Water-cooled screw chiller controller · BACnet points list

Trane Symbio 800 Series R RTWD BACnet points list

Updated 28 October 2026

Short answer

RTWD chillers with Symbio 800 publish about 685 BACnet objects; roughly three-quarters are diagnostic binary inputs. Operating data such as water temperatures, refrigerant pressures, compressor starts and run hours are AIs. Setpoints, lockouts, pump requests and the auto/stop command are AV/BV/MV objects.

This page lists 685 BACnet objects for the Trane Symbio 800 Series R RTWD — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.

Manufacturer
Trane
Model
Symbio 800 Series R RTWD
Equipment
Water-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
685 (20 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017
Source document
Symbio 800 Integration Points List BACnet - Series R Model RTWD · BAS-PTS017A-EN · rev. 11/15/2024
Download CSV 685 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Trane Symbio 800 Series R RTWD

Integration in brief

Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10100Chiller Auto Stop Command BASBMS auto/stop (enable) commandWrite
MV 10100Chiller Mode Command BASCool/heat/ice/free-cooling mode commandWrite
AV 10100Chilled Water SetpointChilled water setpoint from the BMSWrite
AV 10101Demand Limit SetpointCapacity (demand) limit from the BMSWrite
BI 10103Chiller Running StateChiller on/off statusRead
BI 10101Local Setpoint ControlShows if local setpoints override BAS setpointsRead
AI 10103Evaporator Leaving Water TemperatureLeaving chilled water temperatureRead
AI 10108Actual Running CapacityActual running capacity in percentRead
BI 10108Diagnostic PresentAny active diagnostic (alarm) on the chillerRead

Enable & remote start

BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10120 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

Network setup

Watch out for

Trane Symbio 800 Series R RTWD BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

