- Home
- BACnet points lists
- Daikin Applied
- Airstream ADT air handler (Daikin Applied Europe)
Air handling unit controller · BACnet points list
Daikin Applied Airstream ADT air handler (Daikin Applied Europe) BACnet points list
Updated 7 November 2026
The ADT air handler runs Airstream software on a MicroTech controller; BACnet IP comes from a POL908 module and BACnet MS/TP from a POL904 module. The list covers air temperatures, pressures and flows, fan and coil outputs, fan, temperature, humidity and air-quality setpoints, ERQ condensing-unit load, defrost and R-32 leak status, alarms, operating mode and summer/winter changeover. Object instances are fixed but non-sequential.
This page lists 118 BACnet objects for the Daikin Applied Airstream ADT air handler (Daikin Applied Europe) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- Airstream ADT air handler (Daikin Applied Europe)
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 118 (30 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Write NetworkCtrl to run or stop the unit, set summer/winter with SuWiNetworkChgover after setting SuWiChgSrc to BMS, and adjust the fan, temperature and humidity setpoints as needed. Read the operating mode and status, supply and controlled temperatures, ERQ load and the general alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 24562 | NetworkCtrl | Network on/off (1 = Off, 2 = On) | Write |
| MV 28594 | SuWiNetworkChgover | Summer/winter command (1 = Winter, 2 = Summer) | Write |
| MV 9493 | SuWiChgSrc | Must be 3 = BMS for the summer/winter command | Write |
| AV 52572 | SplyFanSpvSt1Spv | Supply fan setpoint (units per SplyEngUnit) | Write |
| MV 39130 | AckAlmPls | Acknowledge all alarms (2 = On) | Write |
| MV 6080 | ActOpMode | Operating mode (Off/On/Ventilation/Economy/Standby) | Read |
| MV 32321 | ActOpSta | Why the unit runs or stops (e.g. 11 = BMS) | Read |
| AI 45150 | SupplyTmp | Supply air temperature | Read |
| AV 52988 | ActCtrlVal | Temperature being controlled | Read |
| BI 41868 | GenAlm | General alarm (1 = Alarm) | Read |
Enable & remote start
NetworkCtrl (MV 24562, "Network source", 1 = Off / 2 = On) is the writable on/off object; ActOpSta (MV 32321) reports 11 = BMS when the network is in control. Summer/winter follows the BMS only when SuWiChgSrc (MV 9493) = 3 (BMS); then write SuWiNetworkChgover (MV 28594). The guide gives no further procedure.
Network setup
- BACnet IP comes from a POL908 module and BACnet MS/TP from a POL904 module plugged onto the MicroTech controller.
- BACnet MS/TP module defaults: MAC address 24, 38400 baud, Max Master 127, Max Info Frames 1; cycle power after changing the address.
- Object instances are fixed, non-sequential numbers (e.g. SupplyTmp = AI 45150); map by instance, not by position.
Watch out for
- Objects only appear when the AHU configuration uses them (fans, coils, recovery, humidity, ERQ units).
- Fan setpoint units follow SplyEngUnit / ExhEngUnit (%, Pa or m3/h); humidity units follow HumEngUnit.
- Multistate commands are 1-based (1 = Off, 2 = On); 0 is not a valid state.
- AckAlmPls (MV 39130) acknowledges every alarm in the controller at once.
- EmergencyStop (BI 9864) reads 0 = Alarm, 1 = OK, the reverse of the other alarm inputs.
