Air-cooled chiller controller · BACnet points list

Trane Symbio 800 ACRB Small (UC800) BACnet points list

Updated 28 October 2026

Short answer

This Symbio 800 list for ACRB Small chillers has about 470 BACnet objects; about 290 are diagnostic binary inputs. AIs cover water temperatures and pressures, compressor drive (AFD) data, free cooling and power metering. The BAS writes chilled water setpoint, demand limit, pump setpoints, mode, lockouts and auto/stop.

This page lists 468 BACnet objects for the Trane Symbio 800 ACRB Small (UC800) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 ACRB Small (UC800)
Equipment
Air-cooled chiller controller
Equipment type
Chillers
BACnet objects
468 (13 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025
Source document
Symbio 800 Integration Points List BACnet - ACRB Small (UC800) · BAS-PTS025A-EN · rev. 12/06/2024
Download CSV 468 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 ACRB Small (UC800)

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10102Chiller Auto Stop Command BASBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10103Chiller Running StateChiller on/off statusRead
BI 10101Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10102Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10185Actual Running CapacityActual running capacity in percentRead
BI 10109Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10102 Chiller Auto Stop Command BAS (Stop/Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10120 External Auto Stop Status reports the hardwired external auto/stop input, and BI 10100 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

Network setup

Watch out for

Trane Symbio 800 ACRB Small (UC800) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