685 of 685 shown
Type
Access
Show
Trane Symbio 800 Series R RTWD BACnet Points List
DescriptionStates
AI10100Active Cool/Heat Setpoint TemperaturePresently in use Chilled/Hot Water SetpointTemperatureRead
AI10101Active Demand Limit SetpointPresently in use or "active" setting of the Demand LimitPercentageRead
AI10102Evaporator Entering Water TemperatureThis is present Evaporator Entering or Return water temperatureTemperatureRead
AImin10103Evaporator Leaving Water TemperatureThis is the temperature of the water leaving the evaporatorTemperatureRead
AI10104Outdoor Air TemperatureThe temperature of the outdoor air temperature sensorTemperatureRead
AI10105Number of CircuitsRead
AI10106Number of Compressors, Circuit 1Read
AI10107Number of Compressors, Circuit 2Read
AImin10108Actual Running CapacityActual chiller running capacity (same as Total Compressor Current %RLA)PercentageRead
AI10109Evaporator Refrigerant Absolute Pressure Circuit 1Evaporator Absolute Refrigerant Pressure circuit 1Pressure, FluidicRead
AI10110Condenser Refrigerant Absolute Pressure Circuit 1Condenser Absolute Refrigerant Pressure circuit 1Pressure, FluidicRead
AI10111Differential Refrigerant Pressure Ckt1Displays the differential pressure for the respective circuit as defined byPressure, FluidicRead
AI10112Evaporator Shell Refrigerant Pressure Ckt1Pressure, FluidicRead
AI10113Evaporator Saturated Rfgt Temp Ckt1TemperatureRead
AI10114Condenser Saturated Rfgt Temp Ckt1TemperatureRead
AI10115Discharge Temperature Cprsr1ATemperatureRead
AI10116Oil Absolute Pressure Cprsr1AAbsolute oil pressure for the compressor 1APressure, FluidicRead
AI10117Starts Cprsr1AThe total number of starts that the given compressor has experiencedRead
AI10118Running Time Cprsr1AThe total accumulated running timeRead
AI10119Evaporator Refrigerant Absolute Pressure Circuit 2Evaporator Absolute Refrigerant Pressure circuit 1Pressure, FluidicRead
AI10120Condenser Refrigerant Absolute Pressure Circuit 2Condenser Absolute Refrigerant Pressure circuit 1Pressure, FluidicRead
AI10121Differential Refrigerant Pressure Ckt2Displays the differential pressure for the respective circuit as defined byPressure, FluidicRead
AI10122Evaporator Shell Refrigerant Pressure Ckt2Pressure, FluidicRead
AI10123Evaporator Saturated Rfgt Temp Ckt2TemperatureRead
AI10124Condenser Saturated Rfgt Temp Ckt2TemperatureRead
AI10125Compressor Suction TemperatureTemperatureRead
AI10126Discharge Temperature Cprsr2ATemperatureRead
AI10127Oil Absolute Pressure Cprsr2AAbsolute oil pressure for the compressor 2APressure, FluidicRead
AI10128Discharge Temperature Cprsr1BTemperatureRead
AI10129Oil Absolute Pressure Cprsr1BAbsolute oil pressure for the compressor 1BPressure, FluidicRead
AI10130Starts Cprsr1BThe total number of starts that the given compressor has experiencedRead
AI10131Running Time Cprsr1BThe total accumulated running timeRead
AI10132Starts Cprsr2AThe total number of starts that the given compressor has experiencedRead
AI10133Running Time Cprsr2AThe total accumulated running timeRead
AI10134Discharge Temperature Cprsr2BTemperatureRead
AI10135Oil Absolute Pressure Cprsr2BAbsolute oil pressure for the compressor 2BPressure, FluidicRead
AI10136Starts Cprsr2BThe total number of starts that the given compressor has experiencedRead
AI10137Running Time Cprsr2BThe total accumulated running timeRead
AI10138Motor Voltage AB Starter 1AMotor voltage Vab for the respective compressorVoltageRead
AI10139Motor Voltage AB Starter 1BMotor voltage Vab for the respective compressorVoltageRead
AI10140Motor Voltage AB Starter 2AMotor voltage Vab for the respective compressorVoltageRead
AI10141Motor Voltage AB Starter 2BMotor voltage Vab for the respective compressorVoltageRead
AI10142Oil Temperature Circuit 1The oil temperature for the respective compressorTemperatureRead
AI10143Oil Temperature Circuit 2The oil temperature for the respective compressorTemperatureRead
AI10144Condenser Entering Water TemperatureThis is present Condenser Entering or Return water temperatureTemperatureRead
AI10145Condenser Leaving Water TemperatureThis is the temperature of the water leaving the CondenserTemperatureRead
AI10146Unit Power ConsumptionEstimate of the total Chiller Power being presently utilizedPower, ElectricalRead
AI10147Energy Consumption NonResetCumulate energy consumption of unitEnergy, ElectricalRead
AI10148Energy Consumption ResettableEnergy, ElectricalRead
AI10149Motor Current L1 Starter 1AMotor current phase A in amps for the respective compressorCurrentRead
AI10150Motor Current L2 Starter 1AMotor current phase B in amps for the respective compressorCurrentRead
AI10151Motor Current L3 Starter 1AMotor current phase C in amps for the respective compressorCurrentRead
AI10152Motor Current L1 % RLA Starter 1AMotor current phase A in % RLA for the respective compressorPercentageRead
AI10153Motor Current L2 % RLA Starter 1AMotor current phase B in % RLA for the respective compressorPercentageRead
AI10154Motor Current L3 % RLA Starter 1AMotor current phase C in % RLA for the respective compressorPercentageRead
AI10155Motor Current L1 Starter 2AMotor current phase A in amps for the respective compressorCurrentRead
AI10156Motor Current L2 Starter 2AMotor current phase B in amps for the respective compressorCurrentRead
AI10157Motor Current L3 Starter 2AMotor current phase C in amps for the respective compressorCurrentRead
AI10158Motor Current L1 % RLA Starter 2AMotor current phase A in % RLA for the respective compressorPercentageRead
AI10159Motor Current L2 % RLA Starter 2AMotor current phase B in % RLA for the respective compressorPercentageRead
AI10160Motor Current L3 % RLA Starter 2AMotor current phase C in % RLA for the respective compressorPercentageRead
AI10161Motor Current L1 Starter 1BMotor current phase A in amps for the respective compressorCurrentRead
AI10162Motor Current L2 Starter 1BMotor current phase B in amps for the respective compressorCurrentRead
AI10163Motor Current L3 Starter 1BMotor current phase C in amps for the respective compressorCurrentRead
AI10164Motor Current L1 % RLA Starter 1BMotor current phase A in % RLA for the respective compressorPercentageRead
AI10165Motor Current L2 % RLA Starter 1BMotor current phase B in % RLA for the respective compressorPercentageRead
AI10166Motor Current L3 % RLA Starter 1BMotor current phase C in % RLA for the respective compressorPercentageRead
AI10167Motor Current L1 Starter 2BMotor current phase A in amps for the respective compressorCurrentRead
AI10168Motor Current L2 Starter 2BMotor current phase B in amps for the respective compressorCurrentRead
AI10169Motor Current L3 Starter 2BMotor current phase C in amps for the respective compressorCurrentRead
AI10170Motor Current L1 % RLA Starter 2BMotor current phase A in % RLA for the respective compressorPercentageRead
AI10171Motor Current L2 % RLA Starter 2BMotor current phase B in % RLA for the respective compressorPercentageRead
AI10172Motor Current L3 % RLA Starter 2BMotor current phase C in % RLA for the respective compressorPercentageRead
AI10173Motor Current A Cprsr1AMotor Current U AFD 1ACurrentRead
AI10174Motor Current B Cprsr1AMotor Current V AFD 1ACurrentRead
AI10175Motor Current C Cprsr1AMotor Current W AFD 1ACurrentRead
AI10176Motor % RLA A Cprsr1AMotor Current U % RLA AFD 1APercentageRead
AI10177Motor % RLA B Cprsr1AMotor Current V % RLA AFD 1APercentageRead
AI10178Motor % RLA C Cprsr1AMotor Current W % RLA AFD 1APercentageRead
AI10179Motor Current A Cprsr2AMotor Current U AFD 2ACurrentRead
AI10180Motor Current B Cprsr2AMotor Current V AFD 2ACurrentRead
AI10181Motor Current C Cprsr2AMotor Current W AFD 2ACurrentRead
AI10182Motor % RLA A Cprsr2AMotor Current U % RLA AFD 2APercentageRead
AI10183Motor % RLA B Cprsr2AMotor Current V % RLA AFD 2APercentageRead
AI10184Motor % RLA C Cprsr2AMotor Current W % RLA AFD 2APercentageRead
AI10185Average Motor Current % RLA AFD 1AMotor average RLA for for the respective compressorPercentageRead
