Water-cooled screw chiller controller · BACnet points list
Trane Symbio 800 Series R RTWD BACnet points list
Updated 28 October 2026
RTWD chillers with Symbio 800 publish about 685 BACnet objects; roughly three-quarters are diagnostic binary inputs. Operating data such as water temperatures, refrigerant pressures, compressor starts and run hours are AIs. Setpoints, lockouts, pump requests and the auto/stop command are AV/BV/MV objects.
This page lists 685 BACnet objects for the Trane Symbio 800 Series R RTWD — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 Series R RTWD
- Equipment
- Water-cooled screw chiller controller
- Equipment type
- Chillers
- BACnet objects
- 685 (20 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017
BMS integration notes: Trane Symbio 800 Series R RTWD
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10100 | Chiller Auto Stop Command BAS | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10103 | Chiller Running State | Chiller on/off status | Read |
| BI 10101 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10103 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10108 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10108 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10120 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
Trane Symbio 800 Series R RTWD BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Cool/Heat Setpoint Temperature | Presently in use Chilled/Hot Water Setpoint | Temperature | Read | |
| AI | 10101 | Active Demand Limit Setpoint | Presently in use or "active" setting of the Demand Limit | Percentage | Read | |
| AI | 10102 | Evaporator Entering Water Temperature | This is present Evaporator Entering or Return water temperature | Temperature | Read | |
| AImin | 10103 | Evaporator Leaving Water Temperature | This is the temperature of the water leaving the evaporator | Temperature | Read | |
| AI | 10104 | Outdoor Air Temperature | The temperature of the outdoor air temperature sensor | Temperature | Read | |
| AI | 10105 | Number of Circuits | Read | |||
| AI | 10106 | Number of Compressors, Circuit 1 | Read | |||
| AI | 10107 | Number of Compressors, Circuit 2 | Read | |||
| AImin | 10108 | Actual Running Capacity | Actual chiller running capacity (same as Total Compressor Current %RLA) | Percentage | Read | |
| AI | 10109 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Evaporator Absolute Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10110 | Condenser Refrigerant Absolute Pressure Circuit 1 | Condenser Absolute Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10111 | Differential Refrigerant Pressure Ckt1 | Displays the differential pressure for the respective circuit as defined by | Pressure, Fluidic | Read | |
| AI | 10112 | Evaporator Shell Refrigerant Pressure Ckt1 | Pressure, Fluidic | Read | ||
| AI | 10113 | Evaporator Saturated Rfgt Temp Ckt1 | Temperature | Read | ||
| AI | 10114 | Condenser Saturated Rfgt Temp Ckt1 | Temperature | Read | ||
| AI | 10115 | Discharge Temperature Cprsr1A | Temperature | Read | ||
| AI | 10116 | Oil Absolute Pressure Cprsr1A | Absolute oil pressure for the compressor 1A | Pressure, Fluidic | Read | |
| AI | 10117 | Starts Cprsr1A | The total number of starts that the given compressor has experienced | Read | ||
| AI | 10118 | Running Time Cprsr1A | The total accumulated running time | Read | ||
| AI | 10119 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Evaporator Absolute Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10120 | Condenser Refrigerant Absolute Pressure Circuit 2 | Condenser Absolute Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10121 | Differential Refrigerant Pressure Ckt2 | Displays the differential pressure for the respective circuit as defined by | Pressure, Fluidic | Read | |
| AI | 10122 | Evaporator Shell Refrigerant Pressure Ckt2 | Pressure, Fluidic | Read | ||
| AI | 10123 | Evaporator Saturated Rfgt Temp Ckt2 | Temperature | Read | ||
| AI | 10124 | Condenser Saturated Rfgt Temp Ckt2 | Temperature | Read | ||
| AI | 10125 | Compressor Suction Temperature | Temperature | Read | ||
| AI | 10126 | Discharge Temperature Cprsr2A | Temperature | Read | ||
| AI | 10127 | Oil Absolute Pressure Cprsr2A | Absolute oil pressure for the compressor 2A | Pressure, Fluidic | Read | |
| AI | 10128 | Discharge Temperature Cprsr1B | Temperature | Read | ||
| AI | 10129 | Oil Absolute Pressure Cprsr1B | Absolute oil pressure for the compressor 1B | Pressure, Fluidic | Read | |
| AI | 10130 | Starts Cprsr1B | The total number of starts that the given compressor has experienced | Read | ||
| AI | 10131 | Running Time Cprsr1B | The total accumulated running time | Read | ||
| AI | 10132 | Starts Cprsr2A | The total number of starts that the given compressor has experienced | Read | ||
| AI | 10133 | Running Time Cprsr2A | The total accumulated running time | Read | ||
| AI | 10134 | Discharge Temperature Cprsr2B | Temperature | Read | ||
| AI | 10135 | Oil Absolute Pressure Cprsr2B | Absolute oil pressure for the compressor 2B | Pressure, Fluidic | Read | |
| AI | 10136 | Starts Cprsr2B | The total number of starts that the given compressor has experienced | Read | ||
| AI | 10137 | Running Time Cprsr2B | The total accumulated running time | Read | ||
| AI | 10138 | Motor Voltage AB Starter 1A | Motor voltage Vab for the respective compressor | Voltage | Read | |
| AI | 10139 | Motor Voltage AB Starter 1B | Motor voltage Vab for the respective compressor | Voltage | Read | |
| AI | 10140 | Motor Voltage AB Starter 2A | Motor voltage Vab for the respective compressor | Voltage | Read | |
| AI | 10141 | Motor Voltage AB Starter 2B | Motor voltage Vab for the respective compressor | Voltage | Read | |
| AI | 10142 | Oil Temperature Circuit 1 | The oil temperature for the respective compressor | Temperature | Read | |
| AI | 10143 | Oil Temperature Circuit 2 | The oil temperature for the respective compressor | Temperature | Read | |
| AI | 10144 | Condenser Entering Water Temperature | This is present Condenser Entering or Return water temperature | Temperature | Read | |
| AI | 10145 | Condenser Leaving Water Temperature | This is the temperature of the water leaving the Condenser | Temperature | Read | |
| AI | 10146 | Unit Power Consumption | Estimate of the total Chiller Power being presently utilized | Power, Electrical | Read | |
| AI | 10147 | Energy Consumption NonReset | Cumulate energy consumption of unit | Energy, Electrical | Read | |
| AI | 10148 | Energy Consumption Resettable | Energy, Electrical | Read | ||
| AI | 10149 | Motor Current L1 Starter 1A | Motor current phase A in amps for the respective compressor | Current | Read | |
| AI | 10150 | Motor Current L2 Starter 1A | Motor current phase B in amps for the respective compressor | Current | Read | |
| AI | 10151 | Motor Current L3 Starter 1A | Motor current phase C in amps for the respective compressor | Current | Read | |
| AI | 10152 | Motor Current L1 % RLA Starter 1A | Motor current phase A in % RLA for the respective compressor | Percentage | Read | |
| AI | 10153 | Motor Current L2 % RLA Starter 1A | Motor current phase B in % RLA for the respective compressor | Percentage | Read | |
| AI | 10154 | Motor Current L3 % RLA Starter 1A | Motor current phase C in % RLA for the respective compressor | Percentage | Read | |
| AI | 10155 | Motor Current L1 Starter 2A | Motor current phase A in amps for the respective compressor | Current | Read | |
| AI | 10156 | Motor Current L2 Starter 2A | Motor current phase B in amps for the respective compressor | Current | Read | |
| AI | 10157 | Motor Current L3 Starter 2A | Motor current phase C in amps for the respective compressor | Current | Read | |
| AI | 10158 | Motor Current L1 % RLA Starter 2A | Motor current phase A in % RLA for the respective compressor | Percentage | Read | |
| AI | 10159 | Motor Current L2 % RLA Starter 2A | Motor current phase B in % RLA for the respective compressor | Percentage | Read | |
| AI | 10160 | Motor Current L3 % RLA Starter 2A | Motor current phase C in % RLA for the respective compressor | Percentage | Read | |
