Water source heat pump controller · BACnet points list

Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet points list

Updated 4 November 2026

Short answer

The MicroTech MT2300 is the controller on Daikin's R32 SmartSource heat pumps. It joins BACnet MS/TP through a separate BACnet communication module, and one object list serves both the SmartSource Series2 and the two-compressor SS2C applications. Points cover setpoints, network overrides for occupancy, mode and space temperature, water and refrigerant temperatures, fan speed, the board's configuration switches, A2L refrigerant-leak inputs and alarm codes.

This page lists 148 BACnet objects for the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) — 73 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.

Manufacturer
Daikin Applied
Model
MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Equipment
Water source heat pump controller
Equipment type
Heat pumps
BACnet objects
148 (73 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
3101000 + MS/TP MAC address
Also known as
MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129
Source document
MicroTech SmartSource WSHP BACnet Network Integration Guide (MT2300, R32) · ED 19129-1 · rev. 2024-05
Download CSV 148 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.

BMS integration notes: Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)

Integration in brief

Commission the BACnet module (baud, MAC and instance) through its serial menu, then run the unit from the BMS with the network override objects: occupancy (MSV 7 or MSV 8), application mode (MSV 10) and compressor enable (MSV 1). Feed space temperature or a setpoint from the network if needed, and set Receive Heartbeat so overrides drop back when the BMS stops writing.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 7OccManCmdOccupancy override from the BMSCommand
MV 10ApplicModeApplication mode (Auto/Heat/Cool/Off/Fan Only/Dehumid)Command
MV 1ComprEnableCompressor enable, usually from loop flow proofCommand
AV 19NetworkSetpointNetwork reference setpointCommand
BV 1ClearAlarmClear active fault alarmsWrite
MV 4McQWSHPStatusUnit operating stateRead
AV 22EffectSpaceTempSpace temperature used for controlRead
AI 2LWTLeaving water temperatureRead
MV 2CurrentAlarmHighest-priority active alarmRead

Enable & remote start

No local/remote switch. The network override objects act as soon as they are written: Occupancy Override Input (MSV 7) or Occupancy Scheduler (MSV 8) set occupancy, Application Mode (MSV 10) limits the unit to Auto/Heat/Cool/Off/Fan Only/Dehumid and overrides the room sensor mode switch, and Compressor Enable (MSV 1) permits compressor operation. All revert to Null after a controller reboot.

Heartbeat & communication loss

Receive Heartbeat (AV 20, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled) sets how long a supported network override may go without being rewritten before it reverts to its default; each supported override has its own timer. Send Heartbeat (AV 21) is not supported by the BACnet module; use COV instead.

Sensors & values from the BMS

Write space temperature to AV 18 and space humidity to AV 45; a network dewpoint goes to AV 51. AV 19 sets the reference setpoint only after local setpoint adjust is disabled with MSV 14 = 1. AV 35 shifts the occupied/standby setpoints, MSV 9 takes a network occupancy sensor, MSV 16 overrides the humidistat and MSV 3 the fan On/Auto switch.

