 "manufacturer": "Daikin Applied",
 "manufacturer_slug": "daikin-applied",
 "model": "MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)",
 "model_slug": "microtech-mt2300-wshp-smartsource-r32",
 "short_model": "MT2300 SmartSource R32 WSHP",
 "aliases": [
  "MT2300",
  "SmartSource Series2",
  "SmartSource SS2C",
  "SCH",
  "SDH",
  "SMH",
  "SNH",
  "SSH",
  "STH",
  "ED 19129"
 ],
 "equipment_type": "Water source heat pump controller",
 "applies_to": "Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).",
 "summary": "The MicroTech MT2300 is the controller on Daikin's R32 SmartSource heat pumps. It joins BACnet MS/TP through a separate BACnet communication module, and one object list serves both the SmartSource Series2 and the two-compressor SS2C applications. Points cover setpoints, network overrides for occupancy, mode and space temperature, water and refrigerant temperatures, fan speed, the board's configuration switches, A2L refrigerant-leak inputs and alarm codes.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "3101000 + MS/TP MAC address",
 "access_inferred": false,
 "notes": [
  "Configuration objects (names starting with cp) are stored in flash; the guide warns that repeated writes wear it out.",
  "Network override objects (access C) revert to their default (Null) after a controller reboot.",
  "BI 15-34 report the baseboard and I/O expansion module configuration switches; some switches mean different things on Series2 and SS2C units.",
  "AV 411 is named MacAddress (writable) when address switch S3 is at 255, otherwise MacAddressSwitch (read-only).",
  "MV 2 and MV 5 return the alarm numbers from the guide's alarm table (1-28)."
 ],
 "source": {
  "title": "MicroTech SmartSource WSHP BACnet Network Integration Guide (MT2300, R32)",
  "doc_number": "ED 19129-1",
  "revision_date": "2024-05",
  "url": "https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MT%20SmartSource%20WSHP%20BACnet%20Protocol%20Document%20ED%2019129-1.pdf/"
 },
 "integration": {
  "summary": "Commission the BACnet module (baud, MAC and instance) through its serial menu, then run the unit from the BMS with the network override objects: occupancy (MSV 7 or MSV 8), application mode (MSV 10) and compressor enable (MSV 1). Feed space temperature or a setpoint from the network if needed, and set Receive Heartbeat so overrides drop back when the BMS stops writing.",
  "minimum_points": [
   {
    "ref": "MV 7",
    "name": "OccManCmd",
    "why": "Occupancy override from the BMS"
   },
   {
    "ref": "MV 10",
    "name": "ApplicMode",
    "why": "Application mode (Auto/Heat/Cool/Off/Fan Only/Dehumid)"
   },
   {
    "ref": "MV 1",
    "name": "ComprEnable",
    "why": "Compressor enable, usually from loop flow proof"
   },
   {
    "ref": "AV 19",
    "name": "NetworkSetpoint",
    "why": "Network reference setpoint"
   },
   {
    "ref": "BV 1",
    "name": "ClearAlarm",
    "why": "Clear active fault alarms"
   },
   {
    "ref": "MV 4",
    "name": "McQWSHPStatus",
    "why": "Unit operating state"
   },
   {
    "ref": "AV 22",
    "name": "EffectSpaceTemp",
    "why": "Space temperature used for control"
   },
   {
    "ref": "AI 2",
    "name": "LWT",
    "why": "Leaving water temperature"
   },
   {
    "ref": "MV 2",
    "name": "CurrentAlarm",
    "why": "Highest-priority active alarm"
   }
  ],
  "enable": "No local/remote switch. The network override objects act as soon as they are written: Occupancy Override Input (MSV 7) or Occupancy Scheduler (MSV 8) set occupancy, Application Mode (MSV 10) limits the unit to Auto/Heat/Cool/Off/Fan Only/Dehumid and overrides the room sensor mode switch, and Compressor Enable (MSV 1) permits compressor operation. All revert to Null after a controller reboot.",
  "heartbeat": "Receive Heartbeat (AV 20, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled) sets how long a supported network override may go without being rewritten before it reverts to its default; each supported override has its own timer. Send Heartbeat (AV 21) is not supported by the BACnet module; use COV instead.",
  "remote_sensors": "Write space temperature to AV 18 and space humidity to AV 45; a network dewpoint goes to AV 51. AV 19 sets the reference setpoint only after local setpoint adjust is disabled with MSV 14 = 1. AV 35 shifts the occupied/standby setpoints, MSV 9 takes a network occupancy sensor, MSV 16 overrides the humidistat and MSV 3 the fan On/Auto switch.",
  "setup": [
   "Device instance is System Minimum Instance (AV 412, default 3101000) plus the MS/TP MAC address.",
   "Baud (default 38400) and Max Masters are set from the module's serial menu: DB-9 port, 19200 bps 8-N-1, null-modem cable; press S to save.",
   "With address switch S3 at 255 (factory default) the MAC is acquired during commissioning and can then be changed through AV 411; any other S3 value is used as a fixed MAC.",
   "Max APDU length is fixed at 480."
