Rooftop unit controller · BACnet points list

Trane Symbio 700 Precedent / Axiom BACnet points list

Updated 28 October 2026

Short answer

Symbio 700 is the factory unit controller on Precedent rooftops and Axiom rooftop water-source heat pumps. It exposes several hundred BACnet objects with 5-digit instances (AI-10101, AV-11403...) grouped by object type. Most writable objects are BAS or Setpoint values feeding Trane's arbitration logic, and several have heartbeat timeouts, so a BAS must keep refreshing them.

This page lists 639 BACnet objects for the Trane Symbio 700 Precedent / Axiom — 232 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 700 Precedent / Axiom
Equipment
Rooftop unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
639 (232 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
V9.00.0007
Also known as
Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001
Source document
Symbio 700 Integration Points List BACnet/Modbus - Precedent, Axiom Rooftop WSHP · BAS-PTS001C-EN · rev. 08/12/2026
Download CSV 639 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 700 Precedent / Axiom

Integration in brief

Leave MV 11100 Arbitration Method Request at 'Enable External/BAS Control'. Then schedule the unit with MV 10106 Occupancy Request and send setpoints to the commandable setpoint BAS points at a priority above 14. If the BMS supplies sensor values such as space temperature, rewrite the '... BAS' points at least every 15 minutes, or the controller drops back to its own sensors.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10106Occupancy RequestOccupancy command (occupied/unoccupied/standby)Write
BV 11113Unit Stop CommandBMS stop/auto of the whole unitWrite
AV 10159Occupied Cooling Setpoint BASOccupied cooling setpoint (dual-setpoint units)Write
AV 10160Occupied Heating Setpoint BASOccupied heating setpoint (dual-setpoint units)Write
AV 10127Space Temperature Setpoint BASSingle-setpoint alternative to the two setpoints aboveWrite
MI 10101Heat Cool Mode StatusCurrent heat/cool operating modeRead
MV 11123Occupancy StatusConfirms the occupancy the unit is running inRead
BI 10226Supply Fan StatusSupply fan on/off statusRead
AV 11178Space Temperature ActiveSpace temperature the unit is actually controlling toRead
BV 11100Alarm Indicator StatusUnit alarm output; on when the controller is in alarmRead

Enable & remote start

MV 11100 Arbitration Method Request picks the control type. 'Enable External/BAS Control' is the factory default: the controller weighs BAS, Air-Fi and wired sources and uses the BAS value while it is valid. 'Standalone Control' ignores all BAS input. BV 11113 Unit Stop Command (Auto/Stop) stops the unit from the BMS.

Heartbeat & communication loss

The sensor BAS points (space temp, OA temp, humidity, CO2, return air) have a 900 s heartbeat in the points list. Per the integration guide, a BAS sensor or setpoint value that is not rewritten at least every 15 minutes fails. Its priority-12 entry then drops out of the Arbitrator and the controller falls back to the next source (Air-Fi, wired, then default). BV 10113 Occupancy Input BAS has the same 15-minute heartbeat; MV 10106 Occupancy Request has none.

Sensors & values from the BMS

Write the value to the matching '... BAS' AV (e.g. AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS) and keep refreshing it. It shows on the '... Arbitrator' object at priority 12, above Air-Fi (14) and wired (15). The '... Active' object reports the value in use. Space setpoints go to AV 10127 Space Temperature Setpoint BAS (single setpoint) or AV 10159/10160 Occupied Cooling/Heating Setpoint BAS (dual setpoint).

Network setup

Watch out for

Trane Symbio 700 Precedent / Axiom BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

