Dedicated outdoor air unit (DOAS) controller · BACnet points list
Trane Tracer UC600 Packaged Outdoor Air Unit BACnet points list
Updated 4 November 2026
The Tracer UC600 is a programmable B-AAC controller; on packaged outdoor air units it runs a Trane program exposing about 175 objects with short instances (AI 1, AV 20, BV 16...). The BMS commands occupancy with MV 1 and writes '... BAS' values for sensors and setpoints, which ship Out of Service and must be put In Service first. Which objects are used depends on the unit type and options (space, discharge or VAV control, heat pump, gas heat, ERV).
This page lists 175 BACnet objects for the Trane Tracer UC600 Packaged Outdoor Air Unit — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Tracer UC600 Packaged Outdoor Air Unit
- Equipment
- Dedicated outdoor air unit (DOAS) controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 175 (58 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Tracer UC600 Packaged Outdoor Air Unit
Command occupancy with MV 1 Occupancy Request and send setpoints (AV 25 space setpoint, AV 30/AV 32 discharge setpoints, AV 67 on multizone VAV). If the BMS supplies sensor values, put the '... BAS' objects In Service and keep refreshing them. Read MV 2, BI 1, AV 5 and the diagnostic BVs; clear latching lockouts with BV 16 Alarm Reset.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | Occupancy Request | Occupancy command (1 = Occupied, 2 = Unoccupied, 5 = Auto) | Write |
| AV 25 | Space Temperature Setpoint BAS | Space setpoint (space control / single zone VAV) | Write |
| AV 30 | Discharge Air Cooling Setpoint | Discharge air cooling setpoint (discharge control) | Write |
| AV 32 | Discharge Air Heating Setpoint | Discharge air heating setpoint (discharge control) | Write |
| BV 16 | Alarm Reset | 1 = reset diagnostics and lockouts; return to 0 after | Write |
| MV 2 | Occupancy Status | Confirms the occupancy in effect | Read |
| BI 1 | Supply Fan Status | Supply fan proof (0 = On, 1 = Off) | Read |
| AV 5 | Discharge Air Temperature Active | Discharge air temperature in use | Read |
| BV 17 | System LOCKOUT | Unit locked out; needs Alarm Reset | Read |
| BV 1 | Diagnostic: Supply Fan Failure | Supply fan failure (latching) | Read |
Enable & remote start
No enable point is described. The BAS controls the unit by writing values and putting points In or Out of Service. MV 1 Occupancy Request sets occupancy.
Heartbeat & communication loss
The guide says the BAS must routinely refresh BAS-supplied sensor values to protect against a communication loss, but gives no timeout value.
Sensors & values from the BMS
Space Temperature BAS (AV 20), Space RH BAS (AV 8), Outdoor Air Temperature BAS (AV 75), Outdoor Air Humidity BAS (AV 81) and Discharge Air Temperature BAS (AV 4) are Out of Service from the factory; put them In Service to use them and keep rewriting them. The matching '... Active' AVs show the value in use.
Network setup
- Three rotary switches set the MS/TP MAC address (1-127; 0 is reserved for a Tracer SC) and, by default, the Device ID.
- For a Device ID above 127, enable 'Use Software Device ID' in Tracer TU or the BACnet Setup Tool, then cycle power.
- MS/TP baud rates 9600, 19200, 38400 and 76800 (default 76800); set with Tracer TU or the BACnet Setup Tool along with the communicated units, then cycle power.
- The controller is BTL listed as a B-AAC and supports COV, alarm summary and trend retrieval.
Watch out for
- BV 16 Alarm Reset resets ALL diagnostics and lockouts; the BMS must set it back to inactive afterwards.
- Latching diagnostics (supply fan failure, OAD proving, temperature lockouts, System LOCKOUT) stay active until reset.
- BAS sensor objects are ignored while Out of Service (the factory default).