AI10186Average Motor Current % RLA AFD 2AMotor average RLA for for the respective compressorPercentageRead
AI10187Unit Source ID (Last Diagnostic Code)Last Logged Diagnostic Spec BASRead
AI10188Chiller Design CapacityPower, CoolingRead
AI10189Active Chilled Water SetpointPresently in use Chilled Water SetpointTemperatureRead
AI10190Active Hot Water SetpointPresently in use Hot Water SetpointTemperatureRead
AI10191Unit Load CommandPercentageRead
AI10192Air Flow Percentage Circuit 1Air Flow Ckt1PercentageRead
AI10193Air Flow Percentage Circuit 2Air Flow Ckt2PercentageRead
AI10194Evaporator Refrigerant Pressure Circuit 1Evaporator Gauge Refrigerant Pressure circuit 1Pressure, FluidicRead
AI10195Condenser Refrigerant Pressure Circuit 1Condenser Gauge Refrigerant Pressure circuit 1Pressure, FluidicRead
AI10196Evaporator Refrigerant Pressure Circuit 2Evaporator Gauge Refrigerant Pressure circuit 2Pressure, FluidicRead
AI10197Condenser Refrigerant Pressure Circuit 2Condenser Gauge Refrigerant Pressure circuit 2Pressure, FluidicRead
AI10198Condenser Control OutputCondenser Head Pressure Control OutputPercentageRead
AI10199Oil Pressure Cprsr1AGauge oil pressure for the compressor 1APressure, FluidicRead
AI10200Oil Pressure Cprsr2AGauge oil pressure for the compressor 2APressure, FluidicRead
AI10201Oil Pressure Cprsr1BGauge oil pressure for the compressor 1BPressure, FluidicRead
AI10202Oil Pressure Cprsr2BGauge oil pressure for the compressor 2BPressure, FluidicRead
AI10203Evaporator Approach Temperature Circuit 1Temperature, DeltaRead
AI10204Evaporator Approach Temperature Circuit 2Temperature, DeltaRead
AI10205Condenser Approach Temperature Circuit 1Temperature, DeltaRead
AI10206Condenser Approach Temperature Circuit 2Temperature, DeltaRead
AI10207Average Line Current Circuit 1Average Line Current Meter 1CurrentRead
AI10208Average Line Current Circuit 2Average Line Current Meter 2CurrentRead
AI10209Average Line Voltage Circuit 1Average Line Voltage Meter 1VoltageRead
AI10210Average Line Voltage Circuit 2Average Line Voltage Meter 2VoltageRead
AI10211Line Current L1 Circuit 1Line Current L1 Meter 1CurrentRead
AI10212Line Current L2 Circuit 1Line Current L2 Meter 1CurrentRead
AI10213Line Current L3 Circuit 1Line Current L3 Meter 1CurrentRead
AI10214Line Current L1 Circuit 2Line Current L1 Meter 2CurrentRead
AI10215Line Current L2 Circuit 2Line Current L3 Meter 2CurrentRead
AI10216Line Current L3 Circuit 2Line Current L3 Meter 2CurrentRead
AI10217Voltage L1-L2 Circuit 1Line Voltage L1-L2 Meter 1VoltageRead
AI10218Voltage L2-L3 Circuit 1Line Voltage L2-L3 Meter 1VoltageRead
AI10219Voltage L1-L3 Circuit 1Line Voltage L1-L3 Meter 1VoltageRead
AI10220Voltage L1-L2 Circuit 2Line Voltage L1-L2 Meter 2VoltageRead
AI10221Voltage L2-L1 Circuit 2Line Voltage L2-L3 Meter 2VoltageRead
AI10222Voltage L1-L3 Circuit 2Line Voltage L1-L3 Meter 2VoltageRead
AI10223Line Frequency Circuit 1Line Frequency Meter 1Read
AI10224Line Frequency Circuit 2Line Frequency Meter 2Read
AI10225Power Factor Circuit 1Power Factor Meter 1Read
AI10226Power Factor Circuit 2Power Factor Meter 2Read
AI10227Power Demand Circuit 1Power Demand Meter 1Power, ElectricalRead
AI10228Power Demand Circuit 2Power Demand Meter 2Power, ElectricalRead
AI10229Power FactorUnit Power FactorRead
AI10230Current L1Meter Line Current L1CurrentRead
AI10231Current L2Meter Line Current L2CurrentRead
AI10232Current L3Meter Line Current L3CurrentRead
AI10233Average CurrentMeter Average Line CurrentCurrentRead
AI10234Voltage L1-L2Meter Line Voltage L1-L2VoltageRead
AI10235Voltage L2-L3Meter Line Voltage L2-L3VoltageRead
AI10236Voltage L1-L3Meter Line Voltage L1-L3VoltageRead
AI10237Average Voltage L-LMeter Average Line VoltageVoltageRead
AI10238Line FrequencyUnit Line FrequencyRead
AI10239Unit Power DemandChiller Power DemandPower, ElectricalRead
AI10240Active Cooling Differential to StartPresently in use Cooling Differential to Start SetpointTemperature, DeltaRead
AI10241Active Cooling Differential to StopPresently in use Cooling Differential to Stop SetpointTemperature, DeltaRead
AI10242Active Heating Differential to StartPresently in use Heating Differential to Start SetpointTemperature, DeltaRead
AI10243Active Heating Differential to StopPresently in use Heating Differential to Stop SetpointTemperature, DeltaRead
AVmin10100Chilled Water SetpointDesired evaporator leaving water temperature if chiller is in cooling modeTemperatureWrite
AVmin10101Demand Limit SetpointSets the maximum capacity that the chiller can usePercentageWrite
AV10102Hot Water SetpointDesired condenser leaving water temperature if chiller is in heating modeTemperatureWrite
AV10103BAS Cooling Differential to StartDesired Cooling Differential to Start if chiller is in cooling modeTemperature, DeltaWrite
AV10104BAS Cooling Differential to StopDesired Cooling Differential to Stop if chiller is in cooling modeTemperature, DeltaWrite
AV10105BAS Heating Differential to StartDesired Heating Differential to Start if chiller is in heating modeTemperature, DeltaWrite
AV10106BAS Heating Differential to StopDesired Heating Differential to Stop if chiller is in heating modeTemperature, DeltaWrite
BI10100Run EnableThe chiller is available to run or is currently runningRead0 = Run Not Enabled, 1 = Run Enabled
BImin10101Local Setpoint ControlThe chiller is being controlled by local setpoints instead of BAS setpointsRead0 = Remote Control, 1 = Local Control
BI10102Limit Mode Relay StatusThe Chiller is in a Limit modeRead0 = Off, 1 = On
BImin10103Chiller Running StatePrimary running mode of the chiller sequenceRead0 = Off, 1 = On
BI10104Maximum CapacityRead0 = Off, 1 = On
BI10105Manual Override ExistsThere is a Manual Override activeRead0 = Off, 1 = On
BI10106Emergency StopDisplays the Status of the Emergency StopRead0 = Auto, 1 = Emergency Stop - Manual Reset Required
BI10107Evaporator Water Flow StatusWater flow through the evaporatorRead0 = No Flow, 1 = Flow
BImin10108Diagnostic PresentRead0 = Normal, 1 = In Alarm
BI10109Diagnostic Shutdown PresentRead0 = Normal, 1 = In Alarm
BI10110Diagnostic: Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10111Diagnostic: Local Manual Reset RequiredRead0 = Normal, 1 = In Alarm
BI10112Diagnostic Present: Information/eVar/Pltm1DiagPrsntInfo/Read0 = Normal, 1 = In Alarm
BI10113Diagnostic Present: Advisory/eVar/Pltm1DiagPrsntAdvsry/Read0 = Normal, 1 = In Alarm
BI10114Diagnostic Present: Critical/eVar/Pltm1DiagPrsntCrtcl/Read0 = Normal, 1 = In Alarm
BI10115Diagnostic Present: Service Required/eVar/Pltm1DiagPrsntSvcRqrd/Read0 = Normal, 1 = In Alarm
BI10116Compressor 1A Running StatusRunning status of compressor 1ARead0 = Stop, 1 = Auto
BI10117Compressor 1B Running StatusRunning status of compressor 1BRead0 = Stop, 1 = Auto
BI10118Compressor 2A Running StatusRunning status of compressor 2ARead0 = Stop, 1 = Auto
BI10119Compressor 2B Running StatusRunning status of compressor 2BRead0 = Stop, 1 = Auto
BI10120External Auto StopStatus of External Auto Stop inputRead0 = Stop, 1 = Auto
BI10121Condenser Water Pump CommandThis provides a status of the Chillers Condenser Water Pump outputRead0 = Inactive, 1 = Active
BI10122Evaporator Water Pump CommandThis provides a status of the Chillers Evaporator Water Pump outputRead0 = Off, 1 = On
BI10123Condenser Water Flow StatusWater flow through the condenserRead0 = Inactive, 1 = Active
BI10124Front Panel Auto Stop StatusStatus of Front Auto Stop inputRead0 = Stop, 1 = Auto
BI10125Circuit Manual Reset Indicator (CMR) Ckt1Or not there is an alarm presentRead0 = Inactive, 1 = Active
BI10126Circuit Manual Reset Indicator (CMR) Ckt2Or not there is an alarm presentRead0 = Inactive, 1 = Active
BI10127Circuit Auto Reset Indicator (CAR) Ckt1Or not there is non-latching alarm present on circuit 1Read0 = Inactive, 1 = Active
BI10128Circuit Auto Reset Indicator (CAR) Ckt2Or not there is non-latching alarm present on circuit 2Read0 = Inactive, 1 = Active
BI10129Head Pressure Relief RequestHead Relief Request RelayRead0 = Normal, 1 = Locked Out
BI10130Alarm - General Latching UnitRead0 = Normal, 1 = In Alarm
