- Home
- BACnet points lists
- Daikin Applied
- Maverick I Packaged Rooftop Unit Controller (MPS)
Rooftop unit controller · BACnet points list
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS) BACnet points list
Updated 4 November 2026
The Maverick I rooftop unit controller talks BACnet IP, BACnet Ethernet or BACnet MS/TP through a plug-in BACnet communication module (a separate module covers LonWorks). The object list is short: unit state and capacities, application mode, emergency shutdown, occupancy, space, outdoor, discharge and return temperatures, setpoints, economizer and CO2 ventilation, dehumidification, VAV pressure and supply temperature points, two field inputs and alarm handling.
This page lists 54 BACnet objects for the Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS) — 31 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- Maverick I Packaged Rooftop Unit Controller (MPS)
- Equipment
- Rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 54 (31 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 47065 (IP) / 3002 + MAC (MS/TP)
- Also known as
- Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Set the keypad occupancy override setting to Network, then schedule the unit with Occupancy Schedule (MV 8) or force it with Occupancy Mode (MV 7). Write Application Mode and the occupied setpoints, and use Emergency Override to stop the unit. Read Unit State, capacities, temperatures and Current Alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 8 | Occupancy Schedule | Scheduled occupancy from the BMS (Occ/Unocc) | Write |
| MV 7 | Occupancy Mode | Occupancy override (Occ/Unocc/TntOvrd/Auto) | Write |
| MV 10 | Emergency Override | Network shutdown (2) / Normal (1) | Write |
| MV 5 | Application Mode | Off/heat only/cool only/fan only/auto | Write |
| AV 9 | Occupied Cooling Setpoint | Occupied cooling setpoint | Write |
| AV 11 | Occupied Heating Setpoint | Occupied heating setpoint | Write |
| MV 15 | Unit State | Current operating state | Read |
| AI 3 | Effective Space Temperature | Space temperature in use (local or network) | Read |
| AI 1 | Discharge Air Temperature | Supply (discharge) air temperature | Read |
| AV 27 | Current Alarm | Highest-priority active alarm number, 0 = none | Read |
Enable & remote start
Network occupancy scheduling needs the keypad occupancy override setting (OCCPCY OVERR SP) set to Network; then Occupancy Schedule (MV 8) or Occupancy Mode (MV 7) drives the unit. Emergency Override (MV 10) = Shutdown stops the unit and it will not restart by schedule or any other means until Normal is written.
Heartbeat & communication loss
Receive Heartbeat (AV 43, seconds, default 0 = off). When set, the network inputs for occupancy schedule, application mode, remote supply fan capacity, remote space temperature, economizer enable and remote space IAQ must be rewritten within that time; otherwise occupancy reverts to Powerup, application mode and economizer enable to Auto, and the remote values to invalid.
Sensors & values from the BMS
Remote Space Temperature (AV 28), Remote Outdoor Air Temperature (AV 29) and Remote Space IAQ (AV 31) take values from the BMS; the effective values (AI 3, AI 4) fall back to the local sensor if the network value is unreliable. Remote Space Temperature Spt Adjust (AV 56) is used only when Room Sensor Setpoint Enable (BV 65) is set to Disabled (Network).
Network setup
- BACnet IP defaults: IP 172.16.5.8, mask 255.255.0.0, UDP 47808, gateway 0.0.0.0; write 0.0.0.0 as the IP to turn on DHCP.
- BACnet MS/TP defaults: MAC 0, 19200 baud (9600-76800 selectable); cycle power after changing the MAC.
- Default device instance is 47065 for IP and 3002 plus the MAC for MS/TP; the device name is RTU_C followed by the instance.
- Addressing is set with the BACnet communication module's web configuration tool (IM 1000); the module reset button restores factory defaults.
- The communication type must be set to match the network (default BACnet IP).
Watch out for
- Writes to configuration points are stored in EEPROM/flash with a limited write life; don't write setpoints and configuration cyclically.
- Clear All Alarms (BV 66) and Clear One Alarm (AV 57) only clear clearable alarms; some faults (smoke, emergency stop, sensor failure) can't be cleared from the network.
