 "manufacturer": "Daikin Applied",
 "manufacturer_slug": "daikin-applied",
 "model": "MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)",
 "model_slug": "microtech-applied-air-rebel-dps-dpsa-dcsa",
 "aliases": [
  "Rebel DPS R-32",
  "Rebel Applied DPSA R-32",
  "DCSA",
  "Rebel ROC",
  "Refrigeration Only Controls",
  "MT4 AHU",
  "ED 19117-8"
 ],
 "equipment_type": "Rooftop unit controller",
 "applies_to": "Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.",
 "summary": "The 2026 edition of the MicroTech Applied Air integration guide adds Rebel DPS with R-32, refrigeration-only (ROC) units and DCSA split condensing systems to the Rebel Applied list. It joins BACnet IP or BACnet MS/TP through a plug-in communication module. Compared with the 2022 Rebel Applied list it adds a third refrigerant circuit, A2L refrigerant sensor objects, VFD fan options, defrost and occupancy-source status, and many new compressor event BIs, and drops the power and IAQ monitoring objects. Most writable inputs only apply when AHU Loc/Net (MV 19) is Network at the HMI.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": "Application 2506036306, BACnet firmware 11.78 (PICS)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Needs a BACnet IP or BACnet MS/TP communication module on the controller; the LonWorks objects in the same guide are not listed.",
  "AHU Loc/Net (MV 19) must be Network for most writable network points to apply; it can only be changed at the HMI.",
  "Points depend on unit type and options: control type (zone, discharge, single-zone VAV, refrigeration only, DCSA), compressor count and circuits, ECM or VFD fans, energy recovery, refrigerant monitoring and the expansion I/O board.",
  "Alarm BIs (Table 35) read 0=Normal/1=In Alarm or 0=Open/1=Closed as marked; event BIs (Tables 36-37) flag active control and standby events. NC 1-4 are Faults, Problems, Warnings and Events.",
  "The older 2022 Rebel Applied list (ED 19117-3) is kept as a separate entry; it still has the power and IAQ monitoring objects removed here.",
  "Range text lists English and SI units; English units are shown here."
 ],
 "source": {
  "title": "MicroTech Applied Air Network Integration Guide, BACnet and LonWorks Communication Protocols",
  "doc_number": "ED 19117-8",
  "revision_date": "2026-06",
  "url": "https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019117-8%20MicroTech%20Applied%20Air%20Systems%20Unit%20Controller%20Protocol%20Document.pdf/"
 },
 "integration": {
  "summary": "Set AHU Loc/Net to Network at the HMI, then drive the unit with Occupancy Mode or Current State, plus Application Mode and the occupied setpoints. Use Emergency Override to stop the unit from the network, and read Unit State, unit status, capacities, temperatures and the alarm objects.",
  "minimum_points": [
   {
    "ref": "MV 7",
    "name": "OccManCmd",
    "why": "Occupancy mode command (Occ/Unocc/TntOvrd/Standby/Auto)"
   },
   {
    "ref": "MV 8",
    "name": "CurrentState",
    "why": "Occupancy Scheduler Input when Occupancy Mode is Auto"
   },
   {
    "ref": "MV 10",
    "name": "EmergOverride",
    "why": "Network shutdown (Off) / Normal"
   },
   {
    "ref": "MV 5",
    "name": "ApplicCmd",
    "why": "Application mode (off/heat/cool/fan only/auto)"
   },
   {
    "ref": "AV 10",
    "name": "OccCoolSP",
    "why": "Occupied cooling setpoint"
   },
   {
    "ref": "AV 12",
    "name": "OccHeatSP",
    "why": "Occupied heating setpoint"
   },
   {
    "ref": "MV 19",
    "name": "AHULoc/Net",
    "why": "Must read Network for network inputs to apply"
   },
   {
    "ref": "MV 15",
    "name": "UnitState",
    "why": "Current operating state"
   },
   {
    "ref": "AI 1",
    "name": "DischAirTemp",
    "why": "Discharge air temperature"
   },
   {
    "ref": "AV 29",
    "name": "ActiveFault",
    "why": "Highest-priority active fault number, 0 = none"
   }
  ],
  "enable": "AHU Loc/Net (MV 19) must be set to Network at the HMI (it is read-only over BACnet) for most network inputs to apply. Occupancy is then commanded with Occupancy Mode (MV 7) or, when MV 7 is Auto, Current State (MV 8). Emergency Override (MV 10) = Off shuts the unit off (Unit Status OffNet) and only writing Normal restarts it. Application Mode (MV 5) only acts when Control Mode is Auto, which is set at the HMI. Cooling, heating and economizer can be enabled or capped from the network with AV 36/37, AV 38/39 and AV 34/35 (Ctrl Mode = Auto).",
  "heartbeat": "No BACnet heartbeat (Receive Heartbeat is listed as N/A for BACnet IP and MS/TP). Values written by the BAS stay at the last valid value if communication is lost; an invalid network value makes the controller use its default, and network sensor inputs fall back to the local sensor.",
  "remote_sensors": "Space Temperature Input (AV 31) and Outdoor Air Temperature Input (AV 32) take network temperatures and revert to the local sensor if the network value becomes unreliable. Network inputs also exist for space humidity (AV 20/21), space CO2 (AV 33), supply and return fan capacity (AV 24/25) and outdoor air damper minimum and maximum position (AV 17/55). A LonWorks value takes precedence over the BACnet one if both are present.",
  "setup": [
   "Initial device instance is calculated from the production code (IP) or MAC address (MS/TP); change it at the HMI and set Apply Changes in the BACnet IP or MS/TP setup menu (the controller restarts).",
   "BACnet IP defaults: DHCP on, given IP 127.0.0.1, mask 255.255.255.0, UDP port 47808.",
   "BACnet MS/TP defaults: MAC address 18, 38400 baud, Max Master 127, Max Info Frames 1.",
   "MS/TP terminating resistor is an HMI setting (Term Resistor) and is lost at power-off; a physical resistor is recommended.",
   "If the BAS cannot subscribe to the notification class recipient lists, enter its device instance in NC Dev 1 or NC Dev 2 in the BACnet setup menu and cycle power."
  ],
  "gotchas": [
   "Multistate objects that are also unit configuration code items read with an extra '(n)' at the end of the state text over BACnet, e.g. 'OnOffT(1)'.",
   "ClearAlarms (MV 13) clears by class and returns to None once the alarms clear; write it only to clear an active alarm.",
   "Network Demand Shed Enable (MV 22) only works when DemandShed is also enabled in the HMI HtgClg ChgOvr Set-Up menu.",
   "The guide prints MV 28 and MV 37 twice: ECM fan status (SAF1Status, RFEF1Status) and VFD fan status (VFD_SAFStatus, VFD_RFEFStatus: 1=OK, 2=Fault, 3=No Comm). Only the ECM names are listed; check the object name on the unit.",
   "BI 144, BI 244 and BI 344 are each printed twice (variable compressor VCmpnHDLTULEvnt and fixed compressor CnHDLTnULEvnt); only the first name is listed.",
   "The heating table prints a 0-based Heating Type list for MV 103 that does not match the unit configuration table; the configuration table version is used here."