BI10131Alarm - General Non Latching UnitRead0 = Normal, 1 = In Alarm
BI10132Alarm - General Latching Ckt1Read0 = Normal, 1 = In Alarm
BI10133Alarm - General Latching Ckt2Read0 = Normal, 1 = In Alarm
BI10134Alarm - General Non Latching Ckt1Read0 = Normal, 1 = In Alarm
BI10135Alarm - General Non Latching Ckt2Read0 = Normal, 1 = In Alarm
BI10136Noise Reduction Request ActiveStatus of Noise Reduction RequestRead0 = Off, 1 = On
BI11000Comm Loss: %RLA Indication Output (Vdc)Read0 = Normal, 1 = In Alarm
BI11001Comm Loss: AFD 1ARead0 = Normal, 1 = In Alarm
BI11002Comm Loss: AFD 2ARead0 = Normal, 1 = In Alarm
BI11003Comm Loss: AFD Fault Input 1ARead0 = Normal, 1 = In Alarm
BI11004Comm Loss: AFD Fault Input 1BRead0 = Normal, 1 = In Alarm
BI11005Comm Loss: AFD Fault Input 2ARead0 = Normal, 1 = In Alarm
BI11006Comm Loss: AFD Fault Input 2BRead0 = Normal, 1 = In Alarm
BI11007Comm Loss: AFD Run Command 1ARead0 = Normal, 1 = In Alarm
BI11008Comm Loss: AFD Run Command 2ARead0 = Normal, 1 = In Alarm
BI11009Comm Loss: AFD Speed Command 1ARead0 = Normal, 1 = In Alarm
BI11010Comm Loss: AFD Speed Command 1BRead0 = Normal, 1 = In Alarm
BI11011Comm Loss: AFD Speed Command 2ARead0 = Normal, 1 = In Alarm
BI11012Comm Loss: AFD Speed Command 2BRead0 = Normal, 1 = In Alarm
BI11013Comm Loss: AOC Inlet Oil Temperature 1ARead0 = Normal, 1 = In Alarm
BI11014Comm Loss: AOC Inlet Oil Temperature 2ARead0 = Normal, 1 = In Alarm
BI11015Comm Loss: Auxiliary Setpoint CommandRead0 = Normal, 1 = In Alarm
BI11016Comm Loss: Chiller Bypass Valve OutputRead0 = Normal, 1 = In Alarm
BI11017Comm Loss: Cond Head Press Cntrl OutputRead0 = Normal, 1 = In Alarm
BI11018Comm Loss: Cond Rfgt Liquid Level Ckt1Read0 = Normal, 1 = In Alarm
BI11019Comm Loss: Cond Rfgt Liquid Level Ckt2Read0 = Normal, 1 = In Alarm
BI11020Comm Loss: Cond Water Pump Analog OutputRead0 = Normal, 1 = In Alarm
BI11021Comm Loss: Condenser Entering Water TempRead0 = Normal, 1 = In Alarm
BI11022Comm Loss: Condenser Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11023Comm Loss: Condenser Rfgt Pressure Ckt2Read0 = Normal, 1 = In Alarm
BI11024Comm Loss: Condenser Rfgt Pressure Ckt1Read0 = Normal, 1 = In Alarm
BI11025Comm Loss: Condenser Rfgt Pressure OutputRead0 = Normal, 1 = In Alarm
BI11026Comm Loss: Condenser Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11027Comm Loss: Condenser Water Pump RelayRead0 = Normal, 1 = In Alarm
BI11028Comm Loss: Cprsr Disch Rfgt Temp 1ARead0 = Normal, 1 = In Alarm
BI11029Comm Loss: Cprsr Disch Rfgt Temp 1BRead0 = Normal, 1 = In Alarm
BI11030Comm Loss: Cprsr Disch Rfgt Temp 2ARead0 = Normal, 1 = In Alarm
BI11031Comm Loss: Cprsr Disch Rfgt Temp 2BRead0 = Normal, 1 = In Alarm
BI11032Comm Loss: Electronic Expansion Valve Ckt1Read0 = Normal, 1 = In Alarm
BI11033Comm Loss: Electronic Expansion Valve Ckt2Read0 = Normal, 1 = In Alarm
BI11034Comm Loss: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11035Comm Loss: Energy Meter Pulse InputRead0 = Normal, 1 = In Alarm
BI11036Comm Loss: Evap Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11037Comm Loss: Evap Entering Water TempRead0 = Normal, 1 = In Alarm
BI11038Comm Loss: Evap Iso Valve Close Switch Ckt1Read0 = Normal, 1 = In Alarm
BI11039Comm Loss: Evap Iso Valve Close Switch Ckt2Read0 = Normal, 1 = In Alarm
BI11040Comm Loss: Evap Iso Valve Open Switch Ckt1Read0 = Normal, 1 = In Alarm
BI11041Comm Loss: Evap Iso Valve Open Switch Ckt2Read0 = Normal, 1 = In Alarm
BI11042Comm Loss: Evap Isolation Valve Relay Ckt1Read0 = Normal, 1 = In Alarm
BI11043Comm Loss: Evap Isolation Valve Relay Ckt2Read0 = Normal, 1 = In Alarm
BI11044Comm Loss: Evap Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11045Comm Loss: Evap Leaving Water TempRead0 = Normal, 1 = In Alarm
BI11046Comm Loss: Evap Oil Return Level Ckt1Read0 = Normal, 1 = In Alarm
BI11047Comm Loss: Evap Oil Return Level Ckt2Read0 = Normal, 1 = In Alarm
BI11048Comm Loss: Evap Pump Inv1 Fault InputRead0 = Normal, 1 = In Alarm
BI11049Comm Loss: Evap Pump Inv1 Run CommandRead0 = Normal, 1 = In Alarm
BI11050Comm Loss: Evap Rfgt Liquid Level Ckt1Read0 = Normal, 1 = In Alarm
BI11051Comm Loss: Evap Rfgt Liquid Level Ckt2Read0 = Normal, 1 = In Alarm
BI11052Comm Loss: Evap Rfgt Pool Temp Ckt1Read0 = Normal, 1 = In Alarm
BI11053Comm Loss: Evap Rfgt Pool Temp Ckt2Read0 = Normal, 1 = In Alarm
BI11054Comm Loss: Evap Shell Rfgt Pressure Ckt1Read0 = Normal, 1 = In Alarm
BI11055Comm Loss: Evap Shell Rfgt Pressure Ckt2Read0 = Normal, 1 = In Alarm
BI11056Comm Loss: Evap Water Pump Analog OutputRead0 = Normal, 1 = In Alarm
BI11057Comm Loss: Evap Water Pump Inv Freq InputRead0 = Normal, 1 = In Alarm
BI11058Comm Loss: Evaporator Pump 1 Fault InputRead0 = Normal, 1 = In Alarm
BI11059Comm Loss: Evaporator Pump 2 Fault InputRead0 = Normal, 1 = In Alarm
BI11060Comm Loss: Evaporator Water Flow SwitchRead0 = Normal, 1 = In Alarm
BI11061Comm Loss: Evaporator Water Pump 1 RelayRead0 = Normal, 1 = In Alarm
BI11062Comm Loss: Evaporator Water Pump 2 RelayRead0 = Normal, 1 = In Alarm
BI11063Comm Loss: Ext Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11064Comm Loss: Ext Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11065Comm Loss: Ext Noise Reduction RequestRead0 = Normal, 1 = In Alarm
BI11066Comm Loss: External Auto/StopRead0 = Normal, 1 = In Alarm
BI11067Comm Loss: External Ckt2 LockoutRead0 = Normal, 1 = In Alarm
BI11068Comm Loss: External Ckt1 LockoutRead0 = Normal, 1 = In Alarm
BI11069Comm Loss: External Hot Water CommandRead0 = Normal, 1 = In Alarm
BI11070Comm Loss: External Ice Building CommandRead0 = Normal, 1 = In Alarm
BI11071Comm Loss: Fan Control Relays, Ckt1Read0 = Normal, 1 = In Alarm
BI11072Comm Loss: Fan Control Relays, Ckt2Read0 = Normal, 1 = In Alarm
BI11073Comm Loss: Fan Inverter Fault Ckt1Read0 = Normal, 1 = In Alarm
BI11074Comm Loss: Fan Inverter Fault Ckt2Read0 = Normal, 1 = In Alarm
BI11075Comm Loss: Fan Inverter Speed Command Ckt1Read0 = Normal, 1 = In Alarm
BI11076Comm Loss: Fan Inverter Speed Command Ckt2Read0 = Normal, 1 = In Alarm
BI11077Comm Loss: High Pressure Cutout Sw 1ARead0 = Normal, 1 = In Alarm
BI11078Comm Loss: High Pressure Cutout Sw 1BRead0 = Normal, 1 = In Alarm
BI11079Comm Loss: High Pressure Cutout Sw 2ARead0 = Normal, 1 = In Alarm
BI11080Comm Loss: High Pressure Cutout Sw 2BRead0 = Normal, 1 = In Alarm
BI11081Comm Loss: High Pressure Cutout Switch Ckt2Read0 = Normal, 1 = In Alarm
BI11082Comm Loss: High Pressure Cutout Switch Ckt1Read0 = Normal, 1 = In Alarm
BI11083Comm Loss: HR Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11084Comm Loss: HR Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11085Comm Loss: Ice Building Status RelayRead0 = Normal, 1 = In Alarm
BI11086Comm Loss: Liquid Line Pressure Ckt1Read0 = Normal, 1 = In Alarm
BI11087Comm Loss: Liquid Line Pressure Ckt2Read0 = Normal, 1 = In Alarm
BI11088Comm Loss: Liquid Line Temperature Ckt1Read0 = Normal, 1 = In Alarm
BI11089Comm Loss: Liquid Line Temperature Ckt2Read0 = Normal, 1 = In Alarm
BI11090Comm Loss: Motor RLA Input 1ARead0 = Normal, 1 = In Alarm
BI11091Comm Loss: Motor RLA Input 1BRead0 = Normal, 1 = In Alarm
BI11092Comm Loss: Motor RLA Input 2ARead0 = Normal, 1 = In Alarm
BI11093Comm Loss: Motor RLA Input 2BRead0 = Normal, 1 = In Alarm
BI11094Comm Loss: Motor Winding Tstat Cprsr1ARead0 = Normal, 1 = In Alarm
BI11095Comm Loss: Motor Winding Tstat Cprsr2ARead0 = Normal, 1 = In Alarm
BI11096Comm Loss: Noise Reduction Request Relay Ckt1Read0 = Normal, 1 = In Alarm
BI11097Comm Loss: Noise Reduction Request Relay Ckt2Read0 = Normal, 1 = In Alarm
BI11098Comm Loss: Off-cycle Freeze Prot RelayRead0 = Normal, 1 = In Alarm
BI11099Comm Loss: Oil Heater Relay 1ARead0 = Normal, 1 = In Alarm
BI11100Comm Loss: Oil Heater Relay 2ARead0 = Normal, 1 = In Alarm
BI11101Comm Loss: Oil Loss Level Sensor Input Ckt1Read0 = Normal, 1 = In Alarm
BI11102Comm Loss: Oil Loss Level Sensor Input Ckt2Read0 = Normal, 1 = In Alarm
BI11103Comm Loss: Oil Pressure 1ARead0 = Normal, 1 = In Alarm
BI11104Comm Loss: Oil Pressure 1BRead0 = Normal, 1 = In Alarm