468 of 468 shown
Type
Access
Show
Trane Symbio 800 ACRB Small (UC800) BACnet Points List
DescriptionStates
AI10100Active Chilled Water SetpointTemperatureRead
AI10101Evaporator Entering Water TemperatureTemperatureRead
AImin10102Evaporator Leaving Water TemperatureTemperatureRead
AI10103Calculated Chiller CapacityPower, CoolingRead
AI10104Active Demand Limit SetpointPercentageRead
AI10105Unit Power ConsumptionPower, ElectricalRead
AI10106Outdoor Air TemperatureTemperatureRead
AI10107Evaporator Refrigerant Gauge Pressure Circuit 1Evaporator Refrigerant Gauge Pressure Ckt1Pressure, FluidicRead
AI10108Condenser Refrigerant Gauge Pressure Circuit 1Condenser Refrigerant Gauge Pressure Ckt1Pressure, FluidicRead
AI10109Differential Refrigerant Pressure Circuit 1Differential Refrigerant Pressure Ckt1Pressure, FluidicRead
AI10110Evaporator Saturated Refrigerant Temperature Circuit 1Evaporator Saturated Rfgt Temp Ckt1TemperatureRead
AI10111Condenser Saturated Refrigerant Temperature Circuit 1Condenser Saturated Rfgt Temp Ckt1TemperatureRead
AI10112Evaporator Refrigerant Gauge Pressure Circuit 2Evaporator Refrigerant Gauge Pressure Ckt2Pressure, FluidicRead
AI10113Condenser Refrigerant Gauge Pressure Circuit 2Condenser Refrigerant Gauge Pressure Ckt2Pressure, FluidicRead
AI10114Differential Refrigerant Pressure Circuit 2Differential Refrigerant Pressure Ckt2Pressure, FluidicRead
AI10115Evaporator Saturated Refrigerant Temperature Circuit 2Evaporator Saturated Rfgt Temp Ckt2TemperatureRead
AI10116Condenser Saturated Refrigerant Temperature Circuit 2Condenser Saturated Rfgt Temp Ckt2TemperatureRead
AI10117Refrigerant Discharge Temperature - Compressor 1ADischarge Temperature Cprsr1ATemperatureRead
AI10118Oil Gauge Pressure - Compressor 1APressure, FluidicRead
AI10119Refrigerant Discharge Temperature - Compressor 2ADischarge Temperature Cprsr2ATemperatureRead
AI10120Oil Gauge Pressure - Compressor 2AOil Gauge Pressure Cprsr2APressure, FluidicRead
AI10121Air Flow Percentage Circuit 1Air Flow Ckt1PercentageRead
AI10122Air Flow Percentage Circuit 2Air Flow Ckt2PercentageRead
AI10123Starts - Compressor 1AStarts Cprsr1ARead
AI10124Run Time - Compressor 1ARunning Time Cprsr1ARead
AI10125Compressor 1A Speed StatusPercent Speed Cprsr1APercentageRead
AI10126Motor Winding Temperature 1 Circuit 1Winding Temp #1 Motor 1ATemperatureRead
AI10127Motor Winding Temperature 2 Circuit 1Winding Temp #2 Motor 1ATemperatureRead
AI10128Drive Motor Current U RLA Compressor 1AMotor Current U % RLA AFD 1APercentageRead
AI10129Drive Motor Current V RLA Compressor 1AMotor Current V % RLA AFD 1APercentageRead
AI10130Drive Motor Current W RLA Compressor 1AMotor Current W % RLA AFD 1APercentageRead
AI10131Drive Motor Average Current RLA Compressor 1AAverage Motor Current % RLA AFD 1APercentageRead
AI10132Drive Motor Current U Compressor 1AMotor Current U AFD 1ACurrentRead
AI10133Drive Motor Current V Compressor 1AMotor Current V AFD 1ACurrentRead
AI10134Drive Motor Current W Compressor 1AMotor Current W AFD 1ACurrentRead
AI10135Drive Motor Voltage UV Circuit 1Motor Voltage UV AFD 1AVoltageRead
AI10136Drive Motor Voltage VW Circuit 1Motor Voltage VW AFD 1AVoltageRead
AI10137Drive Motor Voltage WU Circuit 1Motor Voltage WU AFD 1AVoltageRead
AI10138Drive Motor Average Voltage Circuit 1Average Motor Voltage AFD 1AVoltageRead
AI10139Drive DC Bus Voltage Circuit 1DC Bus Voltage AFD 1AVoltageRead
AI10140Drive Output Power Circuit 1Output Power AFD 1APower, ElectricalRead
AI10141Drive Input Power Circuit 1Input Power AFD 1APower, ElectricalRead
AI10142Drive Line Average Voltage Circuit 1Average Input Voltage AFD 1AVoltageRead
AI10143Drive Average Line Current Circuit 1Average Input Current AFD 1ACurrentRead
AI10144Drive Line Frequency Circuit 1Estimated Input Frequency AFD 1ARead
AI10145AFD Frequency Circuit 1Stator Frequency AFD 1ARead
AI10146AFD Transistor Temperature Circuit 1Transistor Temperature AFD 1ATemperatureRead
AI10147Drive Inverter Base Temperature Circuit 1Inverter Base Temperature AFD 1ATemperatureRead
AI10148Drive Rectifier Base Temperature Circuit 1Rectifier Base Temperature AFD 1ATemperatureRead
AI10149Starts - Compressor 2AStarts Cprsr2ARead
AI10150Run Time - Compressor 2ARunning Time Cprsr2ARead
AI10151Compressor 2A Speed StatusPercent Speed Cprsr2APercentageRead
AI10152Motor Winding Temperature 1 Circuit 2Winding Temp #1 Motor 2ATemperatureRead
AI10153Motor Winding Temperature 2 Circuit 2Winding Temp #2 Motor 2ATemperatureRead
AI10154Drive Motor Current U RLA Compressor 2AMotor Current U % RLA AFD 2APercentageRead
AI10155Drive Motor Current V RLA Compressor 2AMotor Current V % RLA AFD 2APercentageRead
AI10156Drive Motor Current W RLA Compressor 2AMotor Current W % RLA AFD 2APercentageRead
AI10157Drive Motor Average Current RLA Compressor 2AAverage Motor Current % RLA AFD 2APercentageRead
AI10158Drive Motor Current U Compressor 2AMotor Current U AFD 2ACurrentRead
AI10159Drive Motor Current V Compressor 2AMotor Current V AFD 2ACurrentRead
AI10160Drive Motor Current W Compressor 2AMotor Current W AFD 2ACurrentRead
AI10161Drive Motor Voltage UV Circuit 2Motor Voltage UV AFD 2AVoltageRead
AI10162Drive Motor Voltage VW Circuit 2Motor Voltage VW AFD 2AVoltageRead
AI10163Drive Motor Voltage WU Circuit 2Motor Voltage WU AFD 2AVoltageRead
AI10164Drive Motor Average Voltage Circuit 2Average Motor Voltage AFD 2AVoltageRead
