Rooftop unit controller (zone sensor interaction subset) · BACnet points list

Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet points list

Updated 6 November 2026

Short answer

This short list shows which ReliaTel BCI-R objects the Trane commercial touch-screen programmable zone sensor reads and overrides on single-zone packaged units. It covers space temperature, setpoints and offset, heat/cool mode request and status, occupancy request, fan mode, economizer enable setpoints and the BAS control flag. The sensor and BCI-R talk BACnet MS/TP.

This page lists 14 BACnet objects for the Trane ReliaTel BCI-R - touch-screen zone sensor points — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
ReliaTel BCI-R - touch-screen zone sensor points
Equipment
Rooftop unit controller (zone sensor interaction subset)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
14 (11 writable)
Transport
BACnet MS/TP
Firmware
RTRM 19.2 or later, BCI-R 6.0 or later
Also known as
ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A
Source document
Touch Screen Programmable Zone Sensor Integration Guide (Tracer UC400-B, Symbio 400-B/500/700/800, ReliaTel) · BAS-SVP080A-EN · rev. 2023-08
Download CSV 14 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.

BMS integration notes: Trane ReliaTel BCI-R - touch-screen zone sensor points

Integration in brief

Use the BMS mainly for monitoring and alarms when the touch-screen sensor runs the unit. The sensor owns occupancy, mode, fan and setpoint commands; read mode status and fan speed, and only write Space Temperature BAS (priority 5 or higher) if the BMS must supply space temperature.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 7Occupancy RequestOccupancy request (1=Occ, 2=Unocc, 3=Bypass, 4=Standby)Write
MO 8Heat Cool Mode Request BASHeat/cool mode request (1=Auto)Write
BO 8Supply Fan Configuration CommandFan mode: Inactive = Auto, Active = OnWrite
AO 2Space Temperature Setpoint BASSpace temperature setpointWrite
AO 11Space Temperature BASSpace temperature in use by the unitWrite
MI 19Heat Cool Mode Status BASActual heat/cool modeRead
AI 7Supply Fan Speed StatusSupply fan speed, %Read

Enable & remote start

BO 1 System Control Command defaults to Inactive (standalone); the sensor writes Active (BAS control) at power-up. The sensor then holds the occupancy, mode, fan and setpoint objects Out_Of_Service and writes them at priority 7. The guide recommends leaving control with the sensor.

Sensors & values from the BMS

Space Temperature BAS normally comes from the sensor; a BMS can command it at priority 5 or higher (priority 6 is reserved for minimum on/off). Space Temperature Local is the unit's hard-wired sensor.

