  3. Trane
  4. Symbio 400-B/500 Water-Source Heat Pump

Water-source heat pump controller · BACnet points list

Trane Symbio 400-B/500 Water-Source Heat Pump BACnet points list

Updated 28 October 2026

Short answer

The Symbio 400-B/500 is Trane's programmable controller for water-source heat pumps and is BTL listed as a B-BC. The guide covers BACnet MS/TP in detail; Symbio UI also offers BACnet IP, BACnet Air-Fi, Modbus RTU and Modbus TCP. The WSHP application exposes about 100 objects: wired sensor inputs, BAS sensor and setpoint values, occupancy, mode and fan speed requests, capacity status and diagnostics.

This page lists 102 BACnet objects for the Trane Symbio 400-B/500 Water-Source Heat Pump — 51 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 400-B/500 Water-Source Heat Pump
Equipment
Water-source heat pump controller
Equipment type
Heat pumps
BACnet objects
102 (51 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN
Source document
Integration Guide - Symbio 400-B/500 Programmable Controller for Water Source Heat Pump · BAS-SVP061B-EN · rev. December 2024
Download CSV 102 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 400-B/500 Water-Source Heat Pump

Integration in brief

Set the rotary address, then use Symbio UI (USB, http://198.80.18.1) BAS Control Selection to pick BAS or Local for each sensor and setpoint. Schedule with MV 6 Occupancy Request, write AV 27 Space Temperature Setpoint BAS and MV 4 Heat Cool Mode Request, and put the BAS sensor objects in service and refresh them at least every 15 minutes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 6Occupancy RequestOccupancy command from the BMS scheduleWrite
MV 4Heat Cool Mode RequestHeat/cool mode commandWrite
AV 27Space Temperature Setpoint BASSpace setpoint from the BMSWrite
BV 2Reset DiagnosticReset diagnostics (self-clears)Write
MV 7Occupancy StatusConfirms the occupancy in effectRead
MV 5Heat Cool Mode StatusHeat/cool mode in effectRead
AV 59Space Temperature ActiveSpace temperature the unit controls toRead
AI 8Leaving Water TemperatureLeaving water temperatureRead
BV 15Diagnostic: Compressor 1 FailureCompressor 1 protection tripRead

Enable & remote start

The BAS controls the unit by writing values and putting points in or out of service. BAS Control Selection in Symbio UI chooses BAS or Local per sensor and setpoint. MV 9 Emergency Override BAS stops the unit for any value other than 1 = Normal, and AV 10 Compressor Enable BAS limits or disables compressor capacity.

Heartbeat & communication loss

BAS-supplied sensor objects (AV 14 Space Temperature BAS, AV 2 Space Humidity BAS, AV 4 Source Water Temperature BAS) must be rewritten at least every 15 minutes. If a write is not seen in time the object goes to fault and the unit uses its own sensor; at power-up they start in fault until written.

Sensors & values from the BMS

Put the BAS sensor objects in service (out of service by default), then write AV 14 Space Temperature BAS, AV 2 Space Humidity BAS and AV 4 Source Water Temperature BAS. AV 59, AV 6 and AV 5 show the value actually in use. AV 27 Space Temperature Setpoint BAS replaces the local setpoint while in service.

Network setup

Watch out for

Trane Symbio 400-B/500 Water-Source Heat Pump BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