  ]
 },
 "points": [
  {
   "type": "MV",
   "instance": 15,
   "name": "UnitState",
   "description": "Unit State",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Start, 3=Recirc, 4=FanOnly, 5=MinDAT, 6=Htg, 7=Econo, 8=Clg"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "DaikinStatus",
   "description": "Unit Status",
   "units": "",
   "access": "R",
   "states": "1=Enable, 2=OffMan, 3=OffManCtrl, 4=OffNet, 5=OffAlm, 6=OffRetry, 7=OffPassVnt, 8=OffSnsrCfg, 9=OffEvac"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "ClgStatus",
   "description": "Cooling Status",
   "units": "",
   "access": "R",
   "states": "1=Enabled, 2=None, 3=OffAmb, 4=OffAlm, 5=OffNet, 6=OffMan, 7=NA, 8=CfgErr"
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "CoolEnable",
   "description": "Primary Cool Enable",
   "units": "",
   "access": "W",
   "states": "-1=Null, 0=Off (Disabled), 1=Enable"
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "CoolEnablePct",
   "description": "Primary Cool Enable",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "EconoStatus",
   "description": "Economizer Status",
   "units": "",
   "access": "R",
   "states": "1=Enabled, 2=None, 3=OffAmb, 4=OffAlm, 5=OffNet, 6=OffMan, 7=OffDehum, 8=CfgErr"
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "EconEnable",
   "description": "Economizer Enable",
   "units": "",
   "access": "W",
   "states": "-1=Null, 0=Off (Disabled), 1=Enable"
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "EconEnablePct",
   "description": "Economizer Enable",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "PrimaryHtgStatus",
   "description": "Heating Status",
   "units": "",
   "access": "R",
   "states": "1=Enabled, 2=None, 3=OffAmb, 4=OffAlm, 5=OffNet, 6=OffMan, 7=OffDehum, 8=CfgErr"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "SecondaryHtgStatus",
   "description": "Secondary Heating Status",
   "units": "",
   "access": "R",
   "states": "1=Enabled, 2=None, 3=OffAmb, 4=OffAlm, 5=OffNet, 6=OffMan, 7=NA, 8=NA"
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "HeatEnable",
   "description": "Primary Heat Enable",
   "units": "",
   "access": "W",
   "states": "-1=Null, 0=Off (Disabled), 1=Enable"
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "HeatEnablePct",
   "description": "Primary Heat Enable",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "EconCapacity",
   "description": "Outdoor Air Damper Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "ApplicCmd",
   "description": "Application Mode",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly, 5=Auto, 6=NA"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "EmergOverride",
   "description": "Emergency Override",
   "units": "",
   "access": "W",
   "states": "1=Normal, 2=Off"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "UnitSupport",
   "description": "BACnet Units of Measurement",
   "units": "",
   "access": "W",
   "states": "1=Metric, 2=English"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "VAVBoxOutput",
   "description": "VAV Box Output Status",
   "units": "",
   "access": "R",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "AHULoc/Net",
   "description": "Unit Local/Network Control",
   "units": "",
   "access": "R",
   "states": "1=Network, 2=Local"
  },
  {
   "type": "MV",
   "instance": 21,
   "name": "DehumStatus",
   "description": "Dehumidification Status",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 22,
   "name": "DemandShed",
   "description": "Network Demand Shed Enable",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Auto, 3=Manual"
  },
  {
   "type": "MV",
   "instance": 23,
   "name": "MWUStatus",
   "description": "Morning Warmup Status",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 24,
   "name": "FreeClgStatus",
   "description": "Free Cooling Status",
   "units": "",
   "access": "R",
   "states": "1=Unavail, 2=Avail"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "RemSptSrc",
   "description": "Remote Setpoint Source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AI, 3=QMX1, 4=QMX2, 5=QMX3"
  },
  {
   "type": "MV",
   "instance": 49,
   "name": "DefrostStatus",
   "description": "Defrost Status",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "FilterPress1",
   "description": "Filter Pressure Input",
   "units": "inWC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "FilterPress2",
   "description": "Filter Pressure Input",
   "units": "inWC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "FilterPress3",
   "description": "Filter Pressure Input",
   "units": "inWC",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "EffectOccup",
   "description": "Occupancy Status",
   "units": "",
   "access": "R",
   "states": "1=Occ, 2=Unocc, 3=TntOvrd"
  },
  {
   "type": "MV",
   "instance": 46,
   "name": "OccSrc",
   "description": "Occupancy Source",
   "units": "",
   "access": "R",
   "states": "1=None, 2=NetSchd, 3=IntSchd, 4=OneEvnt, 5=RemoteSw, 6=NetManCmd, 7=OccMode, 8=TstatTO, 9=ManTO, 10=UnitDsbld"
  },
  {
   "type": "MV",
   "instance": 47,
   "name": "UnoccSrc",
   "description": "Unoccupancy Source",
   "units": "",
   "access": "R",
   "states": "1=UnoccDehum, 2=UnoccClg, 3=UnoccHtg, 4=IntOptStrt, 5=NetOptStrt, 6=IntPurge, 7=NetPurge, 8=None, 9=A2LSnsrPrb, 10=A2LLeakPrb"
  },
  {
   "type": "MV",
   "instance": 48,
   "name": "MinOASrc",
   "description": "Minimum Outdoor Air Source",
   "units": "",
   "access": "R",
   "states": "1=VentLmt, 2=OAFlw, 3=ExtAI, 4=CO2, 5=PM25, 6=TVOC, 7=Network, 8=BSP, 9=RstTLmt, 10=MaxPos, 11=HiDwpt, 12=FanDiff, 13=ZeroOA"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "OccManCmd",
   "description": "Occupancy Mode (Network)",
   "units": "",
   "access": "W",
   "states": "1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby, 5=Auto"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "CurrentState",
   "description": "Current State",
   "units": "",
   "access": "W",
   "states": "1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby, 5=NA"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "NextState",
   "description": "Next State",
   "units": "",
   "access": "W",
   "states": "1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby, 5=NA"
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "TimeToNextState",
   "description": "Time to Next State",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "MaxPurgeTime",
   "description": "Maximum Purge Time",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "EffSpaceTemp",
   "description": "Effective Space Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "SpaceTempInput",
   "description": "Space Temperature Input",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "SpaceTemp1",
   "description": "Space Temperature Sensor 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "SpaceTemp2",
   "description": "Space Temperature Sensor 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "SpaceTemp3",
   "description": "Space Temperature Sensor 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "RATemp",
   "description": "Return Air Temperature Sensor",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "CtrlTempSrc",
   "description": "Control Temp Source",
   "units": "",
   "access": "W",
   "states": "1=RAT, 2=Space, 3=OAT, 4=None"
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "ControlTemp",
   "description": "Control Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "OutdoorTemp",
   "description": "Effective Outdoor Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "LocalOATemp",
   "description": "Outdoor Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "OutdoorTempInput",
   "description": "Outdoor Air Temperature Input",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "EffDATempSP",
   "description": "Effective Discharge Air Temperature Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "DischAirTemp",
   "description": "Discharge Air Temperature Sensor",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "EFT_LCT",
   "description": "Entering Fan/Leaving Coil Temperature Sensor",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "C1DischLnTemp1",
   "description": "Discharge Line Refrigerant Temperature Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "C1DischLnTemp3",
   "description": "Discharge Line Refrigerant Temperature Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "C1DischLnTemp5",
   "description": "Discharge Line Refrigerant Temperature Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "C2DischLnTemp",
   "description": "Discharge Line Refrigerant Temperature Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "C2DischLnTemp4",
   "description": "Discharge Line Refrigerant Temperature Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "C2DischLnTemp6",
