Dedicated outdoor air unit (DOAS) controller · BACnet points list

Trane Tracer UC600 Packaged Outdoor Air Unit BACnet points list

Updated 4 November 2026

Short answer

The Tracer UC600 is a programmable B-AAC controller; on packaged outdoor air units it runs a Trane program exposing about 175 objects with short instances (AI 1, AV 20, BV 16...). The BMS commands occupancy with MV 1 and writes '... BAS' values for sensors and setpoints, which ship Out of Service and must be put In Service first. Which objects are used depends on the unit type and options (space, discharge or VAV control, heat pump, gas heat, ERV).

This page lists 175 BACnet objects for the Trane Tracer UC600 Packaged Outdoor Air Unit — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Tracer UC600 Packaged Outdoor Air Unit
Equipment
Dedicated outdoor air unit (DOAS) controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
175 (58 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18
Source document
Integration Guide: Tracer UC600 Programmable Controller, Packaged Outdoor Air Unit · BAS-SVP18E-EN · rev. July 2022
Download CSV 175 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.

BMS integration notes: Trane Tracer UC600 Packaged Outdoor Air Unit

Integration in brief

Command occupancy with MV 1 Occupancy Request and send setpoints (AV 25 space setpoint, AV 30/AV 32 discharge setpoints, AV 67 on multizone VAV). If the BMS supplies sensor values, put the '... BAS' objects In Service and keep refreshing them. Read MV 2, BI 1, AV 5 and the diagnostic BVs; clear latching lockouts with BV 16 Alarm Reset.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Occupancy RequestOccupancy command (1 = Occupied, 2 = Unoccupied, 5 = Auto)Write
AV 25Space Temperature Setpoint BASSpace setpoint (space control / single zone VAV)Write
AV 30Discharge Air Cooling SetpointDischarge air cooling setpoint (discharge control)Write
AV 32Discharge Air Heating SetpointDischarge air heating setpoint (discharge control)Write
BV 16Alarm Reset1 = reset diagnostics and lockouts; return to 0 afterWrite
MV 2Occupancy StatusConfirms the occupancy in effectRead
BI 1Supply Fan StatusSupply fan proof (0 = On, 1 = Off)Read
AV 5Discharge Air Temperature ActiveDischarge air temperature in useRead
BV 17System LOCKOUTUnit locked out; needs Alarm ResetRead
BV 1Diagnostic: Supply Fan FailureSupply fan failure (latching)Read

Enable & remote start

No enable point is described. The BAS controls the unit by writing values and putting points In or Out of Service. MV 1 Occupancy Request sets occupancy.

Heartbeat & communication loss

The guide says the BAS must routinely refresh BAS-supplied sensor values to protect against a communication loss, but gives no timeout value.

Sensors & values from the BMS

Space Temperature BAS (AV 20), Space RH BAS (AV 8), Outdoor Air Temperature BAS (AV 75), Outdoor Air Humidity BAS (AV 81) and Discharge Air Temperature BAS (AV 4) are Out of Service from the factory; put them In Service to use them and keep rewriting them. The matching '... Active' AVs show the value in use.

Network setup

Watch out for

Trane Tracer UC600 Packaged Outdoor Air Unit BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