- Values switch between English and metric with BACnet Unit Support (MV 16); check it before scaling temperatures.
- Alarm numbers 1-99 are warnings, 100-199 problems, 200-254 shutdown faults.
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 15 | Unit State | Unit operating state | Read | 1=Off, 2=Start, 4=FanOnly, 6=Htg, 7=Econo, 8=Clg | |
| MV | 16 | BACnet Unit Support | Units sent to BACnet: English or metric (default metric) | Write | ||
| AV | 1 | Cooling Capacity | Compressor cooling capacity | % | Read | |
| AV | 2 | Heating Capacity Primary | Primary heating capacity | % | Read | |
| AV | 44 | Heating Capacity Secondary | Secondary heating capacity | % | Read | |
| AV | 15 | Economizer Capacity | Economizer position feedback | % | Read | |
| AI | 8 | Effective Supply Fan Capacity | Supply fan drive capacity | % | Read | |
| AI | 10 | Return/Exhaust Fan Capacity | Return or exhaust fan capacity | % | Read | |
| MVmin | 5 | Application Mode | Application mode command | Write | 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly, 5=Auto | |
| MVmin | 10 | Emergency Override | Network shutdown command | Write | 1=Normal, 2=Shutdown | |
| MV | 49 | Indoor Fan Occupancy | Indoor fan mode: continuous or cycling | Write | 1=Continous Mode, 2=Cycle On in Heating/Cooling, 3=Continous in Occupied and Cycle in Unoccupied | |
| MV | 6 | Effective Occupancy | Effective occupancy state | Read | 1=Occ, 2=Unocc, 3=TntOvrd | |
| MVmin | 8 | Occupancy Schedule | Occupancy scheduler input from the BMS | Write | 1=Occ, 2=Unocc, 3=NUL (Powerup) | |
| MVmin | 7 | Occupancy Mode | Occupancy mode override | Write | 1=Occ, 2=Unocc, 3=TntOvrd, 4=NUL(Auto) | |
| AV | 3 | Occupancy Schedule Override Setpoint | Bypass (timed override) duration, 0 disables | min | Write | |
| AImin | 3 | Effective Space Temperature | Space temperature in use (local or network) | °F/°C | Read | |
| AV | 4 | Local Space Temperature | Local space temperature sensor | °F/°C | Read | |
| AV | 28 | Remote Space Temperature | Space temperature written by the BMS | °F/°C | Write | |
| AI | 4 | Effective Outdoor Air Temperature | Outdoor air temperature in use (local or network) | °F/°C | Read | |
| AV | 5 | Local OA Temperature | Local outdoor air temperature sensor | °F/°C | Read | |
| AV | 29 | Remote Outdoor Air Temperature | Outdoor air temperature written by the BMS | °F/°C | Write | |
| AImin | 1 | Discharge Air Temperature | Discharge air temperature | °F/°C | Read | |
| AI | 2 | Return Air Temperature | Return air temperature | °F/°C | Read | |
| AV | 50 | Effective Setpoint | Active space setpoint | °F/°C | Read | |
| AV | 51 | Local Space Temperature Setpoint | Local space sensor setpoint | °F/°C | Read | |
| BV | 65 | Room Sensor Setpoint Enable | Enable local hard-wired setpoint adjust | Write | 0=Remote (Disabled), 1=Local (Enabled) | |
| AV | 56 | Remote Space Temperature Spt Adjust | Space setpoint written by the BMS | °F/°C | Write | |
| AVmin | 9 | Occupied Cooling Setpoint | Occupied cooling setpoint | °F/°C | Write | |
| AVmin | 11 | Occupied Heating Setpoint | Occupied heating setpoint | °F/°C | Write | |
| AV | 10 | Unoccupied Cooling Setpoint | Unoccupied cooling setpoint | °F/°C | Write | |
| AV | 12 | Unoccupied Heating Setpoint | Unoccupied heating setpoint | °F/°C | Write | |
| MV | 32 | Economizer Enable | Economizer free cooling / ventilation enable | Write | 1=Disable Free Cooling, Enable Ventilation, 2=Enable Free Cooling, Enable Ventilation, 3=Auto (unit control decides), 4=Disable All Economizer Functionality | |
| AV | 53 | Demand Control Ventilation Limit | Minimum damper position under CO2 override | % | Write | |