102 of 102 shown
Type
Access
Show
Trane Symbio 400-B/500 Water-Source Heat Pump BACnet Points List
DescriptionStates
AI1Space Temperature LocalSpace or return air temperature from the wired sensor°FRead
AI2Space Temperature Setpoint LocalSetpoint from the wired zone sensor°FRead
AI3Space Humidity LocalSpace humidity from the wired sensor%Read
AI4Discharge Air TemperatureDischarge air temperature°FRead
AI5Entering Water Temperature LocalEntering water temperature from the wired sensor°FRead
AImin8Leaving Water TemperatureLeaving water temperature°FRead
AI21Space CO2 Concentration LocalSpace CO2 from the wired sensorppmRead
AO1Supply Fan Motor Signal OutputECM fan speed signal (0 % = low, 100 % = high)%Read
AV2Space Humidity BASSpace humidity written by the BAS%Write
AV3Entering Water Compressor Heat Disable SetpointEntering water temp below which compressors lock out for electric heat°FWrite
AV4Source Water Temperature BASEntering (source) water temperature written by the BAS°FWrite
AV5Entering Water Temperature ActiveEntering water temperature in use°FRead
AV6Space Humidity ActiveSpace humidity in use%Read
AV8Economizer Enable Minimum Water Temperature SetpointMinimum entering water temp that allows waterside economizing (default 50 °F)°FWrite
AV9Supply Fan Off Delay TimeFan off delay after electric heatsWrite
AV10Compressor Enable BASCompressor capacity limit; 100 % = enabled, 0 % = disabled%Write
AV12Filter Runtime Hours SetpointFan runtime hours before a maintenance diagnostic; 0 disableshWrite
AV14Space Temperature BASSpace temperature written by the BAS°FWrite
AV17Supply Fan Speed Maximum Heat Cool CapacityMaximum supply fan speed%Write
AV18Supply Fan Speed DehumidificationFan speed during dehumidification%Write
AV19Supply Fan Speed First Stage MinimumFan speed with first stage of heating or cooling on%Write
AV20Supply Fan Speed VentilationFan speed with fan on and compressors cycled off%Write
AV21Discharge Air Temperature Low Limit SetpointDischarge air temp that trips the low DAT diagnostic°FWrite
AV22Supply Fan Scaling FactorScales minimum fan values from the maximum (AV 17)Write
AV23Unoccupied Cooling SetpointUnoccupied cooling setpoint (default 85 °F)°FWrite
AV24Unoccupied Heating SetpointUnoccupied heating setpoint (default 60 °F)°FWrite
AVmin27Space Temperature Setpoint BASSpace temperature setpoint written by the BAS°FWrite
AV28Space Temperature Setpoint ActiveSetpoint in use after arbitration and offsets°FRead
AV29Heat Cool Mode Changeover DelayAll capacity must be off this long before heat/cool changeoverminWrite
AV30Occupied OffsetOffset from the active setpoint in occupied/bypass (default 2.5 °F)°FWrite
AV33Occupied Bypass TimeTimed override (occupied bypass) durationminWrite
AV34Occupied Standby OffsetOffset from the active setpoint in occupied standby (default 7.5 °F)°FWrite
AV36Space Dehumidification Setpoint BASSpace relative humidity setpoint%Write
AV37Space Temperature Setpoint DefaultFallback setpoint when no BAS or local setpoint (default 72.5 °F)°FWrite
AV38Filter Runtime HoursFan run hours since the last filter timer resethRead
AV39Dehumidification Discharge Air Setpoint BASDischarge air target during passive dehumidification°FWrite
AV40Loop Water Temperature Low LimitLeaving water temp that trips the low LWT diagnostic°FWrite
AV46Compressor PWM Cycle PeriodCompressor PWM cycle period (default 1200 s)sWrite
AV47Electric Heat PWM Cycle PeriodElectric heat PWM cycle period (default 1200 s)sWrite
AV48Waterside Economizer PWM Cycle PeriodWaterside economizer PWM cycle period (default 1200 s)sWrite
AV49Compressor DelayIsolation valve lead time before the compressor startssWrite
AVmin59Space Temperature ActiveSpace temperature in use°FRead
AV64Fan Capacity Low LimitLowest fan speed; not user-adjustable%Read
AV67Auxiliary Heat Control RequestAuxiliary heat capacity limit%Write
AV68Space Relative Humidity DeadbandRH offset below setpoint where dehumidification stops (default 8 %)%Write
AV73Supply Fan Speed StatusCurrent fan capacity%Read
AV74Heating Capacity Primary StatusPrimary (compressor) heating capacity%Read
AV75Heating Capacity Secondary StatusSecondary heat capacity (electric or hot gas reheat)%Read
AV76Cooling Capacity StatusCompressor cooling capacity (50 % per compressor on 2-compressor units)%Read
AV87Cooling Setpoint High LimitCooling setpoint high limit (default 110 °F)°FWrite
AV88Cooling Setpoint Low LimitCooling setpoint low limit (default 40 °F)°FWrite
AV89Heating Setpoint High LimitHeating setpoint high limit (default 105 °F)°FWrite
AV90Heating Setpoint Low LimitHeating setpoint low limit (default 40 °F)°FWrite
BI1Occupancy InputOccupancy contact (normally open)Read0=Occupied, 1=Unoccupied
BI2Compressor 1 Lockout StatusCompressor 1 safety lockout (pressure or freeze)Read0=Inactive, 1=Locked out
BI3Compressor 2 Lockout StatusCompressor 2 safety lockout (pressure or freeze)Read0=Inactive, 1=Locked out
