- MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Water source heat pump controller · BACnet points list
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet points list
Updated 4 November 2026
The MicroTech MT2300 is the controller on Daikin's R32 SmartSource heat pumps. It joins BACnet MS/TP through a separate BACnet communication module, and one object list serves both the SmartSource Series2 and the two-compressor SS2C applications. Points cover setpoints, network overrides for occupancy, mode and space temperature, water and refrigerant temperatures, fan speed, the board's configuration switches, A2L refrigerant-leak inputs and alarm codes.
This page lists 148 BACnet objects for the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) — 73 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
- Equipment
- Water source heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 148 (73 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 3101000 + MS/TP MAC address
- Also known as
- MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Commission the BACnet module (baud, MAC and instance) through its serial menu, then run the unit from the BMS with the network override objects: occupancy (MSV 7 or MSV 8), application mode (MSV 10) and compressor enable (MSV 1). Feed space temperature or a setpoint from the network if needed, and set Receive Heartbeat so overrides drop back when the BMS stops writing.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 7 | OccManCmd | Occupancy override from the BMS | Command |
| MV 10 | ApplicMode | Application mode (Auto/Heat/Cool/Off/Fan Only/Dehumid) | Command |
| MV 1 | ComprEnable | Compressor enable, usually from loop flow proof | Command |
| AV 19 | NetworkSetpoint | Network reference setpoint | Command |
| BV 1 | ClearAlarm | Clear active fault alarms | Write |
| MV 4 | McQWSHPStatus | Unit operating state | Read |
| AV 22 | EffectSpaceTemp | Space temperature used for control | Read |
| AI 2 | LWT | Leaving water temperature | Read |
| MV 2 | CurrentAlarm | Highest-priority active alarm | Read |
Enable & remote start
No local/remote switch. The network override objects act as soon as they are written: Occupancy Override Input (MSV 7) or Occupancy Scheduler (MSV 8) set occupancy, Application Mode (MSV 10) limits the unit to Auto/Heat/Cool/Off/Fan Only/Dehumid and overrides the room sensor mode switch, and Compressor Enable (MSV 1) permits compressor operation. All revert to Null after a controller reboot.
Heartbeat & communication loss
Receive Heartbeat (AV 20, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled) sets how long a supported network override may go without being rewritten before it reverts to its default; each supported override has its own timer. Send Heartbeat (AV 21) is not supported by the BACnet module; use COV instead.
Sensors & values from the BMS
Write space temperature to AV 18 and space humidity to AV 45; a network dewpoint goes to AV 51. AV 19 sets the reference setpoint only after local setpoint adjust is disabled with MSV 14 = 1. AV 35 shifts the occupied/standby setpoints, MSV 9 takes a network occupancy sensor, MSV 16 overrides the humidistat and MSV 3 the fan On/Auto switch.
Network setup
- Device instance is System Minimum Instance (AV 412, default 3101000) plus the MS/TP MAC address.
- Baud (default 38400) and Max Masters are set from the module's serial menu: DB-9 port, 19200 bps 8-N-1, null-modem cable; press S to save.
- With address switch S3 at 255 (factory default) the MAC is acquired during commissioning and can then be changed through AV 411; any other S3 value is used as a fixed MAC.
- Max APDU length is fixed at 480.
Watch out for
- cp... configuration objects are written to flash; do not write them cyclically.
- Network overrides revert to Null on reboot, so the BMS must restore them.
- Changing Units (MSV 15) from English to Metric changes the temperature values the BMS reads.
- An A2L refrigerant leak or loss of A2L board power puts the unit into an alarm state.