Daikin Applied Airstream ADT air handler (Daikin Applied Europe) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 45150 | SupplyTmp | Supply air temperature | °C | Read | |
| AI | 33923 | RmUTmp1 | Room unit temperature | °C | Read | |
| AI | 28256 | ReturnAirTmp | Return air temperature | °C | Read | |
| AI | 53218 | OutTmp | Outside air temperature | °C | Read | |
| AI | 29568 | PreHeatTemp | Pre-Heating temperature | °C | Read | |
| AI | 40895 | ExhaustTmp | Exhaust temperature | °C | Read | |
| AI | 20400 | SupplyPrs | Supply air pressure | Pa | Read | |
| AI | 39576 | ReturnPrs | Return air pressure | Pa | Read | |
| AI | 9497 | SupplyFlow | Supply air flow | m3/h | Read | |
| AI | 38593 | ReturnFlow | Return air flow | m3/h | Read | |
| AI | 37799 | RoomHum | Room humidity relative | %rH | Read | |
| AI | 3737 | AirQuality | Air quality (CO2) | ppm | Read | |
| AI | 19419 | ERQ1Load | ERQ1 actual load | % | Read | |
| AI | 42249 | ERQ2Load | ERQ2 actual load | % | Read | |
| AI | 36987 | ERQGlobalLoad | Global ERQ actual load | % | Read | |
| AI | 16189 | SplyOptDPT | Supply optional transducer | Pa | Read | |
| AI | 35989 | RtrnOptDPT | Return optional transducer | Pa | Read | |
| AO | 59037 | SplyFanVarPos | Supply fan output | % | Read | |
| AO | 40119 | ExhFanVarPos | Return fan output | % | Read | |
| AO | 39618 | HumidityCtrlPos | Humidifier output | % | Read | |
| AO | 37442 | ElectricalHtgPos | Electrical heating / Post heating output | % | Read | |
| AO | 42156 | HrecDampPos | Mixing damper output | % | Read | |
| AO | 24312 | HrecPos | Recovery device output | % | Read | |
| AO | 30925 | CoolingPos | Cooling coil output | % | Read | |
| AO | 26209 | HeatingPos | Heating coil output | % | Read | |
| AO | 62755 | FanTempCompPos | Fan temperature compensation output | % | Read | |
| AVmin | 52572 | SplyFanSpvSt1Spv | Supply fan setpoint | m3/h or Pa | Write | |
| AV | 57915 | SplyFanSpvEcSpv | Supply fan economy setpoint | m3/h or Pa | Write | |
| AV | 25092 | SplyFanSpvMaxForce | Supply fan max force | m3/h or Pa | Write | |
| AV | 45030 | ExhFanSpvSt1Spv | Return fan setpoint | m3/h or Pa | Write | |
| AV | 6118 | ExhFanSpvEcSpv | Return fan economy setpoint | m3/h or Pa | Write | |
| AV | 2525 | ExhFanSpvMaxForce | Return fan max force | m3/h or Pa | Write | |
| AV | 56628 | SplyFanActVal | Supply fan actual value | m3/h or Pa | Read | |
| AV | 59694 | ExhFanActVal | Return fan actual value | m3/h or Pa | Read | |
| AV | 46589 | SplyFanActSpv | Supply fan actual setpoint | m3/h or Pa | Read | |
| AV | 33255 | ExhFanActSpv | Return fan actual setpoint | m3/h or Pa | Read | |
| AV | 22649 | AirQSpv | Air quality setpoint | ppm | Write | |
| AV | 61369 | RmEnth | Room enthalpy | J | Read | |
| AV | 17315 | RmHumAbs | Room humidity absolute | g/kg | Read | |
| AV | 11342 | HumSpvRelSpvDehum | Dehumidity setpoint relative | %rH | Write | |
| AV | 10627 | HumSpvRelSpvHum | Humidity setpoint relative | %rH | Write | |
| AV | 38385 | ActCtrlValHum | Actual controlled humidity | %rH | Read | |
| AV | 8970 | TmpSpvCoSpvClg | Cooling setpoint | °C | Write | |
| AV | 22817 | TmpSpvCoSpvHtg | Heating setpoint | °C | Write | |