639 of 639 shown
Type
Access
Show
Trane Symbio 700 Precedent / Axiom BACnet Points List
DescriptionStates
AI10101Cooling Capacity StatusActual operating unit cooling capacity, in percent%Read
AI10102Heating Capacity Primary StatusUnit (primary) heating capacity, in percent%Read
AI10104Outdoor Air Relative Humidity LocalOA humidity value from sensor connected to the controller%Read
AI10110Return Air Humidity LocalReturn air humidity value from sensor connected to the controller%Read
AI10111Outdoor Air Damper PositionOA Damper Actuator feedback signal%Read
AI10116Space Humidity ActiveActive space relative humidity being used by the controller%Read
AI10117Outdoor Air Dew PointThe outdoor air dewpoint value being utilized by the unit°FRead
AI10118Outdoor Air Temperature ActiveActive OA temperature currently being used by the controller°FRead
AI10120Outdoor Air Humidity ActiveActive outdoor air humidity value used by the controller%Read
AI10124Discharge Air Temperature LocalDischarge air temperature value from a sensor connected to the controller°FRead
AI10126Return Air Temperature InputActual return air temperature being used by the controller°FRead
AI10155Duct Static Pressure LocalDuct static pressure value from a sensor connected to the controllerIn. of waterRead
AI10156Outdoor Air Temperature LocalOA temp value from a sensor connected to the controller°FRead
AI10182Duct Static Pressure ActiveDuct static pressure active value for communication to SC graphicsIn. of waterRead
AI10218Space Temperature InputSpace temp from a wired sensor°FRead
AI10226Space Dew PointCalculated Space Dewpoint°FRead
AI11100Coil Temperature Sensor 1Outdoor Coil Temperature Sensor for Circuit 1 on HP units°FRead
AI11103Space CO2 Concentration InputSpace CO2 concentration from a sensor hardwired to the controllerPPMRead
AI11104Space Humidity InputSpace relative humidity from a sensor wired to the controller%Read
AI11106Supply Fan Speed Command StatusUnit commanded supply fan speed output%Read
AI11109Modulating Heat Command StatusUnit commanded modulating heat output%Read
AI11111Outdoor Air Damper CommandUnit commanded outside air damper position%Read
AI11132On-Board I/O Firmware Major VersionSoftware Major Version for On-Board I/O ModuleRead
AI11133On-Board I/O Firmware Minor VersionOn-Board I/O Module Software build numberRead
AI11134Indoor Options Module Firmware Major VersionSoftware Major Version for Indoor Options ModuleRead
AI11135Indoor Options Module Firmware Minor VersionIndoor Options Module Software build numberRead
AI11136Fresh Air Options Module Firmware Major VersionSoftware Major Version for Fresh Air Options ModuleRead
AI11137Fresh Air Options Module Firmware Minor VersionFresh Air Options Module Software build numberRead
AI11140Customer Options Module Firmware Major VersionSoftware Major Version for Customer Connection Options ModuleRead
AI11141Customer Options Module Firmware Minor VersionCustomer Options Module Software build numberRead
AI11142IGN Module 1 Firmware Major VersionSoftware Major Version for Gas Heat Ignition Module 1Read
AI11143IGN Module 1 Firmware Minor VersionSoftware Minor Version for Gas Heat Ignition Module 1Read
AI11148Remote Minimum PositionHardwired remote minimum position for OA damper control%Read
AI11149Return Air Temperature ActiveReturn Air Temperature being used for control°FRead
AI11150Sensor Battery Status Air-FiStatus percentage of connected AirFi sensor(s)%Read
AI11151Space CO2 Concentration Air- FiSpace CO2 concentration from a wireless sensor connected to the controllerPPMRead
AI11152Space Humidity Air-FiSpace relative humidity from a connected wireless sensor%Read
AI11154Space Temperature Air-FiSpace temp from a connected wireless (AirFi) sensor°FRead
AI11155Space Temperature Cooling Setpoint Air-Fi(occupied) cooling setpoint from the connected wireless space sensor°FRead
AI11156Space Temperature Heating Setpoint Air-Fi(occupied) heating setpoint from the connected wireless space sensor°FRead
AI11157Space Temperature Setpoint Air-FiSpace Temperature Setpoint from a connected wireless sensor°FRead
AI11159Space Temperature Cooling Setpoint Input(occupied) cooling setpoint from the connected wired space sensor°FRead
AI11160Space Temperature Heating Setpoint Input(occupied) heating setpoint from the connected wired space sensor°FRead
AI11161Space Temperature Setpoint InputSpace Temperature Setpoint from a connected wired sensor°FRead
AI11164Reheat Valve 1 Step StatusReheat Valve 1 Status in steps from Stepper Motor ModuleRead
AI11166Evaporator Entering Refrigerant Temperature°FRead
AI11167Stepper Motor Module Firmware Major VersionSoftware Major Version for Stepper Motor ModuleRead
AI11168Stepper Motor Module Firmware Minor VersionStepper Motor Module Software build numberRead
AI11169Saturated Discharge TemperatureSaturated Discharge Temperature sensor used in Ultra High Efficiency°FRead
AI11170Supply Fan Entering Air TemperatureAir temp entering the supply fan°FRead
AI11171Entering Water Temperature ActiveActive Entering Water temperature currently being used by the controller°FRead
AI11172Entering Water Temperature LocalEntering Water temperature value from a sensor connected to the controller°FRead
AI11173Outdoor Air Damper FeedbackOA Damper Actuator feedback signal%Read
AV10103Outdoor Air Temperature ArbitratorOA temp determined by arbitration°FWrite
AV10104Outdoor Air Humidity ArbitratorActual outdoor air humidity being used by the controller%Write
AV10106Space Temperature ArbitratorSpace temp determined by arbitration°FWrite
AV10108Space CO2 Concentration ArbitratorSpace CO2 concentration being used by the controllerPPMWrite
AV10109Space Humidity ArbitratorSpace relative humidity, determined by the arbitration%Write
AV10113Outdoor Air Temperature BASSend the outdoor air temperature sensor value°FWrite
AV10114Space Temperature BASSend the space temperature value°FWrite
AV10116Outdoor Air Humidity BASSend the outdoor air humidity sensor value%Write
AV10118Space CO2 Concentration BASSend the space CO2 concentration valuePPMWrite
AV10119Space Humidity BASSend the space relative humidity value%Write
AV10121Discharge Air Cooling Setpoint BASRequest the discharge air temp cooling setpoint value°FCommand
AV10122Discharge Air Heating Setpoint BASRequest the discharge air temperature heating setpoint value°FCommand
AV10123Unoccupied Cooling SetpointDefine the cooling temp setpoint used for control in unoccupied mode°FWrite
AV10124Unoccupied Heating SetpointDefine the heating temp setpoint used for control in unoccupied mode°FWrite
AVmin10127Space Temperature Setpoint BASBAS-supplied space temperature setpoint value°FWrite
AV10130Occupied OffsetDifference between the occupied cool and heat setpts∆°FWrite
AV10134Discharge Air Reheat Setpoint BASRequest the discharge air temperature reheat setpoint value, for dehumidification control°FCommand
AV10138Filter Runtime Hours SetpointThe setpoint value used by the filter run hours calculationCommand
AV10139Cooling Capacity EnableLimit the cooling capacity of the unit; 0% = no cooling possible%Command
AV10140Heat Primary Enable BASDemand limit the heating capacity; 0% = No Heating Possible%Command
AV10141Morning Warmup Setpoint BASDefines the space temp below which MWU is enabled°FCommand
AV10142Occupied Standby OffsetDifference between the occupied standby cool and heat setpts∆°FWrite
AV10143Duct Static Pressure Setpoint BASRequest the duct static pressure setpoint valueIn. of waterCommand
AV10144Economizer Minimum Position Setpoint BASRequest the ecominizer minimum position setpoint%Command
AV10149Daytime Warmup Setpoint BASDefines the space temp below which daytime warmup will be enabled°FCommand
AV10150Economizer Outdoor Air Enable Setpoint BASTemperature setpoint below which economizing can be used°FCommand
AV10154Space Cooling Setpoint High Limit BAS°FWrite
AV10155Space Cooling Setpoint Low Limit BAS°FWrite
AV10157Space Heating Setpoint High Limit BAS°FWrite
AV10158Space Heating Setpoint Low Limit BAS°FWrite
AVmin10159Occupied Cooling Setpoint BASDefine the occupied cooling setpt°FWrite
AVmin10160Occupied Heating Setpoint BASDefine the occupied heating setpt°FWrite
AV10161Occupied Standby Cooling Setpoint BASDefines the occupied standby cooling setpt when both heat/cool setpoints are provided°FCommand
AV10162Occupied Standby Heating Setpoint BASDefines the occupied standby heating setpt when both heat/cool setpoints are provided°FCommand
AV10167Discharge Air Temperature Minimum Cool LimitDefine the discharge air temperature minimum cool limit°FCommand
AV10168Relief Enable Position SetpointThe OA damper position above which the Relief sequence is enabled%Command
AV10169Occupied Bypass TimeConfigure the occupied bypass time (occupancy override)Write
AV10170Economizer Outdoor Air Enthalpy Enable Setpoint BASDetermine the outdoor air enthalpy below which economizing is enabledBTUs/poundCommand
AV10175Space CO2 High LimitDefine the CO2 high limit, for ventilation purposesPPMCommand
AV10176Space CO2 Low LimitDefine the CO2 low limitPPMCommand
AV10214Space Dehumidification Unoccupied Setpoint ActiveActive value for Space Dehumidification Setpoint BAS point being used for control%Read
AV10228Space Dew Point Unoccupied Setpoint ActiveUnoccupied Space Dew Point Setpoint actively being used for dehumidification control°FRead
AV10281Discharge Air Temperature Setpoint ActiveDischarge air temp setpoint actively being used for control°FRead
AV11103Return Air Humidity BASBAS Source for Return Air Humidity%Write
AV11108Cabinet StyleCabinet style of the unitRead
AV11110Supply Fan Speed CommandRemote supply fan speed request%Command
AV11112Cooling Capacity Setpoint BASRemote cooling capacity request%Command
AV11113Space Dehumidification Setpoint Offset BAS - ActiveThe active value for the offset applied to the Space Dehumidification Setpoint%Read
AV11115Exhaust Or Return Fan TypeIdentifies the product exhaust or return fan typeRead
AV11116Filter Runtime HoursNumber of hours air has flowed through the filterRead
AV11117Outdoor Air Enthalpy ActiveThe outdoor air enthalpy value being utilized by the unitBTUs/poundRead
AV11118Return Air Temperature ArbitratorArbitrator for Return Air Temperature°FWrite
AV11119Return Air Temperature BASBAS source for Return Air Temperature°FWrite
AV11120Heating Demand Limit Capacity Enable Setpoint%Command
AV11121Discharge Air Temperature Maximum Cool LimitMaximum discharge air temperature allowed during space temperature cooling mode of operation°FCommand
AV11122Run Time - Condenser Fan 1 (Hours)Condenser Fan 1 RuntimeRead
AV11123Run Time - Condenser Fan 2 (Hours)Condenser Fan 2 RuntimeRead
AV11124Run Time - Relief Fan (Hours)Relief Fan RuntimeRead
AV11125Run Time - Electric Heat Stage 1 (Hours)Electric Heat Stage 1 RuntimeRead
AV11126Run Time - Electric Heat Stage 2 (Hours)Electric Heat Stage 2 RuntimeRead
AV11127Run Time - Supply Fan (Hours)Supply Fan RuntimeRead
AV11128Space Temp Cooling Setpoint StatusSpace cooling setpoint, being used by the controller°FRead
AV11129Space Temp Heating Setpoint StatusSpace heating setpoint, being used by the controller°FRead
AV11130Design Minimum OA Damper Position at Full Fan Capacity%Command
AV11131Design Minimum OA Damper Position at Mid Fan Capacity%Command
AV11132Design Minimum OA Damper Position at Min Fan Capacity%Command
AV11133DCV Minimum OA Damper Position at Full Fan Capacity%Command
AV11134DCV Minimum OA Damper Position at Mid Fan Capacity%Command
AV11135DCV Minimum OA Damper Position at Min Fan Capacity%Command
AV11136Space Dehumidification Setpoint BAS - ActiveThe active value for the Space Dehumidification Setpoint for Relative Humidity control%Read
AV11137Discharge Air Heating Setpoint High LimitDischarge Air Heating Setpoint High Limit (deg F)°FCommand
AV11138Discharge Air Heating Setpoint (Target)°FCommand
AV11140Discharge Air Cooling Setpoint (Target)°FCommand
AV11147Economizer Dry Bulb Enable OffsetOutdoor air temperature offset below dry bulb economizer enable setpoint∆°FWrite
AV11148Duct Static Pressure P-Gain (%/IWC)Proportional gain for fan speed on duct static pressure control (%/IWC)%Write
AV11149Duct Static Pressure Deadband BASSupply Air Pressure Setpoint DeadbandIn. of waterCommand
AV11150Cooling Reset Start TempDischarge air cooling reset start temperature°FWrite
AV11151Cooling Reset End TempDischarge air cooling reset end temperature°FWrite
AV11152Cooling Reset AmountDischarge air cooling amount to reset between start and end temperatures∆°FWrite
AV11153Service Test Timeout (Minutes)Timer (minutes) to indicate when the unit should cease service testWrite
AV11154Economizer Cooling Reference Enthalpy OffsetBTUs/poundWrite
AV11155Starts - Condenser Fan 1Condenser Fan 1 StartsRead
AV11156Starts - Condenser Fan 2Condenser Fan 2 StartsRead
AV11157Starts - Relief FanRelief Fan StartsRead
AV11158Starts - Electric Heat Stage 1Electric Heat Stage 1 StartsRead
AV11159Starts - Electric Heat Stage 2Electric Heat Stage 2 StartsRead
AV11160Starts - Supply FanCounter for Supply Fan StartsRead
AV11161Supply Fan TypeUnit supply fan typeRead
AV11163Supply Fan Speed StatusEstimated supply fan speed being utilized%Read