AI10165Drive DC Bus Voltage Circuit 2DC Bus Voltage AFD 2AVoltageRead
AI10166Drive Output Power Circuit 2Output Power AFD 2APower, ElectricalRead
AI10167Drive Input Power Circuit 2Input Power AFD 2APower, ElectricalRead
AI10168Drive Line Average Voltage Circuit 2Average Input Voltage AFD 2AVoltageRead
AI10169Drive Average Line Current Circuit 2Average Input Current AFD 2ACurrentRead
AI10170Drive Line Frequency Circuit 2Estimated Input Frequency AFD 2ARead
AI10171AFD Frequency Circuit 2Stator Frequency AFD 2ARead
AI10172AFD Transistor Temperature Circuit 2Transistor Temperature AFD 2ATemperatureRead
AI10173Drive Inverter Base Temperature Circuit 2Inverter Base Temperature AFD 2ATemperatureRead
AI10174Drive Rectifier Base Temperature Circuit 2Rectifier Base Temperature AFD 2ATemperatureRead
AI10175Number Of CircuitsRead
AI10176Number Of Compressors Circuit 1Read
AI10177Number Of Compressors Circuit 2Read
AI10178Free Cooling Capacity StatusFree Cooling CapacityPercentageRead
AI10179Free Cooling Entering Water TemperatureTemperatureRead
AI10180Energy Consumption LifetimeEnergy, ElectricalRead
AI10181Energy ConsumptionEnergy, ElectricalRead
AI10182Unit Source IDLast Logged Diagnostic Spec BASRead
AI10183Chiller Design CapacityPower, CoolingRead
AI10184Active Cool/Heat Setpoint TemperatureActive Chilled Water SetpointTemperatureRead
AImin10185Actual Running CapacityChiller PowerPercentageRead
AI10186Evaporator Water Flow RateApproximate Evaporator Water FlowFlow, FluidicRead
AI10187Evaporator Differential Water PressurePressure, FluidicRead
AI10188Entering Evaporator Water Gauge PressureEvaporator Entering Water Gauge PressurePressure, FluidicRead
AI10189Leaving Evaporator Water Gauge PressureEvaporator Leaving Water Gauge PressurePressure, FluidicRead
AI10190Evaporator Water Pump Speed CommandPercentageRead
AI10191Evaporator Water Pump Speed FeedbackPercentageRead
AI10192Evaporator Water Pump Speed Setpoint ActiveActive Evap Water Pump Speed SetptPercentageRead
AI10193Evaporator Water Pump Flow Rate Setpt ActiveActive Evap Water Flow Rate SetptFlow, FluidicRead
AI10194Discharge Superheat Compressor 1ADischarge Superheat Cprsr 1ATemperature, DeltaRead
AI10195Discharge Superheat Compressor 2ADischarge Superheat Cprsr 2ATemperature, DeltaRead
AI10196Current L1Meter Line Current L1CurrentRead
AI10197Current L2Meter Line Current L2CurrentRead
AI10198Current L3Meter Line Current L3CurrentRead
AI10199Average CurrentMeter Average Line CurrentCurrentRead
AI10200Voltage L1-L2Meter Line Voltage L1-L2VoltageRead
AI10201Voltage L2-L3Meter Line Voltage L2-L3VoltageRead
AI10202Voltage L1-L3Meter Line Voltage L1-L3VoltageRead
AI10203Average Voltage L-LMeter Average Line VoltageVoltageRead
AI10204Line FrequencyUnit Line FrequencyRead
AI10205Power FactorUnit Power FactorRead
AI10206Unit Power DemandChiller Power DemandPower, ElectricalRead
AI10207Free Cooling Entering Glycol TemperatureTemperatureRead
AI10208Free Cooling Leaving Glycol TemperatureTemperatureRead
AI10209Free Cooling Glycol PressurePressure, FluidicRead
AI10210Free Cooling Valve Position StatusFree Cooling Valve Percent OpenPercentageRead
AI10211Free Cooling Bypass Valve Position StatusFree Cooling Bypass Valve Percent OpenPercentageRead
AI10212Free Cooling Pump Override Time RemainingRead
AI10213Free Cooling Target OffsetTemperature, DeltaRead
AI10214Free Cooling Dedicated Fans AirflowFree Cooling Dedicated Fan Air FlowPercentageRead
AI10215Free Cooling Waterside Bypass Valve StatusFree Cooling Waterside Byp Vlv Pct OpenPercentageRead
AI10216Evaporator Refrigerant Pressure Circuit 1Evaporator Refrigerant Absolute Pressure Ckt1Pressure, FluidicRead
AI10217Condenser Refrigerant Pressure Circuit 1Condenser Refrigerant Absolute Pressure Ckt1Pressure, FluidicRead
AI10218Evaporator Refrigerant Pressure Circuit 2Evaporator Refrigerant Absolute Pressure Ckt2Pressure, FluidicRead
AI10219Condenser Refrigerant Pressure Circuit 2Condenser Refrigerant Absolute Pressure Ckt2Pressure, FluidicRead
AI10220Oil Pressure - Compressor 1AOil Absolute Pressure - Compressor 1APressure, FluidicRead
AI10221Oil Pressure - Compressor 2AOil Absolute Pressure Cprsr2APressure, FluidicRead
AI10222Entering Evaporator Water PressureEvaporator Entering Water Absolute PressurePressure, FluidicRead
AI10223Leaving Evaporator Water PressureEvaporator Leaving Water Absolute PressurePressure, FluidicRead
AI10224AFD Coolant Supply Temperature Compressor 1ADrive Cooling Supply Temperature Ckt1TemperatureRead
AI10225AFD Coolant Supply Temperature Compressor 2ADrive Cooling Supply Temperature Ckt2TemperatureRead
AI10226Evaporator Approach Temperature Circuit 1Evaporator Approach Temperature Ckt1Temperature, DeltaRead
AI10227Evaporator Approach Temperature Circuit 2Evaporator Approach Temperature Ckt2Temperature, DeltaRead
AVmin10100Chilled Water SetpointTemperatureWrite
AVmin10101Demand Limit SetpointPercentageWrite
AV10102Evaporator Water Pump Flow Rate Setpt BASBAS Evap Water Flow Rate SetptFlow, FluidicWrite
AV10103Evaporator Water Pump Speed Setpt BASBAS Evap Water Pump Speed SetptPercentageWrite
BI10100Run EnableRead
BImin10101Local Setpoint ControlRead
BI10102Limit Mode Relay StatusRead
BImin10103Chiller Running StateRead
BI10104Maximum CapacityMaximum Capacity RelayRead
BI10105Evaporator Water Pump CommandRead
BI10106Evaporator Water Flow StatusRead
BI10107Manual Override ExistsRead
BI10108Emergency StopRead