| AV | 61866 | TmpSpvEcSpvClg | Economy cooling setpoint | °C | Write | |
| AV | 35713 | TmpSpvEcSpvHtg | Economy heating setpoint | °C | Write | |
| AV | 4018 | ActMainSpvHtg | Actual heating setpoint (per control mode) | °C | Read | |
| AV | 30105 | ActMainSpvClg | Actual cooling setpoint (per control mode) | °C | Read | |
| AV | 56276 | ActTempSetpt | Active temperature setpoint | °C | Read | |
| AVmin | 52988 | ActCtrlVal | Actual controlled temperature | °C | Read | |
| AV | 41552 | HrecDampminFrshAir | Minimum fresh air | % | Write | |
| AV | 24338 | SuWiSwtchCheckOutTmpDampd | Outside air temp damped | °C | Read | |
| AV | 1206 | RoomUnitsOccTm | Room unit presence time | h | Write | |
| AV | 8926 | RoomUnitOffset | Room unit temperature setpoint offset | °C | Write | |
| AV | 753 | MaxSupplyTempSu | Setpoint for maximum supply temperature during summer | °C | Read | |
| AV | 7560 | MaxSupplyTempWi | Setpoint for maximum supply temperature during winter | °C | Write | |
| AV | 18262 | MinSupplyTempSu | Setpoint for minimum supply temperature during summer | °C | Write | |
| AV | 22575 | MinSupplyTempWi | Setpoint for minimum supply temperature during winter | °C | Write | |
| AV | 47818 | SupplyFanRunHours | Running hours of supply fan | h | Read | |
| AV | 52983 | ReturnFanRunHours | Running hours of return fan | h | Read | |
| AV | 19448 | Pursuit – Setpoint | Temperature setpoint for Pursuit mode | °C | Write | |
| AV | 23744 | Pursuit – Setpoint Eco | Temperature setpoint for Eco-Pursuit mode | °C | Write | |
| AV | 12721 | Pursuit – Band | Pursuit Band | °C | Write | |
| AV | 56164 | COPKFactor | COP K factor | % | Write | |
| BI | 21294 | HtgFrstDtctr | Heating frost monitor (Frost switch) | Read | 0=OK, 1=Alarm | |
| BI | 47847 | HtgPmpAlm | Heating pump alarm | Read | 0=OK, 1=Alarm | |
| BI | 4964 | ElHtgAlm | Electrical /Post heating alarm | Read | 0=OK, 1=Alarm | |
| BI | 62931 | HRecAlm | Recovery device alarm | Read | 0=OK, 1=Alarm | |
| BI | 40242 | ClgPmpAlm | Cooling pump alarm | Read | 0=OK, 1=Alarm | |
| BI | 28757 | SplyFanAlm | Supply fan alarm | Read | 0=OK, 1=Alarm | |
| BI | 55865 | ExhFanAlm | Exhaust fan alarm | Read | 0=OK, 1=Alarm | |
| BI | 28514 | FireAlm | Fire alarm | Read | 0=OK, 1=Alarm | |
| BI | 13699 | FilterAlm | Filter alarm | Read | 0=OK, 1=Alarm | |
| BI | 11643 | ExtCtrl1 | Unit Enable Switch | Read | 0=Standby, 1=On | |
| BI | 9864 | EmergencyStop | Emergency stop | Read | 0=Alarm, 1=OK | |
| BI | 19724 | ERQ1OnOff | ERQ1 On/Off state | Read | 0=Off, 1=On | |
| BI | 48775 | ERQ1Defrost | ERQ1 Defrost state | Read | 0=No Defrost, 1=Defrost | |
| BI | 33772 | ERQ2OnOff | ERQ2 On/Off state | Read | 0=Off, 1=On | |
| BI | 30450 | ERQ2Defrost | ERQ2 Defrost state | Read | 0=No Defrost, 1=Defrost | |
| BI | 57484 | ElectricalPreheatingFault | Electrical preheating Fault | Read | 0=OK, 1=Alarm | |
| BI | 610 | ERQ1Alarm | ERQ 1 alarm | Read | 0=OK, 1=Alarm | |
| BI | 16951 | ERQ2Alarm | ERQ 2 alarm | Read | 0=OK, 1=Alarm | |
| BI | 29832 | ERQ1Leakage | ERQ 1 R32 leakage | Read | 0=OK, 1=Alarm | |
| BI | 48381 | ERQ2Leakage | ERQ 2 R32 leakage | Read | 0=OK, 1=Alarm | |