| AI | 10161 | Motor Current L1 Starter 1B | Motor current phase A in amps for the respective compressor | Current | Read | |
| AI | 10162 | Motor Current L2 Starter 1B | Motor current phase B in amps for the respective compressor | Current | Read | |
| AI | 10163 | Motor Current L3 Starter 1B | Motor current phase C in amps for the respective compressor | Current | Read | |
| AI | 10164 | Motor Current L1 % RLA Starter 1B | Motor current phase A in % RLA for the respective compressor | Percentage | Read | |
| AI | 10165 | Motor Current L2 % RLA Starter 1B | Motor current phase B in % RLA for the respective compressor | Percentage | Read | |
| AI | 10166 | Motor Current L3 % RLA Starter 1B | Motor current phase C in % RLA for the respective compressor | Percentage | Read | |
| AI | 10167 | Motor Current L1 Starter 2B | Motor current phase A in amps for the respective compressor | Current | Read | |
| AI | 10168 | Motor Current L2 Starter 2B | Motor current phase B in amps for the respective compressor | Current | Read | |
| AI | 10169 | Motor Current L3 Starter 2B | Motor current phase C in amps for the respective compressor | Current | Read | |
| AI | 10170 | Motor Current L1 % RLA Starter 2B | Motor current phase A in % RLA for the respective compressor | Percentage | Read | |
| AI | 10171 | Motor Current L2 % RLA Starter 2B | Motor current phase B in % RLA for the respective compressor | Percentage | Read | |
| AI | 10172 | Motor Current L3 % RLA Starter 2B | Motor current phase C in % RLA for the respective compressor | Percentage | Read | |
| AI | 10173 | Motor Current A Cprsr1A | Motor Current U AFD 1A | Current | Read | |
| AI | 10174 | Motor Current B Cprsr1A | Motor Current V AFD 1A | Current | Read | |
| AI | 10175 | Motor Current C Cprsr1A | Motor Current W AFD 1A | Current | Read | |
| AI | 10176 | Motor % RLA A Cprsr1A | Motor Current U % RLA AFD 1A | Percentage | Read | |
| AI | 10177 | Motor % RLA B Cprsr1A | Motor Current V % RLA AFD 1A | Percentage | Read | |
| AI | 10178 | Motor % RLA C Cprsr1A | Motor Current W % RLA AFD 1A | Percentage | Read | |
| AI | 10179 | Motor Current A Cprsr2A | Motor Current U AFD 2A | Current | Read | |
| AI | 10180 | Motor Current B Cprsr2A | Motor Current V AFD 2A | Current | Read | |
| AI | 10181 | Motor Current C Cprsr2A | Motor Current W AFD 2A | Current | Read | |
| AI | 10182 | Motor % RLA A Cprsr2A | Motor Current U % RLA AFD 2A | Percentage | Read | |
| AI | 10183 | Motor % RLA B Cprsr2A | Motor Current V % RLA AFD 2A | Percentage | Read | |
| AI | 10184 | Motor % RLA C Cprsr2A | Motor Current W % RLA AFD 2A | Percentage | Read | |
| AI | 10185 | Average Motor Current % RLA AFD 1A | Motor average RLA for for the respective compressor | Percentage | Read | |
| AI | 10186 | Average Motor Current % RLA AFD 2A | Motor average RLA for for the respective compressor | Percentage | Read | |
| AI | 10187 | Unit Source ID (Last Diagnostic Code) | Last Logged Diagnostic Spec BAS | Read | ||
| AI | 10188 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10189 | Active Chilled Water Setpoint | Presently in use Chilled Water Setpoint | Temperature | Read | |
| AI | 10190 | Active Hot Water Setpoint | Presently in use Hot Water Setpoint | Temperature | Read | |
| AI | 10191 | Unit Load Command | Percentage | Read | ||
| AI | 10192 | Air Flow Percentage Circuit 1 | Air Flow Ckt1 | Percentage | Read | |
| AI | 10193 | Air Flow Percentage Circuit 2 | Air Flow Ckt2 | Percentage | Read | |
| AI | 10194 | Evaporator Refrigerant Pressure Circuit 1 | Evaporator Gauge Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10195 | Condenser Refrigerant Pressure Circuit 1 | Condenser Gauge Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10196 | Evaporator Refrigerant Pressure Circuit 2 | Evaporator Gauge Refrigerant Pressure circuit 2 | Pressure, Fluidic | Read | |
| AI | 10197 | Condenser Refrigerant Pressure Circuit 2 | Condenser Gauge Refrigerant Pressure circuit 2 | Pressure, Fluidic | Read | |
| AI | 10198 | Condenser Control Output | Condenser Head Pressure Control Output | Percentage | Read | |
| AI | 10199 | Oil Pressure Cprsr1A | Gauge oil pressure for the compressor 1A | Pressure, Fluidic | Read | |
| AI | 10200 | Oil Pressure Cprsr2A | Gauge oil pressure for the compressor 2A | Pressure, Fluidic | Read | |
| AI | 10201 | Oil Pressure Cprsr1B | Gauge oil pressure for the compressor 1B | Pressure, Fluidic | Read | |
| AI | 10202 | Oil Pressure Cprsr2B | Gauge oil pressure for the compressor 2B | Pressure, Fluidic | Read | |
| AI | 10203 | Evaporator Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10204 | Evaporator Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10205 | Condenser Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10206 | Condenser Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10207 | Average Line Current Circuit 1 | Average Line Current Meter 1 | Current | Read | |
| AI | 10208 | Average Line Current Circuit 2 | Average Line Current Meter 2 | Current | Read | |
| AI | 10209 | Average Line Voltage Circuit 1 | Average Line Voltage Meter 1 | Voltage | Read | |
| AI | 10210 | Average Line Voltage Circuit 2 | Average Line Voltage Meter 2 | Voltage | Read | |
| AI | 10211 | Line Current L1 Circuit 1 | Line Current L1 Meter 1 | Current | Read | |
| AI | 10212 | Line Current L2 Circuit 1 | Line Current L2 Meter 1 | Current | Read | |
| AI | 10213 | Line Current L3 Circuit 1 | Line Current L3 Meter 1 | Current | Read | |
| AI | 10214 | Line Current L1 Circuit 2 | Line Current L1 Meter 2 | Current | Read | |
| AI | 10215 | Line Current L2 Circuit 2 | Line Current L3 Meter 2 | Current | Read | |
| AI | 10216 | Line Current L3 Circuit 2 | Line Current L3 Meter 2 | Current | Read | |
| AI | 10217 | Voltage L1-L2 Circuit 1 | Line Voltage L1-L2 Meter 1 | Voltage | Read | |
| AI | 10218 | Voltage L2-L3 Circuit 1 | Line Voltage L2-L3 Meter 1 | Voltage | Read | |
| AI | 10219 | Voltage L1-L3 Circuit 1 | Line Voltage L1-L3 Meter 1 | Voltage | Read | |
| AI | 10220 | Voltage L1-L2 Circuit 2 | Line Voltage L1-L2 Meter 2 | Voltage | Read | |
| AI | 10221 | Voltage L2-L1 Circuit 2 | Line Voltage L2-L3 Meter 2 | Voltage | Read | |
| AI | 10222 | Voltage L1-L3 Circuit 2 | Line Voltage L1-L3 Meter 2 | Voltage | Read | |
| AI | 10223 | Line Frequency Circuit 1 | Line Frequency Meter 1 | Read | ||
| AI | 10224 | Line Frequency Circuit 2 | Line Frequency Meter 2 | Read | ||
| AI | 10225 | Power Factor Circuit 1 | Power Factor Meter 1 | Read | ||
| AI | 10226 | Power Factor Circuit 2 | Power Factor Meter 2 | Read | ||
| AI | 10227 | Power Demand Circuit 1 | Power Demand Meter 1 | Power, Electrical | Read | |
| AI | 10228 | Power Demand Circuit 2 | Power Demand Meter 2 | Power, Electrical | Read | |
| AI | 10229 | Power Factor | Unit Power Factor | Read | ||
| AI | 10230 | Current L1 | Meter Line Current L1 | Current | Read | |
| AI | 10231 | Current L2 | Meter Line Current L2 | Current | Read | |
| AI | 10232 | Current L3 | Meter Line Current L3 | Current | Read | |
| AI | 10233 | Average Current | Meter Average Line Current | Current | Read | |
| AI | 10234 | Voltage L1-L2 | Meter Line Voltage L1-L2 | Voltage | Read | |
| AI | 10235 | Voltage L2-L3 | Meter Line Voltage L2-L3 | Voltage | Read | |
| AI | 10236 | Voltage L1-L3 | Meter Line Voltage L1-L3 | Voltage | Read | |
| AI | 10237 | Average Voltage L-L | Meter Average Line Voltage | Voltage | Read | |
| AI | 10238 | Line Frequency | Unit Line Frequency | Read | ||
| AI | 10239 | Unit Power Demand | Chiller Power Demand | Power, Electrical | Read | |
| AI | 10240 | Active Cooling Differential to Start | Presently in use Cooling Differential to Start Setpoint | Temperature, Delta | Read | |
| AI | 10241 | Active Cooling Differential to Stop | Presently in use Cooling Differential to Stop Setpoint | Temperature, Delta | Read | |
| AI | 10242 | Active Heating Differential to Start | Presently in use Heating Differential to Start Setpoint | Temperature, Delta | Read | |
| AI | 10243 | Active Heating Differential to Stop | Presently in use Heating Differential to Stop Setpoint | Temperature, Delta | Read | |
| AVmin | 10100 | Chilled Water Setpoint | Desired evaporator leaving water temperature if chiller is in cooling mode | Temperature | Write | |