BImin10109Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10110Diagnostic Shutdown PresentRead0 = Normal, 1 = In Alarm
BI10111Diagnostic: Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10112Diagnostic: Local Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10113Diagnostic Present: InformationRead0 = Normal, 1 = In Alarm
BI10114Diagnostic Present: AdvisoryRead0 = Normal, 1 = In Alarm
BI10115Diagnostic Present: CriticalRead0 = Normal, 1 = In Alarm
BI10116Diagnostic Present: Service RequiredRead0 = Normal, 1 = In Alarm
BI10117Compressor 1A Running StatusRunning Status Cprsr1ARead
BI10118Compressor 2A Running StatusRunning Status Cprsr2ARead
BI10119Free Cooling ActiveRead
BI10120External Auto Stop StatusExternal Auto StopRead
BI10121Front Panel Auto Stop StatusFront Panel Auto/StopRead
BI10122Noise Reduction Request ActiveRead
BI10123Evaporator Water Pump 1 Inverter Running StatusEvap Water Pump 1 Inverter Running StatusRead
BI10124Evaporator Water Pump 1 Fault StatusRead
BI10125Circuit 1 Cooling AvailableCircuit is available to startRead
BI10126Circuit 2 Cooling AvailableCircuit is available to startRead
BI10127Oil Sensor Circuit 1Oil Loss Level Sensor Ckt1Read
BI10128Oil Sensor Circuit 2Oil Loss Level Sensor Ckt2Read
BI10129Free Cooling Pump Command StatusFree Cooling Pump CommandRead
BI10130Free Cooling Front Panel Command StatusFront Panel Free Cooling CommandRead
BI10131Free Cooling Glycol Flow StatusRead
BI11000Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11001Diagnostic: Check ClockRead0 = Normal, 1 = In Alarm
BI11002Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BI11003Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11004Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11005Diagnostic: Software Error 1001: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11006Diagnostic: Software Error 1002: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11007Diagnostic: Software Error 1003: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11009Comm Loss: Energy MeterRead0 = Normal, 1 = In Alarm
BI11010Diagnostic: Energy Meter Write Command FailureRead0 = Normal, 1 = In Alarm
BI11011Comm Loss: Condenser Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11012Comm Loss: Condenser Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11013Comm Loss: Suction Rfgt Pressure, Ckt1Read0 = Normal, 1 = In Alarm
BI11014Comm Loss: Suction Rfgt Pressure, Ckt2Read0 = Normal, 1 = In Alarm
BI11015Diagnostic: Pumpdown Terminated - Ckt1Read0 = Normal, 1 = In Alarm
BI11016Diagnostic: Pumpdown Terminated - Ckt2Read0 = Normal, 1 = In Alarm
BI11017Diagnostic: Condenser Rfgt Pressure Transducer - Ckt1Read0 = Normal, 1 = In Alarm
BI11018Diagnostic: Condenser Rfgt Pressure Transducer - Ckt2Read0 = Normal, 1 = In Alarm
BI11019Diagnostic: Suction Pressure Rfgt Transducer - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11020Diagnostic: Suction Pressure Rfgt Transducer - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11021Diagnostic: Evap Spillover Liquid Level Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11022Diagnostic: Evap Spillover Liquid Level Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11023Comm Loss: Evap Rfgt Liquid Level - Ckt1Read0 = Normal, 1 = In Alarm
BI11024Comm Loss: Evap Rfgt Liquid Level - Ckt2Read0 = Normal, 1 = In Alarm
BI11025Comm Loss: External Ckt Lockout - Ckt1Read0 = Normal, 1 = In Alarm
BI11026Comm Loss: External Ckt Lockout - Ckt2Read0 = Normal, 1 = In Alarm
BI11027Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt1Read0 = Normal, 1 = In Alarm
BI11028Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt2Read0 = Normal, 1 = In Alarm
BI11029Comm Loss: Evap Rfgt Pool Temp, Ckt1Read0 = Normal, 1 = In Alarm
BI11030Comm Loss: Evap Rfgt Pool Temp, Ckt2Read0 = Normal, 1 = In Alarm
BI11031Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1Read0 = Normal, 1 = In Alarm
BI11032Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2Read0 = Normal, 1 = In Alarm
BI11033Diagnostic: Drive Cooling Supply Temp Sensor Ckt1Read0 = Normal, 1 = In Alarm
BI11034Diagnostic: Drive Cooling Supply Temp Sensor Ckt2Read0 = Normal, 1 = In Alarm
BI11035Comm Loss: Drive Cooling Supply Temp Ckt1Read0 = Normal, 1 = In Alarm
BI11036Comm Loss: Drive Cooling Supply Temp Ckt2Read0 = Normal, 1 = In Alarm
BI11037Comm Loss: Drive Cooling Bypass Valve Ckt1Read0 = Normal, 1 = In Alarm
BI11038Comm Loss: Drive Cooling Bypass Valve Ckt2Read0 = Normal, 1 = In Alarm
BI11039Comm Loss: Drive Cooling Inline Valve Ckt1Read0 = Normal, 1 = In Alarm
BI11040Comm Loss: Drive Cooling Inline Valve Ckt2Read0 = Normal, 1 = In Alarm
BI11041Comm Loss: Evaporator Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11042Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11043Comm Loss: Off-cycle Freeze Prot RelayRead0 = Normal, 1 = In Alarm
BI11044Comm Loss: Evaporator Pump Speed CommandRead0 = Normal, 1 = In Alarm
BI11045Comm Loss: Evaporator Pump Speed FeedbackRead0 = Normal, 1 = In Alarm
BI11046Comm Loss: Evaporator Pump Inverter Running StatusRead0 = Normal, 1 = In Alarm
BI11047Comm Loss: Evaporator Pump Fault InputRead0 = Normal, 1 = In Alarm
BI11048Diagnostic: Evaporator Water Pump FaultRead0 = Normal, 1 = In Alarm
BI11049Diagnostic: Evaporator Water Pump Speed FeedbackRead0 = Normal, 1 = In Alarm
BI11050Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11051Comm Loss: Emergency StopRead0 = Normal, 1 = In Alarm