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | LocalSpaceTemp | Local Space Temperature | °F | Read | |
| AImin | 2 | LWT | Leaving Water Temperature | °F | Read | |
| AI | 3 | EWT | Entering Water Temperature | °F | Read | |
| AI | 4 | DischAirTemp | Discharge Air Temperature | °F | Read | |
| AI | 5 | LocalSetpt | Local Setpoint Adjust | °F | Read | |
| AI | 6 | Comp1SuctionTemp | Compressor 1 Suction Temperature | °F | Read | |
| AI | 7 | Comp2SuctionTemp | Compressor 2 Suction Temperature | °F | Read | |
| AI | 8 | Brownout | Brownout Voltage Reading | counts | Read | |
| AI | 9 | LocalSpaceRH | Local Space Humidity | % | Read | |
| AI | 10 | RAT | Return Air Temperature | °F | Read | |
| AV | 1 | cpOccupied_Cool_Setpt | Occupied Cooling Setpoint | °F | Write | |
| AV | 2 | cpStandby_Cool_Setpt | Standby Cool Setpoint | °F | Write | |
| AV | 3 | cpUnoccupied_Cool_Setpt | Unoccupied Cool Setpoint | °F | Write | |
| AV | 4 | cpOccupied_Heat_Setpt | Occupied Heat Setpoint | °F | Write | |
| AV | 5 | cpStandby_Heat_Setpt | Standby Heat Setpoint | °F | Write | |
| AV | 6 | cpUnoccupied_Heat_Setpt | Unoccupied Heat Setpoint | °F | Write | |
| AV | 7 | cpBypassTime | Local Bypass Time Setpoint | min | Write | |
| AV | 8 | cpIntStgOffTmr | Interstage OFF Timer | s | Write | |
| AV | 9 | cpBrownoutRef | Brownout Reference Setpoint | counts | Write | |
| AV | 10 | cpOccDiff | Occupied Setpoint Differential | °F | Write | |
| AV | 11 | cpLowTempProtGL | Compressor Low Suction Temp Protection Setpoint: Glycol | °F | Write | |
| AV | 12 | cpLowTempProt | Compressor Low Suction Temp Protection Setpoint: Water | °F | Write | |
| AV | 13 | cpLowTmpProtDif | Compressor Low Suction Temp Protection Differential | °F | Write | |
| AV | 14 | cpIntStgOnTmr | Interstage ON Timer | s | Write | |
| AV | 15 | cpMinCompOffTmr | Compressor Minimum OFF Timer | s | Write | |
| AV | 16 | cpMinCompOnTmr | Compressor Minimum ON Timer | s | Write | |
| AV | 17 | cpUnoccDiff | Unoccupied Setpoint Differential | °F | Write | |
| AV | 18 | Network SpaceTemp | Space Temperature Input | °F | Command | |
| AVmin | 19 | NetworkSetpoint | Network Temperature Setpoint | °F | Command | |
| AV | 20 | cpRcvHrtBt | Receive Heartbeat | s | Write | |
| AV | 21 | cpSndHrtBt | Send Heartbeat | s | Write | |
| AVmin | 22 | EffectSpaceTemp | Effective Space Temperature Output | °F | Read | |
| AV | 23 | EffectSetpt | Effective Setpoint Output | °F | Read | |
| AV | 24 | SetptShift | Setpoint Shift Output | °F | Read | |
| AV | 25 | cpSptAdjMax | Long Range Setpoint Adjust Maximum | °F | Write | |
| AV | 26 | cpSptAdjMin | Long Range Setpoint Adjust Minimum | °F | Write | |
| AV | 27 | cpHydroClgOnSpt | Hydronic Cooling ON Setpoint | °F | Write | |
| AV | 28 | cpHydronicDiff | Hydronic Setpoint Differential | °F | Write | |
| AV | 29 | cpLowLwtDiff | Low Leaving Water Temp Differential | °F | Write | |
| AV | 30 | cpLowEwtSptGly | Low EWT Setpoint for Glycol | °F | Write | |
| AV | 31 | cpLowEwtSptWtr | Low EWT Setpoint for Water | °F | Write | |
| AV | 32 | cpHydroHtgOnSpt | Hydronic Heating ON Setpoint | °F | Write | |
| AV | 33 | cpStg2SptDiff | Second Stage Setpoints Differential | °F | Write | |