  ],
  "gotchas": [
   "cp... configuration objects are written to flash; do not write them cyclically.",
   "Network overrides revert to Null on reboot, so the BMS must restore them.",
   "Changing Units (MSV 15) from English to Metric changes the temperature values the BMS reads.",
   "An A2L refrigerant leak or loss of A2L board power puts the unit into an alarm state."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "LocalSpaceTemp",
   "description": "Local Space Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "LWT",
   "description": "Leaving Water Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "EWT",
   "description": "Entering Water Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "DischAirTemp",
   "description": "Discharge Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "LocalSetpt",
   "description": "Local Setpoint Adjust",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Comp1SuctionTemp",
   "description": "Compressor 1 Suction Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Comp2SuctionTemp",
   "description": "Compressor 2 Suction Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Brownout",
   "description": "Brownout Voltage Reading",
   "units": "counts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "LocalSpaceRH",
   "description": "Local Space Humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "RAT",
   "description": "Return Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "cpOccupied_Cool_Setpt",
   "description": "Occupied Cooling Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "cpStandby_Cool_Setpt",
   "description": "Standby Cool Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "cpUnoccupied_Cool_Setpt",
   "description": "Unoccupied Cool Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "cpOccupied_Heat_Setpt",
   "description": "Occupied Heat Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "cpStandby_Heat_Setpt",
   "description": "Standby Heat Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "cpUnoccupied_Heat_Setpt",
   "description": "Unoccupied Heat Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "cpBypassTime",
   "description": "Local Bypass Time Setpoint",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "cpIntStgOffTmr",
   "description": "Interstage OFF Timer",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "cpBrownoutRef",
   "description": "Brownout Reference Setpoint",
   "units": "counts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "cpOccDiff",
   "description": "Occupied Setpoint Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "cpLowTempProtGL",
   "description": "Compressor Low Suction Temp Protection Setpoint: Glycol",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "cpLowTempProt",
   "description": "Compressor Low Suction Temp Protection Setpoint: Water",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "cpLowTmpProtDif",
   "description": "Compressor Low Suction Temp Protection Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "cpIntStgOnTmr",
   "description": "Interstage ON Timer",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "cpMinCompOffTmr",
   "description": "Compressor Minimum OFF Timer",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "cpMinCompOnTmr",
   "description": "Compressor Minimum ON Timer",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "cpUnoccDiff",
   "description": "Unoccupied Setpoint Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Network SpaceTemp",
   "description": "Space Temperature Input",
   "units": "°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "NetworkSetpoint",
   "description": "Network Temperature Setpoint",
   "units": "°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "cpRcvHrtBt",
   "description": "Receive Heartbeat",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "cpSndHrtBt",
   "description": "Send Heartbeat",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "EffectSpaceTemp",
   "description": "Effective Space Temperature Output",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "EffectSetpt",
   "description": "Effective Setpoint Output",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "SetptShift",
   "description": "Setpoint Shift Output",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "cpSptAdjMax",
   "description": "Long Range Setpoint Adjust Maximum",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "cpSptAdjMin",
   "description": "Long Range Setpoint Adjust Minimum",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "cpHydroClgOnSpt",