AV11164Heating Capacity Setpoint BASSetpoint to command the unit to a given heating capacity output%Command
AV11167Demand Shed Offset Setpoint∆°FCommand
AV11168Cooling Demand Limit Capacity Enable Setpoint%Command
AV11169Run Time - Compressor 1 (Hours)Compressor 1 RuntimeRead
AV11170Run Time - Compressor 2 (Hours)Compressor 2 RuntimeRead
AV11173Supply Fan Minimum Speed SetpointMinimum supply fan speed command%Command
AV11174Supply Fan Maximum Speed SetpointMaximum supply fan speed command%Command
AVmin11178Space Temperature ActiveActive space temperature being used by the controller°FRead
AV11180Space Temperature Heating Setpoint Input ActiveActive heating space temperature input setpoint°FRead
AV11181Space Temperature Setpoint ActiveActive space temperature setpoint being used by the controller°FRead
AV11183Starts - Compressor 1Compressor 1 StartsRead
AV11184Starts - Compressor 2Compressor 2 StartsRead
AV11185Cooling Capacity Enable - ActiveActive value for Cooling Capacity Enable point being used for control%Read
AV11186Daytime Warmup Setpoint BAS - ActiveActive value for Daytime Warmup Setpoint BAS point being used for control°FRead
AV11187Supply Fan Speed Command - ActiveActive value for Supply Fan Speed Command point being used for control%Read
AV11189Cooling Capacity Setpoint BAS - ActiveActive value for Cooling Capacity Setpoint BAS point being used for control%Read
AV11190Discharge Air Cooling Setpoint BAS - Active°FRead
AV11191Discharge Air Heating Setpoint BAS - Active°FRead
AV11192Discharge Air Reheat Setpoint BAS - Active°FRead
AV11193Discharge Air Temperature Minimum Cool Limit - Active°FRead
AV11195Economizer Minimum Position Setpoint BAS - Active%Read
AV11196Economizer Outdoor Air Enthalpy Enable Setpoint BAS - ActiveBTUs/poundRead
AV11197Economizer Outdoor Air Enable Setpoint BAS - Active°FRead
AV11198Relief Enable Position Setpoint - ActiveActive value for Relief Enable Position Setpoint point being used for control%Read
AV11199Heating Demand Limit Capacity Enable Setpoint - Active%Read
AV11200Discharge Air Temperature Maximum Cool Limit - Active°FRead
AV11202Cool TypeDescribes the type of cooling in the unitRead
AV11204DCV Minimum OA Damper Position at Full Fan Capacity - Active%Read
AV11205DCV Minimum OA Damper Position at Mid Fan Capacity - Active%Read
AV11206DCV Minimum OA Damper Position at Min Fan Capacity - Active%Read
AV11209Demand Shed Offset Setpoint - ActiveActive value for Demand Shed Offset Setpoint point being used for control∆°FRead
AV11211Design Minimum OA Damper Position at Full Fan Capacity - Active%Read
AV11212Design Minimum OA Damper Position at Mid Fan Capacity - Active%Read
AV11213Design Minimum OA Damper Position at Min Fan Capacity - Active%Read
AV11214Economizer Dry Bulb Disable Return Air OffsetDifferential dry bulb economizer disable offset∆°FWrite
AV11217Filter Runtime Hours Setpoint - ActiveActive value for Filter Runtime Hours Setpoint point being used for controlRead
AV11218Heat Primary Enable BAS - ActiveActive value for Heat Primary Enable BAS point being used for control%Read
AV11219Heating Capacity Setpoint BAS - ActiveActive value for Heating Capacity Setpoint BAS point being used for control%Read
AV11220Morning Warmup Setpoint BAS - ActiveActive value for Morning Warmup Setpoint BAS point being used for control°FRead
AV11226Space CO2 High Limit - ActiveActive value for Space CO2 High Limit point being used for controlPPMRead
AV11227Space CO2 Low Limit - ActiveActive value for Space CO2 Low Limit point being used for controlPPMRead
AV11236Discharge Air Cooling Setpoint (Target) - ActiveActive value for Discharge Air Cooling Setpoint°FRead
AV11237Discharge Air Heating Setpoint High Limit - Active°FRead
AV11238Duct Static Pressure Reset Time (seconds)Reset time for fan speed on duct static pressure control (seconds)Write
AV11240Duct Static Pressure Deadband ActiveIn. of waterRead
AV11241Heating Reset Start TempDischarge air heating reset start temperature°FWrite
AV11242Heating Reset End TempDischarge air heating reset end temperature°FWrite
AV11243Supply Fan Maximum Speed Setpoint - Active%Read
AV11245Supply Fan Minimum Speed Setpoint - Active%Read
AV11247Cooling Demand Limit Capacity Enable Setpoint - Active%Read
AV11248Economizer Minimum Position Setpoint ActiveEconomizer min position setpoint value resulting from arbitration%Read
AV11249Heating Capacity Secondary StatusUnit secondary heating capacity being utilized%Read
AV11250Occupied Standby Cooling Setpoint BAS - ActiveActive value for Occupied Standby Cooling Setpoint BAS°FRead
AV11251Occupied Standby Heating Setpoint BAS - ActiveActive value for Occupied Standby Heating Setpoint BAS°FRead
AV11252Preheat TypeIdentifies the product preheat typeRead
AV11253Reheat TypeIdentifies the product reheat typeRead
AV11254Space CO2 Concentration ActiveActive space CO2 concentration being used by the controllerPPMRead
AV11256Compressor Cooling P-Gain (%/F)Proportional gain for single loop Compressor Cooling PI controller (%/F)%Write
AV11257Compressor Cooling Reset Time (seconds)Reset time for single loop compressor Cooling PI controller (second)Write
AV11258Economizer Cooling P-Gain - 1 (%/F)Proportional gain for 1st loop Econ PI controller (%/F), for CVZT/VVZT systems%Write
AV11259Economizer Cooling Reset Time - 1 (Seconds)Reset time for 1st loop Econ PI controller (seconds), for CVZT/VVZT systemsWrite
AV11264Compressor Heating P-Gain (%/F)Proportional gain for single loop Heat Pump Heating PI controller (%/F)%Write
AV11265Compressor Heating Reset Time (seconds)Reset time for single loop Heat Pump Heating PI controller (seconds)Write
AV11266Auxiliary Heating P-Gain (%/F)Proportional gain for Electric single loop PI controller (%/F)%Write
AV11267Auxiliary Heating Reset Time (seconds)Reset time for Electric single loop PI controller (in seconds)Write
AV11268Compressor Cooling P-Gain - 1 (%/F)Proportional gain for 1st loop Cooling PI controller (%/F)%Write
AV11269Compressor Cooling Reset Time - 1 (seconds)Reset time for 1st loop Cooling PI controller (second)Write
AV11270Compressor Cooling P-Gain - 2 (%/F)Proportional gain for 2nd loop compressor cooling PI controller (%/F)%Write
AV11271Compressor Cooling Reset Time - 2 (seconds)Reset time for 2nd loop compressor cooling PI controller (second)Write
AV11272Economizer Discharge Air Setpoint°FCommand
AV11273Economizer Discharge Air Setpoint - Active°FRead
AV11274Heat Pump Heating Lockout Setpoint°FCommand
AV11275Heat Pump Heating Lockout Setpoint - Active°FRead
AV11276Space Temperature Setpoint Input ActiveActive space temperature input setpoint°FRead
AV11277Space Temperature Cooling Setpoint Input ActiveActive cooling space temperature input setpoint°FRead
AV11278Supply Fan PowerSupply Fan Drive Output PowerkWRead
AV11280Duct Static Pressure Setpoint ActiveDuct static pressure control setpoint value resulting from arbitrationIn. of waterRead
AV11281Dehumidification Control StatusStatus of the unit dehumidification capacity%Read
AV11282Supply Fan 1 Maximum RPM StatusRead
AV11283Supply Fan Minimum RPM StatusRead
AV11284Run Time - Supply Fan 2 (Hours)Supply Fan 2 RuntimeRead
AV11285Starts - Supply Fan 2Counter for Supply Fan 2 StartsRead
AV11286Motorized Damper Position Setpoint%Command
AV11287Motorized Damper Position Setpoint - ActiveActive value for Motorized Damper Position Setpoint%Read
AV11288Standby Minimum OA Damper Position at Full Fan Capacity%Command
AV11289Standby Minimum OA Damper Position at Full Fan Capacity - Active%Read
AV11290Standby Minimum OA Damper Position at Mid Fan Capacity%Command
AV11291Standby Minimum OA Damper Position at Mid Fan Capacity - Active%Read
AV11292Standby Minimum OA Damper Position at Min Fan Capacity%Command
AV11293Standby Minimum OA Damper Position at Min Fan Capacity - Active%Read
AV11294Supply Fan 2 PowerSupply Fan 2 Output PowerkWRead
AV11295Run Time - Gas Heat Stage 1 (Hours)Gas heat Stage 1 RuntimeRead
AV11296Starts - Gas Heat Stage 1Gas heat Stage 1 StartsRead
AV11297Run Time - Gas Heat Stage 2 (Hours)Gas heat Stage 2 RuntimeRead
AV11298Starts - Gas Heat Stage 2Gas heat Stage 2 StartsRead
AV11299Return Air Humidity ActiveActive Return Air Humidity sensor used for control%Read
AV11300Return Air Humidity ArbitratorArbitrator for Return Air Humidity%Write
AV11301Return Air Enthalpy ActiveThe return air enthalpy value being utilized by the unitBTUs/poundRead
AV11302Relief Enable Position Setpoint StatusOutdoor air damper position to enable Relief sequence%Read
AV11304Supply Fan RPMSupply Fan 1 RPMRead
AV11305Supply Fan 2 RPMRead
AV11306Supply Fan 2 Maximum RPM StatusRead
AV11307Discharge Air Heating Setpoint (Target) - ActiveActive value for Discharge Air Heating Setpoint°FRead
AV11308Duct Static Pressure Setpoint High Limit Setpoint BASIn. of waterCommand
AV11309Duct Static Pressure Setpoint High Limit Setpoint BAS - ActiveIn. of waterRead
AV11314Comfort Purge Interval (minutes)Write
AV11315Reheat Purge Interval (minutes)Write
AV11316Reheat P-Gain 1Proportional gain for 1st loop Reheat PI controller (%/F)%Write
AV11317Reheat Reset Time - 1Reset time for 1st loop Reheat PI controller (second)Write
AV11318Reheat P-Gain 2Proportional gain for 2nd loop Reheat PI controller (%/F)%Write
AV11319Reheat Reset Time - 2Reset time for discharge air Reheat PI controller (second)Write
AV11320Space Dew Point Setpoint BAS°FWrite
AV11321Dew Point Setpoint Offset BAS°FWrite
AV11323Outdoor Air Dew Point Setpoint BAS°FWrite
AV11326Space Dehumidification Setpoint Offset BAS%Write
AV11327Space Dehumidification Setpoint BASSetting for unit to use to control dehumidification%Write
AV11329Space Dehumidification Unoccupied Setpoint BASDefine the (occupied) space dehumidification setpoint%Command
AV11330Space Dew Point Unoccupied Setpoint BAS°FWrite
AV11331Compressor Dehumid P-Gain 2Proportional Gain for 2nd loop Compressor Dehumid PI controller (%/deg F)°FWrite
AV11332Compressor Dehumid P-Gain 1Proportional gain for 1st loop Compressor Dehumid PI controller (%/F)°FWrite
AV11333Compressor Dehumid Reset Time - 2 (seconds)Reset time for 2nd loop compressor Dehumid PI controller (second)Write
AV11334Compressor Dehumid Reset Time - 1 (seconds)Reset time for 1st loop Dehumid PI controller (second)Write
AV11335Pre Cool Setpoint BASDefines the space temp above which Pre Cool is enabled°FCommand
AV11336Pre Cool Setpoint BAS - ActiveActive value for Pre Cool Setpoint BAS point being used for control°FRead
AV11337Refrigerant Target Setpoint ActiveRefrigerant target setpoint actively being used for dehumidification control°FRead
AV11338Space Dew Point Setpoint ActiveOccupied Space Dew Point Setpoint actively being used for dehumidification control°FRead
AV11340Dew Point Setpoint Offset BAS - ActiveDew Point Setpoint Offset actively being used for dehumidification control°FRead
AV11341Outdoor Air Dew Point Setpoint BAS - ActiveOutdoor Air Dew Point Setpoint Offset actively being used for dehumidification control°FRead
AV11342Unoccupied Dehumidification TimerWrite
AV11343Heating Reset AmountDischarge air heating amount to reset between start and end temperatures∆°FWrite
AV11344VAV Box Stroke TimerWrite
AV11346Economizer Cooling P-Gain (%/F)Proportional gain for VVDA systems Econ PI controller (%/F)%Write
AV11347Economizer Cooling Reset Time (Seconds)Reset time for VVDA systems Econ PI controller (in seconds)Write
AV11348Economizer Cooling P-Gain - 2 (%/F)Proportional gain for 2nd loop Econ PI controller (%/F), for CVZT/VVZT systems%Write
AV11349Economizer Cooling Reset Time - 2 (Seconds)Reset time for 2nd loop Econ PI controller (seconds), for CVZT/VVZT systemsWrite
AV11350Auxiliary Heating P-Gain - 1 (%/F)Space control proportional gain for 1st loop Heating PI controller (%/F)%Write
AV11351Auxiliary Heating Reset Time - 1 (seconds)Space control reset Time for 1st loop Auxiliary Heating PI ControllerWrite
AV11352Auxiliary Heating P-Gain - 2 (%/F)Space control proportional gain for 2nd loop Heating PI controller (%/F)%Write
AV11353Auxiliary Heating Reset Time - 2 (seconds)Space control reset Time for 2nd loop Auxiliary Heating PI ControllerWrite
AV11354Discharge Air Heating Setpoint Low LimitDischarge Air Heating Setpoint Low Limit (deg F)°FCommand
AV11355Discharge Air Heating Setpoint Low Limit - Active°FRead
AV11356Discharge Air Cooling Setpoint StatusActual discharge air cooling setpoint value being used for control°FRead
AV11357Discharge Air Heating Setpoint StatusActual discharge air heating setpoint value being used for control°FRead
AV11358Discharge Air Reheating Setpoint High Limit - Active°FRead
AV11359Discharge Air Reheating Setpoint Low Limit - Active°FRead
AV11360Discharge Air Reheating Setpoint High LimitDischarge Air Reheating Setpoint High Limit (deg F)°FCommand
AV11361Discharge Air Reheating Setpoint Low LimitDischarge Air Reheating Setpoint Low Limit (deg F)°FCommand
AV11362Run Time - Gas Heat Manifold 1 Burner 1 (Hours)Gas heat runtimeRead
AV11363Starts - Gas Heat Manifold 1 Burner 1Gas heat startsRead
AV11364Run Time - Gas Heat Manifold 1 Burner 2 (Hours)Gas heat runtimeRead
AV11365Starts - Gas Heat Manifold 1 Burner 2Gas heat startsRead