| AV | 34 | cpLowPresAlmDly | Compressor Low Pressure Alarm Delay | s | Write | |
| AV | 35 | SetptOffset | Temperature Setpoint Offset Input | °F | Command | |
| AV | 36 | cpStg3SptDiff | Third Stage Heating Setpoint Differential | °F | Write | |
| AV | 37 | cpStg4SptDiff | Fourth Stage Heating Setpoint Differential | °F | Write | |
| AV | 38 | FanSpeedCmd | Fan Speed Output | % | Read | |
| AV | 39 | FanRunHours | Fan Run Hours | h | Write | |
| AV | 40 | CompRunHours | Compressor 1 Run Hours | h | Write | |
| AV | 41 | CompStarts | Compressor 1 Starts | Write | ||
| AV | 42 | Comp2RunHours / CompHiCapRunHours | Compressor 2 / Compressor High Capacity Run Hours | h | Write | |
| AV | 43 | Comp2Starts / CompHiCapStarts | Compressor 2 / Compressor High Capacity Starts | Write | ||
| AV | 44 | EffectSpaceRH | Effective Space Humidity | % | Read | |
| AV | 45 | NetworkSpaceRH | Network Space Humidity Override | % | Command | |
| AV | 46 | cpSpaceRH_Diff | Space Humidity Setpoint Differential | % | Write | |
| AV | 47 | cpSpaceRH_Setpt | Space Humidity Setpoint | % | Write | |
| AV | 48 | EffectControlTemp | Effective Control Temperature | °F | Read | |
| AV | 49 | cpWaitForFlow | Compressor Wait for Flow Timer | s | Write | |
| AV | 50 | LocalDewpointCalc | Local Space Dewpoint | °F | Read | |
| AV | 51 | NetworkDewpoint | Network Dewpoint Override | °F | Command | |
| AV | 52 | EffectiveDewpoint | Effective Dewpoint | °F | Read | |
| AV | 53 | cpDewpointSetp | Dewpoint Setpoint | °F | Write | |
| AV | 54 | cpDewpointDiff | Dewpoint Differential | °F | Write | |
| AV | 55 | cpVsFanOnlyPWM | Variable Fan Speed PWM - Fan-Only | % | Write | |
| AV | 56 | cpVsDehumPWM | Variable Fan Speed PWM - Dehumidification | % | Write | |
| AV | 57 | cpVsCool1PWM | Variable Fan Speed PWM - Cool Stage 1 | % | Write | |
| AV | 58 | cpVsCool2PWM | Variable Fan Speed PWM -Cool Stage 2 | % | Write | |
| AV | 59 | cpVsHeat1PWM | Variable Fan Speed PWM - Heat Stage 1 | % | Write | |
| AV | 60 | cpVsHeat2PWM | Variable Fan Speed PWM - Heat Stage 2 | % | Write | |
| AV | 61 | cpVsElecHeatPWM | Variable Fan Speed PWM - Electric Heat | % | Write | |
| AV | 62 | cpVsHydroHeatPWM | Variable Fan Speed PWM - Hydronic Heat | % | Write | |
| AV | 63 | cpVsHydroCoolPWM | Variable Fan Speed PWM - Hydronic Cool | % | Write | |
| AV | 411 | MacAddress | MAC Address / Address Switch (named MacAddressSwitch, read-only, when switch S3 is below 255) | Write | ||
| AV | 412 | SystemMinInstance | System Minimum Instance | Write | ||
| BI | 1 | A2L_Fault | A2L Board Fault | Read | 0=Alarm; 1=Normal | |
| BI | 2 | EmergShutDn | Emergency Shutdown | Read | 0=Normal; 1=Shutdown | |
| BI | 3 | HiPressure1 | Compressor 1 High Pressure | Read | 0=Normal; 1=Alarm | |
| BI | 4 | LoPressure1 | Compressor 1 Low Pressure | Read | 0=Normal; 1=Alarm | |
| BI | 5 | Tstat_G | Thermostat Fan Input | Read | 0=Off (Auto); 1=On | |
| BI | 6 | Tstat_W1 | Thermostat - Heating Stage 1 | Read | 0=Inactive; 1=Active | |
| BI | 7 | Tstat_W2 | Thermostat - Heating Stage 2 | Read | 0=Inactive; 1=Active | |
| BI | 8 | Tstat_Y1 | Thermostat - Cooling Stage 1 | Read | 0=Inactive; 1=Active | |
| BI | 9 | Tstat_Y2 | Thermostat - Cooling Stage 2 | Read | 0=Inactive; 1=Active | |