   "description": "Discharge Line Refrigerant Temperature Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "C1RefLiqLnTemp",
   "description": "Liquid Line Refrigerant Temperature Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "C2RefLiqLnTemp",
   "description": "Liquid Line Refrigerant Temperature Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "VCmp1Temp",
   "description": "Variable Compressor 1 Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "VCmp2Temp",
   "description": "Variable Compressor 2 Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 135,
   "name": "VCmp3Temp",
   "description": "Variable Compressor 3 Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "C1FCmp1Temp",
   "description": "Fixed Compressor 1 Temperature Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "C1FCmp3Temp",
   "description": "Fixed Compressor 3 Temperature Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "C1FCmp5Temp",
   "description": "Fixed Compressor 5 Temperature Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "C2FCmp2Temp",
   "description": "Fixed Compressor 2 Temperature Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "C2FCmp4Temp",
   "description": "Fixed Compressor 4 Temperature Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "C2FCmp6Temp",
   "description": "Fixed Compressor 6 Temperature Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 136,
   "name": "C3FCmp1Temp",
   "description": "Fixed Compressor 1 Temperature Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 137,
   "name": "C3FCmp3Temp",
   "description": "Fixed Compressor 3 Temperature Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 138,
   "name": "C3FCmp5Temp",
   "description": "Fixed Compressor 5 Temperature Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 104,
   "name": "SAFType",
   "description": "Supply Air Fan Type",
   "units": "",
   "access": "R",
   "states": "1=Anlg, 2=1M, 3=2M, 4=3M, 5=4M, 6=6M, 7=8M, 8=9M, 9=SAFVFD, 10=8M4S, 11=8M8S"
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "SAF1Status",
   "description": "Supply Air Fan 1-6 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV"
  },
  {
   "type": "MV",
   "instance": 29,
   "name": "SAF2Status",
   "description": "Supply Air Fan 1-6 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV"
  },
  {
   "type": "MV",
   "instance": 30,
   "name": "SAF3Status",
   "description": "Supply Air Fan 1-6 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV"
  },
  {
   "type": "MV",
   "instance": 31,
   "name": "SAF4Status",
   "description": "Supply Air Fan 1-6 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV"
  },
  {
   "type": "MV",
   "instance": 32,
   "name": "SAF5Status",
   "description": "Supply Air Fan 1-6 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV"
  },
  {
   "type": "MV",
   "instance": 33,
   "name": "SAF6Status",
   "description": "Supply Air Fan 1-6 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AC_OV, 20=AC_UV"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "SupFanCtrl",
   "description": "Supply Fan Capacity Control",
   "units": "",
   "access": "W",
   "states": "1=DSP, 2=Spd/Net, 3=1ZnVAV, 4=BSP, 5=CO2, 6=Flow, 7=CAV"
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "SAFDSPSpt",
   "description": "Supply Fan Duct Static Pressure Setpoint (DSP)",
   "units": "inWC",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 112,
   "name": "StaticPSens",
   "description": "Duct Static Pressure Sensor",
   "units": "",
   "access": "R",
   "states": "1=NA:NA, 2=DSP:NA, 3=DSP:DSP, 4=DSP:BSP, 5=BSP:NA, 6=NA:DSP, 7=NA:BSP"
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "SAFBSPSpt",
   "description": "Supply Fan Building Static Pressure (BSP) Setpoint",
   "units": "inWC",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "SupFanCapNetIn",
   "description": "Supply Fan Capacity Input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "SAFCap",
   "description": "Effective Supply Fan Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "SAFDSP",
   "description": "Supply Fan Duct Static Pressure",
   "units": "inWC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "SAFFlow",
   "description": "Supply Fan Airflow",
   "units": "CFM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "SAFFlowSpt",
   "description": "Supply Fan Flow Setpoint",
   "units": "CFM",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 110,
   "name": "SAFFlowInput",
   "description": "Supply Fan Flow Input",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1Fan, 3=2Fan, 4=3Fan, 5=4Fan, 6=6Fan"
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "SAFOAFlowSpt",
   "description": "Supply Fan Outdoor Air Flow Setpoint",
   "units": "CFM",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 105,
   "name": "RFEFType",
   "description": "Return Air Fan Type",
   "units": "",
   "access": "R",
   "states": "1=None, 2=RFAnlg, 3=EFAnlg, 4=1ECMRF, 5=2ECMRF, 6=3ECMRF, 7=4ECMRF, 8=1ECMEF, 9=2ECMEF, 10=3ECMEF, 11=4ECMEF, 12=RFVFD, 13=EFVFD"
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "RFEFCapNetIn",
   "description": "Return Fan Capacity Input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "RAFDSP",
   "description": "Return Fan Duct Static Pressure",
   "units": "inWC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "BldgStatPress",
   "description": "Building Static Pressure Sensor",
   "units": "inWC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "BldgStaticSP",
   "description": "Building Static Pressure Setpoint",
   "units": "inWC",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "RFEFCap",
   "description": "Return Fan Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "ExhPSP",
   "description": "Exhaust Air Plenum Static Pressure",
   "units": "inWC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "RFEFFlow",
   "description": "ReturnFan Airflow",
   "units": "CFM",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "ExhRetFanCtrl",
   "description": "Return Fan Capacity Control",
   "units": "",
   "access": "W",
   "states": "1=CAV, 2=BSP, 3=Tracking, 4=DSP, 5=Speed, 6=Flow, 7=OAD, 8=FlowDiff"
  },
  {
   "type": "MV",
   "instance": 37,
   "name": "RFEF1Status",
   "description": "Return Fan 1-4 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AOV, 20=AU"
  },
  {
   "type": "MV",
   "instance": 38,
   "name": "RFEF2Status",
   "description": "Return Fan 1-4 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AOV, 20=AU"
  },
  {
   "type": "MV",
   "instance": 39,
   "name": "RFEF3Status",
   "description": "Return Fan 1-4 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AOV, 20=AU"
  },
  {
   "type": "MV",
   "instance": 40,
   "name": "RFEF4Status",
   "description": "Return Fan 1-4 Status",
   "units": "",
   "access": "R",
   "states": "1=OK, 2=HLL, 3=TFEI, 4=TFM, 5=TFE, 6=LK, 7=SKF, 8=PHA, 9=UzLo, 10=UzHi, 11=UeLo, 12=UeHi, 13=NoCm, 14=OC, 15=OT, 16=RRP, 17=EE, 18=POC, 19=AOV, 20=AU"
  },
  {
   "type": "MV",
   "instance": 111,
   "name": "RFEFFlowInput",
   "description": "ReturnFan Flow Input",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1Fan, 3=2Fan, 4=3Fan"
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "RFEFFlowSpt",
   "description": "Return/Exhaust Fan Flow Setpoint",
   "units": "CFM",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "RAFDSPSpt",
   "description": "Return Air Fan DSP Setpoint",
   "units": "inWC",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "EFFPSPSpt",
   "description": "Effective Exhaust Plenum Static Pressure Setpoint",
   "units": "inWC",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 116,
   "name": "RefrigType",
   "description": "Refrigerant Type",
   "units": "",
   "access": "R",
   "states": "1=None, 2=R410A, 3=R32, 4=R32HP, 5=R32HP75, 6=R32HP50, 7=R32HP25, 8=R32HP0"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "ClgCapacity",
   "description": "Unit Cooling Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "DAClgSetpt",
   "description": "Discharge Air Cooling Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "DefaultDATClgSetpt",
   "description": "Minimum Discharge Air Cooling Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "DATEconSpt",
   "description": "Discharge Air Temperature Economizer Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "OccCoolSP",
   "description": "Occupied Cooling Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "UnoccCoolSetpt",
   "description": "Unoccupied Cooling Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "ReheatCapacity",
   "description": "Reheat Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "EHGBPCfg",
   "description": "Electronic Hot Gas Bypass Input",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Circ12, 3=Circ1, 4=Circ2"