| BI | 54741 | LowFlowThrAlm | Low flow alarm | Read | 0=OK, 1=Alarm | |
| BImin | 41868 | GenAlm | General alarm | Read | 0=OK, 1=Alarm | |
| BO | 6170 | DamperSplyOnOff | Fresh air damper command | Read | 0=Off, 1=On | |
| BO | 18044 | HumidityCtrlCmdOnOff | Humidifier command | Read | 0=Off, 1=On | |
| BO | 10276 | CoolingPmpCmdOnOff | Cooling pump command | Read | 0=Off, 1=On | |
| BO | 10264 | HeatingPmpCmdOnOff | Heating pump command | Read | 0=Off, 1=On | |
| BO | 5714 | AlmOutHigh | AHU General alarm output | Read | 0=Normal, 1=Alarm | |
| SCH | 31059 | ScheduleSt | Time scheduler actual state | Read | 1=Off, 2=On, 3=Ventilation, 4=Economy | |
| MO | 21928 | SplyFanCmdSt | Supply fan command | Read | 1=Off, 2=On | |
| MO | 14719 | ExhFanCmdSt | Exhaust fan command | Read | 1=Off, 2=On | |
| MVmin | 6080 | ActOpMode | Actual operating mode | Read | 1=Off, 2=On, 3=Ventilation, 4=Economy, 5=Standby | |
| MVmin | 32321 | ActOpSta | Present unit status | Read | 1=NA, 2=Fire, 3=Emergency, 4=Replace Fan, 5=Fault, 6=Alarm, 7=Manual, 8=Panel Switch, 9=Local Switch, 10=NA, 11=BMS, 12=Scheduler, 13=Occupancy, 14=NA, 15=NA, 16=NA, 17=Ready | |
| MVmin | 39130 | AckAlmPls | Alarm acknowledge (acknowledges all alarms) | Write | 1=Off, 2=On | |
| MV | 24616 | SuWiSwtchCheckState | Summer Winter mode | Read | 1=Winter, 2=Summer | |
| MV | 46769 | AlmCl0 | Danger alarm (A) | Read | 1=Normal, 2=On | |
| MV | 42640 | AlmCl1 | Critical alarm (A) | Read | 1=Normal, 2=On | |
| MV | 38643 | AlmCl2 | Low alarm (B) | Read | 1=Normal, 2=On | |
| MV | 34514 | AlmCl3 | Warning alarm (C) | Read | 1=Normal, 2=On | |
| MVmin | 24562 | NetworkCtrl | Network source | Write | 1=Off, 2=On | |
| MV | 26007 | NetworkCtrlBMS | Network source | Write | 1=Auto, 2=Off, 3=On, 4=Ventilation, 5=Economy, 6=Boost | |
| MVmin | 28594 | SuWiNetworkChgover | Summer/Winter network changeover command | Write | 1=Winter, 2=Summer | |
| MV | 59712 | FireDamperCmd | Fire damper command | Read | 1=Close, 2=Open | |
| MV | 43819 | ExhEngUnit | Return air engineering Unit | Read | 1=%, 2=Pa, 3=m3/h | |
| MV | 54155 | SplyEngUnit | Supply air engineering Unit | Read | 1=%, 2=Pa, 3=m3/h | |
| MV | 13725 | HumEngUnit | Humidity engineering unit | Read | 1=%rH, 2=g/kg | |
| MV | 25214 | Pre-Htg Electrical | Pre-heating electrical command | Read | 1=Off, 2=Step 1, 3=Step 2 | |
| MV | 58176 | Electrical Heating State/Post Heating | Electrical heating command | Read | 1=Off, 2=Step 1, 3=Step 2 | |
| MV | 9333 | ClgDxStages | Cooling Dx actual stage | Read | 1=Off, 2=Stage 1, 3=Stage 2 | |
| MV | 1708 | CommTestEn | Enable Test | Write | 1=No, 2=Yes | |
| MVmin | 9493 | SuWiChgSrc | Set source for summer/winter changeover | Write | 1=Auto, 2=HMI, 3=BMS (BACnet) | |
| MV | 12316 | TimeSchedSt | Indicates time scheduler active mode | Read | 1=On, 2=Off, 3=Ventilation, 4=Economy | |
| MV | 28279 | ActFanStep | Indicates the active fan step | Read | 1=Off, 2=Stage 1, 3=Stage 2, 4=Stage 3 | |
| MV | 28561 | ActCtrlMode | Indicates mode for the regulation control | Read | 1=Room, 2=Exhaust, 3=Supply | |
| MV | 33544 | OpModeTspCopyUnitPls | Copy Monday time schedule to all weekdays | Write | 1=Off, 2=On |
No points match these filters.