   "description": "Hydronic Cooling ON Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "cpHydronicDiff",
   "description": "Hydronic Setpoint Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "cpLowLwtDiff",
   "description": "Low Leaving Water Temp Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "cpLowEwtSptGly",
   "description": "Low EWT Setpoint for Glycol",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "cpLowEwtSptWtr",
   "description": "Low EWT Setpoint for Water",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "cpHydroHtgOnSpt",
   "description": "Hydronic Heating ON Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "cpStg2SptDiff",
   "description": "Second Stage Setpoints Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "cpLowPresAlmDly",
   "description": "Compressor Low Pressure Alarm Delay",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "SetptOffset",
   "description": "Temperature Setpoint Offset Input",
   "units": "°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "cpStg3SptDiff",
   "description": "Third Stage Heating Setpoint Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "cpStg4SptDiff",
   "description": "Fourth Stage Heating Setpoint Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "FanSpeedCmd",
   "description": "Fan Speed Output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "FanRunHours",
   "description": "Fan Run Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "CompRunHours",
   "description": "Compressor 1 Run Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "CompStarts",
   "description": "Compressor 1 Starts",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "Comp2RunHours / CompHiCapRunHours",
   "description": "Compressor 2 / Compressor High Capacity Run Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Comp2Starts / CompHiCapStarts",
   "description": "Compressor 2 / Compressor High Capacity Starts",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "EffectSpaceRH",
   "description": "Effective Space Humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "NetworkSpaceRH",
   "description": "Network Space Humidity Override",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "cpSpaceRH_Diff",
   "description": "Space Humidity Setpoint Differential",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "cpSpaceRH_Setpt",
   "description": "Space Humidity Setpoint",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "EffectControlTemp",
   "description": "Effective Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "cpWaitForFlow",
   "description": "Compressor Wait for Flow Timer",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "LocalDewpointCalc",
   "description": "Local Space Dewpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "NetworkDewpoint",
   "description": "Network Dewpoint Override",
   "units": "°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "EffectiveDewpoint",
   "description": "Effective Dewpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "cpDewpointSetp",
   "description": "Dewpoint Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "cpDewpointDiff",
   "description": "Dewpoint Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "cpVsFanOnlyPWM",
   "description": "Variable Fan Speed PWM - Fan-Only",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "cpVsDehumPWM",
   "description": "Variable Fan Speed PWM - Dehumidification",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "cpVsCool1PWM",
   "description": "Variable Fan Speed PWM - Cool Stage 1",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "cpVsCool2PWM",
   "description": "Variable Fan Speed PWM -Cool Stage 2",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "cpVsHeat1PWM",
   "description": "Variable Fan Speed PWM - Heat Stage 1",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "cpVsHeat2PWM",
   "description": "Variable Fan Speed PWM - Heat Stage 2",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "cpVsElecHeatPWM",
   "description": "Variable Fan Speed PWM - Electric Heat",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "cpVsHydroHeatPWM",
   "description": "Variable Fan Speed PWM - Hydronic Heat",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "cpVsHydroCoolPWM",
   "description": "Variable Fan Speed PWM - Hydronic Cool",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 411,
   "name": "MacAddress",
