- EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Air-to-water heat pump / air-cooled chiller controller · BACnet points list
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe) BACnet points list
Updated 4 November 2026
The EWAK-CZ chillers and EWYK-CZ heat pumps use a MicroTech controller running the ICARO software. BACnet MS/TP comes from a POL904 module and BACnet IP from a POL908 module. The list covers unit enable, cool/heat mode and network setpoints, capacity and current limits, domestic hot water, bivalent (boiler backup) and collective housing functions, variable-flow pump data, per-circuit compressor data, alarm words and master/slave status.
This page lists 96 BACnet objects for the Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
- Equipment
- Air-to-water heat pump / air-cooled chiller controller
- Equipment type
- Chillers
- BACnet objects
- 96 (34 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1 (BACnet IP module); MS/TP module derives it from the production number and date code
- Also known as
- EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Set the unit to network control, then enable it with ChillerEnableStp (BV 2) and write the operating mode (MV 3) and the cool or heat setpoint at priority 8. Monitor unit status, leaving water temperature, the general alarm and the fault code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | ChillerEnableStp | Network enable/disable of the unit | Command |
| MV 3 | ChillerOperationMode | Cool / heat mode command | Command |
| AV 4 | NetworkCoolTempSetpoint | Leaving water cool setpoint from the BMS | Command |
| AV 6 | NetworkHeatTempSetpoint | Leaving water heat setpoint from the BMS | Command |
| AV 3 | CapacityLimitSetpt | Capacity limit from the BMS | Command |
| BV 8 | ClearAlarm | Clear alarms from the network | Command |
| BI 3 | ChillerLocalRemote | Shows whether network control is active | Read |
| MV 1 | UnitStatus | Unit run state | Read |
| AI 2 | LvgEvapWaterTempUnit | Leaving water temperature | Read |
| BI 10 | AlarmDigitalOutput | Any active unit alarm | Read |
Enable & remote start
ChillerLocalRemote (BI 3) shows 0 = Local / 1 = Network and is read-only; the guide lists no writable local/network selector, so network control is chosen at the unit. With network control active the BMS writes ChillerEnableStp (BV 2) = Enable, then the mode (MV 3) and the network setpoints.
Network setup
- BACnet MS/TP comes from the POL904 module: MAC address 24, 38400 baud, Max Master 127, Max Info Frames 1 by default; the device instance is derived from the production number and date code. Cycle power after changing the address.
- BACnet IP comes from the POL908 module: device instance 1, UDP port 47808, DHCP off by default. Set Apply Changes = Yes after editing, which restarts the controller.
- Both are set from the unit keypad under Commissioning > BACnet with the service password.
Watch out for
- Write the enable, alarm-reset, mode and main network setpoints at priority 8, as the guide states.
- Reduced (_red) objects have no priority array; write Present Value directly.
- The guide warns that writing Clear Alarms continuously can be hazardous; send it once.
- Compressor starts and run-hour AVs are marked writable; don't write them from the BMS.