Trane Tracer UC600 Packaged Outdoor Air Unit BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Space Temperature Local | Local space temperature sensor [Units with Space Temperature Sensor Installed] | °F | Read | |
| AI | 2 | Space Relative Humidity Local | Local space relative humidity sensor [Units with Space Humidity Sensor Installed] | % | Read | |
| AI | 3 | Supply Fan Pressure Local | Local supply fan piezo ring pressure [Units with Piezo Ring on Supply Fan] | in. w.c. | Read | |
| AI | 4 | Circuit 1 Condenser Coil Temperature Local | Local condenser coil temperature sensor on circuit 1 | °F | Read | |
| AI | 5 | Circuit 2 Condenser Coil Temperature Local | Local condenser coil temperature sensor on circuit 2 | °F | Read | |
| AI | 6 | Return Air Temperature Local | Local return air temperature sensor [Units with Modulating Dampers] | °F | Read | |
| AI | 7 | OAD Position Local | Local outside air damper position [Units with Modulating Dampers] | % | Read | |
| AI | 8 | Zone CO2 Local | Local Space CO2 concentration [Units with a CO2 Sensor Installed] | ppm | Read | |
| AI | 9 | Exhaust Fan Pressure Local | Local exhaust fan piezo ring pressure [Units with Piezo Ring on Exhaust Fan] | in. w.c. | Read | |
| AI | 10 | Outdoor Air Flow Local | Local outside air flow [Units with Outside air flow Monitoring] | cfm | Read | |
| AI | 11 | Discharge Air Temperature Local | Local discharge air temperature sensor | °F | Read | |
| AI | 12 | Return Duct/Space Pressure Local | Local return duct or space pressure sensor [Units with Powered Exhaust and Modulating Dampers] | in. w.c. | Read | |
| AI | 13 | Exhaust Leaving Temperature Local | Local exhaust leaving temperature sensor [Units with an ERV] | °F | Read | |
| AI | 14 | Return Air Humidity Local | Local return air humidity sensor [Units with Modulating Dampers] | % | Read | |
| AI | 15 | Evaporator Coil Leaving Temperature Local | Local evaporator leaving air temperature sensor [Units with Compressors] | °F | Read | |
| AI | 16 | Space Occupancy Request Override | Local input that overrides Occupancy Request | Read | ||
| AI | 17 | ERV Supply Side Leaving Temperature Local | Local temperature sensor located post ERV on the supply air side | °F | Read | |
| AI | 18 | Circuit 1 Liquid Line Pressure Local | Local refrigerant pressure sensor on circuit 1 | psi | Read | |
| AI | 19 | Circuit 2 Liquid Line Pressure Local | Local refrigerant pressure sensor on circuit 2 | psi | Read | |
| AI | 20 | Space Temperature Setpoint Local | Local thumbwheel input [Units with Thumbwheel Installed] | °F | Read | |
| AI | 21 | Outdoor Air Temperature Local | Local outside air temperature sensor | °F | Read | |
| AI | 22 | Outdoor Air Relative Humidity Local | Local outside air humidity sensor | % | Read | |
| AI | 23 | Duct Static Pressure Local | Local supply duct pressure sensor [Unit with Multizone VAV] | in. w.c. | Read | |
| AO | 1 | HGRH Command | Analog HGRH output command [Units with Modulating Hot Gas Reheat] | % | Read | |
| AO | 2 | IVFD Command | Analog supply fan VFD speed | % | Read | |
| AO | 3 | Circuit 1 Digital Scroll/ Variable Speed Command | Analog digital scroll or variable speed output command | % | Read | |
| AO | 4 | PEVFD Command | Analog exhaust fan VFD speed [Units with Powered Exhaust] | % | Read | |
| AO | 5 | OAD Position Command | Analog outdoor air damper command [Units with Modulating Dampers] | % | Read | |
| AO | 6 | ERV Bypass Position Command | Analog ERV bypass damper command [Units with ERV] | % | Read | |
| AO | 7 | Condenser Fan Speed Command | Analog condenser fan speed command [Units with Head Pressure Control] | % | Read | |
| AO | 8 | Circuit 2 Digital Scroll/ Variable Speed Command | Analog digital scroll or variable speed output command | % | Read | |
| AO | 11 | Heating Output Command | Analog heating output command [Units with any type of Primary Heat] | % | Read | |