BI4Condensate Overflow InputCondensate overflow switch (normally open)Read0=Normal, 1=Overflow
BI7Refrigerant Leak Detection System InputRefrigerant leak detection sensor statusRead0=Sensor Alarm, Fault, 1=No Alarm, No Fault
BO1Supply Fan EnableECM fan enableRead0=Disable, 1=Enable
BO2Waterside Economizer Valve CommandWaterside economizer valveRead0=Closed, 1=Open
BO4Compressor 1 CommandCompressor 1 outputRead0=OFF, 1=ON
BO5Compressor 2 CommandCompressor 2 outputRead0=OFF, 1=ON
BO6Auxiliary Heat Command / Dehumidification OutputElectric heat or hot gas reheat outputRead0=OFF, 1=ON
BO7Reversing Valve OutputReversing valve outputRead0=Cooling, 1=Heating
BO8Isolation Valve CommandIsolation valve / external pump outputRead0=Closed, 1=Open
BO9Outdoor Air Damper Position StatusTwo-position outdoor air damper outputRead0=Closed, 1=Open
BV1Supply Fan Configuration CommandOccupied fan mode: cycling or continuousWrite0=Cycling, 1=Continuous
BVmin2Reset DiagnosticReset all diagnostics except filter; self-clearsWrite0=Idle, 1=Reset
BV3Diagnostic: Low Discharge Air TemperatureLow discharge air temperature diagnosticRead0=Normal, 1=In Alarm
BV4Diagnostic: Condensate OverflowCondensate overflow diagnostic (latching)Read0=Normal, 1=In alarm
BV5Waterside Economizer Fan SpeedFan speed during waterside economizingWrite0=Low, 1=High
BV6Diagnostic: Low Primary Air FlowLow airflow (fan proving) diagnostic (latching)Read0=Normal, 1=In alarm
BV7First Stage Compressor Minimum Fan SpeedFan speed with 1 of 2 compressors onWrite0=Low (default), 1=High
BV8Diagnostic: Filter Change RequiredFilter change required (fan run hours)Read0=Clean, 1=Dirty
BV9Water Temperature Sampling EnableEntering water temperature sampling enableWrite0=Disabled, 1=Enable
BV10Diagnostic: Compressor 2 FailureCompressor 2 protection trip (one auto-reset per 24 h)Read0=Normal, 1=In alarm
BV11Dehumidification StatusDehumidification activeRead0=Not active, 1=Dehumidification active
BV12Filter Timer ResetReset the filter runtime timer; self-clearsWrite0=Idle, 1=Reset
BV14Predicted Occupied Heat Cool Mode StatusPredicted heat/cool mode for the next occupied periodRead
BVmin15Diagnostic: Compressor 1 FailureCompressor 1 protection trip (one auto-reset per 24 h)Read0=Normal, 1=In alarm
BV17Diagnostic: Low Leaving Water TemperatureLow leaving water temperature diagnosticRead0=Normal, 1=In alarm
BV18Boilerless Control EnableBoilerless control enableWrite0=Disable, 1=Enable
BV19Refrigerant Mitigation ActiveRefrigerant leak mitigation active (from BI 7)Read
BV21Passive Dehumidification EnablePassive dehumidification enableWrite0=Disable, 1=Enable
MI1Timed Override StatusTimed override request/cancel from the zone sensorRead1=Idle, 2=ON, 3=Cancel
MI2Supply Fan Speed Setpoint LocalLocal fan speed switchRead1=Auto, 2=Off, 3=Low, 4=Medium, 5=High
MO1Fan Supply OutputFan speed output for 1- and 2-speed fansRead1=Auto, 2=Off, 3=Low, 4=Medium, 5=High
MV1Supply Fan Staged Speed StatusFan speed status for 1- and 2-speed fansRead1=Auto, 2=Off, 3=Low, 4=Medium, 5=High
MV2Cooling Fan Speed DefaultDefault fan speed in coolingWrite1=Auto, 2=Off, 3=Low, 4=Medium, 5=High
MV3Heating Fan Speed DefaultDefault fan speed in heatingWrite1=Auto, 2=Off, 3=Low, 4=Medium, 5=High
MVmin4Heat Cool Mode RequestHeat/cool mode commandWrite1=Auto, 2=Heat, 3=Morning warm-up, 4=Cool, 5=Night Purge, 6=Pre Cool, 7=Off, 8=Test (status only), 9=Emergency Heat, 10=Fan Only, 11=Free Cool (treats this as Auto), 12=Ice-Making (treat this as Auto), 13=Max Heat (treats this as Auto), 14=Economizer (treats as Auto), 15=Dehumidify (treats this as Auto), 16=Calibrate (treats this as Auto)
MVmin5Heat Cool Mode StatusHeat/cool mode in effectRead1=Auto, 2=Heat, 3=Morning warm-up, 4=Cool, 5=Pre Cool, 6=Off, 7=Test, 8=Emergency Heat
MVmin6Occupancy RequestOccupancy commandWrite1=Occupied, 2=Unoccupied, 3=Occupied Bypass, 4=Occupied Standby, 5=Auto
MVmin7Occupancy StatusOccupancy in effectRead1=Occupied, 2=Unoccupied, 3=Occupied Bypass, 4=Occupied Standby
MV8Supply Fan Staged Speed Setpoint BASFan speed command from the BAS (Auto = local decision)Write1=Auto, 2=Off, 3=Low, 4=Medium, 5=High
MV9Emergency Override BASEmergency override; anything but Normal shuts the unit downWrite1=Normal, 2=Pressurize, 3=De-pressurized, 4=Purge, 5=Shutdown, 6=Fire
MV12Manual Test SequenceManual test sequence (Tracer TU)Write
MV15Economizer Waterside Enable CommandWaterside economizer enable/disable/autoWrite1=Disabled, 2=Enabled, 3=Auto
MI3Communication StatusCommunication status with Trane system controllersRead
BI5In DefrostDefrost input (normally closed)Read0=Not in defrost, 1=In defrost
BI6Supply Fan StatusFan proving input (optional)Read0=OFF, 1=ON (fan running)
MI4Wireless Sensor Battery LevelTrane wireless zone sensor battery levelRead1=Replace Batteries, 2=Schedule Replacement, 3=Good