| BI | 10 | OccSw_In | Occupancy Switch Setting | Read | 0=Off; 1=On | |
| BI | 11 | HiPressure2 | Compressor 2 High Pressure | Read | 0=Normal; 1=Alarm | |
| BI | 12 | LoPressure2 | Compressor 2 Low Pressure | Read | 0=Normal; 1=Alarm | |
| BI | 13 | Tstat_W3 | Thermostat - Heating Stage 3 | Read | 0=Inactive; 1=Active | |
| BI | 14 | Tstat_W4_Y3 | Thermostat - Heating Stage 4 / Cooling Stage 3 | Read | 0=Inactive; 1=Active | |
| BI | 15 | BB_ConfigSw1 | Unit Operation | Read | 0=Off; 1=On | |
| BI | 16 | BB_ConfigSw2 | Fan Operation | Read | 0=Off; 1=On | |
| BI | 17 | BB_ConfigSw3 | Loop Fluid | Read | 0=Off; 1=On | |
| BI | 18 | BB_ConfigSw4 | Freeze Fault Protection | Read | 0=Off; 1=On | |
| BI | 19 | BB_ConfigSw5 | Room Sensor Setpoint Adjust | Read | 0=Off; 1=On | |
| BI | 20 | BB_ConfigSw6 | Thermostat/Room Sensor | Read | 0=Off; 1=On | |
| BI | 21 | BB_ConfigSw7 | Config switch 7: Compressor Heating Enable (Series2) / Compressor Availability (SS2C) | Read | 0=Off; 1=On | |
| BI | 22 | BB_ConfigSw8 | Config switch 8: I/O Expansion Module (Series2) / Compressor Availability (SS2C) | Read | 0=Off; 1=On | |
| BI | 23 | BB_ConfigSw9 | Baseboard Application Select | Read | 0=Off; 1=On | |
| BI | 24 | BB_ConfigSw10 | Discrete Variable Fan Select | Read | 0=Off; 1=On | |
| BI | 25 | IO_ConfigSw1 | Variable Fan Speed Selection (switch 1) | Read | ||
| BI | 26 | IO_ConfigSw2 | Variable Fan Speed Selection (switch 2) | Read | ||
| BI | 27 | IO_ConfigSw3 | Variable Fan Speed Selection (switch 3) | Read | ||
| BI | 28 | IO_ConfigSw4 | Variable Fan Speed Selection (switch 4) | Read | ||
| BI | 29 | IO_ConfigSw5 | Secondary Heating Options | Read | 0=Off; 1=On | |
| BI | 30 | IO_ConfigSw6 | Secondary Heating Options (switch 6) | Read | ||
| BI | 31 | IO_ConfigSw7 | Hot Gas Reheat (HGR) | Read | 0=Off; 1=On | |
| BI | 32 | IO_ConfigSw8 | Waterside Economizer (WSE) | Read | 0=Off; 1=On | |
| BI | 33 | IO_ConfigSw9 | I/O Expansion Module Application Select | Read | 0=Off; 1=On | |
| BI | 34 | IO_ConfigSw10 | Compressor Dual Speed Option (Series2) / Lead Compressor Select (SS2C) | Read | 0=Off; 1=On | |
| BI | 35 | Humidistat | Humidistat Input | Read | 0=Inactive; 1=Active | |
| BO | 1 | Alarm | Thermostat Alarm | Read | 0=Alarm output command is Off (0 VAC); 1=Alarm output command is On (24 VAC) | |
| BO | 2 | Comp1Out | Compressor 1 | Read | 0=Compressor 1 command is Off; 1=Compressor 1 command is On | |
| BO | 3 | FanMainOut | Fan Main Enable | Read | 0=Fan main command is Off; 1=Fan main command is On | |
| BO | 4 | FanLowOut | Fan Speed | Read | 0=Fan high speed command is On; 1=Fan low speed command is On | |
| BO | 5 | PumpOut | Pump Request | Read | 0=Pump command is Off; 1=Pump command is On | |
| BO | 6 | RevVlv1Out | Reversing Valve 1 | Read | 0=Reversing valve 1 command is Off (cooling); 1=Reversing valve 1 command is On (heating) | |
| BO | 7 | Comp2Out | Compressor 2 / Compressor High Capacity | Read | 0=Compressor 2 command is Off; 1=Compressor 2 command is On | |
| BO | 8 | RevVlv2Out | Reversing Valve 2 | Read | 0=Reversing valve 2 command is Off (cooling); 1=Reversing valve 2 command is On (heating) | |
| BO | 9 | AuxHeat1Out | Auxiliary Heat 1 | Read | 0=Electric heat 1 command is Off; 1=Electric heat 1 command is On | |
