy and run-time counters, fault history and a parameter mailbox (AV25/AV26 with BV15/BV16). Most commands only act when the matching drive parameter is set to COMM.

This page lists 72 BACnet objects for the Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP) — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
72 (28 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
MS/TP MAC ID (5302) when 5311 and 5317 are 0
Also known as
MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2
Source document
Daikin Applied MD5 Variable Frequency Drive Controller - Operations Manual · OM 1191-2 · rev. 2023-08
Download CSV 72 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)

Integration in brief

Set 9802 = BACNET (5), the baud in 5303, the device instance in 5311/5317 and the MAC in 5302 (set 5302 last). Set 1001 = COMM and 1103 = COMM, then command BV10 RUN/STOP CMD and AV16 INPUT REF 1. Read BV0, BV2, AV1, AV4 and AV6, and reset faults with BV14. Set 3018/3019 for comm-loss behaviour.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10RUN/STOP CMDStart/stop from the BMSCommand
AV 16INPUT REF 1Speed reference in %Command
BV 14FAULT RESETReset a tripped driveCommand
BV 0RUN/STOP ACTRunning statusRead
BV 4HAND/AUTO ACTShows if the panel has the drive in HandRead
AV 1OUTPUT FREQOutput frequency in HzRead
AV 4CURRENTMotor ampsRead
AV 6POWERDrive power in kWRead
BV 2FAULT ACTAny active drive faultRead
AV 18LAST FLTMost recent fault codeRead

Enable & remote start

Start/stop (BV10) needs parameter 1001 = COMM (EXT1) or 1002 = COMM (EXT2); INPUT REF 1 (AV16) needs 1103 = COMM; run enable (BV12) needs 1601 = COMM; fault reset (BV14) needs 1604 = COMM. BV18 CTL OVERRIDE CMD hands drive control to BACnet from its normal source; panel HAND has priority over it.

Heartbeat & communication loss

3018 COMM FAULT FUNC sets what the drive does on a communication loss (0 not selected, 1 fault, 2 constant speed 7, 3 last speed) and 3019 COMM FAULT TIME sets the delay before it acts.

Sensors & values from the BMS

AV27 EXT PID STPT lets the BMS write the external PID setpoint when 4210 = 19 (INTERNAL).