| AV | 1 | Occupied Cooling Setpoint | Space cooling setpoint used in occupied mode [Units with Space Control or Single Zone VAV] | °F | Write | |
| AV | 2 | Occupied Heating Setpoint | Space heating setpoint used in occupied mode [Units with Space Control or Single Zone VAV] | °F | Write | |
| AV | 3 | Occupied Offset | Offset used to calculate occupied heating/cooling setpoints | Δ°F | Write | |
| AV | 4 | Discharge Air Temperature BAS | Communicated discharge air temperature | °F | Write | |
| AVmin | 5 | Discharge Air Temperature Active | Actively used discharge air temperature | °F | Read | |
| AV | 6 | DAT High Temp Cutout | Discharge air high limit; alarm after AV 16 minutes above it | °F | Write | |
| AV | 7 | Space RH Active | Actively used space relative humidity [Units with Space Humidity Sensor Installed] | % | Read | |
| AV | 8 | Space RH BAS | Communicated space relative humidity | % | Write | |
| AV | 9 | Occupied Bypass Time | Unoccupied delay after the occupied button is pressed | Write | ||
| AV | 10 | Outdoor Air Dewpoint Setpoint (OADS) | If the outdoor air dewpoint is greater than OADS | °F | Write | |
| AV | 11 | Outdoor Air Dewpoint Active | Dewpoint of the outdoor air | °F | Read | |
| AV | 12 | Liquid Line Pressure Setpoint | Pressure setpoint used to modulate condenser fan(s) [Air Source Heat Pumps with Head Pressure Control] | psi | Write | |
| AV | 13 | Outdoor Air Minimum Flow Setpoint BAS | Air flow setpoint used to modulate dampers | cfm | Write | |
| AV | 14 | Evaporator Leaving Temperature Setpoint | Evaporator leaving air temperature setpoint during dehumidification mode or Single Zone VAV | °F | Write | |
| AV | 15 | DAT Low Temp Cutout | Discharge air low limit; alarm after AV 16 minutes below it | °F | Write | |
| AV | 16 | DAT Temp Cutout Time | Minutes beyond a discharge air limit before alarm | Write | ||
| AV | 17 | IVFD Signal | Supply fan speed setpoint | % | Write | |
| AV | 18 | Compressor Heating Capacity | Compressor Heating source capacity [Units that are Air Source or Water Source Heat Pumps] | % | Read | |
| AV | 20 | Space Temperature BAS | Communicated space temperature | °F | Write | |
| AV | 23 | Space Temperature Active | Actively used space temperature | °F | Read | |
| AV | 24 | Condenser Coil Temperature Setpoint | Temperature setpoint used to modulate condenser fan(s) | °F | Write | |
| AVmin | 25 | Space Temperature Setpoint BAS | Communicated space temperature setpoint [Units that are Space Control or Single Zone VAV] | °F | Write | |
| AV | 26 | Unoccupied Cooling Setpoint | Space cooling setpoint used in unoccupied mode [Units with Space Temperature/Humidity Sensor Installed] | °F | Write | |
| AV | 27 | Unoccupied Heating Setpoint | Space heating setpoint used in unoccupied mode [Units with Space Temperature/Humidity Sensor Installed] | °F | Write | |
| AV | 28 | Unoccupied Dewpoint Setpoint | Unoccupied space dewpoint above which dehumidification starts | °F | Write | |
| AV | 29 | Outdoor Air Cooling Setpoint (OACS) | Setpoint used to enable cooling [Units with Space Control, Discharge Control, or Single Zone VAV] | °F | Write | |
| AVmin | 30 | Discharge Air Cooling Setpoint | Discharge air setpoint during cooling mode [Units with Discharge Air Control] | °F | Write | |
| AV | 31 | Compressor Count | Number of compressors installed in the unit [Units with DX Cooling] | Write | ||
| AVmin | 32 | Discharge Air Heating Setpoint | Discharge air setpoing during heating mode [Units with Discharge Air Control] | °F | Write | |
| AV | 33 | Outdoor Air Heating Setpoint (OAHS) | Setpoint used to enable heating [Units with Space Control, Discharge Control, or Single Zone VAV] | °F | Write | |
| AV | 34 | Space Dewpoint Setpoint (SPDS) | Space dewpoint setpoint for dehumidification | °F | Write | |
| AV | 35 | Space Dewpoint Active | Actively used space dewpoint | °F | Read | |
| AV | 36 | Minimum Discharge Air Cooling Setpoint | Cooling capacity is limited in order to not fall below this temperature | °F | Write | |