| AVmin | 10101 | Demand Limit Setpoint | Sets the maximum capacity that the chiller can use | Percentage | Write | |
| AV | 10102 | Hot Water Setpoint | Desired condenser leaving water temperature if chiller is in heating mode | Temperature | Write | |
| AV | 10103 | BAS Cooling Differential to Start | Desired Cooling Differential to Start if chiller is in cooling mode | Temperature, Delta | Write | |
| AV | 10104 | BAS Cooling Differential to Stop | Desired Cooling Differential to Stop if chiller is in cooling mode | Temperature, Delta | Write | |
| AV | 10105 | BAS Heating Differential to Start | Desired Heating Differential to Start if chiller is in heating mode | Temperature, Delta | Write | |
| AV | 10106 | BAS Heating Differential to Stop | Desired Heating Differential to Stop if chiller is in heating mode | Temperature, Delta | Write | |
| BI | 10100 | Run Enable | The chiller is available to run or is currently running | Read | 0 = Run Not Enabled, 1 = Run Enabled | |
| BImin | 10101 | Local Setpoint Control | The chiller is being controlled by local setpoints instead of BAS setpoints | Read | 0 = Remote Control, 1 = Local Control | |
| BI | 10102 | Limit Mode Relay Status | The Chiller is in a Limit mode | Read | 0 = Off, 1 = On | |
| BImin | 10103 | Chiller Running State | Primary running mode of the chiller sequence | Read | 0 = Off, 1 = On | |
| BI | 10104 | Maximum Capacity | Read | 0 = Off, 1 = On | ||
| BI | 10105 | Manual Override Exists | There is a Manual Override active | Read | 0 = Off, 1 = On | |
| BI | 10106 | Emergency Stop | Displays the Status of the Emergency Stop | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | |
| BI | 10107 | Evaporator Water Flow Status | Water flow through the evaporator | Read | 0 = No Flow, 1 = Flow | |
| BImin | 10108 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10109 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10110 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10111 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10112 | Diagnostic Present: Information | /eVar/Pltm1DiagPrsntInfo/ | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10113 | Diagnostic Present: Advisory | /eVar/Pltm1DiagPrsntAdvsry/ | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10114 | Diagnostic Present: Critical | /eVar/Pltm1DiagPrsntCrtcl/ | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10115 | Diagnostic Present: Service Required | /eVar/Pltm1DiagPrsntSvcRqrd/ | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10116 | Compressor 1A Running Status | Running status of compressor 1A | Read | 0 = Stop, 1 = Auto | |
| BI | 10117 | Compressor 1B Running Status | Running status of compressor 1B | Read | 0 = Stop, 1 = Auto | |
| BI | 10118 | Compressor 2A Running Status | Running status of compressor 2A | Read | 0 = Stop, 1 = Auto | |
| BI | 10119 | Compressor 2B Running Status | Running status of compressor 2B | Read | 0 = Stop, 1 = Auto | |
| BI | 10120 | External Auto Stop | Status of External Auto Stop input | Read | 0 = Stop, 1 = Auto | |
| BI | 10121 | Condenser Water Pump Command | This provides a status of the Chillers Condenser Water Pump output | Read | 0 = Inactive, 1 = Active | |
| BI | 10122 | Evaporator Water Pump Command | This provides a status of the Chillers Evaporator Water Pump output | Read | 0 = Off, 1 = On | |
| BI | 10123 | Condenser Water Flow Status | Water flow through the condenser | Read | 0 = Inactive, 1 = Active | |
| BI | 10124 | Front Panel Auto Stop Status | Status of Front Auto Stop input | Read | 0 = Stop, 1 = Auto | |
| BI | 10125 | Circuit Manual Reset Indicator (CMR) Ckt1 | Or not there is an alarm present | Read | 0 = Inactive, 1 = Active | |
| BI | 10126 | Circuit Manual Reset Indicator (CMR) Ckt2 | Or not there is an alarm present | Read | 0 = Inactive, 1 = Active | |
| BI | 10127 | Circuit Auto Reset Indicator (CAR) Ckt1 | Or not there is non-latching alarm present on circuit 1 | Read | 0 = Inactive, 1 = Active | |
| BI | 10128 | Circuit Auto Reset Indicator (CAR) Ckt2 | Or not there is non-latching alarm present on circuit 2 | Read | 0 = Inactive, 1 = Active | |
| BI | 10129 | Head Pressure Relief Request | Head Relief Request Relay | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10130 | Alarm - General Latching Unit | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10131 | Alarm - General Non Latching Unit | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10132 | Alarm - General Latching Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10133 | Alarm - General Latching Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10134 | Alarm - General Non Latching Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10135 | Alarm - General Non Latching Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10136 | Noise Reduction Request Active | Status of Noise Reduction Request | Read | 0 = Off, 1 = On | |
| BI | 11000 | Comm Loss: %RLA Indication Output (Vdc) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Comm Loss: AFD 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Comm Loss: AFD 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Comm Loss: AFD Fault Input 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Comm Loss: AFD Fault Input 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Comm Loss: AFD Fault Input 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Comm Loss: AFD Fault Input 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Comm Loss: AFD Run Command 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Comm Loss: AFD Run Command 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Comm Loss: AFD Speed Command 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Comm Loss: AFD Speed Command 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Comm Loss: AFD Speed Command 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Comm Loss: AFD Speed Command 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Comm Loss: AOC Inlet Oil Temperature 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Comm Loss: AOC Inlet Oil Temperature 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Comm Loss: Auxiliary Setpoint Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Comm Loss: Chiller Bypass Valve Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Comm Loss: Cond Head Press Cntrl Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Comm Loss: Cond Rfgt Liquid Level Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Comm Loss: Cond Rfgt Liquid Level Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Comm Loss: Cond Water Pump Analog Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Comm Loss: Condenser Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Comm Loss: Condenser Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Comm Loss: Condenser Rfgt Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Comm Loss: Condenser Rfgt Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Comm Loss: Condenser Rfgt Pressure Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Comm Loss: Condenser Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Comm Loss: Condenser Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Comm Loss: Cprsr Disch Rfgt Temp 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Comm Loss: Cprsr Disch Rfgt Temp 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Comm Loss: Cprsr Disch Rfgt Temp 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Comm Loss: Cprsr Disch Rfgt Temp 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Comm Loss: Electronic Expansion Valve Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Comm Loss: Electronic Expansion Valve Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Comm Loss: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Comm Loss: Energy Meter Pulse Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11036 | Comm Loss: Evap Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11037 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Comm Loss: Evap Iso Valve Close Switch Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Comm Loss: Evap Iso Valve Close Switch Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Comm Loss: Evap Iso Valve Open