Network setup

Watch out for

Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

148 of 148 shown
Type
Access
Show
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet Points List
DescriptionStates
AI1LocalSpaceTempLocal Space Temperature°FRead
AImin2LWTLeaving Water Temperature°FRead
AI3EWTEntering Water Temperature°FRead
AI4DischAirTempDischarge Air Temperature°FRead
AI5LocalSetptLocal Setpoint Adjust°FRead
AI6Comp1SuctionTempCompressor 1 Suction Temperature°FRead
AI7Comp2SuctionTempCompressor 2 Suction Temperature°FRead
AI8BrownoutBrownout Voltage ReadingcountsRead
AI9LocalSpaceRHLocal Space Humidity%Read
AI10RATReturn Air Temperature°FRead
AV1cpOccupied_Cool_SetptOccupied Cooling Setpoint°FWrite
AV2cpStandby_Cool_SetptStandby Cool Setpoint°FWrite
AV3cpUnoccupied_Cool_SetptUnoccupied Cool Setpoint°FWrite
AV4cpOccupied_Heat_SetptOccupied Heat Setpoint°FWrite
AV5cpStandby_Heat_SetptStandby Heat Setpoint°FWrite
AV6cpUnoccupied_Heat_SetptUnoccupied Heat Setpoint°FWrite
AV7cpBypassTimeLocal Bypass Time SetpointminWrite
AV8cpIntStgOffTmrInterstage OFF TimersWrite
AV9cpBrownoutRefBrownout Reference SetpointcountsWrite
AV10cpOccDiffOccupied Setpoint Differential°FWrite
AV11cpLowTempProtGLCompressor Low Suction Temp Protection Setpoint: Glycol°FWrite
AV12cpLowTempProtCompressor Low Suction Temp Protection Setpoint: Water°FWrite
AV13cpLowTmpProtDifCompressor Low Suction Temp Protection Differential°FWrite
AV14cpIntStgOnTmrInterstage ON TimersWrite
AV15cpMinCompOffTmrCompressor Minimum OFF TimersWrite
AV16cpMinCompOnTmrCompressor Minimum ON TimersWrite
AV17cpUnoccDiffUnoccupied Setpoint Differential°FWrite
AV18Network SpaceTempSpace Temperature Input°FCommand
AVmin19NetworkSetpointNetwork Temperature Setpoint°FCommand
AV20cpRcvHrtBtReceive HeartbeatsWrite
AV21cpSndHrtBtSend HeartbeatsWrite
AVmin22EffectSpaceTempEffective Space Temperature Output°FRead
AV23EffectSetptEffective Setpoint Output°FRead
AV24SetptShiftSetpoint Shift Output°FRead
AV25cpSptAdjMaxLong Range Setpoint Adjust Maximum°FWrite
AV26cpSptAdjMinLong Range Setpoint Adjust Minimum°FWrite
AV27cpHydroClgOnSptHydronic Cooling ON Setpoint°FWrite
AV28cpHydronicDiffHydronic Setpoint Differential°FWrite
AV29cpLowLwtDiffLow Leaving Water Temp Differential°FWrite
AV30cpLowEwtSptGlyLow EWT Setpoint for Glycol°FWrite
AV31cpLowEwtSptWtrLow EWT Setpoint for Water°FWrite
AV32cpHydroHtgOnSptHydronic Heating ON Setpoint°FWrite
AV33cpStg2SptDiffSecond Stage Setpoints Differential°FWrite
AV34cpLowPresAlmDlyCompressor Low Pressure Alarm DelaysWrite
AV35SetptOffsetTemperature Setpoint Offset Input°FCommand
AV36cpStg3SptDiffThird Stage Heating Setpoint Differential°FWrite
AV37cpStg4SptDiffFourth Stage Heating Setpoint Differential°FWrite
AV38FanSpeedCmdFan Speed Output%Read
AV39FanRunHoursFan Run HourshWrite
AV40CompRunHoursCompressor 1 Run HourshWrite
AV41CompStartsCompressor 1 StartsWrite
AV42Comp2RunHours / CompHiCapRunHoursCompressor 2 / Compressor High Capacity Run HourshWrite
AV43Comp2Starts / CompHiCapStartsCompressor 2 / Compressor High Capacity StartsWrite
AV44EffectSpaceRHEffective Space Humidity%Read
AV45NetworkSpaceRHNetwork Space Humidity Override%Command
AV46cpSpaceRH_DiffSpace Humidity Setpoint Differential%Write
AV47cpSpaceRH_SetptSpace Humidity Setpoint%Write
AV48EffectControlTempEffective Control Temperature°FRead
AV49cpWaitForFlowCompressor Wait for Flow TimersWrite