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 3 | ChillerLocalRemote | Local/Network Source | Read | 0=Local; 1=Network | |
| BI | 7 | ChillerEnableOutput | Enabled State | Read | 0=Disabled; 1=Enabled | |
| BI | 6 | ChillerLimited | Capacity Limited | Read | 0=No; 1=Yes | |
| BImin | 10 | AlarmDigitalOutput | Unit general alarm | Read | 0=No; 1=Yes | |
| BI | 4 | ThermostatStatus | Thermoregulation State | Read | 0=Off; 1=On | |
| BVmin | 2 | ChillerEnableStp | Unit Enable Setpoint - Network | Command | 0=Disable; 1=Enable | |
| BVmin | 8 | ClearAlarm | Clear Alarms - Network | Command | 0=Normal; 1=Clear | |
| MV | 2 | ActiveMode | Operation Mode (reduced) | Read | 1=Not Used; 2=Cool; 3=Heat; 4=Not Used; 5=Defrost | |
| AV | 5 | ActiveLvgWaterTarget | Active Setpoint (reduced) | °C | Read | |
| AV | 2 | ChillerCapacity | Actual Capacity (reduced) | % | Read | |
| AV | 1 | ActiveCapacityLimit | Active Capacity Limit Output (reduced) | % | Read | |
| MVmin | 1 | UnitStatus | Status (reduced) | Read | 1=Off; 2=Start; 3=Run; 4=Preshutdown; 5=Service | |
| AI | 1 | EntEvapWaterTemp | Evaporator Entering Water Temp | °C | Read | |
| AImin | 2 | LvgEvapWaterTempUnit | Evaporator Leaving Water Temp Unit | °C | Read | |
| AI | 5 | OutdoorAirTemp | Outdoor Air Temperature | °C | Read | |
| AV | 903 | AVWarningAlarmCode | Warning CODE (reduced) | Read | 0=No Alarm; 1=External event | |
| AV | 904 | AVProblemAlarmCode | Problem CODE (reduced) | Read | 0=No Alarm; 1=Circuit Alarm | |
| AV | 905 | AVFaultAlarmCode | Fault CODE (reduced) | Read | 0=No Alarm; 1=Unit or both Circuit Alarm | |
| MVmin | 3 | ChillerOperationMode | Operation Mode Setpoint - Network | Command | 0=NULL; 1=Not Used; 2=Cool; 3=Heat; 4=Not Used | |
| AVmin | 4 | NetworkCoolTempSetpoint | Cool Setpoint - Network | °C | Command | |
| AVmin | 6 | NetworkHeatTempSetpoint | Heat Setpoint - Network | °C | Command | |
| AVmin | 3 | CapacityLimitSetpt | Capacity Limit Setpoint - Network | % | Command | |
| AV | 39 | CurrentLimitSetpt | Current Limit Setpoint - Network | A | Command | |
| MV | 47 | Units | Unit of Measure (reduced) | Write | 1=Metric; 2=Imperial | |
| MV | 48 | SilentModeSetpt | Noise Reduction Enable Setpoint (reduced) | Write | 1=Off; 2=On | |
| MV | 62 | DefrostOpState | Defrost - Operating State (reduced) | Read | 0=Off; 1=On | |
| MV | 70 | BivOpsEnableStp | Bivalent Operation - Enable Setpoint (reduced) | Write | 0=Off; 1=On | |
| AV | 71 | BivOps'TCutOff | Bivalent Operation - Temperature Cut-Off (reduced) | °C | Write | |
| AV | 72 | BivOps'Tbivalent | Bivalent Operation - Temperature Bivalent Mode (reduced) | °C | Write | |
| AV | 73 | BivOps'BoilerStDelay | Bivalent Operation - Boiler Start Delay (reduced) | min | Write | |
| MV | 80 | ColHsng'EnableStp | Collective Housing - Enable Setpoint (reduced) | Write | 0=Off; 1=On | |
| AI | 81 | CollHsng'TankTemp | Collective Housing - Tank Temperature | °C | Read | |
| AV | 82 | CollHsng'CngovrUpperLim | Collective Housing - Changeover Upper Limit (reduced) | °C | Write | |
| AV | 83 | CollHsng'CngovrLowerLim | Collective Housing - Changeover Lower Limit (reduced) | °C | Write | |
| AV | 84 | CollHsng'TankTempStp | Collective Housing - Tank Temperature Stp (reduced) | °C | Write | |
| BV | 90 | DHWRemoteEn | DHW Enable Setpoint | Command | 0=Off; 1=On | |
| AV | 91 | DHWTempSp | DHW Temperature Setpoint (reduced) | °C | Write | |