Object ID lookup: Daikin Applied Airstream ADT air handler point IDs by name
AI45150SupplyTmpAI33923RmUTmp1AI28256ReturnAirTmpAI53218OutTmpAI29568PreHeatTempAI40895ExhaustTmpAI20400SupplyPrsAI39576ReturnPrsAI9497SupplyFlowAI38593ReturnFlowAI37799RoomHumAI3737AirQualityAI19419ERQ1LoadAI42249ERQ2LoadAI36987ERQGlobalLoadAI16189SplyOptDPTAI35989RtrnOptDPTAO59037SplyFanVarPosAO40119ExhFanVarPosAO39618HumidityCtrlPosAO37442ElectricalHtgPosAO42156HrecDampPosAO24312HrecPosAO30925CoolingPosAO26209HeatingPosAO62755FanTempCompPosAV52572SplyFanSpvSt1SpvAV57915SplyFanSpvEcSpvAV25092SplyFanSpvMaxForceAV45030ExhFanSpvSt1SpvAV6118ExhFanSpvEcSpvAV2525ExhFanSpvMaxForceAV56628SplyFanActValAV59694ExhFanActValAV46589SplyFanActSpvAV33255ExhFanActSpvAV22649AirQSpvAV61369RmEnthAV17315RmHumAbsAV11342HumSpvRelSpvDehumAV10627HumSpvRelSpvHumAV38385ActCtrlValHumAV8970TmpSpvCoSpvClgAV22817TmpSpvCoSpvHtgAV61866TmpSpvEcSpvClgAV35713TmpSpvEcSpvHtgAV4018ActMainSpvHtgAV30105ActMainSpvClgAV56276ActTempSetptAV52988ActCtrlValAV41552HrecDampminFrshAirAV24338SuWiSwtchCheckOutTmpDampdAV1206RoomUnitsOccTmAV8926RoomUnitOffsetAV753MaxSupplyTempSuAV7560MaxSupplyTempWiAV18262MinSupplyTempSuAV22575MinSupplyTempWiAV47818SupplyFanRunHoursAV52983ReturnFanRunHoursAV19448Pursuit – SetpointAV23744Pursuit – Setpoint EcoAV12721Pursuit – BandAV56164COPKFactorBI21294HtgFrstDtctrBI47847HtgPmpAlmBI4964ElHtgAlmBI62931HRecAlmBI40242ClgPmpAlmBI28757SplyFanAlmBI55865ExhFanAlmBI28514FireAlmBI13699FilterAlmBI11643ExtCtrl1BI9864EmergencyStopBI19724ERQ1OnOffBI48775ERQ1DefrostBI33772ERQ2OnOffBI30450ERQ2DefrostBI57484ElectricalPreheatingFaultBI610ERQ1AlarmBI16951ERQ2AlarmBI29832ERQ1LeakageBI48381ERQ2LeakageBI54741LowFlowThrAlmBI41868GenAlmBO6170DamperSplyOnOffBO18044HumidityCtrlCmdOnOffBO10276CoolingPmpCmdOnOffBO10264HeatingPmpCmdOnOffBO5714AlmOutHighSCH31059ScheduleStMO21928SplyFanCmdStMO14719ExhFanCmdStMV6080ActOpModeMV32321ActOpStaMV39130AckAlmPlsMV24616SuWiSwtchCheckStateMV46769AlmCl0MV42640AlmCl1MV38643AlmCl2MV34514AlmCl3MV24562NetworkCtrlMV26007NetworkCtrlBMSMV28594SuWiNetworkChgoverMV59712FireDamperCmdMV43819ExhEngUnitMV54155SplyEngUnitMV13725HumEngUnitMV25214Pre-Htg ElectricalMV58176Electrical Heating State/Post HeatingMV9333ClgDxStagesMV1708CommTestEnMV9493SuWiChgSrcMV12316TimeSchedStMV28279ActFanStepMV28561ActCtrlModeMV33544OpModeTspCopyUnitPls
Integration notes
- Which objects exist depends on the AHU configuration.