  },
  {
   "type": "MV",
   "instance": 103,
   "name": "HtgType",
   "description": "Heating Type",
   "units": "",
   "access": "R",
   "states": "1=None, 2=F&BP, 3=HW_Stm, 4=MG1StgL, 5=MG1StgL, 6=MG1StgL, 7=MG1StgH, 8=MG1StgH, 9=MG2StgL, 10=MG3StgL, 11=MG2StgH, 12=MG3StgH, 13=2StgE, 14=2StgG, 15=4StgE, 16=4StgG, 17=SCR, 18=SCRSRht, 19=Not used, 20=MG4StgL, 21=MG4StgH"
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "PrimaryHtgCap",
   "description": "Primary Heating Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "SecondaryHtgCap",
   "description": "Secondary Heating Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "OccHeatSP",
   "description": "Occupied Heating Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "UnoccHeatSetpt",
   "description": "Unoccupied Heating Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "DAHtgSetpt",
   "description": "Discharge Air Heating Setpoint (No Electric Heat)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "DefaultDATHtgSetpt",
   "description": "Maximum Discharge Air Heating Setpoint (No Electric Heat)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "MaximumHeatRise",
   "description": "Maximum Heat Rise",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 107,
   "name": "ReheatType",
   "description": "Reheat Type",
   "units": "",
   "access": "R",
   "states": "1=None, 2=PriHtg, 3=PriHtBP, 4=MHG, 5=MHGBP, 6=HG_LSC, 7=HGLSCBP, 8=DXBP, 9=MLSC"
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "SpaceRH1",
   "description": "Relative Humidity Sensor 1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "SpaceRH2",
   "description": "Relative Humidity Sensor 2",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "SpaceRH1NetIn",
   "description": "Relative Humidity Input 1",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "SpaceRH2NetIn",
   "description": "Relative Humidity Input 2",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "Humidity1SP",
   "description": "Humidity Sensor 1 Setpoint Input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "Humidity2SP",
   "description": "Humidity Sensor 2 Setpoint Input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "Dewpoint1SP",
   "description": "Dewpoint Setpoint 1",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Dewpoint2SP",
   "description": "Dewpoint Setpoint 2",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "RARelHum",
   "description": "Return Air Relative Humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "RADewpoint",
   "description": "Return Air Dewpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "OARelHum",
   "description": "Outdoor Air Relative Humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "OADewpoint",
   "description": "Outdoor Air Dewpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "MinLCTSpt",
   "description": "Minimum Leaving Coil Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "DXBPMinLCTSpt",
   "description": "DX Coil Bypass Minimum Leaving Coil Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "MaxLCTSpt",
   "description": "Maximum Leaving Coil Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "DXBPMaxLCTSpt",
   "description": "DX Coil Bypass Maximum Leaving Coil Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "LCTSetpoint",
   "description": "Leaving Coil Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "DXBPLCTSetpoint",
   "description": "Leaving Coil Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 41,
   "name": "NetworkReset",
   "description": "Minimum Outdoor Air Reset",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "MV",
   "instance": 102,
   "name": "DamperType",
   "description": "Damper Type",
   "units": "",
   "access": "R",
   "states": "1=None, 2=30A, 3=100A, 4=Econ, 5=EconFDD, 6=100wRec"
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "OAFanCtrl",
   "description": "Outdoor Air Fan Control",
   "units": "",
   "access": "R",
   "states": "1=None, 2=OnOffT, 3=OnOffP, 4=VarVFD, 5=VarECM1, 6=VarECM2, 7=VarDK1, 8=VarDK2"
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "MinOAPosNetIn",
   "description": "Outdoor Air Damper Minimum Position Input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "MaxOAPos",
   "description": "Outdoor Air Damper Maximum Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 108,
   "name": "ExtOAInput",
   "description": "External Outdoor Air Input",
   "units": "",
   "access": "R",
   "states": "1=None, 2=ExtVDC, 3=ExtmA, 4=CO2VDC, 5=CO2mA, 6=CO2QMX+, 7=IAQMB"
  },
  {
   "type": "MV",
   "instance": 109,
   "name": "OAFlowInput",
   "description": "Outdoor Air Flow Input",
   "units": "",
   "access": "R",
   "states": "1=None, 2=VDC, 3=mA"
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "OAFlow",
   "description": "Outdoor Airflow",
   "units": "CFM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "OAFlowSpt",
   "description": "Outdoor Airflow Setpoint",
   "units": "CFM",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 113,
   "name": "SpaceTConfig",
   "description": "Space Temperature Sensor",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1AI, 3=2AI, 4=3AI, 5=1QMXS, 6=2QMXS, 7=3QMXS, 8=1QMX+, 9=2QMX+, 10=3QMX+"
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "SpaceCO2",
   "description": "Space CO2",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "SpaceIAQNetIn",
   "description": "Space IAQ (CO2) Input",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "PassiveVent",
   "description": "Passive Ventilation",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 106,
   "name": "EnergyRec",
   "description": "Energy Recovery",
   "units": "",
   "access": "R",
   "states": "1=None, 2=CS, 3=CSRH, 4=ECM1, 5=ECM2, 6=VFD, 7=Anlg"
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "ERWhlOnOff",
   "description": "Energy Recovery Wheel Status",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "ERWheelCap",
   "description": "Energy Recovery Wheel Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "ERLWT",
   "description": "Energy Recovery Leaving Wheel Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "EREWT",
   "description": "Energy Recovery Entering Wheel Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "SupplyFanHrs",
   "description": "Supply Fan Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "RF_EFHrs",
   "description": "Return Fan Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "ReheatHrs",
   "description": "Reheat Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "CoolingHrs",
   "description": "Cooling Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "C1Comp1Hrs",
   "description": "Compressor 1 Hours Circuit 1",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "C2Comp2Hrs",
   "description": "Compressor 2 Hours Circuit 2",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "C1Comp3Hrs",
   "description": "Compressor 3 Hours Circuit 1",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "C2Comp4Hrs",
   "description": "Compressor 4 Hours Circuit 2",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "C1Comp5Hrs",
   "description": "Compressor 5 Hours Circuit 1",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "C2Comp6Hrs",
   "description": "Compressor 6 Hours Circuit 2",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "HeatingHrs",
   "description": "Heating Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "EconoHrs",
   "description": "Economizer Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "TenantORHrs",
   "description": "Tenant Override Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "DehumHrs",
   "description": "Dehumidification Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "ERWhlHrs",
   "description": "Energy Recovery Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "VarCmp1Hrs",
   "description": "Variable Compressor 1 Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "VarCmp2Hrs",
   "description": "Variable Compressor 2 Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "VarCmp3Hrs",
   "description": "Variable Compressor 3 Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "SCRPrehtHrs",
   "description": "SCR Preheat Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "UVLightHrs",
   "description": "UV Light Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "C3FCmp1Hrs",
   "description": "Compressor 1 Hours Circuit 3",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "C3FCmp3Hrs",
   "description": "Compressor 3 Hours Circuit 3",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "C3FCmp5Hrs",
   "description": "Compressor 5 Hours Circuit 3",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "AlarmValue",
   "description": "Alarm Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "ActiveWarning",
