- ReliaTel BCI-R - touch-screen zone sensor points
Rooftop unit controller (zone sensor interaction subset) · BACnet points list
Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet points list
Updated 6 November 2026
This short list shows which ReliaTel BCI-R objects the Trane commercial touch-screen programmable zone sensor reads and overrides on single-zone packaged units. It covers space temperature, setpoints and offset, heat/cool mode request and status, occupancy request, fan mode, economizer enable setpoints and the BAS control flag. The sensor and BCI-R talk BACnet MS/TP.
This page lists 14 BACnet objects for the Trane ReliaTel BCI-R - touch-screen zone sensor points — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- ReliaTel BCI-R - touch-screen zone sensor points
- Equipment
- Rooftop unit controller (zone sensor interaction subset)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 14 (11 writable)
- Transport
- BACnet MS/TP
- Firmware
- RTRM 19.2 or later, BCI-R 6.0 or later
- Also known as
- ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane ReliaTel BCI-R - touch-screen zone sensor points
Use the BMS mainly for monitoring and alarms when the touch-screen sensor runs the unit. The sensor owns occupancy, mode, fan and setpoint commands; read mode status and fan speed, and only write Space Temperature BAS (priority 5 or higher) if the BMS must supply space temperature.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MO 7 | Occupancy Request | Occupancy request (1=Occ, 2=Unocc, 3=Bypass, 4=Standby) | Write |
| MO 8 | Heat Cool Mode Request BAS | Heat/cool mode request (1=Auto) | Write |
| BO 8 | Supply Fan Configuration Command | Fan mode: Inactive = Auto, Active = On | Write |
| AO 2 | Space Temperature Setpoint BAS | Space temperature setpoint | Write |
| AO 11 | Space Temperature BAS | Space temperature in use by the unit | Write |
| MI 19 | Heat Cool Mode Status BAS | Actual heat/cool mode | Read |
| AI 7 | Supply Fan Speed Status | Supply fan speed, % | Read |
Enable & remote start
BO 1 System Control Command defaults to Inactive (standalone); the sensor writes Active (BAS control) at power-up. The sensor then holds the occupancy, mode, fan and setpoint objects Out_Of_Service and writes them at priority 7. The guide recommends leaving control with the sensor.
Sensors & values from the BMS
Space Temperature BAS normally comes from the sensor; a BMS can command it at priority 5 or higher (priority 6 is reserved for minimum on/off). Space Temperature Local is the unit's hard-wired sensor.
Network setup
- The sensor talks BACnet MS/TP only; default baud 76800 (leave the default).
- Sensor and unit controller should share an MS/TP link where possible to reduce communication loss.
- Trane best practice device ID: MS/TP network number followed by the MAC address (e.g. network 11, MAC 001 = 11001).
- Needs ReliaTel RTRM software 19.2 or later and BCI-R software 6.0 or later.
Watch out for
- The sensor holds these points Out_Of_Service and writes them at priority 7; a BMS writing the same points will fight the sensor.
- BO 1 does not need periodic refresh; the sensor writes it once at power-up.
Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AOmin | 11 | Space Temperature BAS | Space temperature sent by the touch-screen sensor, -40-150 °F | °F/°C | Write | |
| AI | 87 | Space Temperature Local (TempRemSrc) | Hard-wired space temperature at the unit, -40-200 °F | °F/°C | Read | |
| AO | 31 | Unoccupied Cooling Setpoint | Unoccupied cooling setpoint, 50-90 °F (sensor default 85 °F) | °F/°C | Write | |
| AO | 32 | Unoccupied Heating Setpoint | Unoccupied heating setpoint, 50-90 °F (sensor default 60 °F) | °F/°C | Write | |
| AOmin | 2 | Space Temperature Setpoint BAS | Space setpoint from the sensor, 50-90 °F (default 72.5 °F) | °F/°C | Write | |
| AO | 30 | Occupied Offset | Heat/cool setpoint offset, 1-5 °F (default 1.5 °F) | °F/°C | Write | |
| AImin | 7 | Supply Fan Speed Status | Supply fan speed, 0-100 % | % | Read | |
| MOmin | 8 | Heat Cool Mode Request BAS | Heat/cool mode request written by the sensor (default Auto) | Write | 1=Auto, 2=Heat, 3=Morning Warm-up, 4=Cool, 5=Night Purge, 6=Precool, 7=Off, 8=Test, 9=Emergency Heat, 10=Fan Only, 11=Free Cool, 12=Ice Making, 13=Max Heat, 14=Economy Mode, 15=Dehumidifying, 16=Calibrate | |
| MImin | 19 | Heat Cool Mode Status BAS | Actual heat/cool mode of the unit | Read | 1=Auto, 2=Heat, 3=Morning Warm-up, 4=Cool, 5=Night Purge, 6=Precool, 7=Off, 8=Test, 9=Emergency Heat, 10=Fan Only, 11=Free Cool, 12=Ice Making, 13=Max Heat, 14=Economy Mode, 15=Dehumidifying, 16=Calibrate | |
| MOmin | 7 | Occupancy Request | Occupancy request written by the sensor (default Occupied) | Write | 1=Occupied, 2=Unoccupied, 3=Occupied Bypass, 4=Occupied Standby | |
| BOmin | 8 | Supply Fan Configuration Command | Fan mode: auto or continuous on (default Auto) | Write | Inactive=Auto, Active=On | |
| AO | 41 | Economizing Temperature Enable Setpoint | Economizer dry-bulb enable setpoint, 50-140 °F (default disabled, 63 °F) | °F/°C | Write | |
| AO | 42 | Economizing Enthalpy Enable Setpoint | Economizer enthalpy enable setpoint, 19-28 (default disabled, 22) | BTU/lb | Write | |
| BO | 1 | System Control Command | Standalone or BAS control; sensor writes Active at power-up | Write | FALSE=Standalone Control, TRUE=BAS Control |
No points match these filters.