- Most objects share instance numbers with the Modular Light (ALB) and ADK guides; the ERQ load, defrost, alarm and R-32 leakage objects are specific to this guide.
- ScheduleSt (31059) is printed in its own Schedule table; it is listed as SCH.
- The MS/TP device instance is derived from the production number and date code.
- The guide also covers connecting a Daikin iTM (intelligent Touch Manager) over BACnet IP.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Airstream ADT air handler (Daikin Applied Europe) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
How many BACnet points does the Daikin Applied Airstream ADT air handler (Daikin Applied Europe) have?
This list has 118 BACnet objects: 17 analog inputs, 9 analog outputs, 38 analog values, 22 binary inputs, 5 binary outputs, 2 multi-state outputs, 1 schedule, 24 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied Airstream ADT air handler (Daikin Applied Europe) BACnet points are writable?
30 of the 118 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied Airstream ADT air handler (Daikin Applied Europe) BACnet documentation?
The source is BAS Integration Guide - BACnet protocol (ADT, Airstream) (D-EIGOC00104-25_01EN), published free by Daikin Applied at https://www.daikinapplied.eu/hubfs/portale-documentale/D_EIGOC00104_25_01EN_Airstream_ADT.pdf.
What are the minimum BACnet points to integrate the Daikin Applied Airstream ADT air handler (Daikin Applied Europe)?
Start with MV 24562 NetworkCtrl (Network on/off (1 = Off, 2 = On)); MV 28594 SuWiNetworkChgover (Summer/winter command (1 = Winter, 2 = Summer)); MV 9493 SuWiChgSrc (Must be 3 = BMS for the summer/winter command); AV 52572 SplyFanSpvSt1Spv (Supply fan setpoint (units per SplyEngUnit)); MV 39130 AckAlmPls (Acknowledge all alarms (2 = On)); MV 6080 ActOpMode (Operating mode (Off/On/Ventilation/Economy/Standby)); MV 32321 ActOpSta (Why the unit runs or stops (e.g. 11 = BMS)); AI 45150 SupplyTmp (Supply air temperature); AV 52988 ActCtrlVal (Temperature being controlled); BI 41868 GenAlm (General alarm (1 = Alarm)).
How do I enable BMS control of the Daikin Applied Airstream ADT air handler (Daikin Applied Europe)?
NetworkCtrl (MV 24562, "Network source", 1 = Off / 2 = On) is the writable on/off object; ActOpSta (MV 32321) reports 11 = BMS when the network is in control. Summer/winter follows the BMS only when SuWiChgSrc (MV 9493) = 3 (BMS); then write SuWiNetworkChgover (MV 28594). The guide gives no further procedure.
How do I check these points on the real Airstream ADT air handler (Daikin Applied Europe)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: BAS Integration Guide - BACnet protocol (ADT, Airstream) · D-EIGOC00104-25_01EN. Object names, instances and units are reproduced as published; descriptions are our own.