| AV | 37 | Space Temperature Setpoint Active | Actively used space temperature setpoint [Units that are Space Control or Single Zone VAV] | °F | Read | |
| AV | 38 | Outdoor Air Flow Active | Actively used outside air flow [Units with Outside Air Flow Monitoring] | cfm | Read | |
| AV | 39 | Supply Air Flow Setpoint | Setpoint used to modulate the indoor fan speed | cfm | Write | |
| AV | 40 | PEVFD Setpoint | Fan speed setpoint used to control the indoor fan speed | % | Write | |
| AV | 41 | Supply Air Flow Active | Actively used supply airflow [Units with Piezo Ring on Supply Fan] | cfm | Read | |
| AV | 43 | Minimum Discharge Air Heating Setpoint | Primary or Compressor Heating Capacity is limited in order to not fall below | °F | Write | |
| AV | 44 | Heat Capacity | Primary heating source capacity [Units with Primary Heat] | % | Read | |
| AV | 45 | Maximum Supply Air Temperature | Primary or Compressor Heating Capacity is limited in order to not exceed this | °F | Write | |
| AV | 46 | Duct Static Pressure Setpoint BAS | Communicated duct static pressure setpoint [Unit with Multizone VAV] | in. w.c. | Write | |
| AV | 47 | Maximum OA Damper Position | Maximum outdoor air damper position [Units with Modulating Dampers] | % | Write | |
| AV | 48 | Minimum OA Damper Position | Minimum outdoor air damper position [Units with Modulating Dampers] | % | Write | |
| AV | 49 | Duct Static Pressure Setpoint | Setpoint used to modulate indoor fan [Units with Multi Zone VAV] | in. w.c. | Write | |
| AV | 50 | Space CO2 Concentration Setpoints | ppm | Write | ||
| AV | 52 | Cooling Capacity | Primary cooling source capacity [Units with DX Cooling] | % | Read | |
| AV | 53 | Duct Static Pressure Setpoint Active | Actively used duct static pressure setpoint [Unit with Multizone VAV] | in. w.c. | Read | |
| AV | 54 | Exhaust Air Flow Active | Amount of air delivered by the exhaust fan [Units with Piezo Ring on the Exhaust Fan] | cfm | Read | |
| AV | 56 | Return Duct/Space Pressure Setpoint | Setpoint used to modulate exhaust fan speed [Units with Modulating Dampers and Exhaust Fan(s)] | in. w.c. | Write | |
| AV | 57 | Exhaust Air Flow Setpoint | Setpoint used to modulate exhaust fan speed | cfm | Write | |
| AV | 58 | Pre-Heat Enable Temperature | Below this temperature pre-heat will be enabled [Units with an ERV and an Electric Pre-Heater] | °F | Write | |
| AV | 59 | Minimum Supply Air Flow Setpoint | Supply air flow is limited to not fall below this number | cfm | Write | |
| AV | 64 | Duct Static Pressure BAS | Communicated duct static pressure [Units with Multi Zone VAV] | in. w.c. | Write | |
| AV | 65 | Duct Static Pressure Active | Actively used duct static pressure [Units with Multi Zone VAV] | in. w.c. | Read | |
| AV | 66 | Discharge Air Temperature Setpoint Active | Actively used discharge air temperature setpoint [Units with Multi Zone VAV] | °F | Read | |
| AV | 67 | Discharge Air Temperature Setpoint BAS | Communicated discharge air temperature setpoint [Units with Multi Zone VAV] | °F | Write | |
| AV | 68 | Discharge Air Temperature Setpoint | [Units with Multi Zone VAV] | °F | Write | |
| AV | 69 | Heat/Cool Mode Deadband | Deadband between heat and cool mode around discharge setpoint | °F | Write | |
| AV | 70 | Maximum Supply Air Flow Setpoint | Supply air flow is limited to not exceed this number | cfm | Write | |
| AV | 71 | Outdoor Air Minimum Flow Setpoint | Setpoint to modulate the dampers | cfm | Write | |
| AV | 72 | Outdoor Air Minimum Flow Setpoint Active | Actively used setpoint to modulate the dampers | cfm | Read | |
| AV | 75 | Outdoor Air Temperature BAS | Communicated outdoor air temperature | °F | Write | |
| AV | 76 | Outdoor Air Temperature Active | Actively used outdoor air temperature | °F | Read | |
| AV | 81 | Outdoor Air Humidity BAS | Communicated outdoor air relative humidity | % | Write | |
| AV | 82 | Outdoor Air Humidity Active | Actively used outdoor air relative humidity | % | Read | |