| BO | 10 | AuxHeat2Out | Auxiliary Heat 2 | Read | 0=Electric heat 2 command is Off; 1=Electric heat 2 command is On | |
| BO | 11 | HGR_Out | Hot Gas Reheat | Read | 0=HGR command is Off (valve is closed); 1=HGR command is On (valve is open) | |
| BO | 12 | WSE_Out | Waterside Economizer | Read | 0=WSE command is Off (valve is closed); 1=WSE command is On (valve is open) | |
| BVmin | 1 | ClearAlarm | Clear Alarm | Write | 0=Normal; 1=Clear Alarm | |
| MI | 1 | CondOverFlow | Condensate Overflow Status | Read | 1=Dry; 2=Wet; 3=Null | |
| MI | 2 | FanOnAuto | Fan On/Auto Switch Status (Room Sensor) | Read | 1=On; 2=Auto; 3=Null | |
| MI | 3 | HeatCoolAuto | System Mode Switch (Heat/Cool/Auto) Status | Read | 1=Off; 2=Heat; 3=Cool; 4=Auto; 5=Null | |
| MI | 4 | DehumRequired | Dehumidification Required | Read | 1=Dehumid not Required; 2=Dehumid Required; 3=Null | |
| MI | 5 | FanRunStatus | Fan Run Status | Read | 1=Fan is Off; 2=Fan is On | |
| MVmin | 1 | ComprEnable | Compressor Enable Input | Command | 1=Disabled; 2=Enabled; 3=Null (Compressors Enabled) | |
| MVmin | 2 | CurrentAlarm | Current Alarm | Read | Alarm number 1-28 (see the alarm table in the guide) | |
| MV | 3 | NetworkFanOnAuto | Network Fan On/Auto Input | Command | 1=Fan Auto; 2=Fan On; 3=Null | |
| MVmin | 4 | McQWSHPStatus | Unit Status | Read | 1=Off Alarm; 2=Off; 3=Start; 4=Fan Only; 5=Prepare to Heat; 6=Heating; 7=Prepare to Cool; 8=Cooling; 9=Prepare to Dehumidify; 10=Dehumidification | |
| MV | 5 | PreviousAlarm | Previous Alarm | Read | Alarm number 1-28 (see the alarm table in the guide) | |
| MV | 6 | EffectOccup | Effective Occupancy | Read | 1=Occupied; 2=Unoccupied; 3=Bypass; 4=Standby; 5=Null | |
| MVmin | 7 | OccManCmd | Occupancy Override Input | Command | 1=Occupied; 2=Unoccupied; 3=Bypass; 4=Standby; 5=Null | |
| MV | 8 | OccSchedule | Occupancy Scheduler | Command | 1=Occupied; 2=Unoccupied; 3=Standby; 4=Null | |
| MV | 9 | OccSensor | Occupancy Sensor | Command | 1=Occupied; 2=Unoccupied; 3=Null | |
| MVmin | 10 | ApplicMode | Application Mode | Command | 1=Auto; 2=Heat; 3=Cool; 4=Off; 5=Fan Only; 6=Dehumid; 7=Null | |
| MV | 11 | AuxHeatEnable | Auxiliary Heat Enable | Command | 1=Disabled; 2=Enabled; 3=Null | |
| MV | 12 | EnergyHoldOff | Energy Hold Off | Command | 1=Normal; 2=Energy Hold Off; 3=Null | |
| MV | 13 | PumpRequest | Pump Request Output | Read | 1=No Request for Flow; 2=Request for Flow; 3=Null | |
| MV | 14 | cpLocSpEnable | Room Sensor Setpoint Adjust Enable/Disable | Write | 1=Disabled; 2=Enabled | |
| MV | 15 | Units | Units (English/Metric) | Write | 1=English (E); 2=Metric (M) | |
| MV | 16 | NetworkHumidistat | Network Humidistat Input | Command | 1=No Dehumid Request; 2=Request Dehumid; 3=Null | |
| MV | 17 | cpNetVsCnfgEn | Network Variable Speed Fan Enable | Write | 1=Disabled; 2=Enabled; 3=Null | |
| MV | 18 | cpSpaceDehumCnfg | Space Dehumidification Method | Write | 1=Relative Humidity; 2=Dewpoint; 3=Null | |
| MV | 19 | cpSpaceRHSensor | Space Relative Humidity Sensor | Write | 1=Not Installed; 2=Installed; 3=Null | |
| MV | 20 | cpControlTempSrc | Control Temperature Source | Write | 1=Space; 2=Return; 3=Average; 4=Null |
No points match these filters.