| AI | 92 | DHWWaterTemp | DHW Temperature | °C | Read | |
| MV | 93 | DHW3WVState | DHW Switching Valve State (reduced) | Read | 1=DHW Off; 2=Switching; 3=DHW Run; 4=Error | |
| MV | 94 | DHWAntiLegCycle | DHW Anti Legionella Cycle (reduced) | Read | 0=Off; 1=On | |
| MV | 95 | DHWStandbyMode | DHW Standby Mode (reduced) | Write | 0=Off; 1=On | |
| BI | 101 | EvapPumpSta1 | Evaporator Pump #1 Status | Read | 0=Pump Off Request; 1=Pump On Request | |
| AV | 102 | EvapPumpRunHrs1 | Evaporator Pump #1 Run Hours (reduced) | h | Write | |
| AV | 150 | VPF'FixSpeedSetpt1 | Evaporator VFD Pump - Fixed Speed 1 (reduced) | % | Write | |
| AV | 151 | VPF'FixSpeedSetpt2 | Evaporator VFD Pump - Fixed Speed 2 (reduced) | % | Write | |
| AV | 152 | VPF'StbySpeedSetpt | Evaporator VFD Pump - Standby Speed (reduced) | % | Write | |
| AV | 153 | VPF'ActSpeed | Evaporator VFD Pump - Actual Speed (reduced) | % | Read | |
| AV | 154 | VPF'LoadDifPresSetpt | Evaporator VFD Pump - Building Differential Pressure Setpoint (reduced) | kPa | Write | |
| AV | 155 | VPF'EvapDifPresSetpt | Evaporator VFD Pump - Unit Differential Pressure Setpoint (reduced) | kPa | Write | |
| AI | 156 | VPF'LoadDifPres | Evaporator VFD Pump - Building Differential Pressure | kPa | Read | |
| AI | 157 | VPF'EvapDifPress | Evaporator VFD Pump - Unit Differential Pressure | kPa | Read | |
| MV | 158 | VPF'BypVlvSta | Evaporator VFD Pump - Bypass Valve State (reduced) | Read | 1=Closed; 2=Opened | |
| AV | 159 | VPF'DeltaTempSp | Evaporator VFD Pump - DeltaTemperature Setpoint (reduced) | dK | Write | |
| AV | 160 | VPF'DeltaTemp | Evaporator VFD Pump - DeltaTemperature (reduced) | dK | Read | |
| MV | 201 | SiemensController | Siemens Controller type (reduced) | Read | 1=N/A; 2=POL687; 3=POL638; 4=POL687.00; 5=POL687.70; 6=POL688.80; 7=POL688.80UPS; 8=POL468 | |
| MV | 202 | ApplSaveSp | Application Save (reduced) | Write | 1=Off; 2=On | |
| BV | 288 | ExternalAlarm | External Alarm | Read | 0=No Alarm; 1=InAlarm | |
| BV | 289 | UnitExternalEvent | External Event | Read | 0=No Event; 1=Event | |
| AV | 295 | UnitAlarmsWord4 | Unit Alarm Word #5 (reduced) | Read | ||
| AV | 296 | UnitAlarmsWord4 | Unit Alarm Word #4 (reduced) | Read | ||
| AV | 297 | UnitAlarmsWord3 | Unit Alarm Word #3 (reduced) | Read | ||
| AV | 298 | UnitAlarmsWord2 | Unit Alarm Word #2 (reduced) | Read | ||
| AV | 299 | UnitAlarmsWord1 | Unit Alarm Word #1 (reduced) | Read | ||
| MV | 300 | C1State | Circuit #1 State (reduced) | Read | 1=Off; 2=Preopen; 3=Run; 4=Pumpdown | |
| BV | 321 | C1Comp1Status | Circuit #1 Comp #1 - Status | Read | 0=Off; 1=On | |
| AV | 322 | C1Comp1Starts | Circuit #1 Comp #1 - Starts (reduced) | Write | ||
| AV | 323 | C1Comp1Hours | Circuit #1 Comp #1 - Run Hours (reduced) | Write | ||
| AV | 325 | C1Comp1ActCap | Circuit #1 Comp #1 - Actual Capacity (reduced) | % | Read | |
| AV | 326 | C1Comp1RLA | Circuit #1 Comp #1 - Percent RLA (reduced) | % | Read | |
| AV | 396 | C1AlarmWord4 | Circuit #1 or Cir1Comp1 Alarm Word #4 (reduced) | Write | ||
| AV | 397 | C1AlarmWord3 | Circuit #1 or Cir1Comp1 Alarm Word #3 (reduced) | Read | ||
| AV | 398 | C1AlarmWord2 | Circuit #1 or Cir1Comp1 Alarm Word #2 (reduced) | Read | ||
| AV | 399 | C1AlarmWord1 | Circuit #1 or Cir1Comp1 Alarm Word #1 (reduced) | Read | ||