| BImin | 1 | Supply Fan Status | Normally Closed Input | Read | 0 = On, 1 = Off | |
| BI | 2 | ESTOP | Emergency stop input, normally open (auto-reset) | Read | 0 = Normal, 1 = ESTOP | |
| BI | 3 | Filter Status | Normally open input | Read | 0 = Clean, 1 = Clogged | |
| BI | 4 | Occupancy Input | Normally open input | Read | 0 = Unoccupied, 1 = Occupied | |
| BI | 5 | OA Damper End Switch | Normally open input | Read | 0 = Not Proven, 1 = Proven | |
| BI | 6 | Gas Valve Status | Normally open input [Units with Gas as the Primary Heat] | Read | 0 = Off, 1 = On | |
| BI | 7 | Exhaust Damper Endswitch | Normally open input [Units with Isolation Dampers] | Read | 0 = Not Proven, 1 = Proven | |
| BI | 8 | Water Flow | Normally open input [Units that are Water Source Heat Pump] | Read | 0 = Off, 1 = On | |
| BI | 9 | Water Coil Low Temp Switch | Normally closed input [Units that are Water Source Heat Pump] | Read | 0 = Open, 1 = Closed | |
| BO | 1 | Supply Fan Start Stop Command | Supply fan start/stop output | Read | 0 = Off, 1 = On | |
| BO | 2 | Outdoor Air Damper Command | Outdoor air damper output | Read | 0 = Open, 1 = Closed | |
| BO | 3 | Heat 1 Command | [Units with Primary Heat] | Read | 0 = Off, 1 = On | |
| BO | 4 | Inducer Command | [Units with Gas as the Primary Heat] | Read | 0 = Off, 1 = On | |
| BO | 5 | Compressor 3 Command | [Units with 3+ Compressors] | Read | 0 = Off, 1 = On | |
| BO | 6 | Compressor 4 Command | [Units with 4+ Compressors] | Read | 0 = Off, 1 = On | |
| BO | 7 | Heat 2 Command | [Units with Gas as the Primary Heat and is a Split Manifold Burner] | Read | 0 = Off, 1 = On | |
| BO | 8 | Heat 3 Command | [Units with Gas as the Primary Heat and has Two Heaters] | Read | 0 = Off, 1 = On | |
| BO | 9 | Exhaust Damper Actuators | [Units with Isolation Dampers] | Read | 0 = Off, 1 = On | |
| BO | 10 | Powered Exhaust Enable | [Units with Isolation Dampers or has Dual Point Power] | Read | 0 = Off, 1 = On | |
| BO | 11 | Compressor 1 Command | [Units with 1+ Compressors] | Read | 0 = Off, 1 = On | |
| BO | 12 | Compressor 2 Command | [Units with 2+ Compressors] | Read | 0 = Off, 1 = On | |
| BO | 13 | Pre-Heat Enable | [Units with Pre-Heat] | Read | 0 = Off, 1 = On | |
| BO | 14 | Condenser Fan Command | [Units with Sound Attenuation Package or an Air Source Heat Pump] | Read | 0 = Off, 1 = On | |
| BO | 15 | ERV Command | [Units with an ERV] | Read | 0 = Off, 1 = On | |
| BO | 16 | Circuit 1 Reversing Valve | [Units that are Heat Pump] | Read | 0 = Off, 1 = On | |
| BO | 17 | Circuit 2 Reversing Valve | [Units that are Heat Pump and Two Circuits] | Read | 0 = Off, 1 = On | |
| BVmin | 1 | Diagnostic: Supply Fan Failure | Latching; cleared with Alarm Reset (BV 16) | Read | 0 = Normal, 1 = Fail | |
| BV | 2 | Diagnostic: Space Temperature Setpoint Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 3 | Diagnostic: OAD Proving Switch | Latching; cleared with Alarm Reset (BV 16) | Read | 0 = Normal, 1 = Fail | |
| BV | 4 | Defrost Mode | [Units that are Heat Pump] | Read | 0 = Disabled, 1 = Enabled | |
| BV | 5 | HGRH Purge Mode | [Units with Hot Gas Reheat] | Read | 0 = Disabled, 1 = Enabled | |
| BV | 6 | Diagnostic: Discharge Air Temperature Source Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 7 | Auxiliary Heating Mode | [Units that are Heat Pump] | Read | 0 = Disabled, 1 = Enabled | |
| BV | 9 | Economizer Mode | [Units with Modulating Dampers] | Read | 0 = Disabled, 1 = Enabled | |
| BV | 10 | Low Temp Lockout | Latching; cleared with Alarm Reset (BV 16) | Read | 0 = Normal, 1 = Fail | |
| BV | 11 | Diagnostic: Space Temperature Source Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 12 | Diagnostic: Space Humidity Source Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 13 | Diagnostic: Outdoor Air Temperature Source Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 14 | Diagnostic: Outdoor Air Humidity Source Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 15 | High Temp Lockout | Latching; cleared with Alarm Reset (BV 16) | Read | 0 = Normal, 1 = Fail | |