BI11105Comm Loss: Oil Pressure 2ARead0 = Normal, 1 = In Alarm
BI11106Comm Loss: Oil Pressure 2BRead0 = Normal, 1 = In Alarm
BI11107Comm Loss: Oil Return Gas Pump Drain Ckt1Read0 = Normal, 1 = In Alarm
BI11108Comm Loss: Oil Return Gas Pump Drain Ckt2Read0 = Normal, 1 = In Alarm
BI11109Comm Loss: Oil Return Gas Pump Fill Ckt1Read0 = Normal, 1 = In Alarm
BI11110Comm Loss: Oil Return Gas Pump Fill Ckt2Read0 = Normal, 1 = In Alarm
BI11111Comm Loss: Oil Return Purge Valve Ckt1Read0 = Normal, 1 = In Alarm
BI11112Comm Loss: Oil Return Purge Valve Ckt2Read0 = Normal, 1 = In Alarm
BI11113Comm Loss: Oil Temp, Ckt 1Read0 = Normal, 1 = In Alarm
BI11114Comm Loss: Oil Temp, Ckt 2Read0 = Normal, 1 = In Alarm
BI11115Comm Loss: Outdoor Air TemperatureRead0 = Normal, 1 = In Alarm
BI11116Comm Loss: Programmable Relay Board 1Read0 = Normal, 1 = In Alarm
BI11117Comm Loss: Programmable Relay Board 2Read0 = Normal, 1 = In Alarm
BI11118Comm Loss: Reversing ValveRead0 = Normal, 1 = In Alarm
BI11119Comm Loss: Slide Valve Load 1ARead0 = Normal, 1 = In Alarm
BI11120Comm Loss: Slide Valve Load 1BRead0 = Normal, 1 = In Alarm
BI11121Comm Loss: Slide Valve Load 2ARead0 = Normal, 1 = In Alarm
BI11122Comm Loss: Slide Valve Load 2BRead0 = Normal, 1 = In Alarm
BI11123Comm Loss: Slide Valve Unload 1ARead0 = Normal, 1 = In Alarm
BI11124Comm Loss: Slide Valve Unload 1BRead0 = Normal, 1 = In Alarm
BI11125Comm Loss: Slide Valve Unload 2ARead0 = Normal, 1 = In Alarm
BI11126Comm Loss: Slide Valve Unload 2BRead0 = Normal, 1 = In Alarm
BI11127Comm Loss: Starter 1ARead0 = Normal, 1 = In Alarm
BI11128Comm Loss: Starter 1BRead0 = Normal, 1 = In Alarm
BI11129Comm Loss: Starter 2ARead0 = Normal, 1 = In Alarm
BI11130Comm Loss: Starter 2BRead0 = Normal, 1 = In Alarm
BI11131Comm Loss: Step Load 1ARead0 = Normal, 1 = In Alarm
BI11132Comm Loss: Step Load 1BRead0 = Normal, 1 = In Alarm
BI11133Comm Loss: Step Load 2ARead0 = Normal, 1 = In Alarm
BI11134Comm Loss: Step Load 2BRead0 = Normal, 1 = In Alarm
BI11135Comm Loss: Suction Rfgt Pressure Ckt2Read0 = Normal, 1 = In Alarm
BI11136Comm Loss: Suction Rfgt Pressure Ckt1Read0 = Normal, 1 = In Alarm
BI11137Comm Loss: Suction Rfgt Pressure 1ARead0 = Normal, 1 = In Alarm
BI11138Comm Loss: Suction Rfgt Pressure 1BRead0 = Normal, 1 = In Alarm
BI11139Comm Loss: Suction Rfgt Pressure 2ARead0 = Normal, 1 = In Alarm
BI11140Comm Loss: Suction Rfgt Pressure 2BRead0 = Normal, 1 = In Alarm
BI11141Comm Loss: Suction TemperatureRead0 = Normal, 1 = In Alarm
BI11142Comm Loss: Water System Diff PressureRead0 = Normal, 1 = In Alarm
BI11143Comm Loss: Winding Temp 1, Cprsr1ARead0 = Normal, 1 = In Alarm
BI11144Comm Loss: Winding Temp 1, Cprsr2ARead0 = Normal, 1 = In Alarm
BI11145Comm Loss: Winding Temp 2, Cprsr1ARead0 = Normal, 1 = In Alarm
BI11146Diagnostic: AFD %RLA Feedback 1ARead0 = Normal, 1 = In Alarm
BI11147Diagnostic: AFD %RLA Feedback 1BRead0 = Normal, 1 = In Alarm
BI11148Diagnostic: AFD %RLA Feedback 2ARead0 = Normal, 1 = In Alarm
BI11149Diagnostic: AFD %RLA Feedback 2BRead0 = Normal, 1 = In Alarm
BI11150Diagnostic: AFD Bump Complete 1ARead0 = Normal, 1 = In Alarm
BI11151Diagnostic: AFD Bump Complete 2ARead0 = Normal, 1 = In Alarm
BI11152Diagnostic: AFD Bump Current High 1ARead0 = Normal, 1 = In Alarm
BI11153Diagnostic: AFD Bump Current High 2ARead0 = Normal, 1 = In Alarm
BI11154Diagnostic: AFD Comm Loss – 1ARead0 = Normal, 1 = In Alarm
BI11155Diagnostic: AFD Comm Loss – 1BRead0 = Normal, 1 = In Alarm
BI11156Diagnostic: AFD Comm Loss – 2ARead0 = Normal, 1 = In Alarm
BI11157Diagnostic: AFD Comm Loss – 2BRead0 = Normal, 1 = In Alarm
BI11158Diagnostic: AFD Failure to Arm or Start 1ARead0 = Normal, 1 = In Alarm
BI11159Diagnostic: AFD Failure to Arm or Start 1BRead0 = Normal, 1 = In Alarm
BI11160Diagnostic: AFD Failure to Arm or Start 2ARead0 = Normal, 1 = In Alarm
BI11161Diagnostic: AFD Failure to Arm or Start 2BRead0 = Normal, 1 = In Alarm
BI11162Diagnostic: AFD Fault 1ARead0 = Normal, 1 = In Alarm
BI11163Diagnostic: AFD Fault 1BRead0 = Normal, 1 = In Alarm
BI11164Diagnostic: AFD Fault 2ARead0 = Normal, 1 = In Alarm
BI11165Diagnostic: AFD Fault 2BRead0 = Normal, 1 = In Alarm
BI11166Diagnostic: AFD Fault Mains 1ARead0 = Normal, 1 = In Alarm
BI11167Diagnostic: AFD Fault Mains 2ARead0 = Normal, 1 = In Alarm
BI11168Diagnostic: AFD Harmonic Filter Over Temperature 1ARead0 = Normal, 1 = In Alarm
BI11169Diagnostic: AFD Harmonic Filter Over Temperature 2ARead0 = Normal, 1 = In Alarm
BI11170Diagnostic: AFD High Pressure Cutout 1ARead0 = Normal, 1 = In Alarm
BI11171Diagnostic: AFD High Pressure Cutout 2ARead0 = Normal, 1 = In Alarm
BI11172Diagnostic: AFD Interrupt Failure 1ARead0 = Normal, 1 = In Alarm
BI11173Diagnostic: AFD Interrupt Failure 2ARead0 = Normal, 1 = In Alarm
BI11174Diagnostic: AFD Motor Current Overload 1ARead0 = Normal, 1 = In Alarm
BI11175Diagnostic: AFD Motor Current Overload 1BRead0 = Normal, 1 = In Alarm
BI11176Diagnostic: AFD Motor Current Overload 2ARead0 = Normal, 1 = In Alarm
BI11177Diagnostic: AFD Motor Current Overload 2BRead0 = Normal, 1 = In Alarm
BI11178Diagnostic: AFD Motor Fault 1ARead0 = Normal, 1 = In Alarm
BI11179Diagnostic: AFD Motor Fault 2ARead0 = Normal, 1 = In Alarm
BI11180Diagnostic: AFD Motor Speed Too High 1ARead0 = Normal, 1 = In Alarm
BI11181Diagnostic: AFD Motor Speed Too High 2ARead0 = Normal, 1 = In Alarm
BI11182Diagnostic: AFD Motor Speed Too Low 1ARead0 = Normal, 1 = In Alarm
BI11183Diagnostic: AFD Motor Speed Too Low 2ARead0 = Normal, 1 = In Alarm
BI11184Diagnostic: AFD Pump Out Speed Low 1ARead0 = Normal, 1 = In Alarm
BI11185Diagnostic: AFD Pump Out Speed Low 2ARead0 = Normal, 1 = In Alarm
BI11186Diagnostic: AFD Unexpected Shutdown 1ARead0 = Normal, 1 = In Alarm
BI11187Diagnostic: AFD Unexpected Shutdown 2ARead0 = Normal, 1 = In Alarm
BI11188Diagnostic: AFD Unhandled Fault 1ARead0 = Normal, 1 = In Alarm
BI11189Diagnostic: AFD Unhandled Fault 2ARead0 = Normal, 1 = In Alarm
BI11190Diagnostic: AOC Inlet Oil Temperature Sensor 1ARead0 = Normal, 1 = In Alarm
BI11191Diagnostic: AOC Inlet Oil Temperature Sensor 2ARead0 = Normal, 1 = In Alarm
BI11192Diagnostic: Check ClockRead0 = Normal, 1 = In Alarm
BI11193Diagnostic: Chiller Service RecommendedRead0 = Normal, 1 = In Alarm
BI11194Diagnostic: Comm Loss: Winding Temp 2, Cprsr2ARead0 = Normal, 1 = In Alarm
BI11195Diagnostic: Cond Rfgt Liquid Level Sensor Ckt1Read0 = Normal, 1 = In Alarm
BI11196Diagnostic: Cond Rfgt Liquid Level Sensor Ckt2Read0 = Normal, 1 = In Alarm
BI11197Diagnostic: Condenser Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11198Diagnostic: Condenser Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11199Diagnostic: Condenser Rfgt Pressure Sensor Ckt2Read0 = Normal, 1 = In Alarm
BI11200Diagnostic: Condenser Rfgt Pressure Sensor Ckt1Read0 = Normal, 1 = In Alarm
BI11201Diagnostic: Condenser Water Flow LostRead0 = Normal, 1 = In Alarm
BI11202Diagnostic: Condenser Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11203Diagnostic: Cprsr Did Not Accel: Shutdown 1ARead0 = Normal, 1 = In Alarm
BI11204Diagnostic: Cprsr Did Not Accel: Shutdown 1BRead0 = Normal, 1 = In Alarm
BI11205Diagnostic: Cprsr Did Not Accel: Shutdown 2ARead0 = Normal, 1 = In Alarm
BI11206Diagnostic: Cprsr Did Not Accel: Shutdown 2BRead0 = Normal, 1 = In Alarm
BI11207Diagnostic: Cprsr Did Not Accel: Transition 1ARead0 = Normal, 1 = In Alarm
BI11208Diagnostic: Cprsr Did Not Accel: Transition 1BRead0 = Normal, 1 = In Alarm
BI11209Diagnostic: Cprsr Did Not Accel: Transition 2ARead0 = Normal, 1 = In Alarm
BI11210Diagnostic: Cprsr Did Not Accel: Transition 2BRead0 = Normal, 1 = In Alarm
BI11211Diagnostic: Cprsr Disch Rfgt Temp Sensor 1ARead0 = Normal, 1 = In Alarm
BI11212Diagnostic: Cprsr Disch Rfgt Temp Sensor 1BRead0 = Normal, 1 = In Alarm
BI11213Diagnostic: Cprsr Disch Rfgt Temp Sensor 2ARead0 = Normal, 1 = In Alarm
BI11214Diagnostic: Cprsr Disch Rfgt Temp Sensor 2BRead0 = Normal, 1 = In Alarm
BI11215Diagnostic: Emergency Stop Feedback InputRead0 = Normal, 1 = In Alarm