   "description": "Warning Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "ClearAlarms",
   "description": "Clear Alarms",
   "units": "",
   "access": "W",
   "states": "1=No, 2=ClrFlts, 3=ClrPrblms, 4=ClrWrngs, 5=ClrAllAlms"
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "ActiveProblem",
   "description": "Problem Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "C1RefSuctionP",
   "description": "Suction Refrigerant Pressure Circuit 1",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "C2RefSuctionP",
   "description": "Suction Refrigerant Pressure Circuit 2",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "C1SucnRefTemp",
   "description": "Suction Line Refrigerant Temperature Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "C2SucnRefTemp",
   "description": "Suction Line Refrigerant Temperature Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "C1RefDischP",
   "description": "Discharge Refrigerant Pressure Circuit 1",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "C2RefDischP",
   "description": "Discharge Refrigerant Pressure Circuit 2",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 120,
   "name": "SSH1",
   "description": "Suction Superheat Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 125,
   "name": "SSH2",
   "description": "Suction Superheat Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 121,
   "name": "DSH1",
   "description": "Discharge Superheat Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 126,
   "name": "DSH2",
   "description": "Discharge Superheat Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 122,
   "name": "Subcooling1",
   "description": "Subcooling Circuit 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 127,
   "name": "Subcooling2",
   "description": "Subcooling Circuit 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 128,
   "name": "SSH3",
   "description": "Suction Superheat Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 129,
   "name": "DSH3",
   "description": "Discharge Superheat Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 130,
   "name": "Subcooling3",
   "description": "Subcooling Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 131,
   "name": "C3SucnRefTemp",
   "description": "Suction Refrigerant Temperature Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 132,
   "name": "C3RefSuctionP",
   "description": "Suction Refrigerant Pressure Circuit 3",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 133,
   "name": "C3RefDischP",
   "description": "Discharge Refrigerant Pressure Circuit 3",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 134,
   "name": "C3RefLiqLnTemp",
   "description": "Liquid Line Refrigerant Temperature Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 139,
   "name": "C3DischLnTemp1",
   "description": "Discharge Line Refrigerant Temperature 1 Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 140,
   "name": "C3DischLnTemp3",
   "description": "Discharge Line Refrigerant Temperature 3 Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "C3DischLnTemp5",
   "description": "Discharge Line Refrigerant Temperature 5 Circuit 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 100,
   "name": "CtrlType",
   "description": "Control Type",
   "units": "",
   "access": "R",
   "states": "1=Zone, 2=DTC, 3=1ZnVAV, 4=RO_FC, 5=RO_FCGE, 6=RO_DCSA"
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "BNNumVarComps",
   "description": "Fixed Compressors",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "BNNumFixedCmps",
   "description": "Variable Compressors",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "BNNumClgCir",
   "description": "Compressor Circuits",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "UnitSize",
   "description": "Unit Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 114,
   "name": "MonitorPkgs",
   "description": "Monitoring Packages",
   "units": "",
   "access": "R",
   "states": "1=None, 2=RefSys"
  },
  {
   "type": "MV",
   "instance": 117,
   "name": "UnitVoltage",
   "description": "Unit Voltage",
   "units": "",
   "access": "R",
   "states": "1=208_60Hz, 2=230_60Hz, 3=460_60Hz, 4=575_60Hz"
  },
  {
   "type": "MV",
   "instance": 118,
   "name": "PreheatType",
   "description": "Preheat Type",
   "units": "",
   "access": "R",
   "states": "1=None, 2=HW_Stm, 3=F&BP, 4=SCR"
  },
  {
   "type": "MV",
   "instance": 119,
   "name": "EVType",
   "description": "Expansion Valve Type",
   "units": "",
   "access": "R",
   "states": "1=NA/TXV, 2=DFETS, 3=DFCol, 4=FJPAM2, 5=FJPAM3, 6=Spln, 7=Fj2/Fj3, 8=Fj3/Fj2, 9=DFC/Fj2, 10=DFC/Fj3, 11=Spr/Fj2, 12=Spr/Fj3, 13=Spr/DFC, 14=Fj2/Spr, 15=Fj3/Spr, 16=DFC/Spr"
  },
  {
   "type": "MV",
   "instance": 120,
   "name": "IOConfig",
   "description": "I/O Configuration",
   "units": "",
   "access": "R",
   "states": "0=RebApp, 1=Rebel, 2=DCSA"
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "SensorCfg",
   "description": "Sensor Config",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 50,
   "name": "GenericDI1",
   "description": "Generic digital input X1 (expansion I/O board)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 51,
   "name": "GenericDI2",
   "description": "Generic digital input X2 (expansion I/O board)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 52,
   "name": "GenericDI3",
   "description": "Generic digital input X3 (expansion I/O board)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 53,
   "name": "GenericDI4",
   "description": "Generic digital input X4 (expansion I/O board)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 54,
   "name": "GenericDI5",
   "description": "Generic digital input X5 (expansion I/O board)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 55,
   "name": "GenericDI6",
   "description": "Generic digital input X6 (expansion I/O board)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 56,
   "name": "GenericDI7",
   "description": "Generic digital input X7 (expansion I/O board)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 57,
   "name": "GenericDI8",
   "description": "Generic digital input X8 (expansion I/O board)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "GenericBO1",
   "description": "Generic digital output DO1 (expansion I/O board)",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "GenericBO2",
   "description": "Generic digital output DO2 (expansion I/O board)",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "GenericBO3",
   "description": "Generic digital output DO3 (expansion I/O board)",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "GenericBO4",
   "description": "Generic digital output DO4 (expansion I/O board)",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "GenericInput1",
   "description": "Generic analog input X1 (0-10 VDC, 4-20 mA or NTC10K)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "GenericInput2",
   "description": "Generic analog input X2 (0-10 VDC, 4-20 mA or NTC10K)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 152,
   "name": "GenericInput3",
   "description": "Generic analog input X3 (0-10 VDC, 4-20 mA or NTC10K)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 153,
   "name": "GenericInput4",
   "description": "Generic analog input X4 (0-10 VDC, 4-20 mA or NTC10K)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 154,
   "name": "GenericInput5",
   "description": "Generic analog input X5 (0-10 VDC, 4-20 mA or NTC10K)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 155,
   "name": "GenericInput6",
   "description": "Generic analog input X6 (0-10 VDC, 4-20 mA or NTC10K)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 156,
   "name": "GenericInput7",
   "description": "Generic analog input X7 (0-10 VDC, 4-20 mA or NTC10K)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 157,
   "name": "GenericInput8",
   "description": "Generic analog input X8 (0-10 VDC, 4-20 mA or NTC10K)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Generic VDC A01",
   "description": "Generic analog output X1, 0-10 VDC (expansion I/O board)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "Generic VDC A02",
   "description": "Generic analog output X2, 0-10 VDC (expansion I/O board)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "Generic VDC A03",
   "description": "Generic analog output X3, 0-10 VDC (expansion I/O board)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "Generic VDC A04",
   "description": "Generic analog output X4, 0-10 VDC (expansion I/O board)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "Generic VDC A05",
   "description": "Generic analog output X5, 0-10 VDC (expansion I/O board)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "Generic VDC A06",
   "description": "Generic analog output X6, 0-10 VDC (expansion I/O board)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 7,