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 400-B/500 Water-Source Heat Pump and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 400-B/500 Water-Source Heat Pump

How many BACnet points does the Trane Symbio 400-B/500 Water-Source Heat Pump have?

This list has 102 BACnet objects: 7 analog inputs, 1 analog output, 45 analog values, 7 binary inputs, 8 binary outputs, 18 binary values, 4 multi-state inputs, 1 multi-state output, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 400-B/500 Water-Source Heat Pump BACnet points are writable?

51 of the 102 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 400-B/500 Water-Source Heat Pump BACnet documentation?

The source is Integration Guide - Symbio 400-B/500 Programmable Controller for Water Source Heat Pump (BAS-SVP061B-EN), revision December 2024, published free by Trane at https://www.trane.com/content/dam/Trane/Commercial/media/documents/BAS-SVP061B-EN_12082024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 400-B/500 Water-Source Heat Pump?

Start with MV 6 Occupancy Request (Occupancy command from the BMS schedule); MV 4 Heat Cool Mode Request (Heat/cool mode command); AV 27 Space Temperature Setpoint BAS (Space setpoint from the BMS); BV 2 Reset Diagnostic (Reset diagnostics (self-clears)); MV 7 Occupancy Status (Confirms the occupancy in effect); MV 5 Heat Cool Mode Status (Heat/cool mode in effect); AV 59 Space Temperature Active (Space temperature the unit controls to); AI 8 Leaving Water Temperature (Leaving water temperature); BV 15 Diagnostic: Compressor 1 Failure (Compressor 1 protection trip).

How do I enable BMS control of the Trane Symbio 400-B/500 Water-Source Heat Pump?

The BAS controls the unit by writing values and putting points in or out of service. BAS Control Selection in Symbio UI chooses BAS or Local per sensor and setpoint. MV 9 Emergency Override BAS stops the unit for any value other than 1 = Normal, and AV 10 Compressor Enable BAS limits or disables compressor capacity.

Does the Trane Symbio 400-B/500 Water-Source Heat Pump need a BACnet heartbeat or have a communication timeout?

BAS-supplied sensor objects (AV 14 Space Temperature BAS, AV 2 Space Humidity BAS, AV 4 Source Water Temperature BAS) must be rewritten at least every 15 minutes. If a write is not seen in time the object goes to fault and the unit uses its own sensor; at power-up they start in fault until written.

Can the BMS supply sensor values to the Trane Symbio 400-B/500 Water-Source Heat Pump?

Put the BAS sensor objects in service (out of service by default), then write AV 14 Space Temperature BAS, AV 2 Space Humidity BAS and AV 4 Source Water Temperature BAS. AV 59, AV 6 and AV 5 show the value actually in use. AV 27 Space Temperature Setpoint BAS replaces the local setpoint while in service.

How do I check these points on the real Symbio 400-B/500 Water-Source Heat Pump?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Integration Guide - Symbio 400-B/500 Programmable Controller for Water Source Heat Pump · BAS-SVP061B-EN · rev. December 2024. Object names, instances and units are reproduced as published; descriptions are our own.