175 of 175 shown
Type
Multi-state
Access
Show
Trane Tracer UC600 Packaged Outdoor Air Unit BACnet Points List
DescriptionStates
AI1Space Temperature LocalLocal space temperature sensor [Units with Space Temperature Sensor Installed]°FRead
AI2Space Relative Humidity LocalLocal space relative humidity sensor [Units with Space Humidity Sensor Installed]%Read
AI3Supply Fan Pressure LocalLocal supply fan piezo ring pressure [Units with Piezo Ring on Supply Fan]in. w.c.Read
AI4Circuit 1 Condenser Coil Temperature LocalLocal condenser coil temperature sensor on circuit 1°FRead
AI5Circuit 2 Condenser Coil Temperature LocalLocal condenser coil temperature sensor on circuit 2°FRead
AI6Return Air Temperature LocalLocal return air temperature sensor [Units with Modulating Dampers]°FRead
AI7OAD Position LocalLocal outside air damper position [Units with Modulating Dampers]%Read
AI8Zone CO2 LocalLocal Space CO2 concentration [Units with a CO2 Sensor Installed]ppmRead
AI9Exhaust Fan Pressure LocalLocal exhaust fan piezo ring pressure [Units with Piezo Ring on Exhaust Fan]in. w.c.Read
AI10Outdoor Air Flow LocalLocal outside air flow [Units with Outside air flow Monitoring]cfmRead
AI11Discharge Air Temperature LocalLocal discharge air temperature sensor°FRead
AI12Return Duct/Space Pressure LocalLocal return duct or space pressure sensor [Units with Powered Exhaust and Modulating Dampers]in. w.c.Read
AI13Exhaust Leaving Temperature LocalLocal exhaust leaving temperature sensor [Units with an ERV]°FRead
AI14Return Air Humidity LocalLocal return air humidity sensor [Units with Modulating Dampers]%Read
AI15Evaporator Coil Leaving Temperature LocalLocal evaporator leaving air temperature sensor [Units with Compressors]°FRead
AI16Space Occupancy Request OverrideLocal input that overrides Occupancy RequestRead
AI17ERV Supply Side Leaving Temperature LocalLocal temperature sensor located post ERV on the supply air side°FRead
AI18Circuit 1 Liquid Line Pressure LocalLocal refrigerant pressure sensor on circuit 1psiRead
AI19Circuit 2 Liquid Line Pressure LocalLocal refrigerant pressure sensor on circuit 2psiRead
AI20Space Temperature Setpoint LocalLocal thumbwheel input [Units with Thumbwheel Installed]°FRead
AI21Outdoor Air Temperature LocalLocal outside air temperature sensor°FRead
AI22Outdoor Air Relative Humidity LocalLocal outside air humidity sensor%Read
AI23Duct Static Pressure LocalLocal supply duct pressure sensor [Unit with Multizone VAV]in. w.c.Read
AO1HGRH CommandAnalog HGRH output command [Units with Modulating Hot Gas Reheat]%Read
AO2IVFD CommandAnalog supply fan VFD speed%Read
AO3Circuit 1 Digital Scroll/ Variable Speed CommandAnalog digital scroll or variable speed output command%Read
AO4PEVFD CommandAnalog exhaust fan VFD speed [Units with Powered Exhaust]%Read
AO5OAD Position CommandAnalog outdoor air damper command [Units with Modulating Dampers]%Read
AO6ERV Bypass Position CommandAnalog ERV bypass damper command [Units with ERV]%Read
AO7Condenser Fan Speed CommandAnalog condenser fan speed command [Units with Head Pressure Control]%Read
AO8Circuit 2 Digital Scroll/ Variable Speed CommandAnalog digital scroll or variable speed output command%Read
AO11Heating Output CommandAnalog heating output command [Units with any type of Primary Heat]%Read
AV1Occupied Cooling SetpointSpace cooling setpoint used in occupied mode [Units with Space Control or Single Zone VAV]°FWrite
AV2Occupied Heating SetpointSpace heating setpoint used in occupied mode [Units with Space Control or Single Zone VAV]°FWrite
AV3Occupied OffsetOffset used to calculate occupied heating/cooling setpointsΔ°FWrite
AV4Discharge Air Temperature BASCommunicated discharge air temperature°FWrite
AVmin5Discharge Air Temperature ActiveActively used discharge air temperature°FRead
AV6DAT High Temp CutoutDischarge air high limit; alarm after AV 16 minutes above it°FWrite
AV7Space RH ActiveActively used space relative humidity [Units with Space Humidity Sensor Installed]%Read
AV8Space RH BASCommunicated space relative humidity%Write
AV9Occupied Bypass TimeUnoccupied delay after the occupied button is pressedWrite