BI11052Diagnostic: Emergency StopRead0 = Normal, 1 = In Alarm
BI11053Diagnostic: External Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11054Comm Loss: Ext Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11055Comm Loss: Op Status Programmable RelaysRead0 = Normal, 1 = In Alarm
BI11056Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11057Comm Loss: Ext Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11059Comm Loss: Chiller % Capacity OutputRead0 = Normal, 1 = In Alarm
BI11060Comm Loss: Ext Noise Reduction RequestRead0 = Normal, 1 = In Alarm
BI11061Diagnostic: Low Evaporator Rfgt Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11062Diagnostic: Low Evaporator Rfgt Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11063Diagnostic: Low Evaporator Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11064Diagnostic: Low Evaporator Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11065Diagnostic: High Differential Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11066Diagnostic: High Differential Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11067Diagnostic: High Refrigerant Pressure Ratio - Ckt1Read0 = Normal, 1 = In Alarm
BI11068Diagnostic: High Refrigerant Pressure Ratio - Ckt2Read0 = Normal, 1 = In Alarm
BI11069Diagnostic: Low Evaporator Temp (Unit Off) - Ckt1Read0 = Normal, 1 = In Alarm
BI11070Diagnostic: Low Evaporator Temp (Unit Off) - Ckt2Read0 = Normal, 1 = In Alarm
BI11071Diagnostic: Evaporator Approach Error - Ckt1Read0 = Normal, 1 = In Alarm
BI11072Diagnostic: Evaporator Approach Error - Ckt2Read0 = Normal, 1 = In Alarm
BI11073Diagnostic: Low Drive Cooling Supply Temperature - Ckt1Read0 = Normal, 1 = In Alarm
BI11074Diagnostic: Low Drive Cooling Supply Temperature - Ckt2Read0 = Normal, 1 = In Alarm
BI11075Diagnostic: High Evaporator Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11076Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11077Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11078Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11079Diagnostic: High Pressure Cutout - Cprsr 1ARead0 = Normal, 1 = In Alarm
BI11080Diagnostic: High Pressure Cutout - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11081Diagnostic: Excessive Condenser Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11082Diagnostic: Excessive Condenser Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11083Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11084Comm Loss: Ice Building Status RelayRead0 = Normal, 1 = In Alarm
BI11085Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11086Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11087Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11088Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11089Diagnostic: Low Evaporator Water Temp (Unit On)Read0 = Normal, 1 = In Alarm
BI11090Diagnostic: Low Evaporator Water Temp (Unit Off)Read0 = Normal, 1 = In Alarm
BI11091Diagnostic: Evap Water Flow (Entering Water Temp)Read0 = Normal, 1 = In Alarm
BI11092Comm Loss: Evap Diff Water PressureRead0 = Normal, 1 = In Alarm
BI11093Diagnostic: Evaporator Diff Water Pressure XdcrRead0 = Normal, 1 = In Alarm
BI11094Diagnostic: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11095Diagnostic: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11096Comm Loss: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11097Comm Loss: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11098Diagnostic: Low Evaporator Water FlowRead0 = Normal, 1 = In Alarm
BI11099Diagnostic: Low Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11100Diagnostic: Low Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11101Diagnostic: Low Oil Return or AFD Cooling - Ckt1Read0 = Normal, 1 = In Alarm
BI11102Diagnostic: Low Oil Return or AFD Cooling - Ckt2Read0 = Normal, 1 = In Alarm
BI11103Comm Loss: Fan Inverter Fault, Ckt1Read0 = Normal, 1 = In Alarm
BI11104Comm Loss: Fan Inverter Fault, Ckt2Read0 = Normal, 1 = In Alarm
BI11105Comm Loss: Fan Inverter Speed Command, Ckt1Read0 = Normal, 1 = In Alarm
BI11106Comm Loss: Fan Inverter Speed Command, Ckt2Read0 = Normal, 1 = In Alarm
BI11107Diagnostic: Condenser Fan Inverter Fault - Ckt1Read0 = Normal, 1 = In Alarm
BI11108Diagnostic: Condenser Fan Inverter Fault - Ckt2Read0 = Normal, 1 = In Alarm
BI11109Comm Loss: Condenser Fan Enable, Ckt1Read0 = Normal, 1 = In Alarm
BI11110Comm Loss: Condenser Fan Enable, Ckt2Read0 = Normal, 1 = In Alarm
BI11111Comm Loss: Fan Inv Spd Cmd, Shrd Ckt1&2Read0 = Normal, 1 = In Alarm
BI11112Comm Loss: Cond Fan Enbl Shared Ckt 1&2Read0 = Normal, 1 = In Alarm
BI11113Comm Loss: Expansion Valve, Ckt1Read0 = Normal, 1 = In Alarm
BI11114Comm Loss: Expansion Valve, Ckt2Read0 = Normal, 1 = In Alarm
BI11115Diagnostic: Oil Analysis Recommended - Ckt1Read0 = Normal, 1 = In Alarm
BI11116Diagnostic: Oil Analysis Recommended - Ckt2Read0 = Normal, 1 = In Alarm
BI11117Diagnostic: Oil Filter Change Recommended - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11118Diagnostic: Oil Filter Change Recommended - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11119Diagnostic: Starts or Hours Modified - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11120Comm Loss: Var Vi Valve - Cprsr 1ARead0 = Normal, 1 = In Alarm
BI11121Diagnostic: Starts or Hours Modified - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11122Comm Loss: Var Vi Valve - Cprsr 2ARead0 = Normal, 1 = In Alarm