Network setup

Watch out for

Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

72 of 72 shown
Type
Access
Show
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP) BACnet Points List
DescriptionStates
BI0RO 1 ACTRelay output 1 statusRead0=OFF, 1=ON
BI1RO 2 ACTRelay output 2 statusRead0=OFF, 1=ON
BI2RO 3 ACTRelay output 3 statusRead0=OFF, 1=ON
BI3RO 4 ACTRelay output 4 status (OREL-01 option)Read0=OFF, 1=ON
BI4RO 5 ACTRelay output 5 status (OREL-01 option)Read0=OFF, 1=ON
BI5RO 6 ACTRelay output 6 status (OREL-01 option)Read0=OFF, 1=ON
BI6DI 1 ACTDigital input 1 statusRead0=OFF, 1=ON
BI7DI 2 ACTDigital input 2 statusRead0=OFF, 1=ON
BI8DI 3 ACTDigital input 3 statusRead0=OFF, 1=ON
BI9DI 4 ACTDigital input 4 statusRead0=OFF, 1=ON
BI10DI 5 ACTDigital input 5 statusRead0=OFF, 1=ON
BI11DI 6 ACTDigital input 6 statusRead0=OFF, 1=ON
BO0RO1 COMMANDRelay 1 command (needs 1401 = COMM)Command0=OFF, 1=ON
BO1RO2 COMMANDRelay 2 command (needs 1402 = COMM)Command0=OFF, 1=ON
BO2RO3 COMMANDRelay 3 command (needs 1403 = COMM)Command0=OFF, 1=ON
BO3RO4 COMMANDRelay 4 command (needs 1410 = COMM, OREL-01)Command0=OFF, 1=ON
BO4RO5 COMMANDRelay 5 command (needs 1411 = COMM, OREL-01)Command0=OFF, 1=ON
BO5RO6 COMMANDRelay 6 command (needs 1412 = COMM, OREL-01)Command0=OFF, 1=ON
BVmin0RUN/STOP ACTDrive run status, whatever the control sourceRead0=STOP, 1=RUN
BV1FWD/REV ACTRotation direction, whatever the control sourceRead0=FWD, 1=REV
BVmin2FAULT ACTDrive fault statusRead0=OK, 1=FAULT
BV3EXT 1/2 ACTActive control source (EXT1 or EXT2)Read0=EXT1, 1=EXT2
BVmin4HAND/AUTO ACTHand or Auto controlRead0=AUTO, 1=HAND
BV5ALARM ACTDrive alarm statusRead0=OK, 1=ALARM
BV6MAINT REQMaintenance due (group 29)Read0=OK, 1=MAINT
BV7DRIVE READYReady to accept a run commandRead0=NOT READY, 1=READY
BV8AT SETPOINTDrive at the commanded setpointRead0=NO, 1=YES
BV9RUN ENA ACTRun Enable status, whatever the control sourceRead0=DISABLE, 1=ENABLE
BVmin10RUN/STOP CMDStart/stop command (needs 1001 or 1002 = COMM)Command0=STOP, 1=RUN
BV11FWD/REV CMDDirection command (needs 1003 = REQUEST)Command0=FWD, 1=REV
BV12RUN ENA CMDRun Enable command (needs 1601 = COMM)Command0=DISABLE, 1=ENABLE
BV13EXT 1/2 CMDSelect EXT1 or EXT2 (needs 1102 = COMM)Command0=EXT1, 1=EXT2
BVmin14FAULT RESETFault reset, rising edge (needs 1604 = COMM)Command0=NO, 1=RESET
BV15MBOX READMailbox: read parameter in AV25 into AV26Write0=RESET, 1=READ
BV16MBOX WRITEMailbox: write AV26 to parameter in AV25Write0=RESET, 1=WRITE
BV17LOCK PANELLock keypad parameter changes (parameter 1602)Write0=UNLOCK, 1=LOCK
BV18CTL OVERRIDE CMDPut the drive in BACnet Control OverrideCommand0=OFF, 1=ON
BV19CTL OVERRIDE ACTDrive is in BACnet Control OverrideRead0=OFF, 1=ON
BV20START ENABLE 1Start enable 1 (needs 1608 = COMM)Command0=DISABLE, 1=ENABLE
BV21START ENABLE 2Start enable 2 (needs 1609 = COMM)Command0=DISABLE, 1=ENABLE
AI0ANALOG INPUT 1Analog input 1 (parameter 0120)%Read
AI1ANALOG INPUT 2Analog input 2 (parameter 0121)%Read
AO0AO 1 COMMANDAnalog output 1 value (0135; needs 1501 = 135)%Command
AO1AO 2 COMMANDAnalog output 2 value (0136; needs 1507 = 136)%Command
AV0OUTPUT SPEEDCalculated motor speed (0102)rpmRead
AVmin1OUTPUT FREQOutput frequency (0103)HzRead
AV2DC BUS VOLTDC bus voltage (0107)VRead
AV3OUTPUT VOLTOutput voltage to the motor (0109)VRead
AVmin4CURRENTOutput current (0104)ARead
AV5TORQUEMotor torque, % of nominal (0105)%Read
AVmin6POWEROutput power (0106)kWRead
AV7DRIVE TEMPHeatsink temperature (0110)°CRead
AV8KWH (R)Energy since last reset; resettable (0115)kWhWrite
AV9KWH (NR)Total energy, not resettablekWhRead
AV10PRC PID FBCKProcess PID feedback (0130)%Read
AV11PRC PID DEVProcess PID deviation (0132)%Read
AV12EXT PID FBCKExternal PID feedback (0131)%Read
AV13EXT PID DEVExternal PID deviation (0133)%Read
AV14RUN TIME (R)Run time since last reset; resettable (0114)hWrite
AV15MOTOR TEMPMotor temperature°CRead
AVmin16INPUT REF 1Speed reference 1 (needs 1103 = COMM)%Command
AV17INPUT REF 2Reference 2 or process PID setpoint (needs 1106 setup)%Command
AVmin18LAST FLTMost recent fault code (0401)Read
AV19PREV FLT 1Second most recent fault code (0412)Read
AV20PREV FLT 2Third most recent fault code (0413)Read
AV21AO 1 ACTAnalog output 1 level (0124)mARead
AV22AO 2 ACTAnalog output 2 level (0125)mARead
AV23ACCEL1 TIMERamp 1 acceleration time (2202)sWrite
AV24DECEL1 TIMERamp 1 deceleration time (2203)sWrite
AV25MBOX PARAMMailbox parameter numberWrite
AV26MBOX DATAMailbox parameter valueWrite
AV27EXT PID STPTExternal PID setpoint (4211; needs 4210 = 19)%Command
Object ID lookup: Daikin Applied MD5 Variable Frequency Drive point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MD5 Variable Frequency Drive (embedded BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)

How many BACnet points does the Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP) have?

This list has 72 BACnet objects: 2 analog inputs, 2 analog outputs, 28 analog values, 12 binary inputs, 6 binary outputs, 22 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP) BACnet points are writable?

28 of the 72 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP) BACnet documentation?

The source is Daikin Applied MD5 Variable Frequency Drive Controller - Operations Manual (OM 1191-2), revision 2023-08, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/OM%201191-2.pdf.

What are the minimum BACnet points to integrate the Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)?

Start with BV 10 RUN/STOP CMD (Start/stop from the BMS); AV 16 INPUT REF 1 (Speed reference in %); BV 14 FAULT RESET (Reset a tripped drive); BV 0 RUN/STOP ACT (Running status); BV 4 HAND/AUTO ACT (Shows if the panel has the drive in Hand); AV 1 OUTPUT FREQ (Output frequency in Hz); AV 4 CURRENT (Motor amps); AV 6 POWER (Drive power in kW); BV 2 FAULT ACT (Any active drive fault); AV 18 LAST FLT (Most recent fault code).

How do I enable BMS control of the Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)?

Start/stop (BV10) needs parameter 1001 = COMM (EXT1) or 1002 = COMM (EXT2); INPUT REF 1 (AV16) needs 1103 = COMM; run enable (BV12) needs 1601 = COMM; fault reset (BV14) needs 1604 = COMM. BV18 CTL OVERRIDE CMD hands drive control to BACnet from its normal source; panel HAND has priority over it.

Does the Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

3018 COMM FAULT FUNC sets what the drive does on a communication loss (0 not selected, 1 fault, 2 constant speed 7, 3 last speed) and 3019 COMM FAULT TIME sets the delay before it acts.

Can the BMS supply sensor values to the Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)?

AV27 EXT PID STPT lets the BMS write the external PID setpoint when 4210 = 19 (INTERNAL).

How do I check these points on the real MD5 Variable Frequency Drive (embedded BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.