   "description": "MAC Address / Address Switch (named MacAddressSwitch, read-only, when switch S3 is below 255)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 412,
   "name": "SystemMinInstance",
   "description": "System Minimum Instance",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "A2L_Fault",
   "description": "A2L Board Fault",
   "units": "",
   "access": "R",
   "states": "0=Alarm; 1=Normal"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "EmergShutDn",
   "description": "Emergency Shutdown",
   "units": "",
   "access": "R",
   "states": "0=Normal; 1=Shutdown"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "HiPressure1",
   "description": "Compressor 1 High Pressure",
   "units": "",
   "access": "R",
   "states": "0=Normal; 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "LoPressure1",
   "description": "Compressor 1 Low Pressure",
   "units": "",
   "access": "R",
   "states": "0=Normal; 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Tstat_G",
   "description": "Thermostat Fan Input",
   "units": "",
   "access": "R",
   "states": "0=Off (Auto); 1=On"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Tstat_W1",
   "description": "Thermostat - Heating Stage 1",
   "units": "",
   "access": "R",
   "states": "0=Inactive; 1=Active"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Tstat_W2",
   "description": "Thermostat - Heating Stage 2",
   "units": "",
   "access": "R",
   "states": "0=Inactive; 1=Active"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Tstat_Y1",
   "description": "Thermostat - Cooling Stage 1",
   "units": "",
   "access": "R",
   "states": "0=Inactive; 1=Active"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Tstat_Y2",
   "description": "Thermostat - Cooling Stage 2",
   "units": "",
   "access": "R",
   "states": "0=Inactive; 1=Active"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "OccSw_In",
   "description": "Occupancy Switch Setting",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "HiPressure2",
   "description": "Compressor 2 High Pressure",
   "units": "",
   "access": "R",
   "states": "0=Normal; 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "LoPressure2",
   "description": "Compressor 2 Low Pressure",
   "units": "",
   "access": "R",
   "states": "0=Normal; 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "Tstat_W3",
   "description": "Thermostat - Heating Stage 3",
   "units": "",
   "access": "R",
   "states": "0=Inactive; 1=Active"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Tstat_W4_Y3",
   "description": "Thermostat - Heating Stage 4 / Cooling Stage 3",
   "units": "",
   "access": "R",
   "states": "0=Inactive; 1=Active"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "BB_ConfigSw1",
   "description": "Unit Operation",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "BB_ConfigSw2",
   "description": "Fan Operation",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "BB_ConfigSw3",
   "description": "Loop Fluid",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "BB_ConfigSw4",
   "description": "Freeze Fault Protection",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "BB_ConfigSw5",
   "description": "Room Sensor Setpoint Adjust",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "BB_ConfigSw6",
   "description": "Thermostat/Room Sensor",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "BB_ConfigSw7",
   "description": "Config switch 7: Compressor Heating Enable (Series2) / Compressor Availability (SS2C)",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "BB_ConfigSw8",
   "description": "Config switch 8: I/O Expansion Module (Series2) / Compressor Availability (SS2C)",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "BB_ConfigSw9",
   "description": "Baseboard Application Select",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "BB_ConfigSw10",
   "description": "Discrete Variable Fan Select",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "IO_ConfigSw1",
   "description": "Variable Fan Speed Selection (switch 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "IO_ConfigSw2",
   "description": "Variable Fan Speed Selection (switch 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "IO_ConfigSw3",
   "description": "Variable Fan Speed Selection (switch 3)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "IO_ConfigSw4",
   "description": "Variable Fan Speed Selection (switch 4)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "IO_ConfigSw5",
   "description": "Secondary Heating Options",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "IO_ConfigSw6",