AV50LocalDewpointCalcLocal Space Dewpoint°FRead
AV51NetworkDewpointNetwork Dewpoint Override°FCommand
AV52EffectiveDewpointEffective Dewpoint°FRead
AV53cpDewpointSetpDewpoint Setpoint°FWrite
AV54cpDewpointDiffDewpoint Differential°FWrite
AV55cpVsFanOnlyPWMVariable Fan Speed PWM - Fan-Only%Write
AV56cpVsDehumPWMVariable Fan Speed PWM - Dehumidification%Write
AV57cpVsCool1PWMVariable Fan Speed PWM - Cool Stage 1%Write
AV58cpVsCool2PWMVariable Fan Speed PWM -Cool Stage 2%Write
AV59cpVsHeat1PWMVariable Fan Speed PWM - Heat Stage 1%Write
AV60cpVsHeat2PWMVariable Fan Speed PWM - Heat Stage 2%Write
AV61cpVsElecHeatPWMVariable Fan Speed PWM - Electric Heat%Write
AV62cpVsHydroHeatPWMVariable Fan Speed PWM - Hydronic Heat%Write
AV63cpVsHydroCoolPWMVariable Fan Speed PWM - Hydronic Cool%Write
AV411MacAddressMAC Address / Address Switch (named MacAddressSwitch, read-only, when switch S3 is below 255)Write
AV412SystemMinInstanceSystem Minimum InstanceWrite
BI1A2L_FaultA2L Board FaultRead0=Alarm; 1=Normal
BI2EmergShutDnEmergency ShutdownRead0=Normal; 1=Shutdown
BI3HiPressure1Compressor 1 High PressureRead0=Normal; 1=Alarm
BI4LoPressure1Compressor 1 Low PressureRead0=Normal; 1=Alarm
BI5Tstat_GThermostat Fan InputRead0=Off (Auto); 1=On
BI6Tstat_W1Thermostat - Heating Stage 1Read0=Inactive; 1=Active
BI7Tstat_W2Thermostat - Heating Stage 2Read0=Inactive; 1=Active
BI8Tstat_Y1Thermostat - Cooling Stage 1Read0=Inactive; 1=Active
BI9Tstat_Y2Thermostat - Cooling Stage 2Read0=Inactive; 1=Active
BI10OccSw_InOccupancy Switch SettingRead0=Off; 1=On
BI11HiPressure2Compressor 2 High PressureRead0=Normal; 1=Alarm
BI12LoPressure2Compressor 2 Low PressureRead0=Normal; 1=Alarm
BI13Tstat_W3Thermostat - Heating Stage 3Read0=Inactive; 1=Active
BI14Tstat_W4_Y3Thermostat - Heating Stage 4 / Cooling Stage 3Read0=Inactive; 1=Active
BI15BB_ConfigSw1Unit OperationRead0=Off; 1=On
BI16BB_ConfigSw2Fan OperationRead0=Off; 1=On
BI17BB_ConfigSw3Loop FluidRead0=Off; 1=On
BI18BB_ConfigSw4Freeze Fault ProtectionRead0=Off; 1=On
BI19BB_ConfigSw5Room Sensor Setpoint AdjustRead0=Off; 1=On
BI20BB_ConfigSw6Thermostat/Room SensorRead0=Off; 1=On
BI21BB_ConfigSw7Config switch 7: Compressor Heating Enable (Series2) / Compressor Availability (SS2C)Read0=Off; 1=On
BI22BB_ConfigSw8Config switch 8: I/O Expansion Module (Series2) / Compressor Availability (SS2C)Read0=Off; 1=On
BI23BB_ConfigSw9Baseboard Application SelectRead0=Off; 1=On
BI24BB_ConfigSw10Discrete Variable Fan SelectRead0=Off; 1=On
BI25IO_ConfigSw1Variable Fan Speed Selection (switch 1)Read
BI26IO_ConfigSw2Variable Fan Speed Selection (switch 2)Read
BI27IO_ConfigSw3Variable Fan Speed Selection (switch 3)Read
BI28IO_ConfigSw4Variable Fan Speed Selection (switch 4)Read
BI29IO_ConfigSw5Secondary Heating OptionsRead0=Off; 1=On
BI30IO_ConfigSw6Secondary Heating Options (switch 6)Read
BI31IO_ConfigSw7Hot Gas Reheat (HGR)Read0=Off; 1=On
BI32IO_ConfigSw8Waterside Economizer (WSE)Read0=Off; 1=On
BI33IO_ConfigSw9I/O Expansion Module Application SelectRead0=Off; 1=On
BI34IO_ConfigSw10Compressor Dual Speed Option (Series2) / Lead Compressor Select (SS2C)Read0=Off; 1=On
BI35HumidistatHumidistat InputRead0=Inactive; 1=Active
BO1AlarmThermostat AlarmRead0=Alarm output command is Off (0 VAC); 1=Alarm output command is On (24 VAC)
BO2Comp1OutCompressor 1Read0=Compressor 1 command is Off; 1=Compressor 1 command is On