AV11368Auxiliary Heating P-Gain Modulating Gas Staging (%/F)Proportional gain for 2nd loop- Staging control for Modulating Gas Heating%Write
AV11369Auxiliary Heating Reset Time Modulating Gas Staging (seconds)Reset Time for 2nd loop- Staging control for Modulating Gas HeatingWrite
AV11375Run Time - Circuit 1 Condenser Defrost (Hours)Circuit 1 Condenser Defrost Run TimeRead
AV11376Starts - Circuit 1 Condenser DefrostCircuit 1 Condenser Defrost StartsRead
AV11383Condenser Fan CapacityStatus of the total unit condenser fan capacity%Read
AV11384Compressor Cooling Modulating P-Gain - 2 (%/F)Proportional gain for 2nd loop modulating compressor cooling PI controller (%/F)%Write
AV11385Compressor Cooling Modulating Reset Time - 2 (seconds)Reset time for 2nd loop modulating compressor cooling PI controller (second)Write
AV11386Compressor Cooling Modulating P-Gain (%/F)Proportional gain for discharge air control - modulating compressor cooling PI controller%Write
AV11387Compressor Cooling Modulating Reset Time (seconds)Reset time for discharge air controls - modulating compressor cooling PI controllerWrite
AV11388Control StateControl State StatusRead
AV11389Demand Defrost Initiate Delta Temperature∆°FRead
AV11392Discharge Air Cooling Setpoint Y1Request discharge air temp cooling setpoint value°FCommand
AV11393Discharge Air Cooling Setpoint Y1 - Active°FRead
AV11394Discharge Air Cooling Setpoint Y2Request discharge air temp cooling setpoint value°FCommand
AV11395Discharge Air Cooling Setpoint Y2 - Active°FRead
AV11398Dehumidification Disable Space Temperature SetpointValue used to disable Dehumidification when compared to the Space Temperature°FWrite
AV11399Supply Fan Maximum Speed Setpoint HeatingMaximum supply fan speed command Heating%Write
AV11400Low Saturated Suction Refrig Temp Abnormal Deviation Offset∆°FWrite
AV11401Low Saturated Suction Refrig Temp Coefficient 1Write
AV11402Low Saturated Suction Refrig Temp Coefficient 2Write
AV11403Entering Water Temperature ArbitratorEntering Water temperature determined by arbitration°FWrite
AV11404Entering Water Temperature BASSend the Entering Water temperature sensor value°FWrite
AV11405Heat Pump Heating Changeover Delay (Minutes)Time at full heat pump capacity before secondary heat is addedWrite
AV11406Heat Pump Heating Changeover OffsetHeat Pump Changeover Offset is the temperature difference°FWrite
AV11407Heat Pump Heating Space Recovery DeltaHeat Pump Heating Space Recovery Delta isWrite
AV11408Run Time - Circuit 1 Heat Pump (Hours)Circuit 1 Heat Pump Run TimeRead
AV11410Heating Capacity Primary LimitSetpoint to Demand Limit heating capacity for the Primary Heat Source%Command
AV11411Heating Capacity Primary Limit - Active%Read
AV11412Heating Capacity Secondary LimitSetpoint to Demand Limit heating capacity for the Secondary Heat Source%Command
AV11413Heating Capacity Secondary Limit - Active%Read
AV11414Supply Air Tempering Enable SetpointUnits with Supply Air Tempering configured as installed°FWrite
AV11415Supply Air Tempering Disable SetpointUnits with Supply Air Tempering configured as installed°FWrite
AV11416Supply Air Tempering Delay (Seconds)Thermostat controlled units with Supply Air Tempering configured as installedWrite
AV11417Secondary Heating Lockout SetpointSetpoint at which to disable secondary heating based on outdoor air temperature°FCommand
AV11418Secondary Heating Lockout Setpoint - ActiveSetpoint at which to disable secondary heating based on outdoor air temperature°FRead
AV11419Auxiliary Heating P-Gain Modulating Electric Staging (%/F)Proportional gain for 2nd loop- Staging control for Modulating Electric Heating%Write
AV11420Auxiliary Heating Reset Time Modulating Electric Staging (seconds)Reset Time for 2nd loop- Staging control for Modulating Electric HeatingWrite
AV11421Design Air FlowSetting For Units Design Air FlowCFMWrite
AV11422Hydronic Heating Standby Freeze Avoidance PositionHydronic Heating Standby Freeze Avoid Position%Command
AV11423Hydronic Heating Standby Freeze Avoidance Position - Active%Read
AV11424Run Time - Electric Heat 1 Command Status (Hours)Electric Heat 1 Command RuntimeRead
AV11425Run Time - Electric Heat 2 Command Status (Hours)Electric Heat 2 Command RuntimeRead
AV11426Run Time - Electric Heat 3 Command Status (Hours)Electric Heat 3 Command RuntimeRead
AV11427Starts - Electric Heat 1 Command StatusElectric Heat 1 Command StartsRead
AV11428Starts - Electric Heat 2 Command StatusElectric Heat 2 Command StartsRead
AV11429Starts - Electric Heat 3 Command StatusElectric Heat 3 Command StartsRead
AV11430Hydronic Freeze Avoidance SetpointFreeze Avoidance Setpoint°FCommand
AV11431Hydronic Freeze Avoidance Setpoint - Active°FRead
AV11432Heating Primary Capacity Setpoint BASSetpoint to command the unit to a given Primary heating capacity output%Command
AV11433Heating Primary Capacity Setpoint BAS - Active%Read
AV11434Heating Secondary Capacity Setpoint BASSetpoint to command the unit to a given Secondary heating capacity output%Command
AV11435Heating Secondary Capacity Setpoint BAS - Active%Read
AV11448Compressor Heating P-Gain - 2 (%/F)Proportional gain for discharge air control - compressor Heating PI controller (%/F)%Write
AV11449Compressor Heating Reset Time - 2 (seconds)Reset time for discharge air controls - compressor Heating PI controller (seconds)Write
BI10105FDD: Unit Economizing When It Should NotDiagnostic: Unit Economizing When It Should NotReadfalse = Inactive, true = Active
BI10106FDD: Unit Not Economizing When It ShouldDiagnostic: Unit Not Economizing When It ShouldReadfalse = Inactive, true = Active
BI10107FDD: Excessive Outdoor AirDiagnostic: Excessive AirReadfalse = Inactive, true = Active
BI10108FDD: Outdoor Air Damper Not ModulatingDiagnostic: Damper NOT ModulatingReadfalse = Inactive, true = Active
BI10121Relief Fan Output StatusStatus of the Relief fan output on the controllerReadfalse = Off, true = On
BI10143VAV Box CommandThe associated VAV boxes should be AUTO or forced openReadfalse = Off, true = On
BI10170Condensate Overflow InputStatus of the condensate overflow inputReadfalse = Open, true = Closed
BI10172Occupancy InputStatus of the wired occupancy inputReadfalse = Occupied, true = Unoccupied
BI10210Equipment Shutdown Input StatusStatus of the equipment shutdown function of the unitReadfalse = Equipment Run, true = Equipment Shutdown
BI10211External Auto Stop Input StatusStatus of the externally-wired auto/stop inputReadfalse = Stop, true = Auto
BI10219Economizer Airside StatusStatus of airside economizingReadfalse = Inactive, true = Active
BImin10226Supply Fan StatusStatus of the supply fan output of the controllerReadfalse = Off, true = On
BI11100Compressor 1 Command StatusCompressor 1 Run Command StatusReadfalse = Off, true = On
BI11101Circuit 1 LPC StatusCircuit 1 LPC Input StatusReadfalse = Open, true = Closed
BI11102Compressor 1 Proving StatusStatus of input for monitoring Compressor 1 proof of operation circuitReadfalse = Not Proved, true = Proved
BI11103Compressor 2 Command StatusCompressor 2 Run Command StatusReadfalse = Off, true = On
BI11105Compressor 2 Proving StatusStatus of input for monitoring Compressor 2 proof of operation circuitReadfalse = Not Proved, true = Proved
BI11109Compressor 1 Unloader Command StatusReadfalse = Off, true = On
BI11111Compressor 2 Unloader Command StatusReadfalse = Off, true = On
BI11113Demand Limit InputConfigurable, hardwired input to command Demand LimitReadfalse = Not Limited, true = Limited
BI11114Demand Shed InputConfigurable, hardwired input to command Demand ShedReadfalse = Off, true = On
BI11115Phase Monitor StatusStatus of local Phase Monitor InputReadfalse = Tripped, true = Okay
BI11116Condenser Fan 1 Command StatusCondenser Fan 1 Run Command StatusReadfalse = Off, true = On
BI11117Condenser Fan 2 Command StatusCondenser Fan 2 Run Command StatusReadfalse = Off, true = On
BI11118Switchover Valve 1 Command StatusStatus of Switchover Valve Command for HP Circuit 1Readfalse = Off, true = On
BI11120Thermostat G InputThermostat Fan RequestReadfalse = Open, true = Closed
BI11121Thermostat W1/O InputThermostat Heat Stage 1 Request or Thermostat Heat/Cool Mode Request for HPReadfalse = Open, true = Closed
BI11122Thermostat W2 InputThermostat Heat Stage 2 Request (or Emergency Heat)Readfalse = Open, true = Closed
BI11123Thermostat X2 InputThermostat Emergency Heat RequestReadfalse = Open, true = Closed
BI11124Thermostat Y1 InputThermostat Compressor Stage 1 RequestReadfalse = Open, true = Closed
BI11125Thermostat Y2 InputThermostat Compressor Stage 2 RequestReadfalse = Open, true = Closed
BI11126Supply Fan Proving Input StatusStatus of the supply fan proving input on the controllerReadfalse = Not Proved, true = Proved
BI11127FroStat InputStatus of Hardwired Frostat InputReadfalse = Inactive, true = Active
BI11128Electric Heat Stage 1 StatusStatus of Electric Heat Stage 1 commandReadfalse = Off, true = On
BI11129Electric Heat Stage 2 StatusStatus of Electric Heat Stage 2 commandReadfalse = Off, true = On
BI11130Clogged Filter InputStatus of Hardwired Clogged Filter InputReadfalse = Clean, true = Dirty Filter
BI11133Ventilation Override Exhaust StatusHardwired input VOM ExhaustReadfalse = Open, true = Closed
BI11134Ventilation Override Pressurize StatusHardwired input VOM PressurizeReadfalse = Open, true = Closed
BI11135Ventilation Override Purge StatusHardwired input VOM PurgeReadfalse = Open, true = Closed
BI11143Reheat Humidistat InputHardwired input to support dehumidification requests on hot gas reheat unitsReadfalse = Open, true = Closed
BI11149Fan Mode - Air-FiSupply Fan Mode as setReadfalse = Cycling, true = Continuous
BI11150Occupancy Input - Air-FiReadfalse = Occupied, true = Unoccupied
BI11151Fan Mode InputSupply Fan Mode as setReadfalse = Cycling, true = Continuous
BI11152Supply Air Smoke Detector StatusStatus of Hardwired Supply Air Smoke Detector InputReadfalse = Open, true = Closed
BI11153Return Air Smoke Detector StatusStatus of Hardwired Return Air Smoke Detector InputReadfalse = Open, true = Closed
BI11154Gas Heat Stage 1 StatusStatus of gas heat Stage 1Readfalse = Off, true = On
BI11155Gas Heat Stage 2 StatusStatus of gas heat Stage 2Readfalse = Off, true = On
BI11156Diagnostic: ERM Supply Fan Locked Motor - 1Readfalse = Inactive, true = Active
BI11157Diagnostic: ERM Supply Fan Locked Motor - 2Readfalse = Inactive, true = Active
BI11158Diagnostic: ERM Supply Fan Motor Overheated - 1Readfalse = Inactive, true = Active
BI11159Diagnostic: ERM Supply Fan Motor Overheated - 2Readfalse = Inactive, true = Active
BI11160Diagnostic: ERM Supply Fan Power Mod Overheated - 1Readfalse = Inactive, true = Active
BI11161Diagnostic: ERM Supply Fan Power Mod Overheated - 2Readfalse = Inactive, true = Active
BI11162Diagnostic: ERM Fault Supply Fan - 1Readfalse = Inactive, true = Active
BI11163Diagnostic: ERM Fault Supply Fan - 2Readfalse = Inactive, true = Active
BI11164Diagnostic: IGN1 Module LockoutReadfalse = Inactive, true = Active
BI11165Diagnostic: IGN1 Heating High Temp Limit OpenReadfalse = Inactive, true = Active
BI11166Diagnostic: IGN1 Flame Rollout Switch OpenReadfalse = Inactive, true = Active
BI11167Diagnostic: IGN1 Inducer Proving Switch Fail ClosedReadfalse = Inactive, true = Active
BI11168Diagnostic: IGN1 Inducer Proving Switch Fail OpenReadfalse = Inactive, true = Active
BI11169Diagnostic: IGN1 No Flame Sensed on IgnitionReadfalse = Inactive, true = Active
BI11170Diagnostic: IGN1 Flame Sensed w/Gas Valve OffReadfalse = Inactive, true = Active
BI11171Diagnostic: IGN1 Hardware Configuration ErrorReadfalse = Inactive, true = Active
BI11172Diagnostic: IGN1 Weak FlameReadfalse = Inactive, true = Active
BI11173Diagnostic: IGN1 Gas Valve ErrorReadfalse = Inactive, true = Active
BI11174Diagnostic: IGN1 Module FailureReadfalse = Inactive, true = Active
BI11175Diagnostic: ERM Supply Fan Phase Failure - 1Diagnostic:ERM Supply Fan Phase Failure -1Readfalse = Inactive, true = Active
BI11176Diagnostic: ERM Supply Fan Phase Failure - 2Readfalse = Inactive, true = Active
BI11177Diagnostic: ERM Supply Fan Internal Comm Failure - 1Readfalse = Inactive, true = Active
BI11178Diagnostic: ERM Supply Fan Internal Comm Failure - 2Readfalse = Inactive, true = Active
BI11179Diagnostic: ERM Supply Fan Hall Sensor Error - 1Diagnostic: ERM Supply Fan Hall Sensor Error -1Readfalse = Inactive, true = Active
BI11180Diagnostic: ERM Supply Fan Hall Sensor Error - 2Diagnostic: ERM Supply Fan Hall Sensor Error -2Readfalse = Inactive, true = Active
BI11181Diagnostic: ERM Supply Fan Speed Limit Exceeded - 1Readfalse = Inactive, true = Active
BI11182Diagnostic: ERM Supply Fan Speed Limit Exceeded - 2Readfalse = Inactive, true = Active
BI11183Diagnostic: ERM Supply Fan Rotor Calibration - 1Readfalse = Inactive, true = Active
BI11184Diagnostic: ERM Supply Fan Rotor Calibration - 2Readfalse = Inactive, true = Active
BI11185Diagnostic: ERM Supply Fan DC link Undervoltage - 1Diagnostic: ERM Supply Fan DC-link Undervoltage - 1Readfalse = Inactive, true = Active
BI11186Diagnostic: ERM Supply Fan DC link Undervoltage - 2Diagnostic: ERM Supply Fan DC-link Undervoltage - 2Readfalse = Inactive, true = Active
BI11187Reheat Pumpout Solenoid StatusReheat Pumpout Solenoid IMC Command StatusReadfalse = Off, true = On