| BVmin | 16 | Alarm Reset | 1 = reset all diagnostics and lockouts | Write | 1 = Reset | |
| BVmin | 17 | System LOCKOUT | Latching; cleared with Alarm Reset (BV 16) | Read | 0 = Normal, 1 = Fail | |
| BV | 18 | Return Air Damper Option | Write | 0 = Not Installed, 1 = Installed | ||
| BV | 19 | Diagnostic: Space RH Source Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 20 | Space Temp/Humidity Sensor Installed | [Units that are Space Control or Single Zone VAV] | Write | 0 = Not Installed, 1 = Installed | |
| BV | 21 | Heat Cool Mode Active | Read | 0 = Heat, 1 = Cool | ||
| BV | 22 | Unoccupied Cooling Mode BAS | Write | 0 = Disabled, 1 = Enabled | ||
| BV | 23 | Unoccupied Cooling Mode | Read | 0 = Disabled, 1 = Enabled | ||
| BV | 25 | Compressor Stage 1 Request | [Units with 1+ Compressors] | Read | 0 = Off, 1 = On | |
| BV | 26 | Cooling Lockout BAS | [Units with DX Cooling] | Write | 0 = Normal, 1 = Lockout | |
| BV | 27 | Dehumidification Command | [Units that are Space Control, Single Zone VAV, or Discharge Control] | Read | 0 = Disabled, 1 = Enabled | |
| BV | 28 | Thumbwheel Installed | Write | 0 = Not Installed, 1 = Installed | ||
| BV | 29 | Compressor Stage 2 Request | [Units with 2+ Compressors] | Read | 0 = Off, 1 = On | |
| BV | 30 | Compressor Stage 3 Request | [Units with 3+ Compressors] | Read | 0 = Off, 1 = On | |
| BV | 31 | Compressor Stage 4 Request | [Units with 4 Compressors] | Read | 0 = Off, 1 = On | |
| BV | 32 | Diagnostic: ERV Leaving Air Conditions Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 33 | Pre-Purge Status | [Units with Gas as the Primary Heat] | Read | 0 = Disabled, 1 = Enabled | |
| BV | 34 | Diagnostic: Evap Temp Source Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 35 | Y1 Space Lockout | [Units that are Space Control or Single Zone VAV] | Read | 0 = Disabled, 1 = Enabled | |
| BV | 36 | Diagnostic: Duct Static Pressure Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 37 | Unoccupied Dehumid Mode BAS | Write | 0 = Disabled, 1 = Enabled | ||
| BV | 38 | Unoccupied Heating Mode BAS | Write | 0 = Disabled, 1 = Enabled | ||
| BV | 39 | Unoccupied Heating Mode | Read | 0 = Disabled, 1 = Enabled | ||
| BV | 40 | Unoccupied Dehumid Mode | Read | 0 = Disabled, 1 = Enabled | ||
| BV | 42 | Diagnostic: Heat Failure | Auto-reset diagnostic | Read | 0 = Normal, 1 = Fail | |
| BV | 43 | Ventilation | [Units that are Space Control, Single Zone VAV, or Discharge Control] | Read | 0 = Disabled, 1 = Enabled | |
| BV | 45 | Economizer Control Type | Write | 0 = Dry Bulb, 1 = Dry Bulb and Enthalpy | ||
| MVmin | 1 | Occupancy Request | Occupancy command | Write | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MVmin | 2 | Occupancy Status | Occupancy in effect | Read | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Unknown | |
| MV | 4 | Heat Cool Mode Status | Read | 1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off | ||
| MV | 7 | Compressor Stage 3 Status | [Units with 3+ Compressors] | Read | 1 = Off, 2 = On, 3 = Not Present | |
| MV | 8 | Compressor Stage 4 Status | [Units with 4 Compressors] | Read | 1 = Off, 2 = On, 3 = Not Present | |
| MV | 9 | Heat Type | Read | 1 = No Heat, 2 = Indirect Fired Gas Heat, 3 = Electric Heat, 4 = Other, 5 = Direct Fired Gas Heat, 6 = Hot Water/Steam | ||
| MV | 13 | Program Control Type | Configured control program type | Read | 1 = Space Control, 2 = Discharge Control, 3 = Single Zone VAV, 4 = Multi Zone VAV | |
| MV | 16 | Dehumidification System Status | Read | 1 = Off, 2 = On, 3 = Not Present | ||
| MV | 21 | Compressor Stage 1 Status | [Units with 1+ Compressors] | Read | 1 = Off, 2 = On, 3 = Not Present | |
| MV | 22 | Compressor Stage 2 Status | [Units with 2+ Compressors] | Read | 1 = Off, 2 = On, 3 = Not Present |
No points match these filters.