BI11123Diagnostic: No Differential Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11124Diagnostic: No Differential Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11125Diagnostic: Low Differential Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11126Diagnostic: Low Differential Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11127Diagnostic: Oil Flow Protection Fault - Ckt1Read0 = Normal, 1 = In Alarm
BI11128Diagnostic: Oil Flow Protection Fault - Ckt2Read0 = Normal, 1 = In Alarm
BI11129Diagnostic: Low Oil Flow - Cprsr 1ARead0 = Normal, 1 = In Alarm
BI11130Diagnostic: Low Oil Flow - Cprsr 2ARead0 = Normal, 1 = In Alarm
BI11131Comm Loss: Cprsr Discharge Rfgt Temp, Ckt1Read0 = Normal, 1 = In Alarm
BI11132Comm Loss: Cprsr Discharge Rfgt Temp, Ckt2Read0 = Normal, 1 = In Alarm
BI11133Diagnostic: Discharge Rfgt Temp Sensor - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11134Diagnostic: Discharge Rfgt Temp Sensor - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11135Comm Loss: Oil Pressure, Ckt1Read0 = Normal, 1 = In Alarm
BI11136Comm Loss: Oil Pressure, Ckt2Read0 = Normal, 1 = In Alarm
BI11137Diagnostic: Oil Pressure Transducer - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11138Diagnostic: Oil Pressure Transducer - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11139Diagnostic: Low Discharge Superheat - Ckt1Read0 = Normal, 1 = In Alarm
BI11140Diagnostic: Low Discharge Superheat - Ckt2Read0 = Normal, 1 = In Alarm
BI11141Diagnostic: Very Low Evaporator Rfgt Pressure - Ckt1Read0 = Normal, 1 = In Alarm
BI11142Diagnostic: Very Low Evaporator Rfgt Pressure - Ckt2Read0 = Normal, 1 = In Alarm
BI11143Comm Loss: Oil Loss Level Sensor Input, Ckt1Read0 = Normal, 1 = In Alarm
BI11144Comm Loss: Oil Loss Level Sensor Input, Ckt2Read0 = Normal, 1 = In Alarm
BI11145Diagnostic: Loss of Oil (Stopped) - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11146Diagnostic: Loss of Oil (Stopped) - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11147Diagnostic: Loss of Oil (Running) - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11148Diagnostic: Loss of Oil (Running) - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11149Diagnostic: High Discharge Temperature - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11150Diagnostic: High Discharge Temperature - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11151Diagnostic: High Motor Winding Temperature - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11152Diagnostic: High Motor Winding Temperature - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11153Comm Loss: Winding Temp 1, Cprsr1ARead0 = Normal, 1 = In Alarm
BI11154Comm Loss: Winding Temp 1, Cprsr2ARead0 = Normal, 1 = In Alarm
BI11155Comm Loss: Winding Temp 2, Cprsr1ARead0 = Normal, 1 = In Alarm
BI11156Comm Loss: Winding Temp 2, Cprsr2ARead0 = Normal, 1 = In Alarm
BI11157Diagnostic: Motor Winding Temp Sensor - Cprsr1ARead0 = Normal, 1 = In Alarm
BI11158Diagnostic: Motor Winding Temp Sensor - Cprsr2ARead0 = Normal, 1 = In Alarm
BI11159Diagnostic: Failure to Arm or Start - AFD 1ARead0 = Normal, 1 = In Alarm
BI11160Diagnostic: Failure to Arm or Start - AFD 2ARead0 = Normal, 1 = In Alarm
BI11161Comm Loss: AFD 1ARead0 = Normal, 1 = In Alarm
BI11162Comm Loss: AFD 2ARead0 = Normal, 1 = In Alarm
BI11163Diagnostic: Unexpected Shutdown - AFD1ARead0 = Normal, 1 = In Alarm
BI11164Diagnostic: Unexpected Shutdown - AFD2ARead0 = Normal, 1 = In Alarm
BI11165Diagnostic: Interrupt Failure - AFD1ARead0 = Normal, 1 = In Alarm
BI11166Diagnostic: Interrupt Failure - AFD2ARead0 = Normal, 1 = In Alarm
BI11168Diagnostic: AFD 1A DSP Board Over TempRead0 = Normal, 1 = In Alarm
BI11169Diagnostic: AFD 2A DSP Board Over TempRead0 = Normal, 1 = In Alarm
BI11170Diagnostic: AFD 1A DSP Board Initialization FailureRead0 = Normal, 1 = In Alarm
BI11171Diagnostic: AFD 2A DSP Board Initialization FailureRead0 = Normal, 1 = In Alarm
BI11172Diagnostic: AFD 1A DSP Board ID ErrorRead0 = Normal, 1 = In Alarm
BI11173Diagnostic: AFD 2A DSP Board ID ErrorRead0 = Normal, 1 = In Alarm
BI11174Diagnostic: AFD 1A Non-Volatile Memory FailureRead0 = Normal, 1 = In Alarm
BI11175Diagnostic: AFD 2A Non-Volatile Memory FailureRead0 = Normal, 1 = In Alarm
BI11176Diagnostic: AFD 1A A/D Calibration ErrorRead0 = Normal, 1 = In Alarm
BI11177Diagnostic: AFD 2A A/D Calibration ErrorRead0 = Normal, 1 = In Alarm
BI11178Diagnostic: AFD 1A Voltage Transient Protection LossRead0 = Normal, 1 = In Alarm
BI11179Diagnostic: AFD 2A Voltage Transient Protection LossRead0 = Normal, 1 = In Alarm
BI11180Diagnostic: AFD 1A Watchdog Timer OverflowRead0 = Normal, 1 = In Alarm
BI11181Diagnostic: AFD 2A Watchdog Timer OverflowRead0 = Normal, 1 = In Alarm
BI11184Diagnostic: AFD 1A Comm Loss: Main ProcessorRead0 = Normal, 1 = In Alarm
BI11185Diagnostic: AFD 2A Comm Loss: Main ProcessorRead0 = Normal, 1 = In Alarm
BI11186Diagnostic: AFD 1A General FailureRead0 = Normal, 1 = In Alarm
BI11187Diagnostic: AFD 2A General FailureRead0 = Normal, 1 = In Alarm
BI11188Diagnostic: AFD 1A Gate Drive Module Comm LossRead0 = Normal, 1 = In Alarm
BI11189Diagnostic: AFD 2A Gate Drive Module Comm LossRead0 = Normal, 1 = In Alarm
BI11190Diagnostic: AFD 1A Gate Drive FaultRead0 = Normal, 1 = In Alarm
BI11191Diagnostic: AFD 2A Gate Drive FaultRead0 = Normal, 1 = In Alarm
BI11192Diagnostic: AFD 1A Over SpeedRead0 = Normal, 1 = In Alarm
BI11193Diagnostic: AFD 2A Over SpeedRead0 = Normal, 1 = In Alarm