   "description": "Secondary Heating Options (switch 6)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "IO_ConfigSw7",
   "description": "Hot Gas Reheat (HGR)",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "IO_ConfigSw8",
   "description": "Waterside Economizer (WSE)",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "IO_ConfigSw9",
   "description": "I/O Expansion Module Application Select",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "IO_ConfigSw10",
   "description": "Compressor Dual Speed Option (Series2) / Lead Compressor Select (SS2C)",
   "units": "",
   "access": "R",
   "states": "0=Off; 1=On"
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "Humidistat",
   "description": "Humidistat Input",
   "units": "",
   "access": "R",
   "states": "0=Inactive; 1=Active"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Alarm",
   "description": "Thermostat Alarm",
   "units": "",
   "access": "R",
   "states": "0=Alarm output command is Off (0 VAC); 1=Alarm output command is On (24 VAC)"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Comp1Out",
   "description": "Compressor 1",
   "units": "",
   "access": "R",
   "states": "0=Compressor 1 command is Off; 1=Compressor 1 command is On"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "FanMainOut",
   "description": "Fan Main Enable",
   "units": "",
   "access": "R",
   "states": "0=Fan main command is Off; 1=Fan main command is On"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "FanLowOut",
   "description": "Fan Speed",
   "units": "",
   "access": "R",
   "states": "0=Fan high speed command is On; 1=Fan low speed command is On"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "PumpOut",
   "description": "Pump Request",
   "units": "",
   "access": "R",
   "states": "0=Pump command is Off; 1=Pump command is On"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "RevVlv1Out",
   "description": "Reversing Valve 1",
   "units": "",
   "access": "R",
   "states": "0=Reversing valve 1 command is Off (cooling); 1=Reversing valve 1 command is On (heating)"
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "Comp2Out",
   "description": "Compressor 2 / Compressor High Capacity",
   "units": "",
   "access": "R",
   "states": "0=Compressor 2 command is Off; 1=Compressor 2 command is On"
  },
  {
   "type": "BO",
   "instance": 8,
   "name": "RevVlv2Out",
   "description": "Reversing Valve 2",
   "units": "",
   "access": "R",
   "states": "0=Reversing valve 2 command is Off (cooling); 1=Reversing valve 2 command is On (heating)"
  },
  {
   "type": "BO",
   "instance": 9,
   "name": "AuxHeat1Out",
   "description": "Auxiliary Heat 1",
   "units": "",
   "access": "R",
   "states": "0=Electric heat 1 command is Off; 1=Electric heat 1 command is On"
  },
  {
   "type": "BO",
   "instance": 10,
   "name": "AuxHeat2Out",
   "description": "Auxiliary Heat 2",
   "units": "",
   "access": "R",
   "states": "0=Electric heat 2 command is Off; 1=Electric heat 2 command is On"
  },
  {
   "type": "BO",
   "instance": 11,
   "name": "HGR_Out",
   "description": "Hot Gas Reheat",
   "units": "",
   "access": "R",
   "states": "0=HGR command is Off (valve is closed); 1=HGR command is On (valve is open)"
  },
  {
   "type": "BO",
   "instance": 12,
   "name": "WSE_Out",
   "description": "Waterside Economizer",
   "units": "",
   "access": "R",
   "states": "0=WSE command is Off (valve is closed); 1=WSE command is On (valve is open)"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "ClearAlarm",
   "description": "Clear Alarm",
   "units": "",
   "access": "W",
   "states": "0=Normal; 1=Clear Alarm"
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "CondOverFlow",
   "description": "Condensate Overflow Status",
   "units": "",
   "access": "R",
   "states": "1=Dry; 2=Wet; 3=Null"
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "FanOnAuto",
   "description": "Fan On/Auto Switch Status (Room Sensor)",
   "units": "",
   "access": "R",
   "states": "1=On; 2=Auto; 3=Null"
  },
  {
   "type": "MI",
   "instance": 3,
   "name": "HeatCoolAuto",
   "description": "System Mode Switch (Heat/Cool/Auto) Status",
   "units": "",
   "access": "R",
   "states": "1=Off; 2=Heat; 3=Cool; 4=Auto; 5=Null"
  },
  {
   "type": "MI",
   "instance": 4,
   "name": "DehumRequired",
   "description": "Dehumidification Required",
   "units": "",
   "access": "R",
   "states": "1=Dehumid not Required; 2=Dehumid Required; 3=Null"