AV10Outdoor Air Dewpoint Setpoint (OADS)If the outdoor air dewpoint is greater than OADS°FWrite
AV11Outdoor Air Dewpoint ActiveDewpoint of the outdoor air°FRead
AV12Liquid Line Pressure SetpointPressure setpoint used to modulate condenser fan(s) [Air Source Heat Pumps with Head Pressure Control]psiWrite
AV13Outdoor Air Minimum Flow Setpoint BASAir flow setpoint used to modulate damperscfmWrite
AV14Evaporator Leaving Temperature SetpointEvaporator leaving air temperature setpoint during dehumidification mode or Single Zone VAV°FWrite
AV15DAT Low Temp CutoutDischarge air low limit; alarm after AV 16 minutes below it°FWrite
AV16DAT Temp Cutout TimeMinutes beyond a discharge air limit before alarmWrite
AV17IVFD SignalSupply fan speed setpoint%Write
AV18Compressor Heating CapacityCompressor Heating source capacity [Units that are Air Source or Water Source Heat Pumps]%Read
AV20Space Temperature BASCommunicated space temperature°FWrite
AV23Space Temperature ActiveActively used space temperature°FRead
AV24Condenser Coil Temperature SetpointTemperature setpoint used to modulate condenser fan(s)°FWrite
AVmin25Space Temperature Setpoint BASCommunicated space temperature setpoint [Units that are Space Control or Single Zone VAV]°FWrite
AV26Unoccupied Cooling SetpointSpace cooling setpoint used in unoccupied mode [Units with Space Temperature/Humidity Sensor Installed]°FWrite
AV27Unoccupied Heating SetpointSpace heating setpoint used in unoccupied mode [Units with Space Temperature/Humidity Sensor Installed]°FWrite
AV28Unoccupied Dewpoint SetpointUnoccupied space dewpoint above which dehumidification starts°FWrite
AV29Outdoor Air Cooling Setpoint (OACS)Setpoint used to enable cooling [Units with Space Control, Discharge Control, or Single Zone VAV]°FWrite
AVmin30Discharge Air Cooling SetpointDischarge air setpoint during cooling mode [Units with Discharge Air Control]°FWrite
AV31Compressor CountNumber of compressors installed in the unit [Units with DX Cooling]Write
AVmin32Discharge Air Heating SetpointDischarge air setpoing during heating mode [Units with Discharge Air Control]°FWrite
AV33Outdoor Air Heating Setpoint (OAHS)Setpoint used to enable heating [Units with Space Control, Discharge Control, or Single Zone VAV]°FWrite
AV34Space Dewpoint Setpoint (SPDS)Space dewpoint setpoint for dehumidification°FWrite
AV35Space Dewpoint ActiveActively used space dewpoint°FRead
AV36Minimum Discharge Air Cooling SetpointCooling capacity is limited in order to not fall below this temperature°FWrite
AV37Space Temperature Setpoint ActiveActively used space temperature setpoint [Units that are Space Control or Single Zone VAV]°FRead
AV38Outdoor Air Flow ActiveActively used outside air flow [Units with Outside Air Flow Monitoring]cfmRead
AV39Supply Air Flow SetpointSetpoint used to modulate the indoor fan speedcfmWrite
AV40PEVFD SetpointFan speed setpoint used to control the indoor fan speed%Write
AV41Supply Air Flow ActiveActively used supply airflow [Units with Piezo Ring on Supply Fan]cfmRead
AV43Minimum Discharge Air Heating SetpointPrimary or Compressor Heating Capacity is limited in order to not fall below°FWrite
AV44Heat CapacityPrimary heating source capacity [Units with Primary Heat]%Read
AV45Maximum Supply Air TemperaturePrimary or Compressor Heating Capacity is limited in order to not exceed this°FWrite
AV46Duct Static Pressure Setpoint BASCommunicated duct static pressure setpoint [Unit with Multizone VAV]in. w.c.Write
AV47Maximum OA Damper PositionMaximum outdoor air damper position [Units with Modulating Dampers]%Write
AV48Minimum OA Damper PositionMinimum outdoor air damper position [Units with Modulating Dampers]%Write
AV49Duct Static Pressure SetpointSetpoint used to modulate indoor fan [Units with Multi Zone VAV]in. w.c.Write
AV50Space CO2 Concentration SetpointsppmWrite
AV52Cooling CapacityPrimary cooling source capacity [Units with DX Cooling]%Read
AV53Duct Static Pressure Setpoint ActiveActively used duct static pressure setpoint [Unit with Multizone VAV]in. w.c.Read
AV54Exhaust Air Flow ActiveAmount of air delivered by the exhaust fan [Units with Piezo Ring on the Exhaust Fan]cfmRead