BI11194Diagnostic: AFD 1A Motor Current OverloadRead0 = Normal, 1 = In Alarm
BI11195Diagnostic: AFD 2A Motor Current OverloadRead0 = Normal, 1 = In Alarm
BI11196Diagnostic: AFD 1A Ground FaultRead0 = Normal, 1 = In Alarm
BI11197Diagnostic: AFD 2A Ground FaultRead0 = Normal, 1 = In Alarm
BI11198Diagnostic: AFD 1A Output Phase LossRead0 = Normal, 1 = In Alarm
BI11199Diagnostic: AFD 2A Output Phase LossRead0 = Normal, 1 = In Alarm
BI11200Diagnostic: AFD 1A Low Rotor Flux FeedbackRead0 = Normal, 1 = In Alarm
BI11201Diagnostic: AFD 2A Low Rotor Flux FeedbackRead0 = Normal, 1 = In Alarm
BI11202Diagnostic: AFD 1A Bump FailureRead0 = Normal, 1 = In Alarm
BI11203Diagnostic: AFD 2A Bump FailureRead0 = Normal, 1 = In Alarm
BI11204Diagnostic: AFD 1A Compressor Start FailureRead0 = Normal, 1 = In Alarm
BI11205Diagnostic: AFD 2A Compressor Start FailureRead0 = Normal, 1 = In Alarm
BI11206Diagnostic: AFD 1A Instantaneous Current OverloadRead0 = Normal, 1 = In Alarm
BI11207Diagnostic: AFD 2A Instantaneous Current OverloadRead0 = Normal, 1 = In Alarm
BI11208Diagnostic: AFD 1A Desaturation DetectedRead0 = Normal, 1 = In Alarm
BI11209Diagnostic: AFD 2A Desaturation DetectedRead0 = Normal, 1 = In Alarm
BI11210Diagnostic: AFD 1A Current Sensor Self Test FailureRead0 = Normal, 1 = In Alarm
BI11211Diagnostic: AFD 2A Current Sensor Self Test FailureRead0 = Normal, 1 = In Alarm
BI11212Diagnostic: AFD 1A IGBT Self Test FailureRead0 = Normal, 1 = In Alarm
BI11213Diagnostic: AFD 2A IGBT Self Test FailureRead0 = Normal, 1 = In Alarm
BI11214Diagnostic: AFD 1A Gate Kill ActiveRead0 = Normal, 1 = In Alarm
BI11215Diagnostic: AFD 2A Gate Kill ActiveRead0 = Normal, 1 = In Alarm
BI11216Diagnostic: AFD 1A Load Inductor High TemperatureRead0 = Normal, 1 = In Alarm
BI11217Diagnostic: AFD 2A Load Inductor High TemperatureRead0 = Normal, 1 = In Alarm
BI11218Diagnostic: AFD 1A 12-Pulse or Auto Transf High TempRead0 = Normal, 1 = In Alarm
BI11219Diagnostic: AFD 2A 12-Pulse or Auto Transf High TempRead0 = Normal, 1 = In Alarm
BI11220Diagnostic: AFD 1A Inverter Heatsink Over TempRead0 = Normal, 1 = In Alarm
BI11221Diagnostic: AFD 2A Inverter Heatsink Over TempRead0 = Normal, 1 = In Alarm
BI11222Diagnostic: AFD 1A Rectifier Heatsink Over TempRead0 = Normal, 1 = In Alarm
BI11223Diagnostic: AFD 2A Rectifier Heatsink Over TempRead0 = Normal, 1 = In Alarm
BI11224Diagnostic: AFD 1A Estimated Junction Over TempRead0 = Normal, 1 = In Alarm
BI11225Diagnostic: AFD 2A Estimated Junction Over TempRead0 = Normal, 1 = In Alarm
BI11226Diagnostic: AFD 1A Gate Drive Board Over TempRead0 = Normal, 1 = In Alarm
BI11227Diagnostic: AFD 2A Gate Drive Board Over TempRead0 = Normal, 1 = In Alarm
BI11228Diagnostic: AFD 1A Bus Over VoltageRead0 = Normal, 1 = In Alarm
BI11229Diagnostic: AFD 2A Bus Over VoltageRead0 = Normal, 1 = In Alarm
BI11230Diagnostic: AFD 1A Bus Under VoltageRead0 = Normal, 1 = In Alarm
BI11231Diagnostic: AFD 2A Bus Under VoltageRead0 = Normal, 1 = In Alarm
BI11232Diagnostic: AFD 1A IMC 24V Low VoltageRead0 = Normal, 1 = In Alarm
BI11233Diagnostic: AFD 2A IMC 24V Low VoltageRead0 = Normal, 1 = In Alarm
BI11234Diagnostic: AFD 1A AHD Frequency Out of RangeRead0 = Normal, 1 = In Alarm
BI11235Diagnostic: AFD 2A AHD Frequency Out of RangeRead0 = Normal, 1 = In Alarm
BI11236Diagnostic: AFD 1A Bus Voltage Ripple Too HighRead0 = Normal, 1 = In Alarm
BI11237Diagnostic: AFD 2A Bus Voltage Ripple Too HighRead0 = Normal, 1 = In Alarm
BI11238Diagnostic: AFD 1A DSP Board Low Voltage FailureRead0 = Normal, 1 = In Alarm
BI11239Diagnostic: AFD 2A DSP Board Low Voltage FailureRead0 = Normal, 1 = In Alarm
BI11240Diagnostic: Failure to Arm or Hold - AFD 1ARead0 = Normal, 1 = In Alarm
BI11241Diagnostic: Failure to Arm or Hold - AFD 2ARead0 = Normal, 1 = In Alarm
BI11242Diagnostic: AFD 1A Loss of AHD Sync SignalRead0 = Normal, 1 = In Alarm
BI11243Diagnostic: AFD 2A Loss of AHD Sync SignalRead0 = Normal, 1 = In Alarm
BI11244Diagnostic: AFD 1A AHD Sync Signal ErrorRead0 = Normal, 1 = In Alarm
BI11245Diagnostic: AFD 2A AHD Sync Signal ErrorRead0 = Normal, 1 = In Alarm
BI11246Diagnostic: AFD 1A Excessive AHD InhibitRead0 = Normal, 1 = In Alarm
BI11247Diagnostic: AFD 2A Excessive AHD InhibitRead0 = Normal, 1 = In Alarm
BI11248Diagnostic: AFD 1A Gate Drive Low Voltage FailureRead0 = Normal, 1 = In Alarm
BI11249Diagnostic: AFD 2A Gate Drive Low Voltage FailureRead0 = Normal, 1 = In Alarm
BI11250Diagnostic: AFD 1A Temperature Sensor WarningRead0 = Normal, 1 = In Alarm
BI11251Diagnostic: AFD 2A Temperature Sensor WarningRead0 = Normal, 1 = In Alarm
BI11252Diagnostic: AFD 1A Motor ShortedRead0 = Normal, 1 = In Alarm
BI11253Diagnostic: AFD 2A Motor ShortedRead0 = Normal, 1 = In Alarm
BI11254Diagnostic: AFD 1A Over TemperatureRead0 = Normal, 1 = In Alarm
BI11255Diagnostic: AFD 2A Over TemperatureRead0 = Normal, 1 = In Alarm
BI11256Diagnostic: AFD 1A Precharge FaultRead0 = Normal, 1 = In Alarm
BI11257Diagnostic: AFD 2A Precharge FaultRead0 = Normal, 1 = In Alarm
BI11258Diagnostic: AFD 1A Input Phase LossRead0 = Normal, 1 = In Alarm
BI11259Diagnostic: AFD 2A Input Phase LossRead0 = Normal, 1 = In Alarm
BI11260Diagnostic: AFD 1A Motor FaultRead0 = Normal, 1 = In Alarm
BI11261Diagnostic: AFD 2A Motor FaultRead0 = Normal, 1 = In Alarm
BI11262Diagnostic: AFD 1A Customized Protection FaultRead0 = Normal, 1 = In Alarm
BI11263Diagnostic: AFD 2A Customized Protection FaultRead0 = Normal, 1 = In Alarm