Object ID lookup: Trane Tracer UC600 Packaged Outdoor Air Unit point IDs by name
AI1Space Temperature LocalAI2Space Relative Humidity LocalAI3Supply Fan Pressure LocalAI4Circuit 1 Condenser Coil Temperature LocalAI5Circuit 2 Condenser Coil Temperature LocalAI6Return Air Temperature LocalAI7OAD Position LocalAI8Zone CO2 LocalAI9Exhaust Fan Pressure LocalAI10Outdoor Air Flow LocalAI11Discharge Air Temperature LocalAI12Return Duct/Space Pressure LocalAI13Exhaust Leaving Temperature LocalAI14Return Air Humidity LocalAI15Evaporator Coil Leaving Temperature LocalAI16Space Occupancy Request OverrideAI17ERV Supply Side Leaving Temperature LocalAI18Circuit 1 Liquid Line Pressure LocalAI19Circuit 2 Liquid Line Pressure LocalAI20Space Temperature Setpoint LocalAI21Outdoor Air Temperature LocalAI22Outdoor Air Relative Humidity LocalAI23Duct Static Pressure LocalAO1HGRH CommandAO2IVFD CommandAO3Circuit 1 Digital Scroll/ Variable Speed CommandAO4PEVFD CommandAO5OAD Position CommandAO6ERV Bypass Position CommandAO7Condenser Fan Speed CommandAO8Circuit 2 Digital Scroll/ Variable Speed CommandAO11Heating Output CommandAV1Occupied Cooling SetpointAV2Occupied Heating SetpointAV3Occupied OffsetAV4Discharge Air Temperature BASAV5Discharge Air Temperature ActiveAV6DAT High Temp CutoutAV7Space RH ActiveAV8Space RH BASAV9Occupied Bypass TimeAV10Outdoor Air Dewpoint Setpoint (OADS)AV11Outdoor Air Dewpoint ActiveAV12Liquid Line Pressure SetpointAV13Outdoor Air Minimum Flow Setpoint BASAV14Evaporator Leaving Temperature SetpointAV15DAT Low Temp CutoutAV16DAT Temp Cutout TimeAV17IVFD SignalAV18Compressor Heating CapacityAV20Space Temperature BASAV23Space Temperature ActiveAV24Condenser Coil Temperature SetpointAV25Space Temperature Setpoint BASAV26Unoccupied Cooling SetpointAV27Unoccupied Heating SetpointAV28Unoccupied Dewpoint SetpointAV29Outdoor Air Cooling Setpoint (OACS)AV30Discharge Air Cooling SetpointAV31Compressor CountAV32Discharge Air Heating SetpointAV33Outdoor Air Heating Setpoint (OAHS)AV34Space Dewpoint Setpoint (SPDS)AV35Space Dewpoint ActiveAV36Minimum Discharge Air Cooling SetpointAV37Space Temperature Setpoint ActiveAV38Outdoor Air Flow ActiveAV39Supply Air Flow SetpointAV40PEVFD SetpointAV41Supply Air Flow ActiveAV43Minimum Discharge Air Heating SetpointAV44Heat CapacityAV45Maximum Supply Air TemperatureAV46Duct Static Pressure Setpoint BASAV47Maximum OA Damper PositionAV48Minimum OA Damper PositionAV49Duct Static Pressure SetpointAV50Space CO2 Concentration SetpointsAV52Cooling CapacityAV53Duct Static Pressure Setpoint ActiveAV54Exhaust Air Flow ActiveAV56Return Duct/Space Pressure SetpointAV57Exhaust Air Flow SetpointAV58Pre-Heat Enable TemperatureAV59Minimum Supply Air Flow SetpointAV64Duct Static Pressure BASAV65Duct Static Pressure ActiveAV66Discharge Air Temperature Setpoint ActiveAV67Discharge Air Temperature Setpoint BASAV68Discharge Air Temperature SetpointAV69Heat/Cool Mode DeadbandAV70Maximum Supply Air Flow SetpointAV71Outdoor Air Minimum Flow SetpointAV72Outdoor Air Minimum Flow Setpoint ActiveAV75Outdoor Air Temperature BASAV76Outdoor Air Temperature ActiveAV81Outdoor Air Humidity BASAV82Outdoor Air Humidity ActiveBI1Supply Fan StatusBI2ESTOPBI3Filter StatusBI4Occupancy InputBI5OA Damper End SwitchBI6Gas Valve StatusBI7Exhaust Damper EndswitchBI8Water FlowBI9Water Coil Low Temp SwitchBO1Supply Fan Start Stop CommandBO2Outdoor Air Damper CommandBO3Heat 1 CommandBO4Inducer CommandBO5Compressor 3 CommandBO6Compressor 4 CommandBO7Heat 2 CommandBO8Heat 3 CommandBO9Exhaust Damper ActuatorsBO10Powered Exhaust EnableBO11Compressor 1 CommandBO12Compressor 2 CommandBO13Pre-Heat EnableBO14Condenser Fan CommandBO15ERV CommandBO16Circuit 1 Reversing ValveBO17Circuit 2 Reversing ValveBV1Diagnostic: Supply Fan FailureBV2Diagnostic: Space Temperature Setpoint FailureBV3Diagnostic: OAD Proving SwitchBV4Defrost ModeBV5HGRH Purge ModeBV6Diagnostic: Discharge Air Temperature Source FailureBV7Auxiliary Heating ModeBV9Economizer ModeBV10Low Temp LockoutBV11Diagnostic: Space Temperature Source FailureBV12Diagnostic: Space Humidity Source FailureBV13Diagnostic: Outdoor Air Temperature Source FailureBV14Diagnostic: Outdoor Air Humidity Source FailureBV15High Temp LockoutBV16Alarm ResetBV17System LOCKOUTBV18Return Air Damper OptionBV19Diagnostic: Space RH Source FailureBV20Space Temp/Humidity Sensor InstalledBV21Heat Cool Mode ActiveBV22Unoccupied Cooling Mode BASBV23Unoccupied Cooling ModeBV25Compressor Stage 1 RequestBV26Cooling Lockout BASBV27Dehumidification CommandBV28Thumbwheel InstalledBV29Compressor Stage 2 RequestBV30Compressor Stage 3 RequestBV31Compressor Stage 4 RequestBV32Diagnostic: ERV Leaving Air Conditions FailureBV33Pre-Purge StatusBV34Diagnostic: Evap Temp Source FailureBV35Y1 Space LockoutBV36Diagnostic: Duct Static Pressure FailureBV37Unoccupied Dehumid Mode BASBV38Unoccupied Heating Mode BASBV39Unoccupied Heating ModeBV40Unoccupied Dehumid ModeBV42Diagnostic: Heat FailureBV43VentilationBV45Economizer Control TypeMV1Occupancy RequestMV2Occupancy StatusMV4Heat Cool Mode StatusMV7Compressor Stage 3 StatusMV8Compressor Stage 4 StatusMV9Heat TypeMV13Program Control TypeMV16Dehumidification System StatusMV21Compressor Stage 1 StatusMV22Compressor Stage 2 Status
Integration notes
- The guide has no read/write column. Access is inferred: inputs, hardware outputs, Active/Status values and diagnostics are read-only; setpoints, '... BAS' values, configuration values, Alarm Reset and Occupancy Request are writable.