BO3FanMainOutFan Main EnableRead0=Fan main command is Off; 1=Fan main command is On
BO4FanLowOutFan SpeedRead0=Fan high speed command is On; 1=Fan low speed command is On
BO5PumpOutPump RequestRead0=Pump command is Off; 1=Pump command is On
BO6RevVlv1OutReversing Valve 1Read0=Reversing valve 1 command is Off (cooling); 1=Reversing valve 1 command is On (heating)
BO7Comp2OutCompressor 2 / Compressor High CapacityRead0=Compressor 2 command is Off; 1=Compressor 2 command is On
BO8RevVlv2OutReversing Valve 2Read0=Reversing valve 2 command is Off (cooling); 1=Reversing valve 2 command is On (heating)
BO9AuxHeat1OutAuxiliary Heat 1Read0=Electric heat 1 command is Off; 1=Electric heat 1 command is On
BO10AuxHeat2OutAuxiliary Heat 2Read0=Electric heat 2 command is Off; 1=Electric heat 2 command is On
BO11HGR_OutHot Gas ReheatRead0=HGR command is Off (valve is closed); 1=HGR command is On (valve is open)
BO12WSE_OutWaterside EconomizerRead0=WSE command is Off (valve is closed); 1=WSE command is On (valve is open)
BVmin1ClearAlarmClear AlarmWrite0=Normal; 1=Clear Alarm
MI1CondOverFlowCondensate Overflow StatusRead1=Dry; 2=Wet; 3=Null
MI2FanOnAutoFan On/Auto Switch Status (Room Sensor)Read1=On; 2=Auto; 3=Null
MI3HeatCoolAutoSystem Mode Switch (Heat/Cool/Auto) StatusRead1=Off; 2=Heat; 3=Cool; 4=Auto; 5=Null
MI4DehumRequiredDehumidification RequiredRead1=Dehumid not Required; 2=Dehumid Required; 3=Null
MI5FanRunStatusFan Run StatusRead1=Fan is Off; 2=Fan is On
MVmin1ComprEnableCompressor Enable InputCommand1=Disabled; 2=Enabled; 3=Null (Compressors Enabled)
MVmin2CurrentAlarmCurrent AlarmReadAlarm number 1-28 (see the alarm table in the guide)
MV3NetworkFanOnAutoNetwork Fan On/Auto InputCommand1=Fan Auto; 2=Fan On; 3=Null
MVmin4McQWSHPStatusUnit StatusRead1=Off Alarm; 2=Off; 3=Start; 4=Fan Only; 5=Prepare to Heat; 6=Heating; 7=Prepare to Cool; 8=Cooling; 9=Prepare to Dehumidify; 10=Dehumidification
MV5PreviousAlarmPrevious AlarmReadAlarm number 1-28 (see the alarm table in the guide)
MV6EffectOccupEffective OccupancyRead1=Occupied; 2=Unoccupied; 3=Bypass; 4=Standby; 5=Null
MVmin7OccManCmdOccupancy Override InputCommand1=Occupied; 2=Unoccupied; 3=Bypass; 4=Standby; 5=Null
MV8OccScheduleOccupancy SchedulerCommand1=Occupied; 2=Unoccupied; 3=Standby; 4=Null
MV9OccSensorOccupancy SensorCommand1=Occupied; 2=Unoccupied; 3=Null
MVmin10ApplicModeApplication ModeCommand1=Auto; 2=Heat; 3=Cool; 4=Off; 5=Fan Only; 6=Dehumid; 7=Null
MV11AuxHeatEnableAuxiliary Heat EnableCommand1=Disabled; 2=Enabled; 3=Null
MV12EnergyHoldOffEnergy Hold OffCommand1=Normal; 2=Energy Hold Off; 3=Null
MV13PumpRequestPump Request OutputRead1=No Request for Flow; 2=Request for Flow; 3=Null
MV14cpLocSpEnableRoom Sensor Setpoint Adjust Enable/DisableWrite1=Disabled; 2=Enabled
MV15UnitsUnits (English/Metric)Write1=English (E); 2=Metric (M)
MV16NetworkHumidistatNetwork Humidistat InputCommand1=No Dehumid Request; 2=Request Dehumid; 3=Null
MV17cpNetVsCnfgEnNetwork Variable Speed Fan EnableWrite1=Disabled; 2=Enabled; 3=Null
MV18cpSpaceDehumCnfgSpace Dehumidification MethodWrite1=Relative Humidity; 2=Dewpoint; 3=Null
MV19cpSpaceRHSensorSpace Relative Humidity SensorWrite1=Not Installed; 2=Installed; 3=Null
MV20cpControlTempSrcControl Temperature SourceWrite1=Space; 2=Return; 3=Average; 4=Null
Object ID lookup: Daikin Applied MT2300 SmartSource R32 WSHP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)