BI11189Reheat Valve 1 Fault StatusReadfalse = Inactive, true = Active
BI11190Reheat Valve 1 Calibration StatusReheat Valve 1 Calibration Status from Stepper Motor ModuleReadfalse = Inactive, true = Active
BI11192VAV Changeover InputVAV Changeover RequestReadfalse = Open, true = Closed
BI11193Crankcase Heater CommandCrankcase Heater status for VSPD CompressorReadfalse = Off, true = On
BI11195Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 1Readfalse = Inactive, true = Active
BI11196Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 2Readfalse = Inactive, true = Active
BI11197Diagnostic: Modulating Gas Invalid ID Plug Manifold 1Gas heat ignition controller detected an invalid or failed ID PlugReadfalse = Inactive, true = Active
BI11198Diagnostic: Modulating Gas Heat Configuration InvalidReadfalse = Inactive, true = Active
BI11199Diagnostic: Gas Heat Weak Flame Manif 1 Burner 1Weak flame or aged flame rod detected on burner 1Readfalse = Inactive, true = Active
BI11200Diagnostic: Gas Heat Weak Flame Manif 1 Burner 2Weak flame or aged flame rod detected on burner 2Readfalse = Inactive, true = Active
BI11201Diagnostic: Gas Heat Insufficient Combustion AirGas heat is being derated/reduced due to insufficient combustion airReadfalse = Inactive, true = Active
BI11202Diagnostic: Modulating Gas Primary Limit Open Manifold 1Gas heat failure, primary limit detected openReadfalse = Inactive, true = Active
BI11203Diagnostic: Modulating Gas Heat Open Fuse Manifold 1Gas heat failure, fuse detected openReadfalse = Inactive, true = Active
BI11204Diagnostic: Gas Heat Failed Ignition Manifold 1Readfalse = Inactive, true = Active
BI11205Diagnostic: Modulating Gas Valve Failure Manifold 1Modulating gas valve did not reach park or full On positionReadfalse = Inactive, true = Active
BI11206Diagnostic: Modulating Gas Control Board Failure Manifold 1Ignition control board failure during startup self testReadfalse = Inactive, true = Active
BI11231Diagnostic: Gas Heat Lockout Manifold 1Modulating gas heat ignition controller operation is locked outReadfalse = Inactive, true = Active
BI11235Diagnostic: Gas Heat Failed Ignition Manifold 1 Burner 2Modulating gas heat ignition controller burner 2 operation failed ignitionReadfalse = Inactive, true = Active
BI11237Diagnostic: VFD Cprsr Current Overload - Cprsr 1Readfalse = Inactive, true = Active
BI11238Diagnostic: VFD Compressor Ground Fault - Cprsr 1Readfalse = Inactive, true = Active
BI11239Diagnostic: VFD Compressor Short Circuit - Cprsr 1Readfalse = Inactive, true = Active
BI11240Diagnostic: VFD Compressor In Hand Mode - Cprsr 1Readfalse = Inactive, true = Active
BI11241Diagnostic: Gas Heat Air Pressure Sensor Reading LowModulating gas heat ignition controller, air pressure sensor is reading lowReadfalse = Inactive, true = Active
BI11242Diagnostic: Gas Heat Air Pressure Sensor Reading HighReadfalse = Inactive, true = Active
BI11243Diagnostic: Gas Heat Loss of Inducer Motor ControlModulating gas heat ignition controller, loss of inducer motor controlReadfalse = Inactive, true = Active
BI11244Diagnostic: Gas Heat Air Sensor Null Pressure CheckReadfalse = Inactive, true = Active
BI11245Diagnostic: Gas Heat Limited Low FireReadfalse = Inactive, true = Active
BI11246Heating Output Operational LimitHeating capacity is being limited due to heat rise across gas furnaceReadfalse = Inactive, true = Active
BI11247Diagnostic: Refrigerant Concentration Sensor ADiagnostic point that is be activeReadfalse = Inactive, true = Active
BI11248Refrigerant Leak Detection System InputReadfalse = Inactive, true = Active
BI11249Diagnostic: Refrigerant Leak Sensor Failure Sensor ADiagnostic point that shall be activeReadfalse = Inactive, true = Active
BI11250Diagnostic: IGN1 Low Ambient LockoutDiagnostic: IGN1 Low NOx Heat Furnace Low Ambient LockoutReadfalse = Inactive, true = Active
BI11251Diagnostic: Low Saturated Suction Refrig ProtectionReadfalse = Inactive, true = Active
BI11252Diagnostic: Low Saturated Suction Refrig Protection DisabledReadfalse = Inactive, true = Active
BI11253Electric Heat 1 Command StatusStatus of Electric Heat 1 commandReadfalse = Off, true = On
BI11254Electric Heat 2 Command StatusStatus of Electric Heat 2 commandReadfalse = Off, true = On
BI11255Electric Heat 3 Command StatusStatus of Electric Heat 3 commandReadfalse = Off, true = On
BI11256Diagnostic: Freeze ProtectionDiagnostic created when Hydronic Heat Freezestat status is in alarm positionReadfalse = Inactive, true = Active
BI11257Diagnostic: Freeze Avoidance ModeDiagnostic created to notify user Freeze avoidance measure are in placeReadfalse = Inactive, true = Active
BI11258Freezestat InputStatus of Hardwired Freezestat InputReadfalse = Tripped, true = Okay
BV10103Heat Lockout CommandCommand the unit to prevent heating operationCommandfalse = Normal, true = Locked out
BV10104Supply Fan Configuration CommandCommand the supply fan configuration as either cycling or continuousWritefalse = Cycling, true = Continuous
BV10106Dehumidification Enable CommandDisable unit dehumidificationCommandfalse = Disabled, true = Auto
BV10109Filter Timer ResetCommand the unit to reset the accumulated filter run hoursWritefalse = Accumulating, true = Reset
BV10110Reset DiagnosticInitiate a request to reset any controller diagnosticsWritefalse = Normal, true = Reset
BV10111Daytime Warmup Enable CommandEnable daytime warmupCommandfalse = Disabled, true = Enabled
BV10112Morning Warmup Enable CommandEnable morning warmupCommandfalse = Disabled, true = Enabled
BV10113Occupancy Input BASProvide the requested occupancy state to the unitWritefalse = Occupied, true = Unoccupied
BV10115Cooling Lockout BASPrevent all mechanical coolingCommandfalse = Normal, true = Locked out
BV10119Supply Air Tempering EnableEnable the supply (discharge) air tempering feature of the unitCommandfalse = Disable, true = Enable
BVmin11100Alarm Indicator StatusState of the alarm output command from the controllerReadfalse = Off, true = On
BV11101Supply Fan High Speed Command StatusSupply Fan High Speed Command for 2- Speed Fan Relay Controlled EquipmentReadfalse = Off, true = On
BV11112Condenser Defrost StatusStatus point to indicateReadfalse = Inactive, true = Active
BVmin11113Unit Stop CommandPoint used to force the unit into an immediate stop conditionWritefalse = Auto, true = Stop
BV11114Supply Fan Speed Command EnableCommandfalse = Disabled, true = Enabled
BV11115Cooling Capacity Setpoint Enable BASCommandfalse = Disabled, true = Enabled
BV11116Heating Capacity Setpoint Enable BASCommandfalse = Disabled, true = Enabled
BV11119Supply Fan CompensationCommandfalse = Disabled, true = Enabled
BV11121Compressor 1 Run Time ResetCompressor 1 Runtime ResetWritefalse = Accumulating, true = Reset
BV11122Compressor 1 Starts ResetWritefalse = Accumulating, true = Reset
BV11123Compressor 2 Run Time ResetCompressor 2 Runtime ResetWritefalse = Accumulating, true = Reset
BV11124Compressor 2 Starts ResetWritefalse = Accumulating, true = Reset
BV11127Condenser Fan 1 Run Time ResetCondenser Fan 1 Runtime ResetWritefalse = Accumulating, true = Reset
BV11128Condenser Fan 1 Starts ResetWritefalse = Accumulating, true = Reset
BV11129Condenser Fan 2 Run Time ResetCondenser Fan 2 Runtime ResetWritefalse = Accumulating, true = Reset
BV11130Condenser Fan 2 Starts ResetWritefalse = Accumulating, true = Reset
BV11133Relief Fan Run Time ResetRelief Fan Runtime ResetWritefalse = Accumulating, true = Reset
BV11134Relief Fan Starts ResetWritefalse = Accumulating, true = Reset
BV11135Electric Heat Stage 1 Run Time ResetElectric Heat Stage 1 Runtime ResetWritefalse = Accumulating, true = Reset
BV11136Electric Heat Stage 1 Starts ResetWritefalse = Accumulating, true = Reset
BV11137Electric Heat Stage 2 Run Time ResetElectric Heat Stage 2 Runtime ResetWritefalse = Accumulating, true = Reset
BV11138Electric Heat Stage 2 Starts ResetWritefalse = Accumulating, true = Reset
BV11139Supply Fan Run Time ResetSupply Fan Runtime ResetWritefalse = Accumulating, true = Reset
BV11140Supply Fan Starts ResetWritefalse = Accumulating, true = Reset
BV11142Diagnostic: Heat FailureReadfalse = Inactive, true = Active
BV11143Diagnostic: Duct Static Pressure Limit TripReadfalse = Inactive, true = Active
BV11144Diagnostic: Filter Change RequiredDiagnostic: Dirty FilterReadfalse = Inactive, true = Active
BV11145Diagnostic: Condensate Overflow LockoutCondensate Drain Pan Overflow LockoutReadfalse = Inactive, true = Active
BV11146Diagnostic: FroStat TripReadfalse = Inactive, true = Active
BV11155Diagnostic: Comp 1 Proving TripReadfalse = Inactive, true = Active
BV11156Diagnostic: Comp 2 Proving TripReadfalse = Inactive, true = Active
BV11158Diagnostic: Circuit 1 LPC TripReadfalse = Inactive, true = Active
BV11161Diagnostic: Compressor 1 Contactor FailureDiagnostic: Compressor 1 Contactor Fail LockoutReadfalse = Inactive, true = Active
BV11162Diagnostic: Circuit 1 LPC LockoutReadfalse = Inactive, true = Active
BV11166VVZT DAT Control ModeCommandfalse = Auto, true = Manual
BV11172Diagnostic: Compressor 1 Proving LockoutReadfalse = Inactive, true = Active
BV11173Occupancy Input ActiveOccupancy Input being actively used for status determinationReadfalse = Occupied, true = Unoccupied
BV11174Diagnostic: Compressor 2 Contactor FailureDiagnostic: Compressor 2 Contactor Fail LockoutReadfalse = Inactive, true = Active
BV11176Diagnostic: Compressor 2 Proving LockoutReadfalse = Inactive, true = Active
BV11177Diagnostic: Demand Defrost DisabledReadfalse = Inactive, true = Active
BV11180Diagnostic: Demand Defrost Fault AReadfalse = Inactive, true = Active
BV11183Diagnostic: Demand Defrost Fault BReadfalse = Inactive, true = Active
BV11186Diagnostic: Demand Defrost Fault CReadfalse = Inactive, true = Active
BV11189Diagnostic: Demand Defrost Fault DReadfalse = Inactive, true = Active
BV11190Diagnostic: Maintenance RequiredReadfalse = Inactive, true = Active
BV11192Diagnostic: Unit Communications FailureReadfalse = Inactive, true = Active
BV11199Supply Fan Configuration StatusSupply fan configurationReadfalse = Cycling, true = Continuous
BV11200Timed Override Timer Is ActiveOr not the timed override timer is activeReadfalse = Inactive, true = Active
BV11201Supply Fan Speed Command Enable - ActiveReadfalse = Disabled, true = Enabled
BV11202Cooling Capacity Setpoint Enable BAS - ActiveReadfalse = Disabled, true = Enabled
BV11203Cooling Lockout BAS - ActiveActive value for Cooling Lockout BAS point being used for controlReadfalse = Normal, true = Locked out
BV11204Heating Capacity Setpoint Enable BAS - ActiveActive value for Heating Capacity Setpoint Enable point being used for controlReadfalse = Disabled, true = Enabled
BV11205Daytime Warmup Enable Command - ActiveActive value for Daytime Warmup Enable Command point being used for controlReadfalse = Disabled, true = Enabled
BV11208Supply Fan Compensation - ActiveActive value for Supply Fan Compensation point being used for controlReadfalse = Disabled, true = Enabled
BV11209Dehumidification Enable Command - ActiveActive value for Dehumidification Enable Command point being used for controlReadfalse = Disabled, true = Auto
BV11211VVZT DAT Control Mode - ActiveActive value for VVZT DAT Control Mode point being used for controlReadfalse = Auto, true = Manual
BV11216Heat Lockout Command - ActiveActive value for Heat Lockout Command point being used for controlReadfalse = Normal, true = Locked out
BV11217Morning Warmup Enable Command - ActiveActive value for Morning Warmup Enable Command point being used for controlReadfalse = Disabled, true = Enabled
BV11221Supply Air Tempering StatusStatus of the Supply Air Tempering functionReadfalse = Disable, true = Enable
BV11222Supply Air Tempering Enable - ActiveActive value for Supply Air Tempering Enable point being used for controlReadfalse = Disable, true = Enable
BV11224Occupancy Input ArbitratorStatus of the arbitrated occupancy inputsWritefalse = Occupied, true = Unoccupied
BV11226Demand Limit Request BASDemand limit the unit remotelyWritefalse = Not Limited, true = Limited
BV11227Demand Limit Request - ActiveActive Demand Limit Request value used by the equipmentReadfalse = Not Limited, true = Limited
BV11230Diagnostic: VFD Compressor Fault - Cprsr 1Diagnostic that becomes active anytime a drive fault is ActiveReadfalse = Inactive, true = Active
BV11231Daytime Warmup ActiveDaytime warmup is currently activeReadfalse = Inactive, true = Active
BV11232Morning Warmup ActiveMorning warmup is activeReadfalse = Inactive, true = Active
BV11233Supply Fan 2 Run Time ResetSupply Fan 2 Runtime ResetWritefalse = Accumulating, true = Reset
BV11234Supply Fan 2 Starts ResetWritefalse = Accumulating, true = Reset
BV11235Occupied Standby Supply Fan Configuration CommandSelect the Occupied Standby Fan Mode settingCommandfalse = Cycling, true = Continuous
BV11236Occupied Standby Supply Fan Configuration Command - ActiveOccupied Standby Fan Mode settingReadfalse = Cycling, true = Continuous
BV11239Gas Heat Stage 1 Run Time ResetGas heat Stage 1 Runtime ResetWritefalse = Accumulating, true = Reset
BV11240Gas Heat Stage 1 Starts ResetWritefalse = Accumulating, true = Reset