Switch Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Comm Loss: Evap Iso Valve Open Switch Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Comm Loss: Evap Isolation Valve Relay Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Comm Loss: Evap Isolation Valve Relay Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Comm Loss: Evap Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Comm Loss: Evap Oil Return Level Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Comm Loss: Evap Oil Return Level Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Comm Loss: Evap Pump Inv1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Comm Loss: Evap Pump Inv1 Run Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Comm Loss: Evap Rfgt Liquid Level Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Comm Loss: Evap Rfgt Liquid Level Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Comm Loss: Evap Rfgt Pool Temp Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Comm Loss: Evap Rfgt Pool Temp Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Comm Loss: Evap Shell Rfgt Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Comm Loss: Evap Shell Rfgt Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Comm Loss: Evap Water Pump Analog Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Comm Loss: Evap Water Pump Inv Freq Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Comm Loss: Evaporator Pump 1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Comm Loss: Evaporator Pump 2 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Comm Loss: Evaporator Water Pump 1 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Comm Loss: Evaporator Water Pump 2 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Comm Loss: Ext Noise Reduction Request | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Comm Loss: External Ckt2 Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Comm Loss: External Ckt1 Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Comm Loss: External Hot Water Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Comm Loss: Fan Control Relays, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Comm Loss: Fan Control Relays, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Comm Loss: Fan Inverter Fault Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Comm Loss: Fan Inverter Fault Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Comm Loss: Fan Inverter Speed Command Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Comm Loss: Fan Inverter Speed Command Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Comm Loss: High Pressure Cutout Sw 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Comm Loss: High Pressure Cutout Sw 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Comm Loss: High Pressure Cutout Sw 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Comm Loss: High Pressure Cutout Sw 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Comm Loss: High Pressure Cutout Switch Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Comm Loss: High Pressure Cutout Switch Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Comm Loss: HR Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Comm Loss: HR Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: Ice Building Status Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Comm Loss: Liquid Line Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Comm Loss: Liquid Line Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Comm Loss: Liquid Line Temperature Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Comm Loss: Liquid Line Temperature Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Comm Loss: Motor RLA Input 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Comm Loss: Motor RLA Input 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: Motor RLA Input 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Comm Loss: Motor RLA Input 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Comm Loss: Motor Winding Tstat Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Comm Loss: Motor Winding Tstat Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11096 | Comm Loss: Noise Reduction Request Relay Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Comm Loss: Noise Reduction Request Relay Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Comm Loss: Off-cycle Freeze Prot Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Comm Loss: Oil Heater Relay 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Comm Loss: Oil Heater Relay 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Comm Loss: Oil Loss Level Sensor Input Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Comm Loss: Oil Loss Level Sensor Input Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss: Oil Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Comm Loss: Oil Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Comm Loss: Oil Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Comm Loss: Oil Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Comm Loss: Oil Return Gas Pump Drain Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Comm Loss: Oil Return Gas Pump Drain Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11109 | Comm Loss: Oil Return Gas Pump Fill Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11110 | Comm Loss: Oil Return Gas Pump Fill Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11111 | Comm Loss: Oil Return Purge Valve Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Comm Loss: Oil Return Purge Valve Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: Oil Temp, Ckt 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: Oil Temp, Ckt 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Comm Loss: Reversing Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Comm Loss: Slide Valve Load 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: Slide Valve Load 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Comm Loss: Slide Valve Load 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Slide Valve Load 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Comm Loss: Slide Valve Unload 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Comm Loss: Slide Valve Unload 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Comm Loss: Slide Valve Unload 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Comm Loss: Slide Valve Unload 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Comm Loss: Starter 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Comm Loss: Starter 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Comm Loss: Starter 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Comm Loss: Starter 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Step Load 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Step Load 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Comm Loss: Step Load 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Comm Loss: Step Load 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Comm Loss: Suction Rfgt Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Suction Rfgt Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Suction Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Comm Loss: Suction Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Suction Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: Suction Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Comm Loss: Suction Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Comm Loss: Water System Diff Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Winding Temp 1, Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Winding Temp 1, Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Comm Loss: Winding Temp 2, Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Diagnostic: AFD %RLA Feedback 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Diagnostic: AFD %RLA Feedback 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Diagnostic: AFD %RLA Feedback 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Diagnostic: AFD %RLA Feedback 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Diagnostic: AFD Bump Complete 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Diagnostic: AFD Bump Complete 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Diagnostic: AFD Bump