  },
  {
   "type": "MI",
   "instance": 5,
   "name": "FanRunStatus",
   "description": "Fan Run Status",
   "units": "",
   "access": "R",
   "states": "1=Fan is Off; 2=Fan is On"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "ComprEnable",
   "description": "Compressor Enable Input",
   "units": "",
   "access": "C",
   "states": "1=Disabled; 2=Enabled; 3=Null (Compressors Enabled)"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "CurrentAlarm",
   "description": "Current Alarm",
   "units": "",
   "access": "R",
   "states": "Alarm number 1-28 (see the alarm table in the guide)"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "NetworkFanOnAuto",
   "description": "Network Fan On/Auto Input",
   "units": "",
   "access": "C",
   "states": "1=Fan Auto; 2=Fan On; 3=Null"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "McQWSHPStatus",
   "description": "Unit Status",
   "units": "",
   "access": "R",
   "states": "1=Off Alarm; 2=Off; 3=Start; 4=Fan Only; 5=Prepare to Heat; 6=Heating; 7=Prepare to Cool; 8=Cooling; 9=Prepare to Dehumidify; 10=Dehumidification"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "PreviousAlarm",
   "description": "Previous Alarm",
   "units": "",
   "access": "R",
   "states": "Alarm number 1-28 (see the alarm table in the guide)"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "EffectOccup",
   "description": "Effective Occupancy",
   "units": "",
   "access": "R",
   "states": "1=Occupied; 2=Unoccupied; 3=Bypass; 4=Standby; 5=Null"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "OccManCmd",
   "description": "Occupancy Override Input",
   "units": "",
   "access": "C",
   "states": "1=Occupied; 2=Unoccupied; 3=Bypass; 4=Standby; 5=Null"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "OccSchedule",
   "description": "Occupancy Scheduler",
   "units": "",
   "access": "C",
   "states": "1=Occupied; 2=Unoccupied; 3=Standby; 4=Null"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "OccSensor",
   "description": "Occupancy Sensor",
   "units": "",
   "access": "C",
   "states": "1=Occupied; 2=Unoccupied; 3=Null"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "ApplicMode",
   "description": "Application Mode",
   "units": "",
   "access": "C",
   "states": "1=Auto; 2=Heat; 3=Cool; 4=Off; 5=Fan Only; 6=Dehumid; 7=Null"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "AuxHeatEnable",
   "description": "Auxiliary Heat Enable",
   "units": "",
   "access": "C",
   "states": "1=Disabled; 2=Enabled; 3=Null"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "EnergyHoldOff",
   "description": "Energy Hold Off",
   "units": "",
   "access": "C",
   "states": "1=Normal; 2=Energy Hold Off; 3=Null"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "PumpRequest",
   "description": "Pump Request Output",
   "units": "",
   "access": "R",
   "states": "1=No Request for Flow; 2=Request for Flow; 3=Null"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "cpLocSpEnable",
   "description": "Room Sensor Setpoint Adjust Enable/Disable",
   "units": "",
   "access": "W",
   "states": "1=Disabled; 2=Enabled"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "Units",
   "description": "Units (English/Metric)",
   "units": "",
   "access": "W",
   "states": "1=English (E); 2=Metric (M)"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "NetworkHumidistat",
   "description": "Network Humidistat Input",
   "units": "",
   "access": "C",
   "states": "1=No Dehumid Request; 2=Request Dehumid; 3=Null"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "cpNetVsCnfgEn",
   "description": "Network Variable Speed Fan Enable",
   "units": "",
   "access": "W",
   "states": "1=Disabled; 2=Enabled; 3=Null"
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "cpSpaceDehumCnfg",
   "description": "Space Dehumidification Method",
   "units": "",
   "access": "W",
   "states": "1=Relative Humidity; 2=Dewpoint; 3=Null"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "cpSpaceRHSensor",
   "description": "Space Relative Humidity Sensor",
   "units": "",
   "access": "W",
   "states": "1=Not Installed; 2=Installed; 3=Null"
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "cpControlTempSrc",
   "description": "Control Temperature Source",
   "units": "",
   "access": "W",
   "states": "1=Space; 2=Return; 3=Average; 4=Null"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/daikin-applied/microtech-mt2300-wshp-smartsource-r32",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}