| AV | 54 | Ventilation Limit | Maximum damper position under CO2 override | % | Write | |
| AI | 13 | Local Space CO2 | Space CO2 from optional sensor | ppm | Read | |
| AV | 31 | Remote Space IAQ | Space CO2/IAQ written by the BMS | ppm | Write | |
| AV | 48 | Space CO2 High Limit Setpoint | Space CO2 high limit; 0 disables | ppm | Write | |
| AV | 55 | Exhaust On/Off Setpoint | Damper position that switches exhaust fan | % | Write | |
| AV | 65 | Space RH Configuration Setpoint | Space RH setpoint configuration | %RH | Write | |
| AV | 66 | RH Setpoint | Space RH setpoint; 0 disables dehumidification | %RH | Write | |
| AI | 14 | VAV Pressure | VAV system pressure | in. w.c. | Read | |
| AV | 67 | VAV Supply Temp | VAV supply air temperature setpoint | °F/°C | Write | |
| AV | 68 | VAV Supply Pressure | VAV supply pressure setpoint | in. w.c. | Write | |
| AV | 69 | VAV Max Pressure | VAV maximum pressure setpoint | in. w.c. | Write | |
| AV | 61 | Field Input 1 | Field input 1 (temperature) | °F/°C | Read | |
| AV | 62 | Field Input 2 | Field input 2 (configurable unit type) | Read | ||
| AV | 63 | Configurable Input 2 Type (low range) | Field input 2 low voltage range | Write | ||
| AV | 64 | Configurable Input 2 Type (high range) | Field input 2 high voltage range | Write | ||
| AVmin | 27 | Current Alarm | Highest-priority active alarm number, 0 = none | Read | ||
| BV | 66 | Clear All Alarms | Write 1 to clear all clearable alarms | Write | 0=No Alarms, 1=Clear Alarms | |
| AV | 57 | Clear One Alarm | Write an alarm number to clear it | Write | ||
| AV | 43 | Receive Heartbeat | Receive heartbeat timeout; 0 disables | s | Write | |
| AV | 45 | Integrated Furnace Controller Software Version | Integrated furnace controller software version | Read | ||
| AV | 46 | Honeywell Economizer Software Version | Honeywell economizer software version | Read |
No points match these filters.
Object ID lookup: Daikin Applied Maverick I Packaged Rooftop Unit Controller point IDs by name
MV15Unit StateMV16BACnet Unit SupportAV1Cooling CapacityAV2Heating Capacity PrimaryAV44Heating Capacity SecondaryAV15Economizer CapacityAI8Effective Supply Fan CapacityAI10Return/Exhaust Fan CapacityMV5Application ModeMV10Emergency OverrideMV49Indoor Fan OccupancyMV6Effective OccupancyMV8Occupancy ScheduleMV7Occupancy ModeAV3Occupancy Schedule Override SetpointAI3Effective Space TemperatureAV4Local Space TemperatureAV28Remote Space TemperatureAI4Effective Outdoor Air TemperatureAV5Local OA TemperatureAV29Remote Outdoor Air TemperatureAI1Discharge Air TemperatureAI2Return Air TemperatureAV50Effective SetpointAV51Local Space Temperature SetpointBV65Room Sensor Setpoint EnableAV56Remote Space Temperature Spt AdjustAV9Occupied Cooling SetpointAV11Occupied Heating SetpointAV10Unoccupied Cooling SetpointAV12Unoccupied Heating SetpointMV32Economizer EnableAV53Demand Control Ventilation LimitAV54Ventilation LimitAI13Local Space CO2AV31Remote Space IAQAV48Space CO2 High Limit SetpointAV55Exhaust On/Off SetpointAV65Space RH Configuration SetpointAV66RH SetpointAI14VAV PressureAV67VAV Supply TempAV68VAV Supply PressureAV69VAV Max PressureAV61Field Input 1AV62Field Input 2AV63Configurable Input 2 Type (low range)AV64Configurable Input 2 Type (high range)AV27Current AlarmBV66Clear All AlarmsAV57Clear One AlarmAV43Receive HeartbeatAV45Integrated Furnace Controller Software VersionAV46Honeywell Economizer Software Version
Integration notes
- Names are the point names from the main BACnet table (Table 7). The controller's own object names are short codes shown in the parameter detail pages (for example ApplicCmd, OccManCmd, EmergOverride, DischAirTemp).