Current High 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Diagnostic: AFD Bump Current High 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Diagnostic: AFD Comm Loss – 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Diagnostic: AFD Comm Loss – 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Diagnostic: AFD Comm Loss – 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Diagnostic: AFD Comm Loss – 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Diagnostic: AFD Failure to Arm or Start 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Diagnostic: AFD Failure to Arm or Start 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Diagnostic: AFD Failure to Arm or Start 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Diagnostic: AFD Failure to Arm or Start 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Diagnostic: AFD Fault 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Diagnostic: AFD Fault 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Diagnostic: AFD Fault 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Diagnostic: AFD Fault 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Diagnostic: AFD Fault Mains 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Diagnostic: AFD Fault Mains 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Diagnostic: AFD Harmonic Filter Over Temperature 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Diagnostic: AFD Harmonic Filter Over Temperature 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Diagnostic: AFD High Pressure Cutout 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Diagnostic: AFD High Pressure Cutout 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Diagnostic: AFD Interrupt Failure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Diagnostic: AFD Interrupt Failure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Diagnostic: AFD Motor Current Overload 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Diagnostic: AFD Motor Current Overload 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Diagnostic: AFD Motor Current Overload 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Diagnostic: AFD Motor Current Overload 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Diagnostic: AFD Motor Fault 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Diagnostic: AFD Motor Fault 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Diagnostic: AFD Motor Speed Too High 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Diagnostic: AFD Motor Speed Too High 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Diagnostic: AFD Motor Speed Too Low 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Diagnostic: AFD Motor Speed Too Low 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Diagnostic: AFD Pump Out Speed Low 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Diagnostic: AFD Pump Out Speed Low 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Diagnostic: AFD Unexpected Shutdown 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Diagnostic: AFD Unexpected Shutdown 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Diagnostic: AFD Unhandled Fault 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Diagnostic: AFD Unhandled Fault 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Diagnostic: AOC Inlet Oil Temperature Sensor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Diagnostic: AOC Inlet Oil Temperature Sensor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: Check Clock | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: Chiller Service Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Diagnostic: Comm Loss: Winding Temp 2, Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Diagnostic: Cond Rfgt Liquid Level Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: Cond Rfgt Liquid Level Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: Condenser Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: Condenser Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: Condenser Rfgt Pressure Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: Condenser Rfgt Pressure Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Diagnostic: Condenser Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Diagnostic: Condenser Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Diagnostic: Cprsr Did Not Accel: Shutdown 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Diagnostic: Cprsr Did Not Accel: Shutdown 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11205 | Diagnostic: Cprsr Did Not Accel: Shutdown 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Diagnostic: Cprsr Did Not Accel: Shutdown 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Diagnostic: Cprsr Did Not Accel: Transition 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Diagnostic: Cprsr Did Not Accel: Transition 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Diagnostic: Cprsr Did Not Accel: Transition 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: Cprsr Did Not Accel: Transition 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Diagnostic: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Diagnostic: Evap Iso Valve Illegal Switch State Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Diagnostic: Evap Iso Valve Illegal Switch State Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11219 | Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11220 | Diagnostic: Evap Isolation Valve Failed To Close Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: Evap Isolation Valve Failed To Close Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: Evap Isolation Valve Failed To Open Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: Evap Isolation Valve Failed To Open Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: Evap Isolation Valve Open Switch Failure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: Evap Isolation Valve Open Switch Failure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11226 | Diagnostic: Evap Pump 1 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11227 | Diagnostic: Evap Pump 2 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11228 | Diagnostic: Evap Rfgt Pool Temp Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11229 | Diagnostic: Evap Rfgt Pool Temp Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: Evap Spillover Liquid Level Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Diagnostic: Evap Spillover Liquid Level Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Diagnostic: Evap Water Pump 1 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: Evap Water Pump 2 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: Evaporator Approach Error Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Diagnostic: Evaporator Approach Error Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Diagnostic: Evaporator Oil Return Level Sensor, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Diagnostic: Evaporator Oil Return Level Sensor, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11244 | Diagnostic: Evaporator Pump 1 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11245 | Diagnostic: Evaporator Pump 2 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11246 | Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11247 | Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11248 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11249 | Diagnostic: Evaporator Water Flow Lost Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11250 | Diagnostic: Evaporator Water Flow Lost Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11251 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11252 | Diagnostic: Evaporator Water Flow Overdue Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11253 | Diagnostic: Evaporator Water Flow Overdue Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11254 | Diagnostic: Excessive Condenser Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11255 | Diagnostic: Excessive Condenser Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11256 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11257 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11258 | Diagnostic: EXV Pressure Equalization Failed Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11259 | Diagnostic: EXV Pressure Equalization Failed Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11260 | Diagnostic: Fan Inverter Fault Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11261 | Diagnostic: Fan Inverter Fault Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11262 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11263 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11264 | Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11265 | Diagnostic: High Cprsr Rfgt Discharge Temp 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11266 | Diagnostic: High Cprsr Rfgt Discharge Temp 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11267 | Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11268 | Diagnostic: High Cprsr Rfgt Discharge Temp 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11269 | Diagnostic: High Cprsr Rfgt Discharge Temp 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11270 | Diagnostic: High Differential Refrigerant Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11271 | Diagnostic: High Differential Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11272 | Diagnostic: High Differential Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11273 | Diagnostic: High Differential Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11274 | Diagnostic: High Differential Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11275 | Diagnostic: High Evap Shell Rfgt Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11276 | Diagnostic: High Evap Shell Rfgt Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11277 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11278 | Diagnostic: High Motor Winding Temperature 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11279 | Diagnostic: High Motor Winding Temperature 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11280 | Diagnostic: High Motor Winding Temperature Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11281 | Diagnostic: High Motor Winding Temperature Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11282 | Diagnostic: High Oil Temperature Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11283 | Diagnostic: High Oil Temperature Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11284 | Diagnostic: High Pressure Cutout Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11285 | Diagnostic: High Pressure Cutout Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11286 | Diagnostic: High Pressure Cutout 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11287 | Diagnostic: High Pressure Cutout 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11288 | Diagnostic: High Pressure Cutout 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11289 | Diagnostic: High Pressure Cutout 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11290 | Diagnostic: High Refrigerant Pressure Ratio | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11291 | Diagnostic: High Refrigerant Pressure Ratio 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11292 | Diagnostic: High Refrigerant Pressure Ratio 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11293 | Diagnostic: High Refrigerant Pressure Ratio 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11294 | Diagnostic: High Refrigerant Pressure Ratio 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11295 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11296 | Diagnostic: Liquid Line Pressure Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11297 | Diagnostic: Liquid Line Pressure Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11298 | Diagnostic: Liquid Line Temp Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11299 | Diagnostic: Liquid Line Temp Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11300 | Diagnostic: Loss of Oil for Compressor (Running) Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11301 | Diagnostic: Loss of Oil for Compressor (Running) Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11302 | Diagnostic: Loss of Oil for Compressor (Stopped) Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11303 | Diagnostic: Loss of Oil for Compressor (Stopped) Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11304 | Diagnostic: Low Condenser Rfgt Temp Ckt 1: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11305 | Diagnostic: Low Condenser Rfgt Temp Ckt 2: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11306 | Diagnostic: Low Differential Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11307 | Diagnostic: Low Differential Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11308 | Diagnostic: Low Differential Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11309 | Diagnostic: Low Differential Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11310 | Diagnostic: Low Discharge Superheat 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11311 | Diagnostic: Low Discharge Superheat 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11312 | Diagnostic: Low Discharge Superheat 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11313 | Diagnostic: Low Discharge Superheat 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11314 | Diagnostic: Low Evaporator Oil Return Level Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11315 | Diagnostic: Low Evaporator Oil Return Level Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11316 | Diagnostic: Low Evaporator Refrigerant Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11317 | Diagnostic: Low Evaporator Refrigerant Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11318 | Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11319 | Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11320 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11321 | Diagnostic: Low Evaporator Water Temp (Unit On) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11322 | Diagnostic: Low Oil Flow 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11323 | Diagnostic: Low Oil Flow 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11324 | Diagnostic: Low Oil Flow 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11325 | Diagnostic: Low Oil Flow 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11326 | Diagnostic: Low Refrigerant Temperature Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11327 | Diagnostic: Low Refrigerant Temperature Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11328 | Diagnostic: Mfr Maintenance Recommended 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11329 | Diagnostic: Mfr Maintenance Recommended 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11330 | Diagnostic: Mfr Maintenance Recommended 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11331 | Diagnostic: Mfr Maintenance Recommended 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11332 | Diagnostic: Momentary Power Loss 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11333 | Diagnostic: Momentary Power Loss 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11334 | Diagnostic: Momentary Power Loss 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11335 | Diagnostic: Momentary Power Loss 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11336 | Diagnostic: Motor Current Overload 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11337 | Diagnostic: Motor Current Overload 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11338 | Diagnostic: Motor Current Overload 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11339 | Diagnostic: Motor Current Overload 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11340 | Diagnostic: Motor Winding Temp Sensor Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11341 | Diagnostic: Motor Winding Temp Sensor Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11342 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11343 | Diagnostic: MP: Non-Volatile Block Test Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11344 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11345 | Diagnostic: Need Cprsr 1A To Run For Oil Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11346 | Diagnostic: No Differential Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11347 | Diagnostic: No Differential Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11348 | Diagnostic: No Differential Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11349 | Diagnostic: No Differential Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11350 | Diagnostic: Oil Analysis Recommended Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11351 | Diagnostic: Oil Analysis Recommended Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11352 | Diagnostic: Oil Filter Change Recommended Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11353 | Diagnostic: Oil Filter Change Recommended Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11354 | Diagnostic: Oil Flow Protection Fault 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11355 | Diagnostic: Oil Flow Protection Fault 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11356 | Diagnostic: Oil Flow Protection Fault 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11357 | Diagnostic: Oil Flow Protection Fault 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11358 | Diagnostic: Oil Pressure Sensor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11359 | Diagnostic: Oil Pressure Sensor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11360 | Diagnostic: Oil Pressure Sensor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11361 | Diagnostic: Oil Pressure Sensor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11362 | Diagnostic: Oil Temperature Sensor, Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11363 | Diagnostic: Oil Temperature Sensor, Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11364 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11365 | Diagnostic: Over Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11366 | Diagnostic: Over Voltage 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11367 | Diagnostic: Over Voltage 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11368 | Diagnostic: Phase Loss 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11369 | Diagnostic: Phase Loss 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11370 | Diagnostic: Phase Loss 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11371 | Diagnostic: Phase Loss 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11372 | Diagnostic: Phase Reversal 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11373 | Diagnostic: Phase Reversal 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11374 | Diagnostic: Phase Reversal 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11375 | Diagnostic: Phase Reversal 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11376 | Diagnostic: Power Loss 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11377 | Diagnostic: Power Loss 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11378 | Diagnostic: Power Loss 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11379 | Diagnostic: Power Loss 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11380 | Diagnostic: Pumpdown Terminated Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11381 | Diagnostic: Pumpdown Terminated Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11382 | Diagnostic: Pumpdown Terminated By Time Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11383 | Diagnostic: Pumpdown Terminated By Time Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11384 | Diagnostic: Refrigerant Charge Loss Detected Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11385 | Diagnostic: Refrigerant Charge Loss Detected Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11386 | Diagnostic: Restart Inhibit Invoked 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11387 | Diagnostic: Restart Inhibit Invoked 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11388 | Diagnostic: Restart Inhibit Invoked 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11389 | Diagnostic: Restart Inhibit Invoked 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11390 | Diagnostic: Severe Current Imbalance 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11391 | Diagnostic: Severe Current Imbalance 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11392 | Diagnostic: Severe Current Imbalance 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11393 | Diagnostic: Severe Current Imbalance 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11394 | Diagnostic: Software Error 1001: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11395 | Diagnostic: Software Error 1002: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11396 | Diagnostic: Software Error 1003: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11397 | Diagnostic: Starter Comm Loss: Main Processor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11398 | Diagnostic: Starter Comm Loss: Main Processor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11399 | Diagnostic: Starter Comm Loss: Main Processor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11400 | Diagnostic: Starter Comm Loss: Main Processor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11401 | Diagnostic: Starter Contactor Interrupt Failure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11402 | Diagnostic: Starter Contactor Interrupt Failure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11403 | Diagnostic: Starter Contactor Interrupt Failure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11404 | Diagnostic: Starter Contactor Interrupt Failure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11405 | Diagnostic: Starter Did Not Fully Accelerate 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11406 | Diagnostic: Starter Did Not Fully Accelerate 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11407 | Diagnostic: Starter Did Not Fully Accelerate 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11408 | Diagnostic: Starter Did Not Transition 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11409 | Diagnostic: Starter Did Not Transition 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11410 | Diagnostic: Starter Did Not Transition 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11411 | Diagnostic: Starter Did Not Transition 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11412 | Diagnostic: Starter Dry Run Test 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11413 | Diagnostic: Starter Dry Run Test 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11414 | Diagnostic: Starter Dry Run Test 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11415 | Diagnostic: Starter Dry Run Test 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11416 | Diagnostic: Starter Failed to Arm/Start 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11417 | Diagnostic: Starter Failed to Arm/Start 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11418 | Diagnostic: Starter Failed to Arm/Start 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11419 | Diagnostic: Starter Failed to Arm/Start 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11420 | Diagnostic: Starter Fault Type I 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11421 | Diagnostic: Starter Fault Type I 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11422 | Diagnostic: Starter Fault Type I 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11423 | Diagnostic: Starter Fault Type I 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11424 | Diagnostic: Starter Fault Type II 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11425 | Diagnostic: Starter Fault Type II 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11426 | Diagnostic: Starter Fault Type II 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11427 | Diagnostic: Starter Fault Type II 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11428 | Diagnostic: Starter Fault Type III 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11429 | Diagnostic: Starter Fault Type III 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11430 | Diagnostic: Starter Fault Type III 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11431 | Diagnostic: Starter Fault Type III 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11432 | Diagnostic: Starter Module Memory Error Type 1 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11433 | Diagnostic: Starter Module Memory Error Type 1 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11434 | Diagnostic: Starter Module Memory Error Type 1 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11435 | Diagnostic: Starter Module Memory Error Type 1 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11436 | Diagnostic: Starter Module Memory Error Type 2 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11437 | Diagnostic: Starter Module Memory Error Type 2 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11438 | Diagnostic: Starter Module Memory Error Type 2 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11439 | Diagnostic: Starter Module Memory Error Type 2 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11440 | Diagnostic: Starts/Hours Modified 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11441 | Diagnostic: Starts/Hours Modified 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11442 | Diagnostic: Starts/Hours Modified 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11443 | Diagnostic: Starts/Hours Modified 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11444 | Diagnostic: Suction Pressure Transducer Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11445 | Diagnostic: Suction Pressure Transducer Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11446 | Diagnostic: Suction Refrigerant Pressure Sensor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11447 | Diagnostic: Suction Refrigerant Pressure Sensor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11448 | Diagnostic: Suction Refrigerant Pressure Sensor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11449 | Diagnostic: Suction Refrigerant Pressure Sensor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11450 | Diagnostic: Suction Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11451 | Diagnostic: Transition Complete Input Opened 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11452 | Diagnostic: Transition Complete Input Opened 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11453 | Diagnostic: Transition Complete Input Opened 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11454 | Diagnostic: Transition Complete Input Opened 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11455 | Diagnostic: Transition Complete Input Shorted 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11456 | Diagnostic: Transition Complete Input Shorted 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11457 | Diagnostic: Transition Complete Input Shorted 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11458 | Diagnostic: Transition Complete Input Shorted 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11459 | Diagnostic: Under Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11460 | Diagnostic: Under Voltage 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11461 | Diagnostic: Under Voltage 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11462 | Diagnostic: Unexpected Starter Shutdown 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11463 | Diagnostic: Unexpected Starter Shutdown 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11464 | Diagnostic: Unexpected Starter Shutdown 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11465 | Diagnostic: Unexpected Starter Shutdown 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11466 | Diagnostic: Very Low Discharge Superheat 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11467 | Diagnostic: Very Low Discharge Superheat 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11468 | Diagnostic: Very Low Evap Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11469 | Diagnostic: Very Low Evap Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11470 | Diagnostic: Very Low Evap Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11471 | Diagnostic: Very Low Evap Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11472 | Diagnostic: Water System Differential Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11473 | Diagnostic: Energy Meter Write Value Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11474 | Diagnostic: Write Command Failure Energy Meter 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11475 | Diagnostic: Write Command Failure Energy Meter 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11476 | Diagnostic: High Evaporator Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11477 | Comm Loss: Starter Panel High Temperature Limit | Read | 0 = Normal, 1 = In Alarm | ||
| BVmin | 10100 | Chiller Auto Stop Command BAS | BAS command for Chiller Auto Stop | Write | 0 = Stop, 1 = Auto | |
| BV | 10101 | Reset Diagnostic | BAS diagnostic reset command to clear resettable active diagnostics | Write | 0 = Normal, 1 = Reset | |
| BV | 10102 | Circuit 1 Lockout BAS | BAS to lock circuit 1 | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10103 | Circuit 2 Lockout BAS | BAS to lock circuit 2 | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10104 | Energy Consumption Reset | BAS command to reset Energy Consumption Resettable counter | Write | 0 = Accumulating, 1 = Reset | |
| BV | 10105 | Noise Reduction Request BAS | BAS Noise Reduction Command | Write | 0 = Normal, 1 = Reduce Noise | |
| BV | 10106 | Compressor 1A Lockout BAS | BAS Compressor 1A Lockout | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10107 | Compressor 1B Lockout BAS | BAS Compressor 1B Lockout | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10108 | Compressor 2A Lockout BAS | BAS Compressor 2A Lockout | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10109 | Compressor 2B Lockout BAS | BAS Compressor 2B Lockout | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10110 | Evaporator Water Pump Request BAS | BAS Evaporator Water Pump Request | Write | 0 = Auto, 1 = On | |
| BV | 10111 | Condenser Water Pump Request BAS | BAS Condenser Water Pump Request | Write | 0 = Auto, 1 = On | |
| MI | 10100 | Running Mode | Running state of the chiller | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | |
| MI | 10101 | Operating Mode | Operating mode of the chiller | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | |
| MI | 10103 | Refrigerant Type | Chiller refrigerant type | Read | 5 = R-134a, 13 = R-513A, 16 = R-1234ze(E), 18 = R-515B | |
| MI | 10104 | Manufacturing Location | Location that the chiller was manufactured | Read | 3 = Pueblo, 4 = Charmes | |
| MI | 10105 | Cooling Type | Cooling Type of chiller | Read | 1 = Water Cooled, 2 = Air Cooled | |
| MI | 10106 | Model Information [GEN2] | Model information of chiller | Read | 17 = RTWF, 30 = RTSF, 41 = RTWF XSE, 45 = RTWD, 46 = RTUD | |
| MVmin | 10100 | Chiller Mode Command BAS | Command the chiller Mode | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the actual engineering unit is the factory-configured I-P or SI set.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Series R RTWD and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 Series R RTWD
How many BACnet points does the Trane Symbio 800 Series R RTWD have?
This list has 685 BACnet objects: 144 analog inputs, 7 analog values, 515 binary inputs, 12 binary values, 6 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 Series R RTWD BACnet points are writable?
20 of the 685 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 Series R RTWD BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - Series R Model RTWD (BAS-PTS017A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS017A-EN_11152024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 Series R RTWD?
Start with BV 10100 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10103 Chiller Running State (Chiller on/off status); BI 10101 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10103 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10108 Actual Running Capacity (Actual running capacity in percent); BI 10108 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 Series R RTWD?
BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10120 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.
How do I check these points on the real Symbio 800 Series R RTWD?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013
Source: Symbio 800 Integration Points List BACnet - Series R Model RTWD · BAS-PTS017A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.