| MV | 400 | C2State | Circuit #2 State (reduced) | Read | 1=Off; 2=Preopen; 3=Run; 4=Pumpdown | |
| BV | 421 | C2Comp1Status | Circuit #2 Comp #1 - Status | Read | 0=Off; 1=On | |
| AV | 422 | C2Comp1Starts | Circuit #2 Comp #1 - Starts (reduced) | Write | ||
| AV | 423 | C2Comp1Hours | Circuit #2 Comp #1 - Run Hours (reduced) | Write | ||
| AV | 425 | C2Comp1ActCap | Circuit #2 Comp #1 - Actual Capacity (reduced) | % | Read | |
| AV | 426 | C2Comp1RLA | Circuit #2 Comp #1 - Percent RLA (reduced) | % | Read | |
| AV | 496 | C2AlarmWord4 | Circuit #2 or Cir2Comp1 Alarm Word #4 (reduced) | Read | ||
| AV | 497 | C2AlarmWord3 | Circuit #2 or Cir2Comp1 Alarm Word #3 (reduced) | Read | ||
| AV | 498 | C2AlarmWord2 | Circuit #2 or Cir2Comp1 Alarm Word #2 (reduced) | Read | ||
| AV | 499 | C2AlarmWord1 | Circuit #2 or Cir2Comp1 Alarm Word #1 (reduced) | Read | ||
| AI | 151 | SysCtrlTmp | M/S Leaving Water Temperature | °C | Read | |
| BV | 502 | CommonLWTSenf | M/S LWT Sensor Fault | Read | 0=No Alarm; 1=In Alarm | |
| MV | 5 | StandaloneModeSp | M/S Disconnect Setpoint (reduced) | Write | 1=No; 2=Yes | |
| BV | 20 | MasterCommErr | Master Comm Error | Read | 0=No Alarm; 1=In Alarm | |
| BV | 21 | Slave1CommErr | Slave 1 Comm Error | Read | 0=No Alarm; 1=In Alarm | |
| BV | 22 | Slave2CommErr | Slave 2 Comm Error | Read | 0=No Alarm; 1=In Alarm | |
| BV | 23 | Slave3CommErr | Slave 3 Comm Error | Read | 0=No Alarm; 1=In Alarm | |
| AV | 1150 | Slave1Load | Slave Load #1 (reduced) | % | Read | |
| MV | 1154 | Slave1State | Slave State #1 (reduced) | Read | 1=Stop; 2=Run; 3=Alarm; 4=ComErr | |
| AV | 1168 | Slave2Load | Slave Load #2 (reduced) | % | Read | |
| MV | 1172 | Slave2State | Slave State #2 (reduced) | Read | 1=Stop; 2=Run; 3=Alarm; 4=ComErr | |
| AV | 1186 | Slave3Load | Slave Load #3 (reduced) | % | Read | |
| MV | 1190 | Slave3State | Slave State #3 (reduced) | Read | 1=Stop; 2=Run; 3=Alarm; 4=ComErr |
No points match these filters.
Object ID lookup: Daikin Applied EWAK-CZ / EWYK-CZ point IDs by name
BI3ChillerLocalRemoteBI7ChillerEnableOutputBI6ChillerLimitedBI10AlarmDigitalOutputBI4ThermostatStatusBV2ChillerEnableStpBV8ClearAlarmMV2ActiveModeAV5ActiveLvgWaterTargetAV2ChillerCapacityAV1ActiveCapacityLimitMV1UnitStatusAI1EntEvapWaterTempAI2LvgEvapWaterTempUnitAI5OutdoorAirTempAV903AVWarningAlarmCodeAV904AVProblemAlarmCodeAV905AVFaultAlarmCodeMV3ChillerOperationModeAV4NetworkCoolTempSetpointAV6NetworkHeatTempSetpointAV3CapacityLimitSetptAV39CurrentLimitSetptMV47UnitsMV48SilentModeSetptMV62DefrostOpStateMV70BivOpsEnableStpAV71BivOps'TCutOffAV72BivOps'TbivalentAV73BivOps'BoilerStDelayMV80ColHsng'EnableStpAI81CollHsng'TankTempAV82CollHsng'CngovrUpperLimAV83CollHsng'CngovrLowerLimAV84CollHsng'TankTempStpBV90DHWRemoteEnAV91DHWTempSpAI92DHWWaterTempMV93DHW3WVStateMV94DHWAntiLegCycleMV95DHWStandbyModeBI101EvapPumpSta1AV102EvapPumpRunHrs1AV150VPF'FixSpeedSetpt1AV151VPF'FixSpeedSetpt2AV152VPF'StbySpeedSetptAV153VPF'ActSpeedAV154VPF'LoadDifPresSetptAV155VPF'EvapDifPresSetptAI156VPF'LoadDifPresAI157VPF'EvapDifPressMV158VPF'BypVlvStaAV159VPF'DeltaTempSpAV160VPF'DeltaTempMV201SiemensControllerMV202ApplSaveSpBV288ExternalAlarmBV289UnitExternalEventAV295UnitAlarmsWord4AV296UnitAlarmsWord4AV297UnitAlarmsWord3AV298UnitAlarmsWord2AV299UnitAlarmsWord1MV300C1StateBV321C1Comp1StatusAV322C1Comp1StartsAV323C1Comp1HoursAV325C1Comp1ActCapAV326C1Comp1RLAAV396C1AlarmWord4AV397C1AlarmWord3AV398C1AlarmWord2AV399C1AlarmWord1MV400C2StateBV421C2Comp1StatusAV422C2Comp1StartsAV423C2Comp1HoursAV425C2Comp1ActCapAV426C2Comp1RLAAV496C2AlarmWord4AV497C2AlarmWord3AV498C2AlarmWord2AV499C2AlarmWord1AI151SysCtrlTmpBV502CommonLWTSenfMV5StandaloneModeSpBV20MasterCommErrBV21Slave1CommErrBV22Slave2CommErrBV23Slave3CommErrAV1150Slave1LoadMV1154Slave1StateAV1168Slave2LoadMV1172Slave2StateAV1186Slave3LoadMV1190Slave3State
Integration notes
- Objects marked _red in the guide are 'reduced' objects: no priority array, Present Value only. The type is shown without the suffix and the description ends in (reduced).
- Access 'W (Prio 8)' in the guide is shown as C; plain W as W. Units '°Dc' (temperature difference) are shown as dK.
- Alarm words (AV 295-299, 396-399, 496-499) are bit fields decoded with Annex A of the guide.
- The guide prints the object name UnitAlarmsWord4 for both AV 295 (Unit Alarm Word #5) and AV 296; kept as printed.
- Domestic hot water, bivalent, collective housing, variable-flow pump and master/slave objects only apply when those functions are configured.
- AI 151 (master/slave leaving water temperature) and AV 151 (pump fixed speed 2) share an instance number but are different object types.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
How many BACnet points does the Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe) have?
This list has 96 BACnet objects: 8 analog inputs, 50 analog values, 6 binary inputs, 12 binary values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe) BACnet points are writable?
34 of the 96 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe) BACnet documentation?
The source is BAS integration guide - BACnet protocol (EWAK-CZ/EWYK-CZ, ICARO) (D-EIGOC00104-26_00EN-EWYK-CZ), published free by Daikin Applied at https://www.daikinapplied.uk/hubfs/portale-documentale/D_EIGOC00104_26_00EN_EWYK_CZ.pdf.
What are the minimum BACnet points to integrate the Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)?
Start with BV 2 ChillerEnableStp (Network enable/disable of the unit); MV 3 ChillerOperationMode (Cool / heat mode command); AV 4 NetworkCoolTempSetpoint (Leaving water cool setpoint from the BMS); AV 6 NetworkHeatTempSetpoint (Leaving water heat setpoint from the BMS); AV 3 CapacityLimitSetpt (Capacity limit from the BMS); BV 8 ClearAlarm (Clear alarms from the network); BI 3 ChillerLocalRemote (Shows whether network control is active); MV 1 UnitStatus (Unit run state); AI 2 LvgEvapWaterTempUnit (Leaving water temperature); BI 10 AlarmDigitalOutput (Any active unit alarm).
How do I enable BMS control of the Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)?
ChillerLocalRemote (BI 3) shows 0 = Local / 1 = Network and is read-only; the guide lists no writable local/network selector, so network control is chosen at the unit. With network control active the BMS writes ChillerEnableStp (BV 2) = Enable, then the mode (MV 3) and the network setpoints.
How do I check these points on the real EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: BAS integration guide - BACnet protocol (EWAK-CZ/EWYK-CZ, ICARO) · D-EIGOC00104-26_00EN-EWYK-CZ. Object names, instances and units are reproduced as published; descriptions are our own.