AV56Return Duct/Space Pressure SetpointSetpoint used to modulate exhaust fan speed [Units with Modulating Dampers and Exhaust Fan(s)]in. w.c.Write
AV57Exhaust Air Flow SetpointSetpoint used to modulate exhaust fan speedcfmWrite
AV58Pre-Heat Enable TemperatureBelow this temperature pre-heat will be enabled [Units with an ERV and an Electric Pre-Heater]°FWrite
AV59Minimum Supply Air Flow SetpointSupply air flow is limited to not fall below this numbercfmWrite
AV64Duct Static Pressure BASCommunicated duct static pressure [Units with Multi Zone VAV]in. w.c.Write
AV65Duct Static Pressure ActiveActively used duct static pressure [Units with Multi Zone VAV]in. w.c.Read
AV66Discharge Air Temperature Setpoint ActiveActively used discharge air temperature setpoint [Units with Multi Zone VAV]°FRead
AV67Discharge Air Temperature Setpoint BASCommunicated discharge air temperature setpoint [Units with Multi Zone VAV]°FWrite
AV68Discharge Air Temperature Setpoint[Units with Multi Zone VAV]°FWrite
AV69Heat/Cool Mode DeadbandDeadband between heat and cool mode around discharge setpoint°FWrite
AV70Maximum Supply Air Flow SetpointSupply air flow is limited to not exceed this numbercfmWrite
AV71Outdoor Air Minimum Flow SetpointSetpoint to modulate the damperscfmWrite
AV72Outdoor Air Minimum Flow Setpoint ActiveActively used setpoint to modulate the damperscfmRead
AV75Outdoor Air Temperature BASCommunicated outdoor air temperature°FWrite
AV76Outdoor Air Temperature ActiveActively used outdoor air temperature°FRead
AV81Outdoor Air Humidity BASCommunicated outdoor air relative humidity%Write
AV82Outdoor Air Humidity ActiveActively used outdoor air relative humidity%Read
BImin1Supply Fan StatusNormally Closed InputRead0 = On, 1 = Off
BI2ESTOPEmergency stop input, normally open (auto-reset)Read0 = Normal, 1 = ESTOP
BI3Filter StatusNormally open inputRead0 = Clean, 1 = Clogged
BI4Occupancy InputNormally open inputRead0 = Unoccupied, 1 = Occupied
BI5OA Damper End SwitchNormally open inputRead0 = Not Proven, 1 = Proven
BI6Gas Valve StatusNormally open input [Units with Gas as the Primary Heat]Read0 = Off, 1 = On
BI7Exhaust Damper EndswitchNormally open input [Units with Isolation Dampers]Read0 = Not Proven, 1 = Proven
BI8Water FlowNormally open input [Units that are Water Source Heat Pump]Read0 = Off, 1 = On
BI9Water Coil Low Temp SwitchNormally closed input [Units that are Water Source Heat Pump]Read0 = Open, 1 = Closed
BO1Supply Fan Start Stop CommandSupply fan start/stop outputRead0 = Off, 1 = On
BO2Outdoor Air Damper CommandOutdoor air damper outputRead0 = Open, 1 = Closed
BO3Heat 1 Command[Units with Primary Heat]Read0 = Off, 1 = On
BO4Inducer Command[Units with Gas as the Primary Heat]Read0 = Off, 1 = On
BO5Compressor 3 Command[Units with 3+ Compressors]Read0 = Off, 1 = On
BO6Compressor 4 Command[Units with 4+ Compressors]Read0 = Off, 1 = On
BO7Heat 2 Command[Units with Gas as the Primary Heat and is a Split Manifold Burner]Read0 = Off, 1 = On
BO8Heat 3 Command[Units with Gas as the Primary Heat and has Two Heaters]Read0 = Off, 1 = On
BO9Exhaust Damper Actuators[Units with Isolation Dampers]Read0 = Off, 1 = On
BO10Powered Exhaust Enable[Units with Isolation Dampers or has Dual Point Power]Read0 = Off, 1 = On
BO11Compressor 1 Command[Units with 1+ Compressors]Read0 = Off, 1 = On
BO12Compressor 2 Command[Units with 2+ Compressors]Read0 = Off, 1 = On
BO13Pre-Heat Enable[Units with Pre-Heat]Read0 = Off, 1 = On
BO14Condenser Fan Command[Units with Sound Attenuation Package or an Air Source Heat Pump]Read0 = Off, 1 = On
BO15ERV Command[Units with an ERV]Read0 = Off, 1 = On
BO16Circuit 1 Reversing Valve[Units that are Heat Pump]Read0 = Off, 1 = On
BO17Circuit 2 Reversing Valve[Units that are Heat Pump and Two Circuits]Read0 = Off, 1 = On
BVmin1Diagnostic: Supply Fan FailureLatching; cleared with Alarm Reset (BV 16)Read0 = Normal, 1 = Fail
BV2Diagnostic: Space Temperature Setpoint FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV3Diagnostic: OAD Proving SwitchLatching; cleared with Alarm Reset (BV 16)Read0 = Normal, 1 = Fail
BV4Defrost Mode[Units that are Heat Pump]Read0 = Disabled, 1 = Enabled
BV5HGRH Purge Mode[Units with Hot Gas Reheat]Read0 = Disabled, 1 = Enabled