Network setup

Watch out for

Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

14 of 14 shown
Type
Binary
Access
Show
Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet Points List
DescriptionStates
AOmin11Space Temperature BASSpace temperature sent by the touch-screen sensor, -40-150 °F°F/°CWrite
AI87Space Temperature Local (TempRemSrc)Hard-wired space temperature at the unit, -40-200 °F°F/°CRead
AO31Unoccupied Cooling SetpointUnoccupied cooling setpoint, 50-90 °F (sensor default 85 °F)°F/°CWrite
AO32Unoccupied Heating SetpointUnoccupied heating setpoint, 50-90 °F (sensor default 60 °F)°F/°CWrite
AOmin2Space Temperature Setpoint BASSpace setpoint from the sensor, 50-90 °F (default 72.5 °F)°F/°CWrite
AO30Occupied OffsetHeat/cool setpoint offset, 1-5 °F (default 1.5 °F)°F/°CWrite
AImin7Supply Fan Speed StatusSupply fan speed, 0-100 %%Read
MOmin8Heat Cool Mode Request BASHeat/cool mode request written by the sensor (default Auto)Write1=Auto, 2=Heat, 3=Morning Warm-up, 4=Cool, 5=Night Purge, 6=Precool, 7=Off, 8=Test, 9=Emergency Heat, 10=Fan Only, 11=Free Cool, 12=Ice Making, 13=Max Heat, 14=Economy Mode, 15=Dehumidifying, 16=Calibrate
MImin19Heat Cool Mode Status BASActual heat/cool mode of the unitRead1=Auto, 2=Heat, 3=Morning Warm-up, 4=Cool, 5=Night Purge, 6=Precool, 7=Off, 8=Test, 9=Emergency Heat, 10=Fan Only, 11=Free Cool, 12=Ice Making, 13=Max Heat, 14=Economy Mode, 15=Dehumidifying, 16=Calibrate
MOmin7Occupancy RequestOccupancy request written by the sensor (default Occupied)Write1=Occupied, 2=Unoccupied, 3=Occupied Bypass, 4=Occupied Standby
BOmin8Supply Fan Configuration CommandFan mode: auto or continuous on (default Auto)WriteInactive=Auto, Active=On
AO41Economizing Temperature Enable SetpointEconomizer dry-bulb enable setpoint, 50-140 °F (default disabled, 63 °F)°F/°CWrite
AO42Economizing Enthalpy Enable SetpointEconomizer enthalpy enable setpoint, 19-28 (default disabled, 22)BTU/lbWrite
BO1System Control CommandStandalone or BAS control; sensor writes Active at power-upWriteFALSE=Standalone Control, TRUE=BAS Control
Object ID lookup: Trane ReliaTel BCI-R point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ReliaTel BCI-R - touch-screen zone sensor points and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane ReliaTel BCI-R - touch-screen zone sensor points

How many BACnet points does the Trane ReliaTel BCI-R - touch-screen zone sensor points have?

This list has 14 BACnet objects: 2 analog inputs, 7 analog outputs, 2 binary outputs, 1 multi-state input, 2 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet points are writable?

11 of the 14 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane ReliaTel BCI-R - touch-screen zone sensor points BACnet documentation?

The source is Touch Screen Programmable Zone Sensor Integration Guide (Tracer UC400-B, Symbio 400-B/500/700/800, ReliaTel) (BAS-SVP080A-EN), revision 2023-08, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP080A-EN_08302023.pdf.

What are the minimum BACnet points to integrate the Trane ReliaTel BCI-R - touch-screen zone sensor points?

Start with MO 7 Occupancy Request (Occupancy request (1=Occ, 2=Unocc, 3=Bypass, 4=Standby)); MO 8 Heat Cool Mode Request BAS (Heat/cool mode request (1=Auto)); BO 8 Supply Fan Configuration Command (Fan mode: Inactive = Auto, Active = On); AO 2 Space Temperature Setpoint BAS (Space temperature setpoint); AO 11 Space Temperature BAS (Space temperature in use by the unit); MI 19 Heat Cool Mode Status BAS (Actual heat/cool mode); AI 7 Supply Fan Speed Status (Supply fan speed, %).

How do I enable BMS control of the Trane ReliaTel BCI-R - touch-screen zone sensor points?

BO 1 System Control Command defaults to Inactive (standalone); the sensor writes Active (BAS control) at power-up. The sensor then holds the occupancy, mode, fan and setpoint objects Out_Of_Service and writes them at priority 7. The guide recommends leaving control with the sensor.

Can the BMS supply sensor values to the Trane ReliaTel BCI-R - touch-screen zone sensor points?

Space Temperature BAS normally comes from the sensor; a BMS can command it at priority 5 or higher (priority 6 is reserved for minimum on/off). Space Temperature Local is the unit's hard-wired sensor.

How do I check these points on the real ReliaTel BCI-R - touch-screen zone sensor points?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Touch Screen Programmable Zone Sensor Integration Guide (Tracer UC400-B, Symbio 400-B/500/700/800, ReliaTel) · BAS-SVP080A-EN · rev. 2023-08. Object names, instances and units are reproduced as published; descriptions are our own.