- Table 7 lists AV 63 and AV 64 together as Configurable Input 2 Type; the detail pages show them as the field input 2 low and high voltage range, so they are named that way here.
- Three Device-object properties in the table (communication module version, application version, Location) are not separate objects and are left out.
- BACnet Unit Support (MV 16) switches all values between English and metric; the doc gives metric as the default.
- VAV points AI 14 and AV 67-69 were added in 2022 (BACnet software 2.06, unit controller 2.36 or later); field inputs and indoor fan mode need controller 1.5 or later.
- The detail pages print some instance numbers inconsistently; instances here follow Table 7.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Maverick I Packaged Rooftop Unit Controller (MPS) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
How many BACnet points does the Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS) have?
This list has 54 BACnet objects: 8 analog inputs, 35 analog values, 2 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS) BACnet points are writable?
31 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS) BACnet documentation?
The source is Maverick I Packaged Rooftop Systems Unit Controller Protocol Information (ED 15125-6), revision 2022-06, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/Maverick%20I%20Rooftop%20Unit%20Controller%20Protocol%20Information%20-%20ED%2015125-6.pdf.
What are the minimum BACnet points to integrate the Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)?
Start with MV 8 Occupancy Schedule (Scheduled occupancy from the BMS (Occ/Unocc)); MV 7 Occupancy Mode (Occupancy override (Occ/Unocc/TntOvrd/Auto)); MV 10 Emergency Override (Network shutdown (2) / Normal (1)); MV 5 Application Mode (Off/heat only/cool only/fan only/auto); AV 9 Occupied Cooling Setpoint (Occupied cooling setpoint); AV 11 Occupied Heating Setpoint (Occupied heating setpoint); MV 15 Unit State (Current operating state); AI 3 Effective Space Temperature (Space temperature in use (local or network)); AI 1 Discharge Air Temperature (Supply (discharge) air temperature); AV 27 Current Alarm (Highest-priority active alarm number, 0 = none).
How do I enable BMS control of the Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)?
Network occupancy scheduling needs the keypad occupancy override setting (OCCPCY OVERR SP) set to Network; then Occupancy Schedule (MV 8) or Occupancy Mode (MV 7) drives the unit. Emergency Override (MV 10) = Shutdown stops the unit and it will not restart by schedule or any other means until Normal is written.
Does the Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS) need a BACnet heartbeat or have a communication timeout?
Receive Heartbeat (AV 43, seconds, default 0 = off). When set, the network inputs for occupancy schedule, application mode, remote supply fan capacity, remote space temperature, economizer enable and remote space IAQ must be rewritten within that time; otherwise occupancy reverts to Powerup, application mode and economizer enable to Auto, and the remote values to invalid.
Can the BMS supply sensor values to the Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)?
Remote Space Temperature (AV 28), Remote Outdoor Air Temperature (AV 29) and Remote Space IAQ (AV 31) take values from the BMS; the effective values (AI 3, AI 4) fall back to the local sensor if the network value is unreliable. Remote Space Temperature Spt Adjust (AV 56) is used only when Room Sensor Setpoint Enable (BV 65) is set to Disabled (Network).
How do I check these points on the real Maverick I Packaged Rooftop Unit Controller (MPS)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Fan coil unit controller
Daikin Applied MicroTech III Fan Coil Unit Controller
Daikin Applied fan coil units with the MicroTech III unit controller and the plug-in BACnet MS/TP communication module.
Also known as: MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: Maverick I Packaged Rooftop Systems Unit Controller Protocol Information · ED 15125-6 · rev. 2022-06. Object names, instances and units are reproduced as published; descriptions are our own.