BI11216Diagnostic: Evap Iso Valve Illegal Switch State Ckt1Read0 = Normal, 1 = In Alarm
BI11217Diagnostic: Evap Iso Valve Illegal Switch State Ckt2Read0 = Normal, 1 = In Alarm
BI11218Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt1Read0 = Normal, 1 = In Alarm
BI11219Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt2Read0 = Normal, 1 = In Alarm
BI11220Diagnostic: Evap Isolation Valve Failed To Close Ckt1Read0 = Normal, 1 = In Alarm
BI11221Diagnostic: Evap Isolation Valve Failed To Close Ckt2Read0 = Normal, 1 = In Alarm
BI11222Diagnostic: Evap Isolation Valve Failed To Open Ckt1Read0 = Normal, 1 = In Alarm
BI11223Diagnostic: Evap Isolation Valve Failed To Open Ckt2Read0 = Normal, 1 = In Alarm
BI11224Diagnostic: Evap Isolation Valve Open Switch Failure Ckt1Read0 = Normal, 1 = In Alarm
BI11225Diagnostic: Evap Isolation Valve Open Switch Failure Ckt2Read0 = Normal, 1 = In Alarm
BI11226Diagnostic: Evap Pump 1 Starts Run time WrittenRead0 = Normal, 1 = In Alarm
BI11227Diagnostic: Evap Pump 2 Starts Run time WrittenRead0 = Normal, 1 = In Alarm
BI11228Diagnostic: Evap Rfgt Pool Temp Sensor Ckt1Read0 = Normal, 1 = In Alarm
BI11229Diagnostic: Evap Rfgt Pool Temp Sensor Ckt2Read0 = Normal, 1 = In Alarm
BI11230Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt1Read0 = Normal, 1 = In Alarm
BI11231Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt2Read0 = Normal, 1 = In Alarm
BI11232Diagnostic: Evap Spillover Liquid Level Sensor Ckt1Read0 = Normal, 1 = In Alarm
BI11233Diagnostic: Evap Spillover Liquid Level Sensor Ckt2Read0 = Normal, 1 = In Alarm
BI11234Diagnostic: Evap Water Pump 1 Svc RecommendedRead0 = Normal, 1 = In Alarm
BI11235Diagnostic: Evap Water Pump 2 Svc RecommendedRead0 = Normal, 1 = In Alarm
BI11236Diagnostic: Evaporator Approach Error Ckt2Read0 = Normal, 1 = In Alarm
BI11237Diagnostic: Evaporator Approach Error Ckt1Read0 = Normal, 1 = In Alarm
BI11238Diagnostic: Evaporator Entering Water PressureRead0 = Normal, 1 = In Alarm
BI11239Diagnostic: Evaporator Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11240Diagnostic: Evaporator Leaving Water PressureRead0 = Normal, 1 = In Alarm
BI11241Diagnostic: Evaporator Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11242Diagnostic: Evaporator Oil Return Level Sensor, Ckt1Read0 = Normal, 1 = In Alarm
BI11243Diagnostic: Evaporator Oil Return Level Sensor, Ckt2Read0 = Normal, 1 = In Alarm
BI11244Diagnostic: Evaporator Pump 1 FaultRead0 = Normal, 1 = In Alarm
BI11245Diagnostic: Evaporator Pump 2 FaultRead0 = Normal, 1 = In Alarm
BI11246Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt1Read0 = Normal, 1 = In Alarm
BI11247Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt2Read0 = Normal, 1 = In Alarm
BI11248Diagnostic: Evaporator Water Flow LostRead0 = Normal, 1 = In Alarm
BI11249Diagnostic: Evaporator Water Flow Lost Pump1Read0 = Normal, 1 = In Alarm
BI11250Diagnostic: Evaporator Water Flow Lost Pump2Read0 = Normal, 1 = In Alarm
BI11251Diagnostic: Evaporator Water Flow OverdueRead0 = Normal, 1 = In Alarm
BI11252Diagnostic: Evaporator Water Flow Overdue Pump1Read0 = Normal, 1 = In Alarm
BI11253Diagnostic: Evaporator Water Flow Overdue Pump2Read0 = Normal, 1 = In Alarm
BI11254Diagnostic: Excessive Condenser Pressure Ckt2Read0 = Normal, 1 = In Alarm
BI11255Diagnostic: Excessive Condenser Pressure Ckt1Read0 = Normal, 1 = In Alarm
BI11256Diagnostic: External Chilled/Hot Water SetpointRead0 = Normal, 1 = In Alarm
BI11257Diagnostic: External Demand Limit SetpointRead0 = Normal, 1 = In Alarm
BI11258Diagnostic: EXV Pressure Equalization Failed Ckt1Read0 = Normal, 1 = In Alarm
BI11259Diagnostic: EXV Pressure Equalization Failed Ckt2Read0 = Normal, 1 = In Alarm
BI11260Diagnostic: Fan Inverter Fault Ckt1Read0 = Normal, 1 = In Alarm
BI11261Diagnostic: Fan Inverter Fault Ckt2Read0 = Normal, 1 = In Alarm
BI11262Diagnostic: Heat Recovery Entering Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11263Diagnostic: Heat Recovery Leaving Water Temp SensorRead0 = Normal, 1 = In Alarm
BI11264Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 1ARead0 = Normal, 1 = In Alarm
BI11265Diagnostic: High Cprsr Rfgt Discharge Temp 1ARead0 = Normal, 1 = In Alarm
BI11266Diagnostic: High Cprsr Rfgt Discharge Temp 1BRead0 = Normal, 1 = In Alarm
BI11267Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 2ARead0 = Normal, 1 = In Alarm
BI11268Diagnostic: High Cprsr Rfgt Discharge Temp 2ARead0 = Normal, 1 = In Alarm
BI11269Diagnostic: High Cprsr Rfgt Discharge Temp 2BRead0 = Normal, 1 = In Alarm
BI11270Diagnostic: High Differential Refrigerant PressureRead0 = Normal, 1 = In Alarm
BI11271Diagnostic: High Differential Rfgt Pressure 1ARead0 = Normal, 1 = In Alarm
BI11272Diagnostic: High Differential Rfgt Pressure 1BRead0 = Normal, 1 = In Alarm
BI11273Diagnostic: High Differential Rfgt Pressure 2ARead0 = Normal, 1 = In Alarm
BI11274Diagnostic: High Differential Rfgt Pressure 2BRead0 = Normal, 1 = In Alarm
BI11275Diagnostic: High Evap Shell Rfgt Pressure Ckt1Read0 = Normal, 1 = In Alarm
BI11276Diagnostic: High Evap Shell Rfgt Pressure Ckt2Read0 = Normal, 1 = In Alarm
BI11277Diagnostic: High Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11278Diagnostic: High Motor Winding Temperature 1ARead0 = Normal, 1 = In Alarm
BI11279Diagnostic: High Motor Winding Temperature 2ARead0 = Normal, 1 = In Alarm
BI11280Diagnostic: High Motor Winding Temperature Cprsr1ARead0 = Normal, 1 = In Alarm
BI11281Diagnostic: High Motor Winding Temperature Cprsr2ARead0 = Normal, 1 = In Alarm
BI11282Diagnostic: High Oil Temperature Ckt1Read0 = Normal, 1 = In Alarm
BI11283Diagnostic: High Oil Temperature Ckt2Read0 = Normal, 1 = In Alarm
BI11284Diagnostic: High Pressure Cutout Ckt2Read0 = Normal, 1 = In Alarm
BI11285Diagnostic: High Pressure Cutout Ckt1Read0 = Normal, 1 = In Alarm
BI11286Diagnostic: High Pressure Cutout 1ARead0 = Normal, 1 = In Alarm
BI11287Diagnostic: High Pressure Cutout 1BRead0 = Normal, 1 = In Alarm
BI11288Diagnostic: High Pressure Cutout 2ARead0 = Normal, 1 = In Alarm
BI11289Diagnostic: High Pressure Cutout 2BRead0 = Normal, 1 = In Alarm
BI11290Diagnostic: High Refrigerant Pressure RatioRead0 = Normal, 1 = In Alarm
BI11291Diagnostic: High Refrigerant Pressure Ratio 1ARead0 = Normal, 1 = In Alarm
BI11292Diagnostic: High Refrigerant Pressure Ratio 1BRead0 = Normal, 1 = In Alarm
BI11293Diagnostic: High Refrigerant Pressure Ratio 2ARead0 = Normal, 1 = In Alarm
BI11294Diagnostic: High Refrigerant Pressure Ratio 2BRead0 = Normal, 1 = In Alarm
BI11295Diagnostic: Inverted Evaporator Water TemperatureRead0 = Normal, 1 = In Alarm
BI11296Diagnostic: Liquid Line Pressure Sensor Ckt1Read0 = Normal, 1 = In Alarm
BI11297Diagnostic: Liquid Line Pressure Sensor Ckt2Read0 = Normal, 1 = In Alarm
BI11298Diagnostic: Liquid Line Temp Sensor Ckt1Read0 = Normal, 1 = In Alarm
BI11299Diagnostic: Liquid Line Temp Sensor Ckt2Read0 = Normal, 1 = In Alarm
BI11300Diagnostic: Loss of Oil for Compressor (Running) Ckt1Read0 = Normal, 1 = In Alarm
BI11301Diagnostic: Loss of Oil for Compressor (Running) Ckt2Read0 = Normal, 1 = In Alarm
BI11302Diagnostic: Loss of Oil for Compressor (Stopped) Ckt1Read0 = Normal, 1 = In Alarm
BI11303Diagnostic: Loss of Oil for Compressor (Stopped) Ckt2Read0 = Normal, 1 = In Alarm
BI11304Diagnostic: Low Condenser Rfgt Temp Ckt 1: Unit OffRead0 = Normal, 1 = In Alarm
BI11305Diagnostic: Low Condenser Rfgt Temp Ckt 2: Unit OffRead0 = Normal, 1 = In Alarm
BI11306Diagnostic: Low Differential Rfgt Pressure 1ARead0 = Normal, 1 = In Alarm
BI11307Diagnostic: Low Differential Rfgt Pressure 1BRead0 = Normal, 1 = In Alarm
BI11308Diagnostic: Low Differential Rfgt Pressure 2ARead0 = Normal, 1 = In Alarm
BI11309Diagnostic: Low Differential Rfgt Pressure 2BRead0 = Normal, 1 = In Alarm
BI11310Diagnostic: Low Discharge Superheat 1ARead0 = Normal, 1 = In Alarm
BI11311Diagnostic: Low Discharge Superheat 1BRead0 = Normal, 1 = In Alarm
BI11312Diagnostic: Low Discharge Superheat 2ARead0 = Normal, 1 = In Alarm
BI11313Diagnostic: Low Discharge Superheat 2BRead0 = Normal, 1 = In Alarm