BV11241Gas Heat Stage 2 Run Time ResetGas heat Stage 2 Runtime ResetWritefalse = Accumulating, true = Reset
BV11242Gas Heat Stage 2 Starts ResetWritefalse = Accumulating, true = Reset
BV11243Diagnostic: ERM Supply Fan 1 FailureReadfalse = Inactive, true = Active
BV11244Diagnostic: ERM Supply Fan 2 FailureReadfalse = Inactive, true = Active
BV11245Diagnostic: Supply Fan Proving FailureReadfalse = Inactive, true = Active
BV11248Diagnostic: High Condensate Level DetectedReadfalse = Inactive, true = Active
BV11249Diagnostic: Morning Warmup Mode Exceeded 120 MinutesReadfalse = Inactive, true = Active
BV11250Diagnostic: Pre Cool Mode Exceeded 120 MinutesDiagnostic: Precool Mode Exceeded 120 MinutesReadfalse = Inactive, true = Active
BV11251Diagnostic: Night Purge Mode Exceeded 120 MinutesReadfalse = Inactive, true = Active
BV11253Heat Pump Heating Lockout Setpoint EnableEnable the Heat pump Heating Lockout SetpointCommandfalse = Disable, true = Enable
BV11254Heat Pump Heating Lockout Setpoint Enable - ActiveActive value for the Heat pump Heating Lockout Setpoint EnableReadfalse = Inactive, true = Active
BV11255Dehumidification StatusActive state showing whether dehumidification is active or inactiveReadfalse = Inactive, true = Active
BV11256Pre Cool Enable CommandEnable pre CoolCommandfalse = Disabled, true = Enabled
BV11257Pre Cool Enable Command - ActiveActive value for Pre Cool Enable Command point being used for controlReadfalse = Disabled, true = Enabled
BV11258Pre Cool ActivePre Cool is activeReadfalse = Inactive, true = Active
BV11259Occupied Dehumidification Enable BASSetting for unit to use "Enable" or "Disable" for Occupied Dehumidification ControlWritefalse = Disabled, true = Enabled
BV11260Occupied Dehumidification Enable BAS - ActiveActive value for Dehumidification Enable BAS point being used for controlReadfalse = Disabled, true = Enabled
BV11261Unoccupied Dehumidification Enable BASSetting for unit to use "Enable" or "Disable" for Occupied Dehumidification ControlWritefalse = Disabled, true = Enabled
BV11262Unoccupied Dehumidification Enable BAS - ActiveActive value for Dehumidification Enable BAS point being used for controlReadfalse = Disabled, true = Enabled
BV11263Diagnostic: Duct Static Pressure Limit LockoutReadfalse = Inactive, true = Active
BV11264Diagnostic: Duct Static Pressure Local TripReadfalse = Inactive, true = Active
BV11265Diagnostic: Duct Static Pressure Local LockoutReadfalse = Inactive, true = Active
BV11266Gas Heat Manifold 1 Burner 1 Run Time ResetGas heat runtime resetWritefalse = Accumulating, true = Reset
BV11267Gas Heat Manifold 1 Burner 1 Starts ResetGas heat starts counter resetWritefalse = Accumulating, true = Reset
BV11268Gas Heat Manifold 1 Burner 2 Run Time ResetGas heat runtime resetWritefalse = Accumulating, true = Reset
BV11269Gas Heat Manifold 1 Burner 2 Starts ResetGas heat starts counter resetWritefalse = Accumulating, true = Reset
BV11272Circuit 1 Condenser Defrost Run Time ResetCircuit 1 Condenser Defrost Runtime ResetWritefalse = Accumulating, true = Reset
BV11273Circuit 1 Condenser Defrost Starts ResetWritefalse = Accumulating, true = Reset
BV11277Diagnostic: Reheat Valve 1 FaultReadfalse = Inactive, true = Active
BV11283Refrigerant Mitigation ActiveReadfalse = Inactive, true = Active
BV11284Thermostat Control Method RequestDetermines Auto or Conventional mode for enhanced thermostat applicationsWritefalse = Conventional, true = Enhanced
BV11285Thermostat Control Method StatusActive value for Thermostat Control Method being used for controlReadfalse = Conventional, true = Enhanced
BV11288Heating Capacity Control Type Override BASUsed on units leveraging remote capacity controlWritefalse = Disable, true = Enable
BV11289Circuit 1 Heat Pump Run Time ResetWritefalse = Accumulating, true = Reset
BV11291Diagnostic: Primary Heat Installed but Locked Out by ApplicationReadfalse = Inactive, true = Active
BV11292Diagnostic: Secondary Heat Installed but Locked Out by ApplicationReadfalse = Inactive, true = Active
BV11293Secondary Heating Lockout Setpoint EnableEnable the Secondary Heating Lockout SetpointCommandfalse = Disable, true = Enable
BV11294Secondary Heating Lockout Setpoint Enable - ActiveActive value for the Secondary Heating Lockout Setpoint EnableReadfalse = Inactive, true = Active
BV11295Hydronic Heat Valve Direct/Reverse ActingDirection of actuator strokeWritefalse = Direct, true = Reverse
BV11296Freeze Avoidance EnableCommandfalse = Disabled, true = Enabled
BV11297Freeze Avoidance Enable - ActiveActive Value for Freeze Avoidance Enable, for freeze avoidance controlReadfalse = Disabled, true = Enabled
BV11300Electric Heat 1 Command Status Run Time ResetElectric Heat 1 Command Status Runtime ResetWritefalse = Accumulating, true = Reset
BV11301Electric Heat 2 Command Status Run Time ResetElectric Heat 2 Command Status Runtime ResetWritefalse = Accumulating, true = Reset
BV11302Electric Heat 3 Command Status Run Time ResetElectric Heat 3 Command Status Runtime ResetWritefalse = Accumulating, true = Reset
BV11303Electric Heat 1 Command Status Starts ResetWritefalse = Accumulating, true = Reset
BV11304Electric Heat 2 Command Status Starts ResetWritefalse = Accumulating, true = Reset
BV11305Electric Heat 3 Command Status Starts ResetWritefalse = Accumulating, true = Reset
BV11306Relief Fan 2 Run Time ResetRelief Fan 2 Runtime ResetWritefalse = Accumulating, true = Reset
BV11307Relief Fan 2 Starts ResetWritefalse = Accumulating, true = Reset
MImin10101Heat Cool Mode StatusCurrent heat cool mode of the controllerRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MI10144Economizer System StatusOperating state of the airside economizer systemRead1 = Disabled, 2 = Enabled, 3 = Not Present
MI11100System Mode Switch Air-FiStatus of the wireless system mode switch connected to the controllerRead1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat
MI11101Timed Override Air-FiStatus of the Timed Override wireless inputRead1 = Idle, 2 = On, 3 = Cancel
MI11102System Mode Switch InputStatus of the wired system mode switch connected to the controllerRead1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat
MI11103Timed Override InputStatus of the Timed Override wired inputRead1 = Idle, 2 = On, 3 = Cancel
MI11104Supply Fan 1 ERM Information Alarm StatusInformational alarm status from the ERM supply fan 1Read1 = Normal, 2 = Current Limitation in Action, 3 = Line Impedance Too High, 4 = Power Limiter in Action, 5 = Output Stage Temperature High, 6 = Motor Temperature High, 7 = Temperature Inside Electronics High, 8 = DC Link Voltage High, 9 = Braking Mode, 10 = Calibration of Rotor Position, 11 = Actual Speed is Lower Than Run Monitoring Speed Limit, 12 = Cable Break at Analog or PWM Input For Analog Set Value, 13 = DC Link Voltage Low, 14 = Line Voltage High, 15 = Shedding Function Active
MI11105Supply Fan 2 ERM Information Alarm StatusInformational alarm status from the ERM supply fan 2Read1 = Normal, 2 = Current Limitation in Action, 3 = Line Impedance Too High, 4 = Power Limiter in Action, 5 = Output Stage Temperature High, 6 = Motor Temperature High, 7 = Temperature Inside Electronics High, 8 = DC Link Voltage High, 9 = Braking Mode, 10 = Calibration of Rotor Position, 11 = Actual Speed is Lower Than Run Monitoring Speed Limit, 12 = Cable Break at Analog or PWM Input For Analog Set Value, 13 = DC Link Voltage Low, 14 = Line Voltage High, 15 = Shedding Function Active
MV10101Cooling Reset Type StatusType of cooling reset used by the controllerRead1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air
MV10102Emergency Override BASCommand the unit into an emergency mode of operationCommand1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV10103Economizer Airside Enable BASEnable airside economizingCommand1 = Disabled, 2 = Enabled, 3 = Auto
MV10104Heat Cool Mode RequestCommand the unit into a heat/cool modeCommand1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MVmin10106Occupancy RequestCommand the unit into an occupancy modeWrite1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MV10110Timed Override RequestRequest a temporary timed override during unoccupiedWrite1 = Idle, 2 = On, 3 = Cancel
MV11100Arbitration Method RequestWrite1 = Enable External/BAS Control, 2 = Standalone Control
MV11101Customer Options Module Communication StatusCommunication Status of the Customer Options ModuleRead1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11102Economizer TypeGeneral description of the type of economizer systemRead1 = None, 2 = 2 Position Ventilation, 3 = Modulation Economizer, 4 = 2 Position Ventilation/Waterside Economizer, 5 = Waterside Economizer, 6 = Airside/Waterside Economizer, 7 = TRAQ Damper, 8 = Airside Economizer and TRAQ Damper/Sensor, 9 = Waterside Economizer and TRAQ Damper/Sensor, 10 = Airside/Waterside Economizer and TRAQ Damper/Sensor
MV11103Fresh Air Options Module Communication StatusCommunication Status of the Fresh Air Options ModuleRead1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11105Indoor Options Module Communication StatusCommunication Status of the Indoor Options ModuleRead1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11106On-Board I/O Communication StatusCommunication Status of the On-Board Inputs and OutputsRead1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11110Service Test State RequestPoint to request the unit into a service test stepWrite*See (a), 1 = Inactive, 2 = Fan On Econ Open, 3 = High Fan Speed Econ Open, 4 = Ventilation Low Fan Speed, 5 = Ventilation Mid Fan Speed, 6 = Ventilation High Fan Speed, 7 = Cool 1, 8 = Cool 2, 9 = Cool 3, 10 = Cool 4, 11 = Cool 5, 12 = Reheat, 13 = Heat 1, 14 = Heat 2, 15 = Heat 3, 16 = Heat 4, 17 = Aux Heat 1, 18 = Aux Heat 2, 19 = Defrost, 20 = Emergency Heat, 21 = Open Reheat Valve 1, 22 = Close Reheat Valve 1, 23 = Refrigerant Recovery
MV11111Cooling Reset TypeWrite1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air
MV11112System Mode Switch LocalRead1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat
MV11113Timed Override StatusStatus of the timed override requestRead1 = Idle, 2 = On, 3 = Cancel
MV11114Trane Unit TypeEquipment type according to the manufacturer's classificationRead1 = 1 Heat/1 Cool, 2 = Heat Pump, 3 = Blower Coil, 4 = Unit Ventilator, 5 = Fan Coil, 6 = Rooftop, 7 = Air Handler, 8 = Vertical Self Contained, 9 = Unitary, 10 = VAV Box
MV11115Unit Stop SourceSource of the stop command that turned off the equipmentRead1 = None, 2 = Emergency Stop, 3 = Drain Pan Overflow, 4 = Local HI, 5 = Remote HI, 6 = External Auto Stop, 7 = Phase Monitor, 8 = Emergency Override, 9 = Supply Fan Fault, 10 = Equipment Shutdown Input, 11 = Smoke Detector, 12 = Equipment Limit, 13 = Sensor Failure
MV11116Emergency Override BAS - ActiveActive value for Emergency Override BAS point being used for controlRead1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV11118Economizer Decision MethodIndicate the method of enabling airside economizingRead1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy, 5 = Differential Dry Bulb
MV11119Refrigerant TypeType of refrigerant used in the equipmentRead1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E), 17 = R-454B
MV11120Economizer Airside Enable BAS - ActiveActive value for Economizer Airside Enable BAS point being used for controlRead1 = Disabled, 2 = Enabled, 3 = Auto
MV11121Heat Cool Mode Request - ActiveActive value for Heat Cool Mode Request point being used for controlRead1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate
MVmin11123Occupancy StatusActive occupancy mode of the controllerRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MV11125Occupancy Request ActiveActive Occupancy mode being requested of the unitRead1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto
MV11126Supply Fan 1 Communication StatusCommunication Status of the Modbus Supply Fan 1Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11127Supply Fan 2 Communication StatusCommunication Status of the Modbus Supply Fan 2Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11128Gas Heat Ignition Module 1 Communication StatusCommunication Status of the Modbus Gas Heat Ignition Module 1Read1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11130Emergency Override StatusActive Emergency Override mode in control of the equipmentRead1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire
MV11133Stepper Motor Communication StatusCommunication Status of the Stepper Motor Inputs and OutputsRead1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11136Heating Reset TypeWrite1 = None, 2 = Outdoor air, 3 = Zone, 4 = Return Air
MV11137Heating Reset Type StatusDischarge air heating reset type statusRead1 = None, 2 = Outdoor air, 3 = Zone, 4 = Return Air
MV11138Compressor 1 VFD Communication StatusCommunication Status of the Modbus Compressor VFDRead1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured
MV11139Refrigerant Leak Sensor Communication Status Sensor ACommunication status of the Modbus communicating refrigerant detection systemRead1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 700 Precedent / Axiom and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 700 Precedent / Axiom