   "name": "Generic VDC A07",
   "description": "Generic analog output X7, 0-10 VDC (expansion I/O board)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 8,
   "name": "Generic VDC A08",
   "description": "Generic analog output X8, 0-10 VDC (expansion I/O board)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 9,
   "name": "Generic mA AO1",
   "description": "Generic analog output X1, 0-20 mA (expansion I/O board)",
   "units": "mA",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 10,
   "name": "Generic mA AO2",
   "description": "Generic analog output X2, 0-20 mA (expansion I/O board)",
   "units": "mA",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 11,
   "name": "Generic mA AO3",
   "description": "Generic analog output X3, 0-20 mA (expansion I/O board)",
   "units": "mA",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 12,
   "name": "Generic mA AO4",
   "description": "Generic analog output X4, 0-20 mA (expansion I/O board)",
   "units": "mA",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "ActiveFault",
   "description": "Fault Alarm (highest-priority active fault)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 1,
   "name": "Faults",
   "description": "Notification class for faults",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 2,
   "name": "Problems",
   "description": "Notification class for problems",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 3,
   "name": "Warnings",
   "description": "Notification class for warnings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 4,
   "name": "Events",
   "description": "Notification class for events",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "AirFlwFlt",
   "description": "Airflow Fault (208)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "AirFlwStatus",
   "description": "Airflow status",
   "units": "",
   "access": "R",
   "states": "0=NoFlow, 1=Flow"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "FilterSw",
   "description": "Main Filter Switch Input",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "FilterWrn",
   "description": "Main Filter Warning (24)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "FilterSw2",
   "description": "Final Filter Switch Input",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "FilterWrn2",
   "description": "Final Filter Warning (25)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "ERWheelWrn",
   "description": "Energy Wheel Warning (58)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "HiRATFlt",
   "description": "High Return Air Temperature Fault (220)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "OverEconoWrn",
   "description": "Over Economizing Warning (50)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "UnderEconoWrn",
   "description": "Under Economizing Warning (52)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "ExcessOAWrn",
   "description": "Excess Outdoor Air Warning (54)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "OADStuckWrn",
   "description": "Outdoor Air Damper Stuck Warning (56)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "RetExhFanWrn",
   "description": "Return / Exhaust Fan Warning (34)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "FreezeStat",
   "description": "Freeze Fault (252)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "FreezePrb",
   "description": "Freeze Problem (198)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "HeatFailPrb",
   "description": "Heat Fail Problem (199)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "DuctHiLmtSw",
   "description": "Duct High Limit Fault (224)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "EmergencyOffSw",
   "description": "Emergency Off Fault (250)",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed"
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "RefrigSnsrPrb",
   "description": "Refrigerant Sensor Problem (134)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "RefigLeakPrb",
   "description": "Refrigerant Leak Problem (133)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "HiDwptClgDsbdPrb",
   "description": "High Dewpint Cooling Disable Problem (61)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "HiDwptClgDsbdFlt",
   "description": "High Dewpint Cooling Disable Fault (205)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "CondOverflowPrb",
   "description": "Condensate Overflow Problem (62)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "RemRhtDsbld",
   "description": "Remote Condenser Reheat Disable Problem (73)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "RemCmpsDsbld",
   "description": "Remote Condenser Disable Problem (63)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "C1HiPressPrb",
   "description": "High Pressure Problem Circuit 1 (165)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 200,
   "name": "C2HiPressPrb",
   "description": "High Pressure Problem Circuit 2 (166)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 300,
   "name": "C3HiPressPrb",
   "description": "High Pressure Problem Circuit 3 (167)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 101,
   "name": "C1LoPressPrb",
   "description": "Low Pressure Problem Circuit 1 (160)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 201,
   "name": "C2LoPressPrb",
   "description": "Low Pressure Problem Circuit 2 (161)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 301,
   "name": "C3LoPressPrb",
   "description": "Low Pressure Problem Circuit 3 (162)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 102,
   "name": "C1LoDPPrb",
   "description": "Low Discharge Pressure Problem Circuit 1 (170)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 202,
   "name": "C2LoDPPrb",
   "description": "Low Discharge Pressure Problem Circuit 2 (171)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 302,
   "name": "C3LoDPPrb",
   "description": "Low Discharge Pressure Problem Circuit 3 (172)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 103,
   "name": "C1OAFPrb",
   "description": "Outdoor Air Fan 1 Problem (130)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 203,
   "name": "C2OAFPrb",
   "description": "Outdoor Air Fan 2 Problem (131)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 303,
   "name": "C3OAFPrb",
   "description": "Outdoor Air Fan 3 Problem (132)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "C1IFBCommPrb",
   "description": "Inverter Compressor Board (IFB) 1 Problem (190)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 204,
   "name": "C2IFBCommPrb",
   "description": "Inverter Compressor Board (IFB) 2 Problem (191)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 304,
   "name": "C3IFBCommPrb",
   "description": "Inverter Compressor Board (IFB) 3 Problem (189)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "C1ChargeLossPrb",
   "description": "Charge Loss Problem Circuit 1 (150)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 205,
   "name": "C2ChargeLossPrb",
   "description": "Charge Loss Problem Circuit 2 (151)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 305,
   "name": "C3ChargeLossPrb",
   "description": "Charge Loss Problem Circuit 3 (152)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 106,
   "name": "C1LoChargePrb",
   "description": "Low Refrigerant Charge Problem Circuit 1 (145)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 206,
   "name": "C2LoChargePrb",
   "description": "Low Refrigerant Charge Problem Circuit 2 (146)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 306,
   "name": "C3LoChargePrb",
   "description": "Low Refrigerant Charge Problem Circuit 3 (147)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 107,
   "name": "C1HiVCmpTPrb",
   "description": "High Variable Speed Compressor Temperature Problem Circuit 1 (175)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 207,
   "name": "C2HiVCmpTPrb",
   "description": "High Variable Speed Compressor Temperature Problem Circuit 2 (176)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 307,
   "name": "C3HiVCmpTPrb",
   "description": "High Variable Speed Compressor Temperature Problem Circuit 3 (177)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 108,
   "name": "C1VarCompPrb",
   "description": "Variable Speed Compressor Problem Circuit 1 (110)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 208,
   "name": "C2VarCompPrb",
   "description": "Variable Speed Compressor Problem Circuit 2 (111)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 308,
   "name": "C3VarCompPrb",
   "description": "Variable Speed Compressor Problem Circuit 3 (112)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 109,
   "name": "C1LoDischSHPrb",