BI11264Diagnostic: AFD 1A Input Transf or Filter Over TempRead0 = Normal, 1 = In Alarm
BI11265Diagnostic: AFD 2A Input Transf or Filter Over TempRead0 = Normal, 1 = In Alarm
BI11266Diagnostic: AFD 1A Loss Of Motor ControlRead0 = Normal, 1 = In Alarm
BI11267Diagnostic: AFD 2A Loss Of Motor ControlRead0 = Normal, 1 = In Alarm
BI11268Comm Loss: Free Cooling Entering Water TemperatureRead0 = Normal, 1 = In Alarm
BI11269Diagnostic: Free Cooling Entering Water TemperatureRead0 = Normal, 1 = In Alarm
BI11270Comm Loss: Free Cooling ValveRead0 = Normal, 1 = In Alarm
BI11271Comm Loss: Free Cooling Bypass ValveRead0 = Normal, 1 = In Alarm
BI11272Comm Loss: Free Cooling Entering Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11273Diagnostic: Free Cooling Entering Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11274Comm Loss: Free Cooling Leaving Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11275Diagnostic: Free Cooling Leaving Glycol TemperatureRead0 = Normal, 1 = In Alarm
BI11276Comm Loss: Free Cooling PumpRead0 = Normal, 1 = In Alarm
BI11277Diagnostic: Low Glycol Temp Free CoolingRead0 = Normal, 1 = In Alarm
BI11278Diagnostic: Free Cooling Glycol Temperature Equalization OverdueRead0 = Normal, 1 = In Alarm
BI11279Diagnostic: Free Cooling Glycol Flow OverdueRead0 = Normal, 1 = In Alarm
BI11280Comm Loss: Free Cooling Glycol Flow SwitchRead0 = Normal, 1 = In Alarm
BI11281Comm Loss: Free Cooling Glycol PressureRead0 = Normal, 1 = In Alarm
BI11282Diagnostic: Free Cooling Glycol PressureRead0 = Normal, 1 = In Alarm
BI11283Diagnostic: Low Glycol Pressure Free CoolingRead0 = Normal, 1 = In Alarm
BI11284Comm Loss: Free Cooling Glycol Pump FaultRead0 = Normal, 1 = In Alarm
BI11285Diagnostic: Free Cooling Glycol Pump FaultRead0 = Normal, 1 = In Alarm
BI11286Diagnostic: Free Cooling Glycol Flow LostRead0 = Normal, 1 = In Alarm
BI11287Comm Loss: Free Cooling Waterside Bypass ValveRead0 = Normal, 1 = In Alarm
BI11288Comm Loss: Free Cooling Dedicated Fan EnableRead0 = Normal, 1 = In Alarm
BI11289Comm Loss: Free Cooling Dedicated Fan Inverter Speed CommandRead0 = Normal, 1 = In Alarm
BI11290Comm Loss: Free Cooling Dedicated Fan Inverter FaultRead0 = Normal, 1 = In Alarm
BI11291Diagnostic: Free Cooling Dedicated Fan Inverter FaultRead0 = Normal, 1 = In Alarm
BI11292Diagnostic: Energy Meter Write Value FailureRead0 = Normal, 1 = In Alarm
BV10100Reset DiagnosticWrite
BV10101Noise Reduction Request BASWrite
BVmin10102Chiller Auto Stop Command BASWrite
BV10103Free Cooling Auto Stop Command BASWrite
BV10104Free Cooling Compressor LockoutWrite
BV10105Circuit 1 Lockout BASBAS Lockout of Circuit 1Write
BV10106Circuit 2 Lockout BASBAS Lockout of Circuit 2Write
BV10107Energy Consumption ResetWrite
MI10100Running ModeChiller Running StatusReadChiller Off, Chiller In Start Mode, Chiller In Run Mode, Chiller In Pre-Shutdown Mode, Chiller In Service Mode
MI10101Operating ModeReadCool, Heat, Ice Making, Free Cooling
MI10102Chiller Setpoint SourceSetpoint SourceReadBAS, External, Front Panel
MI10103Refrigerant TypeReadR-11, R-12, R-22, R-123, R-134a, R-407C, R-410A, R-113, R-114, R-500, R-502, R-404A, R-513A, R-1233zd(E), R-514A, R-1234ze(E)
MI10104Cooling TypeReadWater Cooled, Air Cooled
MI10105Manufacture LocationReadField Applied, La Crosse, Pueblo, Charmes, Rushville, Macon, Waco, Lexington, Forsyth, Clarksville, Ft. Smith, Penang, Colchester, Curitiba, Taicang, Taiwan, Epinal, Golbey
MI10106Model Information [GEN2]Model InformationReadCVHF, CVGF, CVHS, RTAE, RTAF, RTHA, RTHB, RTHC, RTHD, RTWE, CTVD, CVR, CVHH, CDHH, VMAX, GVAF, RTWF, RTHF, RTAC, CVHM, RTAG, CGAF, RTXG, GVWF, HDWA, CMAC, IPAK, CXAF, ACSA, RTSF, HSWA, ACRA, RTEG, ACXA, CMAF, ACRB Large, ACRB Small
MVmin10100Chiller Mode Command BASWriteCool, Heat, Ice Making, Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 ACRB Small (UC800) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 ACRB Small (UC800)

How many BACnet points does the Trane Symbio 800 ACRB Small (UC800) have?

This list has 468 BACnet objects: 128 analog inputs, 4 analog values, 320 binary inputs, 8 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 ACRB Small (UC800) BACnet points are writable?

13 of the 468 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 ACRB Small (UC800) BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - ACRB Small (UC800) (BAS-PTS025A-EN), revision 12/06/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS025A-EN_12062024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 ACRB Small (UC800)?

Start with BV 10102 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10103 Chiller Running State (Chiller on/off status); BI 10101 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10102 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10185 Actual Running Capacity (Actual running capacity in percent); BI 10109 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 ACRB Small (UC800)?

BV 10102 Chiller Auto Stop Command BAS (Stop/Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10120 External Auto Stop Status reports the hardwired external auto/stop input, and BI 10100 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.

How do I check these points on the real Symbio 800 ACRB Small (UC800)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - ACRB Small (UC800) · BAS-PTS025A-EN · rev. 12/06/2024. Object names, instances and units are reproduced as published; descriptions are our own.