BV6Diagnostic: Discharge Air Temperature Source FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV7Auxiliary Heating Mode[Units that are Heat Pump]Read0 = Disabled, 1 = Enabled
BV9Economizer Mode[Units with Modulating Dampers]Read0 = Disabled, 1 = Enabled
BV10Low Temp LockoutLatching; cleared with Alarm Reset (BV 16)Read0 = Normal, 1 = Fail
BV11Diagnostic: Space Temperature Source FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV12Diagnostic: Space Humidity Source FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV13Diagnostic: Outdoor Air Temperature Source FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV14Diagnostic: Outdoor Air Humidity Source FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV15High Temp LockoutLatching; cleared with Alarm Reset (BV 16)Read0 = Normal, 1 = Fail
BVmin16Alarm Reset1 = reset all diagnostics and lockoutsWrite1 = Reset
BVmin17System LOCKOUTLatching; cleared with Alarm Reset (BV 16)Read0 = Normal, 1 = Fail
BV18Return Air Damper OptionWrite0 = Not Installed, 1 = Installed
BV19Diagnostic: Space RH Source FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV20Space Temp/Humidity Sensor Installed[Units that are Space Control or Single Zone VAV]Write0 = Not Installed, 1 = Installed
BV21Heat Cool Mode ActiveRead0 = Heat, 1 = Cool
BV22Unoccupied Cooling Mode BASWrite0 = Disabled, 1 = Enabled
BV23Unoccupied Cooling ModeRead0 = Disabled, 1 = Enabled
BV25Compressor Stage 1 Request[Units with 1+ Compressors]Read0 = Off, 1 = On
BV26Cooling Lockout BAS[Units with DX Cooling]Write0 = Normal, 1 = Lockout
BV27Dehumidification Command[Units that are Space Control, Single Zone VAV, or Discharge Control]Read0 = Disabled, 1 = Enabled
BV28Thumbwheel InstalledWrite0 = Not Installed, 1 = Installed
BV29Compressor Stage 2 Request[Units with 2+ Compressors]Read0 = Off, 1 = On
BV30Compressor Stage 3 Request[Units with 3+ Compressors]Read0 = Off, 1 = On
BV31Compressor Stage 4 Request[Units with 4 Compressors]Read0 = Off, 1 = On
BV32Diagnostic: ERV Leaving Air Conditions FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV33Pre-Purge Status[Units with Gas as the Primary Heat]Read0 = Disabled, 1 = Enabled
BV34Diagnostic: Evap Temp Source FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV35Y1 Space Lockout[Units that are Space Control or Single Zone VAV]Read0 = Disabled, 1 = Enabled
BV36Diagnostic: Duct Static Pressure FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV37Unoccupied Dehumid Mode BASWrite0 = Disabled, 1 = Enabled
BV38Unoccupied Heating Mode BASWrite0 = Disabled, 1 = Enabled
BV39Unoccupied Heating ModeRead0 = Disabled, 1 = Enabled
BV40Unoccupied Dehumid ModeRead0 = Disabled, 1 = Enabled
BV42Diagnostic: Heat FailureAuto-reset diagnosticRead0 = Normal, 1 = Fail
BV43Ventilation[Units that are Space Control, Single Zone VAV, or Discharge Control]Read0 = Disabled, 1 = Enabled
BV45Economizer Control TypeWrite0 = Dry Bulb, 1 = Dry Bulb and Enthalpy
MVmin1Occupancy RequestOccupancy commandWrite1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MVmin2Occupancy StatusOccupancy in effectRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Unknown
MV4Heat Cool Mode StatusRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off
MV7Compressor Stage 3 Status[Units with 3+ Compressors]Read1 = Off, 2 = On, 3 = Not Present
MV8Compressor Stage 4 Status[Units with 4 Compressors]Read1 = Off, 2 = On, 3 = Not Present
MV9Heat TypeRead1 = No Heat, 2 = Indirect Fired Gas Heat, 3 = Electric Heat, 4 = Other, 5 = Direct Fired Gas Heat, 6 = Hot Water/Steam
MV13Program Control TypeConfigured control program typeRead1 = Space Control, 2 = Discharge Control, 3 = Single Zone VAV, 4 = Multi Zone VAV
MV16Dehumidification System StatusRead1 = Off, 2 = On, 3 = Not Present
MV21Compressor Stage 1 Status[Units with 1+ Compressors]Read1 = Off, 2 = On, 3 = Not Present
MV22Compressor Stage 2 Status[Units with 2+ Compressors]Read1 = Off, 2 = On, 3 = Not Present
Object ID lookup: Trane Tracer UC600 Packaged Outdoor Air Unit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Tracer UC600 Packaged Outdoor Air Unit and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Tracer UC600 Packaged Outdoor Air Unit