BI11314Diagnostic: Low Evaporator Oil Return Level Ckt1Read0 = Normal, 1 = In Alarm
BI11315Diagnostic: Low Evaporator Oil Return Level Ckt2Read0 = Normal, 1 = In Alarm
BI11316Diagnostic: Low Evaporator Refrigerant Pressure Ckt1Read0 = Normal, 1 = In Alarm
BI11317Diagnostic: Low Evaporator Refrigerant Pressure Ckt2Read0 = Normal, 1 = In Alarm
BI11318Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit OffRead0 = Normal, 1 = In Alarm
BI11319Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit OffRead0 = Normal, 1 = In Alarm
BI11320Diagnostic: Low Evaporator Water Temp (Unit Off)Read0 = Normal, 1 = In Alarm
BI11321Diagnostic: Low Evaporator Water Temp (Unit On)Read0 = Normal, 1 = In Alarm
BI11322Diagnostic: Low Oil Flow 1ARead0 = Normal, 1 = In Alarm
BI11323Diagnostic: Low Oil Flow 1BRead0 = Normal, 1 = In Alarm
BI11324Diagnostic: Low Oil Flow 2ARead0 = Normal, 1 = In Alarm
BI11325Diagnostic: Low Oil Flow 2BRead0 = Normal, 1 = In Alarm
BI11326Diagnostic: Low Refrigerant Temperature Ckt2Read0 = Normal, 1 = In Alarm
BI11327Diagnostic: Low Refrigerant Temperature Ckt1Read0 = Normal, 1 = In Alarm
BI11328Diagnostic: Mfr Maintenance Recommended 1ARead0 = Normal, 1 = In Alarm
BI11329Diagnostic: Mfr Maintenance Recommended 1BRead0 = Normal, 1 = In Alarm
BI11330Diagnostic: Mfr Maintenance Recommended 2ARead0 = Normal, 1 = In Alarm
BI11331Diagnostic: Mfr Maintenance Recommended 2BRead0 = Normal, 1 = In Alarm
BI11332Diagnostic: Momentary Power Loss 1ARead0 = Normal, 1 = In Alarm
BI11333Diagnostic: Momentary Power Loss 1BRead0 = Normal, 1 = In Alarm
BI11334Diagnostic: Momentary Power Loss 2ARead0 = Normal, 1 = In Alarm
BI11335Diagnostic: Momentary Power Loss 2BRead0 = Normal, 1 = In Alarm
BI11336Diagnostic: Motor Current Overload 1ARead0 = Normal, 1 = In Alarm
BI11337Diagnostic: Motor Current Overload 1BRead0 = Normal, 1 = In Alarm
BI11338Diagnostic: Motor Current Overload 2ARead0 = Normal, 1 = In Alarm
BI11339Diagnostic: Motor Current Overload 2BRead0 = Normal, 1 = In Alarm
BI11340Diagnostic: Motor Winding Temp Sensor Cprsr1ARead0 = Normal, 1 = In Alarm
BI11341Diagnostic: Motor Winding Temp Sensor Cprsr2ARead0 = Normal, 1 = In Alarm
BI11342Diagnostic: MP: Invalid ConfigurationRead0 = Normal, 1 = In Alarm
BI11343Diagnostic: MP: Non-Volatile Block Test ErrorRead0 = Normal, 1 = In Alarm
BI11344Diagnostic: MP: Reset Has OccurredRead0 = Normal, 1 = In Alarm
BI11345Diagnostic: Need Cprsr 1A To Run For Oil FlowRead0 = Normal, 1 = In Alarm
BI11346Diagnostic: No Differential Rfgt Pressure 1ARead0 = Normal, 1 = In Alarm
BI11347Diagnostic: No Differential Rfgt Pressure 1BRead0 = Normal, 1 = In Alarm
BI11348Diagnostic: No Differential Rfgt Pressure 2ARead0 = Normal, 1 = In Alarm
BI11349Diagnostic: No Differential Rfgt Pressure 2BRead0 = Normal, 1 = In Alarm
BI11350Diagnostic: Oil Analysis Recommended Ckt1Read0 = Normal, 1 = In Alarm
BI11351Diagnostic: Oil Analysis Recommended Ckt2Read0 = Normal, 1 = In Alarm
BI11352Diagnostic: Oil Filter Change Recommended Cprsr1ARead0 = Normal, 1 = In Alarm
BI11353Diagnostic: Oil Filter Change Recommended Cprsr2ARead0 = Normal, 1 = In Alarm
BI11354Diagnostic: Oil Flow Protection Fault 1ARead0 = Normal, 1 = In Alarm
BI11355Diagnostic: Oil Flow Protection Fault 1BRead0 = Normal, 1 = In Alarm
BI11356Diagnostic: Oil Flow Protection Fault 2ARead0 = Normal, 1 = In Alarm
BI11357Diagnostic: Oil Flow Protection Fault 2BRead0 = Normal, 1 = In Alarm
BI11358Diagnostic: Oil Pressure Sensor 1ARead0 = Normal, 1 = In Alarm
BI11359Diagnostic: Oil Pressure Sensor 1BRead0 = Normal, 1 = In Alarm
BI11360Diagnostic: Oil Pressure Sensor 2ARead0 = Normal, 1 = In Alarm
BI11361Diagnostic: Oil Pressure Sensor 2BRead0 = Normal, 1 = In Alarm
BI11362Diagnostic: Oil Temperature Sensor, Circuit 1Read0 = Normal, 1 = In Alarm
BI11363Diagnostic: Oil Temperature Sensor, Circuit 2Read0 = Normal, 1 = In Alarm
BI11364Diagnostic: Outdoor Air Temperature SensorRead0 = Normal, 1 = In Alarm
BI11365Diagnostic: Over VoltageRead0 = Normal, 1 = In Alarm
BI11366Diagnostic: Over Voltage 1ARead0 = Normal, 1 = In Alarm
BI11367Diagnostic: Over Voltage 2ARead0 = Normal, 1 = In Alarm
BI11368Diagnostic: Phase Loss 1ARead0 = Normal, 1 = In Alarm
BI11369Diagnostic: Phase Loss 1BRead0 = Normal, 1 = In Alarm
BI11370Diagnostic: Phase Loss 2ARead0 = Normal, 1 = In Alarm
BI11371Diagnostic: Phase Loss 2BRead0 = Normal, 1 = In Alarm
BI11372Diagnostic: Phase Reversal 1ARead0 = Normal, 1 = In Alarm
BI11373Diagnostic: Phase Reversal 1BRead0 = Normal, 1 = In Alarm
BI11374Diagnostic: Phase Reversal 2ARead0 = Normal, 1 = In Alarm
BI11375Diagnostic: Phase Reversal 2BRead0 = Normal, 1 = In Alarm
BI11376Diagnostic: Power Loss 1ARead0 = Normal, 1 = In Alarm
BI11377Diagnostic: Power Loss 1BRead0 = Normal, 1 = In Alarm
BI11378Diagnostic: Power Loss 2ARead0 = Normal, 1 = In Alarm
BI11379Diagnostic: Power Loss 2BRead0 = Normal, 1 = In Alarm
BI11380Diagnostic: Pumpdown Terminated Ckt1Read0 = Normal, 1 = In Alarm
BI11381Diagnostic: Pumpdown Terminated Ckt2Read0 = Normal, 1 = In Alarm
BI11382Diagnostic: Pumpdown Terminated By Time Ckt2Read0 = Normal, 1 = In Alarm
BI11383Diagnostic: Pumpdown Terminated By Time Ckt1Read0 = Normal, 1 = In Alarm
BI11384Diagnostic: Refrigerant Charge Loss Detected Ckt1Read0 = Normal, 1 = In Alarm
BI11385Diagnostic: Refrigerant Charge Loss Detected Ckt2Read0 = Normal, 1 = In Alarm
BI11386Diagnostic: Restart Inhibit Invoked 1ARead0 = Normal, 1 = In Alarm
BI11387Diagnostic: Restart Inhibit Invoked 1BRead0 = Normal, 1 = In Alarm
BI11388Diagnostic: Restart Inhibit Invoked 2ARead0 = Normal, 1 = In Alarm
BI11389Diagnostic: Restart Inhibit Invoked 2BRead0 = Normal, 1 = In Alarm
BI11390Diagnostic: Severe Current Imbalance 1ARead0 = Normal, 1 = In Alarm
BI11391Diagnostic: Severe Current Imbalance 1BRead0 = Normal, 1 = In Alarm
BI11392Diagnostic: Severe Current Imbalance 2ARead0 = Normal, 1 = In Alarm
BI11393Diagnostic: Severe Current Imbalance 2BRead0 = Normal, 1 = In Alarm
BI11394Diagnostic: Software Error 1001: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11395Diagnostic: Software Error 1002: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11396Diagnostic: Software Error 1003: Call Trane ServiceRead0 = Normal, 1 = In Alarm
BI11397Diagnostic: Starter Comm Loss: Main Processor 1ARead0 = Normal, 1 = In Alarm
BI11398Diagnostic: Starter Comm Loss: Main Processor 1BRead0 = Normal, 1 = In Alarm
BI11399Diagnostic: Starter Comm Loss: Main Processor 2ARead0 = Normal, 1 = In Alarm
BI11400Diagnostic: Starter Comm Loss: Main Processor 2BRead0 = Normal, 1 = In Alarm
BI11401Diagnostic: Starter Contactor Interrupt Failure 1ARead0 = Normal, 1 = In Alarm
BI11402Diagnostic: Starter Contactor Interrupt Failure 1BRead0 = Normal, 1 = In Alarm
BI11403Diagnostic: Starter Contactor Interrupt Failure 2ARead0 = Normal, 1 = In Alarm
BI11404Diagnostic: Starter Contactor Interrupt Failure 2BRead0 = Normal, 1 = In Alarm
BI11405Diagnostic: Starter Did Not Fully Accelerate 1BRead0 = Normal, 1 = In Alarm
BI11406Diagnostic: Starter Did Not Fully Accelerate 1ARead0 = Normal, 1 = In Alarm
BI11407Diagnostic: Starter Did Not Fully Accelerate 2BRead0 = Normal, 1 = In Alarm
BI11408Diagnostic: Starter Did Not Transition 1ARead0 = Normal, 1 = In Alarm
BI11409Diagnostic: Starter Did Not Transition 1BRead0 = Normal, 1 = In Alarm
BI11410Diagnostic: Starter Did Not Transition 2ARead0 = Normal, 1 = In Alarm
BI11411Diagnostic: Starter Did Not Transition 2BRead0 = Normal, 1 = In Alarm
BI11412Diagnostic: Starter Dry Run Test 1ARead0 = Normal, 1 = In Alarm
BI11413Diagnostic: Starter Dry Run Test 1BRead0 = Normal, 1 = In Alarm
BI11414Diagnostic: Starter Dry Run Test 2ARead0 = Normal, 1 = In Alarm
BI11415Diagnostic: Starter Dry Run Test 2BRead0 = Normal, 1 = In Alarm
BI11416Diagnostic: Starter Failed to Arm/Start 1ARead0 = Normal, 1 = In Alarm
BI11417Diagnostic: Starter Failed to Arm/Start 1BRead0 = Normal, 1 = In Alarm
BI11418Diagnostic: Starter Failed to Arm/Start 2ARead0 = Normal, 1 = In Alarm
BI11419Diagnostic: Starter Failed to Arm/Start 2BRead0 = Normal, 1 = In Alarm