Object ID lookup: Daikin Applied MT2300 SmartSource R32 WSHP point IDs by name
AI1LocalSpaceTempAI2LWTAI3EWTAI4DischAirTempAI5LocalSetptAI6Comp1SuctionTempAI7Comp2SuctionTempAI8BrownoutAI9LocalSpaceRHAI10RATAV1cpOccupied_Cool_SetptAV2cpStandby_Cool_SetptAV3cpUnoccupied_Cool_SetptAV4cpOccupied_Heat_SetptAV5cpStandby_Heat_SetptAV6cpUnoccupied_Heat_SetptAV7cpBypassTimeAV8cpIntStgOffTmrAV9cpBrownoutRefAV10cpOccDiffAV11cpLowTempProtGLAV12cpLowTempProtAV13cpLowTmpProtDifAV14cpIntStgOnTmrAV15cpMinCompOffTmrAV16cpMinCompOnTmrAV17cpUnoccDiffAV18Network SpaceTempAV19NetworkSetpointAV20cpRcvHrtBtAV21cpSndHrtBtAV22EffectSpaceTempAV23EffectSetptAV24SetptShiftAV25cpSptAdjMaxAV26cpSptAdjMinAV27cpHydroClgOnSptAV28cpHydronicDiffAV29cpLowLwtDiffAV30cpLowEwtSptGlyAV31cpLowEwtSptWtrAV32cpHydroHtgOnSptAV33cpStg2SptDiffAV34cpLowPresAlmDlyAV35SetptOffsetAV36cpStg3SptDiffAV37cpStg4SptDiffAV38FanSpeedCmdAV39FanRunHoursAV40CompRunHoursAV41CompStartsAV42Comp2RunHours / CompHiCapRunHoursAV43Comp2Starts / CompHiCapStartsAV44EffectSpaceRHAV45NetworkSpaceRHAV46cpSpaceRH_DiffAV47cpSpaceRH_SetptAV48EffectControlTempAV49cpWaitForFlowAV50LocalDewpointCalcAV51NetworkDewpointAV52EffectiveDewpointAV53cpDewpointSetpAV54cpDewpointDiffAV55cpVsFanOnlyPWMAV56cpVsDehumPWMAV57cpVsCool1PWMAV58cpVsCool2PWMAV59cpVsHeat1PWMAV60cpVsHeat2PWMAV61cpVsElecHeatPWMAV62cpVsHydroHeatPWMAV63cpVsHydroCoolPWMAV411MacAddressAV412SystemMinInstanceBI1A2L_FaultBI2EmergShutDnBI3HiPressure1BI4LoPressure1BI5Tstat_GBI6Tstat_W1BI7Tstat_W2BI8Tstat_Y1BI9Tstat_Y2BI10OccSw_InBI11HiPressure2BI12LoPressure2BI13Tstat_W3BI14Tstat_W4_Y3BI15BB_ConfigSw1BI16BB_ConfigSw2BI17BB_ConfigSw3BI18BB_ConfigSw4BI19BB_ConfigSw5BI20BB_ConfigSw6BI21BB_ConfigSw7BI22BB_ConfigSw8BI23BB_ConfigSw9BI24BB_ConfigSw10BI25IO_ConfigSw1BI26IO_ConfigSw2BI27IO_ConfigSw3BI28IO_ConfigSw4BI29IO_ConfigSw5BI30IO_ConfigSw6BI31IO_ConfigSw7BI32IO_ConfigSw8BI33IO_ConfigSw9BI34IO_ConfigSw10BI35HumidistatBO1AlarmBO2Comp1OutBO3FanMainOutBO4FanLowOutBO5PumpOutBO6RevVlv1OutBO7Comp2OutBO8RevVlv2OutBO9AuxHeat1OutBO10AuxHeat2OutBO11HGR_OutBO12WSE_OutBV1ClearAlarmMI1CondOverFlowMI2FanOnAutoMI3HeatCoolAutoMI4DehumRequiredMI5FanRunStatusMV1ComprEnableMV2CurrentAlarmMV3NetworkFanOnAutoMV4McQWSHPStatusMV5PreviousAlarmMV6EffectOccupMV7OccManCmdMV8OccScheduleMV9OccSensorMV10ApplicModeMV11AuxHeatEnableMV12EnergyHoldOffMV13PumpRequestMV14cpLocSpEnableMV15UnitsMV16NetworkHumidistatMV17cpNetVsCnfgEnMV18cpSpaceDehumCnfgMV19cpSpaceRHSensorMV20cpControlTempSrc
Integration notes
- Configuration objects (names starting with cp) are stored in flash; the guide warns that repeated writes wear it out.
- Network override objects (access C) revert to their default (Null) after a controller reboot.
- BI 15-34 report the baseboard and I/O expansion module configuration switches; some switches mean different things on Series2 and SS2C units.
- AV 411 is named MacAddress (writable) when address switch S3 is at 255, otherwise MacAddressSwitch (read-only).