How many BACnet points does the Trane Tracer UC600 Packaged Outdoor Air Unit have?

This list has 175 BACnet objects: 23 analog inputs, 9 analog outputs, 66 analog values, 9 binary inputs, 17 binary outputs, 41 binary values, 10 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Tracer UC600 Packaged Outdoor Air Unit BACnet points are writable?

58 of the 175 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Tracer UC600 Packaged Outdoor Air Unit BACnet documentation?

The source is Integration Guide: Tracer UC600 Programmable Controller, Packaged Outdoor Air Unit (BAS-SVP18E-EN), revision July 2022, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP18E-EN_07012022.pdf.

What are the minimum BACnet points to integrate the Trane Tracer UC600 Packaged Outdoor Air Unit?

Start with MV 1 Occupancy Request (Occupancy command (1 = Occupied, 2 = Unoccupied, 5 = Auto)); AV 25 Space Temperature Setpoint BAS (Space setpoint (space control / single zone VAV)); AV 30 Discharge Air Cooling Setpoint (Discharge air cooling setpoint (discharge control)); AV 32 Discharge Air Heating Setpoint (Discharge air heating setpoint (discharge control)); BV 16 Alarm Reset (1 = reset diagnostics and lockouts; return to 0 after); MV 2 Occupancy Status (Confirms the occupancy in effect); BI 1 Supply Fan Status (Supply fan proof (0 = On, 1 = Off)); AV 5 Discharge Air Temperature Active (Discharge air temperature in use); BV 17 System LOCKOUT (Unit locked out; needs Alarm Reset); BV 1 Diagnostic: Supply Fan Failure (Supply fan failure (latching)).

How do I enable BMS control of the Trane Tracer UC600 Packaged Outdoor Air Unit?

No enable point is described. The BAS controls the unit by writing values and putting points In or Out of Service. MV 1 Occupancy Request sets occupancy.

Does the Trane Tracer UC600 Packaged Outdoor Air Unit need a BACnet heartbeat or have a communication timeout?

The guide says the BAS must routinely refresh BAS-supplied sensor values to protect against a communication loss, but gives no timeout value.

Can the BMS supply sensor values to the Trane Tracer UC600 Packaged Outdoor Air Unit?

Space Temperature BAS (AV 20), Space RH BAS (AV 8), Outdoor Air Temperature BAS (AV 75), Outdoor Air Humidity BAS (AV 81) and Discharge Air Temperature BAS (AV 4) are Out of Service from the factory; put them In Service to use them and keep rewriting them. The matching '... Active' AVs show the value in use.

How do I check these points on the real Tracer UC600 Packaged Outdoor Air Unit?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Integration Guide: Tracer UC600 Programmable Controller, Packaged Outdoor Air Unit · BAS-SVP18E-EN · rev. July 2022. Object names, instances and units are reproduced as published; descriptions are our own.