- Each object is printed twice in the guide (by type in Tables 3-9 and by name in Table 10); names here come from the by-type tables. Table 10 calls AV 50 'Space CO2 Concentration Setpoint' and BV 43 'Ventilation Mode'.
- 'When the point exists' conditions are shown in brackets where they fit; points marked 'All Units' have no bracket.
- BI 1 Supply Fan Status is printed with inverted states (0 = On, 1 = Off).
- The UC600 hardware also has an Ethernet port, but this guide covers BACnet MS/TP only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Tracer UC600 Packaged Outdoor Air Unit and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Tracer UC600 Packaged Outdoor Air Unit
How many BACnet points does the Trane Tracer UC600 Packaged Outdoor Air Unit have?
This list has 175 BACnet objects: 23 analog inputs, 9 analog outputs, 66 analog values, 9 binary inputs, 17 binary outputs, 41 binary values, 10 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Tracer UC600 Packaged Outdoor Air Unit BACnet points are writable?
58 of the 175 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Tracer UC600 Packaged Outdoor Air Unit BACnet documentation?
The source is Integration Guide: Tracer UC600 Programmable Controller, Packaged Outdoor Air Unit (BAS-SVP18E-EN), revision July 2022, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP18E-EN_07012022.pdf.
What are the minimum BACnet points to integrate the Trane Tracer UC600 Packaged Outdoor Air Unit?
Start with MV 1 Occupancy Request (Occupancy command (1 = Occupied, 2 = Unoccupied, 5 = Auto)); AV 25 Space Temperature Setpoint BAS (Space setpoint (space control / single zone VAV)); AV 30 Discharge Air Cooling Setpoint (Discharge air cooling setpoint (discharge control)); AV 32 Discharge Air Heating Setpoint (Discharge air heating setpoint (discharge control)); BV 16 Alarm Reset (1 = reset diagnostics and lockouts; return to 0 after); MV 2 Occupancy Status (Confirms the occupancy in effect); BI 1 Supply Fan Status (Supply fan proof (0 = On, 1 = Off)); AV 5 Discharge Air Temperature Active (Discharge air temperature in use); BV 17 System LOCKOUT (Unit locked out; needs Alarm Reset); BV 1 Diagnostic: Supply Fan Failure (Supply fan failure (latching)).
How do I enable BMS control of the Trane Tracer UC600 Packaged Outdoor Air Unit?
No enable point is described. The BAS controls the unit by writing values and putting points In or Out of Service. MV 1 Occupancy Request sets occupancy.
Does the Trane Tracer UC600 Packaged Outdoor Air Unit need a BACnet heartbeat or have a communication timeout?
The guide says the BAS must routinely refresh BAS-supplied sensor values to protect against a communication loss, but gives no timeout value.
Can the BMS supply sensor values to the Trane Tracer UC600 Packaged Outdoor Air Unit?
Space Temperature BAS (AV 20), Space RH BAS (AV 8), Outdoor Air Temperature BAS (AV 75), Outdoor Air Humidity BAS (AV 81) and Discharge Air Temperature BAS (AV 4) are Out of Service from the factory; put them In Service to use them and keep rewriting them. The matching '... Active' AVs show the value in use.
How do I check these points on the real Tracer UC600 Packaged Outdoor Air Unit?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Integration Guide: Tracer UC600 Programmable Controller, Packaged Outdoor Air Unit · BAS-SVP18E-EN · rev. July 2022. Object names, instances and units are reproduced as published; descriptions are our own.