- MV 2 and MV 5 return the alarm numbers from the guide's alarm table (1-28).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
How many BACnet points does the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) have?
This list has 148 BACnet objects: 10 analog inputs, 65 analog values, 35 binary inputs, 12 binary outputs, 1 binary value, 5 multi-state inputs, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet points are writable?
73 of the 148 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet documentation?
The source is MicroTech SmartSource WSHP BACnet Network Integration Guide (MT2300, R32) (ED 19129-1), revision 2024-05, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MT%20SmartSource%20WSHP%20BACnet%20Protocol%20Document%20ED%2019129-1.pdf/.
What are the minimum BACnet points to integrate the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)?
Start with MV 7 OccManCmd (Occupancy override from the BMS); MV 10 ApplicMode (Application mode (Auto/Heat/Cool/Off/Fan Only/Dehumid)); MV 1 ComprEnable (Compressor enable, usually from loop flow proof); AV 19 NetworkSetpoint (Network reference setpoint); BV 1 ClearAlarm (Clear active fault alarms); MV 4 McQWSHPStatus (Unit operating state); AV 22 EffectSpaceTemp (Space temperature used for control); AI 2 LWT (Leaving water temperature); MV 2 CurrentAlarm (Highest-priority active alarm).
How do I enable BMS control of the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)?
No local/remote switch. The network override objects act as soon as they are written: Occupancy Override Input (MSV 7) or Occupancy Scheduler (MSV 8) set occupancy, Application Mode (MSV 10) limits the unit to Auto/Heat/Cool/Off/Fan Only/Dehumid and overrides the room sensor mode switch, and Compressor Enable (MSV 1) permits compressor operation. All revert to Null after a controller reboot.
Does the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) need a BACnet heartbeat or have a communication timeout?
Receive Heartbeat (AV 20, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled) sets how long a supported network override may go without being rewritten before it reverts to its default; each supported override has its own timer. Send Heartbeat (AV 21) is not supported by the BACnet module; use COV instead.
Can the BMS supply sensor values to the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)?
Write space temperature to AV 18 and space humidity to AV 45; a network dewpoint goes to AV 51. AV 19 sets the reference setpoint only after local setpoint adjust is disabled with MSV 14 = 1. AV 35 shifts the occupied/standby setpoints, MSV 9 takes a network occupancy sensor, MSV 16 overrides the humidistat and MSV 3 the fan On/Auto switch.
How do I check these points on the real MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: MicroTech SmartSource WSHP BACnet Network Integration Guide (MT2300, R32) · ED 19129-1 · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.