How many BACnet points does the Trane Symbio 700 Precedent / Axiom have?

This list has 639 BACnet objects: 53 analog inputs, 294 analog values, 119 binary inputs, 131 binary values, 8 multi-state inputs, 34 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 700 Precedent / Axiom BACnet points are writable?

232 of the 639 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Trane Symbio 700 Precedent / Axiom BACnet documentation?

The source is Symbio 700 Integration Points List BACnet/Modbus - Precedent, Axiom Rooftop WSHP (BAS-PTS001C-EN), revision 08/12/2026, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS001C-EN_08172026.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 700 Precedent / Axiom?

Start with MV 10106 Occupancy Request (Occupancy command (occupied/unoccupied/standby)); BV 11113 Unit Stop Command (BMS stop/auto of the whole unit); AV 10159 Occupied Cooling Setpoint BAS (Occupied cooling setpoint (dual-setpoint units)); AV 10160 Occupied Heating Setpoint BAS (Occupied heating setpoint (dual-setpoint units)); AV 10127 Space Temperature Setpoint BAS (Single-setpoint alternative to the two setpoints above); MI 10101 Heat Cool Mode Status (Current heat/cool operating mode); MV 11123 Occupancy Status (Confirms the occupancy the unit is running in); BI 10226 Supply Fan Status (Supply fan on/off status); AV 11178 Space Temperature Active (Space temperature the unit is actually controlling to); BV 11100 Alarm Indicator Status (Unit alarm output; on when the controller is in alarm).