How many BACnet points does the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) have?

This list has 148 BACnet objects: 10 analog inputs, 65 analog values, 35 binary inputs, 12 binary outputs, 1 binary value, 5 multi-state inputs, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet points are writable?

73 of the 148 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) BACnet documentation?

The source is MicroTech SmartSource WSHP BACnet Network Integration Guide (MT2300, R32) (ED 19129-1), revision 2024-05, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MT%20SmartSource%20WSHP%20BACnet%20Protocol%20Document%20ED%2019129-1.pdf/.

What are the minimum BACnet points to integrate the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)?

Start with MV 7 OccManCmd (Occupancy override from the BMS); MV 10 ApplicMode (Application mode (Auto/Heat/Cool/Off/Fan Only/Dehumid)); MV 1 ComprEnable (Compressor enable, usually from loop flow proof); AV 19 NetworkSetpoint (Network reference setpoint); BV 1 ClearAlarm (Clear active fault alarms); MV 4 McQWSHPStatus (Unit operating state); AV 22 EffectSpaceTemp (Space temperature used for control); AI 2 LWT (Leaving water temperature); MV 2 CurrentAlarm (Highest-priority active alarm).

How do I enable BMS control of the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)?

No local/remote switch. The network override objects act as soon as they are written: Occupancy Override Input (MSV 7) or Occupancy Scheduler (MSV 8) set occupancy, Application Mode (MSV 10) limits the unit to Auto/Heat/Cool/Off/Fan Only/Dehumid and overrides the room sensor mode switch, and Compressor Enable (MSV 1) permits compressor operation. All revert to Null after a controller reboot.

Does the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH) need a BACnet heartbeat or have a communication timeout?

Receive Heartbeat (AV 20, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled) sets how long a supported network override may go without being rewritten before it reverts to its default; each supported override has its own timer. Send Heartbeat (AV 21) is not supported by the BACnet module; use COV instead.

Can the BMS supply sensor values to the Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)?

Write space temperature to AV 18 and space humidity to AV 45; a network dewpoint goes to AV 51. AV 19 sets the reference setpoint only after local setpoint adjust is disabled with MSV 14 = 1. AV 35 shifts the occupied/standby setpoints, MSV 9 takes a network occupancy sensor, MSV 16 overrides the humidistat and MSV 3 the fan On/Auto switch.

How do I check these points on the real MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin Applied BACnet points lists

Source: MicroTech SmartSource WSHP BACnet Network Integration Guide (MT2300, R32) · ED 19129-1 · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.