   "description": "Low Discharge Superheat Problem Circuit 1 (155)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 209,
   "name": "C2LoDischSHPrb",
   "description": "Low Discharge Superheat Problem Circuit 2 (156)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 309,
   "name": "C3LoDischSHPrb",
   "description": "Low Discharge Superheat Problem Circuit 3 (157)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 110,
   "name": "C1HiDischSHPrb",
   "description": "High Discharge Superheat Problem Circuit 1 (185)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 210,
   "name": "C2HiDischSHPrb",
   "description": "High Discharge Superheat Problem Circuit 2 (186)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 310,
   "name": "C3HiDischSHPrb",
   "description": "High Discharge Superheat Problem Circuit 3 (187)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 111,
   "name": "C1HiDLTmpPrb",
   "description": "High Discharge Line Temperature Problem Circuit 1 (120)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 211,
   "name": "C2HiDLTmpPrb",
   "description": "High Discharge Line Temperature Problem Circuit 2 (121)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 311,
   "name": "C3HiDLTmpPrb",
   "description": "High Discharge Line Temperature Problem Circuit 3 (122)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 112,
   "name": "C1EVPrb",
   "description": "Expansion Valve Problem Circuit 1 (125)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 212,
   "name": "C2EVPrb",
   "description": "Expansion Valve Problem Circuit 2 (126)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 312,
   "name": "C3EVPrb",
   "description": "Expansion Valve Problem Circuit 3 (127)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 113,
   "name": "MHGRhtVlv1Prb",
   "description": "Modulating Hot Gas Reheat Valve 1 Problem (101)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 213,
   "name": "MHGRhtVlv2Prb",
   "description": "Modulating Hot Gas Reheat Valve 2 Problem (102)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 114,
   "name": "C14WVPrb",
   "description": "Four-Way Valve Problem Circuit 1 (107)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 214,
   "name": "C24WVPrb",
   "description": "Four-Way Valve Problem Circuit 2 (108)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 314,
   "name": "C34WVPrb",
   "description": "Four-Way Valve Problem Circuit 3 (95)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=In Alarm"
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "FanRetryEvnt",
   "description": "Fan Retry Event",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "TenantOREvnt",
   "description": "Tenant Override Event",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 42,
   "name": "PassVentEvnt",
   "description": "Passive Ventilation Active Event",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "ReheatLmtgEvnt",
   "description": "Reheat Limiting Control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "HtRiseLmtgEvnt",
   "description": "Heat Rise Limiting Event",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 45,
   "name": "BkUpRhtActEvnt",
   "description": "Backup Reheat Active Event",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 46,
   "name": "HPEmrgHtEvnt",
   "description": "Heat Pump Emergency Heat Event",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 141,
   "name": "C1FinTULEvnt",
   "description": "Fin Temperature Unload Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 241,
   "name": "C2FinTULEvnt",
   "description": "Fin Temperature Unload Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 341,
   "name": "C3FinTULEvnt",
   "description": "Fin Temperature Unload Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 142,
   "name": "C1HCRULEvnt",
   "description": "High Compression Ratio Unloading Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 242,
   "name": "C2HCRULEvnt",
   "description": "High Compression Ratio Unloading Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 342,
   "name": "C3HCRULEvnt",
   "description": "High Compression Ratio Unloading Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 144,
   "name": "VCmp1HDLTULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 174,
   "name": "C1HDLT3ULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 175,
   "name": "C1HDLT5ULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 145,
   "name": "C1HiAmpULEvnt",
   "description": "High Current Unload Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 245,
   "name": "C2HiAmpULEvnt",
   "description": "High Current Unload Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 345,
   "name": "C3HiAmpULEvnt",
   "description": "High Current Unload Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 149,
   "name": "C1HPULEvnt",
   "description": "High Pressure Unload Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 249,
   "name": "C2HPULEvnt",
   "description": "High Pressure Unload Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 349,
   "name": "C3HPULEvnt",
   "description": "High Pressure Unload Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 151,
   "name": "C1LDPULEvnt",
   "description": "Low Differential Pressure Unload Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 251,
   "name": "C2LDPULEvnt",
   "description": "Low Differential Pressure Unload Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 351,
   "name": "C3LDPULEvnt",
   "description": "Low Differential Pressure Unload Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 152,
   "name": "C1LoDSHDsbEvnt",
   "description": "Low Discharge Superheat Disable Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 252,
   "name": "C2LoDSHDsbEvnt",
   "description": "Low Discharge Superheat Disable Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 352,
   "name": "C3LoDSHDsbEvnt",
   "description": "Low Discharge Superheat Disable Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 155,
   "name": "C1LPULEvnt",
   "description": "Low Pressure Unload Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 255,
   "name": "C2LPULEvnt",
   "description": "Low Pressure Unload Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 355,
   "name": "C3LPULEvnt",
   "description": "Low Pressure Unload Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 157,
   "name": "C1ReqULEvnt",
   "description": "Unload Request Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 257,
   "name": "C2ReqULEvnt",
   "description": "Unload Request Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 357,
   "name": "C3ReqULEvnt",
   "description": "Unload Request Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 160,
   "name": "C1HiAmbLmtgEvnt",
   "description": "High Ambient Limiting Control Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 260,
   "name": "C2HiAmbLmtgEvnt",
   "description": "High Ambient Limiting Control Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 360,
   "name": "C3HiAmbLmtgEvnt",
   "description": "High Ambient Limiting Control Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 161,
   "name": "C1LoSSH_Evnt",
   "description": "Low Suction Superheat Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 261,
   "name": "C2LoSSH_Evnt",
   "description": "Low Suction Superheat Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 361,
   "name": "C3LoSSH_Evnt",
   "description": "Low Suction Superheat Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 162,
   "name": "C1HiSSH_Evnt",
   "description": "High Suction Superheat Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 262,
   "name": "C2HiSSH_Evnt",
   "description": "High Suction Superheat Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 362,
   "name": "C3HiSSH_Evnt",
   "description": "High Suction Superheat Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 163,
   "name": "C1LoDSH_Evnt",
   "description": "Low Discharge Superheat Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 263,
   "name": "C2LoDSH_Evnt",
   "description": "Low Discharge Superheat Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 363,
   "name": "C3LoDSH_Evnt",
   "description": "Low Discharge Superheat Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 164,
   "name": "C1HiDSH_Evnt",
   "description": "High Discharge Superheat Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 264,
   "name": "C2HiDSH_Evnt",
   "description": "High Discharge Superheat Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 364,
   "name": "C3HiDSH_Evnt",
   "description": "High Discharge Superheat Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 165,
   "name": "C1LoSubCl_Evnt",
   "description": "Low Subcooling Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 265,
   "name": "C2LoSubCl_Evnt",