How do I enable BMS control of the Trane Symbio 700 Precedent / Axiom?

MV 11100 Arbitration Method Request picks the control type. 'Enable External/BAS Control' is the factory default: the controller weighs BAS, Air-Fi and wired sources and uses the BAS value while it is valid. 'Standalone Control' ignores all BAS input. BV 11113 Unit Stop Command (Auto/Stop) stops the unit from the BMS.

Does the Trane Symbio 700 Precedent / Axiom need a BACnet heartbeat or have a communication timeout?

The sensor BAS points (space temp, OA temp, humidity, CO2, return air) have a 900 s heartbeat in the points list. Per the integration guide, a BAS sensor or setpoint value that is not rewritten at least every 15 minutes fails. Its priority-12 entry then drops out of the Arbitrator and the controller falls back to the next source (Air-Fi, wired, then default). BV 10113 Occupancy Input BAS has the same 15-minute heartbeat; MV 10106 Occupancy Request has none.

Can the BMS supply sensor values to the Trane Symbio 700 Precedent / Axiom?

Write the value to the matching '... BAS' AV (e.g. AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS) and keep refreshing it. It shows on the '... Arbitrator' object at priority 12, above Air-Fi (14) and wired (15). The '... Active' object reports the value in use. Space setpoints go to AV 10127 Space Temperature Setpoint BAS (single setpoint) or AV 10159/10160 Occupied Cooling/Heating Setpoint BAS (dual setpoint).

How do I check these points on the real Symbio 700 Precedent / Axiom?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 700 Integration Points List BACnet/Modbus - Precedent, Axiom Rooftop WSHP · BAS-PTS001C-EN · rev. 08/12/2026. Object names, instances and units are reproduced as published; descriptions are our own.