BI11420Diagnostic: Starter Fault Type I 1ARead0 = Normal, 1 = In Alarm
BI11421Diagnostic: Starter Fault Type I 1BRead0 = Normal, 1 = In Alarm
BI11422Diagnostic: Starter Fault Type I 2ARead0 = Normal, 1 = In Alarm
BI11423Diagnostic: Starter Fault Type I 2BRead0 = Normal, 1 = In Alarm
BI11424Diagnostic: Starter Fault Type II 1ARead0 = Normal, 1 = In Alarm
BI11425Diagnostic: Starter Fault Type II 1BRead0 = Normal, 1 = In Alarm
BI11426Diagnostic: Starter Fault Type II 2ARead0 = Normal, 1 = In Alarm
BI11427Diagnostic: Starter Fault Type II 2BRead0 = Normal, 1 = In Alarm
BI11428Diagnostic: Starter Fault Type III 1ARead0 = Normal, 1 = In Alarm
BI11429Diagnostic: Starter Fault Type III 1BRead0 = Normal, 1 = In Alarm
BI11430Diagnostic: Starter Fault Type III 2ARead0 = Normal, 1 = In Alarm
BI11431Diagnostic: Starter Fault Type III 2BRead0 = Normal, 1 = In Alarm
BI11432Diagnostic: Starter Module Memory Error Type 1 1ARead0 = Normal, 1 = In Alarm
BI11433Diagnostic: Starter Module Memory Error Type 1 1BRead0 = Normal, 1 = In Alarm
BI11434Diagnostic: Starter Module Memory Error Type 1 2ARead0 = Normal, 1 = In Alarm
BI11435Diagnostic: Starter Module Memory Error Type 1 2BRead0 = Normal, 1 = In Alarm
BI11436Diagnostic: Starter Module Memory Error Type 2 1ARead0 = Normal, 1 = In Alarm
BI11437Diagnostic: Starter Module Memory Error Type 2 1BRead0 = Normal, 1 = In Alarm
BI11438Diagnostic: Starter Module Memory Error Type 2 2ARead0 = Normal, 1 = In Alarm
BI11439Diagnostic: Starter Module Memory Error Type 2 2BRead0 = Normal, 1 = In Alarm
BI11440Diagnostic: Starts/Hours Modified 1ARead0 = Normal, 1 = In Alarm
BI11441Diagnostic: Starts/Hours Modified 1BRead0 = Normal, 1 = In Alarm
BI11442Diagnostic: Starts/Hours Modified 2ARead0 = Normal, 1 = In Alarm
BI11443Diagnostic: Starts/Hours Modified 2BRead0 = Normal, 1 = In Alarm
BI11444Diagnostic: Suction Pressure Transducer Ckt2Read0 = Normal, 1 = In Alarm
BI11445Diagnostic: Suction Pressure Transducer Ckt1Read0 = Normal, 1 = In Alarm
BI11446Diagnostic: Suction Refrigerant Pressure Sensor 1ARead0 = Normal, 1 = In Alarm
BI11447Diagnostic: Suction Refrigerant Pressure Sensor 1BRead0 = Normal, 1 = In Alarm
BI11448Diagnostic: Suction Refrigerant Pressure Sensor 2ARead0 = Normal, 1 = In Alarm
BI11449Diagnostic: Suction Refrigerant Pressure Sensor 2BRead0 = Normal, 1 = In Alarm
BI11450Diagnostic: Suction Temperature SensorRead0 = Normal, 1 = In Alarm
BI11451Diagnostic: Transition Complete Input Opened 1ARead0 = Normal, 1 = In Alarm
BI11452Diagnostic: Transition Complete Input Opened 1BRead0 = Normal, 1 = In Alarm
BI11453Diagnostic: Transition Complete Input Opened 2ARead0 = Normal, 1 = In Alarm
BI11454Diagnostic: Transition Complete Input Opened 2BRead0 = Normal, 1 = In Alarm
BI11455Diagnostic: Transition Complete Input Shorted 1ARead0 = Normal, 1 = In Alarm
BI11456Diagnostic: Transition Complete Input Shorted 1BRead0 = Normal, 1 = In Alarm
BI11457Diagnostic: Transition Complete Input Shorted 2ARead0 = Normal, 1 = In Alarm
BI11458Diagnostic: Transition Complete Input Shorted 2BRead0 = Normal, 1 = In Alarm
BI11459Diagnostic: Under VoltageRead0 = Normal, 1 = In Alarm
BI11460Diagnostic: Under Voltage 1ARead0 = Normal, 1 = In Alarm
BI11461Diagnostic: Under Voltage 2ARead0 = Normal, 1 = In Alarm
BI11462Diagnostic: Unexpected Starter Shutdown 1ARead0 = Normal, 1 = In Alarm
BI11463Diagnostic: Unexpected Starter Shutdown 1BRead0 = Normal, 1 = In Alarm
BI11464Diagnostic: Unexpected Starter Shutdown 2ARead0 = Normal, 1 = In Alarm
BI11465Diagnostic: Unexpected Starter Shutdown 2BRead0 = Normal, 1 = In Alarm
BI11466Diagnostic: Very Low Discharge Superheat 1ARead0 = Normal, 1 = In Alarm
BI11467Diagnostic: Very Low Discharge Superheat 2ARead0 = Normal, 1 = In Alarm
BI11468Diagnostic: Very Low Evap Rfgt Pressure 1ARead0 = Normal, 1 = In Alarm
BI11469Diagnostic: Very Low Evap Rfgt Pressure 1BRead0 = Normal, 1 = In Alarm
BI11470Diagnostic: Very Low Evap Rfgt Pressure 2ARead0 = Normal, 1 = In Alarm
BI11471Diagnostic: Very Low Evap Rfgt Pressure 2BRead0 = Normal, 1 = In Alarm
BI11472Diagnostic: Water System Differential PressureRead0 = Normal, 1 = In Alarm
BI11473Diagnostic: Energy Meter Write Value FailureRead0 = Normal, 1 = In Alarm
BI11474Diagnostic: Write Command Failure Energy Meter 1Read0 = Normal, 1 = In Alarm
BI11475Diagnostic: Write Command Failure Energy Meter 2Read0 = Normal, 1 = In Alarm
BI11476Diagnostic: High Evaporator PressureRead0 = Normal, 1 = In Alarm
BI11477Comm Loss: Starter Panel High Temperature LimitRead0 = Normal, 1 = In Alarm
BVmin10100Chiller Auto Stop Command BASBAS command for Chiller Auto StopWrite0 = Stop, 1 = Auto
BV10101Reset DiagnosticBAS diagnostic reset command to clear resettable active diagnosticsWrite0 = Normal, 1 = Reset
BV10102Circuit 1 Lockout BASBAS to lock circuit 1Write0 = Normal, 1 = Locked Out
BV10103Circuit 2 Lockout BASBAS to lock circuit 2Write0 = Normal, 1 = Locked Out
BV10104Energy Consumption ResetBAS command to reset Energy Consumption Resettable counterWrite0 = Accumulating, 1 = Reset
BV10105Noise Reduction Request BASBAS Noise Reduction CommandWrite0 = Normal, 1 = Reduce Noise
BV10106Compressor 1A Lockout BASBAS Compressor 1A LockoutWrite0 = Normal, 1 = Locked Out
BV10107Compressor 1B Lockout BASBAS Compressor 1B LockoutWrite0 = Normal, 1 = Locked Out
BV10108Compressor 2A Lockout BASBAS Compressor 2A LockoutWrite0 = Normal, 1 = Locked Out
BV10109Compressor 2B Lockout BASBAS Compressor 2B LockoutWrite0 = Normal, 1 = Locked Out
BV10110Evaporator Water Pump Request BASBAS Evaporator Water Pump RequestWrite0 = Auto, 1 = On
BV10111Condenser Water Pump Request BASBAS Condenser Water Pump RequestWrite0 = Auto, 1 = On
MI10100Running ModeRunning state of the chillerRead1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode
MI10101Operating ModeOperating mode of the chillerRead1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling
MI10103Refrigerant TypeChiller refrigerant typeRead5 = R-134a, 13 = R-513A, 16 = R-1234ze(E), 18 = R-515B
MI10104Manufacturing LocationLocation that the chiller was manufacturedRead3 = Pueblo, 4 = Charmes
MI10105Cooling TypeCooling Type of chillerRead1 = Water Cooled, 2 = Air Cooled
MI10106Model Information [GEN2]Model information of chillerRead17 = RTWF, 30 = RTSF, 41 = RTWF XSE, 45 = RTWD, 46 = RTUD
MVmin10100Chiller Mode Command BASCommand the chiller ModeWrite1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Series R RTWD and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Trane Symbio 800 Series R RTWD

How many BACnet points does the Trane Symbio 800 Series R RTWD have?

This list has 685 BACnet objects: 144 analog inputs, 7 analog values, 515 binary inputs, 12 binary values, 6 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Trane Symbio 800 Series R RTWD BACnet points are writable?

20 of the 685 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Trane Symbio 800 Series R RTWD BACnet documentation?

The source is Symbio 800 Integration Points List BACnet - Series R Model RTWD (BAS-PTS017A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS017A-EN_11152024.pdf.

What are the minimum BACnet points to integrate the Trane Symbio 800 Series R RTWD?

Start with BV 10100 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10103 Chiller Running State (Chiller on/off status); BI 10101 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10103 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10108 Actual Running Capacity (Actual running capacity in percent); BI 10108 Diagnostic Present (Any active diagnostic (alarm) on the chiller).

How do I enable BMS control of the Trane Symbio 800 Series R RTWD?

BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10120 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.

How do I check these points on the real Symbio 800 Series R RTWD?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Trane BACnet points lists

Source: Symbio 800 Integration Points List BACnet - Series R Model RTWD · BAS-PTS017A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.