   "description": "Low Subcooling Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 365,
   "name": "C3LoSubCl_Evnt",
   "description": "Low Subcooling Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 166,
   "name": "C1HiSubCl_Evnt",
   "description": "High Subcooling Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 266,
   "name": "C2HiSubCl_Evnt",
   "description": "High Subcooling Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 366,
   "name": "C3HiSubCl_Evnt",
   "description": "High Subcooling Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 167,
   "name": "C1LoT_Evnt",
   "description": "Low Tc Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 267,
   "name": "C2LoT_Evnt",
   "description": "Low Tc Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 367,
   "name": "C3LoT_Evnt",
   "description": "Low Tc Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 168,
   "name": "C1HiT_Evnt",
   "description": "High Tc Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 268,
   "name": "C2HiT_Evnt",
   "description": "High Tc Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 368,
   "name": "C3HiT_Evnt",
   "description": "High Tc Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 169,
   "name": "C1LoTeg_Evnt",
   "description": "Low Te Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 269,
   "name": "C2LoTeg_Evnt",
   "description": "Low Te Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 369,
   "name": "C3LoTeg_Evnt",
   "description": "Low Te Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 170,
   "name": "C1HiTe_Evnt",
   "description": "High Te Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 270,
   "name": "C2HiTe_Evnt",
   "description": "High Te Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 370,
   "name": "C3HiTe_Evnt",
   "description": "High Te Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 171,
   "name": "C1HiDRT_Evnt",
   "description": "High Discharge Refrigerant Temperature Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 271,
   "name": "C2HiDRT_Evnt",
   "description": "High Discharge Refrigerant Temperature Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 371,
   "name": "C3HiDRT_Evnt",
   "description": "High Discharge Refrigerant Temperature Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 172,
   "name": "C1HiSR_Evnt",
   "description": "High Suction Return Temperature Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 272,
   "name": "C2HiSR_Evnt",
   "description": "High Suction Return Temperature Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 372,
   "name": "C3HiSR_Evnt",
   "description": "High Suction Return Temperature Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 173,
   "name": "C1LowOilPrvntEvnt",
   "description": "Low Oil Prevention Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 273,
   "name": "C2LowOilPrvntEvnt",
   "description": "Low Oil Prevention Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 373,
   "name": "C3LowOilPrvntEvnt",
   "description": "Low Oil Prevention Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 244,
   "name": "VCmp2HDLTULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 274,
   "name": "C2HDLT4ULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 275,
   "name": "C2HDLT6ULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 344,
   "name": "VCmp3HDLTULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 374,
   "name": "C3HDLT3ULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 375,
   "name": "C3HDLT5ULEvnt",
   "description": "High Discharge Line Temperature Unload Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 176,
   "name": "C1OilRetActvEvnt",
   "description": "Oil Return Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 276,
   "name": "C2OilRetActvEvnt",
   "description": "Oil Return Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 376,
   "name": "C3OilRetActvEvnt",
   "description": "Oil Return Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 177,
   "name": "C1HiSSHRHOvrdEvnt",
   "description": "High Suction Superheat Reheat Override Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 277,
   "name": "C2HiSSHRHOvrdEvnt",
   "description": "High Suction Superheat Reheat Override Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 140,
   "name": "C1EVISyncSBEvnt",
   "description": "Expansion Valve Synchronization Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 240,
   "name": "C2EVISyncSBEvnt",
   "description": "Expansion Valve Synchronization Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 340,
   "name": "C3EVSyncSBEvnt",
   "description": "Expansion Valve Synchronization Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 143,
   "name": "C1HDLTSBEvnt",
   "description": "High Discharge Line Temperature Sensor Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 243,
   "name": "C2HDLTSBEvnt",
   "description": "High Discharge Line Temperature Sensor Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 343,
   "name": "C3HDLTSBEvnt",
   "description": "High Discharge Line Temperature Sensor Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 146,
   "name": "C1HiDSHSBEvnt",
   "description": "High Discharge Superheat Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 246,
   "name": "C2HiDSHSBEvnt",
   "description": "High Discharge Superheat Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 346,
   "name": "C3HiDSHSBEvnt",
   "description": "High Discharge Superheat Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 147,
   "name": "C1HiTSBEvnt",
   "description": "Compressor Body High Temperature Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 247,
   "name": "C2HiTSBEvnt",
   "description": "Compressor Body High Temperature Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 347,
   "name": "C3HiTSBEvnt",
   "description": "Compressor Body High Temperature Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 148,
   "name": "C1HPSBEvnt",
   "description": "High Pressure Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 248,
   "name": "C2HPSBEvnt",
   "description": "High Pressure Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 348,
   "name": "C3HPSBEvnt",
   "description": "High Pressure Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 150,
   "name": "C1LDPSBEvnt",
   "description": "Low Pressure Differential Pressure Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 250,
   "name": "C2LDPSBEvnt",
   "description": "Low Pressure Differential Pressure Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 350,
   "name": "C3LDPSBEvnt",
   "description": "Low Pressure Differential Pressure Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 154,
   "name": "C1LPSBEvnt",
   "description": "Low Pressure Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 254,
   "name": "C2LPSBEvnt",
   "description": "Low Pressure Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 354,
   "name": "C3LPSBEvnt",
   "description": "Low Pressure Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 156,
   "name": "C1OAFSBEvnt",
   "description": "Outdoor Air Fan Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 256,
   "name": "C2OAFSBEvnt",
   "description": "Outdoor Air Fan Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 356,
   "name": "C3OAFSBEvnt",
   "description": "Outdoor Air Fan Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 158,
   "name": "C1VCmpPrbSBEvnt",
   "description": "Variable Compressor Problem Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 258,
   "name": "C2VCmpPrbSBEvnt",
   "description": "Variable Compressor Problem Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 358,
   "name": "C3VCmpPrbSBEvnt",
   "description": "Variable Compressor Problem Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 159,
   "name": "C1VCmpReqSBEvnt",
   "description": "Variable Compressor Request Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 259,
   "name": "C2VCmpReqSBEvnt",
   "description": "Variable Compressor Request Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 359,
   "name": "C3VCmpReqSBEvnt",
   "description": "Variable Compressor Request Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 178,
   "name": "C1OAFReqSB_Evnt",
   "description": "Outdoor Air Fan Request for Standby Event Circuit 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 278,
   "name": "C2OAFReqSB_Evnt",
   "description": "Outdoor Air Fan Request for Standby Event Circuit 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 378,
   "name": "C3OAFReqSB_Evnt",
   "description": "Outdoor Air Fan Request for Standby Event Circuit 3",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/daikin-applied/microtech-applied-air-rebel-dps-dpsa-dcsa",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}