Object ID lookup: Trane ReliaTel BCI-R point IDs by name
AO11Space Temperature BASAI87Space Temperature Local (TempRemSrc)AO31Unoccupied Cooling SetpointAO32Unoccupied Heating SetpointAO2Space Temperature Setpoint BASAO30Occupied OffsetAI7Supply Fan Speed StatusMO8Heat Cool Mode Request BASMI19Heat Cool Mode Status BASMO7Occupancy RequestBO8Supply Fan Configuration CommandAO41Economizing Temperature Enable SetpointAO42Economizing Enthalpy Enable SetpointBO1System Control Command
Integration notes
- This is a SUBSET: only the BCI-R objects the touch-screen zone sensor uses (Table 4 of BAS-SVP080A, p15). The full BCI-R list is a separate entry (BCI-R ReliaTel).
- Access is inferred: the doc has no read/write column. Output and multistate-output objects the sensor writes are shown as W; inputs as R.
- The sensor sets Out_Of_Service on most of these objects at power-up and writes them at priority 7. AO 41/AO 42 Out_Of_Service is set from the sensor setup menu (In Use / Not Used) and should be written only once, not refreshed.
- AO 30 on ReliaTel is the standby offset (occupied offset plus shed offset, max 10 °F); the guide uses it because the BCI-R occupied offset object is limited to 5 °F.
- Matching sensor objects (AV 100, AV 44, AV 43, MV 140, MV 16, MV 112, MI 33, MV 17, AV 260, AV 261) belong to the sensor itself. Multiple-zone units (RTAM board) are not supported.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ReliaTel BCI-R - touch-screen zone sensor points and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane ReliaTel BCI-R - touch-screen zone sensor points
How many BACnet points does the Trane ReliaTel BCI-R - touch-screen zone sensor points have?
This list has 14 BACnet objects: 2 analog inputs, 7 analog outputs, 2 binary outputs, 1 multi-state input, 2 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet points are writable?
11 of the 14 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet documentation?
The source is Touch Screen Programmable Zone Sensor Integration Guide (Tracer UC400-B, Symbio 400-B/500/700/800, ReliaTel) (BAS-SVP080A-EN), revision 2023-08, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP080A-EN_08302023.pdf.
What are the minimum BACnet points to integrate the Trane ReliaTel BCI-R - touch-screen zone sensor points?
Start with MO 7 Occupancy Request (Occupancy request (1=Occ, 2=Unocc, 3=Bypass, 4=Standby)); MO 8 Heat Cool Mode Request BAS (Heat/cool mode request (1=Auto)); BO 8 Supply Fan Configuration Command (Fan mode: Inactive = Auto, Active = On); AO 2 Space Temperature Setpoint BAS (Space temperature setpoint); AO 11 Space Temperature BAS (Space temperature in use by the unit); MI 19 Heat Cool Mode Status BAS (Actual heat/cool mode); AI 7 Supply Fan Speed Status (Supply fan speed, %).
How do I enable BMS control of the Trane ReliaTel BCI-R - touch-screen zone sensor points?
BO 1 System Control Command defaults to Inactive (standalone); the sensor writes Active (BAS control) at power-up. The sensor then holds the occupancy, mode, fan and setpoint objects Out_Of_Service and writes them at priority 7. The guide recommends leaving control with the sensor.
Can the BMS supply sensor values to the Trane ReliaTel BCI-R - touch-screen zone sensor points?
Space Temperature BAS normally comes from the sensor; a BMS can command it at priority 5 or higher (priority 6 is reserved for minimum on/off). Space Temperature Local is the unit's hard-wired sensor.
How do I check these points on the real ReliaTel BCI-R - touch-screen zone sensor points?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Touch Screen Programmable Zone Sensor Integration Guide (Tracer UC400-B, Symbio 400-B/500/700/800, ReliaTel) · BAS-SVP080A-EN · rev. 2023-08. Object names, instances and units are reproduced as published; descriptions are our own.